LAC Automator

					                  Hydro One Distribution Generation List of Allocated Capacity

The Distribution System Code requires Distributors to publish information on the capacity for new
generators on the distribution system. This document identifies the potential capacity available for the
connection of generation to stations owned by Hydro One, and the total MW allocated to each feeder by
completed Connection Impact Assessments (CIAs.)

This document will be updated at the beginning of each month.

The Thermal Capacity represents the nameplate amount of generation that can be added to that bus or
station. The Short Circuit capacity represents the remaining ability of the station to accept additional
short circuit contributions. Any additional generation (including previously allocated) must be able to
operate within both the thermal capacity and the short circuit capacity.

This list is for information purposes only, a CIA will finalize if the project is within the existing systems
thermal and short circuit capacities.

The potential capacity of a feeder is described on the Distribution Connected Generation page of Hydro
One's website.

The list was updated on March 31st, 2010. For any questions please contact the Business Customer
Centre at dxgenerationconnections@hydroone.com or 1-877-447-4412.


Notes for March 31st, 2010 update:

Routine data updates.
Short Circuit Capacity values added.
Samples have been added to the end of the document to explain how to use the information provided in
this document.




                              Example Station

                                        STATION NAME
                               Station Thermal Capacity = XX MW
                                                                                                              In this box there will be a
                             Station Short Circuit Capacity = XX MVA
                                                                                                             hyperlink(s) to an upstream
Thermal Bus Capacity (MW)                   Bus 1 Name = Capacity             Bus 2 Name = Capacity            TS or downstream DS if
Short Circuit Bus Capacity (MVA)            Bus 1 Name = Capacity             Bus 2 Name = Capacity                   applicable.
                                            Feeder 1        Feeder 2         Feeder 3         Feeder 4
                                             Name            Name             Name             Name

                                          Total MW on     Total MW on      Total MW on      Total MW on
       Allocated Capacity (MW)
                                           Feeder 1        Feeder 2         Feeder 3         Feeder 4


                            NOTE:
                                          Allocations to the left of the   Allocations to the right of the
                                          double red line are on bus 1      double red line are on bus 2
                                            and contribute to bus 1's         and contribute to bus 2's
                                         allocated capacity. They also     allocated capacity. They also
                                             contribute to the entire          contribute to the entire
                                          station's allocated capacity.     station's allocated capacity.
                    AGIMAK DS
             Thermal Capacity (MW) = 7
          Short Circuit Capacity (MVA) = 652
                                       F1         F2
Allocated Capacity (MW)                0          0




                                                                 AGINCOURT TS                                                                                    Station may supply
                                                     Thermal Capacity (MW) = Sum of Buses                                                                     another LDC's territory.
                                                       Short Circuit Capacity (MVA) = N/A                                                                      Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                     B = 11                                                    Y = 11                                locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                             B = 124                                                    Y = 125
                                       M2         M4      M6         M8        M10      M12            M1      M3         M5        M7      M11
Allocated Capacity (MW)                0          0        0          0         0         0            0       0           0        0        0


           For any information or inquiries please contact Hydro Ottawa
                                                             *ALBION TS                                                                                Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                                another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                                 Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                               BQ = 9                                               JY = 9                                 locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                       BQ = 113                                             JY = 112
                                For any information or inquiries please contact Hydro Ottawa



                 ALEXANDER DS                                           ALEXANDER DS is
             Thermal Capacity (MW) = 16                                downstream of SOUTH
          Short Circuit Capacity (MVA) = N/A                              MARCH TS M5
                                       F1         F4
Allocated Capacity (MW)               5.5         6.4




                      ALLANBURG TS
                  Thermal Capacity (MW) = 22
              Short Circuit Capacity (MVA) = 198
                                      M6       M7           M8
Allocated Capacity (MW)                0        0           0




                                       ALLISTON TS
                                 Thermal Capacity (MW) = 62
                               Short Circuit Capacity (MVA) = 467
                                        M1       M2        M3          M4       M5       M6
Allocated Capacity (MW)                  0         0        0          10       0        10




                        ALMONTE TS
                   Thermal Capacity (MW) = 24
                Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)              J = 17        Q = 29
Short Circuit Bus Capacity (MVA)      J = 1116      Q = 1141
                                        M25      M26       M28
Allocated Capacity (MW)                   5        0        0




                   ARDOCH DS
             Thermal Capacity (MW) = 6
           Short Circuit Capacity (MVA) = 75
                                       F1         F2
Allocated Capacity (MW)                 0         0




                                             ARMITAGE TS DESN 1                                                                      Station may supply
                                           Thermal Capacity (MW) = 118                                                            another LDC's territory.
                                        Short Circuit Capacity (MVA) = 402                                                         Refer to OPA FIT LDC
                                       M11      M12       M13       M14        M21      M22        M23        M24                 locator tool to find LDC.
Allocated Capacity (MW)                 0         0         0        0          0        0          0          0




                                             ARMITAGE TS DESN 2                                                                      Station may supply
                                           Thermal Capacity (MW) = 85                                                             another LDC's territory.
                                        Short Circuit Capacity (MVA) = 133                                                         Refer to OPA FIT LDC
                                       M31      M32       M33       M34        M41      M42        M43        M44                 locator tool to find LDC.
Allocated Capacity (MW)                 0        20         0        0          0        0         1.5         0




                  ARNPRIOR TS
             Thermal Capacity (MW) = 33
          Short Circuit Capacity (MVA) = 895
                                      M1          M2
Allocated Capacity (MW)                0          20




                    AYLMER TS                                           Station may supply
             Thermal Capacity (MW) = 10                              another LDC's territory.
          Short Circuit Capacity (MVA) = 525                          Refer to OPA FIT LDC
                                      M1         M2                  locator tool to find LDC.
Allocated Capacity (MW)                0         10.8




               AZILDA DS                                  AZILDA DS is downstream of
         Thermal Capacity (MW) = 5                           CLARABELLE TS M8
      Short Circuit Capacity (MVA) = N/A
                                        F1
Allocated Capacity (MW)                  0




                                               BARRIE TS                                                                   Station may supply
                                      Thermal Capacity (MW) = 69                                                        another LDC's territory.
                                    Short Circuit Capacity (MVA) = 644                                                   Refer to OPA FIT LDC
                                       M1         M2        M3       M4         M5       M6            M7               locator tool to find LDC.
Allocated Capacity (MW)                 0          0         0        0         0        0             0


          For any information or inquiries please contact Toronto Hydro
                                                             *BASIN TS                                                                                 Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                                another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                                 Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                              A5A6 = 9                                             A7A8 = 8                                locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                      A5A6 = 65                                             A7A8 = 65
                                For any information or inquiries please contact Toronto Hydro


          For any information or inquiries please contact Toronto Hydro
                                                        *BATHURST TS DESN 1                                                                            Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                                another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                                 Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                Y = 37                                              B = 40                                 locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                         Y = 83                                              B = 69
                                For any information or inquiries please contact Toronto Hydro


          For any information or inquiries please contact Toronto Hydro
                                             *BATHURST TS DESN 2                                                                     Station may supply
                                      Thermal Capacity (MW) = Sum of Buses                                                        another LDC's territory.
                                        Short Circuit Capacity (MVA) = N/A                                                         Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                           Q = 34                                    J = 28                              locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                    Q = 98                                    J = 67
                      For any information or inquiries please contact Toronto Hydro



                      BATTERSEA DS
                   Thermal Capacity (MW) = 8
                Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                   T1 = 7         T2 = 8
Short Circuit Bus Capacity (MVA)          T1 = 409        T2 = 396
                                         F1        F2        F3
Allocated Capacity (MW)                 0.5        0         0
   For any information or inquiries please contact Horizon Utilities Corporation
                                                                                         *BEACH TS - DESN1                                                                                          Station may supply
                                                                              Thermal Capacity (MW) = Sum of Buses                                                                               another LDC's territory.
                                                                                 Short Circuit Capacity (MVA) = N/A                                                                               Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                               B1B2 = 0                                                                       Y1Y2 = 5                                  locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                                        B1B2 = 21                                                                      Y1Y2 = 41
                                                        For any information or inquiries please contact Horizon Utilities Corporation


   For any information or inquiries please contact Horizon Utilities Corporation
                                                                                         *BEACH TS - DESN2                                                                                          Station may supply
                                                                              Thermal Capacity (MW) = Sum of Buses                                                                               another LDC's territory.
                                                                                 Short Circuit Capacity (MVA) = N/A                                                                               Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                               Q1Q2 = 6                                                                        J1J2 = 3                                 locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                                        Q1Q2 = 20                                                                      J1J2 = 21
                                                        For any information or inquiries please contact Horizon Utilities Corporation



           BEACHBURG DS                                      BEACHBURG DS is
         Thermal Capacity (MW) = 4                        downstream of COBDEN TS
      Short Circuit Capacity (MVA) = N/A                             M2
                                        F2
Allocated Capacity (MW)                3.5




                          BEAMSVILLE TS                                                      Station may supply
                      Thermal Capacity (MW) = 32                                          another LDC's territory.
                    Short Circuit Capacity (MVA) = 357                                     Refer to OPA FIT LDC
                                      M1        M2          M3         M4                 locator tool to find LDC.
Allocated Capacity (MW)                10        20         0          0




                          BEARDMORE DS
                       Thermal Capacity (MW) = 2
                    Short Circuit Capacity (MVA) = 670
                                       F1        F2         F3         F4
Allocated Capacity (MW)                 0       0.7         0          0




                                               BEAVERTON TS                                                                       PORT BOLSTER DS is
                                           Thermal Capacity (MW) = 72                                                           downstream of BEAVERTON
                                        Short Circuit Capacity (MVA) = 493                                                               TS M27
                                       M23      M24       M25       M26            M27     M28      M29      M30
Allocated Capacity (MW)                 0         0         0        0             0.1      0        0        0




                          BELLE RIVER TS
                      Thermal Capacity (MW) = 27
                    Short Circuit Capacity (MVA) = 253
                                      M1        M2          M3         M4
Allocated Capacity (MW)                 0        10         0          0




                                                       BELLEVILLE TS                                                                          Station may supply
                                                                                                                                                                     STIRLING DS is downstream
                                                Thermal Capacity (MW) = 81                                                                 another LDC's territory.     of BELLEVILLE TS M5
                                              Short Circuit Capacity (MVA) = 704                                                            Refer to OPA FIT LDC
                                       M1        M2         M3        M4       M5           M6       M7       M8        M9                 locator tool to find LDC.
Allocated Capacity (MW)                0          0          0         0       0.5          0        0        0         0




                              BERMONDSEY TS DESN 1                                                            Station may supply
                            Thermal Capacity (MW) = Sum of Buses                                           another LDC's territory.
                              Short Circuit Capacity (MVA) = N/A                                            Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                       J = 10                         Q = 11                      locator tool to find LDC.
Short Circuit Bus Capacity (MVA)               J = 113                         Q = 112
                                      M23        M25      M27    M24            M26        M28
Allocated Capacity (MW)                 0          0       0      0               0         0




                                                              BERMONDSEY TS DESN 2                                                                                      Station may supply
                                                           Thermal Capacity (MW) = Sum of Buses                                                                      another LDC's territory.
                                                             Short Circuit Capacity (MVA) = N/A                                                                       Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                      Y = 11                                                      B = 11                                    locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                               Y = 94                                                     B = 119
                                       M2         M4        M6        M8       M10       M12    M1            M3        M5        M7         M9      M11
Allocated Capacity (MW)                0          0          0         0         0        0     0             0         0         0          0        0




                                   BILBERRY CREEK TS                                                          Station may supply
                                Thermal Capacity (MW) = 59                                                 another LDC's territory.
                              Short Circuit Capacity (MVA) = 178                                            Refer to OPA FIT LDC
                                       M1       M2        M3           M4          M5       M6             locator tool to find LDC.
Allocated Capacity (MW)                 0         0        0           0           0        0




                                                    BIRCH TS                                                                        Station may supply
                                           Thermal Capacity (MW) = 0                                                             another LDC's territory.
                                         Short Circuit Capacity (MVA) = 0                                                         Refer to OPA FIT LDC
                                       M1       M2        M3        M4             M5       M6       M7       M8                 locator tool to find LDC.
Allocated Capacity (MW)                0         0         0         0             0        0        0        0




                                                    BIRMINGHAM TS DESN 1                                                                              Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                               another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                                Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                                QJ = 3                                           BY = 5                   locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                                        QJ = 91                                           BY = 91
                                       M1        M2        M3       M4          M5   M6              M7       M8       M21      M22
Allocated Capacity (MW)                0          0         0         0         0    0               0        0         0         0




                                    BIRMINGHAM TS DESN 2                                                                 Station may supply
                                 Thermal Capacity (MW) = Sum of Buses                                                 another LDC's territory.
                                   Short Circuit Capacity (MVA) = N/A                                                  Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                 EZ = 3                              KD = 20                 locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                         EZ = 51                              KD = 37
                                      M10        M11       M12      M13            M14     M71      M81
Allocated Capacity (MW)                0          0         0         0             0       0         0




                BIRR DS                                   BIRR DS is downstream of
         Thermal Capacity (MW) = 4                            CLARKE TS M2
      Short Circuit Capacity (MVA) = N/A
                                        F2
Allocated Capacity (MW)                0.3




          BRACEBRIDGE TS
        Thermal Capacity (MW) = 40
     Short Circuit Capacity (MVA) = 1004
                                      M20
Allocated Capacity (MW)                0




                                                                 BRAMALEA TS DESN 1                                                                                     Station may supply
                                                           Thermal Capacity (MW) = Sum of Buses                                                                      another LDC's territory.
                                                             Short Circuit Capacity (MVA) = N/A                                                                       Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                      Y=5                                                           B=5                                     locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                               Y = 91                                                        B = 89
                                       M2         M4        M6        M8       M10       M12    M1            M3        M5            M7     M9      M11
Allocated Capacity (MW)                0          0          0         0         0        0     0             0         0             0      0        0




                                      BRAMALEA TS DESN 2                                                                 Station may supply
                                       Thermal Capacity (MW) = 0                                                      another LDC's territory.
                                     Short Circuit Capacity (MVA) = 0                                                  Refer to OPA FIT LDC
                                      M23        M25        M27      M29           M24     M26      M28               locator tool to find LDC.
Allocated Capacity (MW)                 0          0         0        0             0       0        0
                                      BRAMALEA TS DESN 3                                                                 Station may supply
                                       Thermal Capacity (MW) = 0                                                      another LDC's territory.
                                     Short Circuit Capacity (MVA) = 0                                                  Refer to OPA FIT LDC
                                      M44        M46        M48      M50           M43     M45      M47               locator tool to find LDC.
Allocated Capacity (MW)                 0          0         0        0             0       0        0




                                                   BRANT TS                                                                          Station may supply
                                           Thermal Capacity (MW) = 61                                                             another LDC's territory.
                                        Short Circuit Capacity (MVA) = 215                                                         Refer to OPA FIT LDC
                                       M11      M12       M13       M14            M21     M22      M23     M24                   locator tool to find LDC.
Allocated Capacity (MW)                 0         0         0        0              0       0        0       0




                                                          BRANTFORD TS                                                                                Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                               another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                                Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                Y=5                                                Z=5                                    locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                        Y = 131                                            Z = 115
                                       M21      M23       M25       M27       M29    M22            M24     M26        M28         M30
Allocated Capacity (MW)                 0         0         0         0        0      0              0       8.1        0           0


          For any information or inquiries please contact Toronto Hydro
                                                       *BRIDGMAN TS DESN 1                                                                            Station may supply
                                                      Thermal Capacity (MW) = 9                                                                    another LDC's territory.
                                                    Short Circuit Capacity (MVA) = 49                                                               Refer to OPA FIT LDC
                                For any information or inquiries please contact Toronto Hydro                                                      locator tool to find LDC.


          For any information or inquiries please contact Toronto Hydro
                                                       *BRIDGMAN TS DESN 2                                                                            Station may supply
                                                      Thermal Capacity (MW) = 9                                                                    another LDC's territory.
                                                    Short Circuit Capacity (MVA) = 85                                                               Refer to OPA FIT LDC
                                For any information or inquiries please contact Toronto Hydro                                                      locator tool to find LDC.


          For any information or inquiries please contact Toronto Hydro
                                                       *BRIDGMAN TS DESN 3                                                                            Station may supply
                                                      Thermal Capacity (MW) = 5                                                                    another LDC's territory.
                                                    Short Circuit Capacity (MVA) = 21                                                               Refer to OPA FIT LDC
                                For any information or inquiries please contact Toronto Hydro                                                      locator tool to find LDC.


          For any information or inquiries please contact Toronto Hydro
                                                       *BRIDGMAN TS DESN 4                                                                            Station may supply
                                                      Thermal Capacity (MW) = 9                                                                    another LDC's territory.
                                                    Short Circuit Capacity (MVA) = 62                                                               Refer to OPA FIT LDC
                                For any information or inquiries please contact Toronto Hydro                                                      locator tool to find LDC.



   BROCKVILLE SCHOFIELD DS                                BROCKVILLE SCHOFIELD
         Thermal Capacity (MW) = 2                          DS is downstream of
      Short Circuit Capacity (MVA) = N/A                    BROCKVILLE TS M3
                                       F41
Allocated Capacity (MW)                0.1




                                               BROCKVILLE TS                                                                      BROCKVILLE SCHOFIELD
                                          Thermal Capacity (MW) = 36                                                                DS is downstream of
                                        Short Circuit Capacity (MVA) = 160                                                          BROCKVILLE TS M3
                                       M1        M2       M3        M4             M5      M6       M7      B1R
Allocated Capacity (MW)                0          0       0.1        0             0       0        0        0




                                        BRONTE TS DESN 1                                                                 Station may supply
                                     Thermal Capacity (MW) = 64                                                       another LDC's territory.
                                   Short Circuit Capacity (MVA) = N/A                                                  Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                           T5 = 54                              T6 = 54                      locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                    T5 = 430                             T6 = 430
                                      M1         M3        M5       M7             M2      M4       M8
Allocated Capacity (MW)                0          0         0         0            0        0       0




                                   BRONTE TS DESN 2                                                          Station may supply
                                Thermal Capacity (MW) = 54                                                another LDC's territory.
                              Short Circuit Capacity (MVA) = 425                                           Refer to OPA FIT LDC
                                      M23       M24       M25         M26          M27     M28            locator tool to find LDC.
Allocated Capacity (MW)                 0         0        0           0            0       0




                                     BROWN HILL TS
                                Thermal Capacity (MW) = 83
                              Short Circuit Capacity (MVA) = 470
                                       M1       M2        M3           M4          M11     M12
Allocated Capacity (MW)                10         0        0           0            0       0




                                                                     BUCHANAN TS                                                                                         Station may supply
                                                           Thermal Capacity (MW) = Sum of Buses                                                                       another LDC's territory.
                                                             Short Circuit Capacity (MVA) = N/A                                                                        Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                      Y = 25                                                     B = 25                                      locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                               Y=0                                                        B = 89
                                       M22       M24       M26       M28       M30       M38    M21         M23        M25      M27         M29      M37
Allocated Capacity (MW)                19.9       0          0         0         0        0     20           0          0        0           0        0


   For any information or inquiries please contact Horizon Utilities Corporation
                                                                 *BUNTING TS                                                                                     Station may supply
                                                       Thermal Capacity (MW) = Sum of Buses                                                                   another LDC's territory.
                                                         Short Circuit Capacity (MVA) = N/A                                                                    Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                  Q=5                                                     J=0                                        locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                          Q = 112                                                 J = 70
                             For any information or inquiries please contact Horizon Utilities Corporation



                 BURLEIGH DS
             Thermal Capacity (MW) = 2
          Short Circuit Capacity (MVA) = 444
                                       F1         F2
Allocated Capacity (MW)                0          0




                                                                    BURLINGTON TS                                                                                        Station may supply
                                                           Thermal Capacity (MW) = Sum of Buses                                                                       another LDC's territory.
                                                             Short Circuit Capacity (MVA) = N/A                                                                        Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                      BY = 52                                                    QJ = 53                                     locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                               BY = 88                                                    QJ = 89
                                       M1         M2        M3        M4       M5        M6     M31         M32        M33      M34         M35      M36
Allocated Capacity (MW)                0          0          0         0         0        0      0           0          0         0          0        0




                                                                   BUTTONVILLE TS                                                                                        Station may supply
                                                           Thermal Capacity (MW) = Sum of Buses                                                                       another LDC's territory.
                                                             Short Circuit Capacity (MVA) = N/A                                                                        Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                      Q = 11                                                         Z = 11                                  locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                               Q = 109                                                       Z = 109
                                       M1         M3        M5        M7       M9        M11    M2           M4            M6        M8     M10      M12
Allocated Capacity (MW)                0          0          0         0         0        0     0            0             0         0       0        0




                           CALEDONIA TS                                                     Station may supply
                      Thermal Capacity (MW) = 40                                         another LDC's territory.
                     Short Circuit Capacity (MVA) = 0                                     Refer to OPA FIT LDC
                                      M3        M4          M5         M6                locator tool to find LDC.
Allocated Capacity (MW)                0        20          20         0




                 CALSTOCK DS
             Thermal Capacity (MW) = 5
          Short Circuit Capacity (MVA) = 696
                                       F1         F2
Allocated Capacity (MW)                0          0
                                                                                  CAMPBELL TS -DESN 1                                                                                        Station may supply
                                                                             Thermal Capacity (MW) = Sum of Buses                                                                         another LDC's territory.
                                                                               Short Circuit Capacity (MVA) = N/A                                                                          Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                              BY = 9                                                                   QJ = 9                                    locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                                       BY = 61                                                                  QJ = 62
                                      M11       M12       M13       M14      M21       M22       M23       M24    M31      M32      M33      M34      M41      M42      M43      M44
Allocated Capacity (MW)                0         0         0         0         0         0         0        0      0        0        0        0         0       0        0        0




                                           CAMPBELL TS DESN 2                                                                Station may supply
                                          Thermal Capacity (MW) = 30                                                      another LDC's territory.
                                        Short Circuit Capacity (MVA) = 49                                                  Refer to OPA FIT LDC
                                      M51      M52       M53       M54       M61       M62       M63      M64             locator tool to find LDC.
Allocated Capacity (MW)                0         0         0         0        0         0         0        0




                                                           CARDIFF TS                                                                         Station may supply
                                                    Thermal Capacity (MW) = 70                                                             another LDC's territory.
                                                  Short Circuit Capacity (MVA) = 18                                                         Refer to OPA FIT LDC
                                      M1         M2       M3        M4        M5        M6       M7       M8        M9     M10             locator tool to find LDC.
Allocated Capacity (MW)               0          0         0         0         0        0        0        0         0       0


          For any information or inquiries please contact Toronto Hydro
                                                           *CARLAW TS                                                                         Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                       another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                        Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                              A1A2 = 9                                         A6A7 = 5                           locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                      A1A2 = 102                                       A6A7 = 101
                               For any information or inquiries please contact Toronto Hydro


          For any information or inquiries please contact Hydro Ottawa
                                                           *CARLING TS                                                                        Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                       another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                        Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                               KY = 13                                        QZ = 12                             locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                       KY = 138                                        QZ = 138
                                For any information or inquiries please contact Hydro Ottawa



                       CARLTON TS DESN 1                                                 Station may supply
                       Thermal Capacity (MW) = 18                                     another LDC's territory.
                     Short Circuit Capacity (MVA) = 10                                 Refer to OPA FIT LDC
                                      M13       M14       M15       M16               locator tool to find LDC.
Allocated Capacity (MW)                 0         0        0         0




                                                CARLTON TS DESN 2                                                                    Station may supply
                                         Thermal Capacity (MW) = Sum of Buses                                                     another LDC's territory.
                                           Short Circuit Capacity (MVA) = N/A                                                      Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                    KH = 9                                       BY = 0                                  locator tool to find LDC.
Short Circuit Bus Capacity (MVA)            KH = 77                                       BY = 54
                                      M7      M17        M18       M12      M20        M25      M11       M10       M21
Allocated Capacity (MW)               0        0          0         0         0         0         0        0         0


          For any information of inquiries please contact Toronto Hydro
                                                         *CECIL TS DESN 1                                                                     Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                       another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                        Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                              A1A2 = 0                                        A3A4 = 9                            locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                       A1A2 = 0                                        A3A4 = 61
                               For any information of inquiries please contact Toronto Hydro


          For any information of inquiries please contact Toronto Hydro
                                                         *CECIL TS DESN 2                                                                     Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                       another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                        Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                             A5A6 = 14                                        A7A8 = 22                           locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                      A5A6 = 41                                        A7A8 = 42
                               For any information of inquiries please contact Toronto Hydro


          For any information or inquiries please contact Guelph Hydro
                                                                *CEDAR TS DESN 1                                                                                 Station may supply
                                                          Thermal Capacity (MW) = Sum of Buses                                                                another LDC's territory.
                                                            Short Circuit Capacity (MVA) = N/A                                                                 Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                               YB = 9                                                ZE = 5                          locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                                       YB = 131                                              ZE = 153
                                           For any information or inquiries please contact Guelph Hydro


          For any information or inquiries please contact Guelph Hydro
                                             *CEDAR TS DESN 2                                                                Station may supply
                                          Thermal Capacity (MW) = 32                                                      another LDC's territory.
                                        Short Circuit Capacity (MVA) = 139                                                 Refer to OPA FIT LDC
                      For any information or inquiries please contact Guelph Hydro                                        locator tool to find LDC.



                           CENTRALIA TS
                      Thermal Capacity (MW) = 29
                    Short Circuit Capacity (MVA) = 503
                                      M1        M2         M3        M4
Allocated Capacity (MW)               0.3        0         0         0




                 CHAPLEAU DS                                         Station may supply
             Thermal Capacity (MW) = 0                            another LDC's territory.
          Short Circuit Capacity (MVA) = 647                       Refer to OPA FIT LDC
                                       F3        F4               locator tool to find LDC.
Allocated Capacity (MW)                0         0


          For any information or inquiries please contact Toronto Hydro
                                                      *CHARLES TS DESN 1                                                                      Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                       another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                        Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                             A5A6 = 14                                        A7A8 = 11                           locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                      A5A6 = 51                                        A7A8 = 59
                               For any information or inquiries please contact Toronto Hydro


          For any information or inquiries please contact Toronto Hydro
                                                      *CHARLES TS DESN 2                                                                      Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                       another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                        Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                              A1A2 = 9                                        A3A4 = 9                            locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                      A1A2 = 96                                        A3A4 = 97
                               For any information or inquiries please contact Toronto Hydro



                                               CHERRYWOOD TS                                                                 Station may supply
                                         Thermal Capacity (MW) = 77                                                       another LDC's territory.
                                        Short Circuit Capacity (MVA) = 0                                                   Refer to OPA FIT LDC
                                      M1       M2        M3        M4        M5         M6       M7       M8              locator tool to find LDC.
Allocated Capacity (MW)               0         0         0         0        0          0        0        0




               CHESTERVILLE TS
             Thermal Capacity (MW) = 32
          Short Circuit Capacity (MVA) = 1086
                                       M2        M4
Allocated Capacity (MW)                 0        0




                               CLARABELLE TS                                                     Station may supply
                                                                                                                        AZILDA DS is downstream of
                          Thermal Capacity (MW) = 76                                          another LDC's territory.     CLARABELLE TS M8
                        Short Circuit Capacity (MVA) = 323                                     Refer to OPA FIT LDC
                                      M4        M5       M6          M7      M8               locator tool to find LDC.
Allocated Capacity (MW)                0         0       18          0       0
                 CLARENCE DS
             Thermal Capacity (MW) = 2
          Short Circuit Capacity (MVA) = 444
                                       F1        F2
Allocated Capacity (MW)                0         0




                                                 CLARKE TS                                                               Station may supply
                                                                                                                                                  BIRR DS is downstream of
                                           Thermal Capacity (MW) = 0                                                  another LDC's territory.        CLARKE TS M2
                                         Short Circuit Capacity (MVA) = 0                                              Refer to OPA FIT LDC
                                       M1       M2        M3        M4         M5       M6     M7      M8             locator tool to find LDC.
Allocated Capacity (MW)                0        0.3        0         0         0        0      0       0




            CLEARWATER BAY DS
             Thermal Capacity (MW) = 4
          Short Circuit Capacity (MVA) = 706
                                       F1        F2
Allocated Capacity (MW)                0         0




                        COBDEN DS
                   Thermal Capacity (MW) = 8
              Short Circuit Capacity (MVA) = 406
                                       F2      F3          F4
Allocated Capacity (MW)                0        0          0




                   COBDEN TS                                           BEACHBURG DS is         NORTHCOTE DS is
              Thermal Capacity (MW) = 12                            downstream of COBDEN TS downstream of COBDEN TS
           Short Circuit Capacity (MVA) = N/A                                  M2                      M2
Thermal Bus Capacity (MW)            T2 = 12 T1 = 11
Short Circuit Bus Capacity (MVA) T2 = 1302T1 = 1294
                                       M2      M6
Allocated Capacity (MW)                4.7      0




            COBOCONK DS                                     COBOCONK DS is
         Thermal Capacity (MW) = 6                       downstream of LINDSAY TS
      Short Circuit Capacity (MVA) = N/A                            M7
                                        F2
Allocated Capacity (MW)                  0




             COCHRANE WEST DS
             Thermal Capacity (MW) = 4
          Short Circuit Capacity (MVA) = 417
                                       F1        F2
Allocated Capacity (MW)                1         0




                  CONISTON TS
             Thermal Capacity (MW) = 0
          Short Circuit Capacity (MVA) = 573
                                      M1         M5
Allocated Capacity (MW)                0         0




                     CONSTANCE DS
                   Thermal Capacity (MW) = 18
                Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)             T1 = 14        T2 = 16
Short Circuit Bus Capacity (MVA)     T1 = 632        T2 = 632
                                         F1       F2        F4
Allocated Capacity (MW)                  0         0         0




                               COOKSVILLE TS DESN 1                                                     Station may supply
                                 Thermal Capacity (MW) = 0                                           another LDC's territory.
                               Short Circuit Capacity (MVA) = 0                                       Refer to OPA FIT LDC
                                      M10       M12      M14         M11      M13       M9           locator tool to find LDC.
Allocated Capacity (MW)                0         0         0          0        0        0




                               COOKSVILLE TS DESN 2                                                     Station may supply
                                 Thermal Capacity (MW) = 59                                          another LDC's territory.
                               Short Circuit Capacity (MVA) = 37                                      Refer to OPA FIT LDC
                                      M17       M19       M21        M18      M20       M22          locator tool to find LDC.
Allocated Capacity (MW)                 0         0         0         0        0         0




                          CRAIG DS
                  Thermal Capacity (MW) = 10
              Short Circuit Capacity (MVA) = 406
                                       F1      F2          F3
Allocated Capacity (MW)                0        0          0




                                                                 CRAWFORD TS                                                                         Station may supply
                                                          Thermal Capacity (MW) = 62                                                              another LDC's territory.
                                                         Short Circuit Capacity (MVA) = 0                                                          Refer to OPA FIT LDC
                                       M5        M6        M7         M8        M8        M9   M10    M11      M12      M13      M14              locator tool to find LDC.
Allocated Capacity (MW)                0         0         0           0         0        0     0      0        0        0        0




                   CROSBY TS DESN 1
                   Thermal Capacity (MW) = 23
                Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                  T1 = 21       T2 = 21
Short Circuit Bus Capacity (MVA)           T1 = 477      T2 = 479
                                        M3        M5       M6
Allocated Capacity (MW)                  0         0        0




              CROSBY TS DESN 2
             Thermal Capacity (MW) = 47
          Short Circuit Capacity (MVA) = 1053
                                       M1        M2
Allocated Capacity (MW)                 0        0




                CROW RIVER DS
               Thermal Capacity (MW) = 5
           Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)             T3 = 4   T4 = 5
Short Circuit Bus Capacity (MVA)     T3 = 717 T4 = 717
                                        F1       F2
Allocated Capacity (MW)                 0        0




                                                          CROWLAND TS                                                                     Station may supply
                                                    Thermal Capacity (MW) = 57                                                         another LDC's territory.
                                                  Short Circuit Capacity (MVA) = 99                                                     Refer to OPA FIT LDC
                                      M13       M14      M15       M16       M17        M18    M19    M20      M21      M22            locator tool to find LDC.
Allocated Capacity (MW)                0         0         0         0         0        20      0      0        0        0




             CRYSLER DS                                  CRYSLER DS is downstream
         Thermal Capacity (MW) = 4                         of ST ISIDORE TS M2
      Short Circuit Capacity (MVA) = N/A
                                        F2
Allocated Capacity (MW)                0.4




              CRYSTAL FALLS TS
             Thermal Capacity (MW) = 18
          Short Circuit Capacity (MVA) = 852
                                      M1         M2
Allocated Capacity (MW)               8.4        8.5
                          CUMBERLAND DS
                        Thermal Capacity (MW) = 5
                    Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                  T1 = 5             T2 = 3
Short Circuit Bus Capacity (MVA)          T1 = 410           T2 = 408
                                       F2         F4       F1        F3
Allocated Capacity (MW)                 0         0        0         0




                                                         CUMBERLAND TS                                                                          Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                         another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                          Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                B=5                                               Q=5                               locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                        B = 107                                           Q = 107
                                      M22       M24       M26       M28       M30    M21        M23        M25       M27     M29
Allocated Capacity (MW)                0          0         0         0        0      0          0           0        0       0




                          DEEP RIVER DS
                       Thermal Capacity (MW) = 12
                    Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)            T1 = 5         T2 = 6         T3 = 6
Short Circuit Bus Capacity (MVA)    T1 = 414       T2 = 414       T3 = 420
                                       F1        F2        F3        F5
Allocated Capacity (MW)                 0        0         0         0




                   DES JOACHIMS DS
                   Thermal Capacity (MW) = 7
              Short Circuit Capacity (MVA) = 409
                                       F1      F2          F3
Allocated Capacity (MW)                0        0          0




                      DETWEILER TS                                              Station may supply
                  Thermal Capacity (MW) = 22                                 another LDC's territory.
               Short Circuit Capacity (MVA) = 75                              Refer to OPA FIT LDC
                                      M11      M12        M13                locator tool to find LDC.
Allocated Capacity (MW)                 0       7.8        0




                   DOBBIN DS
              Thermal Capacity (MW) = 15
           Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)            T1 = 13 T2 = 13
Short Circuit Bus Capacity (MVA)     T1 = 623 T2 = 624
                                        F1       F2
Allocated Capacity (MW)                 0        0




                                                 DOBBIN TS
                                         Thermal Capacity (MW) = 87
                                       Short Circuit Capacity (MVA) = 431
                                      M1        M2       M3        M4          M5       M6       M7         M8
Allocated Capacity (MW)               0          0         0        0          10       0        8          0




                                      DOUGLAS POINT TS                                                                REID CORNERS DS is
                                     Thermal Capacity (MW) = 39                                                      downstream of DOUGLAS
                                   Short Circuit Capacity (MVA) = 310                                                     POINT TS M6
                                      M1         M2        M3       M4         M5       M6       M8
Allocated Capacity (MW)                0          0         0       8.5        0        0.3      0




                   DRYDEN TS
             Thermal Capacity (MW) = 20
          Short Circuit Capacity (MVA) = 1034
                                       M1        M3
Allocated Capacity (MW)                 0        0


          For any information or inquiries please contact Toronto Hydro
                                                       *DUFFERIN TS DESN 1                                                                      Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                         another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                          Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                              A1A2 = 8                                          A3A4 = 4                            locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                      A1A2 = 24                                          A3A4 = 27
                               For any information or inquiries please contact Toronto Hydro


          For any information or inquiries please contact Toronto Hydro
                                                       *DUFFERIN TS DESN 2                                                                      Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                         another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                          Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                              A5A6 = 9                                          A7A8 = 7                            locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                      A5A6 = 61                                          A7A8 = 62
                               For any information or inquiries please contact Toronto Hydro



                                                 DUNDAS TS                                                                     Station may supply
                                         Thermal Capacity (MW) = 69                                                         another LDC's territory.
                                       Short Circuit Capacity (MVA) = 67                                                     Refer to OPA FIT LDC
                                      M1       M2        M3        M4          M5       M6       M7         M8              locator tool to find LDC.
Allocated Capacity (MW)               0         0         0         0          0        0        0          0




                                     DUNDAS TS #2                                                            Station may supply
                                Thermal Capacity (MW) = 52                                                another LDC's territory.
                              Short Circuit Capacity (MVA) = 96                                            Refer to OPA FIT LDC
                                     M11       M12       M13        M14       M15      M16                locator tool to find LDC.
Allocated Capacity (MW)                0         0         0         0         0        0




                 DUNNVILLE TS                                        Station may supply
             Thermal Capacity (MW) = 20                           another LDC's territory.
          Short Circuit Capacity (MVA) = 504                       Refer to OPA FIT LDC
                                      M1         M2               locator tool to find LDC.
Allocated Capacity (MW)                0         9.9


          For any information or inquiries please contact Toronto Hydro
                                                       *DUPLEX TS DESN 1                                                                        Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                         another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                          Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                              A1A2 = 9                                          A3A4 = 7                            locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                      A1A2 = 59                                          A3A4 = 59
                               For any information or inquiries please contact Toronto Hydro


          For any information or inquiries please contact Toronto Hydro
                                                       *DUPLEX TS DESN 2                                                                        Station may supply
                                                     Thermal Capacity (MW) = 9                                                               another LDC's territory.
                                                   Short Circuit Capacity (MVA) = 64                                                          Refer to OPA FIT LDC
                               For any information or inquiries please contact Toronto Hydro                                                 locator tool to find LDC.



                       DYMOND TS
                  Thermal Capacity (MW) = 17
              Short Circuit Capacity (MVA) = 833
                                      M1       M2          M3
Allocated Capacity (MW)                0        0          9.5




            EAR FALLS TS
        Thermal Capacity (MW) = 10
     Short Circuit Capacity (MVA) = 1303
                                       M1
Allocated Capacity (MW)                0
                                                       EDGEWARE TS                                                                        Station may supply
                                          Thermal Capacity (MW) = Sum of Buses                                                         another LDC's territory.
                                            Short Circuit Capacity (MVA) = N/A                                                          Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                          B=8                                          Y=8                                    locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                  B = 166                                      Y = 168
                                       M1      M3         M5        M7       M2         M4       M6        M8      M10
Allocated Capacity (MW)                0        0          0         0         0        0         0        0        0




                                                                                                         ELGIN TS DESN 1                                                                                                  Station may supply
                                                                                               Thermal Capacity (MW) = Sum of Buses                                                                                    another LDC's territory.
                                                                                                 Short Circuit Capacity (MVA) = N/A                                                                                     Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                                DK = 5                                                                                         JQ = 6                                         locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                                         DK = 91                                                                                       JQ = 74
                                       M41       M42        M43       M44      M45     M46      M47       M48      M22        M23       M24      M25      M26       M27       M28     M30      M31   M32   M33   M34
Allocated Capacity (MW)                 0         0          0         0         0      0        0         0        0          0         0        0        0         0         0       0        0     0     0     0




                                    ELGIN TS DESN 2                                                         Station may supply
                                 Thermal Capacity (MW) = 25                                              another LDC's territory.
                               Short Circuit Capacity (MVA) = 32                                          Refer to OPA FIT LDC
                                      M51       M52       M53         M61     M62      M63               locator tool to find LDC.
Allocated Capacity (MW)                 0         0         0          0       0        0




                                                                     ELLESMERE TS                                                                                     Station may supply
                                                           Thermal Capacity (MW) = Sum of Buses                                                                    another LDC's territory.
                                                             Short Circuit Capacity (MVA) = N/A                                                                     Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                       J = 11                                                Q = 11                                       locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                               J = 110                                                Q = 110
                                       M21       M23       M25        M27      M29       M31    M22       M24      M26      M28         M30      M32
Allocated Capacity (MW)                 0         0          0         0         0        0      0         0        0         0          0        0




                ELLIOT LAKE TS
             Thermal Capacity (MW) = 25
          Short Circuit Capacity (MVA) = 1056
                                       M1         M3
Allocated Capacity (MW)                 0         0




                          ELMIRA TS                                             Station may supply
                  Thermal Capacity (MW) = 30                                 another LDC's territory.
              Short Circuit Capacity (MVA) = 426                              Refer to OPA FIT LDC
                                      M1       M2           M3               locator tool to find LDC.
Allocated Capacity (MW)                0        0           0




                                                                  ERINDALE TS DESN 1                                                                                  Station may supply
                                                           Thermal Capacity (MW) = Sum of Buses                                                                    another LDC's territory.
                                                             Short Circuit Capacity (MVA) = N/A                                                                     Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                      E = 11                                                  Q=5                                         locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                               E = 111                                                Q = 82
                                       M32       M34       M36       M38       M40       M42    M31       M33      M35      M37         M39      M41
Allocated Capacity (MW)                 0         0          0         0         0        0      0         0        0        0           0        0




                                             ERINDALE TS DESN 2                                                                 Station may supply
                                           Thermal Capacity (MW) = 94                                                        another LDC's territory.
                                        Short Circuit Capacity (MVA) = 267                                                    Refer to OPA FIT LDC
                                       M23      M24       M25       M26       M27      M28      M29       M30                locator tool to find LDC.
Allocated Capacity (MW)                 0         0         0        0         0        0        0         0




                                             ERINDALE TS DESN 3                                                                 Station may supply
                                          Thermal Capacity (MW) = 103                                                        another LDC's territory.
                                        Short Circuit Capacity (MVA) = 261                                                    Refer to OPA FIT LDC
                                       M1        M2       M3        M4         M5       M6       M7        M8                locator tool to find LDC.
Allocated Capacity (MW)                0          0         0        0         0        0        0         0




                 ESPANOLA TS
             Thermal Capacity (MW) = 18
          Short Circuit Capacity (MVA) = 1114
                                       M1         M2
Allocated Capacity (MW)                 0         0




                                                ESPLANADE TS                                                                    Station may supply
                                      Thermal Capacity (MW) = Sum of Buses                                                   another LDC's territory.
                                        Short Circuit Capacity (MVA) = N/A                                                    Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                         J1J2 = 23                             Q1Q2 = 17                            locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                   J1J2 = 65                            Q1Q2 = 62
                                       M1        M2        M3       M4     M11         M12     M13        M14
Allocated Capacity (MW)                 0         0         0        0      0           0       0          0


          For any information or inquiries please contact EnWin Utilities
                                         *ESSEX TS                                                          Station may supply
                                 Thermal Capacity (MW) = 54                                              another LDC's territory.
                               Short Circuit Capacity (MVA) = 65                                          Refer to OPA FIT LDC
           For any information or inquiries please contact EnWin Utilities                               locator tool to find LDC.



                          ETON DS
                   Thermal Capacity (MW) = 8
              Short Circuit Capacity (MVA) = 451
                                       F1      F2           F3
Allocated Capacity (MW)                0        0           0




                             EVERETT TS
                      Thermal Capacity (MW) = 64
                    Short Circuit Capacity (MVA) = 528
                                      M5        M6          M7         M8
Allocated Capacity (MW)                 0        0          0          10




                                   FAIRBANK TS DESN 1                                                       Station may supply
                                 Thermal Capacity (MW) = 63                                              another LDC's territory.
                               Short Circuit Capacity (MVA) = 65                                          Refer to OPA FIT LDC
                                      M11       M12        M7          M3      M5       M8               locator tool to find LDC.
Allocated Capacity (MW)                 0         0         0          0       0        0




                                             FAIRBANK TS DESN 2                                                                 Station may supply
                                          Thermal Capacity (MW) = 56                                                         another LDC's territory.
                                        Short Circuit Capacity (MVA) = 41                                                     Refer to OPA FIT LDC
                                       M1      M10        M2       M23        M24       M4       M6        M9                locator tool to find LDC.
Allocated Capacity (MW)                0         0         0         0         0        0        0         0




                                                                  FAIRCHILD TS DESN 1                                                                                 Station may supply
                                                           Thermal Capacity (MW) = Sum of Buses                                                                    another LDC's territory.
                                                             Short Circuit Capacity (MVA) = N/A                                                                     Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                      B = 11                                                    Y = 11                                    locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                               B = 97                                                    Y = 91
                                       M1         M3        M5        M7       M9        M11    M2         M4       M6            M8    M10      M12
Allocated Capacity (MW)                0          0          0         0         0        0     0          0        0             0      0        0




                                                                  FAIRCHILD TS DESN 2                                                                                 Station may supply
                                                           Thermal Capacity (MW) = Sum of Buses                                                                    another LDC's territory.
                                                             Short Circuit Capacity (MVA) = N/A                                                                     Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                       J=5                                                   Q = 11                                       locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                               J = 114                                                Q = 116
                                       M21       M23       M25       M27       M29       M31    M22       M24      M26      M28         M30      M32
Allocated Capacity (MW)                 0         0          0         0         0        0      0         0        0         0          0        0
                  FAUQUIER DS
             Thermal Capacity (MW) = 2
          Short Circuit Capacity (MVA) = 441
                                       F1          F2
Allocated Capacity (MW)                0           0




                                        FERGUS TS
                                 Thermal Capacity (MW) = 98
                               Short Circuit Capacity (MVA) = 346
                                        M1       M2        M3            M4     M7       M8
Allocated Capacity (MW)                 10         0        0            0      0        0




                                                                    FINCH TS DESN 1                                                                            Station may supply
                                                            Thermal Capacity (MW) = Sum of Buses                                                            another LDC's territory.
                                                              Short Circuit Capacity (MVA) = N/A                                                             Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                       B = 11                                                Y = 11                                locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                                B = 100                                              Y = 101
                                        M1        M3         M5        M7       M9        M11    M2       M4       M6        M8     M10      M12
Allocated Capacity (MW)                 0         0           0         0         0        0     0        0        0         0       0        0




                                                                    FINCH TS DESN 2                                                                            Station may supply
                                                            Thermal Capacity (MW) = Sum of Buses                                                            another LDC's territory.
                                                              Short Circuit Capacity (MVA) = N/A                                                             Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                       Q = 11                                                J = 11                                locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                                Q = 116                                              J = 116
                                       M22        M24       M26       M28       M30       M32    M21     M23      M25       M27     M29      M31
Allocated Capacity (MW)                 0          0          0         0         0        0      0       0        0         0       0        0




                          FOREST JURA DS                                                   SPRINGVALE DS is
                       Thermal Capacity (MW) = 18                                        downstream of FOREST
                    Short Circuit Capacity (MVA) = N/A                                       JURA DS F1
Thermal Bus Capacity (MW)                 T2 = 16              T1 = 16
Short Circuit Bus Capacity (MVA)         T2 = 583              T1 = 645
                                       F2        F4          F1       F3
Allocated Capacity (MW)               16.5        0          0         0




                           FOREST LEA DS
                        Thermal Capacity (MW) = 8
                    Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                  T2 = 6               T1 = 7
Short Circuit Bus Capacity (MVA)          T2 = 422             T1 = 422
                                       F3         F4         F1        F2
Allocated Capacity (MW)                 0         0          0         0




          FORT FRANCES TS
        Thermal Capacity (MW) = 53
     Short Circuit Capacity (MVA) = 1338
                                       M1
Allocated Capacity (MW)                0


         For any information or inquires please contact Thunder Bay Hydro
                                                         *FORT WILLIAM TS                                                                     Station may supply
                                                       Thermal Capacity (MW) = 70                                                          another LDC's territory.
                                                     Short Circuit Capacity (MVA) = 54                                                      Refer to OPA FIT LDC
                             For any information or inquires please contact Thunder Bay Hydro                                              locator tool to find LDC.



                                      FRONTENAC TS                                                         Station may supply
                                 Thermal Capacity (MW) = 64                                             another LDC's territory.
                               Short Circuit Capacity (MVA) = 734                                        Refer to OPA FIT LDC
                                        M1       M2        M3            M4     M5       M8             locator tool to find LDC.
Allocated Capacity (MW)                  0         0        0            0      0        0


              For any information or inquires please Horizon Utilities
                                                         *GAGE TS DESN 2                                                                      Station may supply
                                                       Thermal Capacity (MW) = 0                                                           another LDC's territory.
                                                     Short Circuit Capacity (MVA) = 0                                                       Refer to OPA FIT LDC
                                     For any information or inquires please Horizon Utilities                                              locator tool to find LDC.


              For any information or inquires please Horizon Utilities
                                                         *GAGE TS DESN 3                                                                      Station may supply
                                                       Thermal Capacity (MW) = 0                                                           another LDC's territory.
                                                     Short Circuit Capacity (MVA) = 0                                                       Refer to OPA FIT LDC
                                     For any information or inquires please Horizon Utilities                                              locator tool to find LDC.


              For any information or inquires please Horizon Utilities
                                                         *GAGE TS DESN 4                                                                      Station may supply
                                                       Thermal Capacity (MW) = 0                                                           another LDC's territory.
                                                     Short Circuit Capacity (MVA) = 0                                                       Refer to OPA FIT LDC
                                     For any information or inquires please Horizon Utilities                                              locator tool to find LDC.


or any information or inquiries please contact Cambridge North Dumfries Hydro (CND)
                                                                           *GALT TS                                                                            Station may supply
                                                            Thermal Capacity (MW) = Sum of Buses                                                            another LDC's territory.
                                                              Short Circuit Capacity (MVA) = N/A                                                             Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                       J = 11                                               Y = 11                                 locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                               J = 167                                               Y = 164
                           For any information or inquiries please contact Cambridge North Dumfries Hydro (CND)


           For any information or inquiries please contact Toronto Hydro
                                                        *GERRARD TS DESN 1                                                                    Station may supply
                                                       Thermal Capacity (MW) = 0                                                           another LDC's territory.
                                                     Short Circuit Capacity (MVA) = 0                                                       Refer to OPA FIT LDC
                                For any information or inquiries please contact Toronto Hydro                                              locator tool to find LDC.


           For any information or inquiries please contact Toronto Hydro
                                                        *GERRARD TS DESN 2                                                                    Station may supply
                                                       Thermal Capacity (MW) = 0                                                           another LDC's territory.
                                                     Short Circuit Capacity (MVA) = 0                                                       Refer to OPA FIT LDC
                                For any information or inquiries please contact Toronto Hydro                                              locator tool to find LDC.



         GLEN SANDFIELD DS                                 GLEN SANDFIELD DS is
         Thermal Capacity (MW) = 4                        downstream of LONGUEUIL
      Short Circuit Capacity (MVA) = N/A                           TS M23
                                        F3
Allocated Capacity (MW)                0.1




                                                 GLENDALE TS                                                                 Station may supply
                                       Thermal Capacity (MW) = Sum of Buses                                               another LDC's territory.
                                         Short Circuit Capacity (MVA) = N/A                                                Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                             BJ = 3                               DQ = 4                         locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                     BJ = 90                               DQ = 66
                                       M31       M32        M33      M34    M5           M8      M23     M24
Allocated Capacity (MW)                  0         0         0        0     0            0         0      0




             GLENDALE TS DESN 2                                         Station may supply
             Thermal Capacity (MW) = 0                               another LDC's territory.
          Short Circuit Capacity (MVA) = 149                          Refer to OPA FIT LDC
                                      M16         M9                 locator tool to find LDC.
Allocated Capacity (MW)                0          0


           For any information or inquiries please contact Toronto Hydro
                                                     *GLENGROVE TS DESN 1                                                                     Station may supply
                                                       Thermal Capacity (MW) = 24                                                          another LDC's territory.
                                                     Short Circuit Capacity (MVA) = 57                                                      Refer to OPA FIT LDC
                                For any information or inquiries please contact Toronto Hydro                                              locator tool to find LDC.
          For any information or inquiries please contact Toronto Hydro
                                                   *GLENGROVE TS DESN 2                                                                       Station may supply
                                                     Thermal Capacity (MW) = 24                                                            another LDC's territory.
                                                   Short Circuit Capacity (MVA) = 18                                                        Refer to OPA FIT LDC
                               For any information or inquiries please contact Toronto Hydro                                               locator tool to find LDC.



           GLENGARRY DS                                     GLENGARRY DS is
         Thermal Capacity (MW) = 8                       downstream of ST ISIDORE
      Short Circuit Capacity (MVA) = N/A                          TS M4
                                        F1
Allocated Capacity (MW)                  0




                                      GODERICH TS                                                           Station may supply
                                 Thermal Capacity (MW) = 1                                               another LDC's territory.
                              Short Circuit Capacity (MVA) = 299                                          Refer to OPA FIT LDC
                                       M1       M2        M3         M4        M5       M6               locator tool to find LDC.
Allocated Capacity (MW)                 0         0        0         0         0        0




                                                                 GOREWAY TS DESN1                                                                              Station may supply
                                                         Thermal Capacity (MW) = Sum of Buses                                                               another LDC's territory.
                                                           Short Circuit Capacity (MVA) = N/A                                                                Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                    B = 11                                                   Y = 11                                locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                             B = 96                                                   Y = 95
                                      M41       M43      M45       M47       M49       M51    M42         M44      M46      M48      M50     M52
Allocated Capacity (MW)                0         0         0         0         0        0      0           0        0        0        0       0




            GRAND BEND EAST DS
              Thermal Capacity (MW) = 17
           Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)            T1 = 15 T2 = 15
Short Circuit Bus Capacity (MVA)     T1 = 659 T2 = 659
                                        F1       F2
Allocated Capacity (MW)                 6        0




                          GREELY DS
                   Thermal Capacity (MW) = 21
                Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)             T1 = 18        T2 = 19
Short Circuit Bus Capacity (MVA)     T1 = 568        T2 = 583
                                         F3       F2        F4
Allocated Capacity (MW)                  0         0         0




                                                                     HALTON TS                                                                                 Station may supply
                                                         Thermal Capacity (MW) = Sum of Buses                                                               another LDC's territory.
                                                           Short Circuit Capacity (MVA) = N/A                                                                Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                     J = 50                                                  Q = 50                                locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                             J = 105                                                  Q = 111
                                      M22       M24      M26        M28      M30       M32    M21         M23      M25      M27      M29     M31
Allocated Capacity (MW)                0         0         0         0         0        0      0           0        0         0       0       0




                                       HANLON TS                                                            Station may supply
                                Thermal Capacity (MW) = 30                                               another LDC's territory.
                              Short Circuit Capacity (MVA) = 132                                          Refer to OPA FIT LDC
                                      M11       M12       M13       M21       M22      M23               locator tool to find LDC.
Allocated Capacity (MW)                 0         0        0         0         0        0




                                      HANOVER TS
                                Thermal Capacity (MW) = 68
                              Short Circuit Capacity (MVA) = 520
                                       M1       M2        M3         M4        M5      H1E
Allocated Capacity (MW)                 0         0        0         0         18       0




                          HARROWSMITH DS
                       Thermal Capacity (MW) = 10
                    Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                  T1 = 8             T2 = 8
Short Circuit Bus Capacity (MVA)          T1 = 401           T2 = 378
                                       F2         F3       F4        F5
Allocated Capacity (MW)                 0         0        0         0




                                   HAVELOCK TS
                          Thermal Capacity (MW) = 29
                        Short Circuit Capacity (MVA) = 670
                                      M1        M2       M3          M4        M6
Allocated Capacity (MW)               5.4        0        0          6.7       10




                               HAWTHORNE TS                                                      Station may supply
                          Thermal Capacity (MW) = 76                                          another LDC's territory.
                        Short Circuit Capacity (MVA) = 509                                     Refer to OPA FIT LDC
                                      M1        M2       M3          M4        M5             locator tool to find LDC.
Allocated Capacity (MW)                0         0        0          0         0




                          HEARST TS                                             Station may supply
                  Thermal Capacity (MW) = 25                                 another LDC's territory.
              Short Circuit Capacity (MVA) = 527                              Refer to OPA FIT LDC
                                      M1       M2          M3                locator tool to find LDC.
Allocated Capacity (MW)                0        0          0




              HERRIDGE LAKE DS
             Thermal Capacity (MW) = 2
          Short Circuit Capacity (MVA) = 443
                                       F1        F2
Allocated Capacity (MW)                0         0




                                                HIGHBURY TS                                                                  Station may supply
                                          Thermal Capacity (MW) = 67                                                      another LDC's territory.
                                        Short Circuit Capacity (MVA) = 94                                                  Refer to OPA FIT LDC
                                      M11      M12       M13       M14        M15      M16      M17       M18             locator tool to find LDC.
Allocated Capacity (MW)               10         0         0         0         0        0        0         0


          For any information or inquiries please contact Hydro Ottawa
                                                          *HINCHEY TS                                                                         Station may supply
                                                    Thermal Capacity (MW) = 10                                                             another LDC's territory.
                                                  Short Circuit Capacity (MVA) = 117                                                        Refer to OPA FIT LDC
                                For any information or inquiries please contact Hydro Ottawa                                               locator tool to find LDC.



                  HINCHINBROOKE DS
                   Thermal Capacity (MW) = 5
              Short Circuit Capacity (MVA) = 398
                                       F1      F2          F3
Allocated Capacity (MW)                0        0          0




                                                HOLLAND TS                                                                   Station may supply
                                           Thermal Capacity (MW) = 0                                                      another LDC's territory.
                                        Short Circuit Capacity (MVA) = 406                                                 Refer to OPA FIT LDC
                                       M3        M4       M5        M6         M7       M8       M9       M10             locator tool to find LDC.
Allocated Capacity (MW)                0          0         0        0         0        0        0         0
                                                           HORNER TS                                                                                Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                             another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                              Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                Y = 46                                            B = 48                                locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                         Y = 71                                            B = 96
                                       M2        M4        M6       M8        M10    M1           M3        M5          M7      M9
Allocated Capacity (MW)                0          0         0         0        0     0            0          0          0       0




                                                                                        HORNING TS                                                                                               Station may supply
                                                                             Thermal Capacity (MW) = Sum of Buses                                                                             another LDC's territory.
                                                                               Short Circuit Capacity (MVA) = N/A                                                                              Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                                        B = 34                                                                       Q = 34                          locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                                                 B = 141                                                                      Q = 138
                                       M2        M3        M4        M5       M6        M7       M8        M9     M10           M11     M45       M46      M47      M48      M49     M50
Allocated Capacity (MW)                0         0         0         0         0         0         0        0      0             0       0         0        0         0       0       0




                    HOYLE DS
             Thermal Capacity (MW) = 13
          Short Circuit Capacity (MVA) = 631
                                       F1        F2
Allocated Capacity (MW)                0         0




                                                INGERSOLL TS                                                                  KINTORE DS is downstream KIRKTON DS is downstream
                                      Thermal Capacity (MW) = Sum of Buses                                                      of INGERSOLL TS M43      of INGERSOLL TS M43
                                        Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                            E = 11                                Z = 11
Short Circuit Bus Capacity (MVA)                    E = 161                                Z = 160
                                      M43       M45        M49      M51    M44          M46      M50        M52
Allocated Capacity (MW)               18.5        0         8.5      0      0            0        8.5        0




                  IROQUOIS FALLS DS                                           Station may supply
                   Thermal Capacity (MW) = 6                               another LDC's territory.
              Short Circuit Capacity (MVA) = 405                            Refer to OPA FIT LDC
                                       F1      F2          F3              locator tool to find LDC.
Allocated Capacity (MW)                0        0          0




                                               JARVIS TS                                                                Station may supply
                                      Thermal Capacity (MW) = 0                                                      another LDC's territory.
                                    Short Circuit Capacity (MVA) = 0                                                  Refer to OPA FIT LDC
                                      M1         M2        M3        M4       M5         M6       M7                 locator tool to find LDC.
Allocated Capacity (MW)                0          0         0        0        0          0        0




             JELLICOE DS
         Thermal Capacity (MW) = 1
      Short Circuit Capacity (MVA) = 455
                                       F1
Allocated Capacity (MW)                 0


          For any information or inquiries please contact Toronto Hydro
                                                         *JOHN TS DESN 1                                                                            Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                             another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                              Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                             A17A18 = 0                                         A4A6 = 0                                locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                     A17A18 = 78                                         A4A6 = 69
                                For any information or inquiries please contact Toronto Hydro


          For any information or inquiries please contact Toronto Hydro
                                                         *JOHN TS DESN 2                                                                            Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                             another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                              Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                              A3A5 = 0                                         A13A14 = 0                               locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                      A3A5 = 69                                         A13A14 = 98
                                For any information or inquiries please contact Toronto Hydro


          For any information or inquiries please contact Toronto Hydro
                                                         *JOHN TS DESN 3                                                                            Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                             another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                              Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                            A11A12 = 11                                        A15A16 = 11                              locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                     A11A12 = 94                                        A15A16 = 94
                                For any information or inquiries please contact Toronto Hydro



                          KAPUSKASING TS                                                  Station may supply
                      Thermal Capacity (MW) = 46                                       another LDC's territory.
                    Short Circuit Capacity (MVA) = 149                                  Refer to OPA FIT LDC
                                      M1        M2         M3        M4                locator tool to find LDC.
Allocated Capacity (MW)                 0        0         0         0




                                    KEITH TS DESN 1                                                           Station may supply
                                Thermal Capacity (MW) = 58                                                 another LDC's territory.
                               Short Circuit Capacity (MVA) = 0                                             Refer to OPA FIT LDC
                                      M1        M2        M3         M4       M5         M6                locator tool to find LDC.
Allocated Capacity (MW)                0         0        25         20       11         0




           KENILWORTH DS                                    KENILWORTH DS is
         Thermal Capacity (MW) = 2                            downstream of
      Short Circuit Capacity (MVA) = N/A                   PALMERSTON TS M2
                                        F1
Allocated Capacity (MW)                  0




                             KENORA DS
                       Thermal Capacity (MW) = 0
                     Short Circuit Capacity (MVA) = 0
                                       F1       F2         F3        F4
Allocated Capacity (MW)                0         0         0         0




                                                                   KENT TS DESN1                                                                                     Station may supply
                                                          Thermal Capacity (MW) = Sum of Buses                                                                    another LDC's territory.
                                                            Short Circuit Capacity (MVA) = N/A                                                                     Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                  B T1T2 = 50                                                  Y T1T2 = 54                               locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                           B T1T2 = 122                                                 Y T1T2 = 122
                                       M1        M3        M5        M7       M15       M17    M2            M4         M6       M8     M16       M18
Allocated Capacity (MW)                10        0          0         0       18.4       0     19.8          0           0        0     18.5      10




                KENT TS DESN2                                         Station may supply
             Thermal Capacity (MW) = 28                            another LDC's territory.
          Short Circuit Capacity (MVA) = 454                        Refer to OPA FIT LDC
                                      M21       M22                locator tool to find LDC.
Allocated Capacity (MW)                0         0


           For any information or inquiries please contact Hydro Ottawa
                                                         *KING EDWARD TS                                                                            Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                             another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                              Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                             JY T3T4 = 7                                        QZ T3T4 = 9                             locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                     JY T3T4 = 132                                      QZ T3T4 = 145
                                For any information or inquiries please contact Hydro Ottawa



                                                   KINGSTON GARDINER TS                                                                            REDDENDALE DS is
                                                    Thermal Capacity (MW) = 121                                                                  downstream of KINGSTON
                                                  Short Circuit Capacity (MVA) = 372                                                                GARDINER TS M11
                                       M3        M7        M8       M9        M10       M11      M12        M13         M14     M15
Allocated Capacity (MW)                10        0          0         0        0        20        0          0           0       0
                                                          KINGSVILLE TS
                                                     Thermal Capacity (MW) = 59
                                                   Short Circuit Capacity (MVA) = 26
                                        M1        M2       M3        M4        M5        M6      M7      M8         M9      M10
Allocated Capacity (MW)                 9.9       0        12         0         0        0       9.9     10         0        0




            KINMOUNT DS                                       KINMOUNT DS is
         Thermal Capacity (MW) = 4                        downstream of MINDEN TS
      Short Circuit Capacity (MVA) = N/A                            M3
                                        F2
Allocated Capacity (MW)                  0




              KINTORE DS                                 KINTORE DS is downstream
         Thermal Capacity (MW) = 4                         of INGERSOLL TS M43
      Short Circuit Capacity (MVA) = N/A
                                        F1
Allocated Capacity (MW)                  0




                   KIRKLAND LAKE TS
                  Thermal Capacity (MW) = 21
              Short Circuit Capacity (MVA) = 955
                                      M61      M62
Allocated Capacity (MW)                0        0            0




              KIRKTON DS                                 KIRKTON DS is downstream
         Thermal Capacity (MW) = 4                         of INGERSOLL TS M43
      Short Circuit Capacity (MVA) = N/A
                                        F1
Allocated Capacity (MW)                0.3




                                KLEINBURG TS 27.6 KV                                                      Station may supply
                                 Thermal Capacity (MW) = 0                                             another LDC's territory.
                               Short Circuit Capacity (MVA) = 0                                         Refer to OPA FIT LDC
                                      M3        M4        M5         M6        M7        M8            locator tool to find LDC.
Allocated Capacity (MW)                0         0         0         0         0         0




                                   KLEINBURG TS 44 KV                                                     Station may supply       SCHOMBERG DS is
                                Thermal Capacity (MW) = 18                                             another LDC's territory. downstream of KLEINBURG
                              Short Circuit Capacity (MVA) = 578                                        Refer to OPA FIT LDC             TS M24
                                      M23       M24       M25        M26       M27      M28            locator tool to find LDC.
Allocated Capacity (MW)                 0         0        0         0.3        0        0




             LAFOREST ROAD DS
             Thermal Capacity (MW) = 5
          Short Circuit Capacity (MVA) = 516
                                       F1         F2
Allocated Capacity (MW)                14         0




                                                                   LAKE TS DESN 1                                                                                 Station may supply
                                                                Thermal Capacity (MW) = 0                                                                      another LDC's territory.
                                                              Short Circuit Capacity (MVA) = 0                                                                  Refer to OPA FIT LDC
                                        M31      M32       M33       M41       M42      M43      M71     M72       M73      M81      M82       M83             locator tool to find LDC.
Allocated Capacity (MW)                  0        0         0         0         0         0       0       0         0        0        0         0




                                                                   LAKE TS DESN 2                                                                                 Station may supply
                                                          Thermal Capacity (MW) = Sum of Buses                                                                 another LDC's territory.
                                                            Short Circuit Capacity (MVA) = N/A                                                                  Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                     J1J2 = 6                                               Q1Q2 = 7                                  locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                             J1J2 = 36                                              Q1Q2 = 36
                                        M31      M32      M33        M41      M42       M43    M71       M72       M73     M81       M82       M83
Allocated Capacity (MW)                  0        0         0          0        0        0      0         0         0        0        0         0




                                   LAMBTON TS
                             Thermal Capacity (MW) = 80
                          Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                      D T5 = 60              Y T6 = 20
Short Circuit Bus Capacity (MVA)              D T5 = 377              Y T6 = 377
                                        M1        M3       M5        M2       M4
Allocated Capacity (MW)                  0         20       20       0         0




                LARCHWOOD TS
             Thermal Capacity (MW) = 13
          Short Circuit Capacity (MVA) = 1285
                                       M3         M4
Allocated Capacity (MW)                 0         0




                                               LAUZON TS DESN1                                                               Station may supply
                                           Thermal Capacity (MW) = 64                                                     another LDC's territory.
                                         Short Circuit Capacity (MVA) = 31                                                 Refer to OPA FIT LDC
                                        M1       M2        M3        M4        M5        M6      M7      M8               locator tool to find LDC.
Allocated Capacity (MW)                 0         0         0         0        0         0       0       0




                                         LAUZON TS DESN2                                                             Station may supply
                                        Thermal Capacity (MW) = 62                                                another LDC's territory.
                                      Short Circuit Capacity (MVA) = 71                                            Refer to OPA FIT LDC
                                        M23        M24       M25      M26      M27      M28      M29              locator tool to find LDC.
Allocated Capacity (MW)                  0          10         0        1       0        0       11


          For any information or inquiries please contact Toronto Hydro
                                                       *LEASIDE TS DESN 1                                                                        Station may supply
                                                      Thermal Capacity (MW) = 9                                                               another LDC's territory.
                                                    Short Circuit Capacity (MVA) = 16                                                          Refer to OPA FIT LDC
                               For any information or inquiries please contact Toronto Hydro                                                  locator tool to find LDC.



                                              LEASIDE TS DESN 2                                                              Station may supply
                                           Thermal Capacity (MW) = 5                                                      another LDC's territory.
                                         Short Circuit Capacity (MVA) = 66                                                 Refer to OPA FIT LDC
                                        M1       M2        M3        M4        M5        M6      M7      M8               locator tool to find LDC.
Allocated Capacity (MW)                 0         0         0         0        0         0       0       0


          For any information or inquiries please contact Toronto Hydro
                                                         *LESLIE TS DESN                                                                         Station may supply
                                                 Thermal Capacity (MW) = Sum of Buses                                                         another LDC's territory.
                                                   Short Circuit Capacity (MVA) = N/A                                                          Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                 H1 = 0                                        H2 = 0                                locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                        H1 = 251                                       H2 = 248
                               For any information or inquiries please contact Toronto Hydro



                                          LESLIE TS DESN 1                                                           Station may supply
                                   Thermal Capacity (MW) = Sum of Buses                                           another LDC's territory.
                                      Short Circuit Capacity (MVA) = 0                                             Refer to OPA FIT LDC
                                        M2         M3        M4        M5      M6        M7      M8               locator tool to find LDC.
Allocated Capacity (MW)                  0          0         0        0       0         0       0




                                                                   LESLIE TS DESN 2                                                                               Station may supply
                                                          Thermal Capacity (MW) = Sum of Buses                                                                 another LDC's territory.
                                                            Short Circuit Capacity (MVA) = N/A                                                                  Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                     J = 11                                                   Q=7                                     locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                              J = 95                                                  Q = 80
                                        M21      M23      M25       M27       M29       M31    M22       M24       M26      M28      M30       M32
Allocated Capacity (MW)                  0        0         0         0         0        0      0         0         0        0        0         0
          For any information or inquiries please contact Hydro Ottawa
                                                      *LINCOLN HEIGHTS TS                                                                    Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                      another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                       Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                B=0                                             Y=3                              locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                        B = 152                                         Y = 151
                               For any information or inquiries please contact Hydro Ottawa



                                       LINDSAY TS                                                          COBOCONK DS is
                                 Thermal Capacity (MW) = 87                                             downstream of LINDSAY TS
                              Short Circuit Capacity (MVA) = N/A                                                   M7
Thermal Bus Capacity (MW)                      T2 = 74                      T1 = 70
Short Circuit Bus Capacity (MVA)              T2 = 1007                    T1 = 1003
                                       M4        M6       M8         M3       M5        M7
Allocated Capacity (MW)                10       18.5       0         0         0        18.5


          For any information or inquiries please contact Hydro Ottawa
                                                           *LISGAR TS                                                                        Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                      another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                       Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                JY = 0                                         QZ = 9                            locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                        JY = 87                                        QZ = 158
                               For any information or inquiries please contact Hydro Ottawa



                          LODGEROOM DS
                       Thermal Capacity (MW) = 11
                    Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                  T2 = 7             T1 = 8
Short Circuit Bus Capacity (MVA)          T2 = 412           T1 = 409
                                       F1         F2       F3        F4
Allocated Capacity (MW)                 0         0        0         0




                  LONGLAC TS
             Thermal Capacity (MW) = 4
          Short Circuit Capacity (MVA) = 1340
                                       M1        M2
Allocated Capacity (MW)                9.8       0




                           LONGUEUIL TS                                                 GLEN SANDFIELD DS is     PLANTAGENET DS is         STARDALE DS is
                      Thermal Capacity (MW) = 61                                       downstream of LONGUEUIL downstream of LONGUEUIL downstream of LONGUEUIL
                    Short Circuit Capacity (MVA) = 827                                          TS M23                  TS M26                  TS M23
                                      M23       M24       M25       M26
Allocated Capacity (MW)               30.7       20        0        0.2




                          LONGWOOD TS
                       Thermal Capacity (MW) = 0
                     Short Circuit Capacity (MVA) = 0
                                      M23      M24        M25       M26
Allocated Capacity (MW)                0         0        10         0




                                                         LORNE PARK TS                                                                       Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                      another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                       Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                B = 11                                          J = 11                           locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                        B = 120                                         J = 120
                                      M1         M3        M5       M7        M9     M2          M4        M6      M8      M10
Allocated Capacity (MW)               0           0         0         0        0     0           0          0      0        0


          For any information or inquiries please contact Toronto Hydro
                                                             *MAIN TS                                                                        Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                      another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                       Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                              A1A2 = 8                                        A3A4 = 9                           locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                      A1A2 = 71                                        A3A4 = 68
                               For any information or inquiries please contact Toronto Hydro



                                                 MALVERN TS                                                                 Station may supply
                                     Thermal Capacity (MW) = Sum of Buses                                                another LDC's territory.
                                       Short Circuit Capacity (MVA) = N/A                                                 Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                           J = 11                                 Q = 10                        locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                   J = 109                                 Q = 108
                                     M21       M31        M33      M35    M22           M32      M34     M36
Allocated Capacity (MW)                0         0         0        0      0             0         0      0




                                   MANBY TS DESN 1                                                         Station may supply
                                Thermal Capacity (MW) = 34                                              another LDC's territory.
                              Short Circuit Capacity (MVA) = 147                                         Refer to OPA FIT LDC
                                       M1       M3        M5         M7       M9        M12             locator tool to find LDC.
Allocated Capacity (MW)                 0         0        0         0        0          0




                                   MANBY TS DESN 2                                                         Station may supply
                                Thermal Capacity (MW) = 35                                              another LDC's territory.
                              Short Circuit Capacity (MVA) = 146                                         Refer to OPA FIT LDC
                                      M13       M16       M17       M20      M21        M24             locator tool to find LDC.
Allocated Capacity (MW)                 0         0        0         0        0          0




                                               MANBY TS DESN 3                                                              Station may supply
                                         Thermal Capacity (MW) = 75                                                      another LDC's territory.
                                       Short Circuit Capacity (MVA) = 42                                                  Refer to OPA FIT LDC
                                      M4       M6        M8       M10        M23        M25     M27      M29             locator tool to find LDC.
Allocated Capacity (MW)               0         0         0         0         0          0       0        0




                MANITOULIN TS
              Thermal Capacity (MW) = 23
           Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)            T4 = 26 T3 = 23
Short Circuit Bus Capacity (MVA) T4 = 1285T3 = 1272
                                       M26    M25
Allocated Capacity (MW)                 10     8.1




        MANITOUWADGE DS
         Thermal Capacity (MW) = 3
      Short Circuit Capacity (MVA) = 418
                                       F3
Allocated Capacity (MW)                 0




                  MANITOUWADGE TS                                             Station may supply
                  Thermal Capacity (MW) = 11                               another LDC's territory.
              Short Circuit Capacity (MVA) = 1278                           Refer to OPA FIT LDC
                                       M1       M2         M3              locator tool to find LDC.
Allocated Capacity (MW)                0       15.6        0




                           MANOTICK DS
                        Thermal Capacity (MW) = 7
                    Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                  T1 = 7             T2 = 5
Short Circuit Bus Capacity (MVA)          T1 = 410           T2 = 414
                                       F1         F2       F4        F5
Allocated Capacity (MW)                 0         0        0         0




                 MARATHON DS
             Thermal Capacity (MW) = 4
          Short Circuit Capacity (MVA) = 683
                                       F2        F3
Allocated Capacity (MW)                0         0
                        MARGACH DS
                   Thermal Capacity (MW) = 5
              Short Circuit Capacity (MVA) = 687
                                       F1      F2            F3
Allocated Capacity (MW)                0       2.6           0




                MARIONVILLE DS
             Thermal Capacity (MW) = 16
          Short Circuit Capacity (MVA) = 637
                                       F1         F2
Allocated Capacity (MW)                0          0




                                          MARTINDALE TS                                                                   Station may supply
                                      Thermal Capacity (MW) = 76                                                       another LDC's territory.
                                    Short Circuit Capacity (MVA) = 303                                                  Refer to OPA FIT LDC
                                       M1         M2        M3       M4          M5         M6       M7                locator tool to find LDC.
Allocated Capacity (MW)                 0          0         0       1.6         0          0        0




                    MASSEY DS
             Thermal Capacity (MW) = 4
          Short Circuit Capacity (MVA) = 418
                                       F1         F3
Allocated Capacity (MW)                0          0




                   MAZINAW DS
             Thermal Capacity (MW) = 4
          Short Circuit Capacity (MVA) = 408
                                       F1         F2
Allocated Capacity (MW)                0          0




                                    MEADOWVALE TS                                                                 Station may supply
                                 Thermal Capacity (MW) = 129                                                   another LDC's territory.
                               Short Circuit Capacity (MVA) = 333                                               Refer to OPA FIT LDC
                                        M3       M4        M5          M6        M7         M8                 locator tool to find LDC.
Allocated Capacity (MW)                  0         0        0          0         0          0




                   MEAFORD TS
             Thermal Capacity (MW) = 28
          Short Circuit Capacity (MVA) = 989
                                      M1          M2
Allocated Capacity (MW)               9.9         0




                                             MIDHURST TS - DESN 1                                                                  Station may supply
                                           Thermal Capacity (MW) = 119                                                          another LDC's territory.
                                         Short Circuit Capacity (MVA) = 367                                                      Refer to OPA FIT LDC
                                        M3        M4       M5        M6          M7         M8       M9         M10             locator tool to find LDC.
Allocated Capacity (MW)                 20         0        10        0          0          0        9.5         0




                                             MIDHURST TS - DESN 2                                                                  Station may supply
                                           Thermal Capacity (MW) = 71                                                           another LDC's territory.
                                        Short Circuit Capacity (MVA) = 408                                                       Refer to OPA FIT LDC
                                       M21      M22       M23       M24         M25        M26      M27         M28             locator tool to find LDC.
Allocated Capacity (MW)                 0         0         0        0           0          0        0           0




              MILFORD DS                                  MILFORD DS is downstream
         Thermal Capacity (MW) = 2                            of PICTON TS M5
      Short Circuit Capacity (MVA) = N/A
                                        F2
Allocated Capacity (MW)                0.1




                     MINAKI DS
             Thermal Capacity (MW) = 6
           Short Circuit Capacity (MVA) = 0
                                      F1          F2
Allocated Capacity (MW)                0          0




                               MINDEN TS                                                      KINMOUNT DS is
                  Thermal Capacity (MW) = Sum of Buses                                    downstream of MINDEN TS
                    Short Circuit Capacity (MVA) = N/A                                              M3
Thermal Bus Capacity (MW)                  T1 = 3         T2 = 8
Short Circuit Bus Capacity (MVA)         T1 = 1146      T2 = 1143
                                      M1          M3   M2        M4
Allocated Capacity (MW)                 0         0    0         0


r any information or inquiries please contact Blue Water Power Distribution Corporation
                                                       *MODELAND TS                                                                           Station may supply
                                             Thermal Capacity (MW) = Sum of Buses                                                          another LDC's territory.
                                               Short Circuit Capacity (MVA) = N/A                                                           Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                   J = 40                                         Q = 22                          locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                           J = 100                                         Q = 97
           For any information or inquiries please contact Blue Water Power Distribution Corporation



                                                                  MOHAWK TS                                                                                    Station may supply
                                                      Thermal Capacity (MW) = Sum of Buses                                                                  another LDC's territory.
                                                        Short Circuit Capacity (MVA) = N/A                                                                   Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                 B=8                                                       Y=7                                     locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                         B = 120                                                   Y = 126
                                       M52        M53      M62        M63       M64      M71        M72         M73      M81      M82       M83
Allocated Capacity (MW)                 0          0        0          0         0         0         0           0         0       0         0




                   MONTEITH DS
             Thermal Capacity (MW) = 7
          Short Circuit Capacity (MVA) = 404
                                       F1         F2
Allocated Capacity (MW)                0          0


        For any information or inquiries please contact Atikokan Hydro Inc
                          *MOOSE LAKE TS                                                     Station may supply
                        Thermal Capacity (MW) = 6                                         another LDC's territory.
                    Short Circuit Capacity (MVA) = N/A                                     Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                  T2 = 5              T3 = 10                    locator tool to find LDC.
Short Circuit Bus Capacity (MVA)         T2 = 1334            T3 = 1282
For any information or inquiries please contact Atikokan Hydro In



                       MOOSONEE DS
                  Thermal Capacity (MW) = 10
              Short Circuit Capacity (MVA) = 674
                                       F1      F2            F3
Allocated Capacity (MW)                0        0            0




                     MORRISBURG TS
                  Thermal Capacity (MW) = 58
              Short Circuit Capacity (MVA) = 748
                                      M23      M25          M26
Allocated Capacity (MW)                0        0            0




             MOUNTAIN CHUTE DS
             Thermal Capacity (MW) = 2
          Short Circuit Capacity (MVA) = 441
                                       F1         F2
Allocated Capacity (MW)                0          0
                                                  MURILLO DS
                                          Thermal Capacity (MW) = 0
                                       Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                           T1 = 0                                T2 = 0
Short Circuit Bus Capacity (MVA)                   T1 = 606                              T2 = 544
                                      F1        F3         F5       F7         F2      F4        F6     F8
Allocated Capacity (MW)               0          0         0        0          0       0         0      0




                                                                  MURRAY TS DESN 1                                                                            Station may supply
                                                          Thermal Capacity (MW) = Sum of Buses                                                             another LDC's territory.
                                                            Short Circuit Capacity (MVA) = N/A                                                              Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                     QZ = 0                                              Y1Y2 = 9                                 locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                              QZ = 0                                             Y1Y2 = 93
                                     M51         M52      M53       M54       M55       M56    M25     M26      M27     M28        M29     M30
Allocated Capacity (MW)               0           0         0         0         0        0      0       0        0        0         0       0




                                            MURRAY TS DESN 2                                                              Station may supply
                                     Thermal Capacity (MW) = Sum of Buses                                              another LDC's territory.
                                       Short Circuit Capacity (MVA) = N/A                                               Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                     J=1                                     K=8                              locator tool to find LDC.
Short Circuit Bus Capacity (MVA)             J = 122                                 K = 122
                                     M10       M11       M13       M14    M15         M16      M17     M18
Allocated Capacity (MW)                0         0         0        0      0            0       0       0




                                                       MUSKOKA TS                                                                 SUNDRIDGE NORTH DS is
                                                 Thermal Capacity (MW) = 70                                                        downstream of MUSKOKA
                                               Short Circuit Capacity (MVA) = 382                                                           TS M2
                                      M1          M2         M3        M4       M5     M6       M7      M8       M9
Allocated Capacity (MW)               10           0          0         0        0     0        0       0        0




                            NAPANEE TS
                       Thermal Capacity (MW) = 67
                    Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                B T1 = 53           Y T2 = 54
Short Circuit Bus Capacity (MVA)        B T1 = 977          Y T2 = 972
                                      M1         M3        M2        M4
Allocated Capacity (MW)                 0        8.5       28.5       0




                   NAVAN DS DESN 1
                   Thermal Capacity (MW) = 3
              Short Circuit Capacity (MVA) = 425
                                       F1      F2           F3
Allocated Capacity (MW)                0        0           0




          NAVAN DS DESN 2
         Thermal Capacity (MW) = 8
      Short Circuit Capacity (MVA) = 624
                                       F4
Allocated Capacity (MW)                 0




                                    NEBO TS DESN 1                                                       Station may supply
                                Thermal Capacity (MW) = 63                                            another LDC's territory.
                               Short Circuit Capacity (MVA) = 0                                        Refer to OPA FIT LDC
                                      M3        M4        M5         M6        M7      M8             locator tool to find LDC.
Allocated Capacity (MW)                0         0        3.2        0         0       0




                                                NEBO TS DESN2                                                             Station may supply
                                         Thermal Capacity (MW) = 9                                                     another LDC's territory.
                                       Short Circuit Capacity (MVA) = 48                                                Refer to OPA FIT LDC
                                     M51      M52       M53       M54         M61     M62      M63     M64             locator tool to find LDC.
Allocated Capacity (MW)               0         0         0         0          0       0        0       0




                                   NELSON TS DESN 1                                                      Station may supply
                               Thermal Capacity (MW) = 23                                             another LDC's territory.
                             Short Circuit Capacity (MVA) = 169                                        Refer to OPA FIT LDC
                                      M1       M2        M3          M4        M5      M6             locator tool to find LDC.
Allocated Capacity (MW)                0         0        0          0         0       0




                                                                  NELSON TS DESN 2                                                                            Station may supply
                                                          Thermal Capacity (MW) = Sum of Buses                                                             another LDC's territory.
                                                            Short Circuit Capacity (MVA) = N/A                                                              Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                     PK = 5                                               YJ = 5                                  locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                              PK = 65                                              YJ = 90
                                     M31         M32      M33       M34       M35       M36    M11     M12      M13      M14       M15     M16
Allocated Capacity (MW)               0           0         0         0         0        0      0       0        0         0        0       0


        For any information or inquiries please contact Ottawa Hydro Inc
                                      *NEPEAN TS                                                         Station may supply
                               Thermal Capacity (MW) = 101                                            another LDC's territory.
                             Short Circuit Capacity (MVA) = 398                                        Refer to OPA FIT LDC
         For any information or inquiries please contact Ottawa Hydro Inc.                            locator tool to find LDC.



              NESTOR FALLS DS
             Thermal Capacity (MW) = 2
          Short Circuit Capacity (MVA) = 445
                                       F1         F2
Allocated Capacity (MW)                0          0




                NEWINGTON DS
             Thermal Capacity (MW) = 8
          Short Circuit Capacity (MVA) = 621
                                       F1         F2
Allocated Capacity (MW)                0          0




                                                            NEWTON TS                                                                       Station may supply
                                                 Thermal Capacity (MW) = Sum of Buses                                                    another LDC's territory.
                                                   Short Circuit Capacity (MVA) = N/A                                                     Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                 B=5                                          Y=5                               locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                          B=3                                          Y=4
                                      M1          M3        M6       M8        M10    M2        M4      M5       M7       M9
Allocated Capacity (MW)               0            0         0         0        0     0         0       0        0        0




                   NIPIGON DS
             Thermal Capacity (MW) = 2
          Short Circuit Capacity (MVA) = 441
                                       F1         F2
Allocated Capacity (MW)                0          0




                                      NORFOLK TS                                                         Station may supply
                               Thermal Capacity (MW) = 56                                             another LDC's territory.
                             Short Circuit Capacity (MVA) = 462                                        Refer to OPA FIT LDC
                                      M1       M2        M3          M4       M5       M6             locator tool to find LDC.
Allocated Capacity (MW)                0         0       18.4        0        17.5     0




                 NORTH BAY TS                                         Station may supply
             Thermal Capacity (MW) = 15                            another LDC's territory.
          Short Circuit Capacity (MVA) = 515                        Refer to OPA FIT LDC
                                      M1          M3               locator tool to find LDC.
Allocated Capacity (MW)                10         0
               NORTH SHORE DS
             Thermal Capacity (MW) = 1
          Short Circuit Capacity (MVA) = 684
                                       F1       F2
Allocated Capacity (MW)                0        0




                    NORTHBROOK DS
                   Thermal Capacity (MW) = 8
              Short Circuit Capacity (MVA) = 411
                                       F1      F2           F3
Allocated Capacity (MW)                0        0           0




           NORTHCOTE DS                                      NORTHCOTE DS is
         Thermal Capacity (MW) = 4                        downstream of COBDEN TS
      Short Circuit Capacity (MVA) = N/A                             M2
                                        F3
Allocated Capacity (MW)                1.3




                                                           OAKVILLE TS
                                               Thermal Capacity (MW) = Sum of Buses
                                                 Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                               E = 11                                        Z = 11
Short Circuit Bus Capacity (MVA)                       E = 123                                        Z = 115
                                      M43      M45       M47       M49       M51    M44       M46      M48        M50      M52
Allocated Capacity (MW)                0         0         0         0        0      0         0         0         0        0




              ORANGEVILLE TS 27.6 KV - DESN1
                       Thermal Capacity (MW) = 53
                     Short Circuit Capacity (MVA) = 91
                                      M23       M24        M25     M26
Allocated Capacity (MW)                 0         0         9       0




     ORANGEVILLE TS 44 KV - DESN1
             Thermal Capacity (MW) = 34
          Short Circuit Capacity (MVA) = 743
                                      M45       M46
Allocated Capacity (MW)               9.9        0




                              ORANGEVILLE TS DESN2
                                Thermal Capacity (MW) = 68
                              Short Circuit Capacity (MVA) = 532
                                       M1       M2        M3        M4      M5        M6
Allocated Capacity (MW)                 0        10        0        0       0         0




                                                 ORILLIA TS
                                          Thermal Capacity (MW) = 88
                                       Short Circuit Capacity (MVA) = 382
                                      M1        M2       M3        M4       M5        M6       M7       M8
Allocated Capacity (MW)               1.1       2.8       10        0       0         10       0        0




                                                                                                     OSHAWA G.M. TS                                                                                             Station may supply
                                                                                                   Thermal Capacity (MW) = 0                                                                                 another LDC's territory.
                                                                                                Short Circuit Capacity (MVA) = N/A                                                                            Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                                      AB = 9                                                                                    CD = 9                              locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                                              AB = 475                                                                                 CD = 103
                                       A6       A7          A8      A9      A10      A11      A12       A13       A14      A15       B5      B6      B7       B8      B9       B10   B11   B12   B13   B14
Allocated Capacity (MW)                0        0           0       0        0        0        0         0         0        0        0       0       0        0       0         0     0     0     0     0




                           OTONABEE TS DESN 1                                                  Station may supply
                      Thermal Capacity (MW) = Sum of Buses                                  another LDC's territory.
                          Short Circuit Capacity (MVA) = N/A                                 Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                         J=5                  Q=8                  locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                J = 411               Q = 431
                                        M8        M12      M10      M9      M11
Allocated Capacity (MW)                  0         0         0      0         0




                      OTONABEE TS DESN 2                                               Station may supply
                  Thermal Capacity (MW) = Sum of Buses                              another LDC's territory.
                    Short Circuit Capacity (MVA) = N/A                               Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                   Y=6            B=6                      locator tool to find LDC.
Short Circuit Bus Capacity (MVA)          Y = 1071       B = 1050
                                      M26        M28   M25      M27
Allocated Capacity (MW)                 0         0     0       25.6


          For any information or inquiries please contact Hydro Ottawa
                                                          *OVERBROOK TS                                                                      Station may supply
                                               Thermal Capacity (MW) = Sum of Buses                                                       another LDC's territory.
                                                 Short Circuit Capacity (MVA) = N/A                                                        Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                J=9                                          Q=9                                 locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                        J = 83                                        Q = 78
                                For any information or inquiries please contact Hydro Ottawa



                                        OWEN SOUND TS                                                           SQUIRE DS is downstream
                                     Thermal Capacity (MW) = 105                                                of OWEN SOUND TS M25
                                   Short Circuit Capacity (MVA) = 519
                                     M21         M22       M23      M24     M25       M26     M28
Allocated Capacity (MW)                0          0         0        0      0.1        0       0




                                                PALERMO TS                                                                  Station may supply
                                          Thermal Capacity (MW) = 0                                                      another LDC's territory.
                                        Short Circuit Capacity (MVA) = 0                                                  Refer to OPA FIT LDC
                                      M1       M2        M3        M4       M5        M6       M7       M8               locator tool to find LDC.
Allocated Capacity (MW)               4         0         0         0       0         0        0        0




                          PALMERSTON TS                                                KENILWORTH DS is
                                                                                                                ROTHSAY DS is downstream TRALEE DS is downstream
                       Thermal Capacity (MW) = 56                                        downstream of
                                                                                                                 of PALMERSTON TS M2      of PALMERSTON TS M3
                    Short Circuit Capacity (MVA) = 1080                               PALMERSTON TS M2
                                       M1        M2         M3      M4
Allocated Capacity (MW)                  0        0         9       0




                          PARRY SOUND TS
                      Thermal Capacity (MW) = 36
                    Short Circuit Capacity (MVA) = 963
                                      M1        M2          M3      M4
Allocated Capacity (MW)                 0        0          0       0




                      PEMBROKE TS
                  Thermal Capacity (MW) = 15
              Short Circuit Capacity (MVA) = 1131
                                       M1       M2          M3
Allocated Capacity (MW)                0        0           0




             PERRAULT FALLS DS
             Thermal Capacity (MW) = 1
          Short Circuit Capacity (MVA) = 463
                                       F1       F2
Allocated Capacity (MW)                0        0
                                PETAWAWA DS
                             Thermal Capacity (MW) = 5
                          Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                        T1 = 5                  T2 = 4
Short Circuit Bus Capacity (MVA)               T1 = 424                 T2 = 425
                                         F1        F4       F5        F2        F3
Allocated Capacity (MW)                  0         0         0        0         0




                       PIC DS
             Thermal Capacity (MW) = 8
          Short Circuit Capacity (MVA) = 689
                                       F1        F2
Allocated Capacity (MW)                0         0




               PICTON DS                                 PICTON DS is downstream of
         Thermal Capacity (MW) = 3                            PICTON TS M6
      Short Circuit Capacity (MVA) = N/A
                                        F2
Allocated Capacity (MW)                  0




                              PICTON TS                                               MILFORD DS is downstream PICTON DS is downstream of
                      Thermal Capacity (MW) = 57                                          of PICTON TS M5           PICTON TS M6
                    Short Circuit Capacity (MVA) = 599
                                      M5        M6         M7         M8
Allocated Capacity (MW)               0.1        0         0          0




          PLANTAGENET DS                                   PLANTAGENET DS is
         Thermal Capacity (MW) = 4                       downstream of LONGUEUIL
      Short Circuit Capacity (MVA) = N/A                          TS M26
                                        F2
Allocated Capacity (MW)                0.2




                                                                           PLEASANT TS DESN 2                                                                                   Station may supply
                                                                     Thermal Capacity (MW) = Sum of Buses                                                                    another LDC's territory.
                                                                       Short Circuit Capacity (MVA) = N/A                                                                     Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                                BY = 42                                                        EZ = 57                              locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                                        BY = 125                                                       EZ = 126
                                       M7        M8        M9        M10       M11       M12       M13    M14      M43      M44      M45      M46     M47    M48
Allocated Capacity (MW)                0         0         0           0         0         0        0      0        0        0        0         0      0      0




                                                                  PLEASANT TS DESN 3                                                                           Station may supply
                                                          Thermal Capacity (MW) = Sum of Buses                                                              another LDC's territory.
                                                            Short Circuit Capacity (MVA) = N/A                                                               Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                      F=2                                                     V=3                                  locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                              F = 113                                                 V = 116
                                      M61       M63       M65       M67       M69       M71    M62       M64       M66      M68      M70      M72
Allocated Capacity (MW)                0         0          0         0         0        0      0         0         0         0       0        0




                                             PLEASANT TS DESN1                                                               Station may supply
                                          Thermal Capacity (MW) = 101                                                     another LDC's territory.
                                       Short Circuit Capacity (MVA) = 353                                                  Refer to OPA FIT LDC
                                      M21      M22       M23       M24        M25      M26      M27      M28              locator tool to find LDC.
Allocated Capacity (MW)                0         0        10        0          0        0        0        0




                                      PORT ARTHUR TS #1                                                              Station may supply
                                     Thermal Capacity (MW) = 10                                                   another LDC's territory.
                                   Short Circuit Capacity (MVA) = 363                                              Refer to OPA FIT LDC
                                      M2         M3        M4       M5         M6       M1      M27               locator tool to find LDC.
Allocated Capacity (MW)                0          0         0       10         0        0        0




          PORT BOLSTER DS                                  PORT BOLSTER DS is
         Thermal Capacity (MW) = 4                       downstream of BEAVERTON
      Short Circuit Capacity (MVA) = N/A                          TS M27
                                        F2
Allocated Capacity (MW)                0.1




                        PORT COLBORNE TS                                                 Station may supply
                      Thermal Capacity (MW) = 34                                      another LDC's territory.
                    Short Circuit Capacity (MVA) = 267                                 Refer to OPA FIT LDC
                                      M9        M10        M11       M12              locator tool to find LDC.
Allocated Capacity (MW)                 0        0         12.8      10




                      PORT HOPE TS DESN 1
                      Thermal Capacity (MW) = 50
                    Short Circuit Capacity (MVA) = 838
                                      M15       M16        M17       M18
Allocated Capacity (MW)                 0        0          0         0




                      PORT HOPE TS DESN 2
                      Thermal Capacity (MW) = 67
                    Short Circuit Capacity (MVA) = 881
                                      M1        M2         M3         M4
Allocated Capacity (MW)                 0        0         0          10


or any information or inquiries please contact Cambridge North Dumfries Hydro (CND)
                                                *PRESTON TS                                                                  Station may supply
                                      Thermal Capacity (MW) = Sum of Buses                                                another LDC's territory.
                                        Short Circuit Capacity (MVA) = N/A                                                 Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                            J = 10                                Q=9                            locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                    J = 141                               Q = 124
       For any information or inquiries please contact Cambridge North Dumfries Hydro (CND)



                       PUSLINCH DS
                   Thermal Capacity (MW) = 21
                Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)             T1 = 15        T2 = 16
Short Circuit Bus Capacity (MVA)     T1 = 624       T2 = 625
                                         F1       F2        F4
Allocated Capacity (MW)                  0        18         0




                   RAMORE TS
             Thermal Capacity (MW) = 9
          Short Circuit Capacity (MVA) = 653
                                      M3         M5
Allocated Capacity (MW)                0         0




                       RED LAKE TS
                  Thermal Capacity (MW) = 40
              Short Circuit Capacity (MVA) = 1232
                                       M3       M4         M6
Allocated Capacity (MW)                0        10         10




                       RED ROCK DS
                   Thermal Capacity (MW) = 4
              Short Circuit Capacity (MVA) = 415
                                       F1      F2           F3
Allocated Capacity (MW)                0        0           0




           REDDENDALE DS                                    REDDENDALE DS is
         Thermal Capacity (MW) = 3                        downstream of KINGSTON
      Short Circuit Capacity (MVA) = N/A                     GARDINER TS M11
                                        F3
Allocated Capacity (MW)                  0
         REID CORNERS DS                                   REID CORNERS DS is
         Thermal Capacity (MW) = 2                        downstream of DOUGLAS
      Short Circuit Capacity (MVA) = N/A                       POINT TS M6
                                        F1
Allocated Capacity (MW)                0.3




                                                                     REXDALE TS                                                                                Station may supply
                                                          Thermal Capacity (MW) = Sum of Buses                                                              another LDC's territory.
                                                            Short Circuit Capacity (MVA) = N/A                                                               Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                     BY = 54                                                 QJ = 48                               locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                              BY = 78                                                 QJ = 73
                                      M31       M32       M33       M34       M35       M36    M1          M2       M3       M4      M5       M6
Allocated Capacity (MW)                0         0          0         0         0        0     0           0        0         0      0        0




                      RICHMOND DS                                               Station may supply
                   Thermal Capacity (MW) = 4                                 another LDC's territory.
              Short Circuit Capacity (MVA) = 404                              Refer to OPA FIT LDC
                                       F1      F2          F3                locator tool to find LDC.
Allocated Capacity (MW)                0        0          0




                                             RICHVIEW TS DESN 1                                                              Station may supply
                                      Thermal Capacity (MW) = Sum of Buses                                                another LDC's territory.
                                        Short Circuit Capacity (MVA) = N/A                                                 Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                            J = 11                               E = 11                          locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                     J = 80                               E = 74
                                      M12       M14        M16      M18    M11         M13      M15        M17
Allocated Capacity (MW)                 0         0         0        0      0           0        0          0




                                             RICHVIEW TS DESN 2                                                              Station may supply
                                          Thermal Capacity (MW) = 0                                                       another LDC's territory.
                                       Short Circuit Capacity (MVA) = N/A                                                  Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                          Q = 11                                 Z = 11                          locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                   Q = 80                                 Z = 74
                                      M41      M43       M45       M47        M42      M44      M46        M48
Allocated Capacity (MW)                0         0         0        0          0        0        0          0




                                             RICHVIEW TS DESN 3                                                              Station may supply
                                           Thermal Capacity (MW) = 0                                                      another LDC's territory.
                                         Short Circuit Capacity (MVA) = 0                                                  Refer to OPA FIT LDC
                                       M1       M2        M3        M4         M5       M6       M7        M8             locator tool to find LDC.
Allocated Capacity (MW)                0         0         0         0         0        0        0         0


           For any information or inquiries please contact Hydro Ottawa
                                                         *RIVERDALE TS                                                                        Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                       another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                        Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                JY = 13                                         QZ = 11                           locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                        JY = 142                                         QZ = 143
                                For any information or inquiries please contact Hydro Ottawa



                      ROCKLAND DS
                   Thermal Capacity (MW) = 8
              Short Circuit Capacity (MVA) = 402
                                       F1      F2          F3
Allocated Capacity (MW)                0        0          0




                       ROCKLAND EAST DS
                        Thermal Capacity (MW) = 7
                    Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                      T1 = 6              T2 = 6
Short Circuit Bus Capacity (MVA)              T1 = 417            T2 = 418
                                       F4        F5        F6        F1
Allocated Capacity (MW)                 0        0         0         0




             ROTHSAY DS                                  ROTHSAY DS is downstream
         Thermal Capacity (MW) = 4                        of PALMERSTON TS M2
      Short Circuit Capacity (MVA) = N/A
                                        F3
Allocated Capacity (MW)                  0




                                               RUNNYMEDE TS                                                                  Station may supply
                                          Thermal Capacity (MW) = 75                                                      another LDC's territory.
                                        Short Circuit Capacity (MVA) = 51                                                  Refer to OPA FIT LDC
                                       M1       M2        M3        M4         M5       M6       M7        M8             locator tool to find LDC.
Allocated Capacity (MW)                0         0         0         0         0        0        0         0




                             RUSSELL DS
                       Thermal Capacity (MW) = 2
                    Short Circuit Capacity (MVA) = 412
                                       F1        F2        F3        F4
Allocated Capacity (MW)                 0        0         0         0


           For any information or inquiries please contact Hydro Ottawa
                                                           *RUSSELL TS                                                                        Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                       another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                        Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                BY = 9                                           QZ = 8                           locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                       BY = 168                                          QZ = 168
                                For any information or inquiries please contact Hydro Ottawa



                            SAM LAKE DS
                      Thermal Capacity (MW) = 18
                    Short Circuit Capacity (MVA) = 592
                                       F1        F2        F3        F4
Allocated Capacity (MW)                 0        0         0         0




                   SAPAWE DS
             Thermal Capacity (MW) = 2
          Short Circuit Capacity (MVA) = 415
                                       F1        F2
Allocated Capacity (MW)                0         0




                                                                SCARBORO TS -DESN1                                                                             Station may supply
                                                          Thermal Capacity (MW) = Sum of Buses                                                              another LDC's territory.
                                                            Short Circuit Capacity (MVA) = N/A                                                               Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                      J = 11                                                  Q = 11                               locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                              J = 110                                                  Q = 107
                                      M21       M23       M25        M27      M29       M31    M22         M24      M26      M28    M30      M32
Allocated Capacity (MW)                0         0          0         0         0        0      0           0        0         0     0        0




                                                      SCARBORO TS -DESN2                                                                      Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                       another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                        Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                B=4                                             Y = 11                            locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                        B = 128                                          Y = 128
                                       M1        M3        M5       M7        M9     M2          M4        M6       M8      M10
Allocated Capacity (MW)                0          0         0         0        0     0           0          0       0        0




                SCHOMBERG DS                                          SCHOMBERG DS is
             Thermal Capacity (MW) = 9                             downstream of KLEINBURG
          Short Circuit Capacity (MVA) = N/A                                TS M24
                                       F2        F3
Allocated Capacity (MW)                0         0
            SCHREIBER WINNIPG DS
             Thermal Capacity (MW) = 4
          Short Circuit Capacity (MVA) = 409
                                       F1         F2
Allocated Capacity (MW)                0          0




                             SEAFORTH TS
                      Thermal Capacity (MW) = 33
                    Short Circuit Capacity (MVA) = 210
                                      M2        M3          M4        M5
Allocated Capacity (MW)                 0        0          0         0




                       SHABAQUA DS
                   Thermal Capacity (MW) = 4
              Short Circuit Capacity (MVA) = 418
                                      M2       F1            F2
Allocated Capacity (MW)                0        0            0




                        SHARBOT DS
                   Thermal Capacity (MW) = 4
              Short Circuit Capacity (MVA) = 409
                                       F1      F2            F3
Allocated Capacity (MW)                0        0            0


           For any information or inquiries please contact Toronto Hydro
                                 *SHEPPARD TS DESN 1                                                          Station may supply
                                  Thermal Capacity (MW) = 69                                               another LDC's territory.
                                 Short Circuit Capacity (MVA) = 0                                           Refer to OPA FIT LDC
            For any information or inquiries please contact Toronto Hydro                                  locator tool to find LDC.


           For any information or inquiries please contact Toronto Hydro
                                             *SHEPPARD TS DESN 2                                                               Station may supply
                                            Thermal Capacity (MW) = 72                                                      another LDC's territory.
                                          Short Circuit Capacity (MVA) = 61                                                  Refer to OPA FIT LDC
                       For any information or inquiries please contact Toronto Hydro                                        locator tool to find LDC.



           SHININGTREE DS
         Thermal Capacity (MW) = 2
      Short Circuit Capacity (MVA) = 733
                                       M1
Allocated Capacity (MW)                 0




                                                   SIDNEY TS
                                           Thermal Capacity (MW) = 37
                                         Short Circuit Capacity (MVA) = 559
                                        M1        M3       M4        M5          M6         M7      R8S     R9S
Allocated Capacity (MW)                 0          0         0        0          0          9.9      0      15.6




              SIOUX NARROWS DS
             Thermal Capacity (MW) = 1
          Short Circuit Capacity (MVA) = 454
                                       F1         F2
Allocated Capacity (MW)                0          0




            SLATE FALLS DS
         Thermal Capacity (MW) = 2
      Short Circuit Capacity (MVA) = 734
                                       F1
Allocated Capacity (MW)                 0




                                               SMITHS FALLS TS
                                           Thermal Capacity (MW) = 88
                                        Short Circuit Capacity (MVA) = 518
                                       M21      M22       M23       M24         M25        M26      M27     M28
Allocated Capacity (MW)                 0        10        10        0          30          0        0       0




           SMOOTH ROCK FALLS DS
               Thermal Capacity (MW) = 7
           Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)             T1 = 6   T2 = 6
Short Circuit Bus Capacity (MVA)     T1 = 410 T2 = 410
                                        F1       F2
Allocated Capacity (MW)                 0        0




           SOUTH GLOUCESTER DS
             Thermal Capacity (MW) = 4
          Short Circuit Capacity (MVA) = 413
                                       F1         F2
Allocated Capacity (MW)                0          0




                                    SOUTH MARCH TS                                                            Station may supply        ALEXANDER DS is
                                 Thermal Capacity (MW) = 68                                                another LDC's territory.    downstream of SOUTH
                               Short Circuit Capacity (MVA) = 633                                           Refer to OPA FIT LDC          MARCH TS M5
                                        M1       M2        M3         M4        M5          M6             locator tool to find LDC.
Allocated Capacity (MW)                  0         0        10        0         21.9        0




                   SOWERBY DS
             Thermal Capacity (MW) = 4
          Short Circuit Capacity (MVA) = 703
                                       F1         F2
Allocated Capacity (MW)                0          0




                    SPANISH DS
             Thermal Capacity (MW) = 7
          Short Circuit Capacity (MVA) = 403
                                       F1         F2
Allocated Capacity (MW)                0          0


r any information or inquiries please contact Blue Water Power Distribution Corporation
                                               *ST ANDREWS TS
                                            Thermal Capacity (MW) = 82
                                           Short Circuit Capacity (MVA) = 0
      For any information or inquiries please contact Blue Water Power Distribution Corporation



            SPRINGVALE DS                                     SPRINGVALE DS is
         Thermal Capacity (MW) = 7                          downstream of FOREST
      Short Circuit Capacity (MVA) = N/A                        JURA DS F1
                                        F1
Allocated Capacity (MW)                  0




                SQUIRE DS                                 SQUIRE DS is downstream
         Thermal Capacity (MW) = 4                        of OWEN SOUND TS M25
      Short Circuit Capacity (MVA) = N/A
                                        F3
Allocated Capacity (MW)                0.1




                            ST ISIDORE TS                                                 CRYSLER DS is downstream
                                                                                                                      GLENGARRY DS is
                      Thermal Capacity (MW) = 34                                                                   downstream of ST ISIDORE
                                                                                            of ST ISIDORE TS M2
                    Short Circuit Capacity (MVA) = 911                                                                      TS M4
                                      M1        M2          M3        M4
Allocated Capacity (MW)               10.5      10.1        0         0
                              ST LAWRENCE TS
                          Thermal Capacity (MW) = 73
                        Short Circuit Capacity (MVA) = 333
                                      M24       M25      M26        M27      M28
Allocated Capacity (MW)                0         10       0          0        0




                                      ST MARYS TS
                                Thermal Capacity (MW) = 29
                              Short Circuit Capacity (MVA) = 248
                                       M1       M2        M3         M4      M5        M6
Allocated Capacity (MW)                 0         0        0         0       0         0




       ST THOMAS TS DESN 1
        Thermal Capacity (MW) = 16
      Short Circuit Capacity (MVA) = 284
                                       M10
Allocated Capacity (MW)                10




            ST THOMAS TS DESN 2
             Thermal Capacity (MW) = 25
          Short Circuit Capacity (MVA) = 283
                                      M3        M5
Allocated Capacity (MW)                0        0




                                                                     STANLEY TS                                                                               Station may supply
                                                          Thermal Capacity (MW) = Sum of Buses                                                             another LDC's territory.
                                                            Short Circuit Capacity (MVA) = N/A                                                              Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                     QJ = 9                                                 BY = 6                                locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                              QJ = 73                                               BY = 74
                                      M31       M32       M33       M41       M42       M43    M1        M2       M3        M4      M5       M6
Allocated Capacity (MW)                0         0          0         0         0        0     0         0        0         0       0        0




                 STARDALE DS                                           STARDALE DS is
             Thermal Capacity (MW) = 4                             downstream of LONGUEUIL
          Short Circuit Capacity (MVA) = N/A                                TS M23
                                       F2       F3
Allocated Capacity (MW)                0        0.6




                                                STAYNER TS
                                          Thermal Capacity (MW) = 90
                                        Short Circuit Capacity (MVA) = 445
                                       M1        M2       M3        M4       M5        M6       M7       M8
Allocated Capacity (MW)                0         10         0        0       0         0        0        0




                    STEWARTVILLE TS
                  Thermal Capacity (MW) = 21
              Short Circuit Capacity (MVA) = 908
                                      M1       M3          M4
Allocated Capacity (MW)                0        0          0




             STIRLING DS                                 STIRLING DS is downstream
         Thermal Capacity (MW) = 4                          of BELLEVILLE TS M5
      Short Circuit Capacity (MVA) = N/A
                                        F3
Allocated Capacity (MW)                0.5




                                                                                                STIRTON TS                                                                                            Station may supply
                                                                                      Thermal Capacity (MW) = Sum of Buses                                                                         another LDC's territory.
                                                                                        Short Circuit Capacity (MVA) = N/A                                                                          Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                              QZ = 1                                                                           BY = 11                                    locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                                       QZ = 56                                                                          BY = 90
                                      M51       M52       M53       M54      M61      M62      M63      M64      M71         M72   M75      M76      M81      M82     M83     M84      M85   M86
Allocated Capacity (MW)                0         0         0         0         0       0        0        0        0           0     0        0        0         0      0       0        0     0


          For any information or inquiries please contact Toronto Hydro
                                                      *STRACHAN TS DESN 1                                                                    Station may supply
                                               Thermal Capacity (MW) = Sum of Buses                                                       another LDC's territory.
                                                 Short Circuit Capacity (MVA) = N/A                                                        Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                             A5A6 = 7                                       A7A8 = 6                             locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                     A5A6 = 45                                       A7A8 = 45
                               For any information or inquiries please contact Toronto Hydro


          For any information or inquiries please contact Toronto Hydro
                                                      *STRACHAN TS DESN 2                                                                    Station may supply
                                               Thermal Capacity (MW) = Sum of Buses                                                       another LDC's territory.
                                                 Short Circuit Capacity (MVA) = N/A                                                        Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                             A1A2 = 7                                       A3A4 = 7                             locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                     A1A2 = 74                                       A3A4 = 74
                               For any information or inquiries please contact Toronto Hydro



                                               STRATFORD TS                                                                 Station may supply
                                          Thermal Capacity (MW) = 76                                                     another LDC's territory.
                                        Short Circuit Capacity (MVA) = 55                                                 Refer to OPA FIT LDC
                                       M1       M2        M3        M4       M5        M6       M7       M8              locator tool to find LDC.
Allocated Capacity (MW)                0         0         0         0       0         0        10       0




                           STRATHROY TS                                                 Station may supply
                      Thermal Capacity (MW) = 34                                     another LDC's territory.
                    Short Circuit Capacity (MVA) = 456                                Refer to OPA FIT LDC
                                      M1        M2         M3        M4              locator tool to find LDC.
Allocated Capacity (MW)                 0        0         0         0




                   STRIKER DS
              Thermal Capacity (MW) = 11
           Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)             T1 = 8   T2 = 8
Short Circuit Bus Capacity (MVA)     T1 = 690 T2 = 691
                                        F1       F2
Allocated Capacity (MW)                 0        0




       SUNDRIDGE NORTH DS                                SUNDRIDGE NORTH DS is
         Thermal Capacity (MW) = 5                        downstream of MUSKOKA
      Short Circuit Capacity (MVA) = N/A                           TS M2
                                        F2
Allocated Capacity (MW)                  0




                                             TALBOT TS DESN 1                                                               Station may supply
                                           Thermal Capacity (MW) = 0                                                     another LDC's territory.
                                         Short Circuit Capacity (MVA) = 0                                                 Refer to OPA FIT LDC
                                      M11       M12       M13      M14       M21      M22      M23      M25              locator tool to find LDC.
Allocated Capacity (MW)                0         0         0         0        0        0        0        0




                                                                TALBOT TS DESN 2                                                                              Station may supply
                                                          Thermal Capacity (MW) = Sum of Buses                                                             another LDC's territory.
                                                            Short Circuit Capacity (MVA) = N/A                                                              Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                    J1J2 = 11                                            Q1Q2 = 11                                locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                            J1J2 = 133                                            Q1Q2 = 38
                                      M41       M42       M43       M46       M47       M48    M51      M52      M53     M54       M55      M56
Allocated Capacity (MW)                0         0          0         0         0        0      0        0       18.8     0         0        0
                 TEMAGAMI DS
             Thermal Capacity (MW) = 3
          Short Circuit Capacity (MVA) = 437
                                       F1         F2
Allocated Capacity (MW)                0          0


          For any information or inquiries please contact Toronto Hydro
                                                       *TERAULEY TS DESN 1                                                                 Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                    another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                     Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                              A1A2 = 9                                      A7A8 = 9                           locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                      A1A2 = 93                                      A7A8 = 93
                                For any information or inquiries please contact Toronto Hydro


          For any information or inquiries please contact Toronto Hydro
                                                       *TERAULEY TS DESN 2                                                                 Station may supply
                                                Thermal Capacity (MW) = Sum of Buses                                                    another LDC's territory.
                                                  Short Circuit Capacity (MVA) = N/A                                                     Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                              A3A4 = 9                                       A5A6 = 9                          locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                      A3A4 = 100                                     A5A6 = 100
                                For any information or inquiries please contact Toronto Hydro



                                                THORNTON TS                                                               Station may supply
                                          Thermal Capacity (MW) = 98                                                   another LDC's territory.
                                        Short Circuit Capacity (MVA) = 377                                              Refer to OPA FIT LDC
                                       M1        M2       M3        M4             M5    M6    M7       M8             locator tool to find LDC.
Allocated Capacity (MW)                0          0         2        0             0     0     0        10




                       THOROLD TS
            Thermal Capacity (MW) = Sum of Buses
               Short Circuit Capacity (MVA) = 65
                                       M1       M2          M3
Allocated Capacity (MW)                 0        0          0




              TILBURY TS
         Thermal Capacity (MW) = 5
      Short Circuit Capacity (MVA) = 692
                                       M1
Allocated Capacity (MW)                 5




               TILBURY WEST DS
              Thermal Capacity (MW) = 18
           Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)            T1 = 14 T2 = 15
Short Circuit Bus Capacity (MVA)     T1 = 636 T2 = 638
                                        F1       F2
Allocated Capacity (MW)                 0        10




          TILLSONBURG DS                                    TILLSONBURG DS is
         Thermal Capacity (MW) = 3                              downstream of
      Short Circuit Capacity (MVA) = N/A                    TILLSONBURG TS M2
                                        F2
Allocated Capacity (MW)                  0




                                               TILLSONBURG TS                                                             Station may supply       TILLSONBURG DS is
                                          Thermal Capacity (MW) = 66                                                   another LDC's territory.        downstream of
                                        Short Circuit Capacity (MVA) = 288                                              Refer to OPA FIT LDC       TILLSONBURG TS M2
                                       M1        M2       M3        M4             M5    M6    M7       M10            locator tool to find LDC.
Allocated Capacity (MW)                0        19.8        0       19.8           0     0     0        6.7




                                             TIMMINS TS
                                      Thermal Capacity (MW) = 61
                                     Short Circuit Capacity (MVA) = 0
                                       M5         M6        M7        M8           M9    M10   M11
Allocated Capacity (MW)                0           0        5.5       15           0      0     0




                                             TOMKEN TS DESN1                                                              Station may supply
                                          Thermal Capacity (MW) = 101                                                  another LDC's territory.
                                        Short Circuit Capacity (MVA) = 227                                              Refer to OPA FIT LDC
                                       M1        M2       M3        M4             M5    M6    M7       M8             locator tool to find LDC.
Allocated Capacity (MW)                0          0         0        0             0     0     0        0




                                             TOMKEN TS DESN2                                                              Station may supply
                                           Thermal Capacity (MW) = 103                                                 another LDC's territory.
                                        Short Circuit Capacity (MVA) = 269                                              Refer to OPA FIT LDC
                                       M23      M24       M25       M26            M27   M28   M29      M30            locator tool to find LDC.
Allocated Capacity (MW)                 0         0         0        0              0     0     0        0




                                TRAFALGAR TS
                            Thermal Capacity (MW) = 0
                          Short Circuit Capacity (MVA) = 0
                                       M4        M5        M6          M7          M8
Allocated Capacity (MW)                 0         0        0           0           0




              TRALEE DS                                   TRALEE DS is downstream
         Thermal Capacity (MW) = 4                         of PALMERSTON TS M3
      Short Circuit Capacity (MVA) = N/A
                                        F3
Allocated Capacity (MW)                  0




          TROUT CREEK DS                                    TROUT CREEK DS is
         Thermal Capacity (MW) = 5                       downstream of TROUT LAKE
      Short Circuit Capacity (MVA) = N/A                           TS M7
                                        F1
Allocated Capacity (MW)                0.8




                                               TROUT LAKE TS                                                              Station may supply       TROUT CREEK DS is
                                          Thermal Capacity (MW) = 87                                                   another LDC's territory. downstream of TROUT LAKE
                                        Short Circuit Capacity (MVA) = 435                                              Refer to OPA FIT LDC              TS M7
                                       M1        M2       M3        M4             M5    M6    M7       M8             locator tool to find LDC.
Allocated Capacity (MW)                0          0         0        0             9     0     0.8      0




              VALORA DS
         Thermal Capacity (MW) = 2
      Short Circuit Capacity (MVA) = 732
                                       F1
Allocated Capacity (MW)                 0


   For any information or inquiries please contact Horizon Utilities Corporation
                                     *VANSICKLE TS                                                       Station may supply
                                  Thermal Capacity (MW) = 0                                           another LDC's territory.
                                Short Circuit Capacity (MVA) = 0                                       Refer to OPA FIT LDC
   For any information or inquiries please contact Horizon Utilities Corporation                      locator tool to find LDC.



                   VERMILION BAY DS
                   Thermal Capacity (MW) = 4
              Short Circuit Capacity (MVA) = 428
                                       F1      F2           F3
Allocated Capacity (MW)                0        0           0
                          VERNER DS
                   Thermal Capacity (MW) = 6
              Short Circuit Capacity (MVA) = 409
                                       F1      F2             F3
Allocated Capacity (MW)                0        0             0


  For any information or inquiries please contact Niagara Peninsula Energy Inc
                 *VINELAND DS
              Thermal Capacity (MW) = 14
           Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)            T1 = 14 T2 = 16
Short Circuit Bus Capacity (MVA)     T1 = 623 T2 = 616
ation or inquiries please contact Niagara Penins


          For any information or inquiries please contact EnWin Utilities
                                *WALKER TS #1                                                     Station may supply
                             Thermal Capacity (MW) = 0                                         another LDC's territory.
                           Short Circuit Capacity (MVA) = 0                                     Refer to OPA FIT LDC
      For any information or inquiries please contact EnWin Utilities                          locator tool to find LDC.



                       WALLACE TS
                   Thermal Capacity (MW) = 31
                Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)             T3 = 24        T4 = 31
Short Circuit Bus Capacity (MVA) T3 = 1155          T4 = 1164
                                        M1       M4         M6
Allocated Capacity (MW)                 0.6        4         0




                              WALLACEBURG TS
                          Thermal Capacity (MW) = 36
                        Short Circuit Capacity (MVA) = 457
                                      M1        M2       M3            M5        M6
Allocated Capacity (MW)                0         0       10            0         0




                           WANSTEAD TS
                       Thermal Capacity (MW) = 33
                    Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                 T3 = 33              T1T2 = 24
Short Circuit Bus Capacity (MVA)         T3 = 493              T1T2 = 517
                                      M1         M3           M2       M4
Allocated Capacity (MW)                10        4.8          0         0




                                                                   WARDEN TS                                                                                Station may supply
                                                     Thermal Capacity (MW) = Sum of Buses                                                                another LDC's territory.
                                                       Short Circuit Capacity (MVA) = N/A                                                                 Refer to OPA FIT LDC
Thermal Bus Capacity (MW)                                     J = 46                                               Q = 47                                locator tool to find LDC.
Short Circuit Bus Capacity (MVA)                             J = 106                                               Q = 104
                                       M21       M23      M25        M27       M29      M31      M24      M26       M28       M30      M32
Allocated Capacity (MW)                 0         0        0          0         0         0       0        0          0        0        0




                             WARREN DS
                        Thermal Capacity (MW) = 6
                    Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                  T1 = 5                T2 = 5
Short Circuit Bus Capacity (MVA)          T1 = 404              T2 = 404
                                       F1         F2          F3        F4
Allocated Capacity (MW)                 0         0           0         0




                                        WAUBAUSHENE TS
                                      Thermal Capacity (MW) = 57
                                    Short Circuit Capacity (MVA) = 423
                                       M1         M2        M3       M4          M5      M6       M7
Allocated Capacity (MW)                 0          0         0        0          0       0        10




                 WENDOVER DS
              Thermal Capacity (MW) = 15
           Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)            T1 = 14 T2 = 15
Short Circuit Bus Capacity (MVA)     T1 = 635 T2 = 630
                                        F1       F3
Allocated Capacity (MW)                 0        0




               WESTON LAKE DS
             Thermal Capacity (MW) = 7
          Short Circuit Capacity (MVA) = 695
                                       F1         F2
Allocated Capacity (MW)                0          0




               WHARNCLIFFE DS
             Thermal Capacity (MW) = 4
          Short Circuit Capacity (MVA) = 641
                                       F1         F2
Allocated Capacity (MW)                0          0




                     WHITBY TS -27.6 kV DESN1 (T1&T2) -BY                                                  Station may supply
                                 Thermal Capacity (MW) = 11                                             another LDC's territory.
                               Short Circuit Capacity (MVA) = 19                                         Refer to OPA FIT LDC
                                      M43       M44       M45         M46        M47    M48             locator tool to find LDC.
Allocated Capacity (MW)                 0         0         0          0          0      0




             WHITBY TS -44 kV DESN1 (T1&T2) -EZ                                           Station may supply
                      Thermal Capacity (MW) = 11                                       another LDC's territory.
                    Short Circuit Capacity (MVA) = 623                                  Refer to OPA FIT LDC
                                      M5        M6            M7       M8              locator tool to find LDC.
Allocated Capacity (MW)                 0        0            0        0




                                    WHITBY TS -44kV DESN2 (T3&T4)                                                               Station may supply
                                           Thermal Capacity (MW) = 110                                                       another LDC's territory.
                                        Short Circuit Capacity (MVA) = 400                                                    Refer to OPA FIT LDC
                                       M21      M22       M23       M24          M25    M26      M27      M28                locator tool to find LDC.
Allocated Capacity (MW)                0.5        0         0        0            0      0        0        0




                     WHITE RIVER DS
                   Thermal Capacity (MW) = 4
              Short Circuit Capacity (MVA) = 663
                                       F1      F2             F3
Allocated Capacity (MW)                0        0             0




                 WHITEFISH DS
             Thermal Capacity (MW) = 5
          Short Circuit Capacity (MVA) = 412
                                       F1         F2
Allocated Capacity (MW)                0          0




                                   WILHAVEN DS
                             Thermal Capacity (MW) = 25
                          Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                       T1 = 20                  T2 = 21
Short Circuit Bus Capacity (MVA)               T1 = 580                  T2 = 579
                                         F1        F2       F3         F4       F5
Allocated Capacity (MW)                  0         0         0         0         0
                                             WILSON TS DESN 1                                                                   Station may supply
                                           Thermal Capacity (MW) = 110                                                       another LDC's territory.
                                        Short Circuit Capacity (MVA) = 369                                                    Refer to OPA FIT LDC
                                       M1        M2       M3        M4             M5      M6       M7       M8              locator tool to find LDC.
Allocated Capacity (MW)                2.5        0         0        0             0       0        0        20




                                             WILSON TS DESN 2                                                                   Station may supply
                                           Thermal Capacity (MW) = 106                                                       another LDC's territory.
                                        Short Circuit Capacity (MVA) = 366                                                    Refer to OPA FIT LDC
                                       M11      M12       M13       M14            M15    M16      M17      M18              locator tool to find LDC.
Allocated Capacity (MW)                 0         0         0        10            20      0        0        0


          For any information or inquiries please contact Toronto Hydro
                                                       *WILTSHIRE TS DESN 1                                                                      Station may supply
                                                      Thermal Capacity (MW) = 0                                                               another LDC's territory.
                                                    Short Circuit Capacity (MVA) = 97                                                          Refer to OPA FIT LDC
                                For any information or inquiries please contact Toronto Hydro                                                 locator tool to find LDC.



                                                                  WINDSOR MALDEN TS
                                                           Thermal Capacity (MW) = Sum of Buses
                                                             Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)                                      B = 40                                                    Y = 50
Short Circuit Bus Capacity (MVA)                               B = 134                                                  Y = 137
                                       M1         M3        M5        M7       M9        M11    M2           M4       M6        M8     M10      M12
Allocated Capacity (MW)                0          0          0       19.8        0       19.8   0            0        0         0       0       10




                            WINGHAM TS
                      Thermal Capacity (MW) = 57
                    Short Circuit Capacity (MVA) = 726
                                      M3        M4          M5         M6
Allocated Capacity (MW)                 0        0          0          0


   For any information or inquiries please contact Horizon Utilities Corporation
                                       *WINONA TS                                                            Station may supply
                                Thermal Capacity (MW) = 51                                                another LDC's territory.
                              Short Circuit Capacity (MVA) = 165                                           Refer to OPA FIT LDC
   For any information or inquiries please contact Horizon Utilities Corporation                          locator tool to find LDC.



                WOLVERTON DS
              Thermal Capacity (MW) = 19
           Short Circuit Capacity (MVA) = N/A
Thermal Bus Capacity (MW)            T1 = 15 T2 = 15
Short Circuit Bus Capacity (MVA)     T1 = 628 T2 = 628
                                        F1       F2
Allocated Capacity (MW)                 0        0




                                              WONDERLAND TS                                                                     Station may supply
                                          Thermal Capacity (MW) = 68                                                         another LDC's territory.
                                        Short Circuit Capacity (MVA) = 24                                                     Refer to OPA FIT LDC
                                       M1       M2        M3        M4             M5      M6       M7       M8              locator tool to find LDC.
Allocated Capacity (MW)                0         0         0         0             0       0        0        0




                          WOODBRIDGE TS 27.6 kV - DESN1                                                      Station may supply
                                 Thermal Capacity (MW) = 0                                                another LDC's territory.
                              Short Circuit Capacity (MVA) = 352                                           Refer to OPA FIT LDC
                                       M1       M2        M3           M4          M5      M6             locator tool to find LDC.
Allocated Capacity (MW)                 0         0        0           0           0       0




               WOODBRIDGE TS 44 kV - DESN1                                                  Station may supply
                       Thermal Capacity (MW) = 0                                         another LDC's territory.
                    Short Circuit Capacity (MVA) = 134                                    Refer to OPA FIT LDC
                                      M12       M13         M15       M16                locator tool to find LDC.
Allocated Capacity (MW)                 0        0           0         0




                                          WOODSTOCK TS                                                                  Station may supply     WOODSTOCK ZORRA DS is
                                      Thermal Capacity (MW) = 69                                                     another LDC's territory.      downstream of
                                    Short Circuit Capacity (MVA) = 311                                                Refer to OPA FIT LDC       WOODSTOCK TS M9
                                       M3         M4        M6       M7            M8      M9      M10               locator tool to find LDC.
Allocated Capacity (MW)                 0          0         20       0            0       0.1      9




      WOODSTOCK ZORRA DS                                 WOODSTOCK ZORRA DS is
         Thermal Capacity (MW) = 4                           downstream of
      Short Circuit Capacity (MVA) = N/A                   WOODSTOCK TS M9
                                        F2
Allocated Capacity (MW)                0.1
                                                Appendix A

              CASE 1: Single Secondary Winding Station (Bus tie closed)


                                   Sample TS
                            Thermal Capacity = 43 MW
                          Short Circuit Capacity = 240 MVA
                                                   M1        M2   M3   M5   M6
Allocated Capacity (MW)                            0         0    10   0    0



New Proposed Generator Data

Name plate capacity = 10 MW
Short Circuit Contribution = 15 MVA
Feeder = M2

Station Capacity Availability Check

Thermal Capacity = 43 MW
Short Circuit Capacity = 240 MVA
Allocated Capacity on Station = 10 MW
Assume sub-transient reactance of 0.2 p.u. for allocated capacity
Short Circuit Contribution by Allocated Capacity Generator = 5 X 10 = 50 MVA


Thermal Capacity Check = 43 – 10 (allocated) – 10 (new proposed) > 0

Short Circuit Capacity Check = 240 – 50 (allocated) – 15 (new proposed) > 0


Both above mentioned checks should be satisfied when checking for station capacity for a
proposed generation connection to the station.




List of Allocated Capacity – Appendix A
http://www.hydroone.com/Generators/Pages/distribution.aspx                                 I
                     CASE 2: Dual Secondary Winding Station (Bus tie Open)

                                                    SAMPLE TS
                                          Thermal Capacity = Sum of Buses (MW)
                                               Short Circuit Capacity = N/A
Thermal Bus Capacity (MW)                       B = 15                                     Y = 15
Short Circuit Bus Capacity (MVA)               B = 100                                     Y= 200
                                   M1   M3        M5          M7         M9      M2   M4    M6      M8   M10
Allocated Capacity (MW)            0    0         0           0           0      0    0      0      0     0




New Proposed Generator Data

Name plate capacity = 8 MW
Short Circuit Contribution = 40 MVA
Feeder = M4

Station Capacity Availability Check

Bus Capacity = Y = 15 MW
Station Thermal Capacity = “Sum of buses” = 15 + 15 = 30 MW

Bus Short Circuit Capacity = Y = 200 MVA

Allocated Capacity on Station = 0 MW
Assume sub-transient reactance of 0.2 p.u. for Allocated capacity
Short Circuit Contribution by Allocated Capacity Generator = 0 MVA


Bus Thermal Capacity Check = 15 – 0 (allocated) – 8 (new proposed) > 0

Station Thermal Capacity Check = 30 – 0 (allocated) – 8 (new proposed) > 0

Bus Short Circuit Capacity Check = 200 – 0 (allocated) – 40 (new proposed) > 0

All above mentioned checks should be satisfied when checking for station capacity for a
proposed generation connection to the station.




List of Allocated Capacity – Appendix A
http://www.hydroone.com/Generators/Pages/distribution.aspx                                                     II
              Case 3: Single Secondary Winding Station (Bus tie closed)


                                  Sample TS
                            Thermal Capacity = 60 MW
                          Short Circuit Capacity = 10 MVA
                                                   M1       M2   M3   M5   M6
Allocated Capacity (MW)                            0        0     0    0    0

New Proposed Generator Data

Name plate capacity = 10 MW
Short Circuit Contribution = 25 MVA
Feeder = M1

Station Capacity Availability Check

Thermal Capacity = 60 MW
Short Circuit Capacity = 10 MVA
Allocated Capacity on Station = 0 MW
Assume sub-transient reactance of 0.2 p.u. for allocated capacity
Short Circuit Contribution by Allocated Capacity Generator = 0 MVA


Thermal Capacity Check = 60 – 0 (allocated) – 10 (new proposed) = 50 MW

Short Circuit Capacity Check = 10 – 0 (allocated) – 25 (new proposed) = - 15 MVA


Conclusion:

The answer is positive for the thermal capacity check so the proposed generator is within the thermal
capacity limit.

The answer to the SC capacity check is negative. The proposed generator exceeds the short circuit
capacity of the station.




List of Allocated Capacity – Appendix A
http://www.hydroone.com/Generators/Pages/distribution.aspx                                          III
                Case 4: Single Secondary Winding Station (Bus tie open)


                                          Sample TS
                                   Thermal Capacity = 35 MW
                                   Short Circuit Capacity = N/A
Thermal Bus Capacity (MW)                                   T1 = 29          T2 = 31
Short Circuit Bus Capacity (MVA)                            T1 = 600         T2 = 610
                                                         M1   M3     M5   M2   M4     M6
Allocated Capacity (MW)                                  0     0     10   0     20     0

New Proposed Generator Data

Name plate capacity = 10 MW
Short Circuit Contribution = 50 MVA
Feeder = M1

Station Capacity Availability Check

Thermal Bus Capacity = T1 = 29 MW
Thermal Station Capacity = 35 MW

Bus Short Circuit Capacity = T1 = 600 MVA

Allocated Capacity on Bus = 10 MW
Allocated Capacity on Station = 30 MW

Assume sub-transient reactance of 0.2 p.u. for Allocated capacity

Bus Short Circuit Contribution by Allocated Capacity Generator = 10 X 5 = 50 MVA

1. Bus Thermal Capacity Check = 29 – 10 (allocated) – 10 (new proposed) = 9

2. Station Thermal Capacity Check = 35 – 30 (allocated) – 10 (new proposed) = - 5

3. Bus Short Circuit Capacity Check = 600 – 50 (allocated) – 50 (new proposed) = 500

Conclusion:

The answer is positive for check 1 and 3. So, the proposed generator is within the thermal capacity
bus limit and the short circuit capacity of the bus and the station.

However, the answer to the station thermal capacity check is negative. The proposed generator
exceeds the station thermal capacity limit.



List of Allocated Capacity – Appendix A
http://www.hydroone.com/Generators/Pages/distribution.aspx                                            IV

				