                             Background
                             Enrollment at University of Phoenix and other Apollo Group subsidiaries more
                             than doubled between 2001 and 2005, driving the need for a new data center.
                             Because the organization’s educational model depends on continuous availability
                             of information technology services, an adaptive power and cooling infrastructure
                             was critical. It was also important to gain a better understanding of data center
                             operations to enhance growth planning and increase data center efficiency.

                             Case Summary
                             Location: Phoenix, Arizona

                             Emerson Network Power Products/Services:
   University of             •LiebertMPAdvancedIn-Rack   •LiebertDeluxePrecision
                               Power Distribution               Cooling Systems
     Phoenix
                             •LiebertFDCFoundation        •LiebertFoundationEnclosures
                               Distribution Cabinets            with Expansion Channels
                             •LiebertSystemControlCabinets •LiebertServices
                             •LiebertSeries610UPSSystems  •ApertureVISTA
                             •LiebertSiteScanWeb

                             Critical Needs: Create and maintain an adaptive cooling and power
                             infrastructure for mission-critical data center at university serving more than
                             300,000 students worldwide.

                             Results
                               Deployed a flexible and scalable power and cooling architecture that ensures
                               the data center can support future business and technology requirements.

                               Enhanced data center availability through multiple active power and
The parent company for
                               cooling distribution paths with redundant components that are
University of Phoenix
                               concurrently maintainable.
and other education
                               Increased understanding of the current state of critical IT infrastructure
subsidiaries, Apollo
                               through proactive monitoring and management.
Group offers educational
                               Gained real-time visibility into available power and cooling capacity.
programs at 95 campuses
and 153 learning centers       Reduced risk of technology deployment by enabling ability to model impact
in 39 states; Puerto Rico;     of technology changes on data center infrastructure.
Alberta, British Columbia;
Netherlands and Mexico.
                                                                                      A Customer Success
                                                                                      from the Experts in
                                                                                      Business-Critical Continuity™




The Situation                                           scale with tomorrow’s unpredictable power and
                                                        heat loads.”
“Technology has transformed the way we
conduct business,” says Rick Oliver, Apollo Group       Oliver knew that once the data center was
data center manger. “A decade ago we were largely       operational they would need to proactively manage
ground-based, but today a significant portion of our    the data center environment to achieve “world-class”
business is online. That requires continuous access     performance. He also understood that to increase
to information technology. Our ability to provide       data center efficiencies they would need to
online education and services to our students           integrate the monitoring and management
requiresrigorousqualitycontrols.Weservea         of the critical infrastructure.
worldwide student body, and our faculty and
students need to access online classrooms,              The Solution
course materials and services around the clock.”
                                                        Oliver decided early in the planning process that
Withitsincreasingdependenceontechnology,          Emerson Network Power would provide the power
the Apollo Group needed a new, 10,000-square-foot       and cooling infrastructure. And after doing a deep
production data center at its corporate headquarters    evaluation of available tools, he decided to use
inPhoenix,Ariz.Whenfullypopulated,thefacility   ApertureVISTA.
would need to hold more than 1,000 servers. The
                                                        “Wehaveahighlyqualifiedteamthatkeepsour
company’s commitment to technology, one of its
                                                        datacenterupandrunning,”saysOliver.“Wemake
hallmarks, would drive the development of this new
                                                        sure to invest in solutions that make it easier to carry
data center.
                                                        out our mission. In this instance, that investment
“Weareoftenamongthefirstadoptersofany          included multiple active power and cooling
innovation,”saysOliver.“Frombladeserversto       distribution paths, with redundant components
multi-terabytediskstoragetoWANtechnology,         that are concurrently maintainable.”
we’re on the leading edge and that has helped
                                                        The five-person Data Center Operations team worked
fuel the success of our business.”
                                                        withFMSolutions,consultingengineers;Integrated
New technology, however, carries a price in terms       SupportSystems,alocalLiebertRepresentative;
of the power and cooling infrastructure needed to       and,DPAir,anITresellerand.LiebertNetwork
support it.                                             SolutionsPartner.TheteamspecifiedLiebertpower
“Fasterandsmallerusesmorepowerandputs           and cooling equipment that met the high-availability
out more heat,” says Oliver. “Power fluctuations and    needs and could quickly adapt to increasing power
heat tend to destroy the very technology we depend      and heat loads.
on, so we need power and cooling solutions that can
                                                                                        A Customer Success
                                                                                        from the Experts in
                                                                                        Business-Critical Continuity™




Adaptive Power and Cooling Infrastructure                  units are used in a N+1 configuration to provide 572
The power infrastructure employs a dual-bus design         tons of base-level cooling.
that allows for maintenance, testing and repair to
                                                           ThedesignteamdeployedLiebertXDAairflow
be carried out during continuous operation. The
                                                           enhancers on the exhaust side of 50 racks in a
designteamspecifiedfour,750kVALiebertSeries
                                                           high-densityarea.TheLiebertXDApreventsheat
610UPSsystems,eachwithan“A”busanda“B”
                                                           from accumulating inside the enclosure by increasing
bus connected to a System Control Cabinet and an
                                                           the airflow.
independent generator.
                                                           “Rather than waiting for heat to dissipate in a natural
ALiebertFDCdistributioncabinetsitsattheendof
                                                           manner,theLiebertXDAunitsexpeltheheatinto
each row of racks, integrating power distribution
                                                           the hot aisle where it is drawn into the ceiling plenum,
intotherackenvironment.TheLiebertFDCprovides
                                                           cooled, and returned to the room via the cold aisle,”
in-rowpowerdistributionwith168poles(four
                                                           says Oliver.
complete panel boards) in a stand-alone cabinet.
This allows the addition of new equipment without          Data Center Monitoring and Management
dragging power across rows or creating under-floor         EmersonNetworkPower’sLiebertSiteScanWeb,
cable dams.                                                afull-featured,Web-basedmonitoring,control
                                                           and alarm management system, was implemented
ServersarehousedinLiebertFoundationenclosures,
                                                           to monitor the critical infrastructure and provide
which provide the flexibility to accommodate any
                                                           real-time information about the status of the data
variety and size of equipment.
                                                           center down to the smallest device level.
“Wehaveserversfromallthemajormanufacturers,
                                                           The monitoring package’s data analysis and trend
sotheadaptabilityofthedesignwasamajorselling
                                                           reporting tools allow Oliver and his staff to analyze
point,”Oliversaid.“Wewereimpressedbythebuilt-in
                                                           data and use it to prevent specific problems from
channel pathway for the data cabling and the built-in
                                                           recurring. The programmable alarm management
wire management within the channel, as well as by
                                                           enables Oliver to customize the alert depending on
the aesthetic design of the units, which coordinate
                                                           the type and seriousness of the event.
well with the server racks.”
                                                           ApertureVISTA,whichisadatacenterinfrastructure
LiebertMPpowerdistributionunits,whichare
                                                           resource management system, was implemented to
mounted in the racks themselves, provide load
                                                           proactively monitor and manage all aspects of the
monitoring and control to the receptacle level.
                                                           data center environment.
The data center features a hot-aisle/cold-aisle
                                                           Together,LiebertSiteScanandApertureVISTA
configuration and a 24-inch raised floor that allows
                                                           provide Apollo Group a comprehensive data center
ample air circulation through the under-floor plenum.
                                                           infrastructure management solution.
Twenty-sixLiebertDeluxeSystemprecisioncooling
                                                                                                                                           A Customer Success
                                                                                                                                           from the Experts in
                                                                                                                                           Business-Critical Continuity™




Specifically, monitoring and management across                                               The Results
domains can be merged to create new capabilities
                                                                                             The Apollo Group’s new data center has the capacity
such as holistic services at a targeted service level and
                                                                                             to power the company’s existing business as well as
actionable reporting on availability and performance.
                                                                                             the flexibility to scale to the demands of the future.
TwoareaswhereOliverseesLiebertSiteScan                                                The Data Center Operations team is confident that
andApertureVISTAworkingtogethertoenhance                                              it has the adaptive power and cooling infrastructure
operation of his data center are maintenance and                                             needed to provide continuous support to the
capacity planning.                                                                           company’s several hundred thousand students,
Forexample,Olivercanreconfigurethedata                                                faculty and staff.
center to accommodate maintenance activities;                                                “The adaptive power and cooling infrastructure
thereby maintaining the critical infrastructure                                              gave us the availability and flexibility we needed to
withoutdisruptingservice.ApertureVISTAcan                                             continue to grow our business,” says Oliver. “Aperture
map maintenance activity onto affected racks                                                 VISTAelevatedustoanotherlevelintermsoffully
whileLiebertSiteScancansuppressalarmsfor                                              understanding our data center environment.”
the equipment under maintenance.
                                                                                             Specifically, the data center infrastructure
LiebertSiteScanandApertureVISTAcanalsowork                                           resource management system is providing a
together to ensure Apollo Group deploys hardware                                             top-down visualization of the data center with a
without exceeding power, space or cooling capacity.                                          more detailed and sophisticated tracking of assets.
LiebertSiteScanprovidesreal-timedataonpower                                           The team can easily obtain accurate, current views
andcoolingcapacity,andApertureVISTAshows                                              of data configuration and capacities, and a controlled
available capacity for a proposed change.                                                    procedure for equipment moves, additions
                                                                                             and changes.

                                                                                             “This new in-depth view of our data center is going
                                                                                             to provide numerous benefits across the board.
                                                                                             Forinstance,wenowhavetheconfidenceand
                                                                                             understandingweneedtobeginplanningamajor
                                                                                             virtualizationproject.”


Emerson Network Power.
The global leader in enabling Business-Critical Continuity™.                                                                   EmersonNetworkPower.com


     AC Power                         Embedded Computing                                Outside Plant                                    Racks & Integrated Cabinets
     Connectivity                     Embedded Power                                    Power Switching & Control                        Services
     DC Power                         Monitoring                                        Precision Cooling                                Surge Protection

Whileeveryprecautionhasbeentakentoensureaccuracyandcompletenessinthisliterature,LiebertCorporationassumesnoresponsibility,anddisclaimsallliabilityfordamages
resultingfromuseofthisinformationorforanyerrorsoromissions.Specificationssubjecttochangewithoutnotice.©2008LiebertCorporation.Allrightsreservedthroughout
theworld.Trademarksorregisteredtrademarksarepropertyoftheirrespectiveowners.®LiebertandtheLiebertlogoareregisteredtrademarksoftheLiebertCorporation.
Business-CriticalContinuity,EmersonNetworkPowerandtheEmersonNetworkPowerlogoaretrademarksandservicemarksofEmersonElectricCo.©2008EmersonElectricCo.
1108CH-00011(11/08)