              Product Specification                                                             Impulse Measurement
                                                                                                Calibration - Diagnosis
                                                                                                       www.strauss.de




                    Impulse Voltage
                                   Test Technique
        Measurement – Calibration – Diagnosis




1   DR. STRAUSS SYSTEM-ELEKTRONIK GMBH   Phone +49 951-43063   INFO www.strauss.de
    D-96163 Gundelsheim/Bamberg          Fax +49 951-43858     email dr.strauss@strauss.de
                                                                                              TRAS F2-E 23/01/2009
                                                                                                                                                                                   DR. STRAUSS
    Performance Progress of Digital Recorder                                                                                                                                              Impulse Measurement
                                                                   in the last 16 years                                                                                                   Calibration - Diagnosis
                                                                                                                                                                                                 www.strauss.de


 MS/s, MHz
                                                Performance progress of Digital Recorder
                                                                                                                                                   Bit
                                                                                                                                                           Already in 1987, the first TR-AS 100-8 Digital Recor-
                                                          in the last 16 years                                                                             der was delivered to customers for h.v. impulse tests
  220                                                                                                                                              22
                                                                                                                                                           and was therefore the first system with 100 MS/s
  200                                                                                                                                              20
                                  SampleRate MS/s                                                                                                          sampling rate, which fulfilled all requirements of the
  180                                                                                                                                              18      IEC 1083-1, published later in 1991.
                                  Bandwidth MHz
  160                                                                                                                                              16      A short time later in 1989 followed the TR-AS 100-
                                  Resolution Bit
  140                                                                                                                                              14      10 Digital Recorder as the leading systems with 100
  120                                                                                                                                              12      MS/s sampling rate at 10 Bit resolution which fulfil-
  100                                                                                                                                              10
                                                                                                                                                           led all requirements of IEC 1083-1 in all respects for
                                                                                                                                                           comparative measurements, too.
   80                                                                                                                                              8
   60                                                                                                                                              6
                                                                                                                                                           The first competitor system with a sampling rate of
                                                                                                                                                           100 MS/s as required in IEC 1083-1 followed with
   40                                                                                                                                              4
                                                                                                                                                           120 MS/s and 12 Bit resolution years later in 1997,
   20                                                                                                                                              2       when we finished the design of the TR-AS 200-12
    0                                                                                                                                              0       Digital Recorder with 200 MS/s sampling rate and
                                                                                                    HIAS 743 1997
         Requirem. 1991




                                         HIAS 742
                          TR-AS 100




                                                                         TR-AS 100



                                                                                     TR-AS 200




                                                                                                                       TR-AS 200



                                                                                                                                     TR-AS 200
                                                        PowerPro




                                                                                                                                                           12 Bit resolution.
           IEC 1083-1




                            1987




                                                                           1989



                                                                                       1997




                                                                                                                         1997



                                                                                                                                       2003
                                                                                                                                                           End of 2002 we presented a new designed system
                                                                                                                                                           with 200 MS/s and 14 Bit resolution and further
                                                                                                                                                           significantly reduced noice.

200 MS/s reduces measuring uncertainty – 12 to 14 Bit show details of measured waves
The higher sampling rate of 200 MS/s (5ns sampling intervall instead of 8 or 10 ns) show increased accuracy and
reduced standard deviations for the front time of full impulses as also for the peak and the time-to-chopping at
front chopped impulses during calibration. The influence of the increased resolution from 10 Bit (0.1%) to 12 or 14
Bit (0.006 %) to the resulting overall measuring uncertainty of approx. 0.5% to 0.7% is hereby negligible.

TR-AS 200-12 – Kalibrierung bei der PTB / Calibration at PTB

                           voller Blitzstoß/ full wave LI                                abgeschnittener Blitz-                             abgeschnittener Blitz-
 TR-AS 200-                            0,84/60                                            stoß/ chopped wave                                 stoß chopped wave
    12                                200 MS/s                                                 Tc=0,5ms                                           Tc=0,5ms
                                                                                                200 MS/s                                    1 GS/s Oversampling
Meßbereich/                   Û                dÛ             dT1             dT2           Û       dÛ    dTc                                 Û      dÛ     dTc
  Range
    V                       V                %                     %           %           V                        %              %          V          %       %
   2000                   -966,8            -0,3                   0,5        -0,2       -740,4                     0,1            0,6      -742,0       0,0    -0,2
   1600                   -966,2            -0,3                   0,4        -0,6       -740,5                     0,1            0,4
   1250                   -1000             0,0                    1,7        -0,7       -741,8                     0,2            0,4
   1000                   -801,7            0,1                    0,7        -0,6       -742,2                     0,3            0,4      -742,0       0,3    -0,2
   800                    -641,6            0,1                    0,8        -0,8       -635,7                     0,1            0,2                                   TR-AS 200-14: Differential Nonlinearity DNL
                                                                                                                                                                         under dynamic conditions referred to 12 Bit
   640                    -513,0            0,0                    0,7        -0,7       -508,5                     0,0            0,4      -508,0       0,1    -0,2
                                                                                                                                                                         resolution. The result with < 0,2 LSB shown
   500                    -400,8            0,0                    0,8        -0,7       -397,7                     -0,3           0,4
                                                                                                                                                                         in Figure 5 is significantly below the limits
   400                    -321,0            0,2                    0,7        -0,7       -318,1                     -0,3           0,4
                                                                                                                                                                         required in IEC 61083-1 of 0,8 LSB.
   320                    -256,7            0,2                    0,8        -0,8       -254,8                     0,0            0,4      -255,4       -0,1    0,2
   256                    -205,2            0,1                    0,6        -0,7       -203,4                     -0,2           0,8                                    +0,5% Limit IEC 1083
   200                    -160,4            0,1                    0,4        -0,6       -158,3                     -0,4           0,8
   160                    -128,3            0,1                    0,2        -0,6       -127,0                     -0,3           0,6
   128                    -102,7            0,2                    0,4        -0,7       -102,3                     -0,1           0,8
   102                     -82,2            0,2                    0,7        -0,8        -82,4                     0,0            0,8           -82,4   0,2     0,0
    80                     -64,0            0,2                    0,8        -0,9        -64,8                     0,0            0,6
    80                      64,1            0,1                    0,5        -0,4         65,1                     -0,2           0,8
   102                      82,2            0,2                    0,6        -0,3         82,8                     -0,1           1,2           82,8    0,1     0,0
   128                     102,8            0,2                    0,5        -0,4        102,7                     -0,2           0,6
   160                     128,4            0,0                    0,6        -0,3        127,6                     -0,4           0,4
   200                     160,6            0,1                    0,8        -0,3        159,1                     -0,4           0,8
   256                     205,5            0,1                    0,7        -0,5        204,3                     -0,4           0,8
                                                                                                                                                                          -0,5% Limit IEC 1083
   320                     256,9            0,1                    0,8        -0,5        255,7                     -0,3           1,0       256,8       -0,2    0,2
   400                     321,3            0,1                    1,0        -0,3        319,2                     -0,3           0,6
   500                     401,2            -0,1                   1,1        -0,3        399,5                     -0,3           0,8                                   TR-AS 200-14: The static integral non-
   640                     513,7            0,0                    1,0        -0,4        511,3                     -0,2           0,8       512,0       0,0     0,0     linearity INL referred to 14 Bit resolution
   800                     642,1            -0,1                   0,4        -0,3        638,7                     -0,1           0,8                                   shows at 200 MS/s an excellent lapse and
   1000                    803,1            0,0                    0,7        -0,2        747,1                     0,2            0,8       748,0       0,1    -0,2     stays signifikant inside the required limits of
   1250                   1000,3            -0,2                   1,1        -0,4        747,4                     0,3            1,0                                   ± 0,5% in IEC 1083-1. The INL influences
                                                                                                                                                                         directly the measuring accuracy as also the
   1600                    968,6            -0,2                   0,4        -0,6        745,9                     0,1            0,8                                   calibration results.
   2000                    969,7            -0,1                   0,4        -0,4        747,3                     0,3            1,0       748,0       0,1     0,0

DR. STRAUSS SYSTEM-ELEKTRONIK GMBH                                                               Phone +49 951-43063                                 INFO www.strauss.de                                                   2
D-96163 Gundelsheim/Bamberg                                                                      Fax +49 951-43858                                   email dr.strauss@strauss.de
                                                                                                                                                                                      TRAS F2-E 23/01/2009
                                                                                                             DR. STRAUSS
        Digital Impulse Voltage Measuring Systems
                                                                                                                  Impulse Measurement
        TR-AS® 60-10-12 / 100-10-12 / 200-12-14 / 400-12                                                          Calibration - Diagnosis
                                                                                                                         www.strauss.de


    Highest performance with up to 200 MS/s sampling rate and
    12 to 14 Bit resolution simultaneously in all channels
    The well-established Impulse Voltage        simultaneously in up to 16 measuring              sampling rate of 200 MS/s today – and
    Measuring Systems TR-AS, including the      channels.                                         optionally 400 MS/s with 10 to 12 Bit re-
    digital recorders from our own develop-     The new developed composit A/D-                   solution is available for steep i.v. tests.
    ment and manufacturing, were conse-         converter hardware system generates               The high sampling rate of 200 MS/s and
    quently further developed and now fea-      raw data with up to 14 Bit resolution to-         the high bandwidth of 50 MHz show inc-
    ture improved sampling rates up to 200      gether with the highest available                 reased accuracy and reduced standard
    MS/s in real-time with 14 Bit resolution
                                                Desktop-Housing DERA 6                             deviations for the front time of full im-
                                                                                                   pulses as also for the peak and the
                                                Compact design for i.v. tests and calibrati-
                                                ons in the test field and on site with connec-
                                                                                                   time-to-chopping at front chopped im-
                                                tion to printer and fileserver via glassfibre      pulses.
                                                LAN                                                A careful design using sophisticated
                                                12” TFT Color Display                              programmable logic controllers and
                                                Keyboard with trackball in drawer                  SMT optimizes the demanding require-
                                                Measuring rack mount with 1 to 4 channels
                                                                                                   ments like high sampling rate, small
                                                each with                                          risetime, minimized noise, short settling
                                                                                                   time, small measuring uncertainty and
                                                Direct input 100 mV to 10 V on rear
                                                                                                   good long-term accuracy.
                                                Input 12 V to 2000 V on rear
                                                                                                   This results in nearly smooth wavesha-
                                                Dimensions: approx. 55x55x35 cm (BxDxH)
                                                Weight: approx. 25 kg                              pes without visible quantization steps
                                                                                                   and significantly improves the accuracy
                                                Measuring Rack MIRA 25                             of diagnosis using difference method or
                                                Compact design with all components inclu-          transfer function.
                                                ding printer inside the rack
                                                                                                   The direct input of the high bandwidth
                                                easy to move inside the test field                 precision amplifiers with an input impe-
                                                all sensitive connections inside the rack          dance of 1 MOhm allows the measu-
                                                (keyboard, display, printer) are well shielded     rement of the step response of i.v. divi-
                                                17“ or 19“ large TFT-Display                       ders matching to impedance of the
                                                Keyboard with trackball in drawer                  2000 V measuring input.
                                                Wireless keyboard and mouse optional               The patented multi-timebase allows
                                                Laser Printer in drawer                            setting of up to 8 individual sampling
                                                Measuring rack mount with 1 to 4 channels          rates each with a selectable number of
                                                each with:                                         samples, so individual time profiles can
                                                                                                   be generated, e.g. a profile similar to
                                                Direct input 100 mV to 10 V on front
                                                                                                   an exponential timebase.
                                                Input 12 V to 2000 V on front
                                                                                                   As an option, for multichannel applicati-
                                                Measuring line bushings to the rear
                                                                                                   ons in the high power test field, the
                                                Suitable for i.v. tests and calibrations in the    sampling rate of each individual chan-
                                                test field with high electromagnetic distorti-
                                                                                                   nel can be indepently selected. With
                                                ons
                                                                                                   this option fast transients and slow e-
                                                Dimensions:                                        vents can be recorded with reference
                                                approx. 55x65x125 cm (BxDxH)                       to a common trigger event and display-
                                                Weight: approx. 80 kg                              ed together on the monitor.

    Common Features of TR-AS®:                                            TR-AS® and WinTR-AS® are registered trademarks of DR. STRAUSS

    · 80% input range steps allow finest adaptation to measu-             · Input adapter for LEMO, C, UHF matching all kinds of
        ring voltage:                                                           Impulse Voltage Generators of the known manufacturers
    ·    impulse measuring input 2000-1600-1250-1000-800-                 · Uncertainty of 1% (0.7%) for peak and 2% for time para-
        640-500-400-320-250-200-160-125-100-80-64-50-40-32-                     meter
        20-16-12 V                                                        · Noise level of 0.01% and linearity of ± 0,1 LSB are out-
    · direct input 10-8-6.4-5-4-3.2-2.5-2-1.6-1.25-1-0.8-0.64-                  standing values
        0.5-0.4-0.32-0.25-0.2-0.16-0.12-0.1 V                             · Complete Type Test according to IEC 61083 for all TR-
    · double overload of inputs guaranted without saturation                    AS digital recorder available since 1993
        effect e.g. at unexpected high impulse current amplitudes         · Works Calibration Certificate or DKD Calibration Certi-
    · Long-term stable scale factors of all amplifier stages                    ficate with traceability to National Standards at PTB
        guaranting stable calibration results for many years                    Braunschweig

3   DR. STRAUSS SYSTEM-ELEKTRONIK GMBH             Phone +49 951-43063         INFO www.strauss.de
    D-96163 Gundelsheim/Bamberg                    Fax +49 951-43858           email dr.strauss@strauss.de
                                                                                                               TRAS F2-E 23/01/2009
   Digital Impulse Voltage Measuring Systems                                                          DR. STRAUSS
    TR-AS® 60-10-12 / 100-10-12 / 200-12-14 / 400-12                                                         Impulse Measurement
                                                                                                             Calibration - Diagnosis
  Remote Control Digital Recorder TR-AS RC                                                                          www.strauss.de

The TR-AS RC digital recorder are designed for recording task only. The WinTR-AS software installed on
the external control computer overtakes all control functions of the test procedure via the LAN with:
Setting and arming the TR-AS RC, transfer of the raw data after recording, evaluation and display of sha-
pes, saving the records in the database, generating the test record and printing to any network printer.

                                                                                             TR-AS RC Remote Control Housing
                                                                                             for connection via LAN (green) to the host
                                                                                             computer (PC or Laptop)
                                                                                             Measuring rack mount with 1 to 4 channels
                                                                                             with brackets for building into any 19“ mea-
                                                                                             suring rack or for using on the desk
                                                                                             Direct input 100 mV to 10 V
                                                                                             Measuring Input 12 V to 2000 V
                                                                                             suitable for i.v. tests and calibrations in the
                                                                                             test field and on-site
                                                                                             Dimensions: approx. 50x55x20 cm (BxDxH)
                                                                                             Weight: approx. 16 kg
TR-AS RC with 1 to 4 measuring channels                     Control Computer - Laptop PC
located closed to the test field                                   inside the control room

                                                                           Working Desk with Measuring Rack MIRA 12
                                                                           for installation of 19” measuring rack mount, for reducing of
                                                                           electromagnetic interferences into the neccesary connection
                                                                           cables and disturbances caused hereby, with complete as-
                                                                           sembly of the offered components, with additional mains filter,
                                                                           approx. dimensions: Table 160 x 80 x 75 cm, MIRA 55 x 60 x
                                                                           70 cm (bxdxh)
                                                                           Industrial PC Control Computer
                                                                            19“ TFT display, Color Laserprinter, Keyboard and Mouse,
                                                                           connected to the TR-AS digital recorder via glassfibre LAN
                                                                           TR-AS RC Remote Control Housing
                                                                           Measuring rack mount with 1 to 4 channels
                                                                           with brackets for building into any 19“ measuring rack or for
                                                                           using on the desk
                                                                           Direct input 100 mV to 10 V
            Input Connection Unit                                          Measuring Input 12 V to 2000 V
            For easy connection of measuring cables without or             for connection via LAN to the host computer (PC or Laptop)
            with Terminating Resisstor for current measurements

This new designed measuring technique of network controlled digital recorders gives the possibility for applications were mea-
suring channels are distributed in large test fields, in control rooms on-site or anywhere around the world via Internet.
The following example show how to reduce earthing problems in a very large transformer testfield

                                            The left picture show the typical arrangement
                                            of the voltage and current measuring circuit
                                            with a measuring system TR-AS or TR-AS RC
                                            for voltage and current with the known
                                            Earthing Problem:
                                            I.V. Generator, chopping gap and i.v. divider
                                            have with respect to the Test Object a diffe-
                                            rent ground potential. During the impulse test
                                            ground currents are flowing over the coaxial
                                            shield of the measuring lines which cause
                                            distortions in voltage and current lapse.
                                            The right picture show the suggested arrange-
                                            ment with the solved earthing problems u-
                                            sing two separate remote controlled TR-AS
                                            RC digital recorder for voltage and current
                                            measurement.
                                            Both digital recorders are controlled from the
                                            control computer with installed WinTR-AS
                                            software which joins the records of voltage
                                            and current to one common record.


DR. STRAUSS SYSTEM-ELEKTRONIK GMBH             Phone +49 951-43063      INFO www.strauss.de                                                    4
D-96163 Gundelsheim/Bamberg                    Fax +49 951-43858        email dr.strauss@strauss.de
                                                                                                          TRAS F2-E 23/01/2009
    Technical Data of Digital Recorder                                                                              DR. STRAUSS
    TR-AS 60-8-10-12 / 100-8-10-12 / 200-12-14 / 400-12                                                                    Impulse Measurement
                                                                                                                           Calibration - Diagnosis
                                                                                                                                  www.strauss.de

    Digital Recorder                         100 -8 1)            100 -10 1)        100/200 -12               400 -12 3)             200 -14
    Rated resolution of output data (Bit /
                                             8 / 0.4              10 / 0.1          12 / 0.025                12 / 0.025             14 / 0.006
    %)
    Static integral non-linearity (%)        0.5                  0.25              0.2                       0.2                    0.1
    Static differential non-linearity        0.8                  0.6               0.3                       0.3                    0.3
    Dynamic differential non-linearity       0.8                  0.8               0.8                       0.8                    0.8 2)
                                                                                              1)
    Sampling rate selectable                             2.5 kHz - 25 / 60 / 100 / 200 MS/s                   2.5 kHz-400 MS/s       2.5 kHz-200 MS/s
    Sampling interval uncertainty                                                             0.1 ns
    Non-linearity of Quarz Time Base                                                          0.01%
    Record Length (standard/optional)                                              65536 / 262144 / 512K / 1M
    No. of Timebase                                                                       2 to 8 selectable
    Timebase Recording Mode                                                           A-B-C-...H-Sequence
    Input Stage
    No. Measuring Channels                   1 .. 4                            1) 100 MS/s systems available also with 60 and 25 MS/s max. sampling rate
                                                                               2) referenced to 12 Bit (according to IEC 1083-1)
    Measuring input, single ended            N-type / LEMO optional            3) 400 MS/s with terminated input only
    Measuring range for impulse              12 - 2000 V
    Bandwidth analogue (-3dB)                DC - 50 MHz (70 opt.)
    Risetime                                 7 ns (5 ns opt.)
    Input test voltage 0.1/2000 us           7 kV                              Control and Evaluating System
    Input impedance                          1 MOhm / 30 pF                    Personal Computer state of the art, e.g. 2 GHz, RAM 256
    Direct measuring input                   65 mV - 10 V, BNC                 MByte, Harddisk 80 GByte, Diskdrive 3,5", CD/DVD-RW,
    Bandwidth analogue (-3dB)                DC - 70 MHz                       Color-Laserprinter, Streamer, Glassfibre-Netconnection,...
    Risetime                                 5 ns                              Power: Voltage 230 V +10%/-20%, (optional 100/115 V),
    Input impedance                          1 MOhm / 30 pF                    Frequency 50-60 Hz, Power 400 VA
    Input Settings                           Factor 1.2                        Environmental: Ambient Temp +5...+40°C, Humidity
    automatically controled                  23 Stages                         0...90%, non condensating
    Internal Noise Level                     < 0.1%                            Technical data and design subject to change without notice.
    Interferences                            < 0.1%                            Alternative design on request.
    Record Interval
    at sampling rate 200 MHz                 640 µs / 1.25 .. 6 ms             Application
    at sampling rate 100 MHz                 640 µs / 2.5 .. 12 ms
    at sampling rate 5 MHz                   12.5 ms / 50 .. 200 ms
                                                                               Approved and reference measuring systems
                                                                               in high-voltage and high-power tests
    Trigger                                                                    precise steep impulse measurement
    channels single, OR-connected            yes
    internal level                           pos. and neg. level               simultan multichannel systems
    internal dynamic (deviation)             pos. and neg. dU/dt               dynamic tests
    external                                 5 - 200 V, BNC
                                                                               fourier-analyses
    Selftest and Calibration check           memory, scale factor and
                                             risetime
                                                                               quality control ..

    Limits on overall errors                 according to all applicable       DKD-Calibration
                                             Standards (IEC 1083, IEC
                                             60, IEEE 1122, IEEE 4, ... )      The measuring systems can be calibrated in our DKD Ca-
    Impulse scale factor                                                       libration Laboratory accreditated by the PTB. The Calibration
    constancy in time interval 0.25-1.0 µs                                     Laboratory issues DKD-Calibration Certificates which docu-
                                             ≤ 1%
    and 0.42 µs upto >20 ms                                                    ments the traceability to National Standards.
    uncertainty                              < 0.5%
                                                                               Type Test Report TR-AS 100-10
    lightning and switching i.v., full and
    standard chopped, impulse current
                                                                               Since 01.08.1993 a complete type test report according to
    peak value                               1% (0.7% optional)                IEC 1083-1 is available for the digital impulse voltage mea-
    time parameter                           2%                                suring system TR-AS 100-10 which is designed as an appro-
                                                                               ved, reference or reference standard measuring system.
    front chopped voltage 1.2/50 µs
    peak value, Tc=0.5µs                     1.5% (1% optional)                Type Test Report TR-AS 200-14
    time-to-chopping, Tc=0.5µs                3% (2% optional)                 The new family with TR-AS 100-12 to TR-AS 200-14 conse-
                                                                               quently continue developed show improved performance.
    Evaluation                               WinTRAS - Software                The excellent overall performance makes them to the finest
    shape, accuracy:                         according to IEC-61083-2
                                                                               systems available today for comparative measurements du-
    automatic meancurve calculation          ON/OFF selectable
                                                                               ring transformer tests.
    manual evaluation                        ON/OFF selectable

    Calibration Interval                     every 2 to 4 years
                                                                               A complete family of digital recorders!
                                             recommended

5   DR. STRAUSS SYSTEM-ELEKTRONIK GMBH                 Phone +49 951-43063       INFO www.strauss.de
    D-96163 Gundelsheim/Bamberg                        Fax +49 951-43858         email dr.strauss@strauss.de
                                                                                                                      TRAS F2-E 23/01/2009
           Multichannel Transient Recorder                                                               DR. STRAUSS
                             Measuring Systems                                                              Impulse Measurement
                                                                                                            Calibration - Diagnosis
               TR-AS 10-12 / 100-10 / 100-12 / 200-12                                                              www.strauss.de


  10 / 25 / 40 / 60 / 100 MS/s sampling rate and 12 Bit Resolution

                                                                         Desktop-Housing DERA 6
                                                                         Measuring rack mount with
                                                                         10.4” or 12” TFT -Colordisplay
                                                                         PC 1,2 GHz, 256 MB RAM, WindowsXP®, 30 GB
                                                                         harddisc, CD-RW etc.
                                                                         Keyboard with trackball in drawer
                                                                         suitable shielding for high EMC

                                                                         Dimensions: approx. 55x55x40 cm (BxDxH)
                                                                         Weight: approx. 25 kg
                                                                         Environmental: Ambient Temp +5...+40°C, Humidity
                                                                         10...90%, non condensating

                                                                         Rear view: TR-AS 10-12/8-32
                                                                         8 analogue channels with BNC-input
                                                                         optional: Isolating amplifier with 2 or 7kV isolation a.c.
                                                                         32 digital channels with 2 kV optical isolation, multi-
                                                                         contact connectors
                                                                         Connection for Calibrator control, Printer, COM, Net-
                                                                         work, external SVGA-monitor
                                                                         Mains filter, efficient Fan
                                                                         Technical data and design subject to change without
                                                                         notice. Alternative design on request.



                                                                         Applications:
Digital Recorder                     TR-AS 10/25/40-12                   Complexe and precise impulse measuring
Analog-Digital-Converter                                                 with simultan multi-channel system
Resolution                           12 Bit / 0.025 %
                                                                         High-power testfield
Linearity                            1/2 (2) LSB
Filter-Frequency                     5 MHz / 500 / 50 kHz                Switchgear test
Sampling Rate (simultan, realtime)   0.5 kS/s - 10 MS/s
                                                                         Monitoring recorder
Sampling Rate (simultan, realtime)   25 / 40 MS/s optional
No. of Timebase                      2 to 8 selectable                   Protection relay test
Timebase Recording Mode              A-B-C-...H-Sequence                 Quality control
Record Length (standard/optional)    64K / 256K / 1M Data
                                                                         Measurements in developement and
Analogue Input                       1-8                                 testfield, ...
Measuring range via attenuator
                                     10 - 1600 V
160:1
Bandwidth
Input impedance
                                     d.c. - 5 MHz
                                     1 MOhm / 30 pF
                                                                         DKD-Calibration
Direct input                         100 mV - 10 V, BNC
                                                                         The measuring systems can be calibrated in our DKD
Input setting factor 0.8-sequence    0.1-0.125-...-6.4-8-10V
                                                                         Calibration Laboratory accreditated by the PTB. The
automatically controlled             23 Stages
                                                                         Calibration Laboratory issues DKD-Calibration Certifi-
Digital Input                        4 - 32
                                                                         cates which documents the traceability to National
Input range LOW / HIGH               0 V / 5 to 250 V                    Standards.

Trigger                              pre-/posttrigger
channels single, OR-connected        yes
internal level                       pos. and neg. level
internal dynamic (deviation)         pos. and neg. dU/dt
external                             5 - 250 V, BNC

DR. STRAUSS SYSTEM-ELEKTRONIK GMBH                 Phone +49 951-43063     INFO www.strauss.de                                        6
D-96163 Gundelsheim/Bamberg                        Fax +49 951-43858       email dr.strauss@strauss.de
                                                                                                          TRAS F2-E 23/01/2009
           Impulse Measurement Components                                                                         DR. STRAUSS
            Tubular Shunts - Isolation Amplifier                                                                         Impulse Measurement
                                                                                                                         Calibration - Diagnosis
                                                                                                                                www.strauss.de


                          Tubular Impulse Current Measuring Shunt ICMS
                                       The Impulse Current Measuring Shunts ICMS are new designed tubular shunt types with best performance
                                       response behaviour. They show no overshoot or oscillations and need no compensation box to optimize the
                                       transient behaviour as known from e.g. cage shunts.
                                    Tubular shunts type ICMS are therefore ideal for current measurements during transformer tests. The resis-
                                    tance material of the inner tube show high energy absorption capability and very low temperature coefficient
                                    and therefore negligible non-linearity effect for impulses of different magnitude. This is very important for
    comparison of shapes e.g. of 50% and 100% test level during transformer tests.
    The Impulse Current Measuring Shunts ICMS are designed for measurements of impulse currents with shape 8/20 µs according to IEC 60060-
    1. For impulse currents with any shape the maximal action integral or the maximal voltage drop must not be exceeded.

     Typ                                  Type                                              ICMS 20        ICMS 10           ICMS 2.5        ICMS 1
     Nenn-Impulsstrom 8/20                rated Impulse current 8/20                   A      20 000         10 000               2 500       1 000
     Widerstandswert ± 10%                Resistance ± 10%                             W       0.025              0.05              0.2         0.5
                                                                                       V/
     Empfindlichkeit                      Sensitivity                                             25               50              200         500
                                                                                       kA
     Arbeitsbereich mit TR-AS® digi-      Working Area with TR-AS® digi-
                                                                                       A       ≥ 200          ≥ 100                ≥ 25        ≥ 10
     tal recorder                         tal recorder
     Anstiegszeit Tr                      Rise time Tr                                 ns        <30              <10              <10         <10
     Antwortzeit Ta                       Response time Ta                             ns        <20              <10              <10         <10
     Max. Energieintegral ∫i².dt
     Minimale Pausezeit                   max. Action integral ∫i².dt
                                          repetitition rate                        A²s
                                                                                     s        18 000          5 000 60             280           50
     Spannungsabfall max.                 Voltage drop max.                            V                             1000
     Temperaturkoeffizient                temperature coefficient                 1/K                              <100·10-6
     Messanschluß                         Measuring socket                                                          N-type
     Abmessungen ca.                      Dimensions approx.                       mm                            330 x 250 x 50
     Anschluß                             Connection                               mm                               12.5 Ø

    The characteristic impedance of the measuring cable connected to the Impulse Current Measuring Resistor ICMS is recommended to 75 W.
    To avoid reflections on the measuring cable a terminating resistor TERM 75 matching the impedance Z of the measuring cable must be con-
    nected to the far end at the input of the measuring system. Triaxial cable only is recommended.
    The influence of the terminating resistor with value Z connected in parallel to the measuring shunt Rm with respect to the resulting resistance
    value R is negligible, it can be calculated to R = Rm· Z/(Rm+Z).



                  Isolation Amplifier Systems ISO-VER 12 / 2.2
    for applications in the high power test field together with TR-AS multichannel transient recorders

                                                                                                       A floating current input from mA to
                                                             ISO-VER 2.2                               kA can be realized using a sui-
                                                             2 or 4 kv a.c.isolation
                                                                                                       table measuring shunt at the in-
                                                             1 to 8 channels
                                                                                                       put.
                                                             input 1 to 1000 V
                                                             1 MOhm / 30 pF
                                                             output ±1 V
                                                             bandwidth 2 MHz
                                                             accuracy 0.2%



                                                             On-Site Switchgear Test System
                                                             Multichannel-System based on TR-AS 10-12 with 3 analogue and 24 digital inputs for
                                                             measurement of make and break times.
                                                             The picture shows revision checks of elder 110 kV compressed air switchgear. The
                                                             measuring system is placed inside a transportation car and connected to the
                                                             interrupter under test which must be switched free from h.v. during the measurement.
                                                             The triggering of the system follows automatically with help of the releasing coil
                                                             current, measuring data will be evaluated by hand or automatically and then stored on
                                                             to harddisk to generate a test record.


7   DR. STRAUSS SYSTEM-ELEKTRONIK GMBH                   Phone +49 951-43063       INFO www.strauss.de
    D-96163 Gundelsheim/Bamberg                          Fax +49 951-43858         email dr.strauss@strauss.de
                                                                                                                     TRAS F2-E 23/01/2009
                                                                                                            DR. STRAUSS
             VFT Measuring System for GIS                                                                        Impulse Measurement
        Remote Control Digital Recorder TR-AS RC                                                                 Calibration - Diagnosis
                                                                                                                        www.strauss.de




VFT-Measuring System TR-AS RC for VFT              The measuring line is connected to the 250 V
Digital Recorder with     200 MS/s sampling        input of the digital recorder which includes an
rate and 12 Bit resolution, remote controled by    input divider with ratio 25:1.
external Laptop Computer                           The 10 V output of the divider is connected
The VFT-Measuring System TR-AS RC for              with a BNC-bridge to the 10 V input of the
VFT is special designed for high bandwidth         programmable measuring amplifier channel 1
and allows measurements of very fast tran-         of the digital recorder.
sients (VFT) in a frequency range from power       Software Control
frequency up to 100 MHz directly with help of      The VFT-Measuring System is remote control-
capacitive sensors, e.g. PD-sensors installed      led via the local area network (LAN) by an
in Gas - Insulated Switchgear (GIS).               external Laptop Computer with special remote
Additionally measurement of lightning and          control software.
switching impulse voltages as also A.C. mea-       The VFT-Measuring System includes an In-
surements on the finally installed GIS can be      dustry computer with harddisc and LAN-
performed.                                         interface but without display and keyboard.
                                                                                                     Basic Connections
Principle of measuring system                      The WinTRAS-Software for control and mea-         Gas - Insulated Switchgear GIS
The measuring system consists of an electri-       surement is installed on the harddisc of the      Flange with PD-sensor inbuilt
cal field sensor with capacitance C1, a directly   VFT-Measuring System and can be transpa-          with N-Connector
coupled low voltage capacitor and a coaxial        rently operated with help of the remote control   Low-voltage capacitor
measuring line with capacitance C2 which           software on the Laptop Computer.                  Measuring cable to TR-AS RC
forms together a capacitive voltage divider                                                          Short-Circuit-Connector on chain
with a ratio of approximately C2:C1.




Components of the VFT-Measuring System TR-AS RC:                          Connection Box with power cord (in the middle)
Low Voltage Capacitor (blue) with N-Connectors                            LAN-connection cable to PC (0.5 m length)
Coaxial Connection cable with N-connectors (grey)                         Laptop Computer (PC) with power supply (black) and special short
Digital Recorder TR-AS RC with power cord (left side)                     power cord (0.3 m length)
Glassfiber-Connection Cable (orange)

DR. STRAUSS SYSTEM-ELEKTRONIK GMBH                  Phone +49 951-43063       INFO www.strauss.de                                            8
D-96163 Gundelsheim/Bamberg                         Fax +49 951-43858         email dr.strauss@strauss.de
                                                                                                              TRAS F2-E 23/01/2009
                                                                                                             DR. STRAUSS
          VFT Measuring System for GIS                                                                             Impulse Measurement
                                                                                                                   Calibration - Diagnosis
                                                                                                                          www.strauss.de


    Technical Data

    Low-Voltage Capacitor                                         N-Connectors

    rated Voltage                                                 250 V

    Measuring Cable                                               Triaxial 75 Ohm with N-Connectors, 10 m length

    Rated Capacitance C2                                          13 000 pF ± 15%

    Digital Recorder                                              TR-AS 200 - 12
    Rated resolution of output data (Bit / %)                     12 / 0.025
    Sampling rate selectable                                      2.5 kHz-200 MS/s
    Sampling interval uncertainty                                 0.2 ns
    Non-linearity of Quarz Time Base                              0.01%
    Record Length                                                 256K Data
    Input Stage
    No. Measuring Channels                                        1
    Measuring input, single ended                                 250 V input divider 25:1, N-connector
    Measuring range                                               5 V - 250 V
    Input impedance                                               20 MOhm / 30 pF
    Input test voltage 0.1/2000 us                                1000 V
    Measuring input, single ended                                 10 V input, BNC-connector
    Input impedance                                               1 MOhm / 10 pF
    Measuring frequency range for VFT                             10 Hz - 100 MHz
    Input Setting Sequence                                        Factor 1.2
    automatically controlled                                      16 Stages
    Impulse scale factor
    constancy 0,1 µs to >> 1 s                                    1%
    long term stability (one year)                                0.5%
    Limits on overall errors                                      according to all applicable Standards (IEC 61083, IEC 60060, IEEE 1122,
                                                                  IEEE 4, ... )
    Calibration Interval                                          every 2 to 4 years recommended
    Control Computer                                              Industrial type, CPU 1 GHz
    RAM                                                           256 MByte
    Harddisk                                                      80 GByte
    Netconnection                                                 100 M glassfibre SC
    Desktop-Housing                                               TRAS-RC 64-4HE
    Dimensions: (BxDxH)                                           approx. 37x47x24 cm
    Weight:                                                       approx. 12 kg
                                                                  For connection of TRAS-RC and external Laptop PC with following compo-
    Connection box
                                                                  nents:
    Media Converter                                               TP – glassfibre SC, 100M, with power supply
    Power connections                                             To mains and Laptop PC

    Power Requirements

    Voltage                                                       115 –230 V
    Frequency                                                     50-60 Hz
    Power                                                         200 VA

    Environmental:

    Ambient Temp                                                  +5...+40°C
    Humidity                                                      10...90%, non condensating

    Laptop PC                                                     External

    Specification                                                 According to separate Operation Manuals

    Technical data and design subject to change without notice.
    Alternative design on request.

9   DR. STRAUSS SYSTEM-ELEKTRONIK GMBH                Phone +49 951-43063      INFO www.strauss.de
    D-96163 Gundelsheim/Bamberg                       Fax +49 951-43858        email dr.strauss@strauss.de
                                                                                                                TRAS F2-E 23/01/2009
 TR-AS FRA                          High Resolution                                                                  DR. STRAUSS
 Frequency Response Analysis (FRA) System                                                                                   Impulse Measurement
                                                                                                                            Calibration - Diagnosis
   for Power Transformer Diagnosis and Network Analysis                                                                            www.strauss.de

For measurement of
Short-Circuit Admittance Function                                                                                         Remote controlled
Open-Circuit Voltage Transfer Function                                                                                     High Resolution
D.C. and 50/60 Hz impedance                                                                                                     TR-AS
                                                                                                                          Transient Recorder

                                                                                                                         Impulse Voltage Gene-
                                                                                                                                rator for
                                                                                                                            STEP Excitation

                                                                                                                          Connection Unit for
                                                                                                                          Voltage, Current and
                                                                                                                           transferred Voltage

                                                                                                                         Easy 2-pole connecti-
                                                                                                                          on for reproducible
                                                                                                                            On-Site-Tests

                                                                                                      1.1E+3
The Frequency Response Analysis (FRA) on          cible measurements can be expected.                                          HV-w, all-GND
                                                                                                      1.1E+2
power transformers is used for diagnosis at       The output voltage and the respective cur-          1.1E+1
works, after putting into operation and for       rent are recorded with help of a special de-        1.1E+0
maintenance on site. The frequency-               signed transient recorder TR-AS with a ba-          1.1E-1
dependent admittance is determined and re-        sic resolution of 12 Bit at 10 or 40 MS/s ma-       1.1E-2
corded as fingerprint.                            ximum sampling rate, an adapted bandwidth           1.1E-3
The FRA taken before and after a transport        of 5 MHz and minimized noise of 0.013%              1.1E-4
should show no differences, otherwise a mo-       (type test).                                        1.1E-5
vement e.g. of a winding must be assumed.         The basic resolution of 12 Bit is improoved          10Hz      100Hz    1.0KHz      10KHz    100KHz
Because small movements results in very           by a repetitive averaging technique accumu-
small deviations in the FRA lapse, the measu-     lating a number of voltage and current re-
                                                                                                      0.80*pi


rement method must be very stable and sen-        cords phase-equivalent in the time domain.          0.40*pi
sitive.
                                                  Depending on the number of accumulations,
The application of the step response method       resulting resolutions up to 32 Bit are rea-
gives a complete measuring result after apply-    ched with a significant reduced noise.
ing the STEP voltage and calculating the fre-                                                         -0.40*pi


quency-dependent admittance with help of          For e.g. 16 accumulations 16 Bit resolution
the frequency spectra of voltage and current      and for 1024 accumulations 26 Bit resoluti-         -0.80*pi


lapse determined by the fast Fourier transform    on are resulting.                                    10Hz      100Hz    1.0KHz      10KHz    100KHz


(FFT).
                                                                                                      FRA on the windings u, v, w against N
A minimum of 12 Bit resolution and 64K data
for FFT is required, with 256K or 1M data fi-
nest frequency resolution is resulting.                                                               Perfect EMI-reduction
                                                   single shot with 12 Bit resoluti-
                                                                                                      Because the instant of the step voltage exci-
Testing Method                                                                                        tation is not correlated to external electro-
The Frequency Response Test System was                                                                magnetic fields, e.g. caused by power trans-
designed for direct measurement of the fre-                                                           formers, switchgear or radio stations, their
quency behaviour of transformer windings                                                              influence is reduced corresponding to the
with the step voltage method.                                                                         number of accumulations applied. The opti-
The test object is connected as a 2-pole to the                                                       mal No. of accumulations as the best
step voltage impulse generator RIG with 350                                                           compromise between test time and
V peak voltage and sufficient energy without                        16 accumulations with 16          Selecting 16 accumulations is a good
additional measuring lines and shunts.                              Bit resulting resolution          compromise, testing time for each winding
Voltage and current are picked directly at the                                                        is few Minutes, distortions are reduced 16
step voltage generators output and therefore                                                          times and resolution is increased to 16 Bit
not subject of variation of external connecti-                                                        corresponding to 0,0015% accuracy of digi-
ons.                                                                                                  tal data used for FFT calculations.
                                                  current lapse in the time domaine
 This is an important advantage especially for                                                        This aspect allows to get best results
on-site tests after shipping or for maintenan-
                                                  400x zoomed up to 0,025% per                        also during on-site FRA-measurements
ce, because of the easy connection reprodu-       div. vertically                                     in substations etc.


DR. STRAUSS SYSTEM-ELEKTRONIK GMBH                 Phone +49 951-43063            INFO www.strauss.de                                                   10
D-96163 Gundelsheim/Bamberg                        Fax +49 951-43858              email dr.strauss@strauss.de
                                                                                                                         TRAS F2-E 23/01/2009
     TR-AS FRA                            High Resolution                                                     DR. STRAUSS
      Frequency Response Analysis (FRA) System                                                                       Impulse Measurement
                                                                                                                     Calibration - Diagnosis
        for Power Transformer Diagnosis and Network Analysis                                                                www.strauss.de

     Technical Data

     FRA-Analysis System                  TR-AS-FRA                                                                        short circuit test:
                                                                                                                           33 S / 30 mOhm
     frequency range                      D.C. to 1 MHz / 10 MHz
     frequency resolution                 2,4 Hz or 24 Hz selectable
     FFT filter bandwidth                 1 Hz or 10 Hz
     frequency accuracy                   0.01%
     discrete frequency points            512 K (524,288)                             1175 MVA Short Circuit
     display range                        9 decades / 180 dB                          Transformer
     dynamic range                        150 dB                                      winding 3.1-GND
               admittance range           1 µS ... 33 S
               impedance range            30 mOhm .. 1 MOhm
     dynamic vertical accuracy            1 dB
     vertical resolution                  0.00025 ( -72 dB)                         calibration test:
                                                                                    1 mS / 1 kOhm
        with 16 accumulations to 16 Bit   0.000016 ( -95 dB)
     vertical display                     admittance, impedance
                                          lin, log, dB
     horizontal display                   lin, log                                                                           no load test:
     Digital Recorder                     TR-AS - 12 RC                                                                      1 MOhm || 30 pF
     Rated resolution of output data      12 Bit / 0.025 %
     accumulation range                   14 ... 24 Bit
     Record Length each channel           1M Words (1,048,576)
     Input Stage
     No. Measuring Channels               2
     Measuring input, single ended        BNC / N
     Measuring range for impulse          60mV - 10 V / 10 V - 1600 V     FRA results in double-log display:
     Bandwidth analogue (-3dB)            DC - 5 MHz                      horizontal range 10 Hz .. 10 MHz
     automatically controlled             22 Stages                       vertical display range 0,1 µS .. 100 S or 10 MΏ .. 10 mΏ in 9 deca-
     Internal Noise Level                 < 0.02%                         des corresponding to 180 dB
     Impulse scale factor
     constancy 0,5 µs to >> 1 s           1%                              Following tests show the performance of the FRA-System:
     long term stability (one year)       0.5%                            ·       short circuit test: at d.c., resulting value of 33 S / 30 mOhm
     Calibration Interval                 every 2 to 4 years              ·       no load test: resulting value of 1 MOhm || 30 pF
                                          recommended                             corresponding to the impedance of the 160:1 input divider for
     Unit-Step-Voltage-Generator                                                  voltage measurement
     Charge voltage       inbuilt h.v. supply      350 V                  ·       calibration test: inbuilt calibration resistance 1 mS / 1 kOhm
     Charge capacitor     charge-capacity          5.3 µF                 ·       test on a 1175 MVA Short Circuit Transformer, secondary
     Switching-device     Electronically                                          winding 3.1 - GND, all other terminals on GND
                          Risetime (no load)       < 10 ns (10/90%)       ·       the blue limits show the possible working area of the FRA-
     releasing            automatically controlled , manual                       System from d.c. up to 10 MHz and 30 mΏ (33 S) up to 1 MΏ
     impulse output                                350 V, positiv                 ( 1 µS) corresponding to 150 dB vertical dynamic range
     output peak power                             250 W peak             The shapes of the no load test and the short circuit test performed at
     Desktop-Housing                      19“                             the open respectively short-circuit output terminal of the FRA-System
                                                                          show approximately the limits for determining admittances respective-
     Dimensions: (BxDxH)                  approx. 45x45x18 cm             ly impedances of networks, e. g. power transformers, in the frequency
     Weight:                              approx. 12 kg
     Power Requirements
                                                                          Technical data and design subject to change without notice. Alternati-
     Voltage                              230 (115) V +10%/-20%
                                                                          ve design on request.
     Frequency                            50-60 Hz
     Power                                200 VA                          DKD-Calibration
     Environmental:                                                       The measuring systems can be calibrated in our DKD Calibration La-
     Ambient Temp                         +5...+40°C                      boratory accreditated by the PTB. The Calibration Laboratory issues
     Humidity                             ...95%, non condensating        DKD-Calibration Certificates which documents the traceability to Nati-
                                                                          onal Standards.
     Remote Control Computer              LAPTOP PC
     CPU                                  Pentium, min. 1 GHz             Remarks:
     RAM                                  256 MByte                       The Measuring System is not designed and applicable for high-
     Harddisk                             40 GByte                        voltage tests.
     Diskdrive                            3,5"
     CD-RW                                yes                             For more information please refere to our Product Specification and to
     TFT-Color-Display                    14" (15“)                       our website www.strauss.de/products/
     Netconnection                        LAN or WLAN




11   DR. STRAUSS SYSTEM-ELEKTRONIK GMBH                  Phone +49 951-43063   INFO www.strauss.de
     D-96163 Gundelsheim/Bamberg                         Fax +49 951-43858     email dr.strauss@strauss.de
                                                                                                                  TRAS F2-E 23/01/2009
   Arrester Test System TR-AS 60/100-10                                                                             DR. STRAUSS
                                                                                                                          Impulse Measurement
                                       with 4 channels                                                                    Calibration - Diagnosis
                                                                                                                                 www.strauss.de

                                                    The first instant of the list which is found is       W[VAs] =        INTEGRAL(CH5,CH2_tmin,
                                                    set the tmax time                                     CH2_tmax)
                                                    If search automatic integration interval (tmin
                                                    to tmax) is not selected it is possible to se-
                                                    lect different evaluation instants.




Measuring and Evaluating System
TR-AS 60-10 Type DERA 6
The system with 4 simultane channels is
designed with digital recorder compo-
nents TR-AS 60-10 or optional TR-AS                                                                       Operating Duty Tests
100-10/12 as follows:
Ch 1 impulse current recorded with 60
                                                    Input of Evaluation rules with help of the
MS/s up to 1000 ms
Ch 2 residual voltage recorded with 60              MAKRO Formula Editor
MS/s up to 1000 ms
Ch 3 arrester voltage recorded with 2.5
                                                    Energy calculation without integ-
kS/s up to 20 sec.
                                                    ration
Ch 4 arrester current recorded with 2.5             WinTRAS evaluation settings:
kS/s up to 20 sec.
                                                    Ch1 [u(t)] evaluated with PK = peak value
The timebase of the channels can be set             Ch2 [i(t)] evaluated with REC = rectangular,
individually while the trigger event is si-         automatic calculation from tmin to tmax
multan for all channels.                            WinTRAS formula without integral:                     Ch 1 residual voltage           0 to 20 µs
For permanent watching of a.c. voltage              W = CH1_Up · CH2_Ip · CH2_Td                          Ch 2 impulse current            0 to 20 µs
and current during duty tests an additio-
                                                    or                                                    Ch 3 a.c. voltage               0 to 20 s
nal oscilloscope is inbuilt showing the
actual values rms and peak/√2 of Ch 3               W = CH1_Up · CH2_Ip · (CH2_tmax -
                                                    CH2_tmin)
and Ch 4 independent of their recording
status.


Rectangular evaluation
TdThe time duration where the amplitude of
the Impulse is greater than 90% of its peak
value.
Tt      The time duration where the amplitu-
de of the Impulse is greater than 10% of its
peak value.
Tz        Time from T0 (virtual time zero) to the
first crossing with zero line                       Energy calculation with integrati-                    Ch 1      impulse current    0 to 50 µs
Ip, Up Peak value of current, voltage               on
Tmin    begin of the integral interval
                                                                                                          Ch 2      residual voltage   0 to 50 µs
                                                    According to IEC 60099-4
Tmax    end of the integral interval                W = Ures(Ul - Ures) · 1/Z · T = U · I · T             Ch 2*     residual voltage   0 to 250 µs
If search automatic integration interval (tmin to   => W = tmin∫tmax u(t) · i(t) dt                       Ch 3      a.c. voltage       0 to 12 s
tmax) is selected the software searched the         tmin to tmax is the time in which the ampli-          Ch 4      a.c. current       0 to 12 s
tmax instant.                                       tude is greater then 0% of the peak value.            Display application of a.c. voltage 100 ms
The software tries to find following time in-       If found automatic integration interval is on,        behind impulse current in Ch 2*.
stants:                                             the software tries to found the impulse end.          Display of reduction of a.c. voltagt resp.
Tz      time-to-zero, first crossing with 0%        WinTRAS evaluation settings:                          current after 10 seconds in Ch 3 and 4.
level
                                                    Ch1 [u(t)] evaluated with PK = peak value             Digital Voltmeter inbuilt for a.c. measure-
T10     crossing with 10% level, Tt
                                                    Ch2 [i(t)] evaluated with REC = rectangular,
T30     crossing with 30% level, Tie30              automatic calculation from tmin to tmax
T50     crossing with 50% level, T2                 Ch5 = Ch1[u(t)] · Ch2[i(t)]
T70     crossing with 70% level, Tie70              WinTRAS formula:


DR. STRAUSS SYSTEM-ELEKTRONIK GMBH                   Phone +49 951-43063              INFO www.strauss.de                                               12
D-96163 Gundelsheim/Bamberg                          Fax +49 951-43858                email dr.strauss@strauss.de
                                                                                                                       TRAS F2-E 23/01/2009
                                                                                                                DR. STRAUSS
          WinTR-AS for Windows 2000/XP®                                                                                 Impulse Measurement
                                                                                                                        Calibration - Diagnosis
                                                                                                                               www.strauss.de

     WinTRAS is the result of a longstan-            face. All saved data is managed with
                                                                                                       features
     ding know-how of software develop-              an integrated dBase®-compatible
     ment for the use of digital recorder            database. Because of this, the user               Þ        32-Bit software
     measuring sytems and the possibili-             has multiple opportunities of further             Þ        standardized intuitive user interface
     ties, provided by a modern operating            data processing. It is for example                Þ        contextsensitive help system
                                                                                                       Þ        Multi-Threading (=parallel running
     system like Windows 2000/ NT®.                  possible to generate a protocol using                      processes within the application)
     Now you are able to aquire, evaluate            the WinTRAS functions or to do this               Þ        integrated database (dBase® com-
     and process measured data within a              with another application like Micro-                       patible)
     standardized userfriendly user inter-           soft Excel®.                                      Þ        Impulse evaluation acc. to IEC 60
                                                                                                                and 1083 and evaluation of mathe-
                                                                                                                matical operation results of different
                                                                                                                channels
                                                                                                       Þ        Formula-parser for generation of
                                                                                                                synthetic shapes
                                                                                                       Þ        mathematical operation
                                                                                                       Þ        Macro-language for own evaluation
                                                                                                                procedures
                                                                                                       Þ        automatic test-sequences
                                                                                                                (configurable)
                                                                                                       Þ        remote control with OLE-automation
                                                                                                       Þ        remote acces via modem
                                                                                                       Þ        configurable user interface
                                                                                                       Þ        multilingual user texts (online swit-
                                                                                                                chable)
                                                                                                       Þ        multilingual protocol-output with pre-
                                                                                                                view
                                                                                                       Þ        Import of ASCII- and IEC-TDG-
                                                                                                                curves
                                                                                                       Þ        possible integration in a network
                                                                                                       Þ        simple data transfer using the clip-
                                                                                                                board of Windows ® (metafile for-
                                                                                                                mat)
                                                                                                       Þ        Support of color prints
                                                                                                       Þ        integrated hardware-diagnostics
                                                                                                       Þ        extensive database backup functi-
                                                                                                                ons


     Database-concept controls all tests performed:
                                                                                                                          Workstation 1
                                                                                                                             e.g. for
     Meas. system 1 - database
                                                                                                                           analysis of
                                                                  complete database                                       test objects
                                                                       with all
                                                                      measured
     Meas. system 2 - database                                           data                                             Workstation 2
                                                                    central access                                          e.g. for
                                                                   provided by net-                                        statistics
     Meas. system n - database                                       work server
                                                                                                                         Workstation n

     intuitive user interface                                                 ·        subordinated windows for the output of wave shapes and
                                                                                       evaluation results which can be arranged any way in the
     The user interface of WinTRAS is conform to the standards of Win-                 main window of the application
     dows 95® and provides all usual controls of a modern windows appli-      ·        intuitive user dialogues for settings, evaluations, database-
     cation:                                                                           and file operations
     ·       Pull-down menu
                                                                              Additional you have the possibility to activate a user menu panel,
     ·      Toolbar for the most important functions with online hints for    controlled by the function keys of the keyboard. This menu provides
            each button                                                       also important functions of the application, similar to the toolbar.
     ·      contextsensitive help system                                      You can change the properties of the user interface using the
     ·      Statusbar for messages                                            “options” menu of the menu bar.


13   DR. STRAUSS SYSTEM-ELEKTRONIK GMBH                 Phone +49 951-43063       INFO www.strauss.de
     D-96163 Gundelsheim/Bamberg                        Fax +49 951-43858         email dr.strauss@strauss.de
                                                                                                                    TRAS F2-E 23/01/2009
                                                                                                                                                      DR. STRAUSS
                 WinTR-AS for Windows 2000/XP®                                                                                                           Impulse Measurement
                                                                                                                                                         Calibration - Diagnosis
                                                                                                                                                                www.strauss.de


                                                                                                                      integrated database
                                                                                                                      All saved records and evaluation results of WinTRAS are
                                                                                                                      managed in a dBase®-compatible integrated database.
                                                                                                                      The data is organized in projects, which are identified by a
                                                                                                                      definitely project number.
                                                                                                                      The database structure offers a lot of advantages regarding
                                                                                                                      data backup and further processing of the data:
                                                                                                                      ·       central backup using a network
                                                                                                                      ·       easy data transfer of large data quantity between dif-
                                                                                                                              ferent measuring systems or workstations using a
                                                                                                                              network
                                                                                                                      ·       easy data access for additional workstations for eva-
                                                                                                                              luation, analysis, documentation etc.


                                                                                                                      easy digital recorder control
                                                                                                                      All necessary settings for the operation of the digital
                                                                                                                      recorder are made by userfriendly dialogue windows.
                                                                                                                      All dialogues show the actual settings in form of tables
                                                                                                                      for better orientation. Each row of a table represents a
                                                                                                                      channel.

                                                                                                                      The preview area on the upper right side shows online
                                                                                                                      the effects of changes of one of the parameters delay,
                                                                                                                      measuring range, offset and trigger.
                                                                                                                      Of course you have the possibility to save all settings.

                                                                                                                      multiple display view options
                                                                                                                      The display view dialogue allows the user to modify
                                                                                                                      the appearance of the curve window. All settings are
                                                                                                                      shown as well in form of a table with the parameters of
                                                                                                                      one channel in a row. If specific channels are not nee-
                                                                                                                      ded, they can be turned off.
                                                                                                                      As only displayed channels are saved to the database
                                                                                                                      if the function “save curves” is activated, this option
                                                                                                                      allows you to reduce the quantity of stored data. Thus
                                                                                                                      all output and save operations work with the principle
                                                                                                                      “what you see is what you get”.
                                                                                                                      The hardcopy function produces a printout of the actu-
                                                                                                                      al displayed screen using the maximum number of

TB 1 = 1 0 0.0 0 M S /s                                                                     N o .: 2


                                                                                                                      Graphic export using the clip-
10 0 %                                                                                      CH1
                                                                                            A u s w .:   LI
                                                                                            U p=         1 3 6 0V
90%                                                                                         T1=          0 .8 8 µ s



                                                                                                                      board of Windows®
                                                                                            T2=          4 8 .9 µ s




70%



                                                                                                                      The export of WinTRAS graphics is a very useful fea-
50%
                                                                                                                      ture if you have to create documentations.
                                                                                                                      The actual content of the curve window and the status
30%
                                                                                                                      window will be transformed in a metafile and this will
                                                                                                                      be finally copied to the clipboard.
                                                                                                                      Please take note that the metafile format offers vec-
10%                                                                                   CH1
                                                                                                                      torgraphic. That means easy positioning and scaling of
0%
                                                                                                                      the graphic in the further processing application.
         0                20µs   40µs   6 0µ s   80µs   100µs   12 0 µ s   1 4 0µ s




 DR. STRAUSS SYSTEM-ELEKTRONIK GMBH                                             Phone +49 951-43063                     INFO www.strauss.de                                            14
 D-96163 Gundelsheim/Bamberg                                                    Fax +49 951-43858                       email dr.strauss@strauss.de
                                                                                                                                                       TRAS F2-E 23/01/2009
                                                                                                            DR. STRAUSS
         WinTR-AS for Windows 2000/XP®                                                                          Impulse Measurement
                                                                                                                Calibration - Diagnosis
                                                                                                                       www.strauss.de


                                                                          automatic evaluation
                                                                          Another indication for the efficiency of WinTRAS is the auto-
                                                                          matic evaluation.
                                                                          The user has the possibility to select an evaluation mode
                                                                          from a predefined set for each channel. This set contains for
                                                                          example impulse evaluations (LI/SI) according to IEC 60
                                                                          and 1083. The user has the choice between manual and au-
                                                                          tomatic evaluation.
                                                                          Additional mathematical operations with channels are allo-
                                                                          wed. Thus this feature is realized with an integrated formula
                                                                          parser, you have also the possibility to create synthetic wave
                                                                          shapes.
                                                                          Please take note that 80 channels are available for evaluati-
                                                                          ons and channel operations.

                                                                          integrated data backup tools
                                                                          WinTRAS provides also extensive tools for comfor-
                                                                          table data backup of complete projects or single mea-
                                                                          sured data.
                                                                          The following functions are available:
                                                                          ·      backup
                                                                          ·      restore
                                                                          ·      delete
                                                                          You are able to determine any lokal drive or any net-
                                                                          work drive as destination for the data backup.
                                                                          Additional every save action of the user will force an
                                                                          automatic data backup of all database tables.


                                                                          automatic protocol generation
                                                                          The following parameters are selectable:

                                                                          ·        protocol language
                                                                          ·        number of graphics per page (1, 2, 4, 8)
                                                                          ·        graphic printout with or without evaluation results

                                                                          If all parameters are selected, a preview of the actual proto-
                                                                          col will be started. The preview provides a visual check of
                                                                          the protocol, before the printjob is started.
                                                                          All graphics are created and printed as vectorgraphic.

                                                                          Furthermore, the user has the possibility to save a comple-
                                                                          ted protocol and reload it later for printing.
     WinTRAS offers an automatic protocol function for the docu-          Finally you are able to implement your own company logo at
     mentation of test results.                                           the protocol header for individual protocol design.
     This operation uses the data of the actual selected project.
     The protocol contents a list with all saved evaluation results of    All Windows® supported printers are of course accepted by
     the project and a number of further pages with graphic prin-         WinTRAS.
     tout.


     additional software packages                                         ·        Trafo-Test with Compare-Function
     We offer further software packages in combination with the           ·        Transfer-Function and Coherence-Function
     WinTRAS main application. This allows you to choose a speci-         ·        Tolerance-Band-Method
     fic software-bundle depending on your measuring task:                ·        Frequency Response Analysis
     ·      Automatic Calibration acc. to IEC 1083                        ·        Tap Change Operation Sequence Test
     ·      Calibration of H.V. dividers acc. to IEC 60                   ·        Quality-Control software


15   DR. STRAUSS SYSTEM-ELEKTRONIK GMBH             Phone +49 951-43063       INFO www.strauss.de
     D-96163 Gundelsheim/Bamberg                    Fax +49 951-43858         email dr.strauss@strauss.de
                                                                                                             TRAS F2-E 23/01/2009
  Makro Editor for automatic evaluation of DR. STRAUSS
                                             Impulse Measurement
       custom-defined expressions            Calibration - Diagnosis
                                                                                                              www.strauss.de

Easy input of formulas and rules for their automatic calculation im-
mediately after each new record, comprising
Peak values of analogue lapses, e.g.Torque Moment, Current, Voltage, ...
Contact Events recorded into Digital Measuring Channels
Energy by Integration of Voltage and Current lapse during arrester tests
Difference shape of individual channels
Arithmetic Operations with two Channels before Evaluation




         OLE / DCOM / ActiveX - Interface WinTRAS
                                                                                For automatic control of recorder
                                                                                functions by custom programs
                                                                                Programming Examples in Delphi /
                                                                                C++
                                                                                functions with their names; input-parameters /
                                                                                output-paramters with Delphi-type, in brackets
                                                                                C-type ; similar parameters types are available
                                                                                in basic or other programming languages
                                                                                variant IRemoteControl:: StartEvaluation ()
                                                                                input          nothing
                                                                                output:        none
                                                                                This function starts evaluation. All current acti-
                                                                                vated channels for evaluation will be evalua-
                                                                                ted with there current paramters.
                                                                                 variant IRemoteControl:: StartRecord ()
                                                                                input         nothing
                                                                                output:       none
                                                                                This function starts a record (analogue to call
                                                                                of ALT-A directly in WinTRAS)




DR. STRAUSS SYSTEM-ELEKTRONIK GMBH           Phone +49 951-43063    INFO www.strauss.de                                              16
D-96163 Gundelsheim/Bamberg                  Fax +49 951-43858      email dr.strauss@strauss.de
                                                                                                   TRAS F2-E 23/01/2009
                                                                                                DR. STRAUSS
                     Software-Applications                                                               Impulse Measurement
                        Combined Voltage Test                                                            Calibration - Diagnosis
                                                                                                                www.strauss.de

                                                      Combined Voltage Test with AC and LI
                                                      The picture show a combined voltage test with power frequency voltage AC
                                                      with 143.7 kV peak and lightning impulse voltage LI with -498.5 kV peak.

                                                      With help of the Makro-Editor integrated in the WinTRAS-Software addi-
                                                      tional test parameters shown under RESULTS can be calculated automati-
                                                      cally after recording:

                                                           ·    the AC voltage at the instant of the LI peak, UacTP
                                                           ·    the voltage drop Udrop of the AC voltage peak with respect to
                                                                UacTP
                                                           ·    the test voltage Utest as the difference of UacTP and Up of the LI
                                                                peak voltage
                                                           ·    the time difference alpha in ms or degree as the time difference
                                                                between AC peak and LI peak
                                                           ·    the time instant K3TP of the AC voltage
                                                           ·    the time instant K1TP of the LI voltage

                                                      With the evaluation switch formular the evaluation method for each individ-
                                                      ual channel can be selected.

                                                      For channel 1 the selected LI evaluation automatically calculates the peak
                                                      and time parameter and the overshoot beta.

                                                      For channel 3 the AC evaluation was selected.



                                                      Furthermore the macro with name PHASE-LI-K3 was selected, details later.




                                                      The AC evaluatin rules were set to peak value and DC offset as also for
                                                      peak time for phase calculation.

                                                      To eliminate digitzer noise the channel 3 is smoothed with 100 samples with
                                                      help of an virtual auxiliary channel 4 (selectable for further evaluations) and
                                                      then evaluated in the displayed evaluation interval tmin = –1000 ms to tmax
                                                      = 1000 ms




                                                      Makro Editor

                                                      The Makro Editor allows definition of
                                                      MAKROS which contain expressions with
                                                      reference to evaluation results of the basic
                                                      evaluations, , e.g. LI, SI, OI, IC, RECT, STEP.
                                                      TIME, FFT, TFUM, ...

                                                      The expressions can be input in the formula
                                                      field line for line, the variable names can be
                                                      named free.

                                                      This expressions are evaluated immediately
                                                      after the basic evaluations are performed and
                                                      then the results are shown in the evaluation
                                                      window under RESULTS on the right side of
                                                      the display window.


17   DR. STRAUSS SYSTEM-ELEKTRONIK GMBH   Phone +49 951-43063    INFO www.strauss.de
     D-96163 Gundelsheim/Bamberg          Fax +49 951-43858      email dr.strauss@strauss.de
                                                                                                       TRAS F2-E 23/01/2009
                 Software-Applications                                                    DR. STRAUSS
         A.C. Routine Test - Waterfall Diagrams -                                                Impulse Measurement
                                                                                                 Calibration - Diagnosis
               Superimposed Voltage Test                                                                www.strauss.de

                                                 AC Routine Tests
                                                 The picture show an A.C. Routine test with constant voltage starting at
                                                 “Start” for approx. 15 Seconds, then the test volage was increase slowly
                                                 until the breakdown occured.
                                                 The breakdown automatically triggers the digital recorder and switches the
                                                 timebase from 10 kS/s upto 10 MS/s to show the breakdown behavior in
                                                 detail.
                                                 In the information window right beside the display window the A.C. voltage
                                                 immediately before the breakdown is shown as also further selected evalua-
                                                 tion parameters e.g. the frequency and the test time
                                                 Digital Voltmeter inbuilt (peak, peak/√2, rms)
                                                 for a.c. measurement of voltage and current a digital multimeter can be
                                                 displayed for each physical recorder channel
                                                 START - STOP button for test time control




                                                 Waterfall Diagram for Type Tests on Cables


                                                 The picture show a superimposed voltage type test with direct voltage d.c.
                                                 and superimposed switching voltage SI displayed as waterfall diagramm
                                                 with selectable No. of shapes, e.g. 14 shapes with horizontal offset of 4%.

                                                 The shapes can be preselected and moved horizontally and vertically with
                                                 selectable offset values.

                                                 The test voltage was increased starting with No. 11 and the breakdown oc-
                                                 curs with No. 14.




                                                 Superimposed Voltage Test on H.V. Cables with D.C.
                                                 and SI
                                                 The picture show a superimposed voltage test on H.V. Cables with D.C.
                                                 and SI




                                                 Evaluation settings for superimposed voltage and initial peak amplitudes
                                                 can be selected




DR. STRAUSS SYSTEM-ELEKTRONIK GMBH   Phone +49 951-43063   INFO www.strauss.de                                                 18
D-96163 Gundelsheim/Bamberg          Fax +49 951-43858     email dr.strauss@strauss.de
                                                                                             TRAS F2-E 23/01/2009
                   Steep Voltage Measurement                                                                                    DR. STRAUSS
                                                                                                                                         Impulse Measurement
                                     with TR-AS 200-12                                                                                   Calibration - Diagnosis
                                                                                                                                                www.strauss.de

     We have made some investigations for measuring         suring accuracy:                                          with respect to the mean value amounts to 1,9%
                                                                                                                      (4%) which are both below the desired limit accor-
     steep impulses with the TR-AS 200-12 System with
     200 MS/s to show in this respect the sufficiency and
                                                            ·   the sampling rate which makes an statistical          ding to CEI IEC 1211 of 5%.
     compliance of this TR-AS- System to the Standards          error for the peak voltage which can be measu-
                                                                                                                      This calibration easily shows the sufficiency of the
     CEI IEC 1211, CEI IEC 60-2 and IEC 1083-1 and -2.          red during a pulse calibration with steep low
                                                                                                                      TR-AS digital recorder with 200 MS/s as also with
                                                                voltage impulses as the standard deviation of
     There are tree major effects influencing the mea-                                                                100 MS/s sampling rate for steep voltage tests.
                                                                20 impulses, see picture 1;
                                                                                                                      The number of sampling points in the front a-
                                                            ·   the response parameters of the digital recor-         mounts to 20 (10) for 100 ns chopping time.
                                                                der as also of the i.v. divider which makes an
                                                                                                                      Picture 2: The TR-AS software can easily calcula-
                                                                error in the rising area oft the impulse and in       te automatically by interpolation the exact time
                                                                the peak of chopped impulses. The rise time of        instants of the 30% and 90% values and herewith
                                                                the digital recorder together with the i.v. divider   the steepness of the front Sfr as shown in picture
                                                                should be so small, that for the 30% value            2 to Sfr = 2,01*E7 V/s for a 2 V peak. The cor-
                                                                (approx. at 30 ns) the input has settled. This is     responding steepness for a peak voltage of 200
                                                                fulfilled for 5 times of the time constant resp.      kV in the h.v. testfield woud be calculated for the
                                                                the first partial response time Ta with 30 ns / 5     same shape to 2,01 MV/ms (2,01*E12 V/s).
                                         Picture 1              = 6 ns. The risetime is approx. 2.2 times of the
                                                                time constant and therefore sufficient with <=        Picture 3 shows the calibration result of a steep
                                                                12 ns as required under Item 4.4 of Standard          voltage with 210 V peak and oscillations in the
                                                                CEI IEC 1211. The TR-AS 200-12 systems                front area. For this shape the TR-AS software
                                                                with rise times of <= 7 ns for the 1600 V input       calculates automatically by signal processing and
                                                                and a first partial response time Ta of typical 3     interpolation the exact time instants of the 30%
                                                                ns therefore is well-suited for steep voltage         and 90% values, too. The standard deviation of
                                                                measurements;                                         1,2% for the peak and 1,1% for the front time T1
                                                                                                                      shows an excellent stability of the digital recorder.
                                                            ·   the error by the resolution for 10 and 12 Bit         The maximal measuring uncertainty of 2,4% for
                                                                systems corresponding to 0,1% resp. 0,025%            the peak voltage determined from 20 measure-
                                         Picture 2              is negligible in this respect - more important is     ments is inside the required limits of the Stan-
                                                                the differential non-linearity of the system          dards.
                                                                which produces an additional statistical error,       Remarks: Standard digital recorders of competi-
                                                                whereby this error is included in the standard        tors built for measurements in the electronic labo-
                                                                deviation of the performed calibrations.              ratory show often great standard deviations for
                                                            Picture 1: The picture shows the calibration result       front time and peak parameters if measuring front
                                                            at 200 MS/s with linearly rising voltage chopped at       chopped impulses. The respective calibration
                                                            0,104 ms for 20 pulses (values in brackets refe-          results for steep voltages are mostly not available.
                                                            renced to 100 MS/s):                                      Additionally the limited bandwidth, resp. risetime
                                                                                                                      and interesting response behavier of the high
                                                            the standard deviation for the peak amounts to            voltage probe neccessary for the l.v. input forces
                                         Picture 3          0,98% (2,0%), the max. measuring uncertainty              additional measuring errors.




                                TFUM - Transfer Function Method
                                                                                          The transfer function which is calculated by dividing the frequency
                                                                                          spectra of current and voltage measured during impulse voltage
                                                                                          tests becomes more validity especially at chopped voltages, consi-
                                                                                          dering higher frequencies up to 50 MHz, too.
                                                                                          Comparison of full and chopped voltage transfer functions show bet-
                                                                                          ter accordance considering higher frequencies.
                                                                                          The coherence function is a measure of the power in the output sig-
                                                                                          nal caused by the input. If the coherence is 1, then all the output po-
                                                                                          wer is caused by the input. If the coherence is 0, then none of the
                                                                                          output is caused by the input. For this calculation with help of cross
                                                                                          power spectra of voltage and current also higher frequent parts
                                                                                          must be considered and must be recorded precisely.
                                                                                          Therefore, the statement, that a bandwidth of 20 MHz is sufficient
                                                                                          for a digitizer, because the high voltage divider does not transmit
                                                                                          more, is not acceptable.




                                                                                          Probe Calibration
                                                                                          with RIG 1000
                                                                                          h.v. probes of standard digital oscilloscopes can be calibra-
                                                                                          ted reproducible with up to 1000 V STEP voltage.




19   DR. STRAUSS SYSTEM-ELEKTRONIK GMBH                      Phone +49 951-43063             INFO www.strauss.de
     D-96163 Gundelsheim/Bamberg                             Fax +49 951-43858               email dr.strauss@strauss.de
                                                                                                                                    TRAS F2-E 23/01/2009
   Impulse-Calibration-System KAL 1000                                                               DR. STRAUSS
                  Calibration-Software TRAS-KAL                                                          Impulse Measurement
           according to IEC 61083-1, IEEE 1122 and IEC 60060-2, IEEE 4                                   Calibration - Diagnosis
                                                                                                                www.strauss.de

           Application
For the calibration and for performance
tests and checks according to IEC 1083-
1 und IEC-60-2 several calibration gen-
erators with high accuracy are required
which are optimally adapted to the digital
impulse voltage measuring system to be
tested.
For this purpose a new family of precise
calibration generators became devel-
oped including the necessary software to
perform the required calibrations and
tests in the high-voltage testfield in ac-
cordance with IEC 1083-1 and IEC 60-2
in an easy manner and in short time to
save costs.
The impulse calibration system KAL                    Pulse Calibration                    range.
1000 is a modular system to perform           The pulse calibration is performed with      With help of the control relay in the
tests on complete impulse voltage meas-       help of the impulse calibration genera-      measuring system automatically the
uring systems and on digital recorders        tors KAL-LI 0.84/60 (optional KAL-LI         selected number of e.g. 20 measure-
for the measurement of high impulse           1.56/60) for full and chopped lightning      ments are performed and evaluated
voltages and impulse currents. The            impulse voltage or with help of the im-      according to IEC 1083-1.
modular design allows an optimal KAL-         pulse calibration generator KAL-SI           The mean value of the selected num-
configuration depending on the actual         20/4000 for full or chopped switching        ber of records and the largest devia-
application.                                  impulse voltage.                             tion dedected is stored into a protocol-
Additional, this modularity allows to up-     The time-to-chopping can be set to any       file for generation of the calibration
grade or modify an existing KAL 1000          value from 0.1 µs to 10 000 µs includ-       certificate subsequently.
system in case of changing or additional      ing the standard chopping time of 0.5        The Basic System includes the elec-
requirements.                                 µs.                                          tronically controled d.c. voltage source
The technical design of the impulse cali-                                                  with precise settable output voltage,
                                                 Step Voltage Calibration
bration system KAL 1000 was done con-                                                      available on a coaxial output and addi-
sidering the international standards IEC      The step voltage calibration is per-         tional two measuring taps for control
1083-1, Digital recorders for measure-        formed with help of the impulse calibra-     measuring with an calibrated external
ments in high-voltage impulse tests and       tion generator KAL-STEP.                     d.c. voltmeter.
the revision of IEC 60-2, at this time un-                                                 In this way the calibration may be ref-
                                                       Time Calibration
der consideration, the requirements for                                                    erenced to a National Standard, e.g. to
calibration generators in IEC 1083-1,         The time calibration is performed with
                                                                                           an approved DKD-testlab or the PTB.
Table 3 are fulfilled.                        help of the time mark generator KAL-
                                              TIME.                                        At the start of the automatic calibration
    Calibration of Digital-                                                                procedur the value of this d.c. charge
  Recorders according to IEC                  Calibration-Software TRAS-KAL                voltage must be input to the measuring
           1083-1                             The impulse calibration system KAL           system as reference level for the cal-
                                              1000 is controlled automatically by the      culations.
the calibration, performance check or
performance test of the measuring             digital impulse voltage measuring sys-
                                              tem TR-AS with help of an inbuilt or
                                                                                                     Calibration Record
ranges of the digital impulse voltage
                                              completable relais.                          The calibration results of a KAL 1000
measuring systems TR-AS according to
                                                                                           impulse calibrator with shapes STEP,
IEC 1083-1 may be performed either by         The channels under calibration were
                                                                                           ZEIT, LI, LIC und SI performed with an
the method pulse calibration or alterna-      connected separate or parallel to the
                                                                                           high-resolution digital impulse voltage
tively by a separate calibration of voltage   respective output of the calibrator. After
                                                                                           measuring system TR-AS 200-12 is
and time with a step voltage calibration      setting the d.c. charging voltage the
                                                                                           documented in parts in the following
and a time calibration.                       calibration is done simultan on all
                                                                                           calibration record:
                                              channels for the selected measuring




DR. STRAUSS SYSTEM-ELEKTRONIK GMBH            Phone +49 951-43063      INFO www.strauss.de                                             20
D-96163 Gundelsheim/Bamberg                   Fax +49 951-43858        email dr.strauss@strauss.de
                                                                                                       TRAS F2-E 23/01/2009
        Impulse-Calibration-System RIG 1000                                                     DR. STRAUSS
                  Calibration-Software TRAS-TEIL                                                   Impulse Measurement
             according to IEC 61083-1, IEEE 1122 and IEC 60060-2, IEEE 4                           Calibration - Diagnosis
                                                                                                          www.strauss.de


                                                                  Calibration of Impulse-Measuring-
                                                                   Systems according to IEC 60-2
                                                                The automatic controlled calibration of the complete measur-
                                                                ing system comprising the impulse voltage divider, the nec-
                                                                cessary leads, the measuring cable and the digital impulse
                                                                voltage measuring system TR-AS, follows by the parameter
                                                                method with help of the unit-step-voltage-generator RIG
                                                                1000 and the calibration software TRAS-TEIL.




                                                                Unit-Step-Voltage-Generator RIG 1000
                                                                At the parameter method, applicable for performance check
                                                                or test, the impulse scale factor and the time parameters of
                                                                the measuring system are determined by measuring and
                                                                evaluating the step response of the measuring system. The
                                                                result can be compared with the manufacturers specification
                                                                or with performance tests or checks performed in the past.
                                                                For automatically calibration and generation of an calibration
                                                                report the powerful software TRAS-TEIL with menu-oriented
                                                                operations is available.




                                                                Test setup according to IEC 60-2


21   DR. STRAUSS SYSTEM-ELEKTRONIK GMBH   Phone +49 951-43063     INFO www.strauss.de
     D-96163 Gundelsheim/Bamberg          Fax +49 951-43858       email dr.strauss@strauss.de
                                                                                                 TRAS F2-E 23/01/2009
    Impulse-Calibration-System RIG 1000                                                                     DR. STRAUSS
                 Calibration-Software TRAS-TEIL                                                                Impulse Measurement
              according to IEC 1083-1, IEEE 1122 and IEC 60-2, IEEE 4                                          Calibration - Diagnosis
                                                                                                                      www.strauss.de

The determination of the impulse scale factor and the respon-
se parameters of the complete measuring system according to
IEC 60-2 is done with the unit step voltage generator RIG
1000 using a repetitive sampling methode included in the soft-
ware TRAS-TEIL, which allows sampling rates of 1 to 5 GHz
corresponding to sampling intevals of 1 ns downto 200 ps with
our digital recorders TR-AS.




                                                                     measurement REF in the past as also the actual test results
                                                                     of the AMS (approved measuring system). For each indivi-
                                                                     dual parameter the actual difference AMS/REF-1 is calcula-
                                                                     ted and then compared with an earlier specified accepted
                                                                     differenc. The test result "accepted" or "not accepted" auto-
                                                                     matically is written to the rightmost column.
                                                                     E.g., the determination of the impulse scale factor shows in
                                                                     the selected time interval 0.4 - 20.0 µs negligible deviations
                                                                     from the specified value of the manufacturer. The scale fac-
                                                                     tor was determined to 1.005 corresponding to a ratio of
                                                                     1554.8.


The unit step voltage generator RIG 1000 is controlled auto-
matically by the digital impulse voltage measuring system TR-
AS with help of an inbuilt or completable relais.
For example, the performance check of an 3 MV impulse vol-
tage divider in the h.v. testfield of an big transformer manufac-
turer was performed, the test results are shown in the follo-
wing.
First of all the step response g(t) is measured, whereby a
sampling rate of 1 GHz corresponding to 1 ns time resolution
yields a satisfying accuracy within a short testing time.
The response parameter of the measured step response g(t)
and the time behavior of the response time T(t) by integration
of the function 1-g(t) automatically is calculated by the AT-
computer inside the measuring system.

                                                                     Definition of response parameters and settling time
                                                                     The calculated results of the measurment are:
                                                                     ß         overshoot
                                                                     F         actual impulse scale factor
                                                                     O1        virtual origin, set to t=0
                                                                     To        initial distortion time
                                                                     Ta        partial response time
                                                                     TN        experimental response time at t=tmax
                                                                     ts        settling time
                                                                     tmin      begin of evaluation
                                                                     tmax      end of evaluation


                                                                     For automatically determination of the settling time the limit-
Calibration of a 3 MV impulse voltage divider in a big
transformer testfield                                                ing functions T ± 0.02t are calculated and displayed together
The evaluation of the response time T(t) follows inside of an        with the response time T(t). The latest point of intersection of
selectable time intervall tmin to tmax                               T(t) with the limiting functions is the wanted settling time ac-
The calibration report includes the test results of the reference    cording to IEC 60-2.


DR. STRAUSS SYSTEM-ELEKTRONIK GMBH             Phone +49 951-43063        INFO www.strauss.de                                            22
D-96163 Gundelsheim/Bamberg                    Fax +49 951-43858          email dr.strauss@strauss.de
                                                                                                             TRAS F2-E 23/01/2009
       Technical Data:                                KAL 1000 / RIG 1000 DR. STRAUSS
                                                                                                                             Impulse Measurement
                                                                                                                             Calibration - Diagnosis
                                                                                                                                    www.strauss.de

              Calibrator Basic-Device                 KAL 1000                                       time-to-half-value          ± 2% / ± 0.2%      1)
                                                                                                     time-to-chopping            ± 2% / ± 1%        1)
     for supply and control of the KAL-Generators described below, rack                              according to                IEC 1083-1 table 3
     mount with power supply, line filter, built into a 19" housing
     design              cassette                 4 HE, 42 TE                    Switching-Impulse-Generator KAL-SI 20/4000
                         housing (BxHxD)          500x200x320 mm              for pulse calibration of the digital impulse voltage measuring system
                         or 19" rack mount                                    according to IEC 1083-1.
     weight              approx. 10 kg
                                                                              design                                             cassette 12 TE
         H.V. Load Circuit, electronically controled                          charge voltage         basic-device                0 - +1000 V
     design                                       in basic device                                    switching-device            electronically
     charge voltage, adjustable                                                                      chopping-device             electronically
     with 10-turn-potentiometer                   0 - +1000 V positiv                                charge-capacity             1 µF
                          setting-accuracy        < 0.1 %                     impulse output         BNC                         ±50 .. ±1000 V         2)
     digital display      LED                     0-1000.0 V                                         output-resistance           20 Ohm
                          measuring-accuracy      ± 0.1 % ± 2 digit                                  cable-length                1.5 m
     charge time          modul-dependent         1 .. 10 s                   shape                  standard                    20/4000 µs
     output               frontside               coaxial                                            optional                    250/2500 µs
                          measurement             2 plugs                     chopping time          selectable                  0.1 .. 10 000 µs
     max. cable length unlimited                                              accuracy               peak-voltage                ± 1% / ± 0.2%          1)
     load resistance                              >= 200 kOhm                                        time-to-peak                ± 2% / ± 0.2%          1)
                                                                                                     time-to-half-value          ± 2% / ± 0.2%          1)
                                                                                                     time-to-chopping            ± 2% / ± 1%            1)
                          Control Electronic                                                         according to                IEC 1083-1 table 3
     design                                       in basic device
     releasing           manual                   key
                         BNC-input                TTL LO-level or                         Timemark-Generator                      KAL-ZEIT
                                                  external relais             For time calibration of the digital impulse voltage measuring system
     impulse output      switching gap SG         5 Vp, BNC                   according to IEC 1083-1.

     time-to-chopping    adjustable               0.1 - 10 000 µs             design                                             in base device
                         step                     0.1 µs                                             time-intervall              20 ms ±0.01%
                         quarz-timebase           10 MHz, 100 ppm             output BNC             squarewave                  0 / 5 V, TTL-level
     impulse output      chopping gap CG          5 Vp, BNC

              Step-Voltage-Generator KAL-STEP                                    Unit-Step-Voltage-Generator RIG 1000 (H)
     for the step calibration of the inputs of digital impulse voltage measur- for determination of the impulse scale factor and the response pa-
     ing system according to IEC 1083-1                                        rameters of the high voltage impulse measuring system with the unit
                                                                               step method according to IEC 60-2. The generator is placed on the
     design                                           in basic device          floor or wall in the h.v. testfield and connected to the h.v. divider.
     charge voltage        base-device                0 .. +1000 V
     switching-device      electronically                                      design                 cassette                 4 HE, 42 TE
                           output                     short-circuited                                 housing (BxHxD)          260x200x320 mm
                           falltime                   < 10 ns (90/10%)         weight                 approx. 4 kg
     impulse output        BNC                        10 .. 1000 V
                           polarity                   negative step            charge voltage         coax-input               0 - +1000 V
                           output-resistance          50 Ohm                                          feeding                  basic device
                           load-resistance            >= 200 kOhm                                                              via coaxcable 20 m
                           cable-length               1,5 m                    type H                 optionally               inbuilt h.v. supply
     accuracy              step-voltage               ± 0.5% / ± 0.2%    1)
                                                                               Charge capacitor charge-capacity                5.3 µF
       Lightning-Impulse-Generator KAL-LI 0.84/60                             switching-device                                   electronically
     for pulse calibration of the digital impulse voltage measuring system                           output-resistance           2 Ohm
     according to IEC 1083-1                                                                         risetime                    < 10 ns (10/90%)
                                                                              releasing              BNC-input                   TTL LO-level or
     design                                       cassette 12 TE                                                                 relay (meas.system)
     charge voltage      basic-device             0 - +1000 V                                                                    via coaxcable 20 m
                         switching-device         electronically
                         chopping-device          electronically              impulse output                                     0 .. ±1000 V
                         charge-capacity          0.6 µF                                             polarity                    positive or negative
     impulse output      BNC                      ±50 .. ±1000 V        2)                           connection                  to i.v. divider
                         output-resistance        20 Ohm                                             load                        >= 5 kOhm || 10 nF
                         cable-length             1,5 m                       accuracy               peak value                  ± 0.1% stat.
     shape               standard                 0.84/60 µs                  power supply                                       battery inside
                         optional                 1.56/60 µs
     chopping time       selectable               0.1 .. 10 000 µs            1) long term stability / short term stability
     accuracy            peak-voltage             ± 1% / ± 0.2%         1)    2) efficiency < 1
                         front-time               ± 2% / ± 0.5%         1)    Technical data and design subject to modification without notice.




     wave form                                                      chopping time             output voltage range                  for input range
     full wave lightning impulse LI 0,84/60                         100 ns—20 ms                  ±50 V to ±1000 V                    50 V - 2500 V
     front-chopped lightning impulse, Tc=500ns                          500 ns                    ±50 V to ± 750 V                   100 V - 1800 V
     switching impulse SI 20/4000                                   100 ns—20 ms                  ±50 V to ±1000 V                    50 V - 2500 V
     switching impulse SI 250/2500                                  100 ns—20 ms                  ±50 V to ±1000 V                    50 V - 2500 V
     STEP Voltage                                                                                   10 V to 1000 V                    10 V - 2500 V
23   DR. STRAUSS SYSTEM-ELEKTRONIK GMBH                 Phone +49 951-43063        INFO www.strauss.de
     D-96163 Gundelsheim/Bamberg                        Fax +49 951-43858          email dr.strauss@strauss.de
                                                                                                                          TRAS F2-E 23/01/2009
DEUTSCHER KALIBRIERDIENST (DKD)
                                                                                           DR. STRAUSS
      Kalibrierlaboratorium für elektrische Impulsgrößen                                          Impulse Measurement
        Calibration laboratory for electrical impulse parameter                                   Calibration - Diagnosis
                                                                                                         www.strauss.de

         Träger
          holder
                    DR. STRAUSS SYSTEM-ELEKTRONIK GMBH
     akkreditiert   Akkreditierungsstelle des DKD bei der
       durch die    PHYSIKALISCH-TECHNISCHE BUNDESANSTALT (PTB)
   accredited by
                                                                               DKD-K-11701

        Kalibrierdienste in der EA / Calibration Service inside the EA
                                                                               Der Deutsche Kalibrierdienst (DKD) ist ein Zu-
                                                                               sammenschluss von Kalibrierlaboratorien aus
                                                                               Industrieunternehmen, Forschungsinstituten,
                                                                               technischen Behörden, Überwachungs- und
                                                                               Prüfinstitutionen. Diese Laboratorien werden
                                                                               von der Akkreditierungsstelle des Deutschen
                                                                               Kalibrierdienstes akkreditiert und überwacht.
                                                                               Sie führen Kalibrierungen von Messgeräten
                                                                               und Maßverkörperungen für die bei der Akkre-
                                                                               ditierung festgelegten Messgrößen und Mess-
                                                                               bereiche durch. Die von ihnen ausgestellten
                                                                               DKD-Kalibrierscheine sind ein Nachweis für
                                                                               die Rückführung auf nationale Normale, wie
                                                                               sie von der Normenfamilie DIN EN ISO 9000
                                                                               und der DIN EN ISO/IEC 17025 gefordert
                                                                               werden.

                                                                               Kalibrierungen durch DKD-Laboratorien ge-
                                                                               ben dem Anwender Sicherheit für die Verläss-
                                                                               lichkeit von Messergebnissen, erhöhen das
                                                                               Vertrauen der Kunden und die Wettbewerbs-
                                                                               fähigkeit auf dem nationalen und internationa-
                                                                               len Markt. Sie dienen als messtechnische
                                                                               Grundlage für die Mess- und Prüfmittelüber-
                                                                               wachung im Rahmen des Qualitätsmanage-
                                                                               ments.

                                                                               The Deutscher Kalibrierdienst (DKD) is an as-
                                                                               sociation of calibration laboratories of industri-
                                                                               al firms, research institutes, technical authori-
                                                                               ties, inspection and testing institutes. These
                                                                               laboratories are accredited and supervised by
                                                                               the Accreditation Body of Deutscher Kalibrier-
                                                                               dienst. They calibrate measuring instruments
Akkreditierungsverfahren im           Accreditation procedure of the           and material measures for measurands and
DKD (Deutscher Kalibrierdienst)       DKD (German Calibration Servi-           measurement ranges specified within the fra-
                                                                               mework of accreditation. The DKD calibration
                                      ce)                                      certificates issued by these laboratories prove
                                                                               traceability to national standards as required
                                                                               in the “standards’ family” ISO 9000 and the
                                                                               ISO/IEC 17025.

                                                                               Calibrations carried out by DKD laboratories
                                                                               allow the user to trust in the reliability of mea-
                                                                               surement results. They increase the custo-
                                                                               mers’




                                                                               Das Bild zeigt das akkreditierungsverfahren
                                                                               im Deutschen Kalibrierdienst DKD

                                                                               The picture show the Accredidation procedure
                                                                               of the German Calibration Service DKD




DR. STRAUSS SYSTEM-ELEKTRONIK GMBH     Phone +49 951-43063   INFO www.strauss.de                                                    24
D-96163 Gundelsheim/Bamberg            Fax +49 951-43858     email dr.strauss@strauss.de
                                                                                              TRAS F2-E 23/01/2009
     Organisationsstruktur zur Rückführung von Impulsspannungs-Meßsystemen                                                      DR. STRAUSS
     auf nationale Normale in Deutschland
     Calibration system to establish traceability of impulse voltage measuring                                                          Impulse Measurement
     systems to national standards in Germany                                                                                           Calibration - Diagnosis
                                                                                                                                               www.strauss.de

                                                     Voraussetzung der                                                                             Dokumentation der
           Normal                Anwender                                        Meßeinrichtung           Hersteller Typ      Meßunsicherheit
                                                        Kalibrierung                                                                                  Kalibrierung
     Standard of measure-                          supposition for calibra-                                                                       documentation of ca-
                                    User                                        measuring system        manufacturer type   measuring uncertainty
            ment                                            tion                                                                                        libration
                                                                               Gleichspannung Im-
      Nationales Normal             PTB                                                                                                           PTB-Kalibrier- schein
                                                                                  pulsmessung
                                                                              direct voltage impulse                                             PTB-calibration certifi-
      National Standard
                                                                                  measurement                                                            cate
                                                                                                         DR. STRAUSS
                                                                                                           KAL 1000             LI, SI / LIC
                                                                           Impuls-
                       DKD Kalibrierlaborato-                                                                                peak: 0,5% / 0,7%
     Bezugs-Normal Me-                                             Kalibriergenerator Digi-
                           rium bei DR.       PTB- Kalibrierschein                                       DR. STRAUSS             time: 2%         DKD-Kalibrier schein
        ßeinrichtung                                               talrecorder Digitalvolt-
                        STRAUSS GMBH                                                                     TR-AS 200-14
                                                                            meter
                                                                                                                                STEP: 0,4%
                                                                                                          Solartron 7150
                                                                             digital recorder
                            DKD Calibration labo-
     Reference Standard                           PTB- Calibration Certi- impulse calibr. genera-                                                DKD Calibration Certi-
                               ratory at DR.
      of measurement                                     ficate                      tor                                                               ficate
                             STRAUSS GMBH
                                                                             digital voltmeter
                                                                                                                                 LI, SI / LIC
                                                                                     Impuls-               KAL 1000
        Werks-Normal   Innerbetriebliches Ka-                                                                                  peak: 1% / 2%
                                                   DKD- Kalibrierschein         Kalibriergenerator      TR-AS 100-10/12                          Werks- Kalibrierschein
     Referenz-Meßsystem librierlaboratorium                                                                                       time: 2%
                                                                                 Digitalrecorder        TR-AS 200-12-14
                                                                                                                                STEP: 0,5%
                                                                              impulse calibr. genera-
     Reference measuring Calibration laboratory DKD-Calibration Certi-                                                                           Works Calibrat. Certifi-
                                                                                        tor
           system           of organisation           ficate                                                                                            cate
                                                                                 digital recorder
                                                                                                          TR-AS 25-8/12         LI, SI, LIC
      Gebrauchs-Normal      Prüffeld, betriebliche
                                                   Werks- Kalibrierschein         Digitalrecorder       TR-AS 100-8/10/12     peak: 2% / 3%        Werks- Prüfschein
       Meß-/Prüfsystem            Bereiche
                                                                                                         TR-AS 200-12-14         time: 4%
     Approved measuring Test laboratory of or- Works-Calibrat. Certifi-
                                                                                 digital recorder                                                  Works Test Record
           system             ganisation              cate


     Akkreditierung durch die PTB / Accredidation by PTB (DIN EN ISO/IEC 17025)
                                                                                           Die Akkreditierung erfolgte am 06.06.1994 durch die Physikalisch-
                                                                                           Technische Bundesanstalt (PTB), Deutscher Kalibrierdienst (DKD),
                                                                                           vertreten im Deutschen AkkreditierungsRat als Kalibrierlaboratorium
                                                                                           für elektrische Impulsgrößen unter der DAR-Registriernummer DKD-
                                                                                           K-11701.
                                                                                           Die Firma DR. STRAUSS SYSTEM-ELEKTRONIK GMBH ist somit
                                                                                           das erste Unternehmen, welches Impuls-Kalibrier- und Meßeinrichtun-
                                                                                           gen für Stoßspannungs- und Stoßstromprüfungen rückführbar auf
                                                                                           nationale Normale kalibrieren darf und hierfür Kalibrierscheine aus-
                                                                                           stellt, die innerhalb der WECC in ganz Europa anerkannt werden.
                                                                                           Die für die Einrichtung des Kalibrierlaboratoriums notwendigen Be-
                                                                                           zugs-Normal Meßeinrichtungen TR-AS 100-10/12, TR-AS 200-14 und
                                                                                           KAL 1000 kommen aus der eigenen Fertigung und sind an die natio-
                                                                                           nalen Normale bei der PTB angebunden.
                                                                                           Die hierbei durch die PTB bestätigte hohe Qualität unserer Produkte,
                                                                                           dokumentiert durch ausführliche Typenprüfungen unter Beachtung der
                                                                                           einschlägigen Normen, findet ihren Niederschlag in den für unsere
                                                                                           Kunden bestimmten Produkte.
                                                                                           The accreditation was performed on 06.06.1994 by the Physikalisch-
                                                                                           Technische Bundesanstalt (PTB), Deutscher Kalibrierdienst (DKD),
                                                                                           represented in the Deutschen AkkreditierungsRat as calibration labo-
                                                                                           ratory for electrical impulse parameter with DAR registration number
                                                                                           DKD-K-11701.
                                                                                           DR. STRAUSS SYSTEM-ELEKTRONIK GMBH therefore is the first
                                                                                           company, which may calibrate impulse measuring and calibration sys-
                                                                                           tems for high voltage impulse tests with traceability to national stan-
                                                                                           dards and issues calibration certificates recognized inside the WECC
                                                                                           in Europe.
                                                                                           The Reference Standards of measurement TR-AS 100-10/12, TR-AS
                                                                                           200-14 and KAL 1000 neccessary for furnishing the calibration labora-
                                                                                           tory come from our own production and are traced to the national
                                                                                           standards at the PTB.
                                                                                           The high quality standard of this equipment confirmed by the PTB
                                                                                           herewith and documented in detailed type test reports under consid-
                                                                                           eration of the respective standards, finds its reflection in the products
                                                                                           delivered to our customers too.




25   DR. STRAUSS SYSTEM-ELEKTRONIK GMBH                         Phone +49 951-43063             INFO www.strauss.de
     D-96163 Gundelsheim/Bamberg                                Fax +49 951-43858               email dr.strauss@strauss.de
                                                                                                                                    TRAS F2-E 23/01/2009
DEUTSCHER KALIBRIERDIENST (DKD)
                                                                                                     DR. STRAUSS
       Kalibrierlaboratorium für elektrische Impulsgrößen                                                Impulse Measurement
           Calibration laboratory for electrical impulse parameter                                       Calibration - Diagnosis
                                                                                                                www.strauss.de

PTB: The Physikalisch-Technische Bundesanstalt at Braun-             PTB: Die Physikalisch-Technische Bundesanstalt in Braun-
schweig is the metrological institute of the Federal Republic of     schweig ist das metrologische Staatsinstitut und die tech-
Germany and has by law the responsibility for the national           nische Oberbehörde für das Meßwesen in Deutschland. Sie
standards of measurement. PTB develops the national stan-            entwickelt und bewahrt die "nationalen Normale" zur Darstel-
dards of measurement for representating the international            lung der SI-Einheiten und stellt in Zusammenarbeit mit
units SI and is responsible for the necessary international          Staatsinstituten anderer Länder deren Vergleichbarkeit in in-
comparisons.                                                         ternationalem Rahmen sicher.


DKD: In the German Calibration Service (Deutscher Kalibri-           DKD: Im Deutschen Kalibrierdienst sind Kalibrierlaborato-
erdienst) calibration laboratories of industry and other institu-    rien der Industrie und anderer Institutionen zusam-
tions are jointed, which are accredited and supervised by PTB        mengeschlossen, die von der PTB nach festgelegten
according to fixed criterions.                                       Kriterien akkreditiert und überwacht werden.


Calibration laboratory: The calibration laboratories are             Kalibrierlaboratorium: In den Betrieben werden Kali-
installed within the organisation and hold the reference meas-       brierlaboratorien betrieben, welche vom DKD kalibrierte Ref-
uring systems calibrated by DKD to calibrate the measuring           erenz-Meßsysteme als Werks-Normale zur Kalibrierung der
and test systems used in the test laboratories (approved             Meß- und Prüfsysteme im Prüffeld einsetzen (kalibrierte
measuring systems).                                                  Meßsysteme).




                                                                     Das Kalibrierlaboratorium bietet die Kalibrierung von

                                                                                  Impuls-Kalibriergeneratoren
                                                                                     Sprunggeneratoren
                                                                                       Digitalrecordern
                                                                                        Stoßvoltmetern

                                                                     an und stellt dafür DKD-Kalibrierscheine aus, welche die
                                                                     Rückführung auf nationale Normale zur Darstellung der
                                                                     physikalischen Einheiten in Übereinstimmung mit den Inter-
                                                                     nationalen Einheiten (SI) dokumentieren.




                                                                     The DKD Calibration laboratory offers the calibration of
                                                                                 impulse calibration generators
                                                                                  unit step voltage generators
                                                                                         digital recorders
                                                                                       impulse voltmeters

                                                                     and issues DKD-Calibration Certificates which document the
                                                                     traceability to national standards which realize the physical
                                                                     units of measurement according to the international system
                                                                     of Units (SI).
   DKD Kalibrierschein (Muster)
   DKD Calibration Certificate (Example)




DR. STRAUSS SYSTEM-ELEKTRONIK GMBH             Phone +49 951-43063     INFO www.strauss.de                                           26
D-96163 Gundelsheim/Bamberg                    Fax +49 951-43858       email dr.strauss@strauss.de
                                                                                                      TRAS F2-E 23/01/2009
      Electronic Voltage Transformer                                                                       DR. STRAUSS
                                                                                                              Impulse Measurement
                                               EVT                                                            Calibration - Diagnosis
                                                                                                                     www.strauss.de


               for capacitive coupling with minimized transient errors
     Voltage transformers usually are inductive types designed with       For the classical capacitive v.t. the inductive part can be
     single stage coils. For higher system voltages upside 110 kV         substituted to an electronic low-voltage part to eliminate the
     the manufacturing costs for inductive v.t’s and their dimensi-       known resonant problems and sawtooth frequencies and of-
     ons increase overproportionally. Therefore a cost-efficient al-      fers better transient behavier.
     ternative to the inductive high-voltage part is desirable: e.g. a    The excellent long-term stability of electronic components
     capacitive voltage divider with electronic low-voltage part. For     together with suitable high-voltage capacitors allow the de-
     GIS the h.v. capacitor can be integrated easy and place-             sign of precise voltage transformers of class 0,1 which can
     saving as a coaxial cylinder capacitor inside the switchgear.        be calibrated on site with burdens up to 25 VA at 100/Ö3 V
     For other applications a compressed gas capacitor with few           rated voltage.
     pF capacity can be used.

         400 kV GIS at BEWAG Berlin




                                                                          primary short circuit with oscillating recovery voltage




                                                                          short interrupt with trapped charges

     Preamplifier EVT-VC:                                                                     amplifier.
     class 0,1/0,2 or 0,5 for 0,8 - 1,2 x UN     Common Data:
     high-voltage capacitor CH=10 pF ad-         2 redundant power supplies              Supervising Concept
     justable from +5% to -20% with inbuilt      lumuniscence diode for ready            The supervising relays are active nor-
     precision potentiometer with 0.01% reso-    4 contacts (make and break) and lumu-   mally and falls inactive in case of a fault.
     lution                                      niscence diode for amplification faulty a-
                                                                                         The voltage level of the virtual input on
     rated voltage 400000/Ö3 V : 6,5Ö3 V or      bove ±2.5% in 0.8 - 1.9 x UN or         input and the output voltage of the ampli-
     any other depending from h.v. capacitor     supply voltage faulty above ±20%        fiers continuously are supervised. In ca-
     rated burden 0.1 VA                         lumuniscence diode for stored faults    se a deviation greater than an error limit
                                                 clear-key for reset stored fault        of 2.5% with respect to the peak value of
     Measuring Amplifier EVT-M05:                fault detection time = 2 ms             UN during a time interval greater than a
     class 0,1/0,2 or 0,5 for 0,8 - 1,2 x UN     reaktion time of contakts < 6 ms        specified fault detection time will cause
     rated voltage 6.5/Ö3 V : 100/Ö3 V                                                   an error.
     rated burden 25 VA                      Saturation effects caused by d.c. tran- A deviation of a supply voltage greater
                                             siens are not possible because of the di- than 20% of the nominal value will cau-
     Protection Amplifier EVT-P3:            rect coupled iron-free output stage se an error.
     class 3P for 0,05 - 1,5 x UN            without transformer.
     rated voltage 6.5/Ö3 V : 100/Ö3 V                                                   Adaptation and Calibration Amplifier
     rated burden 5 VA                       Short-Circuit Protection                    for unconventional VT‘s and CT‘s
                                             Any load between no load and short cir- Application as adaptation amplifier of un-
     Protection Amplifier EVT-P3EN           cuit does not disturb the output amplifier. conventional electronic voltage transfor-
     for connection to preamplifiers EVT-VC                                              mers of any type from 4-5-6.5/Ö3 V se-
     of phases L1, L2 und L3.                Reverse-feeding Protection of Output: cundary voltage up to 100/Ö3 Volt for ca-
     rated voltage 3x6.5/Ö3 V : 100/3 V      Any voltage feeded to the output below libration purpose with conventional ra-
     rated burden 5 VA                       <= 1,9 x UN does not disturb the output tio and burden measuring bridges.


27   DR. STRAUSS SYSTEM-ELEKTRONIK GMBH             Phone +49 951-43063     INFO www.strauss.de
     D-96163 Gundelsheim/Bamberg                    Fax +49 951-43858       email dr.strauss@strauss.de
                                                                                                            TRAS F2-E 23/01/2009
Tapchanger Test Plant                                                                                     DR. STRAUSS
more than 20 test plants at MR Reinhausen, Germany                                                           Impulse Measurement
                                                                                                             Calibration - Diagnosis
equipped with TR-AS Measuring Systems                                                                               www.strauss.de




 Tapchanger Test Plant at MR Reinhausen Germany
 equipped with TR-AS Measuring Systems

 Systems based on TR-AS 10-12 with 8 analogue inputs
 for measuring voltage, current and torque and 32 digi-
 tal inputs for contact events.
 Software for automatic routine test with verification of
 test results with given parameters.




Technical data and design subject to change without notice. Alternative design on request.


For further informations please contact:
Representative                                                           Manufacturer:
                                                                         DR. STRAUSS SYSTEM-ELEKTRONIK GMBH