					DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                          Page 1
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Bay County

License Number: 1305238                                         ALEXAN LAGUNA BEACH
License Type: Apartment                                         90 SANDAL LANE, PANAMA CITY BEACH 32413

   Inspection Date: 09/15/2008           Inspection Number: 1221827              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DESHAZIER, ERNEST                                                                                                   Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

07-06-2            Observed an electrical outlet missing a cover plate. For reporting purposes only.              NFPA 70, 300-31 Suitable covers shall be installed on
                   Corrected On Site.Room 1303.                                                                   all boxes to prevent accidental contact with energized
                                                                                                                  parts or physical damage to parts or insulation. FOR
                                                                                                                  REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                             Page 2
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Brevard County

License Number: 1500451                                            KIRKLAND CT APT MOTEL
License Type: Apartment                                            2930 NE KIRKLAND RD, PALM BAY 329057409

   Inspection Date: 09/17/2008              Inspection Number: 1212140              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: WEIMER, EDWIN                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                    Violation Citation

01-03-2               Observed an appropriately sized fire extinguisher is missing. For reporting                    61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                      purposes only.no proper size fire extinguisher s on site, tenents say no                       Extinguisher Installation -- Fire extinguishers shall be
                      extinguisher s in the units while I was conducting the unnanounced inspection                  installed in accordance with NFPA 10, Standard for
                      thus is a reporting to the AHJ observation only                                                Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                     include guest room areas of hotels/motels, etc. [These
                                                                                                                     locations shall be protected by the installation of potable
                                                                                                                     fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                     provided for each 3000 square feet of floor space on
                                                                                                                     each level and installed so that the travel distance to
                                                                                                                     any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                     level, the area protected and the travel distances shall
                                                                                                                     be based of fire extinguishers installed in accordance
                                                                                                                     with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                     PURPOSES ONLY.

License Number: 1502749                                            DAYS INN
License Type: Motel                                                5600 SR 524, COCOA 32926

   Inspection Date: 09/17/2008              Inspection Number: 1127763              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: PFISTER, JOHN                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                    Violation Citation

06-07-2               Observed the floor diagram evacuation route is missing in second floor                         NFPA 101, 28-7.4.1 [Transient Establishments - Fire
                      rooms253,258,. For reporting purposes only.                                                    Evacuation Requirements] A floor diagram reflecting
                                                                                                                     the actual floor arrangement, exit locations, and room
                                                                                                                     identification shall be posted in a location and manner
                                                                                                                     acceptable to the authority having jurisdiction on or
                                                                                                                     immediately adjacent to every guest room door in hotels
                                                                                                                     and should be oriented with the actual direction to the
                                                                                                                     exits. FOR REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                               Page 3
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Broward County

License Number: 1607162                                              BEST WESTERN HALLANDALE INN
License Type: Motel                                                  101 ANSIN BLVD, HALLANDALE 330093992

   Inspection Date: 09/17/2008               Inspection Number: 1134606              Inspection Type: Complaint Full                        Inspection Disposition: Inspection
   Inspector Name: CONSIGLIO, CAMILLE                                                                                                       Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

08-03                 Observed no boiler certificate available.                                                        61C-1.004(12) FAC The insurance inspector's boiler
                                                                                                                       report is required annually for power boilers and high
                      Boiler Information: No Boiler Certificate Provided.                                              pressure/high temperature boilers and biannually for low
                                                                                                                       pressure steam or vapor heating boilers and shall be
                                                                                                                       posted in the boiler room. The provisions of this section
                                                                                                                       do not apply to the common areas of resort
                                                                                                                       condominiums.

License Number: 1603326                                              ENTRADA MOTEL
License Type: Motel                                                  509 N FEDERAL HWY, HOLLYWOOD 33020

   Inspection Date: 09/17/2008               Inspection Number: 1123765              Inspection Type: Routine - Lodging                     Inspection Disposition: Inspection
   Inspector Name: CHAPDELAINE, MARIE                                                                                                       Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.                    61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                       meter rooms, laundry rooms, and storage rooms shall
                                                                                                                       be kept clean and free of debris and flammables. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

02-02-2               Observed flammable material stored in attic/laundry/boiler room. For reporting                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                      purposes only--dried branches                                                                    meter rooms, laundry rooms, and storage rooms shall
                       in gas water heater room.                                                                       be kept clean and free of debris and flammables. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

07-02-2               Observed an extension cord in use. For reporting purposes only-tv.                               61C-1.004(11) FAC No extension cords shall be used
                                                                                                                       except during cleaning, maintenance and other
                                                                                                                       temporary activities. FOR REPORTING PURPOSES
                                                                                                                       ONLY.

License Number: 1620768                                              SURF N SPRAY I
License Type: Motel                                                  1932 TAFT ST, HOLLYWOOD 33020

   Inspection Date: 09/18/2008               Inspection Number: 1128133              Inspection Type: Routine - Lodging                     Inspection Disposition: Warning
   Inspector Name: CHAPDELAINE, MARIE                                                                                                       Issued

Violation Code        Observation                                                                                      Violation Citation

04-15-2               Observed no completed/up to date smoke detector log for the battery powered                      69A-43.009(1)(b)(c)FAC Battery powered, single station
                      smoke detectors. For reporting purposes only.                                                    smoke detectors, where used, shall be tested and
                                                                                                                       inspected not less frequently than once per week. A log
                                                                                                                       of the required tests and inspections shall be kept and
                                                                                                                       available to the authority having jurisdiction at any time.
                                                                                                                       This log shall include, but not be limited to, the following
                                                                                                                       information and any other information as may be
                                                                                                                       required by the authority having jurisdiction; 1. A list,
                                                                                                                       clearly identifying each individual detector by its physical
                                                                                                                       location. 2. The date of each required test and
                                                                                                                       inspection. 3. The identity and signature of the
                                                                                                                       inspector. 4. The result of each test and inspection. 5.
                                                                                                                       The completion date and form of any maintenance
                                                                                                                       performed. 6. The completion date and form of any
                                                                                                                       corrective measures taken for each improperly
                                                                                                                       functioning device. 7. A copy of the manufacturer's
                                                                                                                       recommended maintenance schedule and procedures.
                                                                                                                       (c) At such time that the authority having jurisdiction
                                                                                                                       finds cause to believe that the requirements of (a) or (b)
                                                                                                                       are not being fulfilled, detectors powered by the building
                                                                                                                       electrical system shall be required. FOR REPORTING
                                                                                                                       PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                                  Page 4
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Broward County

License Number: 1601945                                               NEW KENT MOTEL
License Type: Motel                                                   1120 S FEDERAL HWY, HOLLYWOOD 330206028

   Inspection Date: 09/17/2008                Inspection Number: 1124515                 Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: CHAPDELAINE, MARIE                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                         Violation Citation

02-02-2               Observed flammable material stored in attic/laundry/boiler room. For reporting                      61C-1.004(7) FAC Attics, basements, boiler rooms,
                      purposes only--wood doors and shelves leaning on gas tank..                                         meter rooms, laundry rooms, and storage rooms shall
                                                                                                                          be kept clean and free of debris and flammables. FOR
                                                                                                                          REPORTING PURPOSES ONLY.

06-07-2               Observed the floor diagram is missing/incorrect. For reporting purposes only.                       NFPA 101, 28-7.4.1 [Transient Establishments - Fire
                                                                                                                          Evacuation Requirements] A floor diagram reflecting
                                                                                                                          the actual floor arrangement, exit locations, and room
                                                                                                                          identification shall be posted in a location and manner
                                                                                                                          acceptable to the authority having jurisdiction on or
                                                                                                                          immediately adjacent to every guest room door in hotels
                                                                                                                          and should be oriented with the actual direction to the
                                                                                                                          exits. FOR REPORTING PURPOSES ONLY.

License Number: 1605407                                               HOLLYWOOD COURTYARD APTS WEST
License Type: Apartment                                               4928 HOLLYWOOD BLVD, HOLLYWOOD 33021

   Inspection Date: 09/12/2008                Inspection Number: 1204238                 Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: PROCTOR, JORGE                                                                                                              Completed - No Further Action

Violation Code        Observation                                                                                         Violation Citation

06-04-2               Observed an inadequately marked exit. Exit sign on the left side of the building,                   61-C1.004(10) FAC Exits shall be clearly marked with
                      second level, by the front stairs, has arrows pointing to the left and right direction.             approved illuminated exit signs. FOR REPORTING
                      But there is only a left exit. For reporting purposes only.                                         PURPOSES ONLY.

License Number: 1605685                                               LOMAR APARTMENTS
License Type: Apartment                                               4933 HOLLYWOOD BLVD, HOLLYWOOD 330216527

   Inspection Date: 09/12/2008                Inspection Number: 1220379                 Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: PROCTOR, JORGE                                                                                                              Completed - No Further Action

Violation Code        Observation                                                                                         Violation Citation

02-02-2               Observed a build up of lint in the lower level laundry room. For reporting purposes                 61C-1.004(7) FAC Attics, basements, boiler rooms,
                      only.                                                                                               meter rooms, laundry rooms, and storage rooms shall
                                                                                                                          be kept clean and free of debris and flammables. FOR
                                                                                                                          REPORTING PURPOSES ONLY.

License Number: 1620854                                               HOLIDAY INN EXPRESS HOTEL & SUITES
License Type: Hotel                                                   14651 NW 20 ST, PEMBROKE PINES 33028

   Inspection Date: 09/17/2008                Inspection Number: 1099161                 Inspection Type: Lodging-Licensing                    Inspection Disposition: Inspection
   Inspector Name: PROCTOR, JORGE                                                        Inspection                                            Completed - No Further Action

Violation Code        Observation                                                                                         Violation Citation

06-16-2               Observed the stair signage is inadequate/not provided. No exit sign with the                        NFPA 101, 7-2.2.5.4 Stairs serving five or more stories
                      direction of the exit posted. For reporting purposes only.                                          shall be provided with signage within the enclosure at
                                                                                                                          each floor landing. The signage shall indicate the floor
                                                                                                                          level, the terminus of the top and bottom of the stair
                                                                                                                          enclosure, and the identification of the stair. The
                                                                                                                          signage also shall state the floor level of, and the direct
                                                                                                                          to, exit discharge. The signage shall be inside the
                                                                                                                          enclosure, located approximately 5 ft above the floor
                                                                                                                          landing in a position that is readily visible when the door
                                                                                                                          is in the open or closed position. FOR REPORTING
                                                                                                                          PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 5
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Broward County

License Number: 1604697                                             CHATEAU ARMS
License Type: Apartment                                             1131 NE 25 AVE, POMPANO BEACH 33060

   Inspection Date: 09/16/2008               Inspection Number: 1218207              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: NUTTALL, JOHN                                                                                                           Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

06-01-2               Observed an exit path blocked. For reporting purposes only. Outside number 1A                   61C-1.004(6) FAC All building structural components,
                      stairway blocked.                                                                               attachments and fixtures shall be kept free of
                                                                                                                      obstructions. FOR REPORTING PURPOSES ONLY.

License Number: 1618827                                             KOOL APARTMENTS IV
License Type: Apartment                                             1300 NW 2 AVE, POMPANO BEACH 33060

   Inspection Date: 09/15/2008               Inspection Number: 1209084              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: NUTTALL, JOHN                                                                                                           Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

01-09-2               Observed a fire extinguisher pressure gauge indicating the extinguisher is in need              NFPA 10,1-6.2 Portable extinguishers shall be
                      of recharge. For reporting purposes only. Outside number 7                                      maintained in a fully charged and operable condition.
                                                                                                                      FOR REPORTING PURPOSES ONLY.

License Number: 1602907                                             COUNTRY HAVEN MOTEL
License Type: Motel                                                 1100 N SR 7, MARGATE 33063

   Inspection Date: 09/17/2008               Inspection Number: 1123057              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DIEHL, TERRENCE                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

04-01-2               Observed a smoke detector not functioning when tested. For reporting purposes                   61C-1.004(5)FAC All fire safety, protection and
                      only. Corrected On Site.                                                                        prevention equipment must be installed, approved,
                                                                                                                      maintained and used in accordance with Chapter 509,
                                                                                                                      FS and the National Fire Protection Association Life
                                                                                                                      Safety Code Chapter 101, as adopted by the Division of
                                                                                                                      State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

License Number: 1607829                                             COCO PALMS APT
License Type: Apartment                                             2131 NE 41 ST, LIGHTHOUSE POINT 33064

   Inspection Date: 09/15/2008               Inspection Number: 1213609              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: EARP, NICOLETTE                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                      meter rooms, laundry rooms, and storage rooms shall
                                                                                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

License Number: 1606055                                             OASIS APARTMENTS
License Type: Apartment                                             8500 NW 40 ST, CORAL SPRINGS 33065

   Inspection Date: 09/16/2008               Inspection Number: 1218201              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BECKER, ROBERT                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                      meter rooms, laundry rooms, and storage rooms shall
                                                                                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                                 Page 6
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Broward County

License Number: 1612710                                             ATLANTIC INN
License Type: Motel                                                 151 NW 17 AVE, POMPANO BEACH 33069

   Inspection Date: 09/15/2008               Inspection Number: 1123048               Inspection Type: Routine - Lodging                     Inspection Disposition: Inspection
   Inspector Name: NUTTALL, JOHN                                                                                                             Completed - No Further Action

Violation Code        Observation                                                                                       Violation Citation

04-01-2               Observed a smoke detector not functioning when tested. For reporting purposes                     61C-1.004(5)FAC All fire safety, protection and
                      only.116.                                                                                         prevention equipment must be installed, approved,
                                                                                                                        maintained and used in accordance with Chapter 509,
                                                                                                                        FS and the National Fire Protection Association Life
                                                                                                                        Safety Code Chapter 101, as adopted by the Division of
                                                                                                                        State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                        REPORTING PURPOSES ONLY.

04-01-2               Observed an alarm silenced on the fire alarm control panel. For reporting                         61C-1.004(5)FAC All fire safety, protection and
                      purposes only. Maintenance being worked on.                                                       prevention equipment must be installed, approved,
                                                                                                                        maintained and used in accordance with Chapter 509,
                                                                                                                        FS and the National Fire Protection Association Life
                                                                                                                        Safety Code Chapter 101, as adopted by the Division of
                                                                                                                        State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                        REPORTING PURPOSES ONLY.

License Number: 1620628                                             THE PRESERVE AT COCONUT CREEK
License Type: Apartment                                             4804 N ST RD 7, COCONUT CREEK 33073

   Inspection Date: 09/12/2008               Inspection Number: 1198217               Inspection Type: Routine - Lodging                     Inspection Disposition: Call Back -
   Inspector Name: DIEHL, TERRENCE                                                                                                           Admin. complaint recommended

Violation Code        Observation                                                                                       Violation Citation

03-04                 Violation: 03-04                                                                                  NFPA 25, 1-8 Records Records. Records of
                                                                                                                        inspections, tests, and maintenance of the system and
                      Observed no inspection report available for the fire sprinkler system.                            its components shall be made available to the authority
                                                                                                                        having jurisdiction upon request. Typical records
                                                                                                                        include, but are not limited to, valve inspections; flow,
                                                                                                                        drain, and pump tests; and trip tests of dry pipe, deluge,
                                                                                                                        and preaction valves.

04-01                 Violation: 04-01                                                                                  61C-1.004(5)FAC All fire safety, protection and
                                                                                                                        prevention equipment must be installed, approved,
                      Observed a trouble/alarm light illuminated on the smoke detector panel connected                  maintained and used in accordance with Chapter 509,
                      to the fire alarm system. BLDG#1; BLDG#8; BLDG#11;                                                FS and the National Fire Protection Association Life
                                                                                                                        Safety Code Chapter 101, as adopted by the Division of
                                                                                                                        State Fire Marshal in Chapter 4A-3, FAC.

06-04                 Violation: 06-04                                                                                  61-C1.004(10) FAC Exits shall be clearly marked with
                                                                                                                        approved illuminated exit signs.
                      Observed an exit sign that is not visible/obstructed from view. GIVES
                      INCORRECT DIRECTIONAL INFORMATION: BLDG#1-205;

License Number: 1601872                                             SEA CLUB OCEAN RESORT HOTEL
License Type: Hotel                                                 619 N ATLANTIC BLVD, FORT LAUDERDALE 33304-4127

   Inspection Date: 09/12/2008               Inspection Number: 1105039               Inspection Type: Complaint Full                        Inspection Disposition: Warning
   Inspector Name: TORRES, LARRY                                                                                                             Issued

Violation Code        Observation                                                                                       Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.                     61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                        meter rooms, laundry rooms, and storage rooms shall
                                                                                                                        be kept clean and free of debris and flammables. FOR
                                                                                                                        REPORTING PURPOSES ONLY.

06-02-2               Observed a blocked exit. For reporting purposes only. emergency exit where                        61C-1.004(10) FAC Means of access must permit
                      beach chairs and a vacuum cleaner are stored                                                      unobstructed travel at all times and be maintained free
                                                                                                                        of obstructions. FOR REPORTING PURPOSES ONLY.

06-07-2               Observed the floor diagram is missing. room 410 .For reporting purposes only.                     NFPA 101, 28-7.4.1 [Transient Establishments - Fire
                                                                                                                        Evacuation Requirements] A floor diagram reflecting
                                                                                                                        the actual floor arrangement, exit locations, and room
                                                                                                                        identification shall be posted in a location and manner
                                                                                                                        acceptable to the authority having jurisdiction on or
                                                                                                                        immediately adjacent to every guest room door in hotels
                                                                                                                        and should be oriented with the actual direction to the
                                                                                                                        exits. FOR REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 7
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Broward County

License Number: 1605676                                             2850 NE 30 PL APARTMENTS
License Type: Apartment                                             2850 NE 30 PL, FT LAUDERDALE 333061911

   Inspection Date: 09/11/2008               Inspection Number: 1218177              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MULLINGS, SEANTELE                                                                                                      Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

04-13-2               Observed no inspection report available for the fire alarm system. For reporting                NFPA 72, 7-5.2.2 A permanent record of all inspections,
                      purposes only.                                                                                  testing, and maintenance shall be provided that includes
                                                                                                                      the following information of periodic tests and all
                                                                                                                      applicable information requested in Figure 7-5.2.2. (a)
                                                                                                                      Date; (b) Test frequency; (c) Name of property; (d)
                                                                                                                      Address; (e) Name of person performing inspection,
                                                                                                                      maintenance, tests, or combination thereof, and
                                                                                                                      affiliation, business address, and telephone number; (f)
                                                                                                                      Name, address, and representative of approving
                                                                                                                      agency(ies); (g) Designation of the detector(s) tested;
                                                                                                                      (h) Functional test of detectors; (i) Functional test of
                                                                                                                      required sequence of operations; (j) Check of all smoke
                                                                                                                      detectors; (k) Loop resistance for all fixed-temperature
                                                                                                                      line-type heat detectors; (l) Other tests as required by
                                                                                                                      equipment manufacturers; (m) Other tests as required
                                                                                                                      by the authority having jurisdiction; (n) Signatures of
                                                                                                                      tester and approved authority representative; (o)
                                                                                                                      Disposition of problems identified during testing (e.g.,
                                                                                                                      owner notified, problem, corrected/successfully
                                                                                                                      retested, device abondoned in place). FOR
                                                                                                                      REPORTING PURPOSES ONLY.

License Number: 1620717                                             B SEASIDE
License Type: Apartment                                             4609 N OCEAN DR, LAUDERDALE-BY-THE-SE 33308

   Inspection Date: 09/17/2008               Inspection Number: 1220603              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MULLINGS, SEANTELE                                                                                                      Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

01-09-2               Observed a fire extinguisher pressure gauge indicating the extinguisher is in need              NFPA 10,1-6.2 Portable extinguishers shall be
                      of recharge. For reporting purposes only. 2nd floor                                             maintained in a fully charged and operable condition.
                                                                                                                      FOR REPORTING PURPOSES ONLY.

License Number: 1604193                                             LA CELE MOTEL
License Type: Motel                                                 4553 N OCEAN DR, LAUDERDALE BY SEA 33308-3610

   Inspection Date: 09/12/2008               Inspection Number: 1124545              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: GROSVENOR, SEAN                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed flammable material stored in meter room. For reporting purposes only.                  61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                      meter rooms, laundry rooms, and storage rooms shall
                                                                                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

02-04-2               Observed an LP gas tank having a water capacity greater than 2 1/2 lbs.stored by                NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                      building . For reporting purposes only.                                                         capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                      located on balconies above the first floor that are
                                                                                                                      attached to a multiple family dwelling of 3 or more living
                                                                                                                      units one above the other. Exception: Where such
                                                                                                                      balconies are served by outside stairways and where
                                                                                                                      only such stairways are used to transport the container.
                                                                                                                      FOR REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                           Page 8
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Broward County

License Number: 1605084                                          COUNTRY CLUB GOLF APTS
License Type: Apartment                                          4737 NE 25 AVE, FT LAUDERDALE 333084863

   Inspection Date: 09/17/2008            Inspection Number: 1215798              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MULLINGS, SEANTELE                                                                                                   Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-03-2            Observed an appropriately sized fire extinguisher is missing. For reporting                     61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only. by unit 104                                                                      Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                   installed in accordance with NFPA 10, Standard for
                                                                                                                   Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                   include guest room areas of hotels/motels, etc. [These
                                                                                                                   locations shall be protected by the installation of potable
                                                                                                                   fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                   provided for each 3000 square feet of floor space on
                                                                                                                   each level and installed so that the travel distance to
                                                                                                                   any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                   level, the area protected and the travel distances shall
                                                                                                                   be based of fire extinguishers installed in accordance
                                                                                                                   with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

License Number: 1601212                                          LA FONTANA APTS
License Type: Apartment                                          5641 NE 18 AVE, FT LAUDERDALE 333346204

   Inspection Date: 09/17/2008            Inspection Number: 1206991              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: SCHNEIDER, MICHELE                                                                                                   Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

04-10-2            Observed the fire alarm panel with an expired inspection tag. For reporting                     NFPA 72 7-3.2 and TABLE 7-3.2 Testing shall be
                   purposes only,3/05 has a green light all normal.                                                performed in accordance with the schedules in Chapter
                                                                                                                   7 or more often if required by the authority having
                                                                                                                   jurisdiction. If automatic testing is performed at least
                                                                                                                   weekly by a remotely monitored fire alarm control unit
                                                                                                                   specifically listed for the application, the manual testing
                                                                                                                   frequency shall be permitted to be extended to annual.
                                                                                                                   Table 7-3.2 shall apply. All components must be tested
                                                                                                                   upon acceptance and at least annually. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

04-13-2            Observed no inspection report available for the fire alarm system. For reporting                NFPA 72, 7-5.2.2 A permanent record of all inspections,
                   purposes only.                                                                                  testing, and maintenance shall be provided that includes
                                                                                                                   the following information of periodic tests and all
                                                                                                                   applicable information requested in Figure 7-5.2.2. (a)
                                                                                                                   Date; (b) Test frequency; (c) Name of property; (d)
                                                                                                                   Address; (e) Name of person performing inspection,
                                                                                                                   maintenance, tests, or combination thereof, and
                                                                                                                   affiliation, business address, and telephone number; (f)
                                                                                                                   Name, address, and representative of approving
                                                                                                                   agency(ies); (g) Designation of the detector(s) tested;
                                                                                                                   (h) Functional test of detectors; (i) Functional test of
                                                                                                                   required sequence of operations; (j) Check of all smoke
                                                                                                                   detectors; (k) Loop resistance for all fixed-temperature
                                                                                                                   line-type heat detectors; (l) Other tests as required by
                                                                                                                   equipment manufacturers; (m) Other tests as required
                                                                                                                   by the authority having jurisdiction; (n) Signatures of
                                                                                                                   tester and approved authority representative; (o)
                                                                                                                   Disposition of problems identified during testing (e.g.,
                                                                                                                   owner notified, problem, corrected/successfully
                                                                                                                   retested, device abondoned in place). FOR
                                                                                                                   REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                          Page 9
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Broward County

License Number: 1620183                                         VILLAS BY THE BEACH
License Type: Apartment                                         1920 NE 5 ST, DEERFIELD BCH 33441

   Inspection Date: 09/16/2008           Inspection Number: 1204501              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: EARP, NICOLETTE                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

02-04-2            Observed an LP gas tank stored next to building. For reporting purposes only.                  NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                                                                                                                  capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                  located on balconies above the first floor that are
                                                                                                                  attached to a multiple family dwelling of 3 or more living
                                                                                                                  units one above the other. Exception: Where such
                                                                                                                  balconies are served by outside stairways and where
                                                                                                                  only such stairways are used to transport the container.
                                                                                                                  FOR REPORTING PURPOSES ONLY.

License Number: 1602188                                         GOLDEN SANDS CO
License Type: Apartment                                         512 SE 20 AVE, DEERFIELD BEACH 33441

   Inspection Date: 09/16/2008           Inspection Number: 1218246              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: EARP, NICOLETTE                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-01-2            Observed a fire extinguisher pressure gauge indicating the extinguisher is                     61C-1.004(5) FAC All fire safety, protection and
                   overcharged. For reporting purposes only.                                                      prevention equipment must be installed, approved,
                                                                                                                  maintained and used in accordance with Chapter 509,
                                                                                                                  FS, and the National Fire Protection Association Life
                                                                                                                  Safety Code Chapter 101, as adopted by the Division of
                                                                                                                  State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                  REPORTING PURPOSES ONLY.

02-02-2            Observed flammable material stored in attic/laundry/boiler room. For reporting                 61C-1.004(7) FAC Attics, basements, boiler rooms,
                   purposes only.                                                                                 meter rooms, laundry rooms, and storage rooms shall
                                                                                                                  be kept clean and free of debris and flammables. FOR
                                                                                                                  REPORTING PURPOSES ONLY.

06-01-2            Observed an exit path blocked. For reporting purposes only.                                    61C-1.004(6) FAC All building structural components,
                                                                                                                  attachments and fixtures shall be kept free of
                                                                                                                  obstructions. FOR REPORTING PURPOSES ONLY.

License Number: 1620759                                         OCEAN VILLA RESORT INC
License Type: Apartment                                         317 SE 20 AVE, DEERFIELD BEACH 33441

   Inspection Date: 09/16/2008           Inspection Number: 1204503              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: EARP, NICOLETTE                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

06-01-2            Observed an exit path blocked observed on 2nd floor. For reporting purposes                    61C-1.004(6) FAC All building structural components,
                   only.                                                                                          attachments and fixtures shall be kept free of
                                                                                                                  obstructions. FOR REPORTING PURPOSES ONLY.

License Number: 1600558                                         BELCLARE ON EIGTH
License Type: Apartment                                         1911 SE 8 ST, DEERFIELD BCH 334415007

   Inspection Date: 09/17/2008           Inspection Number: 1206768              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: EARP, NICOLETTE                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

06-04-2            Observed an unmarked exit. For reporting purposes only.                                        61-C1.004(10) FAC Exits shall be clearly marked with
                                                                                                                  approved illuminated exit signs. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

07-06-2            Observed an electrical outlet missing a cover plate. For reporting purposes only.              NFPA 70, 300-31 Suitable covers shall be installed on
                                                                                                                  all boxes to prevent accidental contact with energized
                                                                                                                  parts or physical damage to parts or insulation. FOR
                                                                                                                  REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                          Page 10
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Broward County

License Number: 1604419                                         VILLA MARIA
License Type: Apartment                                         756 SE 19 AVE, DEERFIELD BCH 334415032

   Inspection Date: 09/17/2008           Inspection Number: 1204497              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: EARP, NICOLETTE                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-09-2            Observed a fire extinguisher pressure gauge indicating the extinguisher is in need             NFPA 10,1-6.2 Portable extinguishers shall be
                   of recharge. For reporting purposes only.                                                      maintained in a fully charged and operable condition.
                                                                                                                  FOR REPORTING PURPOSES ONLY.

License Number: 1614871                                         BLOCK TO BEACH INN
License Type: Apartment                                         381 SE 20 AVE, DEERFIELD BCH 334415123

   Inspection Date: 09/17/2008           Inspection Number: 1218245              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: EARP, NICOLETTE                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

06-01-2            Observed an exit path blocked. For reporting purposes only.                                    61C-1.004(6) FAC All building structural components,
                                                                                                                  attachments and fixtures shall be kept free of
                                                                                                                  obstructions. FOR REPORTING PURPOSES ONLY.

06-04-2            Observed an unmarked exit. For reporting purposes only.                                        61-C1.004(10) FAC Exits shall be clearly marked with
                                                                                                                  approved illuminated exit signs. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

License Number: 1604798                                         PICTURE APARTMENTS
License Type: Apartment                                         2037 SE 3 ST, DEERFIELD BCH 334415149

   Inspection Date: 09/17/2008           Inspection Number: 1220658              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: EARP, NICOLETTE                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

06-04-2            Observed an unmarked exit. For reporting purposes only.                                        61-C1.004(10) FAC Exits shall be clearly marked with
                                                                                                                  approved illuminated exit signs. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

07-01-2            Observed frayed wire(s). For reporting purposes only.                                          61C-1.004(11)FAC Electrical wiring - To prevent fire or
                                                                                                                  injury, defective electrical wiring shall be replaced and
                                                                                                                  wiring shall be kept in good repair. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

License Number: 1607355                                         VILLA P APTS
License Type: Apartment                                         2019 SE 5 ST, DEERFIELD BCH 334415185

   Inspection Date: 09/17/2008           Inspection Number: 1215850              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: EARP, NICOLETTE                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

07-06-2            Observed an electrical outlet missing a cover plate. For reporting purposes only.              NFPA 70, 300-31 Suitable covers shall be installed on
                                                                                                                  all boxes to prevent accidental contact with energized
                                                                                                                  parts or physical damage to parts or insulation. FOR
                                                                                                                  REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                               Page 11
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Collier County

License Number: 2102346                                              JASMINE CAY APARTMENTS
License Type: Apartment                                              100 JASMINE CIR, NAPLES 34102

   Inspection Date: 09/15/2008               Inspection Number: 1222009               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MORRIS, CHARLES                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

04-15-2               Observed no completed/up to date smoke detector log for the battery powered                      69A-43.009(1)(b)(c)FAC Battery powered, single station
                      smoke detectors. For reporting purposes only.                                                    smoke detectors, where used, shall be tested and
                                                                                                                       inspected not less frequently than once per week. A log
                                                                                                                       of the required tests and inspections shall be kept and
                                                                                                                       available to the authority having jurisdiction at any time.
                                                                                                                       This log shall include, but not be limited to, the following
                                                                                                                       information and any other information as may be
                                                                                                                       required by the authority having jurisdiction; 1. A list,
                                                                                                                       clearly identifying each individual detector by its physical
                                                                                                                       location. 2. The date of each required test and
                                                                                                                       inspection. 3. The identity and signature of the
                                                                                                                       inspector. 4. The result of each test and inspection. 5.
                                                                                                                       The completion date and form of any maintenance
                                                                                                                       performed. 6. The completion date and form of any
                                                                                                                       corrective measures taken for each improperly
                                                                                                                       functioning device. 7. A copy of the manufacturer's
                                                                                                                       recommended maintenance schedule and procedures.
                                                                                                                       (c) At such time that the authority having jurisdiction
                                                                                                                       finds cause to believe that the requirements of (a) or (b)
                                                                                                                       are not being fulfilled, detectors powered by the building
                                                                                                                       electrical system shall be required. FOR REPORTING
                                                                                                                       PURPOSES ONLY.

License Number: 2102299                                              BEST WESTERN HOTEL & SUITES
License Type: Motel                                                  6400 DUDLEY DR, NAPLES 34105

   Inspection Date: 09/18/2008               Inspection Number: 1125124               Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: MORRIS, CHARLES                                                                                                          Issued

Violation Code        Observation                                                                                      Violation Citation

08-03                 Observed a boiler certificate is not posted in the boiler room. unable to obtain data            61C-1.004(12) FAC The insurance inspector's boiler
                                                                                                                       report is required annually for power boilers and high
                      Boiler Information: No Boiler Certificate Provided.                                              pressure/high temperature boilers and biannually for low
                                                                                                                       pressure steam or vapor heating boilers and shall be
                                                                                                                       posted in the boiler room. The provisions of this section
                                                                                                                       do not apply to the common areas of resort
                                                                                                                       condominiums.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 12
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Columbia County

License Number: 2200067                                             MOTEL 8
License Type: Motel                                                 4427 SW SR 47, LAKE CITY 32024

   Inspection Date: 09/10/2008               Inspection Number: 1126309              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: FULTON, DANIEL                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

07-06-2               Out of compliance: Suitable covers shall be installed on all boxes to prevent                   NFPA 70, 300-31 Suitable covers shall be installed on
                      accidental contact with energized parts or physical damage to parts or insulation.              all boxes to prevent accidental contact with energized
                      FOR REPORTING PURPOSES ONLY.                                                                    parts or physical damage to parts or insulation. FOR
                                                                                                                      REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                           Page 13
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2310005                                          AUDY UNISON LLC
License Type: Apartment                                          101- 111 W 11 ST, HIALEAH 33010

   Inspection Date: 09/15/2008            Inspection Number: 1217532              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BRADOR, MOISES                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

02-02-2            Observed a build up of lint in the laundry room. For reporting purposes only.                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                   meter rooms, laundry rooms, and storage rooms shall
                                                                                                                   be kept clean and free of debris and flammables. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

02-04-2            Observed an LP gas tank having a water capacity greater than 2 1/2 lbs. on a                    NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                   balcony. For reporting purposes only.                                                           capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                   located on balconies above the first floor that are
                                                                                                                   attached to a multiple family dwelling of 3 or more living
                                                                                                                   units one above the other. Exception: Where such
                                                                                                                   balconies are served by outside stairways and where
                                                                                                                   only such stairways are used to transport the container.
                                                                                                                   FOR REPORTING PURPOSES ONLY.

License Number: 2311094                                          SAN SHERRI SOUTH
License Type: Apartment                                          1345 W 28 ST, HIALEAH 33010

   Inspection Date: 09/17/2008            Inspection Number: 1219996              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BRADOR, MOISES                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

02-02-2            Observed a build up of lint in the laundry room. For reporting purposes only.                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                   meter rooms, laundry rooms, and storage rooms shall
                                                                                                                   be kept clean and free of debris and flammables. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

License Number: 2312038                                          LOS PORTALES
License Type: Apartment                                          202 EAST 3 STREET, HIALEAH 33010

   Inspection Date: 09/17/2008            Inspection Number: 1208473              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BRADOR, MOISES                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-06-2            Observed a locked fire extinguisher box missing a breaking device. For reporting                NFPA 10,1-6.5 Cabinets housing fire extinguishers shall
                   purposes only.                                                                                  not be locked. Except locked cabinets may be used
                                                                                                                   provided they include means of emergency access.
                                                                                                                   FOR REPORTING PURPOSES ONLY.

License Number: 2318417                                          RB2 HOLDINGS LLC
License Type: Apartment                                          55 W 6 ST, HIALEAH 33010

   Inspection Date: 09/16/2008            Inspection Number: 1240029              Inspection Type: Lodging-Licensing                    Inspection Disposition: Inspection
   Inspector Name: BRADOR, MOISES                                                 Inspection                                            Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-06-2            Observed a locked fire extinguisher box missing a breaking device. For reporting                NFPA 10,1-6.5 Cabinets housing fire extinguishers shall
                   purposes only.                                                                                  not be locked. Except locked cabinets may be used
                                                                                                                   provided they include means of emergency access.
                                                                                                                   FOR REPORTING PURPOSES ONLY.

License Number: 2326331                                          RUBEN ARMAS
License Type: Apartment                                          130 WEST 11 ST, HIALEAH 33010

   Inspection Date: 09/15/2008            Inspection Number: 1220000              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BRADOR, MOISES                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

02-02-2            Observed a build up of lint in the laundry room. For reporting purposes only.                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                   meter rooms, laundry rooms, and storage rooms shall
                                                                                                                   be kept clean and free of debris and flammables. FOR
                                                                                                                   REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                           Page 14
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2328204                                         3RD STREET APARTMENTS INC
License Type: Apartment                                         147 W 12 ST, HIALEAH 33010

   Inspection Date: 09/15/2008           Inspection Number: 1215252               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BRADOR, MOISES                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-06-2            Observed a locked fire extinguisher box missing a breaking device. For reporting                NFPA 10,1-6.5 Cabinets housing fire extinguishers shall
                   purposes only.                                                                                  not be locked. Except locked cabinets may be used
                                                                                                                   provided they include means of emergency access.
                                                                                                                   FOR REPORTING PURPOSES ONLY.

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only.                         NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                   maintenance not more than one year apart. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

02-04-2            Observed an LP gas tank having a water capacity greater than 2 1/2 lbs. on a                    NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                   balcony. For reporting purposes only.                                                           capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                   located on balconies above the first floor that are
                                                                                                                   attached to a multiple family dwelling of 3 or more living
                                                                                                                   units one above the other. Exception: Where such
                                                                                                                   balconies are served by outside stairways and where
                                                                                                                   only such stairways are used to transport the container.
                                                                                                                   FOR REPORTING PURPOSES ONLY.

License Number: 2328228                                         GONZALEZ APARTMENTS
License Type: Apartment                                         137 W 6 ST, HIALEAH 33010

   Inspection Date: 09/15/2008           Inspection Number: 1203866               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BRADOR, MOISES                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-03-2            Observed an appropriately sized fire extinguisher is missing. For reporting                     61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                  Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                   installed in accordance with NFPA 10, Standard for
                                                                                                                   Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                   include guest room areas of hotels/motels, etc. [These
                                                                                                                   locations shall be protected by the installation of potable
                                                                                                                   fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                   provided for each 3000 square feet of floor space on
                                                                                                                   each level and installed so that the travel distance to
                                                                                                                   any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                   level, the area protected and the travel distances shall
                                                                                                                   be based of fire extinguishers installed in accordance
                                                                                                                   with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

License Number: 2329017                                         DEL REY APTS
License Type: Apartment                                         118 W 6 ST, HIALEAH 33010

   Inspection Date: 09/15/2008           Inspection Number: 1217567               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BRADOR, MOISES                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only.                         NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                   maintenance not more than one year apart. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

License Number: 2307019                                         320 W 20 ST APTS
License Type: Apartment                                         320 W 20 ST, HIALEAH 330102534

   Inspection Date: 09/18/2008           Inspection Number: 1215236               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BRADOR, MOISES                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only.                         NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                   maintenance not more than one year apart. FOR
                                                                                                                   REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                          Page 15
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2309032                                         E & G REALTY APTS
License Type: Apartment                                         179 W 9 ST, HIALEAH 330104085

   Inspection Date: 09/16/2008           Inspection Number: 1212940              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BRADOR, MOISES                                                                                                      Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-06-2            Observed a locked fire extinguisher box missing a breaking device. For reporting               NFPA 10,1-6.5 Cabinets housing fire extinguishers shall
                   purposes only.                                                                                 not be locked. Except locked cabinets may be used
                                                                                                                  provided they include means of emergency access.
                                                                                                                  FOR REPORTING PURPOSES ONLY.

License Number: 2310405                                         ABRANTES APTS
License Type: Apartment                                         180 E 9 ST, HIALEAH 330104243

   Inspection Date: 09/16/2008           Inspection Number: 1206127              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BRADOR, MOISES                                                                                                      Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

02-04-2            Observed an LP gas tank having a water capacity greater than 2 1/2 lbs. on a                   NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                   balcony. For reporting purposes only.                                                          capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                  located on balconies above the first floor that are
                                                                                                                  attached to a multiple family dwelling of 3 or more living
                                                                                                                  units one above the other. Exception: Where such
                                                                                                                  balconies are served by outside stairways and where
                                                                                                                  only such stairways are used to transport the container.
                                                                                                                  FOR REPORTING PURPOSES ONLY.

License Number: 2304889                                         MAGGIES HOUSE INVESTMENTS LLC
License Type: Apartment                                         1440 W 29 STREET, HIALEAH 33012

   Inspection Date: 09/18/2008           Inspection Number: 1210739              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                 Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-05-2            Observed a fire extinguisher obscured from view. For reporting purposes only.                  NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                  obscured or obstructed from view. Except in large
                                                                                                                  rooms and in certain locations where visual obstruction
                                                                                                                  can not be completely avoided, a means shall be
                                                                                                                  provided to indicate location. FOR REPORTING
                                                                                                                  PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                           Page 16
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2328279                                          BELLAMAR INVESTMENTS APARTMNTS
License Type: Apartment                                          1475 W 39 PL, HIALEAH 33012

   Inspection Date: 09/16/2008            Inspection Number: 1210731              Inspection Type: Routine - Lodging                    Inspection Disposition: Administrative
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                  complaint recommended

Violation Code     Observation                                                                                     Violation Citation

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only.                         NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                   maintenance not more than one year apart. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

04-10-2            Observed the fire alarm panel with an expired inspection tag. For reporting                     NFPA 72 7-3.2 and TABLE 7-3.2 Testing shall be
                   purposes only.                                                                                  performed in accordance with the schedules in Chapter
                                                                                                                   7 or more often if required by the authority having
                                                                                                                   jurisdiction. If automatic testing is performed at least
                                                                                                                   weekly by a remotely monitored fire alarm control unit
                                                                                                                   specifically listed for the application, the manual testing
                                                                                                                   frequency shall be permitted to be extended to annual.
                                                                                                                   Table 7-3.2 shall apply. All components must be tested
                                                                                                                   upon acceptance and at least annually. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

04-13-2            Observed no inspection report available for the fire alarm system. For reporting                NFPA 72, 7-5.2.2 A permanent record of all inspections,
                   purposes only.                                                                                  testing, and maintenance shall be provided that includes
                                                                                                                   the following information of periodic tests and all
                                                                                                                   applicable information requested in Figure 7-5.2.2. (a)
                                                                                                                   Date; (b) Test frequency; (c) Name of property; (d)
                                                                                                                   Address; (e) Name of person performing inspection,
                                                                                                                   maintenance, tests, or combination thereof, and
                                                                                                                   affiliation, business address, and telephone number; (f)
                                                                                                                   Name, address, and representative of approving
                                                                                                                   agency(ies); (g) Designation of the detector(s) tested;
                                                                                                                   (h) Functional test of detectors; (i) Functional test of
                                                                                                                   required sequence of operations; (j) Check of all smoke
                                                                                                                   detectors; (k) Loop resistance for all fixed-temperature
                                                                                                                   line-type heat detectors; (l) Other tests as required by
                                                                                                                   equipment manufacturers; (m) Other tests as required
                                                                                                                   by the authority having jurisdiction; (n) Signatures of
                                                                                                                   tester and approved authority representative; (o)
                                                                                                                   Disposition of problems identified during testing (e.g.,
                                                                                                                   owner notified, problem, corrected/successfully
                                                                                                                   retested, device abondoned in place). FOR
                                                                                                                   REPORTING PURPOSES ONLY.

License Number: 2318085                                          PEREZ PROPERTY
License Type: Apartment                                          26 W 31 ST, HIALEAH 330125424

   Inspection Date: 09/18/2008            Inspection Number: 1220028              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                  Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only.                         NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                   maintenance not more than one year apart. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

License Number: 2309229                                          CABALLERO & TRIGOURA APTS
License Type: Apartment                                          3160 PALM AVE BX 1046, HIALEAH 330125431

   Inspection Date: 09/16/2008            Inspection Number: 1208509              Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                  Issued

Violation Code     Observation                                                                                     Violation Citation

01-05-2            Observed a fire extinguisher obscured from view. For reporting purposes only.                   NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                   obscured or obstructed from view. Except in large
                                                                                                                   rooms and in certain locations where visual obstruction
                                                                                                                   can not be completely avoided, a means shall be
                                                                                                                   provided to indicate location. FOR REPORTING
                                                                                                                   PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                          Page 17
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2309980                                         SHERMAN PALMS APTS
License Type: Apartment                                         33 W 30 ST, HIALEAH 330125437

   Inspection Date: 09/16/2008           Inspection Number: 1213011              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                 Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-03-2            Observed an insufficient number of fire extinguishers provided. For reporting                  61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                 Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                  installed in accordance with NFPA 10, Standard for
                                                                                                                  Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                  include guest room areas of hotels/motels, etc. [These
                                                                                                                  locations shall be protected by the installation of potable
                                                                                                                  fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                  provided for each 3000 square feet of floor space on
                                                                                                                  each level and installed so that the travel distance to
                                                                                                                  any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                  level, the area protected and the travel distances shall
                                                                                                                  be based of fire extinguishers installed in accordance
                                                                                                                  with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

License Number: 2305641                                         MAJO PROPERTIES APARTMENTS
License Type: Apartment                                         995 W 29 ST, HIALEAH 330125688

   Inspection Date: 09/17/2008           Inspection Number: 1215300              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                 Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only.                        NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                  maintenance not more than one year apart. FOR
                                                                                                                  REPORTING PURPOSES ONLY.

License Number: 2302049                                         MANUEL RIVERO
License Type: Apartment                                         609 E 21 ST, 609-617 E 21 ST, HIALEAH 33013

   Inspection Date: 09/11/2008           Inspection Number: 1210735              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                 Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-03-2            Observed an insufficient number of fire extinguishers provided. For reporting                  61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                 Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                  installed in accordance with NFPA 10, Standard for
                                                                                                                  Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                  include guest room areas of hotels/motels, etc. [These
                                                                                                                  locations shall be protected by the installation of potable
                                                                                                                  fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                  provided for each 3000 square feet of floor space on
                                                                                                                  each level and installed so that the travel distance to
                                                                                                                  any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                  level, the area protected and the travel distances shall
                                                                                                                  be based of fire extinguishers installed in accordance
                                                                                                                  with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                  PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                          Page 18
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2306776                                         RIVERO RENTAL
License Type: Apartment                                         659 E 21 ST, HIALEAH 33013

   Inspection Date: 09/11/2008           Inspection Number: 1210708              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                 Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-03-2            Observed an insufficient number of fire extinguishers provided. For reporting                  61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                 Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                  installed in accordance with NFPA 10, Standard for
                                                                                                                  Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                  include guest room areas of hotels/motels, etc. [These
                                                                                                                  locations shall be protected by the installation of potable
                                                                                                                  fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                  provided for each 3000 square feet of floor space on
                                                                                                                  each level and installed so that the travel distance to
                                                                                                                  any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                  level, the area protected and the travel distances shall
                                                                                                                  be based of fire extinguishers installed in accordance
                                                                                                                  with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

License Number: 2306783                                         PARK VIEW HIALEAH APARTMENTS LLC
License Type: Apartment                                         2701 E 4 AVE, HIALEAH 33013

   Inspection Date: 09/15/2008           Inspection Number: 1208528              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                 Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-05-2            Observed a fire extinguisher obscured from view. For reporting purposes only.                  NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                  obscured or obstructed from view. Except in large
                                                                                                                  rooms and in certain locations where visual obstruction
                                                                                                                  can not be completely avoided, a means shall be
                                                                                                                  provided to indicate location. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

License Number: 2301868                                         MEDINA APTS
License Type: Apartment                                         601 E 21 ST, HIALEAH 330134023

   Inspection Date: 09/11/2008           Inspection Number: 1220025              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                 Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-03-2            Observed an insufficient number of fire extinguishers provided. For reporting                  61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                 Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                  installed in accordance with NFPA 10, Standard for
                                                                                                                  Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                  include guest room areas of hotels/motels, etc. [These
                                                                                                                  locations shall be protected by the installation of potable
                                                                                                                  fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                  provided for each 3000 square feet of floor space on
                                                                                                                  each level and installed so that the travel distance to
                                                                                                                  any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                  level, the area protected and the travel distances shall
                                                                                                                  be based of fire extinguishers installed in accordance
                                                                                                                  with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                  PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                          Page 19
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2302526                                         DELGADO APARTMENTS
License Type: Apartment                                         675 E 21 ST, HIALEAH 330134031

   Inspection Date: 09/15/2008           Inspection Number: 1217595              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                 Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-03-2            Observed an insufficient number of fire extinguishers provided. For reporting                  61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                 Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                  installed in accordance with NFPA 10, Standard for
                                                                                                                  Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                  include guest room areas of hotels/motels, etc. [These
                                                                                                                  locations shall be protected by the installation of potable
                                                                                                                  fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                  provided for each 3000 square feet of floor space on
                                                                                                                  each level and installed so that the travel distance to
                                                                                                                  any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                  level, the area protected and the travel distances shall
                                                                                                                  be based of fire extinguishers installed in accordance
                                                                                                                  with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

License Number: 2302449                                         ACOSTA APARTMENTS
License Type: Apartment                                         667 E 21 ST, HIALEAH 330134032

   Inspection Date: 09/11/2008           Inspection Number: 1220027              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                 Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-03-2            Observed an insufficient number of fire extinguishers provided. For reporting                  61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                 Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                  installed in accordance with NFPA 10, Standard for
                                                                                                                  Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                  include guest room areas of hotels/motels, etc. [These
                                                                                                                  locations shall be protected by the installation of potable
                                                                                                                  fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                  provided for each 3000 square feet of floor space on
                                                                                                                  each level and installed so that the travel distance to
                                                                                                                  any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                  level, the area protected and the travel distances shall
                                                                                                                  be based of fire extinguishers installed in accordance
                                                                                                                  with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

License Number: 2304503                                         ARH BUILDING APTS
License Type: Apartment                                         641 E 21 ST, HIALEAH 330134035

   Inspection Date: 09/11/2008           Inspection Number: 1208508              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                 Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-03-2            Observed an insufficient number of fire extinguishers provided. For reporting                  61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                 Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                  installed in accordance with NFPA 10, Standard for
                                                                                                                  Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                  include guest room areas of hotels/motels, etc. [These
                                                                                                                  locations shall be protected by the installation of potable
                                                                                                                  fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                  provided for each 3000 square feet of floor space on
                                                                                                                  each level and installed so that the travel distance to
                                                                                                                  any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                  level, the area protected and the travel distances shall
                                                                                                                  be based of fire extinguishers installed in accordance
                                                                                                                  with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                  PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                          Page 20
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2301934                                         BEVANS APARTMENTS
License Type: Apartment                                         633 E 21 ST, HIALEAH 330134036

   Inspection Date: 09/11/2008           Inspection Number: 1203891              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                 Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-03-2            Observed an insufficient number of fire extinguishers provided. For reporting                  61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                 Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                  installed in accordance with NFPA 10, Standard for
                                                                                                                  Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                  include guest room areas of hotels/motels, etc. [These
                                                                                                                  locations shall be protected by the installation of potable
                                                                                                                  fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                  provided for each 3000 square feet of floor space on
                                                                                                                  each level and installed so that the travel distance to
                                                                                                                  any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                  level, the area protected and the travel distances shall
                                                                                                                  be based of fire extinguishers installed in accordance
                                                                                                                  with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

License Number: 2301950                                         ARIAS APARTMENTS
License Type: Apartment                                         625 E 21 ST, HIALEAH 330134037

   Inspection Date: 09/11/2008           Inspection Number: 1210710              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                 Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-03-2            Observed an insufficient number of fire extinguishers provided. For reporting                  61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                 Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                  installed in accordance with NFPA 10, Standard for
                                                                                                                  Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                  include guest room areas of hotels/motels, etc. [These
                                                                                                                  locations shall be protected by the installation of potable
                                                                                                                  fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                  provided for each 3000 square feet of floor space on
                                                                                                                  each level and installed so that the travel distance to
                                                                                                                  any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                  level, the area protected and the travel distances shall
                                                                                                                  be based of fire extinguishers installed in accordance
                                                                                                                  with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                  PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                         Page 21
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2309966                                        LAGO AZUL APARTMENTS
License Type: Apartment                                        1060 W 74 ST, HIALEAH 33014

   Inspection Date: 09/19/2008           Inspection Number: 1208477             Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: SIMANEK, MICHELLE                                                                                                  Completed - No Further Action

Violation Code     Observation                                                                                   Violation Citation

02-04-2            Observed an LP gas tank having a water capacity greater than 2 1/2 lbs. on a                  NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                   balcony. For reporting purposes only.                                                         capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                 located on balconies above the first floor that are
                                                                                                                 attached to a multiple family dwelling of 3 or more living
                                                                                                                 units one above the other. Exception: Where such
                                                                                                                 balconies are served by outside stairways and where
                                                                                                                 only such stairways are used to transport the container.
                                                                                                                 FOR REPORTING PURPOSES ONLY.

04-01-2            Observed a smoke detector not functioning when tested. For reporting purposes                 61C-1.004(5)FAC All fire safety, protection and
                   only. (APT #108, #222)                                                                        prevention equipment must be installed, approved,
                                                                                                                 maintained and used in accordance with Chapter 509,
                                                                                                                 FS and the National Fire Protection Association Life
                                                                                                                 Safety Code Chapter 101, as adopted by the Division of
                                                                                                                 State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                 REPORTING PURPOSES ONLY.

04-01-2            Observed a smoke detector in disrepair. For reporting purposes only. (MISSING                 61C-1.004(5)FAC All fire safety, protection and
                   IN APT #221)                                                                                  prevention equipment must be installed, approved,
                                                                                                                 maintained and used in accordance with Chapter 509,
                                                                                                                 FS and the National Fire Protection Association Life
                                                                                                                 Safety Code Chapter 101, as adopted by the Division of
                                                                                                                 State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                 REPORTING PURPOSES ONLY.

License Number: 2311941                                        BELLA VILLA APTS
License Type: Apartment                                        1150 W 79 ST, HIALEAH 330143580

   Inspection Date: 09/19/2008           Inspection Number: 1215273             Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: SIMANEK, MICHELLE                                                                                                  Completed - No Further Action

Violation Code     Observation                                                                                   Violation Citation

02-04-2            Observed an LP gas tank having a water capacity greater than 2 1/2 lbs. on a                  NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                   balcony. For reporting purposes only.                                                         capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                 located on balconies above the first floor that are
                                                                                                                 attached to a multiple family dwelling of 3 or more living
                                                                                                                 units one above the other. Exception: Where such
                                                                                                                 balconies are served by outside stairways and where
                                                                                                                 only such stairways are used to transport the container.
                                                                                                                 FOR REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                          Page 22
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2313622                                         900 W 74 ST
License Type: Apartment                                         880 W 74 ST, HIALEAH 330144762

   Inspection Date: 09/19/2008           Inspection Number: 1220010              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: SIMANEK, MICHELLE                                                                                                   Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-03-2            Observed appropriately sized fire extinguishers missing. For reporting purposes                61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   only.                                                                                          Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                  installed in accordance with NFPA 10, Standard for
                                                                                                                  Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                  include guest room areas of hotels/motels, etc. [These
                                                                                                                  locations shall be protected by the installation of potable
                                                                                                                  fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                  provided for each 3000 square feet of floor space on
                                                                                                                  each level and installed so that the travel distance to
                                                                                                                  any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                  level, the area protected and the travel distances shall
                                                                                                                  be based of fire extinguishers installed in accordance
                                                                                                                  with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

06-01-2            Observed an exit path blocked. For reporting purposes only. (SHOPPING CARTS                    61C-1.004(6) FAC All building structural components,
                   IN HALLWAYS)                                                                                   attachments and fixtures shall be kept free of
                                                                                                                  obstructions. FOR REPORTING PURPOSES ONLY.

06-20-2            Observed an exit sign in disrepair. For reporting purposes only. (MISSING IN 2ND               61C-1.004(5)FAC All fire safety, protection and
                   FLOOR HALLWAY)                                                                                 prevention equipment must be installed, approved,
                                                                                                                  maintained and used in accordance with Chapter 509,
                                                                                                                  FS and the National Fire Protection Association Life
                                                                                                                  Safety Code Chapter 101, as adopted by the Division of
                                                                                                                  State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                  REPORTING PURPOSES ONLY.

License Number: 2308733                                         875-885-915MATTHEW RYAN INVEST
License Type: Apartment                                         W 74 ST, HIALEAH 330144774

   Inspection Date: 09/19/2008           Inspection Number: 1210697              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: SIMANEK, MICHELLE                                                                                                   Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-06-2            Observed a locked fire extinguisher box missing a breaking device. For reporting               NFPA 10,1-6.5 Cabinets housing fire extinguishers shall
                   purposes only.                                                                                 not be locked. Except locked cabinets may be used
                                                                                                                  provided they include means of emergency access.
                                                                                                                  FOR REPORTING PURPOSES ONLY.

06-20-2            Observed an emergency light in disrepair. For reporting purposes only. (HANGING                61C-1.004(5)FAC All fire safety, protection and
                   BY WIRES)                                                                                      prevention equipment must be installed, approved,
                                                                                                                  maintained and used in accordance with Chapter 509,
                                                                                                                  FS and the National Fire Protection Association Life
                                                                                                                  Safety Code Chapter 101, as adopted by the Division of
                                                                                                                  State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                  REPORTING PURPOSES ONLY.

License Number: 2313588                                         WESTWOOD MANOR APTS
License Type: Apartment                                         250 W 74 PL, HIALEAH 330145060

   Inspection Date: 09/19/2008           Inspection Number: 1217581              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: SIMANEK, MICHELLE                                                                                                   Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

06-20-2            Observed an emergency light in disrepair. For reporting purposes only. (HANGING                61C-1.004(5)FAC All fire safety, protection and
                   BY THE WIRES)                                                                                  prevention equipment must be installed, approved,
                                                                                                                  maintained and used in accordance with Chapter 509,
                                                                                                                  FS and the National Fire Protection Association Life
                                                                                                                  Safety Code Chapter 101, as adopted by the Division of
                                                                                                                  State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                  REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                           Page 23
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2313253                                         6861 APARTMENTS
License Type: Apartment                                         6861 W 4 AVE, HIALEAH 330145404

   Inspection Date: 09/17/2008           Inspection Number: 1220009               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: SIMANEK, MICHELLE                                                                                                    Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-06-2            Observed a locked fire extinguisher box missing a breaking device. For reporting                NFPA 10,1-6.5 Cabinets housing fire extinguishers shall
                   purposes only.                                                                                  not be locked. Except locked cabinets may be used
                                                                                                                   provided they include means of emergency access.
                                                                                                                   FOR REPORTING PURPOSES ONLY.

06-01-2            Observed an exit path blocked. For reporting purposes only. (SHOPPING CARTS                     61C-1.004(6) FAC All building structural components,
                   IN WALKWAY)                                                                                     attachments and fixtures shall be kept free of
                                                                                                                   obstructions. FOR REPORTING PURPOSES ONLY.

06-20-2            Observed an emergency light that is not functioning when tested. For reporting                  61C-1.004(5)FAC All fire safety, protection and
                   purposes only. (STAIR WELL. CHECK ALL EMERGENCY LIGHTS)                                         prevention equipment must be installed, approved,
                                                                                                                   maintained and used in accordance with Chapter 509,
                                                                                                                   FS and the National Fire Protection Association Life
                                                                                                                   Safety Code Chapter 101, as adopted by the Division of
                                                                                                                   State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

License Number: 2329061                                         EMERALD DUNES APTS
License Type: Apartment                                         1931 NW 207 ST, MIAMI GARDENS 33056

   Inspection Date: 09/17/2008           Inspection Number: 1219852               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: UNOLD, RICARDO                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

06-01-2            Observed an exit path blocked. For reporting purposes only. chairs                              61C-1.004(6) FAC All building structural components,
                                                                                                                   attachments and fixtures shall be kept free of
                                                                                                                   obstructions. FOR REPORTING PURPOSES ONLY.

License Number: 2313312                                         1542 APTS
License Type: Apartment                                         1542 NW 3 ST, MIAMI 331254677

   Inspection Date: 09/19/2008           Inspection Number: 1240068               Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: BLAIR, ANTONIO                                                                                                       Issued

Violation Code     Observation                                                                                     Violation Citation

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only.                         NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                   maintenance not more than one year apart. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

License Number: 2309010                                         1333 APTS
License Type: Apartment                                         1333 NW 6 ST, MIAMI 331254745

   Inspection Date: 09/15/2008           Inspection Number: 1210758               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BLAIR, ANTONIO                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-03-2            Observed an appropriately sized fire extinguisher is missing. For reporting                     61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                  Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                   installed in accordance with NFPA 10, Standard for
                                                                                                                   Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                   include guest room areas of hotels/motels, etc. [These
                                                                                                                   locations shall be protected by the installation of potable
                                                                                                                   fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                   provided for each 3000 square feet of floor space on
                                                                                                                   each level and installed so that the travel distance to
                                                                                                                   any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                   level, the area protected and the travel distances shall
                                                                                                                   be based of fire extinguishers installed in accordance
                                                                                                                   with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                   PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 24
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2310526                                             DARGELO APARTMENTS
License Type: Apartment                                             1646 NW 2 ST, MIAMI 331255527

   Inspection Date: 09/19/2008               Inspection Number: 1240067              Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: BLAIR, ANTONIO                                                                                                          Issued

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed flammable material stored in attic/laundry/boiler room. For reporting                  61C-1.004(7) FAC Attics, basements, boiler rooms,
                      purposes only.                                                                                  meter rooms, laundry rooms, and storage rooms shall
                                                                                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

License Number: 2318748                                             EXECUTIVE AIRPORT HOTEL
License Type: Motel                                                 6700 NW 13 ST, MIAMI 331262036

   Inspection Date: 09/19/2008               Inspection Number: 1123005              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: CHOW, ZULEIMA                                                                                                           Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                      meter rooms, laundry rooms, and storage rooms shall
                                                                                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

06-18-2               Observed too many locks on a door, requiring too many motions to exit. For                      NFPA 101, 7.2.1.5.4 A latch or other fastening device
                      reporting purposes only.                                                                        on a door shall be provided with a releasing device
                                                                                                                      having an obvious method of operation and that is
                                                                                                                      readily operated under all lighting conditions. The
                                                                                                                      releasing mechanism for any latch shall be located not
                                                                                                                      less than 34 in. (86 cm), and not more than 48 in. (122
                                                                                                                      cm), above the finished floor. Doors shall be operable
                                                                                                                      with not more than one releasing operation. [Exception
                                                                                                                      No. 1: Egress doors from individual living units and
                                                                                                                      guest rooms of residential occupancies shall be
                                                                                                                      permitted to be provided with devices that require not
                                                                                                                      more than one additional releasing operation, provided
                                                                                                                      that such device is operable from the inside without the
                                                                                                                      use of a key or tool and is mounted at a height not
                                                                                                                      exceeding 48 in. (122 cm) above the finished floor.
                                                                                                                      Existing security devices shall be permitted to have two
                                                                                                                      additional releasing operations. Existing security
                                                                                                                      devices other than automatic latching devices shall not
                                                                                                                      be located more than 60 in. (152 cm) above the finished
                                                                                                                      floor. Automatic latching devices shall not be located
                                                                                                                      more than 48 in. (122 cm) above the finished floor.
                                                                                                                      Exception No. 2: The minimum mounting height for the
                                                                                                                      release mechanism shall not be applicable to existing
                                                                                                                      installations.] FOR REPORTING PURPOSES ONLY.

License Number: 2303037                                             LAM APT
License Type: Apartment                                             552 SW 3 ST, MIAMI 331301335

   Inspection Date: 09/16/2008               Inspection Number: 1220155              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: GARCIA, BARBARO                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

01-10-2               Observed an expired fire extinguisher tag. For reporting purposes only.                         NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                      maintenance not more than one year apart. FOR
                                                                                                                      REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                             Page 25
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2310560                                            COUTO'S APTS
License Type: Apartment                                            769 SW 3 ST, MIAMI 331302331

   Inspection Date: 08/29/2008               Inspection Number: 1204017             Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: GARCIA, BARBARO                                                                                                        Completed - No Further Action

Violation Code        Observation                                                                                    Violation Citation

01-05-2               Observed a fire extinguisher obscured from view. For reporting purposes only.                  NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                     obscured or obstructed from view. Except in large
                                                                                                                     rooms and in certain locations where visual obstruction
                                                                                                                     can not be completely avoided, a means shall be
                                                                                                                     provided to indicate location. FOR REPORTING
                                                                                                                     PURPOSES ONLY.

License Number: 2308981                                            GUERRERO APARTMENTS
License Type: Apartment                                            926 SW 5 ST, MIAMI 331302547

   Inspection Date: 09/16/2008               Inspection Number: 1240050             Inspection Type: Routine - Lodging                    Inspection Disposition: Administrative
   Inspector Name: BURROWS, LEON                                                                                                          complaint recommended

Violation Code        Observation                                                                                    Violation Citation

06-01-2               Observed an exit path blocked. For reporting purposes only. storage on porch                   61C-1.004(6) FAC All building structural components,
                                                                                                                     attachments and fixtures shall be kept free of
                                                                                                                     obstructions. FOR REPORTING PURPOSES ONLY.

06-04-2               Observed an unmarked exit. For reporting purposes only. 2nd floor rear                         61-C1.004(10) FAC Exits shall be clearly marked with
                                                                                                                     approved illuminated exit signs. FOR REPORTING
                                                                                                                     PURPOSES ONLY.

License Number: 2329005                                            CONRAD MIAMI
License Type: Hotel                                                1395 BRICKELL AVENUE, MIAMI 33131

   Inspection Date: 09/17/2008               Inspection Number: 1100130             Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: GARCIA, BARBARO                                                                                                        Completed - No Further Action

Violation Code        Observation                                                                                    Violation Citation

08-03                 Observed an expired boiler certificate.                                                        61C-1.004(12) FAC The insurance inspector's boiler
                                                                                                                     report is required annually for power boilers and high
                                                                                                                     pressure/high temperature boilers and biannually for low
                      Boiler Information: Boiler Jurisdiction Number: FL086068, Boiler Expiration Date:              pressure steam or vapor heating boilers and shall be
                      9-10-06                                                                                        posted in the boiler room. The provisions of this section
                                                                                                                     do not apply to the common areas of resort
                                                                                                                     condominiums.

License Number: 2301170                                            COURTYARD BY MARRIOTT MIAMI CORAL GABLES
License Type: Motel                                                2051 S LEJEUNE RD, MIAMI 33134

   Inspection Date: 09/17/2008               Inspection Number: 1126603             Inspection Type: Routine - Lodging                    Inspection Disposition: Administrative
   Inspector Name: MORGADANES, DOUGLAS                                                                                                    complaint recommended

Violation Code        Observation                                                                                    Violation Citation

04-02-2               Observed no smoke detector provided. For reporting purposes only.                              NFPA 72, NFPA 101, and 4A-43.009 FAC Transient
                                                                                                                     lodging establishments: Each sleeping and living area
                                                                                                                     shall be protected by the installation of single station
                                                                                                                     smoke detectors powered from the building electrical
                                                                                                                     system. FOR REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 26
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2310929                                             CHATEAUBLEAU INN SOUTH
License Type: Hotel                                                 1211 E PONCE DE LEON BLVD, CORAL GABLES 331343316

   Inspection Date: 09/15/2008               Inspection Number: 1101923              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MORGADANES, DOUGLAS                                                                                                     Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

06-04-2               Observed an exit sign that is not illuminated/not functioning when tested. For                  61-C1.004(10) FAC Exits shall be clearly marked with
                      reporting purposes only.                                                                        approved illuminated exit signs. FOR REPORTING
                                                                                                                      PURPOSES ONLY.

06-20-2               Observed an emergency light that is not functioning when tested. For reporting                  61C-1.004(5)FAC All fire safety, protection and
                      purposes only.                                                                                  prevention equipment must be installed, approved,
                                                                                                                      maintained and used in accordance with Chapter 509,
                                                                                                                      FS and the National Fire Protection Association Life
                                                                                                                      Safety Code Chapter 101, as adopted by the Division of
                                                                                                                      State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

License Number: 2305076                                             CHATEAU BLEAU INN
License Type: Hotel                                                 1111 PONCE DE LEON BLVD, CORAL GABLES 331343321

   Inspection Date: 09/15/2008               Inspection Number: 1101580              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MORGADANES, DOUGLAS                                                                                                     Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

06-20-2               Observed an emergency light that is not functioning when tested. For reporting                  61C-1.004(5)FAC All fire safety, protection and
                      purposes only.                                                                                  prevention equipment must be installed, approved,
                                                                                                                      maintained and used in accordance with Chapter 509,
                                                                                                                      FS and the National Fire Protection Association Life
                                                                                                                      Safety Code Chapter 101, as adopted by the Division of
                                                                                                                      State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

License Number: 2300863                                             BAMBOO GARDEN APARTMENTS
License Type: Apartment                                             1201 E PONCE DE LEON, CORAL GABLES 331343344

   Inspection Date: 09/15/2008               Inspection Number: 1215455              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MORGADANES, DOUGLAS                                                                                                     Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

04-10-2               Observed the fire alarm panel with an expired inspection tag. For reporting                     NFPA 72 7-3.2 and TABLE 7-3.2 Testing shall be
                      purposes only.                                                                                  performed in accordance with the schedules in Chapter
                                                                                                                      7 or more often if required by the authority having
                                                                                                                      jurisdiction. If automatic testing is performed at least
                                                                                                                      weekly by a remotely monitored fire alarm control unit
                                                                                                                      specifically listed for the application, the manual testing
                                                                                                                      frequency shall be permitted to be extended to annual.
                                                                                                                      Table 7-3.2 shall apply. All components must be tested
                                                                                                                      upon acceptance and at least annually. FOR
                                                                                                                      REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                               Page 27
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2312910                                             PONCE DE LEON HOTEL
License Type: Hotel                                                 1721 PONCE DE LEON BLVD, CORAL GABLES 331344416

   Inspection Date: 09/15/2008               Inspection Number: 1100132               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MORGADANES, DOUGLAS                                                                                                      Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

04-01-2               Observed a trouble/alarm light illuminated on the fire alarm control panel. For                  61C-1.004(5)FAC All fire safety, protection and
                      reporting purposes only.                                                                         prevention equipment must be installed, approved,
                                                                                                                       maintained and used in accordance with Chapter 509,
                                                                                                                       FS and the National Fire Protection Association Life
                                                                                                                       Safety Code Chapter 101, as adopted by the Division of
                                                                                                                       State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

04-01-2               Observed a smoke detector hanging by the wires. For reporting purposes only.                     61C-1.004(5)FAC All fire safety, protection and
                                                                                                                       prevention equipment must be installed, approved,
                                                                                                                       maintained and used in accordance with Chapter 509,
                                                                                                                       FS and the National Fire Protection Association Life
                                                                                                                       Safety Code Chapter 101, as adopted by the Division of
                                                                                                                       State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

04-01-2               Observed an alarm silenced on the fire alarm control panel. For reporting                        61C-1.004(5)FAC All fire safety, protection and
                      purposes only.                                                                                   prevention equipment must be installed, approved,
                                                                                                                       maintained and used in accordance with Chapter 509,
                                                                                                                       FS and the National Fire Protection Association Life
                                                                                                                       Safety Code Chapter 101, as adopted by the Division of
                                                                                                                       State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

04-11-2               Observed the fire alarm system not being maintained. For reporting purposes only.                NFPA 72, 7-4.1 Fire alarm system equipment shall be
                                                                                                                       maintained in accordance with the manufacturer's
                                                                                                                       instructions. The frequency of maintenance shall
                                                                                                                       depend on the type of equipment and the local ambient
                                                                                                                       conditions. FOR REPORTING PURPOSES ONLY.

License Number: 2307147                                             TOPS MOTEL
License Type: Motel                                                 3151 SW 8 ST, MIAMI 331354533

   Inspection Date: 09/16/2008               Inspection Number: 1124441               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: PIERRE-LOUIS, LOUIS                                                                                                      Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

04-01-2               Observed a smoke detector not functioning when tested. For reporting purposes                    61C-1.004(5)FAC All fire safety, protection and
                      only.in room 6                                                                                   prevention equipment must be installed, approved,
                                                                                                                       maintained and used in accordance with Chapter 509,
                                                                                                                       FS and the National Fire Protection Association Life
                                                                                                                       Safety Code Chapter 101, as adopted by the Division of
                                                                                                                       State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

License Number: 2307648                                             EL NIDO MOTEL
License Type: Motel                                                 3141 SW 8 ST, MIAMI 331354533

   Inspection Date: 09/16/2008               Inspection Number: 1124439               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: PIERRE-LOUIS, LOUIS                                                                                                      Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

04-01-2               Observed a smoke detector not functioning when tested. For reporting purposes                    61C-1.004(5)FAC All fire safety, protection and
                      only.in room 1                                                                                   prevention equipment must be installed, approved,
                                                                                                                       maintained and used in accordance with Chapter 509,
                                                                                                                       FS and the National Fire Protection Association Life
                                                                                                                       Safety Code Chapter 101, as adopted by the Division of
                                                                                                                       State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

07-06-2               Observed an electrical outlet missing a cover plate. For reporting purposes only.                NFPA 70, 300-31 Suitable covers shall be installed on
                                                                                                                       all boxes to prevent accidental contact with energized
                                                                                                                       parts or physical damage to parts or insulation. FOR
                                                                                                                       REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                            Page 28
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2300855                                          ACF HOLDINGS LLC
License Type: Apartment                                          504 NW 12 AVE, MIAMI 33136

   Inspection Date: 09/19/2008            Inspection Number: 1240065              Inspection Type: Routine - Lodging                    Inspection Disposition: Administrative
   Inspector Name: BLAIR, ANTONIO                                                                                                       complaint recommended

Violation Code     Observation                                                                                     Violation Citation

01-06-2            Observed a locked fire extinguisher box missing a breaking device. For reporting                NFPA 10,1-6.5 Cabinets housing fire extinguishers shall
                   purposes only.                                                                                  not be locked. Except locked cabinets may be used
                                                                                                                   provided they include means of emergency access.
                                                                                                                   FOR REPORTING PURPOSES ONLY.

License Number: 2305546                                          ROBERTS APTS
License Type: Apartment                                          1650 NW 2 AVE, MIAMI 331361820

   Inspection Date: 10/17/2005            Inspection Number: 1152349              Inspection Type: Routine - Lodging                    Inspection Disposition: Call Back -
   Inspector Name: CHI, MAURICE                                                                                                         Complied

Violation Code     Observation                                                                                     Violation Citation

01-10              Observed an expired fire extinguisher tag.                                                      NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                   maintenance not more than one year apart

06-04              Observed an exit sign that is not illuminated/not functioning when tested.                      61-C1.004(10) FAC Exits shall be clearly marked with
                                                                                                                   approved illuminated exit signs.

License Number: 2308739                                          352 CORPORATION
License Type: Apartment                                          352 NW 11 ST, MIAMI 331362519

   Inspection Date: 09/19/2008            Inspection Number: 1240066              Inspection Type: Routine - Lodging                    Inspection Disposition: Administrative
   Inspector Name: BLAIR, ANTONIO                                                                                                       complaint recommended

Violation Code     Observation                                                                                     Violation Citation

01-03-2            Observed an appropriately sized fire extinguisher is missing. For reporting                     61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                  Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                   installed in accordance with NFPA 10, Standard for
                                                                                                                   Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                   include guest room areas of hotels/motels, etc. [These
                                                                                                                   locations shall be protected by the installation of potable
                                                                                                                   fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                   provided for each 3000 square feet of floor space on
                                                                                                                   each level and installed so that the travel distance to
                                                                                                                   any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                   level, the area protected and the travel distances shall
                                                                                                                   be based of fire extinguishers installed in accordance
                                                                                                                   with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

License Number: 2310280                                          INDIAN RIVER APTS
License Type: Apartment                                          1232 NW 1 PL, MIAMI 331362639

   Inspection Date: 09/19/2008            Inspection Number: 1240072              Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: BLAIR, ANTONIO                                                                                                       Issued

Violation Code     Observation                                                                                     Violation Citation

01-03-2            Observed an appropriately sized fire extinguisher is missing. For reporting                     61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                  Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                   installed in accordance with NFPA 10, Standard for
                                                                                                                   Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                   include guest room areas of hotels/motels, etc. [These
                                                                                                                   locations shall be protected by the installation of potable
                                                                                                                   fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                   provided for each 3000 square feet of floor space on
                                                                                                                   each level and installed so that the travel distance to
                                                                                                                   any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                   level, the area protected and the travel distances shall
                                                                                                                   be based of fire extinguishers installed in accordance
                                                                                                                   with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                   PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                         Page 29
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2311542                                         READY, SET, GO
License Type: Apartment                                         688 NE 85 STREET, MIAMI 33138

   Inspection Date: 09/11/2008           Inspection Number: 1203614               Inspection Type: Routine - Lodging                    Inspection Disposition: Administrative
   Inspector Name: RICHARD, DICKSON                                                                                                     complaint recommended

Violation Code     Observation                                                                                     Violation Citation

01-03-2            Observed an appropriately sized fire extinguisher is missing. For reporting                     61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                  Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                   installed in accordance with NFPA 10, Standard for
                                                                                                                   Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                   include guest room areas of hotels/motels, etc. [These
                                                                                                                   locations shall be protected by the installation of potable
                                                                                                                   fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                   provided for each 3000 square feet of floor space on
                                                                                                                   each level and installed so that the travel distance to
                                                                                                                   any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                   level, the area protected and the travel distances shall
                                                                                                                   be based of fire extinguishers installed in accordance
                                                                                                                   with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

License Number: 2306482                                         MIAMI SHORES APTS
License Type: Apartment                                         1316 NE 105 ST, MIAMI 331382129

   Inspection Date: 09/11/2008           Inspection Number: 1214976               Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: RICHARD, DICKSON                                                                                                     Issued

Violation Code     Observation                                                                                     Violation Citation

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only.                         NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                   maintenance not more than one year apart. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

License Number: 2302499                                         1385 APARTMENTS
License Type: Apartment                                         1385 NE 105 ST, MIAMI 331382132

   Inspection Date: 09/11/2008           Inspection Number: 1219683               Inspection Type: Routine - Lodging                    Inspection Disposition: Administrative
   Inspector Name: RICHARD, DICKSON                                                                                                     complaint recommended

Violation Code     Observation                                                                                     Violation Citation

01-11-2            Observed a fire extinguisher missing an inspection tag. For reporting purposes                  61C-1.004(9)(b) FAC A standard state approved service
                   only.                                                                                           tag shall be attached to each extinguisher and a person
                                                                                                                   holding a valid state permit issued by the State Fire
                                                                                                                   Marshal shall recharge or inspect the extinguisher and
                                                                                                                   shall prepare the tag to include the information required
                                                                                                                   by rule 4A-21.241, FAC, herein adopted by reference.
                                                                                                                   FOR REPORTING PURPOSES ONLY.

License Number: 2306297                                         BARBET APTS
License Type: Apartment                                         696 NE 85 ST, MIAMI 331383531

   Inspection Date: 09/11/2008           Inspection Number: 1208196               Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: RICHARD, DICKSON                                                                                                     Issued

Violation Code     Observation                                                                                     Violation Citation

01-05-2            Observed a fire extinguisher obscured from view. For reporting purposes only.                   NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                   obscured or obstructed from view. Except in large
                                                                                                                   rooms and in certain locations where visual obstruction
                                                                                                                   can not be completely avoided, a means shall be
                                                                                                                   provided to indicate location. FOR REPORTING
                                                                                                                   PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                         Page 30
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2313941                                          LAUREANO PEREZ APTS
License Type: Apartment                                          1060 NE 78 RD, MIAMI 331384218

   Inspection Date: 09/10/2008            Inspection Number: 1202929              Inspection Type: Routine - Lodging                    Inspection Disposition: Administrative
   Inspector Name: RICHARD, DICKSON                                                                                                     complaint recommended

Violation Code     Observation                                                                                     Violation Citation

01-03-2            Observed an appropriately sized fire extinguisher is missing. For reporting                     61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                  Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                   installed in accordance with NFPA 10, Standard for
                                                                                                                   Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                   include guest room areas of hotels/motels, etc. [These
                                                                                                                   locations shall be protected by the installation of potable
                                                                                                                   fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                   provided for each 3000 square feet of floor space on
                                                                                                                   each level and installed so that the travel distance to
                                                                                                                   any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                   level, the area protected and the travel distances shall
                                                                                                                   be based of fire extinguishers installed in accordance
                                                                                                                   with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

License Number: 2309777                                          SHADA CARGO SHIPPING
License Type: Apartment                                          1030 NE 80 ST, MIAMI 331384249

   Inspection Date: 09/11/2008            Inspection Number: 1219707              Inspection Type: Routine - Lodging                    Inspection Disposition: Administrative
   Inspector Name: RICHARD, DICKSON                                                                                                     complaint recommended

Violation Code     Observation                                                                                     Violation Citation

01-03-2            Observed an appropriately sized fire extinguisher is missing. For reporting                     61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                  Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                   installed in accordance with NFPA 10, Standard for
                                                                                                                   Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                   include guest room areas of hotels/motels, etc. [These
                                                                                                                   locations shall be protected by the installation of potable
                                                                                                                   fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                   provided for each 3000 square feet of floor space on
                                                                                                                   each level and installed so that the travel distance to
                                                                                                                   any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                   level, the area protected and the travel distances shall
                                                                                                                   be based of fire extinguishers installed in accordance
                                                                                                                   with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

06-20-2            Observed an exit sign in disrepair. For reporting purposes only.                                61C-1.004(5)FAC All fire safety, protection and
                                                                                                                   prevention equipment must be installed, approved,
                                                                                                                   maintained and used in accordance with Chapter 509,
                                                                                                                   FS and the National Fire Protection Association Life
                                                                                                                   Safety Code Chapter 101, as adopted by the Division of
                                                                                                                   State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

License Number: 2304240                                          SMP LLC
License Type: Apartment                                          1 NE 78 ST, MIAMI 331384339

   Inspection Date: 09/16/2008            Inspection Number: 1212688              Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: RICHARD, DICKSON                                                                                                     Issued

Violation Code     Observation                                                                                     Violation Citation

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only.                         NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                   maintenance not more than one year apart. FOR
                                                                                                                   REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                            Page 31
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2310950                                          PLUS VENTURES APARTMENTS
License Type: Apartment                                          8045 NE 1 AVE, MIAMI 331384342

   Inspection Date: 09/16/2008            Inspection Number: 1210411               Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: RICHARD, DICKSON                                                                                                      Issued

Violation Code     Observation                                                                                      Violation Citation

01-03-2            Observed an appropriately sized fire extinguisher is missing. For reporting                      61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                   Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                    installed in accordance with NFPA 10, Standard for
                                                                                                                    Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                    include guest room areas of hotels/motels, etc. [These
                                                                                                                    locations shall be protected by the installation of potable
                                                                                                                    fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                    provided for each 3000 square feet of floor space on
                                                                                                                    each level and installed so that the travel distance to
                                                                                                                    any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                    level, the area protected and the travel distances shall
                                                                                                                    be based of fire extinguishers installed in accordance
                                                                                                                    with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                    PURPOSES ONLY.

License Number: 2303791                                          LITTLE RIVER RECOVERY HOUSE
License Type: Rooming House                                      237 NE 80 TERR, MIAMI 331384443

   Inspection Date: 09/10/2008            Inspection Number: 1088695               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: RICHARD, DICKSON                                                                                                      Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

01-05-2            Observed a fire extinguisher obscured from view. For reporting purposes only.                    NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                    obscured or obstructed from view. Except in large
                                                                                                                    rooms and in certain locations where visual obstruction
                                                                                                                    can not be completely avoided, a means shall be
                                                                                                                    provided to indicate location. FOR REPORTING
                                                                                                                    PURPOSES ONLY.

License Number: 2310798                                          SCHRAGER APARTMENTS
License Type: Apartment                                          301 NE 77 ST, MIAMI 331384850

   Inspection Date: 09/16/2008            Inspection Number: 1212692               Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: RICHARD, DICKSON                                                                                                      Issued

Violation Code     Observation                                                                                      Violation Citation

04-01-2            Observed a trouble/alarm light illuminated on the fire alarm control panel. For                  61C-1.004(5)FAC All fire safety, protection and
                   reporting purposes only.                                                                         prevention equipment must be installed, approved,
                                                                                                                    maintained and used in accordance with Chapter 509,
                                                                                                                    FS and the National Fire Protection Association Life
                                                                                                                    Safety Code Chapter 101, as adopted by the Division of
                                                                                                                    State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                    REPORTING PURPOSES ONLY.

04-10-2            Observed the fire alarm panel with an expired inspection tag. For reporting                      NFPA 72 7-3.2 and TABLE 7-3.2 Testing shall be
                   purposes only.                                                                                   performed in accordance with the schedules in Chapter
                                                                                                                    7 or more often if required by the authority having
                                                                                                                    jurisdiction. If automatic testing is performed at least
                                                                                                                    weekly by a remotely monitored fire alarm control unit
                                                                                                                    specifically listed for the application, the manual testing
                                                                                                                    frequency shall be permitted to be extended to annual.
                                                                                                                    Table 7-3.2 shall apply. All components must be tested
                                                                                                                    upon acceptance and at least annually. FOR
                                                                                                                    REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                           Page 32
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2308951                                         17 NW INC
License Type: Apartment                                         7509 NE 3 AVE, MIAMI 331384948

   Inspection Date: 09/10/2008           Inspection Number: 1203606               Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: RICHARD, DICKSON                                                                                                     Issued

Violation Code     Observation                                                                                     Violation Citation

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only.                         NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                   maintenance not more than one year apart. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

License Number: 2309464                                         420 NE 70TH ST APTS
License Type: Apartment                                         420 NE 70 ST, MIAMI 331385631

   Inspection Date: 09/10/2008           Inspection Number: 1214983               Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: RICHARD, DICKSON                                                                                                     Issued

Violation Code     Observation                                                                                     Violation Citation

01-03-2            Observed an appropriately sized fire extinguisher is missing. For reporting                     61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                  Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                   installed in accordance with NFPA 10, Standard for
                                                                                                                   Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                   include guest room areas of hotels/motels, etc. [These
                                                                                                                   locations shall be protected by the installation of potable
                                                                                                                   fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                   provided for each 3000 square feet of floor space on
                                                                                                                   each level and installed so that the travel distance to
                                                                                                                   any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                   level, the area protected and the travel distances shall
                                                                                                                   be based of fire extinguishers installed in accordance
                                                                                                                   with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

License Number: 2305688                                         MORANIA BUILDING
License Type: Apartment                                         250- 260 COLLINS AVE, MIAMI BEACH 33139

   Inspection Date: 09/17/2008           Inspection Number: 1240027               Inspection Type: Lodging-Licensing                    Inspection Disposition: Inspection
   Inspector Name: TORRES-SALGADO, JOSE                                           Inspection                                            Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only.                         NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                   maintenance not more than one year apart. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

02-02-2            Observed flammable material stored in laundry/. For reporting purposes only.                    61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                   meter rooms, laundry rooms, and storage rooms shall
                                                                                                                   be kept clean and free of debris and flammables. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

02-04-2            Observed an LP gas tank having a water capacity greater than 2 1/2 lbs. on a                    NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                   balcony. For reporting purposes only.                                                           capacities greater than 21/2 pounds (1kg) shall not be
                   BY COLLINS 2nd floor                                                                            located on balconies above the first floor that are
                                                                                                                   attached to a multiple family dwelling of 3 or more living
                                                                                                                   units one above the other. Exception: Where such
                                                                                                                   balconies are served by outside stairways and where
                                                                                                                   only such stairways are used to transport the container.
                                                                                                                   FOR REPORTING PURPOSES ONLY.

02-05-2            Observed a fire hazard in the means of egress[under stairway]. For reporting                    61C-1.004(10) FAC Means of access must be
                   purposes only.                                                                                  maintained free of fire hazards. FOR REPORTING
                                                                                                                   PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 33
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2327192                                              HABANA LIBRE BEACH RESORT
License Type: Hotel                                                  3010 COLLINS AVE, MIAMI 33140

   Inspection Date: 09/16/2008               Inspection Number: 1100803              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: RICHARD, DICKSON                                                                                                        Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

06-07-2               Observed the floor diagram is missing/incorrect room 302. For reporting purposes                NFPA 101, 28-7.4.1 [Transient Establishments - Fire
                      only.                                                                                           Evacuation Requirements] A floor diagram reflecting
                                                                                                                      the actual floor arrangement, exit locations, and room
                                                                                                                      identification shall be posted in a location and manner
                                                                                                                      acceptable to the authority having jurisdiction on or
                                                                                                                      immediately adjacent to every guest room door in hotels
                                                                                                                      and should be oriented with the actual direction to the
                                                                                                                      exits. FOR REPORTING PURPOSES ONLY.

08-03                 Observed no boiler certificate available.                                                       61C-1.004(12) FAC The insurance inspector's boiler
                                                                                                                      report is required annually for power boilers and high
                                                                                                                      pressure/high temperature boilers and biannually for low
                      Boiler Information: No Boiler Certificate Provided.                                             pressure steam or vapor heating boilers and shall be
                                                                                                                      posted in the boiler room. The provisions of this section
                                                                                                                      do not apply to the common areas of resort
                                                                                                                      condominiums.

License Number: 2328225                                              CLARIDGE HOTEL
License Type: Hotel                                                  3500 COLLINS AVE, MIAMI BEACH 33140

   Inspection Date: 09/17/2008               Inspection Number: 1100488              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: RICHARD, DICKSON                                                                                                        Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

04-01-2               Observed a trouble/alarm light illuminated on the smoke detector panel connected                61C-1.004(5)FAC All fire safety, protection and
                      to the fire alarm system. For reporting purposes only.                                          prevention equipment must be installed, approved,
                                                                                                                      maintained and used in accordance with Chapter 509,
                                                                                                                      FS and the National Fire Protection Association Life
                                                                                                                      Safety Code Chapter 101, as adopted by the Division of
                                                                                                                      State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

04-10-2               Observed the fire alarm panel with an expired inspection tag. For reporting                     NFPA 72 7-3.2 and TABLE 7-3.2 Testing shall be
                      purposes only.                                                                                  performed in accordance with the schedules in Chapter
                                                                                                                      7 or more often if required by the authority having
                                                                                                                      jurisdiction. If automatic testing is performed at least
                                                                                                                      weekly by a remotely monitored fire alarm control unit
                                                                                                                      specifically listed for the application, the manual testing
                                                                                                                      frequency shall be permitted to be extended to annual.
                                                                                                                      Table 7-3.2 shall apply. All components must be tested
                                                                                                                      upon acceptance and at least annually. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

License Number: 2328890                                              OCEAN SPRAY HOTEL
License Type: Hotel                                                  4130 COLLINS AVENUE, MIAMI BEACH 33140

   Inspection Date: 09/17/2008               Inspection Number: 1101552              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: RICHARD, DICKSON                                                                                                        Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

08-03                 Observed no boiler certificate available.                                                       61C-1.004(12) FAC The insurance inspector's boiler
                                                                                                                      report is required annually for power boilers and high
                      Boiler Information: No Boiler Certificate Provided.                                             pressure/high temperature boilers and biannually for low
                                                                                                                      pressure steam or vapor heating boilers and shall be
                                                                                                                      posted in the boiler room. The provisions of this section
                                                                                                                      do not apply to the common areas of resort
                                                                                                                      condominiums.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                            Page 34
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2309886                                          7333 BYRON AVE LLC
License Type: Apartment                                          7333 BYRON AVE, NORTH BAY VILLAGE 33141

   Inspection Date: 09/15/2008            Inspection Number: 1205984               Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: TORRES-SALGADO, JOSE                                                                                                  Issued

Violation Code     Observation                                                                                      Violation Citation

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only.                          NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                    maintenance not more than one year apart. FOR
                                                                                                                    REPORTING PURPOSES ONLY.

License Number: 2307374                                          BOZY APT
License Type: Apartment                                          6949 BYRON AVE, MIAMI BEACH 331413189

   Inspection Date: 09/15/2008            Inspection Number: 1219770               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: ALONZO, GUILLERMO                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

01-06-2            Observed a locked fire extinguisher box missing a breaking device. For reporting                 NFPA 10,1-6.5 Cabinets housing fire extinguishers shall
                   purposes only.                                                                                   not be locked. Except locked cabinets may be used
                                                                                                                    provided they include means of emergency access.
                                                                                                                    FOR REPORTING PURPOSES ONLY.

License Number: 2303730                                          JOINT II APTS
License Type: Apartment                                          6950 BYRON AVE, MIAMI BEACH 331413191

   Inspection Date: 09/15/2008            Inspection Number: 1208274               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: ALONZO, GUILLERMO                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

02-02-2            Observed flammable material stored in meter room. For reporting purposes only.                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                    meter rooms, laundry rooms, and storage rooms shall
                                                                                                                    be kept clean and free of debris and flammables. FOR
                                                                                                                    REPORTING PURPOSES ONLY.

License Number: 2310367                                          SIERRA APARTMENTS
License Type: Apartment                                          6960 BYRON AVE, MIAMI BEACH 331413192

   Inspection Date: 09/15/2008            Inspection Number: 1210452               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: ALONZO, GUILLERMO                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

04-01-2            Observed a trouble/alarm light illuminated on the fire alarm control panel. For                  61C-1.004(5)FAC All fire safety, protection and
                   reporting purposes only.                                                                         prevention equipment must be installed, approved,
                                                                                                                    maintained and used in accordance with Chapter 509,
                                                                                                                    FS and the National Fire Protection Association Life
                                                                                                                    Safety Code Chapter 101, as adopted by the Division of
                                                                                                                    State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                    REPORTING PURPOSES ONLY.

License Number: 2310105                                          WATERWAY VILLAGE
License Type: Apartment                                          1945 CALAIS DR, MIAMI BEACH 331413520

   Inspection Date: 09/12/2008            Inspection Number: 1217349               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: ALONZO, GUILLERMO                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

02-02-2            Observed a build up of lint in the laundry room. For reporting purposes only.                    61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                    meter rooms, laundry rooms, and storage rooms shall
                                                                                                                    be kept clean and free of debris and flammables. FOR
                                                                                                                    REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                            Page 35
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2311369                                          NAGYMIHALY APARTMENTS
License Type: Apartment                                          2629 NW 17 AVE, MIAMI 331427667

   Inspection Date: 09/15/2008            Inspection Number: 1210918               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: KHAN, MOHAMMAD                                                                                                        Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

01-06-2            Observed a locked fire extinguisher box missing a breaking device. For reporting                 NFPA 10,1-6.5 Cabinets housing fire extinguishers shall
                   purposes only.                                                                                   not be locked. Except locked cabinets may be used
                                                                                                                    provided they include means of emergency access.
                                                                                                                    FOR REPORTING PURPOSES ONLY.

02-02-2            Observed a build up of lint in the laundry room. For reporting purposes only.                    61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                    meter rooms, laundry rooms, and storage rooms shall
                                                                                                                    be kept clean and free of debris and flammables. FOR
                                                                                                                    REPORTING PURPOSES ONLY.

License Number: 2304399                                          ALL CHRISTIANS ENTERPRISES INC
License Type: Apartment                                          5974 SW 5 TERR, MIAMI 33144

   Inspection Date: 09/19/2008            Inspection Number: 1204106               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MERNO, RAHLIBA                                                                                                        Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

06-04-2            Observed an exit sign that is not illuminated/. For reporting purposes only. By                  61-C1.004(10) FAC Exits shall be clearly marked with
                   terrace on second floor .                                                                        approved illuminated exit signs. FOR REPORTING
                                                                                                                    PURPOSES ONLY.

License Number: 2302868                                          6510 APTS
License Type: Apartment                                          6510 W FLAGLER ST, MIAMI 331442940

   Inspection Date: 09/19/2008            Inspection Number: 1217850               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MERNO, RAHLIBA                                                                                                        Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

01-03-2            Observed an insufficient number of fire extinguishers provided. For reporting                    61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only. Missing from extinguisher holder                                                  Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                    installed in accordance with NFPA 10, Standard for
                                                                                                                    Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                    include guest room areas of hotels/motels, etc. [These
                                                                                                                    locations shall be protected by the installation of potable
                                                                                                                    fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                    provided for each 3000 square feet of floor space on
                                                                                                                    each level and installed so that the travel distance to
                                                                                                                    any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                    level, the area protected and the travel distances shall
                                                                                                                    be based of fire extinguishers installed in accordance
                                                                                                                    with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                    PURPOSES ONLY.

License Number: 2309494                                          BAYMEN INN
License Type: Apartment                                          6390 W FLAGLER ST, MIAMI 331443052

   Inspection Date: 09/19/2008            Inspection Number: 1210938               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MERNO, RAHLIBA                                                                                                        Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

01-06-2            Observed a locked fire extinguisher box missing a breaking device. For reporting                 NFPA 10,1-6.5 Cabinets housing fire extinguishers shall
                   purposes only.                                                                                   not be locked. Except locked cabinets may be used
                                                                                                                    provided they include means of emergency access.
                                                                                                                    FOR REPORTING PURPOSES ONLY.

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only.                          NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                    maintenance not more than one year apart. FOR
                                                                                                                    REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                           Page 36
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2300783                                          KENDOR APTS
License Type: Apartment                                          6261 W FLAGLER ST, MIAMI 331443071

   Inspection Date: 09/16/2008            Inspection Number: 1215501              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MERNO, RAHLIBA                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

04-13-2            Observed no inspection report available for the fire alarm system. For reporting                NFPA 72, 7-5.2.2 A permanent record of all inspections,
                   purposes only.                                                                                  testing, and maintenance shall be provided that includes
                                                                                                                   the following information of periodic tests and all
                                                                                                                   applicable information requested in Figure 7-5.2.2. (a)
                                                                                                                   Date; (b) Test frequency; (c) Name of property; (d)
                                                                                                                   Address; (e) Name of person performing inspection,
                                                                                                                   maintenance, tests, or combination thereof, and
                                                                                                                   affiliation, business address, and telephone number; (f)
                                                                                                                   Name, address, and representative of approving
                                                                                                                   agency(ies); (g) Designation of the detector(s) tested;
                                                                                                                   (h) Functional test of detectors; (i) Functional test of
                                                                                                                   required sequence of operations; (j) Check of all smoke
                                                                                                                   detectors; (k) Loop resistance for all fixed-temperature
                                                                                                                   line-type heat detectors; (l) Other tests as required by
                                                                                                                   equipment manufacturers; (m) Other tests as required
                                                                                                                   by the authority having jurisdiction; (n) Signatures of
                                                                                                                   tester and approved authority representative; (o)
                                                                                                                   Disposition of problems identified during testing (e.g.,
                                                                                                                   owner notified, problem, corrected/successfully
                                                                                                                   retested, device abondoned in place). FOR
                                                                                                                   REPORTING PURPOSES ONLY.

License Number: 2305119                                          MAJESTIC APTS
License Type: Apartment                                          6150 W FLAGLER ST, MIAMI 331443200

   Inspection Date: 09/16/2008            Inspection Number: 1204108              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MERNO, RAHLIBA                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

06-04-2            Observed an exit sign that is not illuminated/For reporting purposes only.                      61-C1.004(10) FAC Exits shall be clearly marked with
                                                                                                                   approved illuminated exit signs. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

License Number: 2307142                                          6031 APTS
License Type: Apartment                                          6031 W FLAGLER ST, MIAMI 331443240

   Inspection Date: 09/16/2008            Inspection Number: 1204113              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MERNO, RAHLIBA                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-06-2            Observed a locked fire extinguisher box missing a breaking device. For reporting                NFPA 10,1-6.5 Cabinets housing fire extinguishers shall
                   purposes only.                                                                                  not be locked. Except locked cabinets may be used
                                                                                                                   provided they include means of emergency access.
                                                                                                                   FOR REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                           Page 37
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2309804                                          APARTMENT BUILDING
License Type: Apartment                                          6000 W FLAGLER ST, MIAMI 331443264

   Inspection Date: 09/16/2008            Inspection Number: 1220253              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MERNO, RAHLIBA                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-07-2            Observed a fire extinguisher not mounted at the correct height. For reporting                   NFPA 10,1-6.10 Fire extinguishers having a gross
                   purposes only.                                                                                  weight not exceeding 40 LB.shall be installed so that the
                                                                                                                   top of the fire extinguisher is not more than 5 ft. above
                                                                                                                   the floor. Fire extinguishers having a gross weight
                                                                                                                   greater than 40 LB (except wheeled type) shall be so
                                                                                                                   installed that the top of the fire extinguisher is not more
                                                                                                                   than 31/2 ft. above the floor. In no case shall the
                                                                                                                   clearance between the bottom of the fire extinguisher
                                                                                                                   and the floor be less than 4 inches. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

06-04-2            Observed an exit sign that is not illuminated/For reporting purposes only.                      61-C1.004(10) FAC Exits shall be clearly marked with
                                                                                                                   approved illuminated exit signs. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

License Number: 2309434                                          MILAN PROPERTIES
License Type: Apartment                                          6055 W FLAGLER ST, MIAMI 331443265

   Inspection Date: 09/16/2008            Inspection Number: 1206390              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MERNO, RAHLIBA                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

02-04-2            Observed an LP gas tank having a water capacity greater than 2 1/2 lbs. on a                    NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                   balcony. For reporting purposes only. Gas tank not protected.                                   capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                   located on balconies above the first floor that are
                                                                                                                   attached to a multiple family dwelling of 3 or more living
                                                                                                                   units one above the other. Exception: Where such
                                                                                                                   balconies are served by outside stairways and where
                                                                                                                   only such stairways are used to transport the container.
                                                                                                                   FOR REPORTING PURPOSES ONLY.

12-04              Observed an opening greater than 4 inches in the railing. Bars are missing                      NFPA 101, 5-2.2.4.6(c) Open guards shall have
                                                                                                                   intermediate rails or an ornamental pattern such that a
                                                                                                                   sphere 4 inch (10.1 cm) in diameter cannot pass
                                                                                                                   through any opening. [Exception No.3 to (c): Approved
                                                                                                                   existing open guards.]

License Number: 2310974                                          FLAGLER CLUB APTS
License Type: Apartment                                          6101 W FLAGLER ST, MIAMI 331443266

   Inspection Date: 09/16/2008            Inspection Number: 1215504              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: MERNO, RAHLIBA                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

07-01-2            Observed frayed wire(s). For reporting purposes only. Hallway on third floor                    61C-1.004(11)FAC Electrical wiring - To prevent fire or
                                                                                                                   injury, defective electrical wiring shall be replaced and
                                                                                                                   wiring shall be kept in good repair. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

12-04              Observed an opening greater than 4 inches in the railing.                                       NFPA 101, 5-2.2.4.6(c) Open guards shall have
                                                                                                                   intermediate rails or an ornamental pattern such that a
                                                                                                                   sphere 4 inch (10.1 cm) in diameter cannot pass
                                                                                                                   through any opening. [Exception No.3 to (c): Approved
                                                                                                                   existing open guards.]
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                             Page 38
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2304756                                          SIENNA APTS
License Type: Apartment                                          5990 W FLAGLER ST, MIAMI 331443371

   Inspection Date: 09/16/2008            Inspection Number: 1217853               Inspection Type: Routine - Lodging                     Inspection Disposition: Inspection
   Inspector Name: MERNO, RAHLIBA                                                                                                         Completed - No Further Action

Violation Code     Observation                                                                                       Violation Citation

02-02-2            Observed flammable material stored in attic/laundry/boiler room. For reporting                    61C-1.004(7) FAC Attics, basements, boiler rooms,
                   purposes only. Storage in electrical room                                                         meter rooms, laundry rooms, and storage rooms shall
                                                                                                                     be kept clean and free of debris and flammables. FOR
                                                                                                                     REPORTING PURPOSES ONLY.

06-04-2            Observed an exit sign that is not illuminated/ For reporting purposes only.                       61-C1.004(10) FAC Exits shall be clearly marked with
                                                                                                                     approved illuminated exit signs. FOR REPORTING
                                                                                                                     PURPOSES ONLY.

License Number: 2302284                                          5700 SW 2ND TERR APTS
License Type: Apartment                                          5700 SW 2 TERR, MIAMI 331443450

   Inspection Date: 09/19/2008            Inspection Number: 1217846               Inspection Type: Routine - Lodging                     Inspection Disposition: Inspection
   Inspector Name: MERNO, RAHLIBA                                                                                                         Completed - No Further Action

Violation Code     Observation                                                                                       Violation Citation

02-02-2            Observed flammable material stored in attic/laundry/boiler room. For reporting                    61C-1.004(7) FAC Attics, basements, boiler rooms,
                   purposes only. In electrical room                                                                 meter rooms, laundry rooms, and storage rooms shall
                                                                                                                     be kept clean and free of debris and flammables. FOR
                                                                                                                     REPORTING PURPOSES ONLY.

License Number: 2319601                                          JOEL INVESTMENTS APARTMENTS
License Type: Apartment                                          5831 SW 9 ST, W MIAMI 331445061

   Inspection Date: 09/19/2008            Inspection Number: 1213225               Inspection Type: Routine - Lodging                     Inspection Disposition: Inspection
   Inspector Name: MERNO, RAHLIBA                                                                                                         Completed - No Further Action

Violation Code     Observation                                                                                       Violation Citation

02-02-2            Observed flammable material stored in attic/laundry/boiler room. For reporting                    61C-1.004(7) FAC Attics, basements, boiler rooms,
                   purposes only. In electrical room                                                                 meter rooms, laundry rooms, and storage rooms shall
                                                                                                                     be kept clean and free of debris and flammables. FOR
                                                                                                                     REPORTING PURPOSES ONLY.

License Number: 2302539                                          SKYLINE PROPERTIES
License Type: Apartment                                          7001 NW 15 AVE, MIAMI 33147

   Inspection Date: 09/16/2008            Inspection Number: 1239986               Inspection Type: Complaint Full                        Inspection Disposition: Inspection
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                    Completed - No Further Action

Violation Code     Observation                                                                                       Violation Citation

01-05-2            Observed a fire extinguisher obscured from view. For reporting purposes only.                     NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                     obscured or obstructed from view. Except in large
                                                                                                                     rooms and in certain locations where visual obstruction
                                                                                                                     can not be completely avoided, a means shall be
                                                                                                                     provided to indicate location. FOR REPORTING
                                                                                                                     PURPOSES ONLY.

License Number: 2306492                                          EBONY APTS
License Type: Apartment                                          1510 NW 68 ST, MIAMI 33147

   Inspection Date: 09/16/2008            Inspection Number: 1212988               Inspection Type: Routine - Lodging                     Inspection Disposition: Warning
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                    Issued

Violation Code     Observation                                                                                       Violation Citation

01-05-2            Observed a fire extinguisher obscured from view. For reporting purposes only.                     NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                     obscured or obstructed from view. Except in large
                                                                                                                     rooms and in certain locations where visual obstruction
                                                                                                                     can not be completely avoided, a means shall be
                                                                                                                     provided to indicate location. FOR REPORTING
                                                                                                                     PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                         Page 39
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2308592                                         AUGUSTIN APARTMENT
License Type: Apartment                                         1700 NW 63 ST, MIAMI 33147

   Inspection Date: 09/16/2008           Inspection Number: 1208534              Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                 Issued

Violation Code     Observation                                                                                    Violation Citation

01-05-2            Observed a fire extinguisher obscured from view. For reporting purposes only.                  NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                  obscured or obstructed from view. Except in large
                                                                                                                  rooms and in certain locations where visual obstruction
                                                                                                                  can not be completely avoided, a means shall be
                                                                                                                  provided to indicate location. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

License Number: 2327032                                         GONZALEZ APTS
License Type: Apartment                                         10600 NW 27 AVE APT 4, MIAMI 33147

   Inspection Date: 09/16/2008           Inspection Number: 1203914              Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                 Issued

Violation Code     Observation                                                                                    Violation Citation

01-05-2            Observed a fire extinguisher obscured from view. For reporting purposes only.                  NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                  obscured or obstructed from view. Except in large
                                                                                                                  rooms and in certain locations where visual obstruction
                                                                                                                  can not be completely avoided, a means shall be
                                                                                                                  provided to indicate location. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

License Number: 2328119                                         SEVEN STARS
License Type: Apartment                                         791 NW 95 ST, MIAMI 33147

   Inspection Date: 09/16/2008           Inspection Number: 1220048              Inspection Type: Routine - Lodging                    Inspection Disposition: Administrative
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                 complaint recommended

Violation Code     Observation                                                                                    Violation Citation

01-03-2            Observed an insufficient number of fire extinguishers provided. For reporting                  61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                 Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                  installed in accordance with NFPA 10, Standard for
                                                                                                                  Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                  include guest room areas of hotels/motels, etc. [These
                                                                                                                  locations shall be protected by the installation of potable
                                                                                                                  fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                  provided for each 3000 square feet of floor space on
                                                                                                                  each level and installed so that the travel distance to
                                                                                                                  any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                  level, the area protected and the travel distances shall
                                                                                                                  be based of fire extinguishers installed in accordance
                                                                                                                  with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

07-06-2            Observed an electrical box missing a cover. For reporting purposes only.                       NFPA 70, 300-31 Suitable covers shall be installed on
                                                                                                                  all boxes to prevent accidental contact with energized
                                                                                                                  parts or physical damage to parts or insulation. FOR
                                                                                                                  REPORTING PURPOSES ONLY.

License Number: 2328400                                         DREAM APTS (THE)
License Type: Apartment                                         6229 NW 2 AVE, MIAMI 33147

   Inspection Date: 09/16/2008           Inspection Number: 1213019              Inspection Type: Routine - Lodging                    Inspection Disposition: Administrative
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                 complaint recommended

Violation Code     Observation                                                                                    Violation Citation

01-05-2            Observed a fire extinguisher obscured from view. For reporting purposes only.                  NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                  obscured or obstructed from view. Except in large
                                                                                                                  rooms and in certain locations where visual obstruction
                                                                                                                  can not be completely avoided, a means shall be
                                                                                                                  provided to indicate location. FOR REPORTING
                                                                                                                  PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                          Page 40
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2329277                                          MT 1231 LLC
License Type: Apartment                                          1231 NW 61 ST, MIAMI 33147

   Inspection Date: 09/16/2008            Inspection Number: 1239984              Inspection Type: Lodging-Licensing                   Inspection Disposition: Inspection
   Inspector Name: DE LOS SANTOS, JUAN                                            Inspection                                           Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-03-2            Observed an insufficient number of fire extinguishers provided. For reporting                  61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                 Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                  installed in accordance with NFPA 10, Standard for
                                                                                                                  Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                  include guest room areas of hotels/motels, etc. [These
                                                                                                                  locations shall be protected by the installation of potable
                                                                                                                  fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                  provided for each 3000 square feet of floor space on
                                                                                                                  each level and installed so that the travel distance to
                                                                                                                  any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                  level, the area protected and the travel distances shall
                                                                                                                  be based of fire extinguishers installed in accordance
                                                                                                                  with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

01-05-2            Observed a fire extinguisher obscured from view. For reporting purposes only.                  NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                  obscured or obstructed from view. Except in large
                                                                                                                  rooms and in certain locations where visual obstruction
                                                                                                                  can not be completely avoided, a means shall be
                                                                                                                  provided to indicate location. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

04-01-2            Observed an alarm silenced on the fire alarm control panel. For reporting                      61C-1.004(5)FAC All fire safety, protection and
                   purposes only.                                                                                 prevention equipment must be installed, approved,
                                                                                                                  maintained and used in accordance with Chapter 509,
                                                                                                                  FS and the National Fire Protection Association Life
                                                                                                                  Safety Code Chapter 101, as adopted by the Division of
                                                                                                                  State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                  REPORTING PURPOSES ONLY.

04-11-2            Observed the fire alarm system not being maintained. For reporting purposes only.              NFPA 72, 7-4.1 Fire alarm system equipment shall be
                                                                                                                  maintained in accordance with the manufacturer's
                                                                                                                  instructions. The frequency of maintenance shall
                                                                                                                  depend on the type of equipment and the local ambient
                                                                                                                  conditions. FOR REPORTING PURPOSES ONLY.

04-13-2            Observed no inspection report available for the fire alarm system. For reporting               NFPA 72, 7-5.2.2 A permanent record of all inspections,
                   purposes only.                                                                                 testing, and maintenance shall be provided that includes
                                                                                                                  the following information of periodic tests and all
                                                                                                                  applicable information requested in Figure 7-5.2.2. (a)
                                                                                                                  Date; (b) Test frequency; (c) Name of property; (d)
                                                                                                                  Address; (e) Name of person performing inspection,
                                                                                                                  maintenance, tests, or combination thereof, and
                                                                                                                  affiliation, business address, and telephone number; (f)
                                                                                                                  Name, address, and representative of approving
                                                                                                                  agency(ies); (g) Designation of the detector(s) tested;
                                                                                                                  (h) Functional test of detectors; (i) Functional test of
                                                                                                                  required sequence of operations; (j) Check of all smoke
                                                                                                                  detectors; (k) Loop resistance for all fixed-temperature
                                                                                                                  line-type heat detectors; (l) Other tests as required by
                                                                                                                  equipment manufacturers; (m) Other tests as required
                                                                                                                  by the authority having jurisdiction; (n) Signatures of
                                                                                                                  tester and approved authority representative; (o)
                                                                                                                  Disposition of problems identified during testing (e.g.,
                                                                                                                  owner notified, problem, corrected/successfully
                                                                                                                  retested, device abondoned in place). FOR
                                                                                                                  REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                           Page 41
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2300873                                         BRYANT APARTMENT
License Type: Apartment                                         6820 NW 17 AVE, MIAMI 331477475

   Inspection Date: 09/16/2008           Inspection Number: 1215282               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DE LOS SANTOS, JUAN                                                                                                  Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-05-2            Observed a fire extinguisher obscured from view. For reporting purposes only.                   NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                   obscured or obstructed from view. Except in large
                                                                                                                   rooms and in certain locations where visual obstruction
                                                                                                                   can not be completely avoided, a means shall be
                                                                                                                   provided to indicate location. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

License Number: 2328401                                         GMAL APTS
License Type: Apartment                                         6832 NW 5 PL, MIAMI 33150

   Inspection Date: 09/10/2008           Inspection Number: 1219711               Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: RICHARD, DICKSON                                                                                                     Issued

Violation Code     Observation                                                                                     Violation Citation

01-03-2            Observed an appropriately sized fire extinguisher is missing. For reporting                     61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                  Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                   installed in accordance with NFPA 10, Standard for
                                                                                                                   Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                   include guest room areas of hotels/motels, etc. [These
                                                                                                                   locations shall be protected by the installation of potable
                                                                                                                   fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                   provided for each 3000 square feet of floor space on
                                                                                                                   each level and installed so that the travel distance to
                                                                                                                   any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                   level, the area protected and the travel distances shall
                                                                                                                   be based of fire extinguishers installed in accordance
                                                                                                                   with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

License Number: 2329020                                         MYAMI MONEY GROUP INC
License Type: Rooming House                                     7808 NW 7 AVE, MIAMI 33150

   Inspection Date: 09/15/2008           Inspection Number: 1088789               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: RICHARD, DICKSON                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-03-2            Observed an appropriately sized fire extinguisher is missing. For reporting                     61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                  Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                   installed in accordance with NFPA 10, Standard for
                                                                                                                   Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                   include guest room areas of hotels/motels, etc. [These
                                                                                                                   locations shall be protected by the installation of potable
                                                                                                                   fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                   provided for each 3000 square feet of floor space on
                                                                                                                   each level and installed so that the travel distance to
                                                                                                                   any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                   level, the area protected and the travel distances shall
                                                                                                                   be based of fire extinguishers installed in accordance
                                                                                                                   with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                   PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                           Page 42
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2314247                                          BAYVIEW 60 APTS
License Type: Apartment                                          3800 NE 168 ST, NORTH MIAMI BEACH 331603594

   Inspection Date: 09/18/2008            Inspection Number: 1215141              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: TONEY, BRANDY                                                                                                        Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

06-16-2            Observed the stair signage is inadequate/not provided. For reporting purposes                   NFPA 101, 7-2.2.5.4 Stairs serving five or more stories
                   only.                                                                                           shall be provided with signage within the enclosure at
                                                                                                                   each floor landing. The signage shall indicate the floor
                                                                                                                   level, the terminus of the top and bottom of the stair
                                                                                                                   enclosure, and the identification of the stair. The
                                                                                                                   signage also shall state the floor level of, and the direct
                                                                                                                   to, exit discharge. The signage shall be inside the
                                                                                                                   enclosure, located approximately 5 ft above the floor
                                                                                                                   landing in a position that is readily visible when the door
                                                                                                                   is in the open or closed position. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

06-20-2            Observed an exit sign in disrepair. For reporting purposes only.                                61C-1.004(5)FAC All fire safety, protection and
                                                                                                                   prevention equipment must be installed, approved,
                                                                                                                   maintained and used in accordance with Chapter 509,
                                                                                                                   FS and the National Fire Protection Association Life
                                                                                                                   Safety Code Chapter 101, as adopted by the Division of
                                                                                                                   State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

06-20-2            Observed a missing emergency light. For reporting purposes only.                                61C-1.004(5)FAC All fire safety, protection and
                                                                                                                   prevention equipment must be installed, approved,
                                                                                                                   maintained and used in accordance with Chapter 509,
                                                                                                                   FS and the National Fire Protection Association Life
                                                                                                                   Safety Code Chapter 101, as adopted by the Division of
                                                                                                                   State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

License Number: 2312176                                          SUN WORLD APARTMENTS
License Type: Apartment                                          3847 NE 168 ST, NORTH MIAMI BEACH 331603597

   Inspection Date: 09/18/2008            Inspection Number: 1208351              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: TONEY, BRANDY                                                                                                        Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

06-16-2            Observed the stair signage is inadequate/not provided. For reporting purposes                   NFPA 101, 7-2.2.5.4 Stairs serving five or more stories
                   only.                                                                                           shall be provided with signage within the enclosure at
                                                                                                                   each floor landing. The signage shall indicate the floor
                                                                                                                   level, the terminus of the top and bottom of the stair
                                                                                                                   enclosure, and the identification of the stair. The
                                                                                                                   signage also shall state the floor level of, and the direct
                                                                                                                   to, exit discharge. The signage shall be inside the
                                                                                                                   enclosure, located approximately 5 ft above the floor
                                                                                                                   landing in a position that is readily visible when the door
                                                                                                                   is in the open or closed position. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

License Number: 2308431                                          DAVID APARTMENTS
License Type: Apartment                                          54 CANAL ST, MIAMI SPGS 331664404

   Inspection Date: 09/17/2008            Inspection Number: 1208332              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: JARAMILLO, MARIA C                                                                                                   Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-07-2            Observed a fire extinguisher on the ground/floor. For reporting purposes only.                  NFPA 10,1-6.10 Fire extinguishers having a gross
                                                                                                                   weight not exceeding 40 LB.shall be installed so that the
                                                                                                                   top of the fire extinguisher is not more than 5 ft. above
                                                                                                                   the floor. Fire extinguishers having a gross weight
                                                                                                                   greater than 40 LB (except wheeled type) shall be so
                                                                                                                   installed that the top of the fire extinguisher is not more
                                                                                                                   than 31/2 ft. above the floor. In no case shall the
                                                                                                                   clearance between the bottom of the fire extinguisher
                                                                                                                   and the floor be less than 4 inches. FOR REPORTING
                                                                                                                   PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                           Page 43
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Dade County

License Number: 2326973                                          CARRIBEAN WEST APARTMENTS
License Type: Apartment                                          12140 SW 200 ST, MIAMI 33177

   Inspection Date: 09/15/2008            Inspection Number: 1208748              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: ALFONSO, ARELYS                                                                                                      Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-05-2            Observed a fire extinguisher obscured from view. For reporting purposes only.                   NFPA 10, 1-6.10 Fire extinguishers shall not be
                   Corrected On Site.                                                                              obscured or obstructed from view. Except in large
                                                                                                                   rooms and in certain locations where visual obstruction
                                                                                                                   can not be completely avoided, a means shall be
                                                                                                                   provided to indicate location. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

04-13-2            Observed no inspection report available for the fire alarm system. For reporting                NFPA 72, 7-5.2.2 A permanent record of all inspections,
                   purposes only.                                                                                  testing, and maintenance shall be provided that includes
                                                                                                                   the following information of periodic tests and all
                                                                                                                   applicable information requested in Figure 7-5.2.2. (a)
                                                                                                                   Date; (b) Test frequency; (c) Name of property; (d)
                                                                                                                   Address; (e) Name of person performing inspection,
                                                                                                                   maintenance, tests, or combination thereof, and
                                                                                                                   affiliation, business address, and telephone number; (f)
                                                                                                                   Name, address, and representative of approving
                                                                                                                   agency(ies); (g) Designation of the detector(s) tested;
                                                                                                                   (h) Functional test of detectors; (i) Functional test of
                                                                                                                   required sequence of operations; (j) Check of all smoke
                                                                                                                   detectors; (k) Loop resistance for all fixed-temperature
                                                                                                                   line-type heat detectors; (l) Other tests as required by
                                                                                                                   equipment manufacturers; (m) Other tests as required
                                                                                                                   by the authority having jurisdiction; (n) Signatures of
                                                                                                                   tester and approved authority representative; (o)
                                                                                                                   Disposition of problems identified during testing (e.g.,
                                                                                                                   owner notified, problem, corrected/successfully
                                                                                                                   retested, device abondoned in place). FOR
                                                                                                                   REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 44
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Duval County

License Number: 2608774                                            SAN JOSE VILLAGE
License Type: Apartment                                            8291 OLD KINGS RD, JACKSONVILLE 32217

   Inspection Date: 09/16/2008              Inspection Number: 1210034               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: TUCKER, CATHY                                                                                                           Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

01-05-2               Observed a fire extinguisher obscured from view. For reporting purposes only.                   NFPA 10, 1-6.10 Fire extinguishers shall not be
                      None on exterior of property                                                                    obscured or obstructed from view. Except in large
                                                                                                                      rooms and in certain locations where visual obstruction
                                                                                                                      can not be completely avoided, a means shall be
                                                                                                                      provided to indicate location. FOR REPORTING
                                                                                                                      PURPOSES ONLY.

License Number: 2601603                                            ETTA MOTEL
License Type: Motel                                                5913 W MONCRIEF RD, JACKSONVILLE 322193438

   Inspection Date: 09/17/2008              Inspection Number: 1124187               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: ESPINOSA-BECKERT, ILIANA                                                                                                Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

07-08-2               Observed an open spaces in an electrical box. For reporting purposes only. panel                NFPA 70, 110-12(a) Unused openings in boxes or
                      by water heater                                                                                 housings shall be effectively closed to afford protection
                                                                                                                      substantially equivalent to the wall of the equipment.
                                                                                                                      FOR REPORTING PURPOSES ONLY.

License Number: 2612564                                            HILTON GARDEN INN
License Type: Hotel                                                9745 GATE PKWY, JACKSONVILLE 32246

   Inspection Date: 09/12/2008              Inspection Number: 1105010               Inspection Type: Routine - Lodging                    Inspection Disposition: Administrative
   Inspector Name: BRADSHAW, BONNIE                                                                                                        complaint recommended

Violation Code        Observation                                                                                     Violation Citation

03-02                 Observed a fire sprinkler system not being maintained. connection endcap                        61C-1.004(5)FAC All fire safety, protection and
                      missing                                                                                         prevention equipment must be installed, approved,
                                                                                                                      maintained and used in accordance with Chapter 509,
                                                                                                                      FS and the National Fire Protection Association Life
                                                                                                                      Safety Code Chapter 101, as adopted by the Division of
                                                                                                                      State Fire Marshal in Chapter 4A-3, FAC.

03-09                 Observed a fire sprinkler head/deflector with less than an 18 inch clearance                    NFPA 13, 4-5.5.3 and 5-5.6 Continuous or
                      provided. 5th and 2nd floor                                                                     noncontinuous obstructions that interrupt the water
                                                                                                                      discharge in a horizontal plane more than 18 inches
                                                                                                                      below the sprinkler deflector in a manner to limit the
                                                                                                                      distribution from reaching the protected hazard shall
                                                                                                                      comply with this section. The clearance between the
                                                                                                                      deflector and the top of storage shall be 18 inches or
                                                                                                                      greater.

04-01-2               Observed a trouble/alarm light illuminated on the fire alarm control panel. For                 61C-1.004(5)FAC All fire safety, protection and
                      reporting purposes only. maintenance stated that system needs to be reset from                  prevention equipment must be installed, approved,
                      earlier work done                                                                               maintained and used in accordance with Chapter 509,
                                                                                                                      FS and the National Fire Protection Association Life
                                                                                                                      Safety Code Chapter 101, as adopted by the Division of
                                                                                                                      State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

06-16-2               Observed the stair signage is inadequate/not provided. missing direction to                     NFPA 101, 7-2.2.5.4 Stairs serving five or more stories
                      discharge. For reporting purposes only.                                                         shall be provided with signage within the enclosure at
                                                                                                                      each floor landing. The signage shall indicate the floor
                                                                                                                      level, the terminus of the top and bottom of the stair
                                                                                                                      enclosure, and the identification of the stair. The
                                                                                                                      signage also shall state the floor level of, and the direct
                                                                                                                      to, exit discharge. The signage shall be inside the
                                                                                                                      enclosure, located approximately 5 ft above the floor
                                                                                                                      landing in a position that is readily visible when the door
                                                                                                                      is in the open or closed position. FOR REPORTING
                                                                                                                      PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                           Page 45
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Duval County

License Number: 2603947                                         PLAZA APARTMENTS
License Type: Apartment                                         3780 UNIVERSITY CLUB BLVD, JACKSONVILLE 32277-1974

   Inspection Date: 09/12/2008           Inspection Number: 1205479               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DAVIS, MOSES                                                                                                         Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

04-10-2            Observed the fire alarm panel with an expired inspection tag. For reporting                     NFPA 72 7-3.2 and TABLE 7-3.2 Testing shall be
                   purposes only.                                                                                  performed in accordance with the schedules in Chapter
                                                                                                                   7 or more often if required by the authority having
                                                                                                                   jurisdiction. If automatic testing is performed at least
                                                                                                                   weekly by a remotely monitored fire alarm control unit
                                                                                                                   specifically listed for the application, the manual testing
                                                                                                                   frequency shall be permitted to be extended to annual.
                                                                                                                   Table 7-3.2 shall apply. All components must be tested
                                                                                                                   upon acceptance and at least annually. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

07-08-2            Observed an open spaces in an electrical box. For reporting purposes onlly.                     NFPA 70, 110-12(a) Unused openings in boxes or
                   301.                                                                                            housings shall be effectively closed to afford protection
                                                                                                                   substantially equivalent to the wall of the equipment.
                                                                                                                   FOR REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                             Page 46
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Escambia County

License Number: 2702623                                            HOSPITALITY INN
License Type: Motel                                                4910 MOBILE HWY, PENSACOLA 32506

   Inspection Date: 09/15/2008              Inspection Number: 1125725              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: LEWANDOWSKI, KAREN                                                                                                     Completed - No Further Action

Violation Code        Observation                                                                                    Violation Citation

06-07-2               Observed the floor diagram/emergency instructions is missing/incorrect in room                 NFPA 101, 28-7.4.1 [Transient Establishments - Fire
                      101. For reporting purposes only.                                                              Evacuation Requirements] A floor diagram reflecting
                                                                                                                     the actual floor arrangement, exit locations, and room
                                                                                                                     identification shall be posted in a location and manner
                                                                                                                     acceptable to the authority having jurisdiction on or
                                                                                                                     immediately adjacent to every guest room door in hotels
                                                                                                                     and should be oriented with the actual direction to the
                                                                                                                     exits. FOR REPORTING PURPOSES ONLY.

06-07-2               Observed the floor diagram is missing/incorrect. Room 113. For reporting                       NFPA 101, 28-7.4.1 [Transient Establishments - Fire
                      purposes only.                                                                                 Evacuation Requirements] A floor diagram reflecting
                                                                                                                     the actual floor arrangement, exit locations, and room
                                                                                                                     identification shall be posted in a location and manner
                                                                                                                     acceptable to the authority having jurisdiction on or
                                                                                                                     immediately adjacent to every guest room door in hotels
                                                                                                                     and should be oriented with the actual direction to the
                                                                                                                     exits. FOR REPORTING PURPOSES ONLY.

06-07-2               Observed the floor diagram is missing/incorrect in room207. For reporting                      NFPA 101, 28-7.4.1 [Transient Establishments - Fire
                      purposes only.                                                                                 Evacuation Requirements] A floor diagram reflecting
                                                                                                                     the actual floor arrangement, exit locations, and room
                                                                                                                     identification shall be posted in a location and manner
                                                                                                                     acceptable to the authority having jurisdiction on or
                                                                                                                     immediately adjacent to every guest room door in hotels
                                                                                                                     and should be oriented with the actual direction to the
                                                                                                                     exits. FOR REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                            Page 47
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Flagler County

License Number: 2800155                                           OCEAN SHORE VILLA
License Type: Motel                                               6287 N OCEAN SHORE BLVD, PALM COAST 321372412

   Inspection Date: 09/16/2008              Inspection Number: 1123403             Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: SCARPELLI, DAVID                                                                                                      Completed - No Further Action

Violation Code        Observation                                                                                   Violation Citation

07-02-2               Observed an extension cord in use. For reporting purposes only.                               61C-1.004(11) FAC No extension cords shall be used
                                                                                                                    except during cleaning, maintenance and other
                                                                                                                    temporary activities. FOR REPORTING PURPOSES
                                                                                                                    ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                             Page 48
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Hamilton County

License Number: 3400021                                            SCOTTISH INN WEST
License Type: Motel                                                8075 W SR 6, JASPER 32052

   Inspection Date: 09/15/2008              Inspection Number: 1125675              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: HENTGES, JUDY                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                    Violation Citation

01-09-2               Observed a fire extinguisher pressure gauge indicating the extinguisher is in need             NFPA 10,1-6.2 Portable extinguishers shall be
                      of recharge. For reporting purposes only. near room 164                                        maintained in a fully charged and operable condition.
                                                                                                                     FOR REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 49
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Hernando County

License Number: 3700022                                             SUNSET MOTEL
License Type: Motel                                                 301 W BROAD ST, BROOKSVILLE 34601

   Inspection Date: 09/16/2008               Inspection Number: 1123949              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DANCHO, JOHN                                                                                                            Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

04-15-2               Observed no completed/up to date smoke detector log for the battery powered                     69A-43.009(1)(b)(c)FAC Battery powered, single station
                      smoke detectors. For reporting purposes only. Corrected On Site.                                smoke detectors, where used, shall be tested and
                                                                                                                      inspected not less frequently than once per week. A log
                                                                                                                      of the required tests and inspections shall be kept and
                                                                                                                      available to the authority having jurisdiction at any time.
                                                                                                                      This log shall include, but not be limited to, the following
                                                                                                                      information and any other information as may be
                                                                                                                      required by the authority having jurisdiction; 1. A list,
                                                                                                                      clearly identifying each individual detector by its physical
                                                                                                                      location. 2. The date of each required test and
                                                                                                                      inspection. 3. The identity and signature of the
                                                                                                                      inspector. 4. The result of each test and inspection. 5.
                                                                                                                      The completion date and form of any maintenance
                                                                                                                      performed. 6. The completion date and form of any
                                                                                                                      corrective measures taken for each improperly
                                                                                                                      functioning device. 7. A copy of the manufacturer's
                                                                                                                      recommended maintenance schedule and procedures.
                                                                                                                      (c) At such time that the authority having jurisdiction
                                                                                                                      finds cause to believe that the requirements of (a) or (b)
                                                                                                                      are not being fulfilled, detectors powered by the building
                                                                                                                      electrical system shall be required. FOR REPORTING
                                                                                                                      PURPOSES ONLY.

License Number: 3700048                                             BUDGET INN
License Type: Motel                                                 1795 E JEFFERSTON ST, BROOKSVILLE 34601

   Inspection Date: 09/17/2008               Inspection Number: 1127627              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DANCHO, JOHN                                                                                                            Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed a build up of lint in the laundry room....behind dryer. For reporting                  61C-1.004(7) FAC Attics, basements, boiler rooms,
                      purposes only.                                                                                  meter rooms, laundry rooms, and storage rooms shall
                                                                                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

04-01-2               Observed a smoke detector not functioning when tested....room #106. For                         61C-1.004(5)FAC All fire safety, protection and
                      reporting purposes only. Corrected On Site.                                                     prevention equipment must be installed, approved,
                                                                                                                      maintained and used in accordance with Chapter 509,
                                                                                                                      FS and the National Fire Protection Association Life
                                                                                                                      Safety Code Chapter 101, as adopted by the Division of
                                                                                                                      State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                      REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                                  Page 50
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Hillsborough County

License Number: 3905029                                              HYATT REGENCY TAMPA CITY CTR
License Type: Hotel                                                  211 N TAMPA ST, TAMPA 336025144

   Inspection Date: 09/11/2008               Inspection Number: 1100270                Inspection Type: Routine - Lodging                     Inspection Disposition: Inspection
   Inspector Name: KLUSENDORF, JEANNE                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                        Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.                      61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                         meter rooms, laundry rooms, and storage rooms shall
                                                                                                                         be kept clean and free of debris and flammables. FOR
                                                                                                                         REPORTING PURPOSES ONLY.

License Number: 3901566                                              DAYS INN AIRPORT
License Type: Motel                                                  2522 N DALE MABRY, TAMPA 33607

   Inspection Date: 09/16/2008               Inspection Number: 1134624                Inspection Type: Complaint Full                        Inspection Disposition: Inspection
   Inspector Name: MIRABELLA, FRANK                                                                                                           Completed - No Further Action

Violation Code        Observation                                                                                        Violation Citation

08-03                 Observed an expired boiler certificate.                                                            61C-1.004(12) FAC The insurance inspector's boiler
                                                                                                                         report is required annually for power boilers and high
                      Boiler Information: Boiler Jurisdiction Number: FL093998, Boiler Expiration Date:                  pressure/high temperature boilers and biannually for low
                      05/26/08                                                                                           pressure steam or vapor heating boilers and shall be
                                                                                                                         posted in the boiler room. The provisions of this section
                                                                                                                         do not apply to the common areas of resort
                                                                                                                         condominiums.

License Number: 3912117                                              PALM TREE APTS
License Type: Apartment                                              13113 N 22 ST, TAMPA 33612

   Inspection Date: 09/18/2008               Inspection Number: 1207192                Inspection Type: Routine - Lodging                     Inspection Disposition: Inspection
   Inspector Name: CHEW, TEOW                                                                                                                 Completed - No Further Action

Violation Code        Observation                                                                                        Violation Citation

04-01-2               Observed a smoke detector not functioning when tested. For reporting purposes                      61C-1.004(5)FAC All fire safety, protection and
                      only.(apt. 3)                                                                                      prevention equipment must be installed, approved,
                                                                                                                         maintained and used in accordance with Chapter 509,
                                                                                                                         FS and the National Fire Protection Association Life
                                                                                                                         Safety Code Chapter 101, as adopted by the Division of
                                                                                                                         State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                         REPORTING PURPOSES ONLY.

License Number: 3912809                                              GABLES WEST PARK VILLAGE
License Type: Apartment                                              10116 MONTAGUE ST, TAMPA 33626

   Inspection Date: 04/16/2008               Inspection Number: 1240049                Inspection Type: Routine - Lodging                     Inspection Disposition: Warning
   Inspector Name: DECKER, RICHARD                                                                                                            Issued

Violation Code        Observation                                                                                        Violation Citation

04-01                 Out of compliance: All fire safety, protection and prevention equipment must be                    61C-1.004(5)FAC All fire safety, protection and
                      installed, approved, maintained and used in accordance with Chapter 509, FS and                    prevention equipment must be installed, approved,
                      the National Fire Protection Association Life Safety Code Chapter 101, as adopted                  maintained and used in accordance with Chapter 509,
                      by the Division of State Fire Marshal in Chapter 4A-3, FAC.                                        FS and the National Fire Protection Association Life
                                                                                                                         Safety Code Chapter 101, as adopted by the Division of
                                                                                                                         State Fire Marshal in Chapter 4A-3, FAC.

07-08                 Out of compliance: Unused openings in boxes or housings shall be effectively                       NFPA 70, 110-12(a) Unused openings in boxes or
                      closed to afford protection substantially equivalent to the wall of the equipment.                 housings shall be effectively closed to afford protection
                                                                                                                         substantially equivalent to the wall of the equipment.

   Inspection Date: 07/01/2008               Inspection Number: 1240049                Inspection Type: Routine - Lodging                     Inspection Disposition: Call Back -
   Inspector Name: DECKER, RICHARD                                                                                                            Admin. complaint recommended

Violation Code        Observation                                                                                        Violation Citation

07-08                 Out of compliance: Unused openings in boxes or housings shall be effectively                       NFPA 70, 110-12(a) Unused openings in boxes or
                      closed to afford protection substantially equivalent to the wall of the equipment.                 housings shall be effectively closed to afford protection
                                                                                                                         substantially equivalent to the wall of the equipment.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                         Page 51
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Indian River County

License Number: 4100212                                        SPORTSMAN'S MARINA & LODGE
License Type: Apartment                                        412 S INDIAN RIVER DR, SEBASTIAN 329584708

   Inspection Date: 09/15/2008           Inspection Number: 1218914             Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: SCHOENLY, BARBARA                                                                                                  Completed - No Further Action

Violation Code     Observation                                                                                   Violation Citation

07-02-2            Observed an extension cord in use./laundry For reporting purposes only.                       61C-1.004(11) FAC No extension cords shall be used
                                                                                                                 except during cleaning, maintenance and other
                                                                                                                 temporary activities. FOR REPORTING PURPOSES
                                                                                                                 ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                            Page 52
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Jackson County

License Number: 4200454                                          SUPER 8 MOTEL
License Type: Motel                                              2226 HWY 71, MARIANNA 32448

   Inspection Date: 09/15/2008             Inspection Number: 1134611             Inspection Type: Complaint Full                        Inspection Disposition: Inspection
   Inspector Name: HARDING, LINDA                                                                                                        Completed - No Further Action

Violation Code        Observation                                                                                   Violation Citation

04-01-2               Observed a smoke detector hanging by the wires. For reporting purposes only.                  61C-1.004(5)FAC All fire safety, protection and
                      Corrected On Site.                                                                            prevention equipment must be installed, approved,
                                                                                                                    maintained and used in accordance with Chapter 509,
                                                                                                                    FS and the National Fire Protection Association Life
                                                                                                                    Safety Code Chapter 101, as adopted by the Division of
                                                                                                                    State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                    REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 53
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Lake County

License Number: 4500326                                            PALACE HOTELS & RESORTS
License Type: Motel                                                20349 US HWY 27, CLERMONT 347118797

   Inspection Date: 09/18/2008              Inspection Number: 1123367               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: CRISTWELL, HENRY                                                                                                        Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

04-10-2               Observed the fire alarm panel with an expired inspection tag. For reporting                     NFPA 72 7-3.2 and TABLE 7-3.2 Testing shall be
                      purposes only. Dated 07/07                                                                      performed in accordance with the schedules in Chapter
                                                                                                                      7 or more often if required by the authority having
                                                                                                                      jurisdiction. If automatic testing is performed at least
                                                                                                                      weekly by a remotely monitored fire alarm control unit
                                                                                                                      specifically listed for the application, the manual testing
                                                                                                                      frequency shall be permitted to be extended to annual.
                                                                                                                      Table 7-3.2 shall apply. All components must be tested
                                                                                                                      upon acceptance and at least annually. FOR
                                                                                                                      REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                          Page 54
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Lee County

License Number: 4603937                                         ABACO BEACH VAC VILLAS
License Type: Apartment                                         133 ESTERO BLVD, FT MYERS BCH 339312010

   Inspection Date: 09/11/2008           Inspection Number: 1219593              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: HUGHES, RANDALL                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only.abc exterior            NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                   fire extinguisher has a tag date of 12/2006 on first floor at rear of building                 maintenance not more than one year apart. FOR
                                                                                                                  REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 55
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Leon County

License Number: 4702017                                             SUBURBAN EXTENDED STAY HOTEL
License Type: Motel                                                 521 SILVER SLIPPER LN, TALLAHASSEE 32304

   Inspection Date: 09/19/2008               Inspection Number: 1126473              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: PRAGER, JOAN                                                                                                            Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

01-06-2               Observed a locked fire extinguisher box missing a breaking device by room 258.                  NFPA 10,1-6.5 Cabinets housing fire extinguishers shall
                      For reporting purposes only.                                                                    not be locked. Except locked cabinets may be used
                                                                                                                      provided they include means of emergency access.
                                                                                                                      FOR REPORTING PURPOSES ONLY.

License Number: 4702799                                             SKYVIEW APARTMENTS
License Type: Apartment                                             615 ST AUGUSTINE RD, TALLAHASSEE 32304

   Inspection Date: 09/18/2008               Inspection Number: 1205607              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: HARGROVE, DAVID                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

07-06-2               Observed an electrical outlet cracked cover plate in the laundry room. For                      NFPA 70, 300-31 Suitable covers shall be installed on
                      reporting purposes only.                                                                        all boxes to prevent accidental contact with energized
                                                                                                                      parts or physical damage to parts or insulation. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

07-06-2               Observed (2) electrical outlets missing a cover plate in the laundry room. For                  NFPA 70, 300-31 Suitable covers shall be installed on
                      reporting purposes only.                                                                        all boxes to prevent accidental contact with energized
                                                                                                                      parts or physical damage to parts or insulation. FOR
                                                                                                                      REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                             Page 56
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Marion County

License Number: 5202449                                            BEST WESTERN OCALA PARK CENTRE
License Type: Hotel                                                3701 SW 38 AVE, OCALA 34474-4383

   Inspection Date: 09/17/2008              Inspection Number: 1099640              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: ANAZIA, ROLAND                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                    Violation Citation

07-04-2               Observed a splitter/multi-plug adapter in use. For reporting purposes only. Room               61C-1.004(11)FAC In accordance with the provisions of
                      #212 .                                                                                         NFPA 70, the National Electrical Code, as adopted by
                                                                                                                     the Division of State Fire Marshal in Chapter 4A03,
                                                                                                                     FAC, Uniform Fire Safety Rules and Standards,
                                                                                                                     sufficient electrical outlets shall be provided. FOR
                                                                                                                     REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 57
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Martin County

License Number: 5300982                                             JUPITER WATERFRONT INN
License Type: Motel                                                 18903 SE US 1, TEQUESTA 33469

   Inspection Date: 09/12/2008               Inspection Number: 1127499              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DERVIN, RICHARD                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.dryer.             61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                      meter rooms, laundry rooms, and storage rooms shall
                                                                                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 58
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Monroe County

License Number: 5400615                                             DAYS INN OCEAN FRONT SUITES
License Type: Motel                                                 82749 OVERSEAS HWY, ISLAMORADA 330363609

   Inspection Date: 09/18/2008               Inspection Number: 1128095              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: ALFONSO, ARELYS                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

01-28.22              Observed a standpipe inspection report is not available. For reporting purposes                 NFPA 25, 1-8 Records. Records of inspections, tests
                      only.                                                                                           and maintenance of the system and its components
                                                                                                                      shall be made available to the authority having
                                                                                                                      jurisdiction upon request. Typical records include, but
                                                                                                                      are not limited to, valve inspections; flow, drain, and
                                                                                                                      pump tests; and trip tests of dry pipe, deluge, and
                                                                                                                      preaction valves. FOR REPORTING PURPOSES
                                                                                                                      ONLY.

04-10-2               Observed the fire alarm panel with an expired inspection tag. For reporting                     NFPA 72 7-3.2 and TABLE 7-3.2 Testing shall be
                      purposes only.                                                                                  performed in accordance with the schedules in Chapter
                                                                                                                      7 or more often if required by the authority having
                                                                                                                      jurisdiction. If automatic testing is performed at least
                                                                                                                      weekly by a remotely monitored fire alarm control unit
                                                                                                                      specifically listed for the application, the manual testing
                                                                                                                      frequency shall be permitted to be extended to annual.
                                                                                                                      Table 7-3.2 shall apply. All components must be tested
                                                                                                                      upon acceptance and at least annually. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

04-13-2               Observed no inspection report available for the fire alarm system. For reporting                NFPA 72, 7-5.2.2 A permanent record of all inspections,
                      purposes only.                                                                                  testing, and maintenance shall be provided that includes
                                                                                                                      the following information of periodic tests and all
                                                                                                                      applicable information requested in Figure 7-5.2.2. (a)
                                                                                                                      Date; (b) Test frequency; (c) Name of property; (d)
                                                                                                                      Address; (e) Name of person performing inspection,
                                                                                                                      maintenance, tests, or combination thereof, and
                                                                                                                      affiliation, business address, and telephone number; (f)
                                                                                                                      Name, address, and representative of approving
                                                                                                                      agency(ies); (g) Designation of the detector(s) tested;
                                                                                                                      (h) Functional test of detectors; (i) Functional test of
                                                                                                                      required sequence of operations; (j) Check of all smoke
                                                                                                                      detectors; (k) Loop resistance for all fixed-temperature
                                                                                                                      line-type heat detectors; (l) Other tests as required by
                                                                                                                      equipment manufacturers; (m) Other tests as required
                                                                                                                      by the authority having jurisdiction; (n) Signatures of
                                                                                                                      tester and approved authority representative; (o)
                                                                                                                      Disposition of problems identified during testing (e.g.,
                                                                                                                      owner notified, problem, corrected/successfully
                                                                                                                      retested, device abondoned in place). FOR
                                                                                                                      REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 59
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Monroe County

License Number: 5400695                                             DAYS INN OCEAN FRONT SUITES 2
License Type: Motel                                                 82749 OVERSEAS HWY, ISLAMORADA 330363609

   Inspection Date: 09/18/2008               Inspection Number: 1125203              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: ALFONSO, ARELYS                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

04-10-2               Observed the fire alarm panel with an expired inspection tag. For reporting                     NFPA 72 7-3.2 and TABLE 7-3.2 Testing shall be
                      purposes only.                                                                                  performed in accordance with the schedules in Chapter
                                                                                                                      7 or more often if required by the authority having
                                                                                                                      jurisdiction. If automatic testing is performed at least
                                                                                                                      weekly by a remotely monitored fire alarm control unit
                                                                                                                      specifically listed for the application, the manual testing
                                                                                                                      frequency shall be permitted to be extended to annual.
                                                                                                                      Table 7-3.2 shall apply. All components must be tested
                                                                                                                      upon acceptance and at least annually. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

04-13-2               Observed no inspection report available for the fire alarm system. For reporting                NFPA 72, 7-5.2.2 A permanent record of all inspections,
                      purposes only.                                                                                  testing, and maintenance shall be provided that includes
                                                                                                                      the following information of periodic tests and all
                                                                                                                      applicable information requested in Figure 7-5.2.2. (a)
                                                                                                                      Date; (b) Test frequency; (c) Name of property; (d)
                                                                                                                      Address; (e) Name of person performing inspection,
                                                                                                                      maintenance, tests, or combination thereof, and
                                                                                                                      affiliation, business address, and telephone number; (f)
                                                                                                                      Name, address, and representative of approving
                                                                                                                      agency(ies); (g) Designation of the detector(s) tested;
                                                                                                                      (h) Functional test of detectors; (i) Functional test of
                                                                                                                      required sequence of operations; (j) Check of all smoke
                                                                                                                      detectors; (k) Loop resistance for all fixed-temperature
                                                                                                                      line-type heat detectors; (l) Other tests as required by
                                                                                                                      equipment manufacturers; (m) Other tests as required
                                                                                                                      by the authority having jurisdiction; (n) Signatures of
                                                                                                                      tester and approved authority representative; (o)
                                                                                                                      Disposition of problems identified during testing (e.g.,
                                                                                                                      owner notified, problem, corrected/successfully
                                                                                                                      retested, device abondoned in place). FOR
                                                                                                                      REPORTING PURPOSES ONLY.

License Number: 5400642                                             CHELSEA HOUSE POOL AND GARDENS
License Type: Rooming House                                         709 TRUMAN AVE, KEY WEST 33040

   Inspection Date: 09/12/2008               Inspection Number: 1088897              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BOAK, MICHAEL                                                                                                           Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

01-11-2               Observed a fire extinguisher missing an inspection tag date. For reporting                      61C-1.004(9)(b) FAC A standard state approved service
                      purposes only.                                                                                  tag shall be attached to each extinguisher and a person
                                                                                                                      holding a valid state permit issued by the State Fire
                                                                                                                      Marshal shall recharge or inspect the extinguisher and
                                                                                                                      shall prepare the tag to include the information required
                                                                                                                      by rule 4A-21.241, FAC, herein adopted by reference.
                                                                                                                      FOR REPORTING PURPOSES ONLY.

07-06-2               Observed an electrical outlet missing a cover plate. For reporting purposes only.               NFPA 70, 300-31 Suitable covers shall be installed on
                                                                                                                      all boxes to prevent accidental contact with energized
                                                                                                                      parts or physical damage to parts or insulation. FOR
                                                                                                                      REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                         Page 60
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Monroe County

License Number: 5400343                                         ALOHA DEVELOPERS LLC
License Type: Apartment                                         6973 OVERSEAS HWY, MARATHON 33050

   Inspection Date: 09/17/2008           Inspection Number: 1204147               Inspection Type: Routine - Lodging                    Inspection Disposition: Administrative
   Inspector Name: ALFONSO, ARELYS                                                                                                      complaint recommended

Violation Code     Observation                                                                                     Violation Citation

01-03-2            Observed an appropriately sized fire extinguisher is missing. For reporting                     61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   purposes only.                                                                                  Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                   installed in accordance with NFPA 10, Standard for
                                                                                                                   Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                   include guest room areas of hotels/motels, etc. [These
                                                                                                                   locations shall be protected by the installation of potable
                                                                                                                   fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                   provided for each 3000 square feet of floor space on
                                                                                                                   each level and installed so that the travel distance to
                                                                                                                   any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                   level, the area protected and the travel distances shall
                                                                                                                   be based of fire extinguishers installed in accordance
                                                                                                                   with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                   PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 61
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Okaloosa County

License Number: 5603598                                             HEATHER GLENN APARTMENTS
License Type: Apartment                                             1600 HUNT CLUB DR, FT WALTON BEACH 32548

   Inspection Date: 09/10/2008               Inspection Number: 1221815              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: FRANZALIA, CHARLES                                                                                                      Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

07-01-2               Observed frayed wire(s). For reporting purposes only....wires (dead current???)                 61C-1.004(11)FAC Electrical wiring - To prevent fire or
                      from side of bldg. #1...                                                                        injury, defective electrical wiring shall be replaced and
                                                                                                                      wiring shall be kept in good repair. FOR REPORTING
                                                                                                                      PURPOSES ONLY.

License Number: 5600255                                             VILLAGER APARTMENTS (THE)
License Type: Apartment                                             22 NW WRIGHT PKY, FT WALTON BCH 325484668

   Inspection Date: 09/10/2008               Inspection Number: 1219402              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: FRANZALIA, CHARLES                                                                                                      Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-04-2               Observed an LP gas tank having a water capacity greater than 2 1/2 lbs. on a                    NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                      balcony. For reporting purposes only.                                                           capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                      located on balconies above the first floor that are
                                                                                                                      attached to a multiple family dwelling of 3 or more living
                                                                                                                      units one above the other. Exception: Where such
                                                                                                                      balconies are served by outside stairways and where
                                                                                                                      only such stairways are used to transport the container.
                                                                                                                      FOR REPORTING PURPOSES ONLY.

License Number: 5603153                                             369 AND 370 BLUEFISH DR
License Type: Apartment                                             369 BLUEFISH DR, FT WALTON BCH 325486159

   Inspection Date: 09/17/2008               Inspection Number: 1207918              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: FRANZALIA, CHARLES                                                                                                      Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

07-02-2               Observed cable & elec. wiring loose under wooden eves...                                        61C-1.004(11) FAC No extension cords shall be used
                                                                                                                      except during cleaning, maintenance and other
                                                                                                                      temporary activities. FOR REPORTING PURPOSES
                                                                                                                      ONLY.

License Number: 5600056                                             SANDMAN MOTEL-SUITES INC
License Type: Motel                                                 480 SANTA ROSA BLVD, FT WALTON BCH 325486902

   Inspection Date: 09/13/2008               Inspection Number: 1124215              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: FRANZALIA, CHARLES                                                                                                      Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                      meter rooms, laundry rooms, and storage rooms shall
                                                                                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

04-01-2               Observed a smoke detector not functioning when tested. For reporting purposes                   61C-1.004(5)FAC All fire safety, protection and
                      only...#113                                                                                     prevention equipment must be installed, approved,
                                                                                                                      maintained and used in accordance with Chapter 509,
                                                                                                                      FS and the National Fire Protection Association Life
                                                                                                                      Safety Code Chapter 101, as adopted by the Division of
                                                                                                                      State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                      REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 62
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Okaloosa County

License Number: 5600810                                             SANDMAN MOTEL - SUITES INC
License Type: Motel                                                 482 SANTA ROSA BLVD, FT WALTON BCH 325486904

   Inspection Date: 09/13/2008               Inspection Number: 1127901              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: FRANZALIA, CHARLES                                                                                                      Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                      meter rooms, laundry rooms, and storage rooms shall
                                                                                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

04-01-2               Observed a smoke detector not functioning when tested. For reporting purposes                   61C-1.004(5)FAC All fire safety, protection and
                      only...#120                                                                                     prevention equipment must be installed, approved,
                                                                                                                      maintained and used in accordance with Chapter 509,
                                                                                                                      FS and the National Fire Protection Association Life
                                                                                                                      Safety Code Chapter 101, as adopted by the Division of
                                                                                                                      State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

License Number: 5600069                                             TISA'S FRIENDLY INN
License Type: Motel                                                 626 JOHN SIMS PKWY, NICEVILLE 32578

   Inspection Date: 09/18/2008               Inspection Number: 1124293              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: WIGGINS, GISELE                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

01-03-2               Observed an appropriately sized fire extinguisher is missing, between rooms 112                 61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                      and 113. For reporting purposes only.                                                           Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                      installed in accordance with NFPA 10, Standard for
                                                                                                                      Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                      include guest room areas of hotels/motels, etc. [These
                                                                                                                      locations shall be protected by the installation of potable
                                                                                                                      fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                      provided for each 3000 square feet of floor space on
                                                                                                                      each level and installed so that the travel distance to
                                                                                                                      any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                      level, the area protected and the travel distances shall
                                                                                                                      be based of fire extinguishers installed in accordance
                                                                                                                      with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                      PURPOSES ONLY.

01-03-2               Observed an appropriately sized fire extinguisher is missing, between rooms 120                 61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                      and 121. For reporting purposes only.                                                           Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                      installed in accordance with NFPA 10, Standard for
                                                                                                                      Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                      include guest room areas of hotels/motels, etc. [These
                                                                                                                      locations shall be protected by the installation of potable
                                                                                                                      fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                      provided for each 3000 square feet of floor space on
                                                                                                                      each level and installed so that the travel distance to
                                                                                                                      any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                      level, the area protected and the travel distances shall
                                                                                                                      be based of fire extinguishers installed in accordance
                                                                                                                      with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                      PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                            Page 63
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Orange County

License Number: 5800892                                           BECLA APARTMENTS
License Type: Apartment                                           636 S DELANEY AVE, ORLANDO 32801

   Inspection Date: 09/11/2008            Inspection Number: 1216582               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: PAYTON, MARK                                                                                                          Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

07-06-2            Observed an electrical box missing a cover. In laundry room ceiling. For reporting               NFPA 70, 300-31 Suitable covers shall be installed on
                   purposes only.                                                                                   all boxes to prevent accidental contact with energized
                                                                                                                    parts or physical damage to parts or insulation. FOR
                                                                                                                    REPORTING PURPOSES ONLY.

License Number: 5800080                                           RHINEHART TERRACE APTS
License Type: Apartment                                           417 RUTH LN, ORLANDO 328011531

   Inspection Date: 09/16/2008            Inspection Number: 1219001               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: PAYTON, MARK                                                                                                          Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

01-07-2            Observed a fire extinguisher not mounted at the correct height in back of                        NFPA 10,1-6.10 Fire extinguishers having a gross
                   building.n For reporting purposes only.                                                          weight not exceeding 40 LB.shall be installed so that the
                                                                                                                    top of the fire extinguisher is not more than 5 ft. above
                                                                                                                    the floor. Fire extinguishers having a gross weight
                                                                                                                    greater than 40 LB (except wheeled type) shall be so
                                                                                                                    installed that the top of the fire extinguisher is not more
                                                                                                                    than 31/2 ft. above the floor. In no case shall the
                                                                                                                    clearance between the bottom of the fire extinguisher
                                                                                                                    and the floor be less than 4 inches. FOR REPORTING
                                                                                                                    PURPOSES ONLY.

License Number: 5809025                                           JACKSON RENTAL
License Type: Apartment                                           1217 - 1223 OREGON ST, ORLANDO 32803

   Inspection Date: 09/16/2008            Inspection Number: 1216693               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: GORIS, WILBERTO                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

02-04-2            Observed a charcole grill on first floor balcony. For reporting purposes only.                   NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                                                                                                                    capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                    located on balconies above the first floor that are
                                                                                                                    attached to a multiple family dwelling of 3 or more living
                                                                                                                    units one above the other. Exception: Where such
                                                                                                                    balconies are served by outside stairways and where
                                                                                                                    only such stairways are used to transport the container.
                                                                                                                    FOR REPORTING PURPOSES ONLY.

License Number: 5809977                                           WOODWARD APARTMENTS
License Type: Apartment                                           808 E WOODWARD ST, ORLANDO 32803

   Inspection Date: 09/16/2008            Inspection Number: 1212115               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: GORIS, WILBERTO                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

01-05-2            Observed a fire extinguisher obscured from view. chair in frint of extinguisher For              NFPA 10, 1-6.10 Fire extinguishers shall not be
                   reporting purposes only.                                                                         obscured or obstructed from view. Except in large
                                                                                                                    rooms and in certain locations where visual obstruction
                                                                                                                    can not be completely avoided, a means shall be
                                                                                                                    provided to indicate location. FOR REPORTING
                                                                                                                    PURPOSES ONLY.

02-05-2            Observed a fire hazard in the means of access. grill by front door of right side                 61C-1.004(10) FAC Means of access must be
                   apartment For reporting purposes only.                                                           maintained free of fire hazards. FOR REPORTING
                                                                                                                    PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                                 Page 64
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Orange County

License Number: 5811096                                              CENTRAL ORLANDO PROPERTIES LLC
License Type: Apartment                                              611 E AMELIA ST, ORLANDO 32803

   Inspection Date: 09/16/2008               Inspection Number: 1209908                 Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: GORIS, WILBERTO                                                                                                            Issued

Violation Code        Observation                                                                                        Violation Citation

02-05-2               Observed a fire hazard in the means of access grill by rear porch right side of                    61C-1.004(10) FAC Means of access must be
                      building For reporting purposes only.                                                              maintained free of fire hazards. FOR REPORTING
                                                                                                                         PURPOSES ONLY.

License Number: 5800181                                              VIRGINIA PORTLAND APTS
License Type: Apartment                                              1216 VIRGINIA DR, ORLANDO 328032634

   Inspection Date: 09/16/2008               Inspection Number: 1214429                 Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: GORIS, WILBERTO                                                                                                            Completed - No Further Action

Violation Code        Observation                                                                                        Violation Citation

02-05-2               Observed a fire hazard in the means of access grill on second floor For reporting                  61C-1.004(10) FAC Means of access must be
                      purposes only.                                                                                     maintained free of fire hazards. FOR REPORTING
                                                                                                                         PURPOSES ONLY.

License Number: 5800371                                              AMBASSADOR HOTEL
License Type: Motel                                                  929 W COLONIAL DR, ORLANDO 328047313

   Inspection Date: 09/17/2008               Inspection Number: 1127681                 Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: GORDON, NORMA                                                                                                              Completed - No Further Action

Violation Code        Observation                                                                                        Violation Citation

06-04-2               Observed an exit sign that is not illuminated/not functioning when tested. [ Office                61-C1.004(10) FAC Exits shall be clearly marked with
                      area]. For reporting purposes only.                                                                approved illuminated exit signs. FOR REPORTING
                                                                                                                         PURPOSES ONLY.

07-08-2               Observed an open spaces in an electrical box. [Electrical box in the hot water                     NFPA 70, 110-12(a) Unused openings in boxes or
                      room]. For reporting purposes only.                                                                housings shall be effectively closed to afford protection
                                                                                                                         substantially equivalent to the wall of the equipment.
                                                                                                                         FOR REPORTING PURPOSES ONLY.

License Number: 5803664                                              RESERVE AT ROSEMONT (THE)
License Type: Apartment                                              3997 ROSEWOOD WAY, ORLANDO 32808

   Inspection Date: 09/12/2008               Inspection Number: 1207411                 Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: GORDON, NORMA                                                                                                              Completed - No Further Action

Violation Code        Observation                                                                                        Violation Citation

06-04-2               Observed an exit sign that is not illuminated/not functioning when tested.                         61-C1.004(10) FAC Exits shall be clearly marked with
                      [Throughout the property]. For reporting purposes only.                                            approved illuminated exit signs. FOR REPORTING
                                                                                                                         PURPOSES ONLY.

08-03                 Observed a boiler certificate is not posted in the boiler room.                                    61C-1.004(12) FAC The insurance inspector's boiler
                                                                                                                         report is required annually for power boilers and high
                      Boiler Information: Boiler Jurisdiction Number: FL097540, Boiler Expiration Date:                  pressure/high temperature boilers and biannually for low
                      Inspected 8/1/08                                                                                   pressure steam or vapor heating boilers and shall be
                                                                                                                         posted in the boiler room. The provisions of this section
                                                                                                                         do not apply to the common areas of resort
                                                                                                                         condominiums.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                           Page 65
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Orange County

License Number: 5803760                                          FOUNTAIN APARTMENTS AT LAKE ORLANDO
License Type: Apartment                                          5175 CINDER LANE PKWY, ORLANDO 32808

   Inspection Date: 09/12/2008            Inspection Number: 1205236              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: GORDON, NORMA                                                                                                        Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-03-2            Observed an appropriately sized fire extinguisher is missing. [Laundry room at                  61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   building 16]. For reporting purposes only.                                                      Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                   installed in accordance with NFPA 10, Standard for
                                                                                                                   Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                   include guest room areas of hotels/motels, etc. [These
                                                                                                                   locations shall be protected by the installation of potable
                                                                                                                   fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                   provided for each 3000 square feet of floor space on
                                                                                                                   each level and installed so that the travel distance to
                                                                                                                   any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                   level, the area protected and the travel distances shall
                                                                                                                   be based of fire extinguishers installed in accordance
                                                                                                                   with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

01-09-2            Observed a fire extinguisher pressure gauge indicating the extinguisher is in need              NFPA 10,1-6.2 Portable extinguishers shall be
                   of recharge. [Building 34, laundry area]. For reporting purposes only.                          maintained in a fully charged and operable condition.
                                                                                                                   FOR REPORTING PURPOSES ONLY.

02-04-2            Observed an LP gas tank having a water capacity greater than 2 1/2 lbs. on a                    NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                   balcony. [ On the porches]. For reporting purposes only. Repeat Violation.                      capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                   located on balconies above the first floor that are
                                                                                                                   attached to a multiple family dwelling of 3 or more living
                                                                                                                   units one above the other. Exception: Where such
                                                                                                                   balconies are served by outside stairways and where
                                                                                                                   only such stairways are used to transport the container.
                                                                                                                   FOR REPORTING PURPOSES ONLY.

02-05-2            Observed a fire hazard in the means of access. [ Charcoal grills on the porches].               61C-1.004(10) FAC Means of access must be
                   For reporting purposes only. Repeat Violation.                                                  maintained free of fire hazards. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

License Number: 5804559                                          PINEVIEW APARTMENTS
License Type: Apartment                                          4731 N PINE HILLS RD, ORLANDO 32808

   Inspection Date: 09/17/2008            Inspection Number: 1212006              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: GORDON, NORMA                                                                                                        Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-10-2            Observed an missing fire extinguisher tag. [ Laundry room]. For reporting                       NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                   purposes only.                                                                                  maintenance not more than one year apart. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

02-02-2            Observed a build up of lint in the laundry room. [ Behind the dryers in the laundry             61C-1.004(7) FAC Attics, basements, boiler rooms,
                   room]. For reporting purposes only.                                                             meter rooms, laundry rooms, and storage rooms shall
                    Repeat Violation.                                                                              be kept clean and free of debris and flammables. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

02-05-2            Observed a fire hazard in the means of access. [Charcoal grills in the means of                 61C-1.004(10) FAC Means of access must be
                   access, apts. 57/73/82/108/904/]. For reporting purposes only.                                  maintained free of fire hazards. FOR REPORTING
                                                                                                                   PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                             Page 66
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Orange County

License Number: 5807562                                           THE RESERVE AT ROSEMONT
License Type: Apartment                                           3997 ROSEWOOD WAY, ORLANDO 32808

   Inspection Date: 09/12/2008            Inspection Number: 1221425                Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: GORDON, NORMA                                                                                                          Completed - No Further Action

Violation Code     Observation                                                                                       Violation Citation

01-03-2            Observed an appropriately sized fire extinguisher is missing. [ Laundry area 2].                  61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   For reporting purposes only.                                                                      Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                     installed in accordance with NFPA 10, Standard for
                                                                                                                     Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                     include guest room areas of hotels/motels, etc. [These
                                                                                                                     locations shall be protected by the installation of potable
                                                                                                                     fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                     provided for each 3000 square feet of floor space on
                                                                                                                     each level and installed so that the travel distance to
                                                                                                                     any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                     level, the area protected and the travel distances shall
                                                                                                                     be based of fire extinguishers installed in accordance
                                                                                                                     with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                     PURPOSES ONLY.

02-05-2            Observed a fire hazard in the means of access. [Grills on the porches]. For                       61C-1.004(10) FAC Means of access must be
                   reporting purposes only.                                                                          maintained free of fire hazards. FOR REPORTING
                                                                                                                     PURPOSES ONLY.

04-01-2            Observed an alarm silenced on the fire alarm control panel. [Building 5525]. For                  61C-1.004(5)FAC All fire safety, protection and
                   reporting purposes only.                                                                          prevention equipment must be installed, approved,
                                                                                                                     maintained and used in accordance with Chapter 509,
                                                                                                                     FS and the National Fire Protection Association Life
                                                                                                                     Safety Code Chapter 101, as adopted by the Division of
                                                                                                                     State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                     REPORTING PURPOSES ONLY.

06-04-2            Observed an exit sign that is not illuminated/not functioning when tested.                        61-C1.004(10) FAC Exits shall be clearly marked with
                   [Throughout the property]. For reporting purposes only.                                           approved illuminated exit signs. FOR REPORTING
                                                                                                                     PURPOSES ONLY.

08-03              Observed a boiler certificate is not posted in the boiler room. [Mech. Rm.2]                      61C-1.004(12) FAC The insurance inspector's boiler
                   Boiler Information: Boiler Jurisdiction Number: FL097540/BOARD#207975, Boiler                     report is required annually for power boilers and high
                   Expiration Date: Inspection date 8/1/08, #1.        Boiler Jurisdiction Number:                   pressure/high temperature boilers and biannually for low
                   FL121914, Boiler Expiration Date: 1/1/09 , Mech. Rm #2.           Boiler Jurisdiction             pressure steam or vapor heating boilers and shall be
                   Number: FL121915, Boiler Expiration Date: 1/1/09, #3. Boiler Jurisdiction                         posted in the boiler room. The provisions of this section
                   Number: FL12193, Boiler Expiration Date: 1/1/09, #4. Boiler Jurisdiction Number:                  do not apply to the common areas of resort
                   FL097184, Boiler Expiration Date: 2010, # 5.                                                      condominiums.

08-03              Observed a boiler certificate is not posted in the boiler room. [Mech. Rm. 3].                    61C-1.004(12) FAC The insurance inspector's boiler
                   Boiler Information: Boiler Jurisdiction Number: FL097540/BOARD#207975, Boiler                     report is required annually for power boilers and high
                   Expiration Date: Inspection date 8/1/08, #1.        Boiler Jurisdiction Number:                   pressure/high temperature boilers and biannually for low
                   FL121914, Boiler Expiration Date: 1/1/09 , Mech. Rm #2.           Boiler Jurisdiction             pressure steam or vapor heating boilers and shall be
                   Number: FL121915, Boiler Expiration Date: 1/1/09, #3. Boiler Jurisdiction                         posted in the boiler room. The provisions of this section
                   Number: FL12193, Boiler Expiration Date: 1/1/09, #4. Boiler Jurisdiction Number:                  do not apply to the common areas of resort
                   FL097184, Boiler Expiration Date: 2010, # 5.                                                      condominiums.

08-03              Observed a boiler certificate is not posted in the boiler room. [Mech. Rm. 1]                     61C-1.004(12) FAC The insurance inspector's boiler
                                                                                                                     report is required annually for power boilers and high
                                                                                                                     pressure/high temperature boilers and biannually for low
                   Boiler Information: Boiler Jurisdiction Number: FL097540/BOARD#207975, Boiler                     pressure steam or vapor heating boilers and shall be
                   Expiration Date: Inspection date 8/1/08, #1.      Boiler Jurisdiction Number:                     posted in the boiler room. The provisions of this section
                   FL121914, Boiler Expiration Date: 1/1/09 , Mech. Rm #2.         Boiler Jurisdiction               do not apply to the common areas of resort
                   Number: FL121915, Boiler Expiration Date: 1/1/09, #3. Boiler Jurisdiction                         condominiums.
                   Number: FL12193, Boiler Expiration Date: 1/1/09, #4. Boiler Jurisdiction Number:
                   FL097184, Boiler Expiration Date: 2010, # 5.

08-03              Observed a boiler certificate is not posted in the boiler room. [Mech. Rm. #5].                   61C-1.004(12) FAC The insurance inspector's boiler
                   Boiler Information: Boiler Jurisdiction Number: FL097540/BOARD#207975, Boiler                     report is required annually for power boilers and high
                   Expiration Date: Inspection date 8/1/08, #1.        Boiler Jurisdiction Number:                   pressure/high temperature boilers and biannually for low
                   FL121914, Boiler Expiration Date: 1/1/09 , Mech. Rm #2.           Boiler Jurisdiction             pressure steam or vapor heating boilers and shall be
                   Number: FL121915, Boiler Expiration Date: 1/1/09, #3. Boiler Jurisdiction                         posted in the boiler room. The provisions of this section
                   Number: FL12193, Boiler Expiration Date: 1/1/09, #4. Boiler Jurisdiction Number:                  do not apply to the common areas of resort
                   FL097184, Boiler Expiration Date: 2010, # 5.                                                      condominiums.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 67
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Orange County

License Number: 5804487                                             MCKINLEY AT WESTWOOD SUITES
License Type: Apartment                                             6800 VILLA DE COSTA DR., ORLANDO 32821

   Inspection Date: 09/12/2008               Inspection Number: 1209778              Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: TILLEY, GEMMA                                                                                                           Issued

Violation Code        Observation                                                                                     Violation Citation

01-03-2               Observed an appropriately sized fire extinguisher is missing. For reporting                     61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                      purposes only.Unit 102.                                                                         Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                      installed in accordance with NFPA 10, Standard for
                                                                                                                      Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                      include guest room areas of hotels/motels, etc. [These
                                                                                                                      locations shall be protected by the installation of potable
                                                                                                                      fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                      provided for each 3000 square feet of floor space on
                                                                                                                      each level and installed so that the travel distance to
                                                                                                                      any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                      level, the area protected and the travel distances shall
                                                                                                                      be based of fire extinguishers installed in accordance
                                                                                                                      with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                      PURPOSES ONLY.

08-03                 Observed a boiler certificate is not posted in the boiler room.At mechanical room               61C-1.004(12) FAC The insurance inspector's boiler
                      1. Repeat Violation.                                                                            report is required annually for power boilers and high
                                                                                                                      pressure/high temperature boilers and biannually for low
                                                                                                                      pressure steam or vapor heating boilers and shall be
                      Boiler Information: Boiler Jurisdiction Number: Fl059315, Boiler Expiration Date:               posted in the boiler room. The provisions of this section
                      6/27/09 Boiler Jurisdiction Number: Fl096869, Boiler Expiration Date: 6/27/09                   do not apply to the common areas of resort
                                                                                                                      condominiums.

08-03                 Observed no boiler certificate available.For boilers in mechanical room#1. Repeat               61C-1.004(12) FAC The insurance inspector's boiler
                      Violation.                                                                                      report is required annually for power boilers and high
                                                                                                                      pressure/high temperature boilers and biannually for low
                                                                                                                      pressure steam or vapor heating boilers and shall be
                      Boiler Information: Boiler Jurisdiction Number: Fl059315, Boiler Expiration Date:               posted in the boiler room. The provisions of this section
                      6/27/09 Boiler Jurisdiction Number: Fl096869, Boiler Expiration Date: 6/27/09                   do not apply to the common areas of resort
                                                                                                                      condominiums.

License Number: 5806250                                             HAWTHORN SUITES ORLANDO CONVENTION CENTER
License Type: Hotel                                                 6435 WESTWOOD BOULEVARD, ORLANDO 32821-8025

   Inspection Date: 09/18/2008               Inspection Number: 1105079              Inspection Type: Lodging-Licensing                    Inspection Disposition: Inspection
   Inspector Name: TILLEY, GEMMA                                                     Inspection                                            Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

08-03                 Observed no boiler certificate available for boiler FL87356.                                    61C-1.004(12) FAC The insurance inspector's boiler
                                                                                                                      report is required annually for power boilers and high
                      Boiler Information: Boiler Jurisdiction Number: FL122288, Boiler Expiration Date:               pressure/high temperature boilers and biannually for low
                      6/26/2010                                                                                       pressure steam or vapor heating boilers and shall be
                                                                                                                      posted in the boiler room. The provisions of this section
                                                                                                                      do not apply to the common areas of resort
                                                                                                                      condominiums.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                            Page 68
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Orange County

License Number: 5804584                                          BROADWATER APARTMENTS
License Type: Apartment                                          6677 TANGLEWOOD BAY DR, ORLANDO 328219368

   Inspection Date: 09/18/2008            Inspection Number: 1218986               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: TILLEY, GEMMA                                                                                                         Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

02-04-2            Observed an LP gas tank having a water capacity greater than 2 1/2 lbs. on a                     NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                   balcony. For reporting purposes only.Apartment 811.                                              capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                    located on balconies above the first floor that are
                                                                                                                    attached to a multiple family dwelling of 3 or more living
                                                                                                                    units one above the other. Exception: Where such
                                                                                                                    balconies are served by outside stairways and where
                                                                                                                    only such stairways are used to transport the container.
                                                                                                                    FOR REPORTING PURPOSES ONLY.

04-01-2            Observed a trouble/alarm light illuminated on the fire alarm control panel. For                  61C-1.004(5)FAC All fire safety, protection and
                   reporting purposes only.                                                                         prevention equipment must be installed, approved,
                                                                                                                    maintained and used in accordance with Chapter 509,
                                                                                                                    FS and the National Fire Protection Association Life
                                                                                                                    Safety Code Chapter 101, as adopted by the Division of
                                                                                                                    State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                    REPORTING PURPOSES ONLY.

License Number: 5803661                                          G & I VI FISHERMAN'S VILLAGE LLC
License Type: Apartment                                          5800 DOLPHIN DR, ORLANDO 32822

   Inspection Date: 09/16/2008            Inspection Number: 1239953               Inspection Type: Lodging-Licensing                    Inspection Disposition: Inspection
   Inspector Name: RULLAN, ALFONSO                                                 Inspection                                            Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

04-01-2            Observed a trouble/alarm light illuminated on the fire alarm control panel. For                  61C-1.004(5)FAC All fire safety, protection and
                   reporting purposes only, maintenance supervisor said will work, by apt 4964.                     prevention equipment must be installed, approved,
                                                                                                                    maintained and used in accordance with Chapter 509,
                                                                                                                    FS and the National Fire Protection Association Life
                                                                                                                    Safety Code Chapter 101, as adopted by the Division of
                                                                                                                    State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                    REPORTING PURPOSES ONLY.

License Number: 5810977                                          CAMDEN LAGO VISTA
License Type: Apartment                                          6000 BENT PINE DR, ORLANDO 32822

   Inspection Date: 09/12/2008            Inspection Number: 1207514               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: RULLAN, ALFONSO                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

06-20-2            Observed an emergency light that is not functioning when tested by apt 3215. For                 61C-1.004(5)FAC All fire safety, protection and
                   reporting purposes only.                                                                         prevention equipment must be installed, approved,
                                                                                                                    maintained and used in accordance with Chapter 509,
                                                                                                                    FS and the National Fire Protection Association Life
                                                                                                                    Safety Code Chapter 101, as adopted by the Division of
                                                                                                                    State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                    REPORTING PURPOSES ONLY.

License Number: 5811083                                          MILL CREEK APARTMENTS
License Type: Apartment                                          5087 COMMANDER DR, ORLANDO 32822

   Inspection Date: 09/16/2008            Inspection Number: 1218987               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: RULLAN, ALFONSO                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

01-07-2            Observed a fire extinguisher on the ground/floor. For reporting purposes only.                   NFPA 10,1-6.10 Fire extinguishers having a gross
                                                                                                                    weight not exceeding 40 LB.shall be installed so that the
                                                                                                                    top of the fire extinguisher is not more than 5 ft. above
                                                                                                                    the floor. Fire extinguishers having a gross weight
                                                                                                                    greater than 40 LB (except wheeled type) shall be so
                                                                                                                    installed that the top of the fire extinguisher is not more
                                                                                                                    than 31/2 ft. above the floor. In no case shall the
                                                                                                                    clearance between the bottom of the fire extinguisher
                                                                                                                    and the floor be less than 4 inches. FOR REPORTING
                                                                                                                    PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                           Page 69
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Orange County

License Number: 5811130                                          MARBELLA POINTE
License Type: Apartment                                          7528 MARBELLA POINTE DR, ORLANDO 32822

   Inspection Date: 09/16/2008            Inspection Number: 1240041              Inspection Type: Lodging-Licensing                    Inspection Disposition: Inspection
   Inspector Name: RULLAN, ALFONSO                                                Inspection                                            Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

02-03-2            Observed flammable liquid stored inside maintenance shop, gas cans.                             61C-1.004(8) FAC Flammable materials inside an
                                                                                                                   establishment shall be stored in approved-type
                                                                                                                   containers (maximum size 5 gallons) and in such a
                                                                                                                   manner as to prevent a fire hazard. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

License Number: 5811131                                          MARBELLA COVE
License Type: Apartment                                          7528 MARBELLA POINTE DR, ORLANDO 32822

   Inspection Date: 09/16/2008            Inspection Number: 1240042              Inspection Type: Lodging-Licensing                    Inspection Disposition: Inspection
   Inspector Name: RULLAN, ALFONSO                                                Inspection                                            Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

02-03-2            Observed flammable liquid stored inside maintenance shop without protection.                    61C-1.004(8) FAC Flammable materials inside an
                                                                                                                   establishment shall be stored in approved-type
                                                                                                                   containers (maximum size 5 gallons) and in such a
                                                                                                                   manner as to prevent a fire hazard. FOR REPORTING
                                                                                                                   PURPOSES ONLY.

License Number: 5806829                                          ARBORS AT LEE VISTA
License Type: Apartment                                          5900 BENT PINE DR, ORLANDO 32822-3308

   Inspection Date: 09/12/2008            Inspection Number: 1207521              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: RULLAN, ALFONSO                                                                                                      Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

02-04-2            Observed charcoal grill stored inside patio apt 152 blg 8. For reporting purposes               NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                   only.                                                                                           capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                   located on balconies above the first floor that are
                                                                                                                   attached to a multiple family dwelling of 3 or more living
                                                                                                                   units one above the other. Exception: Where such
                                                                                                                   balconies are served by outside stairways and where
                                                                                                                   only such stairways are used to transport the container.
                                                                                                                   FOR REPORTING PURPOSES ONLY.

License Number: 5807875                                          GRAND RESERVE (THE)
License Type: Apartment                                          6201 BENT PINE DR, ORLANDO 328224925

   Inspection Date: 09/12/2008            Inspection Number: 1207516              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: RULLAN, ALFONSO                                                                                                      Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

02-02-2            Observed a build up of lint in the laundry room. For reporting purposes only.                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                   meter rooms, laundry rooms, and storage rooms shall
                                                                                                                   be kept clean and free of debris and flammables. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

06-20-2            Observed an exit sign in disrepair. For reporting purposes only, by apt 624 B blg 6.            61C-1.004(5)FAC All fire safety, protection and
                   Corrected On Site.                                                                              prevention equipment must be installed, approved,
                                                                                                                   maintained and used in accordance with Chapter 509,
                                                                                                                   FS and the National Fire Protection Association Life
                                                                                                                   Safety Code Chapter 101, as adopted by the Division of
                                                                                                                   State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                   REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                          Page 70
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Orange County

License Number: 5803062                                         THE CANOPY APARTMENT VILLAS
License Type: Apartment                                         5762 FOLKSTONE LN, ORLANDO 328229432

   Inspection Date: 09/12/2008           Inspection Number: 1221406              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: RULLAN, ALFONSO                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-03-2            Observed an appropriately sized fire extinguisher is missing inside apt 5911, and              61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                   5864. For reporting purposes only. Corrected On Site.                                          Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                  installed in accordance with NFPA 10, Standard for
                                                                                                                  Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                  include guest room areas of hotels/motels, etc. [These
                                                                                                                  locations shall be protected by the installation of potable
                                                                                                                  fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                  provided for each 3000 square feet of floor space on
                                                                                                                  each level and installed so that the travel distance to
                                                                                                                  any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                  level, the area protected and the travel distances shall
                                                                                                                  be based of fire extinguishers installed in accordance
                                                                                                                  with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

License Number: 5809710                                         FOUNTAINS AT WATERFORD LAKES
License Type: Apartment                                         12101 FOUNTAINBROOK LAKES, ORLANDO 32825

   Inspection Date: 09/17/2008           Inspection Number: 1205201              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BANDELE, NYAHIRI                                                                                                    Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

06-20-2            Observed an emergency light that is not functioning when tested near 1138. For                 61C-1.004(5)FAC All fire safety, protection and
                   reporting purposes only.                                                                       prevention equipment must be installed, approved,
                                                                                                                  maintained and used in accordance with Chapter 509,
                                                                                                                  FS and the National Fire Protection Association Life
                                                                                                                  Safety Code Chapter 101, as adopted by the Division of
                                                                                                                  State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                  REPORTING PURPOSES ONLY.

License Number: 5806281                                         POLO EAST APTS
License Type: Apartment                                         1700 WOODBURY RD, ORLANDO 328286015

   Inspection Date: 09/12/2008           Inspection Number: 1207477              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BANDELE, NYAHIRI                                                                                                    Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

02-04-2            Observed an LP gas tank having a water capacity greater than 2 1/2 lbs. located                NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                   adjacent to apartment [near 1102], required to be at least 10 feet away from any               capacities greater than 21/2 pounds (1kg) shall not be
                   building. For reporting purposes only.                                                         located on balconies above the first floor that are
                                                                                                                  attached to a multiple family dwelling of 3 or more living
                                                                                                                  units one above the other. Exception: Where such
                                                                                                                  balconies are served by outside stairways and where
                                                                                                                  only such stairways are used to transport the container.
                                                                                                                  FOR REPORTING PURPOSES ONLY.

02-05-2            Observed a fire hazard in the means of access. Motorcycle located under balcony                61C-1.004(10) FAC Means of access must be
                   and stairway near apartment 1102. For reporting purposes only.                                 maintained free of fire hazards. FOR REPORTING
                                                                                                                  PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                               Page 71
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Orange County

License Number: 5800432                                             POLYNESIAN VILLAGE HTL
License Type: Hotel                                                 1600 SEVEN SEAS DR, LAKE BUENA VISTA 32830

   Inspection Date: 09/15/2008               Inspection Number: 1105086              Inspection Type: Complaint Full                        Inspection Disposition: Inspection
   Inspector Name: SPEIGHTS, BLANCHIE MACHELLE                                                                                              Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

01-07-2               Observed a fire extinguisher on the ground/floor. For reporting purposes only.                   NFPA 10,1-6.10 Fire extinguishers having a gross
                      linen room                                                                                       weight not exceeding 40 LB.shall be installed so that the
                                                                                                                       top of the fire extinguisher is not more than 5 ft. above
                                                                                                                       the floor. Fire extinguishers having a gross weight
                                                                                                                       greater than 40 LB (except wheeled type) shall be so
                                                                                                                       installed that the top of the fire extinguisher is not more
                                                                                                                       than 31/2 ft. above the floor. In no case shall the
                                                                                                                       clearance between the bottom of the fire extinguisher
                                                                                                                       and the floor be less than 4 inches. FOR REPORTING
                                                                                                                       PURPOSES ONLY.

License Number: 5804293                                             WATERWAYS FLORIDA
License Type: Apartment                                             4937 WATERWAY COURT, ORLANDO 32839

   Inspection Date: 09/12/2008               Inspection Number: 1207483              Inspection Type: Routine - Lodging                     Inspection Disposition: Administrative
   Inspector Name: PIEL, ANDREA                                                                                                             complaint recommended

Violation Code        Observation                                                                                      Violation Citation

04-01-2               Observed a smoke detector hanging by the wires in apt 222. For reporting                         61C-1.004(5)FAC All fire safety, protection and
                      purposes only.                                                                                   prevention equipment must be installed, approved,
                                                                                                                       maintained and used in accordance with Chapter 509,
                                                                                                                       FS and the National Fire Protection Association Life
                                                                                                                       Safety Code Chapter 101, as adopted by the Division of
                                                                                                                       State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

License Number: 5807926                                             G & I VI ANDOVER PLACE LLC
License Type: Apartment                                             1968 LAKE HERITAGE CIR, ORLANDO 32839

   Inspection Date: 09/15/2008               Inspection Number: 1239969              Inspection Type: Lodging-Licensing                     Inspection Disposition: Inspection
   Inspector Name: RIVERA, STEVEN                                                    Inspection                                             Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

01-10-2               Observed fire extinguishers with no inspection tag provided thru-out property .for               NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                      reporting purposes only.                                                                         maintenance not more than one year apart. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

License Number: 5808741                                             ELAD PROMENADE MANAGEMENT LLC
License Type: Apartment                                             1240 WINTER GARDEN VINELAND RD, WINTER GARDEN 34787

   Inspection Date: 09/18/2008               Inspection Number: 1240077              Inspection Type: Lodging-Licensing                     Inspection Disposition: Inspection
   Inspector Name: CHIU, ALEX                                                        Inspection                                             Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

02-04-2               Observed an LP gas tank having a water capacity greater than 2 1/2 lbs. on a                     NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                      balcony. [second floor, Building B] For reporting purposes only.                                 capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                       located on balconies above the first floor that are
                                                                                                                       attached to a multiple family dwelling of 3 or more living
                                                                                                                       units one above the other. Exception: Where such
                                                                                                                       balconies are served by outside stairways and where
                                                                                                                       only such stairways are used to transport the container.
                                                                                                                       FOR REPORTING PURPOSES ONLY.

02-05-2               Observed a fire hazard in the means of access. [Observed a BBQ grill/smoker on                   61C-1.004(10) FAC Means of access must be
                      the second balcony. ] For reporting purposes only.                                               maintained free of fire hazards. FOR REPORTING
                                                                                                                       PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                               Page 72
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Osceola County

License Number: 5910934                                             GRAHAM PLAZA APTS
License Type: Apartment                                             18 N GRAHAM AVE, ORLANDO 32803

   Inspection Date: 09/16/2008               Inspection Number: 1219126              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: GORIS, WILBERTO                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-04-2               Observed an LP gas tank having a water capacity greater than 2 1/2 lbs. on a                    NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                      balcony GRILLS BY REAR DOORS For reporting purposes only.                                       capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                      located on balconies above the first floor that are
                                                                                                                      attached to a multiple family dwelling of 3 or more living
                                                                                                                      units one above the other. Exception: Where such
                                                                                                                      balconies are served by outside stairways and where
                                                                                                                      only such stairways are used to transport the container.
                                                                                                                      FOR REPORTING PURPOSES ONLY.

02-05-2               Observed a fire hazard in the means of access. grill on secind floor porch For                  61C-1.004(10) FAC Means of access must be
                      reporting purposes only.                                                                        maintained free of fire hazards. FOR REPORTING
                                                                                                                      PURPOSES ONLY.

License Number: 5900225                                             SERALAGO HOTEL & SUITES MAIN GATE EAST
License Type: Hotel                                                 5678 W IRLO BRONSON HWY, KISSIMMEE 34746

   Inspection Date: 09/18/2008               Inspection Number: 1102097              Inspection Type: Routine - Lodging                    Inspection Disposition: Call Back -
   Inspector Name: WRIGHT, NERLINE                                                                                                         Complied

Violation Code        Observation                                                                                     Violation Citation

06-04-2               Violation: 06-04-2                                                                              61-C1.004(10) FAC Exits shall be clearly marked with
                                                                                                                      approved illuminated exit signs. FOR REPORTING
                      Observed an exit sign that is not illuminated/not functioning when tested/ staircase            PURPOSES ONLY.
                      by room 200. For reporting purposes only.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                               Page 73
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Osceola County

License Number: 5900759                                             HOWARD JOHNSON'S ENCHANTED LAND
License Type: Motel                                                 4985 W IRLO BRONSON HWY, KISSIMMEE 34746

   Inspection Date: 09/17/2008               Inspection Number: 1127743              Inspection Type: Routine - Lodging                     Inspection Disposition: Warning
   Inspector Name: WRIGHT, ANDREW                                                                                                           Issued

Violation Code        Observation                                                                                      Violation Citation

01-02-2               Observed the fire hose not being reracked annually. For reporting purposes only.                 61C-1.004(9)(c) FAC Fire Hose Maintenance --
                      Repeat Violation.                                                                                Inspections shall be made every 6 months to assure
                                                                                                                       that the hose is in proper position on the racks and that
                                                                                                                       all of the equipment is in place and in good condition.
                                                                                                                       The hose shall be removed and re-racked at least
                                                                                                                       annually and new gaskets installed in the couplings,
                                                                                                                       both at the hose valves and at the nozzles if necessary.
                                                                                                                       Where couplings are polished, care should be taken to
                                                                                                                       see that polish used does not touch fabric of hose.
                                                                                                                       FOR REPORTING PURPOSES ONLY.

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.                    61C-1.004(7) FAC Attics, basements, boiler rooms,
                      Repeat Violation.                                                                                meter rooms, laundry rooms, and storage rooms shall
                                                                                                                       be kept clean and free of debris and flammables. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

06-07-2               Observed the floor diagram is missing/incorrect. For reporting purposes only.                    NFPA 101, 28-7.4.1 [Transient Establishments - Fire
                      Room 226 sign does not designate room.                                                           Evacuation Requirements] A floor diagram reflecting
                                                                                                                       the actual floor arrangement, exit locations, and room
                                                                                                                       identification shall be posted in a location and manner
                                                                                                                       acceptable to the authority having jurisdiction on or
                                                                                                                       immediately adjacent to every guest room door in hotels
                                                                                                                       and should be oriented with the actual direction to the
                                                                                                                       exits. FOR REPORTING PURPOSES ONLY.

06-20-2               Observed an emergency light that is not functioning when tested. Next to room                    61C-1.004(5)FAC All fire safety, protection and
                      245. For reporting purposes only.                                                                prevention equipment must be installed, approved,
                                                                                                                       maintained and used in accordance with Chapter 509,
                                                                                                                       FS and the National Fire Protection Association Life
                                                                                                                       Safety Code Chapter 101, as adopted by the Division of
                                                                                                                       State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

07-04-2               Observed a splitter/multi-plug adapter in use in room 147. For reporting purposes                61C-1.004(11)FAC In accordance with the provisions of
                      only. Repeat Violation.                                                                          NFPA 70, the National Electrical Code, as adopted by
                                                                                                                       the Division of State Fire Marshal in Chapter 4A03,
                                                                                                                       FAC, Uniform Fire Safety Rules and Standards,
                                                                                                                       sufficient electrical outlets shall be provided. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

07-08-2               Observed an open spaces in an electrical box in electrical room by room 129. For                 NFPA 70, 110-12(a) Unused openings in boxes or
                      reporting purposes only.                                                                         housings shall be effectively closed to afford protection
                                                                                                                       substantially equivalent to the wall of the equipment.
                                                                                                                       FOR REPORTING PURPOSES ONLY.

License Number: 5905901                                             STAR ISLAND RESORT & CLUB
License Type: Resort Dwelling                                       5000 AVENUE OF THE STARS, KISSIMMEE 34746

   Inspection Date: 09/16/2008               Inspection Number: 1091099              Inspection Type: Complaint Full                        Inspection Disposition: Inspection
   Inspector Name: WRIGHT, ANDREW                                                                                                           Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

01-07-2               Observed a fire extinguisher on the ground/floor; room 2064. For reporting                       NFPA 10,1-6.10 Fire extinguishers having a gross
                      purposes only.                                                                                   weight not exceeding 40 LB.shall be installed so that the
                                                                                                                       top of the fire extinguisher is not more than 5 ft. above
                                                                                                                       the floor. Fire extinguishers having a gross weight
                                                                                                                       greater than 40 LB (except wheeled type) shall be so
                                                                                                                       installed that the top of the fire extinguisher is not more
                                                                                                                       than 31/2 ft. above the floor. In no case shall the
                                                                                                                       clearance between the bottom of the fire extinguisher
                                                                                                                       and the floor be less than 4 inches. FOR REPORTING
                                                                                                                       PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                                Page 74
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Osceola County

License Number: 5903723                                              GOOD SAMARITAN RETIREMENT
License Type: Apartment                                              4260 VILLAGE DR, KISSIMMEE 347466480

   Inspection Date: 09/19/2008               Inspection Number: 1212084                Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: WRIGHT, ANDREW                                                                                                            Completed - No Further Action

Violation Code        Observation                                                                                       Violation Citation

06-20-2               Observed an emergency light that is not functioning when tested; 2nd floor landing                61C-1.004(5)FAC All fire safety, protection and
                      North stairwell. For reporting purposes only.                                                     prevention equipment must be installed, approved,
                                                                                                                        maintained and used in accordance with Chapter 509,
                                                                                                                        FS and the National Fire Protection Association Life
                                                                                                                        Safety Code Chapter 101, as adopted by the Division of
                                                                                                                        State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                        REPORTING PURPOSES ONLY.

License Number: 5900879                                              RADISON RESORT PARKWAY
License Type: Hotel                                                  2900 PARKWAY BLVD., KISSIMMEE 34747

   Inspection Date: 09/17/2008               Inspection Number: 1102049                Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: NIEVES, RAFAEL                                                                                                            Completed - No Further Action

Violation Code        Observation                                                                                       Violation Citation

04-01-2               Observed a trouble/alarm light illuminated on the fire alarm control panel. At main               61C-1.004(5)FAC All fire safety, protection and
                      panel located at front lobby area and panel located in security office. For reporting             prevention equipment must be installed, approved,
                      purposes only.                                                                                    maintained and used in accordance with Chapter 509,
                                                                                                                        FS and the National Fire Protection Association Life
                                                                                                                        Safety Code Chapter 101, as adopted by the Division of
                                                                                                                        State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                        REPORTING PURPOSES ONLY.

License Number: 5900038                                              FLORIDIAN SUNSHINE INN
License Type: Motel                                                  1220 GEORGIA AVE, ST CLOUD 347694160

   Inspection Date: 09/16/2008               Inspection Number: 1125501                Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: KHAN, MOZHARUL                                                                                                            Completed - No Further Action

Violation Code        Observation                                                                                       Violation Citation

01-03-2               Observed an appropriately sized fire extinguisher is missing. Laundry room. For                   61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                      reporting purposes only.                                                                          Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                        installed in accordance with NFPA 10, Standard for
                                                                                                                        Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                        include guest room areas of hotels/motels, etc. [These
                                                                                                                        locations shall be protected by the installation of potable
                                                                                                                        fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                        provided for each 3000 square feet of floor space on
                                                                                                                        each level and installed so that the travel distance to
                                                                                                                        any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                        level, the area protected and the travel distances shall
                                                                                                                        be based of fire extinguishers installed in accordance
                                                                                                                        with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                        PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 75
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Palm Beach County

License Number: 6013762                                             APARTMENTS
License Type: Apartment                                             821 SILVER BEACH RD, RIVIERA BCH 33404

   Inspection Date: 09/16/2008               Inspection Number: 1209260              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: JONES, ANTHONY                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

06-02-2               Observed a window provided as a secondary means of escape secured shut. For                     61C-1.004(10) FAC Means of access must permit
                      reporting purposes only. FRONT BEDROOM WINDOW                                                   unobstructed travel at all times and be maintained free
                                                                                                                      of obstructions. FOR REPORTING PURPOSES ONLY.

License Number: 6007204                                             HILTON SINGER ISLAND OCEANFRON
License Type: Hotel                                                 3700 N OCEAN DR, RIVIERA BCH 334042806

   Inspection Date: 09/16/2008               Inspection Number: 1101636              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: JONES, ANTHONY                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                      meter rooms, laundry rooms, and storage rooms shall
                                                                                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

License Number: 6003216                                             EBONY MOTEL
License Type: Motel                                                 1101 OLD DIXIE HWY, RIVIERA BCH 334047399

   Inspection Date: 09/18/2008               Inspection Number: 1127493              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: JONES, ANTHONY                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

06-04-2               Observed an unmarked exit. For reporting purposes only.                                         61-C1.004(10) FAC Exits shall be clearly marked with
                                                                                                                      approved illuminated exit signs. FOR REPORTING
                                                                                                                      PURPOSES ONLY.

License Number: 6001238                                             THE ANCHORAGE AT SOUTHWINDS
License Type: Apartment                                             405 SOUTHWIND DR, NORTH PALM BEACH 33408

   Inspection Date: 09/17/2008               Inspection Number: 1218425              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: ROTONDI, VICTOR                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

01-09-2               Observed a fire extinguisher pressure gauge indicating the extinguisher is in need              NFPA 10,1-6.2 Portable extinguishers shall be
                      of recharge. For reporting purposes only.abc/hallway                                            maintained in a fully charged and operable condition.
                                                                                                                      FOR REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                               Page 76
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Palm Beach County

License Number: 6008686                                             LA QUINTA INNS & SUITES #7716
License Type: Hotel                                                 1910 PALM BEACH LAKES BLVD, WEST PALM BEACH 33409

   Inspection Date: 09/18/2008               Inspection Number: 1100877               Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: JONES, ANTHONY                                                                                                           Issued

Violation Code        Observation                                                                                      Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.                    61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                       meter rooms, laundry rooms, and storage rooms shall
                                                                                                                       be kept clean and free of debris and flammables. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

04-01-2               Observed a trouble/alarm light illuminated on the fire alarm control panel. For                  61C-1.004(5)FAC All fire safety, protection and
                      reporting purposes only.                                                                         prevention equipment must be installed, approved,
                                                                                                                       maintained and used in accordance with Chapter 509,
                                                                                                                       FS and the National Fire Protection Association Life
                                                                                                                       Safety Code Chapter 101, as adopted by the Division of
                                                                                                                       State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

06-16-2               Observed the stair signage is inadequate/not provided. For reporting purposes                    NFPA 101, 7-2.2.5.4 Stairs serving five or more stories
                      only.                                                                                            shall be provided with signage within the enclosure at
                                                                                                                       each floor landing. The signage shall indicate the floor
                                                                                                                       level, the terminus of the top and bottom of the stair
                                                                                                                       enclosure, and the identification of the stair. The
                                                                                                                       signage also shall state the floor level of, and the direct
                                                                                                                       to, exit discharge. The signage shall be inside the
                                                                                                                       enclosure, located approximately 5 ft above the floor
                                                                                                                       landing in a position that is readily visible when the door
                                                                                                                       is in the open or closed position. FOR REPORTING
                                                                                                                       PURPOSES ONLY.

07-06-2               Observed an electrical outlet missing a cover plate. For reporting purposes only.                NFPA 70, 300-31 Suitable covers shall be installed on
                      across fRom boiler room                                                                          all boxes to prevent accidental contact with energized
                                                                                                                       parts or physical damage to parts or insulation. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

License Number: 6001611                                             BOCA WINDS APT
License Type: Apartment                                             541 NE 42 ST, BOCA RATON 334314556

   Inspection Date: 09/18/2008               Inspection Number: 1213626               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BANNIGAN, TIM                                                                                                            Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

06-04-2               Observed an exit sign that is not illuminated/not functioning when tested. For                   61-C1.004(10) FAC Exits shall be clearly marked with
                      reporting purposes only.                                                                         approved illuminated exit signs. FOR REPORTING
                                                                                                                       PURPOSES ONLY.

License Number: 6010914                                             BOCA GARDENS APTS
License Type: Apartment                                             541 NE 43 ST, BOCA RATON 33431-5115

   Inspection Date: 09/18/2008               Inspection Number: 1220693               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BANNIGAN, TIM                                                                                                            Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

07-01-2               Observed exposed capped elec. wire(s). at sprinkler timer on S.W. corner of                      61C-1.004(11)FAC Electrical wiring - To prevent fire or
                      building.                                                                                        injury, defective electrical wiring shall be replaced and
                      For reporting purposes only.                                                                     wiring shall be kept in good repair. FOR REPORTING
                                                                                                                       PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                             Page 77
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Palm Beach County

License Number: 6011056                                            CARLTON HOUSE II
License Type: Apartment                                            520 NE 45 ST, BOCA RATON 334315141

   Inspection Date: 09/16/2008              Inspection Number: 1206798              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BANNIGAN, TIM                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                    Violation Citation

02-04-2               Observed an LP gas tank having a water capacity greater than 2 1/2 lbs. on a                   NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                      FIRST FLOOR SCREENED ENCLOSED PATIO. For reporting purposes only.                              capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                     located on balconies above the first floor that are
                                                                                                                     attached to a multiple family dwelling of 3 or more living
                                                                                                                     units one above the other. Exception: Where such
                                                                                                                     balconies are served by outside stairways and where
                                                                                                                     only such stairways are used to transport the container.
                                                                                                                     FOR REPORTING PURPOSES ONLY.

License Number: 6000266                                            BOCA RETREAT APTS
License Type: Apartment                                            520 NE 46 ST, BOCA RATON 334315173

   Inspection Date: 09/18/2008              Inspection Number: 1206794              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BANNIGAN, TIM                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                    Violation Citation

02-02-2               Observed flammable material stored in attic/laundry/boiler room. For reporting                 61C-1.004(7) FAC Attics, basements, boiler rooms,
                      purposes only.                                                                                 meter rooms, laundry rooms, and storage rooms shall
                      --- PAINTS/FLAMMABLES STORED IN LAUNDRY ROOM ABUTTING HOT                                      be kept clean and free of debris and flammables. FOR
                      WATER HEATER.                                                                                  REPORTING PURPOSES ONLY.

License Number: 6003309                                            AMBASSADOR II
License Type: Apartment                                            521 NE 43 ST, BOCA RATON 334315174

   Inspection Date: 09/18/2008              Inspection Number: 1204519              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BANNIGAN, TIM                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                    Violation Citation

02-04-2               Observed an LP gas tank having a water capacity greater than 2 1/2 lbs. on apar                NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                      ment #1. THIS IS A 1ST FLOOR ENCLOSED LANAI . For reporting purposes                           capacities greater than 21/2 pounds (1kg) shall not be
                      only.                                                                                          located on balconies above the first floor that are
                                                                                                                     attached to a multiple family dwelling of 3 or more living
                                                                                                                     units one above the other. Exception: Where such
                                                                                                                     balconies are served by outside stairways and where
                                                                                                                     only such stairways are used to transport the container.
                                                                                                                     FOR REPORTING PURPOSES ONLY.

License Number: 6003403                                            BOCA INN
License Type: Motel                                                1801 N FEDERAL HWY, BOCA RATON 334321998

   Inspection Date: 09/19/2008              Inspection Number: 1123799              Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
   Inspector Name: BANNIGAN, TIM                                                                                                          Issued

Violation Code        Observation                                                                                    Violation Citation

07-08-2               Observed an open spaces in an electrical box. For reporting purposes only.                     NFPA 70, 110-12(a) Unused openings in boxes or
                      Repeat Violation.                                                                              housings shall be effectively closed to afford protection
                                                                                                                     substantially equivalent to the wall of the equipment.
                                                                                                                     FOR REPORTING PURPOSES ONLY.
                      This violation must be corrected by : 11/20/02.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                               Page 78
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Palm Beach County

License Number: 6007819                                             MOTEL 6 #688
License Type: Motel                                                 1310 W LANTANA RD, LANTANA 334621519

   Inspection Date: 09/18/2008               Inspection Number: 1125315               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DERVIN, RICHARD                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only. boiler             61C-1.004(7) FAC Attics, basements, boiler rooms,
                      room.                                                                                            meter rooms, laundry rooms, and storage rooms shall
                                                                                                                       be kept clean and free of debris and flammables. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

08-03                 Observed an expired boiler certificate.                                                          61C-1.004(12) FAC The insurance inspector's boiler
                                                                                                                       report is required annually for power boilers and high
                      Boiler Information: Boiler Jurisdiction Number: fl051081, *Boiler Expiration Date:               pressure/high temperature boilers and biannually for low
                      7/25/08                                                                                          pressure steam or vapor heating boilers and shall be
                                                                                                                       posted in the boiler room. The provisions of this section
                                                                                                                       do not apply to the common areas of resort
                                                                                                                       condominiums.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                         Page 79
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Pasco County

License Number: 6101179                                        PARK PLACE APARTMENTS
License Type: Apartment                                        39234 23 PARK PLACE CIR, ZEPHYRHILLS 33542

   Inspection Date: 09/08/2008           Inspection Number: 1205056             Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BROTHAG, SANDRA                                                                                                    Completed - No Further Action

Violation Code     Observation                                                                                   Violation Citation

01-05-2            Observed a fire extinguisher obscured from view. For reporting purposes only.                 NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                 obscured or obstructed from view. Except in large
                                                                                                                 rooms and in certain locations where visual obstruction
                                                                                                                 can not be completely avoided, a means shall be
                                                                                                                 provided to indicate location. FOR REPORTING
                                                                                                                 PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                                  Page 80
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Pinellas County

License Number: 6200773                                              OLD NORTHEAST APTS
License Type: Apartment                                              146 6TH AVE NORTHEAST, ST PETERSBURG 33701

   Inspection Date: 09/17/2008               Inspection Number: 1211623                Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: WAGNER, MARGARET                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                       Violation Citation

08-03                 Observed no boiler certificate available.                                                         61C-1.004(12) FAC The insurance inspector's boiler
                      Operator can fax copy to Tampa District Office 813 356 1613                                       report is required annually for power boilers and high
                                                                                                                        pressure/high temperature boilers and biannually for low
                                                                                                                        pressure steam or vapor heating boilers and shall be
                      Boiler Information: No Boiler Certificate Provided. No access to boiler in                        posted in the boiler room. The provisions of this section
                      basement                                                                                          do not apply to the common areas of resort
                                                                                                                        condominiums.

License Number: 6200719                                              ALLARD APARTMENTS
License Type: Apartment                                              417 4 STREET N (417-419), ST. PETERSBURG 33701

   Inspection Date: 09/18/2008               Inspection Number: 1207125                Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: WAGNER, MARGARET                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                       Violation Citation

06-06-2               Observed an interior corridor door is not self-closing. self closing arms in disrepair            NFPA 101, 30-3.6.3 Each guest room door that opens
                      [top of both stairwells] For reporting purposes only.                                             onto an interior corridor shall be self-closing and shall
                                                                                                                        meet the requirements of [NFPA]30, 17-3.6.2. FOR
                                                                                                                        REPORTING PURPOSES ONLY.

07-06-2               Observed an electrical outlet missing a cover plate. 3rd floor hallway     For                    NFPA 70, 300-31 Suitable covers shall be installed on
                      reporting purposes only.                                                                          all boxes to prevent accidental contact with energized
                                                                                                                        parts or physical damage to parts or insulation. FOR
                                                                                                                        REPORTING PURPOSES ONLY.

08-03                 Observed a boiler certificate is not posted in the boiler room. Operator can fax                  61C-1.004(12) FAC The insurance inspector's boiler
                      copy to Tampa District Office 813 356 1613                                                        report is required annually for power boilers and high
                                                                                                                        pressure/high temperature boilers and biannually for low
                                                                                                                        pressure steam or vapor heating boilers and shall be
                      Boiler Information: no access                                                                     posted in the boiler room. The provisions of this section
                                                                                                                        do not apply to the common areas of resort
                                                                                                                        condominiums.

License Number: 6200629                                              227 APARTMENTS
License Type: Apartment                                              227 NE 7 AVE, ST PETERSBURG 337012632

   Inspection Date: 09/18/2008               Inspection Number: 1209437                Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: WAGNER, MARGARET                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                       Violation Citation

01-10-2               Observed an expired fire extinguisher tag. For reporting purposes only.                           NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                        maintenance not more than one year apart. FOR
                                                                                                                        REPORTING PURPOSES ONLY.

08-03                 Observed no boiler certificate available.                                                         61C-1.004(12) FAC The insurance inspector's boiler
                      Operator can fax copy to Tampa District Office 813 356 1613                                       report is required annually for power boilers and high
                                                                                                                        pressure/high temperature boilers and biannually for low
                      Boiler Information: no access No Boiler Certificate Provided.                                     pressure steam or vapor heating boilers and shall be
                                                                                                                        posted in the boiler room. The provisions of this section
                                                                                                                        do not apply to the common areas of resort
                                                                                                                        condominiums.

License Number: 6203267                                              EL PATIO MOTEL
License Type: Motel                                                  6733 N 4 ST, ST PETERSBURG 337026842

   Inspection Date: 09/15/2008               Inspection Number: 1127545                Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: JACKSON, BEATRICE                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                       Violation Citation

07-06-2               Observed an electrical outlet missing a cover plate in laundry room. For reporting                NFPA 70, 300-31 Suitable covers shall be installed on
                      purposes only.                                                                                    all boxes to prevent accidental contact with energized
                                                                                                                        parts or physical damage to parts or insulation. FOR
                                                                                                                        REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 81
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Pinellas County

License Number: 6213658                                            1717 APARTMENTS
License Type: Apartment                                            1717 N 5 ST, ST PETERSBURG 337044357

   Inspection Date: 09/16/2008              Inspection Number: 1204865               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: WAGNER, MARGARET                                                                                                        Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed flammable material stored around gas water heater, obstructing access                  61C-1.004(7) FAC Attics, basements, boiler rooms,
                      [holiday decorations, oversized stuffed teddy bear, wooden dining table] For                    meter rooms, laundry rooms, and storage rooms shall
                      reporting purposes only. Repeat Violation.                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

License Number: 6203659                                            PALM CREST RESORT MOTEL
License Type: Motel                                                3848 GULF BLVD, ST PETE BCH 337063933

   Inspection Date: 09/18/2008              Inspection Number: 1124701               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BIROCCO, JOSEPH                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

07-06-2               Observed an electrical outlet missing a cover plate. For reporting purposes                     NFPA 70, 300-31 Suitable covers shall be installed on
                      only.Room nine.                                                                                 all boxes to prevent accidental contact with energized
                                                                                                                      parts or physical damage to parts or insulation. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

License Number: 6201618                                            CAMELOT BY THE SEA
License Type: Apartment                                            1705 GULF WAY, ST PETE BCH 337064238

   Inspection Date: 09/09/2008              Inspection Number: 1205034               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BIROCCO, JOSEPH                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed Paper flammable material stored in front of the hotwater tank on built in              61C-1.004(7) FAC Attics, basements, boiler rooms,
                      shelves under the stairwell . For reporting purposes only.                                      meter rooms, laundry rooms, and storage rooms shall
                                                                                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

License Number: 6202981                                            CAMELOT BY THE SEA
License Type: Apartment                                            1801 GULF WAY, ST PETE BCH 337064297

   Inspection Date: 09/09/2008              Inspection Number: 1218811               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BIROCCO, JOSEPH                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed a build up of lint in the laundry room on hotwater tank and dryer. For                 61C-1.004(7) FAC Attics, basements, boiler rooms,
                      reporting purposes only.                                                                        meter rooms, laundry rooms, and storage rooms shall
                                                                                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

07-06-2               Observed an electrical box missing a cover. For reporting purposes only.Laundry                 NFPA 70, 300-31 Suitable covers shall be installed on
                      room.                                                                                           all boxes to prevent accidental contact with energized
                                                                                                                      parts or physical damage to parts or insulation. FOR
                                                                                                                      REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                          Page 82
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Pinellas County

License Number: 6201997                                         CASTLE HOTEL
License Type: Rooming House                                     401 GULF WAY, ST PETE BCH 337064322

   Inspection Date: 09/15/2008           Inspection Number: 1088657              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BIROCCO, JOSEPH                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-07-2            Observed a fire extinguisher on the ground/floor. For reporting purposes                       NFPA 10,1-6.10 Fire extinguishers having a gross
                   only.Lobby area.                                                                               weight not exceeding 40 LB.shall be installed so that the
                                                                                                                  top of the fire extinguisher is not more than 5 ft. above
                                                                                                                  the floor. Fire extinguishers having a gross weight
                                                                                                                  greater than 40 LB (except wheeled type) shall be so
                                                                                                                  installed that the top of the fire extinguisher is not more
                                                                                                                  than 31/2 ft. above the floor. In no case shall the
                                                                                                                  clearance between the bottom of the fire extinguisher
                                                                                                                  and the floor be less than 4 inches. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

01-07-2            Observed a fire extinguisher on the ground/floor. For reporting purposes only.Two              NFPA 10,1-6.10 Fire extinguishers having a gross
                   in lobby area.                                                                                 weight not exceeding 40 LB.shall be installed so that the
                                                                                                                  top of the fire extinguisher is not more than 5 ft. above
                                                                                                                  the floor. Fire extinguishers having a gross weight
                                                                                                                  greater than 40 LB (except wheeled type) shall be so
                                                                                                                  installed that the top of the fire extinguisher is not more
                                                                                                                  than 31/2 ft. above the floor. In no case shall the
                                                                                                                  clearance between the bottom of the fire extinguisher
                                                                                                                  and the floor be less than 4 inches. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only.Throughout              NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                   the building.                                                                                  maintenance not more than one year apart. FOR
                                                                                                                  REPORTING PURPOSES ONLY.

02-05-2            Observed a fire hazard in the means of access. For reporting purposes                          61C-1.004(10) FAC Means of access must be
                   only.Furniture stored in hallway at fire exit.                                                 maintained free of fire hazards. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

06-04-2            Observed exit signs that are not illuminated/not functioning when tested. For                  61-C1.004(10) FAC Exits shall be clearly marked with
                   reporting purposes only.Throughout building.                                                   approved illuminated exit signs. FOR REPORTING
                                                                                                                  PURPOSES ONLY.

License Number: 6201753                                         7100 DARTMOUTH AVE APT
License Type: Apartment                                         7100 DARTMOUTH AVE N, ST PETERSBURG 33710

   Inspection Date: 09/18/2008           Inspection Number: 1204747              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: BURKE, LAWRENCE                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-05-2            Observed a fire extinguisher obscured from view. For reporting purposes only.                  NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                  obscured or obstructed from view. Except in large
                                                                                                                  rooms and in certain locations where visual obstruction
                                                                                                                  can not be completely avoided, a means shall be
                                                                                                                  provided to indicate location. FOR REPORTING
                                                                                                                  PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                                 Page 83
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Pinellas County

License Number: 6204420                                              KNIGHTS INN
License Type: Motel                                                  4601 34 ST S, ST. PETERSBURG 33711

   Inspection Date: 09/16/2008               Inspection Number: 1134559                Inspection Type: Complaint Full                        Inspection Disposition: Warning
   Inspector Name: WILLIAMS, TRINETTE                                                                                                         Issued

Violation Code        Observation                                                                                        Violation Citation

01-07-2               Observed a fire extinguisher on the ground/floor. For reporting purposes only in                   NFPA 10,1-6.10 Fire extinguishers having a gross
                      lobby area.                                                                                        weight not exceeding 40 LB.shall be installed so that the
                                                                                                                         top of the fire extinguisher is not more than 5 ft. above
                                                                                                                         the floor. Fire extinguishers having a gross weight
                                                                                                                         greater than 40 LB (except wheeled type) shall be so
                                                                                                                         installed that the top of the fire extinguisher is not more
                                                                                                                         than 31/2 ft. above the floor. In no case shall the
                                                                                                                         clearance between the bottom of the fire extinguisher
                                                                                                                         and the floor be less than 4 inches. FOR REPORTING
                                                                                                                         PURPOSES ONLY.

02-02-2               Observed flammable material stored in attic/laundry/boiler room. For reporting                     61C-1.004(7) FAC Attics, basements, boiler rooms,
                      purposes only.                                                                                     meter rooms, laundry rooms, and storage rooms shall
                                                                                                                         be kept clean and free of debris and flammables. FOR
                                                                                                                         REPORTING PURPOSES ONLY.

04-01-2               Observed a smoke detector not functioning when tested. For reporting purposes                      61C-1.004(5)FAC All fire safety, protection and
                      only. 147                                                                                          prevention equipment must be installed, approved,
                                                                                                                         maintained and used in accordance with Chapter 509,
                                                                                                                         FS and the National Fire Protection Association Life
                                                                                                                         Safety Code Chapter 101, as adopted by the Division of
                                                                                                                         State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                         REPORTING PURPOSES ONLY.

07-01-2               Observed spliced wire(s) near boiler with light fixture attached. For reporting                    61C-1.004(11)FAC Electrical wiring - To prevent fire or
                      purposes only.                                                                                     injury, defective electrical wiring shall be replaced and
                                                                                                                         wiring shall be kept in good repair. FOR REPORTING
                                                                                                                         PURPOSES ONLY.

07-06-2               Observed an electrical box missing a cover near boiler. For reporting purposes                     NFPA 70, 300-31 Suitable covers shall be installed on
                      only.                                                                                              all boxes to prevent accidental contact with energized
                                                                                                                         parts or physical damage to parts or insulation. FOR
                                                                                                                         REPORTING PURPOSES ONLY.

08-03                 Observed no boiler certificate available.                                                          61C-1.004(12) FAC The insurance inspector's boiler
                                                                                                                         report is required annually for power boilers and high
                      Boiler Information: No Boiler Certificate Provided.                                                pressure/high temperature boilers and biannually for low
                                                                                                                         pressure steam or vapor heating boilers and shall be
                                                                                                                         posted in the boiler room. The provisions of this section
                                                                                                                         do not apply to the common areas of resort
                                                                                                                         condominiums.

License Number: 6215321                                              BRENTWOOD APTS
License Type: Apartment                                              1430 1432 SPRING LN, CLEARWATER 33755

   Inspection Date: 09/17/2008               Inspection Number: 1218663                Inspection Type: Routine - Lodging                     Inspection Disposition: Inspection
   Inspector Name: WINSOR, KIMBERLY                                                                                                           Completed - No Further Action

Violation Code        Observation                                                                                        Violation Citation

01-10-2               Observed an expired fire extinguisher tag. For reporting purposes only.                            NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                         maintenance not more than one year apart. FOR
                                                                                                                         REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                           Page 84
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Pinellas County

License Number: 6201859                                          BELLEAIR HIGHLAND APARTMENTS
License Type: Apartment                                          1462 HAMLET AVE, CLEARWATER 33756

   Inspection Date: 09/12/2008            Inspection Number: 1207047              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DAVIS, CAROL S                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-09-2            Observed a fire extinguisher pressure gauge indicating the extinguisher is in need              NFPA 10,1-6.2 Portable extinguishers shall be
                   of recharge. For reporting purposes only.                                                       maintained in a fully charged and operable condition.
                                                                                                                   FOR REPORTING PURPOSES ONLY.

01-11-2            Observed a fire extinguisher missing an inspection tag. For reporting purposes                  61C-1.004(9)(b) FAC A standard state approved service
                   only.                                                                                           tag shall be attached to each extinguisher and a person
                                                                                                                   holding a valid state permit issued by the State Fire
                                                                                                                   Marshal shall recharge or inspect the extinguisher and
                                                                                                                   shall prepare the tag to include the information required
                                                                                                                   by rule 4A-21.241, FAC, herein adopted by reference.
                                                                                                                   FOR REPORTING PURPOSES ONLY.

License Number: 6205605                                          WAVERLY WAY APTS
License Type: Apartment                                          221 WAVERLY WAY, CLEARWATER 33756

   Inspection Date: 09/12/2008            Inspection Number: 1209361              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DAVIS, CAROL S                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

02-02-2            Observed a build up of lint in the laundry room. For reporting purposes only.                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                   meter rooms, laundry rooms, and storage rooms shall
                                                                                                                   be kept clean and free of debris and flammables. FOR
                                                                                                                   REPORTING PURPOSES ONLY.

License Number: 6214985                                          611 GREENWOOD APARTMENT
License Type: Apartment                                          611 S MARTIN LUTHER KING AVE, CLEARWATER 33756

   Inspection Date: 09/12/2008            Inspection Number: 1204749              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DAVIS, CAROL S                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-11-2            Observed a fire extinguisher missing an inspection tag. For reporting purposes                  61C-1.004(9)(b) FAC A standard state approved service
                   only.                                                                                           tag shall be attached to each extinguisher and a person
                                                                                                                   holding a valid state permit issued by the State Fire
                                                                                                                   Marshal shall recharge or inspect the extinguisher and
                                                                                                                   shall prepare the tag to include the information required
                                                                                                                   by rule 4A-21.241, FAC, herein adopted by reference.
                                                                                                                   FOR REPORTING PURPOSES ONLY.

License Number: 6215627                                          CARMEL AVE APTS
License Type: Apartment                                          1527 CARMEL AVE, CLEARWATER 33756

   Inspection Date: 09/16/2008            Inspection Number: 1207034              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DAVIS, CAROL S                                                                                                       Completed - No Further Action

Violation Code     Observation                                                                                     Violation Citation

01-11-2            Observed a fire extinguisher missing an inspection tag. For reporting purposes                  61C-1.004(9)(b) FAC A standard state approved service
                   only.                                                                                           tag shall be attached to each extinguisher and a person
                                                                                                                   holding a valid state permit issued by the State Fire
                                                                                                                   Marshal shall recharge or inspect the extinguisher and
                                                                                                                   shall prepare the tag to include the information required
                                                                                                                   by rule 4A-21.241, FAC, herein adopted by reference.
                                                                                                                   FOR REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                               Page 85
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Pinellas County

License Number: 6215680                                             203-213 WAVERLY WAY APARTMENTS
License Type: Apartment                                             203 -213 WAVERLY WAY, CLEARWATER 33756

   Inspection Date: 09/12/2008               Inspection Number: 1213846               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DAVIS, CAROL S                                                                                                           Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

01-05-2               Observed a fire extinguisher obscured from view. For reporting purposes only.                    NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                       obscured or obstructed from view. Except in large
                                                                                                                       rooms and in certain locations where visual obstruction
                                                                                                                       can not be completely avoided, a means shall be
                                                                                                                       provided to indicate location. FOR REPORTING
                                                                                                                       PURPOSES ONLY.

License Number: 6206044                                             FARRINGTON APARTMENTS (THE)
License Type: Apartment                                             2738 ROOSEVELT BLVD, CLEARWATER 33760

   Inspection Date: 09/16/2008               Inspection Number: 1218883               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: PORTER, LINDSAY                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.on                  61C-1.004(7) FAC Attics, basements, boiler rooms,
                      floor behind dryers.                                                                             meter rooms, laundry rooms, and storage rooms shall
                                                                                                                       be kept clean and free of debris and flammables. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

License Number: 6209700                                             BEST WESTERN
License Type: Motel                                                 3655 HOSPITALITY LN, CLEARWATER 33762

   Inspection Date: 09/19/2008               Inspection Number: 1123965               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: PORTER, LINDSAY                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only. on                 61C-1.004(7) FAC Attics, basements, boiler rooms,
                      pipes behind dryer.                                                                              meter rooms, laundry rooms, and storage rooms shall
                                                                                                                       be kept clean and free of debris and flammables. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

04-01-2               Observed a trouble/alarm light illuminated on the fire alarm control panel. For                  61C-1.004(5)FAC All fire safety, protection and
                      reporting purposes only.                                                                         prevention equipment must be installed, approved,
                                                                                                                       maintained and used in accordance with Chapter 509,
                                                                                                                       FS and the National Fire Protection Association Life
                                                                                                                       Safety Code Chapter 101, as adopted by the Division of
                                                                                                                       State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

License Number: 6211022                                             COURTYARD BY MARRIOTT
License Type: Hotel                                                 3131 EXECUTIVE DR, CLEARWATER 33762

   Inspection Date: 09/16/2008               Inspection Number: 1101338               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: PORTER, LINDSAY                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

04-01-2               Observed a trouble/alarm light illuminated on the fire alarm control panel. For                  61C-1.004(5)FAC All fire safety, protection and
                      reporting purposes only.                                                                         prevention equipment must be installed, approved,
                                                                                                                       maintained and used in accordance with Chapter 509,
                                                                                                                       FS and the National Fire Protection Association Life
                                                                                                                       Safety Code Chapter 101, as adopted by the Division of
                                                                                                                       State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

06-04-2               Observed an exit sign that is not illuminated/not functioning when tested. For                   61-C1.004(10) FAC Exits shall be clearly marked with
                      reporting purposes only.near guest laundry.                                                      approved illuminated exit signs. FOR REPORTING
                                                                                                                       PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 86
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Pinellas County

License Number: 6214166                                            EXTENDED STAY OF AMERICA #303
License Type: Hotel                                                3089 EXECUTIVE, CLEARWATER 33762

   Inspection Date: 09/15/2008              Inspection Number: 1102045               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: PORTER, LINDSAY                                                                                                         Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

01-03-2               Observed an appropriately sized fire extinguisher is missing. For reporting                     61C-1.004(9)FAC,NFPA 10,1-5.1,3-1.4,3-5 Fire
                      purposes only. no extinguisher in extinguisher box near room 134                                Extinguisher Installation -- Fire extinguishers shall be
                                                                                                                      installed in accordance with NFPA 10, Standard for
                                                                                                                      Portable Fire Extinguishers. [Low] hazard . locations
                                                                                                                      include guest room areas of hotels/motels, etc. [These
                                                                                                                      locations shall be protected by the installation of potable
                                                                                                                      fire extinguishers with a minimum rating of] 2-A10BC
                                                                                                                      provided for each 3000 square feet of floor space on
                                                                                                                      each level and installed so that the travel distance to
                                                                                                                      any extinguisher shall not exceed 75 feet. On each floor
                                                                                                                      level, the area protected and the travel distances shall
                                                                                                                      be based of fire extinguishers installed in accordance
                                                                                                                      with Tables 3-2.1 and 3-3.1. FOR REPORTING
                                                                                                                      PURPOSES ONLY.

License Number: 6202369                                            TUCKERS MOTEL
License Type: Motel                                                14650 66 ST N, CLEARWATER 33764

   Inspection Date: 09/18/2008              Inspection Number: 1126785               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DAVIS, CAROL S                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

04-15-2               Observed no completed/up to date smoke detector log for the battery powered                     69A-43.009(1)(b)(c)FAC Battery powered, single station
                      smoke detectors. For reporting purposes only.                                                   smoke detectors, where used, shall be tested and
                                                                                                                      inspected not less frequently than once per week. A log
                                                                                                                      of the required tests and inspections shall be kept and
                                                                                                                      available to the authority having jurisdiction at any time.
                                                                                                                      This log shall include, but not be limited to, the following
                                                                                                                      information and any other information as may be
                                                                                                                      required by the authority having jurisdiction; 1. A list,
                                                                                                                      clearly identifying each individual detector by its physical
                                                                                                                      location. 2. The date of each required test and
                                                                                                                      inspection. 3. The identity and signature of the
                                                                                                                      inspector. 4. The result of each test and inspection. 5.
                                                                                                                      The completion date and form of any maintenance
                                                                                                                      performed. 6. The completion date and form of any
                                                                                                                      corrective measures taken for each improperly
                                                                                                                      functioning device. 7. A copy of the manufacturer's
                                                                                                                      recommended maintenance schedule and procedures.
                                                                                                                      (c) At such time that the authority having jurisdiction
                                                                                                                      finds cause to believe that the requirements of (a) or (b)
                                                                                                                      are not being fulfilled, detectors powered by the building
                                                                                                                      electrical system shall be required. FOR REPORTING
                                                                                                                      PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 87
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Pinellas County

License Number: 6209543                                             DAYS INN
License Type: Motel                                                 11333 US HWY 19, CLEARWATER 33764

   Inspection Date: 09/18/2008               Inspection Number: 1123845              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DAVIS, CAROL S                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                      meter rooms, laundry rooms, and storage rooms shall
                                                                                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

04-15-2               Observed no completed/up to date smoke detector log for the battery powered                     69A-43.009(1)(b)(c)FAC Battery powered, single station
                      smoke detectors. For reporting purposes only.                                                   smoke detectors, where used, shall be tested and
                                                                                                                      inspected not less frequently than once per week. A log
                                                                                                                      of the required tests and inspections shall be kept and
                                                                                                                      available to the authority having jurisdiction at any time.
                                                                                                                      This log shall include, but not be limited to, the following
                                                                                                                      information and any other information as may be
                                                                                                                      required by the authority having jurisdiction; 1. A list,
                                                                                                                      clearly identifying each individual detector by its physical
                                                                                                                      location. 2. The date of each required test and
                                                                                                                      inspection. 3. The identity and signature of the
                                                                                                                      inspector. 4. The result of each test and inspection. 5.
                                                                                                                      The completion date and form of any maintenance
                                                                                                                      performed. 6. The completion date and form of any
                                                                                                                      corrective measures taken for each improperly
                                                                                                                      functioning device. 7. A copy of the manufacturer's
                                                                                                                      recommended maintenance schedule and procedures.
                                                                                                                      (c) At such time that the authority having jurisdiction
                                                                                                                      finds cause to believe that the requirements of (a) or (b)
                                                                                                                      are not being fulfilled, detectors powered by the building
                                                                                                                      electrical system shall be required. FOR REPORTING
                                                                                                                      PURPOSES ONLY.

License Number: 6200819                                             TROPIC ISLE APARTMENTS INC
License Type: Motel                                                 23 ROCKAWAY ST, CLEARWATER BCH 33767

   Inspection Date: 09/17/2008               Inspection Number: 1126787              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DAVIS, CAROL S                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                      meter rooms, laundry rooms, and storage rooms shall
                                                                                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

License Number: 6204072                                             GOLDEN VILLA APARTMENTS
License Type: Motel                                                 225 CORONADO DRIVE, CLEARWATER BCH 33767

   Inspection Date: 09/17/2008               Inspection Number: 1123849              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DAVIS, CAROL S                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                      meter rooms, laundry rooms, and storage rooms shall
                                                                                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

License Number: 6201228                                             MIDTOWN PLAZA APTS
License Type: Apartment                                             575 CLEARWATER LARGO RD, LARGO 33770

   Inspection Date: 09/17/2008               Inspection Number: 1204810              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: OLSEN, JAMES                                                                                                            Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

01-10-2               Observed an expired fire extinguisher tag. For reporting purposes only. abc near                NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                      apartment 10 last inspection 2/07                                                               maintenance not more than one year apart. FOR
                                                                                                                      REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                             Page 88
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Pinellas County

License Number: 6201198                                          OVERBROOK APTS
License Type: Apartment                                          2101 W BAY DR, LARGO 337701962

   Inspection Date: 09/16/2008            Inspection Number: 1218585               Inspection Type: Routine - Lodging                     Inspection Disposition: Inspection
   Inspector Name: OLSEN, JAMES                                                                                                           Completed - No Further Action

Violation Code     Observation                                                                                       Violation Citation

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only. abc in                    NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                   laundry room last inspection 10/04                                                                maintenance not more than one year apart. FOR
                                                                                                                     REPORTING PURPOSES ONLY.

License Number: 6201931                                          HERITAGE VILLAGE MOBILE HM PRK
License Type: Apartment                                          12840 SEMINOLE BLVD, LARGO 337782318

   Inspection Date: 09/16/2008            Inspection Number: 1213888               Inspection Type: Routine - Lodging                     Inspection Disposition: Inspection
   Inspector Name: OLSEN, JAMES                                                                                                           Completed - No Further Action

Violation Code     Observation                                                                                       Violation Citation

01-10-2            Observed an expired fire extinguisher tag. For reporting purposes only. abc near                  NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                   apartment 4 last inspection 5/06                                                                  maintenance not more than one year apart. FOR
                                                                                                                     REPORTING PURPOSES ONLY.

License Number: 6213137                                          PARK SIDE VILLAS
License Type: Apartment                                          3715 N 66 AVE, PINELLAS PARK 337816101

   Inspection Date: 09/19/2008            Inspection Number: 1220932               Inspection Type: Routine - Lodging                     Inspection Disposition: Inspection
   Inspector Name: BURKE, LAWRENCE                                                                                                        Completed - No Further Action

Violation Code     Observation                                                                                       Violation Citation

01-07-2            Observed a fire extinguisher not mounted at the correct height. For reporting                     NFPA 10,1-6.10 Fire extinguishers having a gross
                   purposes only.                                                                                    weight not exceeding 40 LB.shall be installed so that the
                                                                                                                     top of the fire extinguisher is not more than 5 ft. above
                                                                                                                     the floor. Fire extinguishers having a gross weight
                                                                                                                     greater than 40 LB (except wheeled type) shall be so
                                                                                                                     installed that the top of the fire extinguisher is not more
                                                                                                                     than 31/2 ft. above the floor. In no case shall the
                                                                                                                     clearance between the bottom of the fire extinguisher
                                                                                                                     and the floor be less than 4 inches. FOR REPORTING
                                                                                                                     PURPOSES ONLY.

License Number: 6214883                                          PLANTATION GARDEN APTS
License Type: Apartment                                          5501 110 AVE, PINELLAS PARK 33782

   Inspection Date: 09/15/2008            Inspection Number: 1240002               Inspection Type: Complaint Full                        Inspection Disposition: Inspection
   Inspector Name: PORTER, LINDSAY                                                                                                        Completed - No Further Action

Violation Code     Observation                                                                                       Violation Citation

04-01-2            Observed a trouble/alarm light illuminated on the fire alarm control panel. For                   61C-1.004(5)FAC All fire safety, protection and
                   reporting purposes only. near unit #102                                                           prevention equipment must be installed, approved,
                                                                                                                     maintained and used in accordance with Chapter 509,
                                                                                                                     FS and the National Fire Protection Association Life
                                                                                                                     Safety Code Chapter 101, as adopted by the Division of
                                                                                                                     State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                     REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                             Page 89
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Pinellas County

License Number: 6204595                                            GOLFVIEW MOTEL
License Type: Motel                                                1475 S PINELLAS AVE, TARPON SPGS 346893723

   Inspection Date: 09/12/2008              Inspection Number: 1124663              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: PEARCE, LAURA                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                    Violation Citation

01-07-2               Observed a fire extinguisher on the ground/floor. For reporting purposes only. on              NFPA 10,1-6.10 Fire extinguishers having a gross
                      ground -back of building                                                                       weight not exceeding 40 LB.shall be installed so that the
                                                                                                                     top of the fire extinguisher is not more than 5 ft. above
                                                                                                                     the floor. Fire extinguishers having a gross weight
                                                                                                                     greater than 40 LB (except wheeled type) shall be so
                                                                                                                     installed that the top of the fire extinguisher is not more
                                                                                                                     than 31/2 ft. above the floor. In no case shall the
                                                                                                                     clearance between the bottom of the fire extinguisher
                                                                                                                     and the floor be less than 4 inches. FOR REPORTING
                                                                                                                     PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                                 Page 90
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Polk County

License Number: 6301014                                             HOWARD JOHNSON INN
License Type: Motel                                                 1300 3RD STREET SW, WINTER HAVEN 33880

   Inspection Date: 09/16/2008               Inspection Number: 1126101               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: WHITE, CHERYL                                                                                                            Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.                    61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                       meter rooms, laundry rooms, and storage rooms shall
                                                                                                                       be kept clean and free of debris and flammables. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

06-06-2               Observed an interior corridor door is not self-closing. For reporting purposes only.             NFPA 101, 30-3.6.3 Each guest room door that opens
                      Door open hallway in second building                                                             onto an interior corridor shall be self-closing and shall
                                                                                                                       meet the requirements of [NFPA]30, 17-3.6.2. FOR
                                                                                                                       REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                          Page 91
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Santa Rosa County

License Number: 6701316                                         RUSSELL CROWLEY APARTMENTS
License Type: Apartment                                         3875 AVALON BLVD, MILTON 32583

   Inspection Date: 09/18/2008           Inspection Number: 1216920              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: WINN, RONALD                                                                                                        Completed - No Further Action

Violation Code     Observation                                                                                    Violation Citation

01-05-2            Observed a fire extinguisher not furnished in Apt #4, according to resident. No                NFPA 10, 1-6.10 Fire extinguishers shall not be
                   observable exterior extinguishers on buildings. For reporting purposes only.                   obscured or obstructed from view. Except in large
                                                                                                                  rooms and in certain locations where visual obstruction
                                                                                                                  can not be completely avoided, a means shall be
                                                                                                                  provided to indicate location. FOR REPORTING
                                                                                                                  PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                                Page 92
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Sarasota County

License Number: 6800907                                              GOLDEN HOST RESORT
License Type: Motel                                                  4675 N TAMIAMI TRAIL, SARASOTA 34234

   Inspection Date: 09/16/2008               Inspection Number: 1124409               Inspection Type: Routine - Lodging                    Inspection Disposition: Call Back -
   Inspector Name: QUINTANA, JOSE                                                                                                           Complied

Violation Code        Observation                                                                                      Violation Citation

01-05-2               Violation: 01-05-2                                                                               NFPA 10, 1-6.10 Fire extinguishers shall not be
                                                                                                                       obscured or obstructed from view. Except in large
                      Observed a fire extinguisher meter obscured from view between rooms 220 and                      rooms and in certain locations where visual obstruction
                      222. For reporting purposes only.                                                                can not be completely avoided, a means shall be
                                                                                                                       provided to indicate location. FOR REPORTING
                                                                                                                       PURPOSES ONLY.

01-06-2               Violation: 01-06-2                                                                               NFPA 10,1-6.5 Cabinets housing fire extinguishers shall
                                                                                                                       not be locked. Except locked cabinets may be used
                      Observed a locked fire extinguisher box missing a breaking device between rooms                  provided they include means of emergency access.
                      131 and 133. For reporting purposes only.                                                        FOR REPORTING PURPOSES ONLY.

04-01-2               Violation: 04-01-2                                                                               61C-1.004(5)FAC All fire safety, protection and
                                                                                                                       prevention equipment must be installed, approved,
                      Observed a smoke detector not functioning when tested in room 212. For                           maintained and used in accordance with Chapter 509,
                      reporting purposes only.                                                                         FS and the National Fire Protection Association Life
                                                                                                                       Safety Code Chapter 101, as adopted by the Division of
                                                                                                                       State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

06-04-2               Violation: 06-04-2                                                                               61-C1.004(10) FAC Exits shall be clearly marked with
                                                                                                                       approved illuminated exit signs. FOR REPORTING
                      Observed an exit sign that is not illuminated/not functioning when tested. in front              PURPOSES ONLY.
                      lobby, For reporting purposes only.

06-20-2               Violation: 06-20-2                                                                               61C-1.004(5)FAC All fire safety, protection and
                                                                                                                       prevention equipment must be installed, approved,
                      Observed an emergency light that is not functioning when tested between rooms                    maintained and used in accordance with Chapter 509,
                      220 and 222. For reporting purposes only.                                                        FS and the National Fire Protection Association Life
                                                                                                                       Safety Code Chapter 101, as adopted by the Division of
                                                                                                                       State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                       REPORTING PURPOSES ONLY.

License Number: 6801133                                              LIDO ISLANDER
License Type: Apartment                                              528 S POLK DR, SARASOTA 34236

   Inspection Date: 09/19/2008               Inspection Number: 1212518               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: POSA, ANTHONY                                                                                                            Completed - No Further Action

Violation Code        Observation                                                                                      Violation Citation

01-10-2               Observed expired fire extinguisher tags. For reporting purposes only.                            NFPA 10, 4-4.1 Fire extinguishers shall be subjected to
                                                                                                                       maintenance not more than one year apart. FOR
                                                                                                                       REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                              Page 93
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

St. Johns County

License Number: 6501467                                             HILTON GARDEN INN
License Type: Hotel                                                 45 PGA TOUR BLVD, PONTE VEDRA BEACH 32082

   Inspection Date: 09/17/2008               Inspection Number: 1101039              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: LAMIE, ERNEST                                                                                                           Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

02-02-2               Observed a build up of lint in the laundry room. For reporting purposes only.                   61C-1.004(7) FAC Attics, basements, boiler rooms,
                                                                                                                      meter rooms, laundry rooms, and storage rooms shall
                                                                                                                      be kept clean and free of debris and flammables. FOR
                                                                                                                      REPORTING PURPOSES ONLY.

License Number: 6501241                                             PENNY FARTHING INN
License Type: Bed and Breakfast                                     83 CEDAR ST, SAINT AUGUSTINE 32084

   Inspection Date: 09/15/2008               Inspection Number: 1086468              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: GOSAI, MATT                                                                                                             Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

07-02-2               Observed an extension cord in use. For reporting purposes only. ROOM DAWN                       61C-1.004(11) FAC No extension cords shall be used
                                                                                                                      except during cleaning, maintenance and other
                                                                                                                      temporary activities. FOR REPORTING PURPOSES
                                                                                                                      ONLY.

License Number: 6500239                                             BEST WESTERN
License Type: Motel                                                 6 CASTILLO DR, ST AUGUSTINE 320843652

   Inspection Date: 09/17/2008               Inspection Number: 1124175              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: GOSAI, MATT                                                                                                             Completed - No Further Action

Violation Code        Observation                                                                                     Violation Citation

07-06-2               Observed an electrical outlet missing a cover plate. For reporting purposes only.               NFPA 70, 300-31 Suitable covers shall be installed on
                      WASHER TOP LID NOT SECURE . EXPOSED WIRE                                                        all boxes to prevent accidental contact with energized
                                                                                                                      parts or physical damage to parts or insulation. FOR
                                                                                                                      REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                             Page 94
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

St. Lucie County

License Number: 6602517                                            HAMPTON INN & SUITES FT PIERCE
License Type: Hotel                                                1985 REYNOLDS DR, FORT PIERCE 34945

   Inspection Date: 09/18/2008              Inspection Number: 1102065              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: PARNASS, LAUREN P                                                                                                      Completed - No Further Action

Violation Code        Observation                                                                                    Violation Citation

06-20-2               Observed an emergency light that is not functioning when tested, west side exit.               61C-1.004(5)FAC All fire safety, protection and
                      For reporting purposes only.                                                                   prevention equipment must be installed, approved,
                                                                                                                     maintained and used in accordance with Chapter 509,
                                                                                                                     FS and the National Fire Protection Association Life
                                                                                                                     Safety Code Chapter 101, as adopted by the Division of
                                                                                                                     State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                     REPORTING PURPOSES ONLY.

License Number: 6600368                                            THE NOCERA TRUST
License Type: Apartment                                            3206 LOUISIANA AVE (3208 & 3210), FT PIERCE 34947

   Inspection Date: 09/12/2008              Inspection Number: 1216519              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DAVIS, DIANNA                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                    Violation Citation

01-09-2               Observed a fire extinguisher pressure gauge indicating the extinguisher is over                NFPA 10,1-6.2 Portable extinguishers shall be
                      charged- building 3208. For reporting purposes only.                                           maintained in a fully charged and operable condition.
                                                                                                                     FOR REPORTING PURPOSES ONLY.

License Number: 6602439                                            SEAWAY APTS
License Type: Apartment                                            637 N. 2ND STREET, FORT PIERCE 34950

   Inspection Date: 09/12/2008              Inspection Number: 1207437              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DAVIS, DIANNA                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                    Violation Citation

01-09-2               Observed a fire extinguisher pressure gauge indicating the extinguisher is in need             NFPA 10,1-6.2 Portable extinguishers shall be
                      of recharge-second floor by window at top of stairs. For reporting purposes only.              maintained in a fully charged and operable condition.
                                                                                                                     FOR REPORTING PURPOSES ONLY.

License Number: 6600855                                            HEATHER WAY FT PIERCE LTD
License Type: Apartment                                            5001 SPARKLING PINES CIR, FT PIERCE 349513515

   Inspection Date: 09/17/2008              Inspection Number: 1218941              Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DAVIS, DIANNA                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                    Violation Citation

02-04-2               Observed several LP gas tanks having a water capacity greater than 2 1/2 lbs.                  NFPA 58, 3-4.9.2 [LP Gas] Containers having water
                      stored on front porches of several units.                                                      capacities greater than 21/2 pounds (1kg) shall not be
                                                                                                                     located on balconies above the first floor that are
                                                                                                                     attached to a multiple family dwelling of 3 or more living
                                                                                                                     units one above the other. Exception: Where such
                                                                                                                     balconies are served by outside stairways and where
                                                                                                                     only such stairways are used to transport the container.
                                                                                                                     FOR REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                            Page 95
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

St. Lucie County

License Number: 6602526                                          KITTERMAN WOODS
License Type: Apartment                                          6600 WOODS ISLAND CIR, PORT ST LUCIE 34952

   Inspection Date: 09/12/2008            Inspection Number: 1207447               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: PARNASS, LAUREN P                                                                                                     Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

01-09-2            Observed a fire extinguisher pressure gauge indicating the extinguisher is in need               NFPA 10,1-6.2 Portable extinguishers shall be
                   of recharge, building 4 next to unit 108. For reporting purposes only.                           maintained in a fully charged and operable condition.
                                                                                                                    FOR REPORTING PURPOSES ONLY.

04-01-2            Observed a trouble/alarm light illuminated on the fire alarm control panel. For                  61C-1.004(5)FAC All fire safety, protection and
                   reporting purposes only.                                                                         prevention equipment must be installed, approved,
                                                                                                                    maintained and used in accordance with Chapter 509,
                                                                                                                    FS and the National Fire Protection Association Life
                                                                                                                    Safety Code Chapter 101, as adopted by the Division of
                                                                                                                    State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                    REPORTING PURPOSES ONLY.

License Number: 6601024                                          ATLANTIS COVE
License Type: Apartment                                          2476 ATLANTIS DR, FT PIERCE 34981

   Inspection Date: 09/18/2008            Inspection Number: 1216529               Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
   Inspector Name: DAVIS, DIANNA                                                                                                         Completed - No Further Action

Violation Code     Observation                                                                                      Violation Citation

04-01-2            Observed a trouble/alarm light illuminated on the fire alarm control panelbu lding               61C-1.004(5)FAC All fire safety, protection and
                   2477. For reporting purposes only.                                                               prevention equipment must be installed, approved,
                                                                                                                    maintained and used in accordance with Chapter 509,
                                                                                                                    FS and the National Fire Protection Association Life
                                                                                                                    Safety Code Chapter 101, as adopted by the Division of
                                                                                                                    State Fire Marshal in Chapter 4A-3, FAC. FOR
                                                                                                                    REPORTING PURPOSES ONLY.
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                                Page 96
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Volusia County

License Number: 7406429                                              BGT APARTMENTS
License Type: Apartment                                              565 DR MARY MCLEOD BETHUNE BLVD, DAYTONA BEACH 32114

     Inspection Date: 09/16/2008             Inspection Number: 1214355                Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
     Inspector Name: BRANNER, LISELOTTE                                                                                                      Issued

Violation Code        Observation                                                                                       Violation Citation

07-06-2               Observed an electrical outlet missing a cover plate by mail boxes for apartment's                 NFPA 70, 300-31 Suitable covers shall be installed on
                      2,3,4. For reporting purposes only.                                                               all boxes to prevent accidental contact with energized
                                                                                                                        parts or physical damage to parts or insulation. FOR
                                                                                                                        REPORTING PURPOSES ONLY.

License Number: 7402515                                              CENTRAL MANOR APTS
License Type: Apartment                                              136 FAIRVIEW AVE, DAYTONA BCH 321142120

     Inspection Date: 09/16/2008             Inspection Number: 1219065                Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
     Inspector Name: BRANNER, LISELOTTE                                                                                                      Completed - No Further Action

Violation Code        Observation                                                                                       Violation Citation

06-04-2               Observed an exit sign that is not illuminated /First floor stairway south end. For                61-C1.004(10) FAC Exits shall be clearly marked with
                      reporting purposes only.                                                                          approved illuminated exit signs. FOR REPORTING
                                                                                                                        PURPOSES ONLY.

License Number: 7400876                                              BUDGET INN OF DAYTONA BCH
License Type: Motel                                                  640 S RIDGEWOOD AVE, DAYTONA BCH 321144932

     Inspection Date: 09/17/2008             Inspection Number: 1126255                Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
     Inspector Name: BRANNER, LISELOTTE                                                                                                      Completed - No Further Action

Violation Code        Observation                                                                                       Violation Citation

01-07-2               Observed a fire extinguisher on the ground/floor water heater room.. For reporting                NFPA 10,1-6.10 Fire extinguishers having a gross
                      purposes only.                                                                                    weight not exceeding 40 LB.shall be installed so that the
                                                                                                                        top of the fire extinguisher is not more than 5 ft. above
                                                                                                                        the floor. Fire extinguishers having a gross weight
                                                                                                                        greater than 40 LB (except wheeled type) shall be so
                                                                                                                        installed that the top of the fire extinguisher is not more
                                                                                                                        than 31/2 ft. above the floor. In no case shall the
                                                                                                                        clearance between the bottom of the fire extinguisher
                                                                                                                        and the floor be less than 4 inches. FOR REPORTING
                                                                                                                        PURPOSES ONLY.

License Number: 7401279                                              RIDGEWOOD INN
License Type: Motel                                                  128 RIDGEWOOD AVENUE, HOLLY HILL 321175028

     Inspection Date: 09/08/2008             Inspection Number: 1127685                Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
     Inspector Name: BERGSTRESSER, REBECCA L                                                                                                 Completed - No Further Action

Violation Code        Observation                                                                                       Violation Citation

02                    Out of compliance: Fire Hazards                                                                   FS: 509; FAC 61C Fire Hazards



License Number: 7400131                                              DIPLOMATIC TOWERS
License Type: Apartment                                              101 SEABREEZE BLVD, DAYTONA BEACH 32118

     Inspection Date: 05/28/2008             Inspection Number: 1207559                Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
     Inspector Name: BARRETT, KAREN                                                                                                          Issued

Violation Code        Observation                                                                                       Violation Citation

03                    Out of compliance: Sprinkler system                                                               FS: 509; FAC 61C Sprinkler system


07                    Out of compliance: Electrical deficiencies                                                        FAC: 61C-1.004(11) Electrical deficiencies
DIVISION OF HOTELS AND RESTAURANTS                                                                                                                                                Page 97
FIRE CODE VIOLATIONS OBSERVED IN PUBLIC LODGING ESTABLISHMENTS - WEEK ENDING 9/20/2008
www.MyFloridaLicense.com/dbpr/hr/

Volusia County

License Number: 7400133                                              SEASHELLS BEACH CLUB
License Type: Motel                                                  1014 N. ATLANTIC AVE, DAYTONA BEACH 32118

     Inspection Date: 09/15/2008             Inspection Number: 1127003                Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
     Inspector Name: BARRETT, KAREN                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                       Violation Citation

07-02-2               Observed an extension cord in use on light in laundry room For reporting                          61C-1.004(11) FAC No extension cords shall be used
                      purposes only.                                                                                    except during cleaning, maintenance and other
                                                                                                                        temporary activities. FOR REPORTING PURPOSES
                                                                                                                        ONLY.

07-04-2               Observed a splitter/multi-plug adapter in use. on electrical outlet outlet outside                61C-1.004(11)FAC In accordance with the provisions of
                      laundry room For reporting purposes only.                                                         NFPA 70, the National Electrical Code, as adopted by
                                                                                                                        the Division of State Fire Marshal in Chapter 4A03,
                                                                                                                        FAC, Uniform Fire Safety Rules and Standards,
                                                                                                                        sufficient electrical outlets shall be provided. FOR
                                                                                                                        REPORTING PURPOSES ONLY.

License Number: 7400620                                              DIPLOMATIC TOWERS
License Type: Apartment                                              100 SEABREEZE BLVD, DAYTONA BEACH 32118

     Inspection Date: 05/28/2008             Inspection Number: 1216605                Inspection Type: Routine - Lodging                    Inspection Disposition: Warning
     Inspector Name: BARRETT, KAREN                                                                                                          Issued

Violation Code        Observation                                                                                       Violation Citation

01                    Out of compliance: Fire extinguishers/standpipe systems                                           FAC: 61C NFPA: 10; FAC: 4A-43 Fire
                                                                                                                        extinguishers/standpipe systems

03                    Out of compliance: Sprinkler system                                                               FS: 509; FAC 61C Sprinkler system



License Number: 7401295                                              MAJESTY COURT
License Type: Motel                                                  999 N ATLANTIC AVE, DAYTONA BEACH 32118

     Inspection Date: 08/06/2008             Inspection Number: 1126223                Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
     Inspector Name: BARRETT, KAREN                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                       Violation Citation

01                    Out of compliance: Fire extinguishers/standpipe systems                                           FAC: 61C NFPA: 10; FAC: 4A-43 Fire
                                                                                                                        extinguishers/standpipe systems

06                    Out of compliance: Exits; obstructions, exit signs, emergency lights                              FAC: 61C-1.004(6), (10) Exits; obstructions, exit signs,
                                                                                                                        emergency lights

07                    Out of compliance: Electrical deficiencies                                                        FAC: 61C-1.004(11) Electrical deficiencies



License Number: 7401465                                              TROPIC AIR MOTEL
License Type: Motel                                                  1000 S ATLANTIC AVE, DAYTONA BCH 321184765

     Inspection Date: 09/19/2008             Inspection Number: 1124821                Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
     Inspector Name: BARRETT, KAREN                                                                                                          Completed - No Further Action

Violation Code        Observation                                                                                       Violation Citation

07-01-2               Observed an electrical box in disrepair. For reporting purposes only.observed light               61C-1.004(11)FAC Electrical wiring - To prevent fire or
                      hanging from wire on south side of buikding.                                                      injury, defective electrical wiring shall be replaced and
                                                                                                                        wiring shall be kept in good repair. FOR REPORTING
                                                                                                                        PURPOSES ONLY.

License Number: 7400712                                              CORAL SANDS INN & SEASIDE COTTAGES
License Type: Motel                                                  1009 OCEANSHORE BLVD, ORMOND BEACH 32176-4105

     Inspection Date: 09/04/2008             Inspection Number: 1134629                Inspection Type: Routine - Lodging                    Inspection Disposition: Inspection
     Inspector Name: BERGSTRESSER, REBECCA L                                                                                                 Completed - No Further Action

Violation Code        Observation                                                                                       Violation Citation

04                    Out of compliance: Smoke detectors; fire alarm systems                                            FS: 509.215(4),(6); FAC: 61C-1.004(5) Smoke
                                                                                                                        detectors; fire alarm systems

				