					                         Alien Crosstalk for the
www.meggernetworks.com




                          Inexperienced User




                                                   1
                                              Agenda
                         �What is alien crosstalk
                         �Where does alien crosstalk occur in the link
www.meggernetworks.com




                         �Standards & guidelines defining alien crosstalk
                         �Creating a quality plan to address requirements
                         �Link performance requirements
                         �Link certification




                                                                            2
                         What is Alien Crosstalk
www.meggernetworks.com




                                                   3
                                        What is Alien Crosstalk
                         � Alien crosstalk (AXT) is a unwanted disturbing signal coupling
                           from one balanced twisted-pair component, channel or
                           permanent link to another
www.meggernetworks.com




                         � The term “Alien” is used because unlike pair to pair crosstalk,
                           alien crosstalk is a disturbing noise source that originates from
                           outside the affected link’s cable and components




                                                                                               4
                                      History - Alien Crosstalk
                         � In 2006 the IEEE ratified 10GBASE-T and later published
                           IEEE 802.3-2008 defining a version of Ethernet with a nominal
                           data rate of 10 Gbit/s, ten times faster than Gigabit Ethernet
www.meggernetworks.com




                         � Achieving 10GBASE-T over copper required new encoding
                           schemes, 500MHz bandwidth and full duplex transmission
                         � Due to these changes alien crosstalk, which has always been
                           present in twisted pair copper networks and cannot currently be
                           cancelled, became a significant noise source capable of
                           disrupting 10GBASE-T
                         � In response the industry defined new standards and guidelines
                           for acceptable levels of alien crosstalk and developed test
                           methods for measuring alien crosstalk


                                                                                             5
                              Reflected Mode of Alien Crosstalk
                         � Near end alien crosstalk is a reflected mode that is
                           sourced and received at the same ends of the
                           disturbing and disturbed links
www.meggernetworks.com




                                                                                  6
                          Transmitted Mode of Alien Crosstalk
                         � Far end alien crosstalk is a transmitted mode that
                           is sourced and received at opposite ends of the
                           disturbing and disturbed links
www.meggernetworks.com




                                                                                7
                         Where Does Alien Crosstalk
www.meggernetworks.com




                             Occur in the Link




                                                      8
                              Where Does Alien Crosstalk Occur
                         � Alien crosstalk occurs between the cables and components
                           of a disturber link and a disturbed (victim) link
                         � Alien crosstalk coupling increases as the components and
www.meggernetworks.com




                           cables of the two links approach each other
                         � Alien crosstalk is extremely dependent upon installation
                           practices such as patch cord positioning, cable bundling,
                           use of tie-wraps, pathway fills and component placement
                         � Alien crosstalk is not simply limited to a single disturbing
                           link, multiple disturbing links may add to the total alien
                           crosstalk present on a disturbed link



                                                                                          9
                            Alien Crosstalk in the Horizontal Link
                         � Alien crosstalk occurs when
                           different cables run in parallel for
                           an extended distance in close
www.meggernetworks.com




                           proximity
                         � Long, tightly bound cable bundles
                           present an ideal location for
                           significant levels of alien crosstalk
                         � A worst case condition exists
                           when a disturbed (victim) cable is
                           surround by six disturbing cables



                                                                     10
                                      Alien Crosstalk in Cords
                         � Alien crosstalk occurs when
                           different equipment and patch
                           cords are routed together in
www.meggernetworks.com




                           close proximity
                         � Bound cords present an ideal
                           location for significant levels
                           of alien crosstalk in the first
                           few metres of the link
                         � Management bar lay and
                           waterfalls also present
                           opportunity for alien crosstalk


                                                                 11
                                 Alien Crosstalk in Components
                         � Alien crosstalk occurs where
                           components of different links
                           come into close proximity
www.meggernetworks.com




                         � Patch panels present an ideal
                           location for significant levels
                           of alien crosstalk
                         � A worst case condition exists
                           when a disturbed port is
                           surrounded on three or four
                           sides by disturber ports



                                                                 12
                         Standards & Guidelines
www.meggernetworks.com




                         Defining Alien Crosstalk




                                                    13
                              Standards Defining Alien Crosstalk
                         � ISO/IEC 11801 Ed 2.0 Amendment 1 provides channel
                           and alien crosstalk requirements for Class EA, Class F and
                           Class FA
www.meggernetworks.com




                         � BS EN 50173-1 A1 provides channel and alien crosstalk
                           requirements for Class EA, Class F and Class FA
                         � ANSI/TIA-568-C.2 provides channel, permanent link and
                           alien crosstalk requirements for Category 6A




                                                                                        14
                             Guidelines Defining Alien Crosstalk
                         � Guidelines provide methods for re-characterizing installed
                           Class E and Category 6 cabling to ensure 10GBASE-T
                           operation
www.meggernetworks.com




                         � ISO/IEC TR 24750 and CLC/TR 50173-99-1:2007 both
                           provide channel and alien crosstalk recommendations for
                           installed Class E
                         � TIA TSB-155 provides channel, permanent link and alien
                           crosstalk recommendations for installed Category 6
                         � Class E and Category 6 cabling is not recommended for
                           new installations supporting 10GBASE-T operation



                                                                                        15
www.meggernetworks.com




                         Creating a Quality
                                Plan



                                              16
                                       Cable Considerations
                         � UTP Class EA and Category 6A cables with improved alien
                           crosstalk performance may be constructed with an inner
                           seperator, a larger outside wall thikness and an increased
www.meggernetworks.com




                           cable diameter.
                         � Cable alien crosstalk performance can be compromised by
                           deforming the outer jacket or inner separator due to tie
                           wraps, excessive conduit/pathway fill or exceeding
                           recommended bend radius
                         � Pathway and conduit fill ratios increase for the same
                           number of cables if the cable diameter increases



                                                                                        17
                            Cord and Component Considerations
                         � UTP Class EA and Category 6A equipment and patch
                           cords typically have a larger outside wall thickness to
                           reduce alien crosstalk
www.meggernetworks.com




                         � Cord alien crosstalk performance can be compromised by
                           deforming the outer jacket due to tie wraps and exceeding
                           recommended bend radius
                         � Compacting cords in management bars and trays brings
                           cords into closer proximity increasing alien crosstalk in the
                           critical first few meters of the link
                         � UTP Class EA and Category 6A patch panels are typically
                           lower density than Class E and Category 6


                                                                                           18
                                     Reducing Alien Crosstalk
                         � Minimize the number of cables in a bundle, reducing the
                           number of possible disturbers
                         � Un-bundle the horizontal link in the first 15 metres
www.meggernetworks.com




                           allowing the cables to separate
                         � Eliminate cable ties if possible, if not reduce cable tie
                           tension and space cable ties farther apart
                         � Randomly lay cable in trays to prevent any two cables from
                           running in close proximity their entire length
                         � Use F/UTP or S/FTP cables and cords to significantly
                           reduces alien crosstalk



                                                                                        19
                                Reducing Alien Crosstalk (cont)
                         � Separate equipment and patch cords and eliminate cable
                           ties to reduces the alien crosstalk coupling in the first few
                           metres of the link
www.meggernetworks.com




                         � Lay cords randomly in management bars to prevent any
                           two cords from running in close proximity their entire
                           length
                         � Reduce the number of cords in a waterfall and maximize
                           the radius to reduce cord compaction
                         � Use fully shielded components to significantly reduce alien
                           crosstalk



                                                                                           20
                                  Alien Crosstalk Consideration
                         � Alien crosstalk is extremely dependent upon installation
                           practices such as patch cord positioning, cable bundling,
                           use of tie-wraps, pathway fills and component placement
www.meggernetworks.com




                         � Alien crosstalk certification is unique, its a selective process
                           using statistical data about the installation to identify and
                           certify the links deemed most prone to alien crosstalk
                           interference
                         � Certifying alien crosstalk on each Class EA/F/FA and
                           Category 6A link or re-certifying alien crosstalk on each
                           Class E or Category 6 link may not be necessary nor
                           plausible due to test times


                                                                                              21
                             Alien Crosstalk Consideration (cont)
                         � Alien crosstalk testing consumes significantly more time
                           than channel or link testing
                         � Worst case instrument test time for a single disturbed link
www.meggernetworks.com




                           testing PSANEXT and PSAACRF at both ends of the link

                               # of Disturbing Links   Worst Case Instrument Test Time
                                         1                       1.5 minutes
                                        2                         3 minutes
                                        4                         6 minutes
                                        8                        12 minutes



                                                                                         22
                                        Additional Guidance
                         � Seek guidance from cable and component manufacturers
                           for installing and certifying Class EA/F/FA or Category 6A
                           links
www.meggernetworks.com




                         � Seek additional guidance from cable and component
                           manufacturers for identifying and selecting disturbed and
                           disturbing links for alien crosstalk certification
                         � Consult ISO/IEC TR 24750, CLC/TR 50173-99-1:2007
                           or TIA TSB-155 for determining the Class E or Category 6
                           alien crosstalk environment and alien crosstalk mitigation
                           techniques



                                                                                        23
                                         Create a Quality Plan
                         � Create a quality plan that considers how the selection and
                           installation of cable and components affects the alien
                           crosstalk environment
www.meggernetworks.com




                         � The quality plan should identify changes to the installation
                           brought on by Class EA/F/FA or Category 6A components
                         � The quality plan should address alien crosstalk certification,
                           including identification & selection of test links and criteria
                           for obtaining satisfactory performance
                         � A Class E and Category 6 quality plan should address alien
                           crosstalk mitigation practices
                         � Obtain agreement from all parties


                                                                                             24
                                 Create a Quality Plan (cont)

                         �A good quality plan that
                          considers and incorporates the
www.meggernetworks.com




                          elements in the previous slides
                          will reduce installation and
                          certification time while
                          increasing confidence in
                          installation’s ability to meet
                          alien crosstalk requirements



                                                                25
                         Link Performance Requirements
www.meggernetworks.com




                                                         26
                         Performance 10GBASE-T Class E & Category 6

                         � Pair measurements              � Alien crosstalk added
                             � Wiremap                      1-500MHz
                             � Delay/Delay Skew/Length*       � PSANEXT
www.meggernetworks.com




                             � Resistance**                   � Average PSANEXT
                                                              � PSAACRF
                         � Pair to pair performance
                                                              � Average PSAACRF
                           extended to 500MHz
                                                              � Marginal Computation
                             � Insertion Loss
                             � Return Loss
                             � NEXT & PSNEXT
                             � ACR-N & PSACR-N**
                                                              * Not a recognized Class E measurement
                             � ACR-F & PSACR-F                ** Not a recognized Category 6 measurement



                                                                                                           27
                            Performance Class EA & Category 6A
                         � Pair measurements              � Alien crosstalk 1-500MHz
                             � Wiremap                        � PSANEXT
                             � Delay/Delay Skew/Length*       � Average PSANEXT
www.meggernetworks.com




                             � Resistance**                   � PSAACRF
                                                              � Average PSAACRF
                         � Pair to pair performance
                           1-500MHz
                             � Insertion Loss
                             � Return Loss
                             � NEXT & PSNEXT
                             � ACR-N & PSACR-N**
                                                              * Not a recognized Class EA measurement
                             � ACR-F & PSACR-F                ** Not a recognized Category 6A measurement



                                                                                                            28
                                        Performance Class F
                         � Pair measurements          � Alien crosstalk added
                             � Wiremap                  1-600MHz
                             � Delay/Delay Skew           � PSANEXT
www.meggernetworks.com




                             � Resistance                 � Average PSANEXT
                                                          � PSAACRF
                         � Pair to pair performance
                                                          � Average PSAACRF
                           1-600MHz
                             � Insertion Loss
                             � Return Loss
                             � NEXT & PSNEXT
                             � ACR-N & PSACR-N
                             � ACR-F & PSACR-F


                                                                                29
                                       Performance Class FA
                         � Pair measurements          � Alien crosstalk 1-1000MHz
                             � Wiremap                    � PSANEXT
                             � Delay/Delay Skew           � Average PSANEXT
www.meggernetworks.com




                             � Resistance                 � PSAACRF
                                                          � Average PSAACRF
                         � Pair to pair performance
                           1-1000MHz
                             � Insertion Loss
                             � Return Loss
                             � NEXT & PSNEXT
                             � ACR-N & PSACR-N
                             � ACR-F & PSACR-F


                                                                                    30
                            Power Sum Alien NEXT (PSANEXT)
                         � PSANEXT sums four near end alien crosstalk measurements from
                           each pair of the disturbing link to a single pair of the disturbed link
                         � Four PSANEXT results are calculated at the end of a disturbed link for
www.meggernetworks.com




                           a total of 8 results if both ends are tested




                                                                                                     31
                             Power Sum Alien ACRF (PSAACRF)
                         � PSAACRF sums four far end alien crosstalk measurements from each
                           pair of the disturbing link to a single pair of the disturbed link
                         � Four PSACRF results are calculated at the end of a disturbed link for a
www.meggernetworks.com




                           total of 8 results if both ends are tested




                                                                                                     32
                                Average PSANEXT & PSAACRF
                         � Average PSANEXT is the average of the PSANEXT
                           results on each of the disturbed link pairs
                         � Average PSAACRF is the average of the PSAACRF results
www.meggernetworks.com




                           on each of the disturbed link pairs
                         � One Average PSANEXT or PSAACRF result is calculated
                           at the end of a disturbed link for a total of 2 results if both
                           ends are tested




                                                                                             33
                            Alien Crosstalk Margin Computation
                         � The alien crosstalk margin computation is used if the
                           PSANEXT or the PSAACRF limits are not met on Class
                           E or Category 6 links
www.meggernetworks.com




                         � The alien crosstalk margin computation ensures that the
                           total combined PSAFEXT and PSANEXT that couples
                           into a channel is limited in order to maintain the
                           10GBASE-T minimum signal to noise ratio
                         � The alien crosstalk margin calculation is a sufficient
                           qualification for suitability of Class E or Category 6
                           channels to support 10GBASE-T operation



                                                                                     34
                             35
Link Certification
    www.meggernetworks.com
                           Certifying Class EA/F/FA & Category 6A
                         � Certify the channel or link performance of every link saving
                           the Autotest result and graphical data
                         � Using the test plan criteria and result data, identify the
www.meggernetworks.com




                           disturbed links deemed most prone to alien crosstalk
                           interference and their associated disturbing links
                         � Per the test plan criteria, select from the identified links
                           those disturbed and disturbing links that require alien
                           crosstalk certification
                         � Certify the alien crosstalk of the selected disturbed links per
                           the test plan



                                                                                             36
                                Re-certifying Class E & Category 6
                         � Re-certify the channel or link performance of every link
                           designated to support 10BASE-T saving the Autotest
                           result and graphical data
www.meggernetworks.com




                         � Using the test plan criteria and result data, identify the
                           disturbed links deemed most prone to alien crosstalk
                           interference and their associated disturbing links
                         � Re-test the channel or link performance of all identified
                           disturbing links saving the Autotest result and graphical
                           data*
                         � Certify the alien crosstalk of the selected disturbed links
                           per the test plan
                          *Links designated only as a disturber do not have to pass channel or link certification



                                                                                                                    37
                         Typical PSANEXT Test Setup
www.meggernetworks.com




                                                      38
                         Typical PSAACRF Test Setup
www.meggernetworks.com




                                                      39
                                       Alien Crosstalk Testing
                         � Testing is conducted from
                           the PC result manager alien
                           crosstalk (AXT) application
www.meggernetworks.com




                         � The AXT application
                           provides the tools needed to
                           certify alien crosstalk
                         � The AXT application
                           displays alien crosstalk
                           certification results and link
                           statistics in real time



                                                                 40
                                               Conclusion
                         � Alien crosstalk is a unwanted disturbing signal coupling
                           from one balanced twisted-pair component, channel or
                           permanent link to another
www.meggernetworks.com




                         � Alien crosstalk is extremely dependent upon installation
                           practices and occurs where links come into close proximity
                           such as in cable bundles and patch panels
                         � ISO/IEC 11801 Ed 2.0 Amendment 1 and BS EN 50173-
                           1 A1 provide channel and alien crosstalk performance
                           requirements for Class EA/F/FA links
                         � ANSI/TIA-568-C.2 provides channel or link and alien
                           crosstalk performance requirements for Category 6A links


                                                                                        41
                                           Conclusion (cont)
                         � ISO/IEC TR 24750 & CLC/TR 50173-99-1:2007 provide
                           guidance for supporting 10GBASE-T on Class E channels
                         � TIA TSB-155 provides guidance for supporting
www.meggernetworks.com




                           10GBASE-T on Category 6 channels and links
                         � Create a quality plan addressing the unique requirements for
                           installation, certification and alien crosstalk mitigation prior
                           to starting
                         � A good quality plan will reduce installation and certification
                           time while increasing confidence in installation’s ability to
                           meet alien crosstalk requirements



                                                                                              42
                           43
Thank you
  www.meggernetworks.com

				