Docstoc

SECTION 26 05 00

Document Sample
SECTION 26 05 00 Powered By Docstoc
					 1                                      SECTION 26 05 00
 2                             COMMON WORK RESULTS FOR ELECTRICAL
 3
 4                                             PART 1 - GENERAL
 5
 6   SCOPE
 7   The work under this section includes basic electrical requirements, which are applicable to all Division 26
 8   and Division 27 sections. This section includes information common to two or more technical specification
 9   sections or items that are of a general nature, not conveniently fitting into other technical sections.
10   Included are the following topics:
11   PART 1 - GENERAL
12            Scope
13            Related Work
14            Reference Standards
15            Regulatory Requirements
16            Quality Assurance
17            Continuity of Existing Services and Systems
18            Protection of Finished Surfaces
19            Approved Electrical Testing Laboratories
20            Sleeves and Openings
21            Sealing and Firestopping
22            State and/or User Agency Furnished Equipment
23            Work by State and/or User Agency
24            Provisions for Future Work
25            Intent
26            Omissions
27            Submittals
28            Project/Site Conditions
29            Asbestos Abatement
30            Work Sequence and Scheduling
31            Work by Other Trades
32            Offsite Storage
33            Request and Certificate for Payment
34            Salvage Materials
35            Certificates and Inspections
36            Operating and Maintenance Instructions
37            Training of User Agency Personnel
38            Record Drawings
39   PART 2 - PRODUCTS
40            Access Panels and Doors
41            Sealing and Firestopping
42   PART 3 - EXECUTION
43            Excavation and Backfill
44            Concrete Work
45            Cutting and Patching
46            Building Access
47            Equipment Access
48            Coordination
49            Sleeves
50            Sealing and Firestopping
51            Housekeeping and Clean Up
52
53   RELATED WORK
54   Applicable provisions of Division 1 govern work under this Section.
55
56   REFERENCE STANDARDS
57   Abbreviations of standards organizations referenced in this and other sections are as follows:
58   ANSI American National Standards Institute
59   EPA     Environmental Protection Agency
60   ETL     Electrical Testing Laboratories, Inc.
61   IEEE Institute of Electrical and Electronics Engineers
62   ISA     Instrument Society of America
63   NEC     National Electric Code



                                                   DSF Project No.
                                                    26 05 00 - 1
 1   NEMA     National Electrical Manufacturers Association
 2   NESC     National Electrical Safety Code
 3   NFPA     National Fire Protection Association
 4   UL       Underwriters Laboratories Inc.
 5
 6   REGULATORY REQUIREMENTS
 7   All work and materials are to conform in every detail to applicable rules and requirements of the Wisconsin
 8   State Electrical Code Volumes 1 and 2, the National Electrical Code (ANSI/NFPA 70), other applicable
 9   National Fire Protection Association codes, the National Electrical Safety Code, and present manufacturing
10   standards (including NEMA).
11
12   All Division 26 work shall be done under the direction of a currently certified State of Wisconsin Certified
13   Master Electrician.
14
15   QUALITY ASSURANCE
16   Where equipment or accessories are used which differ in arrangement, configuration, dimensions, ratings,
17   or engineering parameters from those indicated on the contract documents, the contractor is responsible for
18   all costs involved in integrating the equipment or accessories into the system and the assigned space and for
19   obtaining the performance from the system into which these items are placed.
20
21   Manufacturer references used herein are intended to establish a level of quality and performance
22   requirements unless more explicit restrictions are stated to apply.
23
24   All materials, except medium voltage equipment and components, shall be listed by and shall bear the label
25   of an approved electrical testing laboratory. If none of the approved electrical testing laboratories has
26   published standards for a particular item, then other national independent testing standards, if available,
27   applicable, and approved by DSF, shall apply and such items shall bear those labels. Where one of the
28   approved electrical testing laboratories has an applicable system listing and label, the entire system, except
29   for medium voltage equipment and components, shall be so labeled.
30
31   CONTINUITY OF EXISTING SERVICES AND SYSTEMS
32   No outages shall be permitted on existing systems except at the time and during the interval specified by
33   the user agency and by the DSF Project Representative. The institution may require written approval. Any
34   outage must be scheduled when the interruption causes the least interference with normal institutional
35   schedules and business routines. No extra costs will be paid to the Contractor for such outages which must
36   occur outside of regular weekly working hours.
37
38   This Contractor shall restore any circuit interrupted as a result of this work to proper operation as soon as
39   possible. Note that institutional operations are on a seven-day week schedule.
40
41   PROTECTION OF FINISHED SURFACES
42   Furnish one can of touch-up paint for each different color factory finish furnished by the Contractor.
43   Deliver touch-up paint with other "loose and detachable parts" as covered in the General Requirements.
44
45   APPROVED ELECTRICAL TESTING LABORATORIES
46   The following laboratories are approved for providing electrical product safety testing and listing services
47   as required in these specifications:
48   Underwriters Laboratories Inc.
49   Electrical Testing Laboratories, Inc.
50
51   SLEEVES AND OPENINGS
52   Openings that are required shall be the responsibility of the contractor requiring the opening. The
53   contractor shall install sleeves or cut openings as required. Each contractor shall be responsible for
54   coordinating locations of their sleeves and openings with work of other trades.
55
56   SEALING AND FIRESTOPPING
57   Sealing and firestopping of sleeves/openings between conduits, cable trays, wireways, troughs, cablebus,
58   busduct, etc. and the structural or partition opening shall be the responsibility of the contractor whose work
59   penetrates the opening. The contractor responsible shall hire individuals skilled in such work to do the
60   sealing and firestopping. These individuals hired shall normally and routinely be employed in the sealing
61   and fireproofing occupation.
62
63



                                                    DSF Project No.
                                                     26 05 00 - 2
 1   STATE AND/OR USER AGENCY FURNISHED EQUIPMENT
 2   None
 3
 4   WORK BY STATE AND/OR USER AGENCY
 5   Asbestos abatement and PCB equipment (other than light fixture ballasts) removal and disposal, if required,
 6   will be by the DSF under separate contract.
 7
 8   PROVISIONS FOR FUTURE WORK
 9   None
10
11   INTENT
12   The Contractor shall furnish and install all the necessary materials, apparatus, and devices to complete the
13   electrical equipment and systems installation herein specified, except such parts as are specifically
14   exempted herein.
15
16   If an item is either called for in the specifications or shown on the plans, it shall be considered sufficient for
17   the inclusion of said item in this contract. If a conflict exists within the Specifications or exists within the
18   Drawings, the Contractor shall furnish the item, system, or workmanship, which is the highest quality,
19   largest, or most closely fits the DSF's intent (as determined by the DSF Project Manager).
20
21   It must be understood that the details and drawings are diagrammatic. The Contractor shall verify all
22   dimensions at the site and be responsible for their accuracy.
23
24   Materials and labor shall be new (unless noted or stated otherwise), first class, and workmanlike, and shall
25   be subject at all times to the DSF's and/or A/E's inspections, tests and approval from the commencement
26   until the acceptance of the completed work.
27
28   Whenever a particular manufacturer's product is named, it is intended to establish a level of quality and
29   performance requirements unless more explicit restrictions are stated to apply.
30
31   OMISSIONS
32   No later than ten (10) days before bid opening, the Contractor shall call the attention of the DSF to any
33   materials or apparatus the Contractor believes to be inadequate and to any necessary items of work omitted.
34
35   SUBMITTALS
36   Submit for all equipment and systems as indicated in the respective specification sections, marking each
37   submittal with that specification section number. Mark general catalog sheets and drawings to indicate
38   specific items being submitted and proper identification of equipment by name and/or number, as indicated
39   in the contract documents. Failure to do this may result in the submittal(s) being returned to the Contractor
40   for correction and resubmission. Failing to follow these instructions does not relieve the Contractor from
41   the requirement of meeting the project schedule.
42
43   On request from the DSF, the successful bidder shall furnish additional drawings, illustrations, catalog data,
44   performance characteristics, etc.
45
46   Submittals shall be grouped to include complete submittals of related systems, products, and accessories in
47   a single submittal. Mark dimensions and values in units to match those specified. Include wiring diagrams
48   of electrically powered equipment.
49
50   The submittals must be approved before fabrication is authorized.
51
52   Submit sufficient quantities of submittals to allow the following distribution:
53           File Copy                                                                              2 copies
54           User agency                                                                            2 copies
55           A/E                                                                                    2 copy
56
57   PROJECT/SITE CONDITIONS
58   Install Work in locations shown on Drawings, unless prevented by Project conditions.
59
60   Prepare drawings showing proposed rearrangement of Work to meet Project conditions, including changes
61   to Work specified in other Sections. Obtain permission of DSF before proceeding.
62   Tools, materials and equipment shall be confined to areas designated by the DSF and user agency.
63



                                                     DSF Project No.
                                                      26 05 00 - 3
 1   ASBESTOS ABATEMENT
 2   The State is responsible for identifying Asbestos Containing Materials (ACMs) in State buildings. The
 3   Contractor is responsible for marking the extent of the identified ACMs that will be disturbed by the
 4   Contractor’s work and coordination with an asbestos abatement contractor under a direct contract with the
 5   State. The asbestos abatement contractor will require sole occupancy of the work space during asbestos
 6   abatement work. Contractor shall communicate with the asbestos abatement contractor and make adequate
 7   allowance for the asbestos abatement work in the work schedule. Contractor shall not supply or install any
 8   materials that contain any amount of asbestos.
 9
10   WORK SEQUENCE AND SCHEDULING
11   Install work in phases to accommodate user agency's occupancy requirements. During the construction
12   period coordinate electrical schedule and operations with DSF's Construction Representatives.
13
14   WORK BY OTHER TRADES
15   Every attempt has been made to indicate in this trade's specifications and drawings all work required of this
16   Contractor. However, there may be additional specific paragraphs in other trade specifications and
17   addenda, and additional notes on drawings for other trades which pertain to this Trade's work, and thus
18   those additional requirements are hereby made a part of these specifications and drawings.
19
20   Electrical details on drawings for equipment to be provided by others is based on preliminary design data
21   only. This Contractor shall lay out the electrical work and shall be responsible for its correctness to match
22   equipment actually provided by others.
23
24   OFFSITE STORAGE
25   If payment will be requested for approved offsite stored material, then the Contractor shall complete an
26   "Off-site Storage Agreement" which is available from the DSF. Prior approval by DSF personnel for
27   offsite storage will be needed. No material will be accepted for offsite storage unless submittals for the
28   material have been approved.
29
30   REQUEST AND CERTIFICATE FOR PAYMENT
31   Within 10 days after Notice to Proceed, the successful bidder will submit to the DSF in a form prescribed
32   below and by the General Conditions of the Contract, Scheduling and Coordination of Work, Reports,
33   Records and Data, and Payments to Contractor, a cost breakdown of the proposed values for work
34   performed which, if approved by the DSF, will become the basis for construction progress and monthly
35   payments. The cost breakdown items shall reflect actual work progress stages as closely as feasible.
36
37   In addition, if payment will be requested for approved off-site stored material, then that material shall be
38   listed as a line item and the Contractor shall complete an "Off-site Storage Agreement" which is available
39   from the DSF.
40
41   SALVAGE MATERIALS
42   No materials removed from this project shall be reused except as specifically noted below. All materials
43   removed shall become the property of and shall be disposed of by the Contractor.
44
45   CERTIFICATES AND INSPECTIONS
46   Obtain and pay for all required State installation inspections except those provided by the DSF in
47   accordance with Wis. Adm. Code Section Comm. 50.12. Deliver originals of these certificates to the DSF's
48   Project Representative. Include copies of the certificates in the Operating and Maintenance Instructions.
49
50   OPERATING AND MAINTENANCE INSTRUCTIONS
51   Assemble material in three-ring or post binders, using an index at the front of each volume and tabs for
52   each system or type of equipment. In addition to the data indicated in the General Requirements, include
53   the following information:
54            Copies of all approved submittals.
55            Manufacturer's wiring diagrams for electrically powered equipment
56            Records of tests performed to certify compliance with system requirements
57            Certificates of inspection by regulatory agencies
58            Parts lists for manufactured equipment
59            Preventive maintenance recommendations
60            Warranties
61            Additional information as indicated in the technical specification sections
62
63



                                                   DSF Project No.
                                                    26 05 00 - 4
 1   TRAINING OF USER AGENCY PERSONNEL
 2   Instruct user agency's personnel in the proper operation and maintenance of systems and equipment
 3   provided as part of this project; video tape all training sessions. Include not less than 16 hours of
 4   instruction, using the Operating and Maintenance manuals during this instruction. Demonstrate startup and
 5   shutdown procedures for all equipment. All training to be during normal working hours.
 6
 7   RECORD DRAWINGS
 8   The Contractor shall maintain at least one copy each of the specifications and drawings on the job site at all
 9   times.
10
11   The DSF will provide the Contractor with a suitable set of contract drawings on which daily records of
12   changes and deviations from contract shall be recorded. Dimensions and elevations on the record drawings
13   shall locate all buried or concealed piping, conduit, or similar items.
14
15   The daily record of changes shall be the responsibility of Contractor's field superintendent. No arbitrary
16   mark-ups will be permitted.
17
18   At completion of the project, the Contractor shall submit the marked-up record drawings to the DSF prior
19   to final payment.
20
21                                             PART 2 – PRODUCTS
22
23   ACCESS PANELS AND DOORS
24   Lay-in Ceilings:
25   Removable lay-in ceiling tiles in 2 x 2 foot or 2 x 4 foot configuration provided under other divisions are
26   sufficient; no additional access provisions are required unless specifically indicated.
27
28   Concealed Spline Ceilings:
29   Removable sections of ceiling tile held in position with metal slats or tabs compatible with the ceiling
30   system used will be provided under other divisions.
31
32   Metal Pan Ceilings:
33   Removable sections of ceiling tile held in position by pressure fit will be provided under other divisions.
34
35   Plaster Walls and Ceilings:
36   16 gauge frame with not less than a 20 gauge hinged door panel, prime coated steel for general
37   applications, stainless steel for use in toilets, showers and similar wet areas, concealed hinges, screwdriver
38   operated cam latch for general application, key lock for use in public areas, UL listed for use in fire rated
39   partitions if required by the application. Use the largest size access opening possible, consistent with the
40   space and the equipment needing service; minimum size is 12" by 12".
41
42   SEALING AND FIRESTOPPING
43   FIRE AND/OR SMOKE RATED PENETRATIONS:
44   Manufacturers:
45   3M, STI/SpecSeal, Tremco, Hilti or approved equal.
46
47   All firestopping systems shall be by the same manufacturer.
48
49   Submittals:
50   Contractor shall submit product data for each firestop system. Submittals shall include product
51   characteristics, performance and limitation criteria, test data, MSDS sheets, installation details and
52   procedures for each method of installation applicable to this project. For non-standard conditions where no
53   UL tested system exists, submit manufacturer's drawings for UL system with known performance for which
54   an engineering judgement can be based upon.
55
56   Product:
57   Firestop systems shall be UL listed or tested by an independent testing laboratory approved by the
58   Department of Commerce.
59
60   Use a product that has a rating not less than the rating of the wall or floor being penetrated. Reference
61   architectural drawings for identification of fire and/or smoke rated walls and floors.
62




                                                   DSF Project No.
                                                    26 05 00 - 5
 1   Contractor shall use firestop putty, caulk sealant, intumescent wrapstrips, intumescent firestop collars,
 2   firestop mortar or a combination of these products to provide a UL listed system for each application
 3   required for this project. Provide mineral wool backing where specified in manufacturer's application detail.
 4
 5   NON-RATED PENETRATIONS:
 6   Conduit Penetrations Through Below Grade Walls:
 7   In exterior wall openings below grade, use a modular mechanical type seal consisting of interlocking
 8   synthetic rubber links shaped to continuously fill the annular space between the uninsulated conduit and the
 9   cored opening or a water-stop type wall sleeve.
10
11   Conduit and Cable Tray Penetrations:
12   At conduit and cable tray penetrations of non-rated interior partitions, floors and exterior walls above
13   grade, use urethane caulk in annular space between conduit and sleeve, or the core drilled opening.
14
15                                              PART 3 - EXECUTION
16
17   EXCAVATION AND BACKFILL
18   Perform all excavation and backfill work to accomplish indicated electrical systems installation. Grade and
19   landscaping shall be restored to its original state.
20
21   CONCRETE WORK
22   Contractor will perform all cast-in-place concrete unless noted otherwise elsewhere. Provide all layout
23   drawings, anchor bolts, metal shapes, and/or templates required to be cast into concrete or used to form
24   concrete for the support of electrical equipment.
25
26   CUTTING AND PATCHING
27   Cutting and patching required to access work in existing walls, in chases, above inaccessible ceilings,
28   below floors, etc., shall be by the Contractor who requires the access, unless shown on the bid documents
29   otherwise or noted otherwise.
30
31   The Contractor shall do all cutting, or fitting of the work as required to make its several parts fit together,
32   or to receive the work of others, as shown or reasonably implied by the drawings or specifications, or as
33   may be directed by DSF. Holes cut in exterior walls and/or roofs shall be waterproofed.
34
35   The Contractor who cuts shall also be responsible for patching. Where cutting and patching is required, the
36   Contractor shall hire individuals skilled in such work to do cutting and patching.
37
38   The Contractor who removes or relocates building components which leaves a remaining opening shall be
39   responsible for patching the opening.
40
41   Patching includes repairing openings to match adjacent construction and painting the surface to match
42   existing. Painting means covering the entire wall where patching is to be done to nearest break point or
43   corner unless indicated to be done by other trades.
44
45   Contractor shall not endanger any work by cutting, digging or otherwise and shall not cut or alter the work
46   of others without their consent.
47
48   Do not pierce beams or columns without permission of DSF and then only as directed in writing. If any
49   ductwork, piping, conduit, etc. is required through walls or floors where no sleeve has been provided, use a
50   core drill or saw cut to prevent damage and structural weakening.
51
52   Wherever any material, finish, or equipment, is damaged, the skilled trade shall accomplish the repair or
53   replacement, in that particular work and the cost shall be charged to the party responsible for the damage.
54   DSF reserves the right to disallow any means and/or methods that, in the opinion of DSF, are harmful to
55   and/or not in the best interest of preserving the improvements receiving the work.
56
57   BUILDING ACCESS
58   Arrange for the necessary openings in the building to allow for admittance of all apparatus. When the
59   building access was not previously arranged and must be provided by this contractor, restore any opening
60   to its original condition after the apparatus has been brought into the building.
61
62
63



                                                     DSF Project No.
                                                      26 05 00 - 6
 1   EQUIPMENT ACCESS
 2   Install all piping, conduit, ductwork, and accessories to permit access to equipment for maintenance.
 3   Coordinate the exact location of wall and ceiling access panels and doors with the Contractor, making sure
 4   that access is available for all equipment and specialties. Where access is required in plaster or drywall
 5   walls or ceilings, furnish the access doors to the contractor and reimburse the contractor for installation of
 6   those access doors.
 7
 8   COORDINATION
 9   The Contractor shall cooperate with other trades and DSF's personnel in locating work in a proper manner.
10   Should it be necessary to raise or lower or move longitudinally any part of the electrical work to better fit
11   the general installation, such work shall be done at no extra cost to the DSF, provided such decision is
12   reached prior to actual installation. The Contractor shall check location of electrical outlets with respect to
13   other installations before installing.
14
15   The Contractor shall verify that all devices are compatible for the surfaces on which they will be used.
16   This includes, but is not limited to light fixtures, panelboards, devices, etc. and recessed or semi-recessed
17   heating units installed in/on architectural surfaces.
18
19   Coordinate all work with other contractors prior to installation. Any installed work that is not coordinated
20   and that interferes with other contractor's work shall be removed or relocated at the installing contractor's
21   expense.
22
23   Cooperate with the testing consultant in ensuring specification Section 26 05 04 compliance. Verify
24   system completion to the testing consultant. Demonstrate the starting, interlocking and control features of
25   each system so the testing contractor can perform its work.
26
27   SLEEVES
28   Pipe sleeves for conduits 6" in diameter and smaller, in new poured concrete construction, shall be schedule
29   40 steel pipe, plastic removable sleeve or sheet metal sleeve, all cast in place.
30
31   In wet area floor penetrations, top of sleeve to be 2 inches above the adjacent floor. In existing wet area
32   floor penetrations, core drill sleeve openings large enough to insert schedule 40 sleeve and grout the area
33   around the sleeve. If a pipe clamp resting on the sleeve supports the pipe penetrating the sleeve, weld a
34   collar or struts to the sleeve that will transfer weight to the existing floor structure. Wet areas for this
35   paragraph are rooms or spaces containing air handling unit coils, converters, pumps, chillers, boilers, and
36   similar waterside equipment.
37
38   Pipe penetrations in existing concrete floors that are not in wet areas may omit the use of schedule 40
39   sleeve and use the core drilled opening as the sleeve.
40
41   SEALING AND FIRESTOPPING
42   Fire and/or Smoke Penetrations:
43   Install approved product in accordance with the manufacturer's instructions where a pipe (i.e. cable tray,
44   bus, cable bus, conduit, wireway, trough, etc.) penetrates a fire rated surface.
45
46   Where firestop mortar is used to infill large fire-rated floor openings that could be required to support
47   weight, provide permanent structural forming. Firestop mortar alone is not adequate to support any
48   substantial weight.
49
50   None-Rated Surfaces:
51   When the opening is through a non-fire rated wall, floor, ceiling or roof the opening must be sealed using
52   an approved type of material.
53
54   Use galvanized sheet metal sleeves in hollow wall penetrations to provide a backing for the sealant. Grout
55   area around sleeve in masonry construction.
56
57   Install escutcheons or floor/ceiling plates where conduit, penetrates non-fire rated surfaces in occupied
58   spaces. Occupied spaces for this paragraph include only those rooms with finished ceilings and the
59   penetration occurs below the ceiling.
60
61   In exterior wall openings below grade, assemble rubber links of mechanical seal to the proper size for the
62   conduit and tighten in place, in accordance with the manufacturer's instructions. Install so that the bolts
63   used to tighten the seal are accessible from the interior of the building or vault.



                                                    DSF Project No.
                                                     26 05 00 - 7
 1   At interior partitions, conduit penetrations are required to be sealed for all clean rooms, laboratories, and
 2   most hospital spaces, computer rooms, dormitory rooms, tele/data/com rooms and similar spaces where the
 3   room pressure or odor transmission must be controlled. Apply sealant to both sides of the penetration in
 4   such a manner that the annular space between the conduit sleeve and the conduit is completely filled.
 5
 6   HOUSEKEEPING AND CLEAN UP
 7   The Contractor shall clean up and remove from the premises, on a daily basis, all debris and rubbish
 8   resulting from its work and shall repair all damage to new and existing equipment resulting from its work.
 9   When job is complete, this Contractor shall remove all tools, excess material and equipment from the site.
10
11                                           END OF SECTION




                                                   DSF Project No.
                                                    26 05 00 - 8
 1                                     SECTION 26 05 26
 2                      GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
 3
 4                                              PART 1 - GENERAL
 5
 6   SCOPE
 7   The work under this section includes grounding electrodes and conductors, equipment grounding
 8   conductors, and bonding. Included are the following topics:
 9   PART 1 - GENERAL
10           Scope
11           Related Work
12           References
13           Performance Requirements
14           Submittals
15           Project Record Documents
16           Regulatory Requirements
17   PART 2 - PRODUCTS
18           Rod Electrode
19           Mechanical Connectors
20           Compression Connectors
21           Exothermic Connections
22           Wire
23           Bus
24   PART 3 - EXECUTION
25           Examination
26           General
27           Medium Voltage System Grounding
28           Less Than 600 Volt System Grounding
29           Field Quality Control
30
31   RELATED WORK
32   Applicable provisions of Division 1 govern work under this Section.
33   Section 26 05 33 – Raceway and Boxes for Electrical Systems
34   Section 27 05 00 – Master Antenna Television System
35
36   REFERENCES
37   NFPA 70 - National Electrical Code.
38   ANSI/IEEE 142 Recommended Practice for Grounding of Industrial and Commercial Power Systems.
39
40   PERFORMANCE REQUIREMENTS
41   Grounding System Resistance: 2ohms maximum at building service entrance.
42
43   SUBMITTALS
44   Product Data: Provide data for grounding electrodes and connections.
45
46   Test Reports: Indicate overall resistance to ground.
47
48   Manufacturer's Instructions: Include instructions for preparation, installation and examination of
49   exothermic connectors.
50
51   PROJECT RECORD DOCUMENTS
52   Accurately record actual locations of grounding electrodes.
53
54   REGULATORY REQUIREMENTS
55   Conform to requirements of NFPA 70.
56
57   Furnish products listed and classified by Underwriters Laboratories, Inc. or testing firm acceptable to
58   authority having jurisdiction as suitable for purpose specified and shown.
59
60                                             PART 2 - PRODUCTS
61
62   ROD ELECTRODE
63   Material: Copper-clad steel.
64   Diameter: 3/4 inch (19 mm) minimum.



                                                     26 05 26 - 1
 1   Length: 10 feet (3.5 m) minimum. Rod shall be driven at least 9' 6" deep.
 2
 3   MECHANICAL CONNECTORS
 4   The mechanical connector bodies shall be manufactured from high strength, high conductivity cast copper
 5   alloy material. Bolts, nuts, washers and lockwashers shall be made of Silicon Bronze and supplied as a part
 6   of the connector body and shall be of the two bolt type.
 7
 8   Split bolt connector types are NOT allowed.
 9
10   The connectors shall meet or exceed UL 467 and be clearly marked with the catalog number, conductor
11   size and manufacturer.
12
13   COMPRESSION CONNECTORS
14   The compression connectors shall be manufactured from pure wrought copper. The conductivity of this
15   material shall be no less than 99% by IACS standards.
16
17   The connectors shall meet or exceed the performance requirements of IEEE 837, latest revision.
18
19   The installation of the connectors shall be made with a compression, tool and die system, as recommended
20   by the manufacturer of the connectors.
21
22   The connectors shall be clearly marked with the manufacturer, catalog number, conductor size and the
23   required compression tool settings.
24
25   Each connector shall be factory filled with an oxide-inhibiting compound.
26
27   EXOTHERMIC CONNECTIONS
28   As manufactured by Cadweld or similar.
29
30   WIRE
31   Material: Stranded copper (aluminum not permitted).
32
33   Grounding Electrode Conductor: Size as shown on drawings, specifications or as required by NFPA 70,
34   whichever is larger.
35
36   Foundation Electrodes: As shown on drawings.
37
38   Manhole, Main Switchgear room and Vault Bonding: No. 4/0 minimum.
39
40   Feeder and Branch Circuit Equipment Ground: Size as shown on drawings, specifications or as required by
41   NFPA 70, whichever is larger. Differentiate between the normal ground and the isolated ground when both
42   are used on the same facility.
43
44   BUS
45   Material: Copper (aluminum not permitted).
46
47   Size: 1/4" X 2" minimum.
48
49                                            PART 3 - EXECUTION
50
51   EXAMINATION
52   Verify that final backfill and compaction has been completed before driving rod electrodes.
53
54   GENERAL
55   Install Products in accordance with manufacturer's instructions.
56
57   Mechanical connections shall be accessible for inspection and checking. No insulation shall be installed
58   over mechanical ground connections.
59
60   Ground connection surfaces shall be cleaned and all connections shall be made so that it is impossible to
61   move them.
62
63   Attach grounds permanently before permanent building service is energized.




                                                     26 05 26 - 2
 1   All grounding electrode conductors shall be installed in PVC conduit or rigid galvanized steel conduit
 2   bonded at both ends to the grounding electrode conductor with an approved grounding fitting.
 3
 4   MEDIUM VOLTAGE SYSTEM GROUNDING
 5   Provide and install a ground bus 18" above finished floor with insulated standoffs 36” on center,
 6   completely around the perimeter of the room (vault) containing the high voltage switchgear and unit
 7   substation. Route bus over door. All connections to bus shall be bolted with Belleville washers and
 8   compression (tool applied) spade lugs or Exothermic.
 9
10   Provide six ground rods equally spaced around high voltage switchgear room. Connect to ground bus with
11   4/0 copper. Exothermic connection shall be made between conductor, ground rod and ground bus.
12
13   Provide separate 4/0 copper conductor from ground bus to:
14            XO terminal of each transformer.
15            Each high voltage switch ground bus.
16            Secondary service equipment ground bus.
17            Transformer high voltage grounded terminal (if required).
18
19   Provide full size 600V copper THHN/THWN or XHHW-2 grounding conductor in each conduit, raceway
20   or enclosure which contains high voltage conductors. Terminate at ground bus of equipment containing
21   high voltage terminations. Connect to ground rod and grounding conductor in manhole.
22
23   Bond each enclosure containing high voltage parts (switches, fuses, transformers, pull boxes, etc.) to room
24   ground bus with 4/0 copper conductor.
25
26   Bond all conduits containing high voltage conductors or secondary service conductors to penetrated
27   enclosures using grounding bushing and #4 copper conductor. Attach to penetrated enclosures using
28   grounding bushing and #4 copper conductor. Attach to penetrated enclosure using compression lug on stud
29   or bolt and Belleville washers.
30
31   Bond all conduits carrying individual grounding or grounding electrode conductors with grounding bushing
32   and separate #4 copper grounding conductor to ground bus.
33
34   Provide #10 stranded wire from each termination shield drain wire to ground bus within enclosure.
35   Connect to nearest grounded conductor if ground bus is not within 24". Route shield drains away from
36   energized parts. Make connections with "Sta-Kon" type terminals or tool applied tap connectors.
37
38   Provide ground rod in each section of each secondary switchboard. Make Exothermic or UL Listed
39   Mechanical connection between 4/0 copper to ground rod and to switchgear ground bus.
40
41   LESS THAN 600 VOLT SYSTEM GROUNDING
42   Provide code sized copper grounding electrode conductor from secondary switchboard ground bus, each
43   separately derived system neutral, secondary service system neutral to street side of water meter, building
44   steel, ground rod, and any concrete encased electrodes. Provide bonding jumper around water meter.
45
46   Bond together system neutrals, service equipment enclosures, exposed non-current carrying metal parts of
47   electrical equipment, metal raceway systems, grounding conductor in raceways and cables, receptacle
48   ground connectors, and plumbing systems.
49
50   Install ground grid under access floors where indicated. Construct grid of #4 AWG bare copper wire
51   installed on 72 inch centers both ways. Bond each access floor support pedestal to grid.
52
53   Bond together each metallic raceway, pipe, duct and other metal object entering space under access floors.
54   Bond to underfloor ground grid. Use #4 AWG bare copper conductor.
55
56   Equipment Grounding Conductor: Provide separate, insulated equipment grounding conductor within each
57   raceway. Terminate each end on suitable lug, bus, enclosure or bushing. Provide a ground wire from each
58   device to the respective enclosure.
59
60   Provide communications system grounding conductor at point of service entrance and connect to building
61   common grounding electrode system.
62
63
64



                                                     26 05 26 - 3
 1   Telecommunications and Audio Visual systems shall be installed with an isolated grounding system which
 2   has only one ground point. That ground point is to be the common grounding electrode system at the
 3   electrical service entrance for the building. Contractor is to provide an isolated grounding conductor from
 4   the electrical service entrance of the building to each Telecommunications Grounding Bus Bar (TGBB) in
 5   each Telecommunication Room. Use a minimum No. 2/0 AWG copper conductor, or as indicated on the
 6   plans, for the telecommunications service grounding conductor. Leave 10 feet slack grounding conductor
 7   at each Telecommunications Room. The grounding conductor MUST NOT be attached to building steel
 8   (except as allowed at the main electrical service entrance).
 9
10   Telecommunications Equipment Rack Grounding: Use a #6 or larger AWG copper conductor from all
11   telecommunications cabinets and racks to the Telecommunications Grounding Bus Bar (TGBB) in each
12   Telecommunication Room.
13
14   FIELD QUALITY CONTROL
15   Inspect grounding and bonding system conductors and connections for tightness and proper installation.
16
17                                                   END OF SECTION




                                                     26 05 26 - 4
 1                                      SECTION 26 05 29
 2                       HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
 3
 4                                              PART 1 - GENERAL
 5
 6   SCOPE
 7   The work under this sections includes conduit and equipment supports, straps, clamps, steel channel, etc,
 8   and fastening hardware for supporting electrical work. Included are the following topics:
 9   PART 1 - GENERAL
10            Scope
11            Related Work
12            Submittals
13            Quality Assurance
14   PART 2 - PRODUCTS
15            Material
16   PART 3 - EXECUTION
17            Installation
18
19   RELATED WORK
20   Applicable provisions of Division 1 govern work under this Section.
21   Section 26 05 33 – Raceway and Boxes for Electrical Systems
22
23   SUBMITTALS
24   Product Data: Provide data for support channel.
25
26   QUALITY ASSURANCE
27   Support systems shall be adequate for weight of equipment and conduit, including wiring, which they
28   carry.
29
30                                             PART 2 - PRODUCTS
31
32   MATERIAL
33   Support Channel: Galvanized.
34
35   Hardware: Corrosion resistant.
36
37   Minimum sized threaded rod for supports shall be 3/8”.
38
39   Conduit clamps, straps, supports, etc., shall be steel or malleable iron. One-hole straps shall be heavy duty
40   type. All straps shall have steel or malleable backing plates when conduit is installed on the interior or
41   exterior surface of any exterior building wall.
42
43                                             PART 3 - EXECUTION
44
45   INSTALLATION
46   Fasten hanger rods, conduit clamps, outlet, junction and pull boxes to building structure using pre-cast
47   insert system, preset inserts, beam clamps, expansion anchors, or spring steel clips (interior metal stud
48   walls only).
49
50   Use toggle bolts or hollow wall fasteners in hollow masonry, plaster, or gypsum board partitions and walls;
51   expansion anchors or preset inserts in solid masonry walls; self-drilling anchors or expansion anchors on
52   concrete surfaces; sheet metal screws in sheet metal studs and wood screws in wood construction.
53
54   Do not use powder-actuated or plastic anchors.
55
56   File and de-bur cut ends of support channel and spray paint with cold galvanized paint to prevent rusting.
57
58   Do not fasten supports to piping, ductwork, mechanical equipment, cable tray or conduit.
59
60   Do not drill structural steel members unless approved by DSF.
61
62   Fabricate supports from galvanized structural steel or steel channel, rigidly welded or bolted to present a
63   neat appearance. Use hexagon head bolts with spring lock washers under all nuts.
64



                                                      26 05 29 - 1
 1   In wet locations, mechanical rooms and electrical rooms install free-standing electrical equipment on 3.5
 2   inch (89 mm) concrete pads.
 3   Install surface-mounted cabinets and panelboards with minimum of four anchors. Provide steel channel
 4   supports to stand cabinet one inch (25 mm) off wall.
 5
 6   Bridge studs top and bottom with channels to support flush-mounted cabinets and panelboards in stud
 7   walls.
 8
 9   Furnish and install all supports as required to fasten all electrical components required for the project,
10   including free standing supports required for those items remotely mounted from the building structure,
11   catwalks, walkways etc.
12
13                                                END OF SECTION




                                                      26 05 29 - 2
 1                                      SECTION 26 05 33
 2                         RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
 3
 4                                             PART 1 - GENERAL
 5
 6   SCOPE
 7   The work under this section includes conduits, surface raceways, multi-outlet assemblies, auxiliary gutters,
 8   wall duct, and boxes for electrical systems including wall and ceiling outlet boxes, floor boxes, and
 9   junction boxes. Included are the following topics:
10   PART 1 - GENERAL
11            Scope
12            Related Work
13            Submittals
14   PART 2 - PRODUCTS
15            Rigid Metal Conduit and Fittings
16            PVC Coated Rigid Metal Conduit
17            Intermediate Metal Conduit (IMC) and Fittings
18            Electrical Metallic Tubing (EMT) and Fittings
19            Flexible Metal Conduit and Fittings
20            Liquidtight Flexible Metal Conduit and Fittings
21            Electrical Nonmetallic Tubing (ENT) and Fittings
22            Rigid Nonmetallic Conduit and Fittings
23            Conduit Supports
24            Surface Metal Raceway
25            Surface Nonmetal Raceway
26            Multi-Outlet Assembly
27            Auxiliary Gutters (Wireways)
28            Wall Duct
29            Outlet Boxes
30            Floor Boxes
31            Pull and Junction Boxes
32            General
33   PART 3 - EXECUTION
34            Conduit Sizing, Arrangement and Support
35            Conduit Installation
36            Conduit Installation Schedule
37            Surface Metal Raceway and Multi-Outlet Assembly Installation
38            Nonmetallic Surface Raceway Installation
39            Auxiliary Gutters (Wireways) Installation
40            Coordination of Box Locations
41            Outlet Box Installation
42            Floor Box Installation
43            Pull and Junction Box Installation
44
45   RELATED WORK
46   Applicable provisions of Division 1 govern work under this section.
47   Section 26 05 26 – Grounding and Bonding for Electrical Systems
48   Section 26 05 29 – Hangers and Supports for Electrical Systems
49
50   SUBMITTALS
51   Surface Raceway System - submit product data and catalog sheets for all components.
52
53   Boxes - provide product data showing configurations, finishes, dimensions, and manufacturer's instructions.
54
55
56                                             PART 2 - PRODUCTS
57
58   RIGID METAL CONDUIT AND FITTINGS
59   Conduit: Heavy wall, galvanized steel, schedule 40, threaded.
60
61   Fittings and Conduit Bodies: Use all steel threaded fittings and conduit bodies.
62
63
64



                                                     26 05 33 - 1
 1   PVC COATED RIGID METAL CONDUIT
 2   PVC Externally Coated Conduit: Rigid heavy wall, schedule 40, steel conduit with external 40 mil (0.1
 3   mm) PVC coating. Conduit must be hot dipped galvanized inside and out including threads. The PVC
 4   coating bond to the galvanized steel conduit shall be stronger than the tensile strength of the coating itself.
 5
 6   Fittings and Conduit Bodies: Threaded type, material to match conduit. PVC coated fittings and couplings
 7   shall have specially formed sleeves to tightly seal to conduit PVC coating. The sleeves shall extend beyond
 8   the fitting or coupling a distance equal to the pipe outside steel diameter or two inches (50 mm) whichever
 9   is greater.
10
11   INTERMEDIATE METAL CONDUIT (IMC) AND FITTINGS
12   Conduit: Galvanized steel, threaded.
13
14   Fittings and Conduit Bodies: Use all steel threaded fittings and conduit bodies.
15
16   ELECTRICAL METALLIC TUBING (EMT) AND FITTINGS
17   Conduit: Steel, galvanized tubing.
18
19   Fittings: All steel, set screw, water tight, concrete tight. No push-on or indenter types permitted.
20   Conduit Bodies: All steel threaded conduit bodies.
21
22   FLEXIBLE METAL CONDUIT AND FITTINGS
23   Conduit: steel, galvanized, spiral strip.
24
25   Fittings and Conduit Bodies: All steel, galvanized, or malleable iron.
26
27   LIQUIDTIGHT FLEXIBLE METAL CONDUIT AND FITTINGS
28   Conduit: flexible, steel, galvanized, spiral strip with an outer Liquidtight, nonmetallic, sunlight-resistant
29   jacket.
30
31   Fittings and Conduit Bodies: ANSI/NEMA FB 1, compression type. There shall be a metallic cover/insert
32   on the end of the conduit inside the connector housing to seal the cut conduit end.
33
34   ELECTRICAL NONMETALLIC TUBING (ENT) AND FITTINGS
35   Conduit: ENT (smurf tube), UL listed and NEC recognized.
36
37   Fittings: One piece quick connect fittings for 1/2 inch to 1 inch size and schedule 40 cemented fittings for
38   larger size. When installed in concrete, fittings shall be suitable for damp locations and shall be concrete–
39   tight, stub-ups and stub-downs kits shall meet manufacturer’s recommendations.
40
41   RIGID NONMETALLIC CONDUIT AND FITTINGS
42   Conduit: Schedule 40 PVC minimum, Listed, sunlight resistant, rated for 90 0 C conductors.
43
44   Fittings and Conduit Bodies: NEMA TC 2, Listed.
45
46   CONDUIT SUPPORTS
47   See section 26 05 29.
48
49   SURFACE METAL RACEWAY
50   Description: Sheet metal channel with fitted cover, suitable for use as surface metal raceway.
51
52   Fittings: Couplings, elbows, and connectors designed for use with raceway system.
53
54   Boxes and Extension Rings: Designed for use with raceway systems.
55
56   SURFACE NONMETAL RACEWAY
57   Description: Nonmetallic channel with fitted cover, suitable for use as surface raceway.
58
59   Fittings: Couplings, elbows, and connectors designed for use with raceway system.
60
61   Boxes and Extension Rings: Designed for use with raceway systems.
62
63
64



                                                       26 05 33 - 2
 1   MULTI-OUTLET ASSEMBLY
 2   Description: Sheet metal channel with fitted cover, suitable for use as a multi-outlet assembly.
 3
 4   Fittings: Couplings, elbows, and connectors designed for use with multi-outlet system.
 5
 6   AUXILIARY GUTTERS (Wireways)
 7   Description: General purpose type wireway without knockouts.
 8
 9   Size/Type: as indicated on Drawings.
10
11   Finish: Rust inhibiting primer coat with gray enamel finish.
12
13   WALL DUCT
14   Description: Sheet metal wall duct suitable for installation of X-ray cables; with covers and accessories.
15
16   OUTLET BOXES
17   Sheet Metal Outlet Boxes: galvanized steel, with stamped knockouts.
18
19   Luminaire and Equipment Supporting Boxes: Rated for weight of equipment supported;
20   include 3/8 inch male fixture studs where required.
21
22   Concrete Ceiling Boxes: Concrete type.
23
24   Cast Boxes: Cast ferroalloy, or aluminum type deep type, gasketed cover, threaded hubs.
25
26   FLOOR BOXES
27   Floor Boxes for Installation in Cast-In-Place Concrete Floors: cast iron or formed steel.
28
29   PULL AND JUNCTION BOXES
30   Pull boxes and junction boxes shall be minimum 4 inch square (100 mm) by 2 1/8th inches (54 mm) deep
31   for use with 1 inch (25 mm) conduit and smaller. On conduit systems using 1 1/4 inch (31.75 mm) conduit
32   or larger, pull and junction boxes shall be sized per NEC but not less than 4 11/16 inch square (117 mm).
33
34   For telecommunication, fiber optic, security, and other low voltage cable installations the NEC box size
35   requirements shall apply. All boxes, used on telecommunication, security, other low voltage and fiber optic
36   systems with conduits of 1 1/4” and larger, shall be sized per the NEC conduit requirements. For
37   determining box size, the conduit is the determining factor not the wire size.
38
39   Sheet Metal Boxes: code gauge galvanized steel, screw covers, flanged and spot welded joints and corners.
40
41   Sheet Metal Boxes Larger Than 12 Inches (300 mm) in any dimension shall have a hinged cover or a chain
42   installed between box and cover.
43
44   Cast Metal Boxes for Outdoor and Wet Location Installations: Type 4 and Type 6, flat-flanged,
45   surface-mounted junction box, UL listed as raintight. Galvanized cast iron or aluminum box and cover
46   with ground flange, neoprene gasket, and stainless steel cover screws.
47
48   Fiberglass or Concrete Handholes with weatherproof cover of non-skid finish shall be used for
49   underground installations.
50
51   Box extensions and adjacent boxes within 48” of each other are not allowed for the purpose of creating
52   more wire capacity.
53
54   Junction boxes 6" x 6" or larger size shall be without stamped knock-outs.
55
56   Wireways shall not be used in lieu of junction boxes.
57
58   GENERAL
59   All steel fittings and conduit bodies shall be galvanized.
60
61   No cast metal, split or gland type fittings permitted.
62
63   Condulets larger than 2 inch (50 mm) not permitted except as approved or detailed.
64



                                                       26 05 33 - 3
 1   All condulet covers must be fastened to the condulet body with screws and be of the same manufacture.
 2
 3   Wireways and gutters shall not be used in lieu of pull boxes and condulets.
 4
 5   All boxes shall be of sufficient size to provide free space for all conductors enclosed in the box and shall
 6   comply with NEC requirements.
 7
 8                                             PART 3 - EXECUTION
 9
10   CONDUIT SIZING, ARRANGEMENT, AND SUPPORT
11   EMT is permitted to be used in sizes 4" (50 mm) and smaller for power and telecommunication systems.
12
13   Size power conductor raceways for conductor type installed. Conduit size shall be 1/2 inch (13 mm)
14   minimum except as specified elsewhere. Caution: Per the NEC, the allowable conductor ampacity is
15   reduced when more than three current-carrying conductors are installed in a raceway. Contractor
16   must take the NEC ampacity adjustment factors into account when sizing the raceway and wiring
17   system.
18
19   Size conduit for all other wiring, including but not limited to data, control, security, fire alarm,
20   telecommunications, signal, video, etc. shall be sized per number of conductors pulled and their cross-
21   section. 40% fill shall be maximum for all new conduit fills.
22
23   Arrange conduit to maintain headroom and present a neat appearance.
24
25   Route exposed conduit and conduit above accessible ceilings parallel and perpendicular to walls and
26   adjacent piping.
27
28   Maintain minimum 6 inch (150 mm) clearance between conduit and piping. Maintain 12 inch (300 mm)
29   clearance between conduit and heat sources such as flues, steam pipes, and heating appliances.
30
31   Arrange conduit supports to prevent distortion of alignment by wire pulling operations. Fasten conduit
32   using galvanized pipe straps, conduit racks (lay-in adjustable hangers), clevis hangers, or bolted split
33   stamped galvanized hangers.
34
35   Group conduit in parallel runs where practical and use conduit rack (lay-in adjustable hangers) constructed
36   of steel channel with conduit straps or clamps. Provide space for 25 percent additional conduit.
37
38   Do not fasten conduit with wire or perforated pipe straps. Before conductors are pulled, remove all wire
39   used for temporary conduit support during construction.
40
41   Support and fasten metal conduit at a maximum of 8 feet (2.4 m) on center.
42
43   Supports shall be independent of the installations of other trades, e.g. ceiling support wires, HVAC pipes,
44   etc., unless so approved or detailed.
45
46   In general, all conduit shall be concealed except where noted on the drawings or approved by the
47   Architect/Engineer. Contractor shall verify with Architect/Engineer all surface conduit installations except
48   in mechanical rooms.
49
50   Changes in direction shall be made with symmetrical bends, cast steel boxes, stamped metal boxes or cast
51   steel conduit bodies.
52
53   No continuous conduit run shall exceed 100 feet (30 meters) without a junction box.
54
55   CONDUIT INSTALLATION
56   Cut conduit square using a saw or pipecutter; de-burr cut ends.
57
58   Conduit shall not be fastened to the corrugated metal roof deck.
59
60   Bring conduit to the shoulder of fittings and couplings and fasten securely.
61
62   Use conduit hubs for fastening conduit to cast boxes. Use sealing locknuts or conduit hubs for fastening
63   conduit to sheet metal boxes in damp or wet locations (sheet metal boxes 4 & 11/16th” square and larger,
64   shall contain NO pre-punched or concentric knockouts).



                                                      26 05 33 - 4
 1   All conduit terminations (except for terminations into conduit bodies) shall use connectors or conduit hubs
 2   with one locknut or shall use double locknuts (one each side of box wall) and insulating bushing. Provide
 3   bushings for the ends of all conduit not terminated in box walls. Refer to Section 26 05 26 – Grounding
 4   and Bonding for Electrical Systems for grounding bushing requirements.
 5
 6   Install no more than the equivalent of three 90 degree bends between boxes.
 7
 8   Use hydraulic one-shot conduit bender or factory elbows for bends in conduit larger than 2 inch (50 mm)
 9   size unless sweep elbows are required.
10
11   Conduit shall be bent according to manufacturers recommendations. Torches or open flame shall not be
12   used to aid in bend of PVC conduit.
13
14   Use suitable conduit caps or other approved seals to protect installed conduit against entrance of dirt and
15   moisture.
16
17   Provide 1/8 inch (3 mm) nylon pull string in empty conduit, except sleeves and nipples.
18
19   Install expansion-deflection joints where conduit crosses building expansion joints. Note: expansion-
20   deflection joints are not required where conduit crosses building control joints if the control joint does not
21   act as an expansion joint. Install expansion fitting in PVC conduit runs as recommended by the
22   manufacturer.
23
24   Avoid moisture traps where possible. Where moisture traps are unavoidable, provide junction boxes with
25   drain fittings at conduit low points.
26
27   Where conduit passes between areas of differing temperatures such as into or out of cool rooms, freezers,
28   unheated and heated spaces, buildings, etc., provide Listed conduit seals to prevent the passage of moisture
29   and water vapor through the conduit.
30
31   Route conduit through roof openings for piping and ductwork where possible.
32
33   Conduit is not permitted in any slab topping of two inches (50 mm) or less.
34
35   Ground and bond conduit under provisions of Section 26 05 26.
36
37   Maximum Size Conduit in Slabs Above Grade: 3/4 inch (19 mm). Do not route conduits to cross each
38   other in slabs above grade.
39
40   PVC conduit shall transition to galvanized rigid metal conduit before it enters a concrete pole base,
41   foundation, wall (where exposed) or up through a concrete floor.
42
43   Use PVC-coated rigid steel factory elbows for bends in plastic conduit larger than 2”. PVC elbows are
44   allowed in PVC conduit runs 2” and smaller.
45
46   All conduit installed underground (exterior to building) shall be buried a minimum of 24” below finished
47   grade, whether or not the conduit is concrete encased.
48
49   PVC conduit shall be cleaned with solvent, and dried before application of glue. The temperature rating of
50   glue/cement shall match weather condition. Apply full even coat of cement/glue to entire area that will be
51   inserted into fitting. The entire installation shall meet manufacturers recommendations.
52
53   Medium voltage conduit may be installed in interior locations other than electrical vaults only with special
54   permission from Architect/Engineer.
55
56   CONDUIT INSTALLATION SCHEDULE
57   Conduit other than that specified below for specific applications shall not be used.
58
59   Underground Installations Within Five Feet (1.5 m) of Foundation Wall: Rigid steel conduit.
60
61   Underground Installations More than Five Feet (1.5 m) From Foundation Wall: Rigid steel conduit.
62
63   Under Slab on Grade Installations: Schedule 40 PVC conduit.
64



                                                      26 05 33 - 5
 1   Exposed Outdoor Locations: Rigid steel conduit.
 2
 3   Concealed in Concrete and Block Walls: Rigid steel conduit.
 4
 5   Within Concrete Slab: Schedule 40 PVC conduit.
 6
 7   Wet Interior Locations: Rigid steel conduit.
 8
 9   Concealed Dry Interior Locations: Electrical metallic tubing.
10
11   Exposed Dry Interior Locations: Electrical metallic tubing.
12
13   Medium Voltage Applications (Interior Locations): Rigid steel conduit.
14
15   SURFACE METAL RACEWAY AND MULTI-OUTLET ASSEMBLY INSTALLATION
16   Use flat-head screws to fasten channel to surfaces every twenty-four (24) inches. Mount plumb and level.
17
18   Use suitable insulating bushings and inserts at connections to outlets and corner fittings.
19
20   Maintain grounding continuity between raceway components to provide a continuous grounding path under
21   provisions of Section 26 05 26.
22
23   Fastener Option: Use clips and straps suitable for the purpose.
24
25   NONMETALLIC SURFACE RACEWAY INSTALLATION
26   Use flat headed screws with appropriate anchors to fasten channel to surfaces secured every twenty-four
27   (24) inches. Mount plumb and level. All surface mounted devices shall be fastened to the wall utilizing
28   flat head screws along with appropriate anchors. No device shall be adhered to the wall surface using two-
29   faced tape or any means other than as described above.
30
31   Use suitable insulating bushings and inserts at connections to outlets and corner fittings.
32
33   In areas where the walls cannot be fished, the station cable serving these outlets shall be covered with
34   raceways. No exposed wire shall be permitted within offices, laboratories, and conference rooms or like
35   facilities.
36
37   The non-metallic raceway shall have a screw applied base. Both the base and cover shall be manufactured
38   of rigid PVC materials.
39
40   The raceway shall originate from a surface mounted box mounted adjacent to and at the same height as
41   existing electrical boxes in the room, be attached to the wall and terminate above the ceiling.
42
43   All fittings including, but not limited to, extension boxes, elbows, tees, fixture bodies shall match the color
44   of the raceway.
45
46   The raceway and all systems devices shall be UL listed and exhibit nonflammable self extinguishing
47   characteristics, tested to specifications of UL94V-0.
48
49   The raceway and all systems devices shall adhere to the EIA/TIA Category 5e bend radius standard.
50   AUXILIARY GUTTERS INSTALLATION
51   Bolt auxiliary gutter to wall using two-piece hangers or steel channels fastened to the wall or in
52   self-supporting structure.
53
54   Gasket each joint in oil-tight gutter.
55
56   Mount rain-tight gutter in horizontal position only.
57
58   Maintain grounding continuity between raceway components to provide a continuous grounding path under
59   provisions of Section 26 05 26.
60
61   COORDINATION OF BOX LOCATIONS
62   Provide electrical boxes as shown on Drawings, and as required for splices, taps, wire pulling, equipment
63   connections, and code compliance.
64



                                                      26 05 33 - 6
 1   Electrical box locations shown on Contract Drawings are approximate unless dimensioned. Verify location
 2   of floor boxes and outlets in offices and work areas prior to rough-in.
 3
 4   No outlet shall be located where it will be obstructed by other equipment, piping, lockers, benches,
 5   counters, etc.
 6
 7   Boxes shall not be fastened to the metal roof deck.
 8
 9   It shall be the Contractor's responsibility to study drawings pertaining to other trades, to discuss location of
10   outlets with workmen installing other piping and equipment and to fit all electrical outlets to job conditions.
11
12   In case of any question or argument over the location of an outlet, the Contractor shall refer the matter to
13   the Architect/Engineer and install outlet as instructed by the Architect/Engineer.
14
15   The proper location of each outlet is considered a part of this contract and no additional compensation will
16   be paid to the Contractor for moving outlets which were improperly located.
17
18   Locate and install boxes to allow access to them. Where installation is inaccessible, coordinate locations
19   and provide 18 inch (450 mm) by 24 inch (600 mm) access doors.
20
21   Locate and install to maintain headroom and to present a neat appearance.
22
23   Install boxes to preserve fire resistance rating of partitions and other elements, using approved materials
24   and methods.
25
26   OUTLET BOX INSTALLATION
27   Do not install boxes back-to-back in walls. Provide minimum 6 inch (150 mm) separation, except provide
28   minimum 24 inch (600 mm) separation in acoustic-rated walls.
29
30   Power:
31   Recessed (1/4” maximum) outlet boxes in masonry, concrete or tile construction shall be masonry type,
32   minimum 4 inch square. Device covers shall be square-cut except rounded corner plaster rings are allowed
33   in drywall applications. Angle cut plaster rings are not permitted. Coordinate masonry cutting to achieve
34   neat openings for boxes.
35
36   Low Voltage:
37   Recessed (1/4” maximum) outlet boxes in masonry, concrete or tile construction shall be masonry type,
38   minimum 4 11/16 inch square. Device covers shall be square-cut except rounded corner plaster rings are
39   allowed in drywall applications. Angle cut plaster rings are not permitted. Coordinate masonry cutting to
40   achieve neat openings for boxes.
41
42   Provide knockout closures for unused openings.
43
44   Support boxes independently of conduit except for cast boxes that are connected to two rigid metal
45   conduits, both supported within 12 inches (300 mm) of box.
46
47   Use multiple-gang boxes where more than one device are mounted together; do not use sectional boxes.
48   Provide non-metallic barriers to separate wiring of different voltage systems.
49
50   Install boxes in walls without damaging wall insulation.
51
52   Coordinate mounting heights and locations of outlets mounted above counters, benches, and backsplashes.
53
54   Ceiling outlets shall be 4 inch (100 mm) octagon or 4 inch square, minimum 2-1/8 inch (54 mm) deep
55   except that concrete boxes and plates will be approved where applicable. Position outlets to locate
56   luminaires as shown on reflected ceiling plans. All ceiling outlets shall be equipped with 3/8 inch (10 mm)
57   fixture studs.
58
59   In inaccessible ceiling areas, position outlets and junction boxes within 6 inches (150 mm) of recessed
60   luminaire, to be accessible through luminaire ceiling opening.
61
62   Provide recessed outlet boxes in finished areas; secure boxes to interior wall and partition studs, accurately
63   positioning to allow for surface finish thickness. Use stamped steel stud bridges for flush outlets in hollow
64   stud wall, and adjustable steel channel fasteners for flush ceiling outlet boxes.



                                                      26 05 33 - 7
 1   Align wall-mounted outlet boxes for switches, thermostats, and similar devices.
 2
 3   Provide cast ferroalloy or aluminum outlet boxes in exterior and wet locations.
 4
 5   Surface wall outlets shall be 4 inch (100 mm) square with raised covers for one and two gang requirements.
 6   For three gang or larger requirements, use gang boxes with non-overlapping covers.
 7
 8   FLOOR BOX INSTALLATION
 9   Set boxes level and flush with finish flooring material.
10
11   PULL AND JUNCTION BOX INSTALLATION
12   Locate pull boxes and junction boxes above accessible ceilings, in unfinished areas or furnish and install
13   DSF approved access panels in non-accessible ceilings where boxes are installed.
14
15   Support pull and junction boxes independent of conduit.
16
17                                                END OF SECTION




                                                      26 05 33 - 8
 1                                           SECTION 27 00 00
 2                                  FIBER OPTIC CABLE AND EQUIPMENT
 3
 4                                              PART 1 - GENERAL
 5
 6   SCOPE
 7   This section describes the products and execution requirements relating to furnishing and installation of
 8   fiber optic cabling, termination components and related sub-systems as part of a cable system installation at
 9   the Central Wisconsin Center and Mendota Mental Health Institute. Included are the following topics:
10   PART 1 - GENERAL
11             Scope
12             Related Work
13             Regulatory References
14             Design Intent
15             Work Sequence
16             Submittals
17             Project Record Documents
18             Quality Assurance
19             Delivery, Storage and Handling
20             Drawings
21   PART 2 - PRODUCTS
22             Backbone Fiber Optic Cable
23             Duct Type Fiber Optic Cable
24             Direct Buried Type Fiber Optic Cable
25             Indoor Type Fiber Optic Cable
26             Indoor/Outdoor Fiber Optic Cable
27             Optical Fiber Specification
28             Fiber Optic Connectors
29             Fiber Optic Patch Panels
30             Equipment Rack
31             Equipment Cabinets (Wall Mount)
32             Flexible Nonmetallic Innerduct and Fittings
33             Miscellaneous Materials
34   PART 3 - EXECUTION
35             General
36             Innerduct
37             Cable Termination
38             Testing and Acceptance
39             Documentation
40             As-Built Construction Drawings
41             Warranty
42
43   RELATED WORK
44   Applicable provisions of Division 1 govern work under this Section.
45   Section 27 05 00 – Master Antenna Television System
46
47   REGULATORY REFERENCES
48   All work and materials shall conform in every detail to the rules and requirements of the National Fire
49   Protection Association (NFPA), the Wisconsin Electrical Code and present manufacturing standards.
50
51   All materials shall be listed by UL and shall bear the UL label. If UL has no published standards for a
52   particular item, then other national independent testing standards shall apply and such items shall bear
53   those labels. Where UL has an applicable system listing and label, the entire system shall be so labeled.
54
55   Other applicable standards are as follows: ANSI, TIA/EIA Standards, IEEE
56
57   DESIGN INTENT
58   Fiber optic cables shall be installed in conduit in building riser pathways, ductbanks, cable trays, and/or as
59   identified on the drawings. Backbone intra-building fiber optic cabling shall be installed in conduit and/or
60   cable tray.
61
62   All cables and related termination, support and grounding hardware, bonding, shall be furnished, installed,
63   wired, tested, labeled, and documented by the Contractor, as detailed in the following sections.




                                                      27 00 00 - 1
 1   The Contractor shall provide all labor and materials necessary to construct the system as described herein.
 2   This includes - but is not limited to - furnishing and installing cable, cable supports, innerduct, racking and
 3   termination components, termination, testing, labeling and documentation.
 4
 5   WORK SEQUENCE
 6   During the construction period, coordinate schedule and operations with the State of Wisconsin, Division
 7   of State Facilities Construction Representative and Owner.
 8
 9   SUBMITTALS
10   Under the provisions of Section 26 05 00 and Division 1, prior to the start of work the Contractor shall
11   submit:
12
13   Six (6) sets of Manufacturer’s Data covering all products proposed indicating construction, materials,
14   ratings and all other parameters identified in Part 2 (Products) below.
15
16   Submittals should be grouped to include complete documentation of related systems, products and
17   accessories in a single submittal. Where applicable, dimensions should be marked in units to match those
18   specified.
19
20   Submittals shall be original catalog sheets, photocopies, or electronic format (ADOBE Portable Document
21   format “.pdf”) thereof. Facsimile (fax) sheets shall not be accepted.
22
23   The Engineer shall review the Submittals and annotate them indicating approvals and shall return to the
24   contractor.
25
26   Work shall not proceed without the Engineer’s approval of the submitted items.
27
28   If materials are furnished as specified no further qualifications is necessary, except for items requiring shop
29   drawings. However, if the Contractor wishes to substitute another manufacturer and/or catalog number, the
30   following information in triplicate shall be submitted to the Engineer:
31
32            A complete description of the material which the contractor proposes to substitute (shop drawings,
33            illustrations, catalog data, performance characteristics, etc.) and the reason for the substitution
34            identifying any benefit to the Owner.
35
36   The Contractor shall receive approval from the Engineer on all substitutions of material. No substituted
37   materials shall be installed except by written approval from the Engineer.
38
39   PROJECT RECORD DOCUMENTS
40   Submit and record documents under provisions of 26 05 00.
41
42   Accurately record exact sizes, locations and quantities of cables.
43
44   QUALITY ASSURANCE
45   The manufacturer shall be a company specializing in communication cable and/or accessories with a
46   minimum of five years documented experience in producing cable and/or accessories similar to those
47   specified below.
48
49   The contractor shall have been in this line of business for a minimum of five (5) years and completed four
50   (4) jobs of the magnitude specified in the following sections.
51
52   The installing contractor shall have at a minimum one (1) Certified Installer trained to the latest industry
53   standards to ensure the most reliable installation available.
54
55   DELIVERY, STORAGE AND HANDLING
56   Cable shall be stored according to manufacturer's recommendations as minimum. In addition, cable must be
57   stored in a location protected from vandalism and weather. If cable is stored outside, it must be covered
58   with opaque plastic or canvas with provision for ventilation to prevent condensation and for protection
59   from weather. If air temperature at cable storage location will be below 4 degrees C., the cable shall be
60   moved to a heated (10 degrees C. minimum) location.
61
62   If the contractor wishes to have a trailer on site for storage of materials, arrangements shall be made with
63   the Owner. If necessary, cable shall be stored off site at the contractor's expense.
64



                                                      27 00 00 - 2
 1   DRAWINGS
 2   It shall be understood that the electrical and telecommunication details and drawings provided with the
 3   specification package are diagrammatic. They are included to show the intent of the specifications and to
 4   aid the Contractor in bidding the job. The Contractor shall make allowance in the bid proposal to cover
 5   whatever work is required to comply with the intent of the plans and specifications.
 6
 7   The Contractor shall verify all dimensions at the site and be responsible for their accuracy.
 8
 9   Prior to submitting the bid, the Contractor shall call the attention of the Engineer to any materials or
10   apparatus the Contractor believes to be inadequate and to any necessary items of work omitted, within ten
11   (10) days prior to the Bid Due Date.
12
13                                              PART 2 - PRODUCTS
14
15   BACKBONE FIBER OPTIC CABLE
16   Cables shall incorporate optical fibers meeting the specifications detailed in the sub-section(s) below.
17   Backbone fiber optic cable sizing (fiber count) shall be per project drawings. Fiber cables installed in a
18   plenum area shall be installed in the appropriate sized conduit.
19
20   DUCT TYPE FIBER OPTICAL CABLE
21   This cable shall be suitable for installation in underground duct and in innerduct.
22
23   Cable shall be a Loose Buffer design.
24
25   Cable materials shall be all dielectric (no conductive materials).
26
27   Cable shall be filled with a water-blocking material.
28
29   Outer Sheath:
30   The outer Sheath shall be Polyethylene (PE) and free of holes, splits, and blisters. The outer sheath shall be
31   marked with the manufacturer’s name, words identifying the cable type (e.g. “Optical Cable” or “Fiber
32   Optic Cable”), year of manufacture, and sequential length markings. The actual length of the cable shall be
33   within -0/+1% of the length markings. The marking shall be in a contrasting color to the cable jacket.
34
35   Temperature Range:
36   Storage:                   -40o to +70oC (no irreversible change in attenuation)
37   Operating                  -40o to +70oC
38   Installation               -30o to +70oC
39
40   Humidity Range:
41                              0 to 100%
42
43   Maximum Tensile Strength:
44   During Installation:  2700 Newton (600 lb. force) (no irreversible change in attenuation)
45   Long Term:            890 N (200 lb. force)
46
47   Bending Radius:
48   During Installation:       20 times cable diameter
49   No Load:                   10 times cable diameter
50
51   DIRECT BURIED TYPE FIBER OPTIC CABLE
52   This cable shall be suitable for direct burial.
53
54   Cable shall incorporate a corrugated Steel Armor Tape to provide for resistance to rodent attack and all
55   other cable materials shall be all dielectric (no conductive materials).
56
57   Cable shall be filled with a water blocking compound.
58
59   Outer Sheath:
60   Polyethylene (PE)
61   The outer sheath shall be marked with the manufacturer’s name, words identifying the cable type (e.g.
62   “Optical Cable” or “Fiber Optic Cable”), year of manufacture, and sequential length markings. The actual
63   length of the cable shall be within -/+1% of the length markings. The marking shall be in a contrasting
64   color to the cable jacket.



                                                      27 00 00 - 3
 1   Temperature Range:
 2   Storage:                     -40o to +70oC (no irreversible change in attenuation)
 3   Operating                    -40o to +70oC
 4
 5   Humidity Range:
 6                                0 to 100%
 7
 8   Maximum Tensile Strength:
 9   During Installation:  2700 Newton (600 lb. force) (no irreversible change in attenuation)
10   Long Term:            890 N (200 lb. force)
11
12   Bending Radius:
13   During Installation:         20 times cable diameter
14   No Load:                     10 times cable diameter
15
16   INDOOR TYPE FIBER OPTIC CABLE
17   This cable shall be suitable for installation in building riser systems, in conduit, in cable tray or in
18   innerduct. Cable shall carry an OFNR rating (Optical Fiber Non-Conductive Riser).
19
20   Cable materials shall be all dielectric (no conductive material).
21
22   Outer Sheath:
23    PVC
24   The outer sheath shall be marked with the manufacture’s name, date of manufacture, fiber type, flame
25   rating, UL symbol, and sequential length markings every two feet.
26
27   Temperature Range:
28   Storage:                     -40o to +70oC (no irreversible change in attenuation)
29   Operating                    -40o to +70oC
30
31   Humidity Range:
32                                0 to 100%
33
34   Max. Tensile Load (Riser and Tie)
35   During Installation:    1332 Newton (300 lb. force) (no irreversible change in attenuation)
36   Long Term:              600 N (135-lb. force)
37
38   Bending Radius:
39   During Installation:         20 times cable diameter
40   No Load:                     10 times cable diameter
41
42   INDOOR/OUTDOOR FIBER OPTIC CABLE
43   “Hybrid” cables suitable for installation in multiple environments (e.g. underground duct and building
44   risers) may be used at Contractor’s option.
45
46   Such cables shall meet all specifications noted above for cables designated for each environment through
47   which the cable shall pass.
48
49   Backbone Fiber Optic Cable
50   This cable shall be suitable for installation free-air, in building Risers, in Conduit, in Cable Tray and/or in
51   Innerduct.
52
53   Cable Materials shall be all dielectric (no conductive materials).
54
55   Cabling shall carry an OFNR rating (Optical Fiber Non-Conductive Riser) and shall be listed as being
56   suitable for use in a vertical run in a shaft or from floor to floor and shall be listed as having fire-resistant
57   characteristics capable of preventing the carrying of fire from floor to floor.
58
59   Outer Sheath: PVC
60   The Outer Sheath shall be marked with the manufacturer's name, date of manufacture, fiber type, flame
61   rating, UL symbol, and sequential length markings every two feet.
62
63
64



                                                        27 00 00 - 4
 1   Temperature Range:
 2   Storage:                   -40o to +70 C (no irreversible change in attenuation)
 3   Operating:                 -20o to +70 C (OFNR)
 4   Humidity Range:            0 to 100%
 5
 6   Max. Tensile Load (Backbone Intra-building)
 7           12-fibers
 8          During Installation:    1332 Newton’s (300 lb. force) (no irreversible change in attenuation)
 9          Long Term:              600 N (135 lb. force)
10          <12-fibers
11          During Installation:    1000 Newton’s (225 lb. force) (no irreversible change in attenuation)
12          Long Term:              300 N (67 lb. force)
13
14   Bending Radius:
15   During Installation:       20 times cable diameter
16   No Load:                   10 times cable diameter.
17
18   OPTICAL FIBER SPECIFICATION
19   General
20   The fiber count in each cross-section will vary. For quantities and other design information, refer to the
21   Project Drawings.
22
23   All optical fibers shall be sufficiently free of surface imperfections and inclusions to meet the optical,
24   mechanical, and environmental requirements of this specification. Factory optical fiber splices are not
25   allowed.
26
27   All fibers shall have been subjected to a minimum tensile proof test by the fiber manufacturer equivalent to
28   100-kpsi.
29
30   All fibers in each cable shall be guaranteed to meet the stated specifications.
31
32   Single Mode Optical Fibers
33   Fiber Type              Single mode; doped silica core surrounded by a concentric glass cladding.
34
35   Core Diameter:             8-9 µm. All fibers shall be of the same nominal core diameter and profile.
36
37   Cladding Diameter:         125±1.0µm
38
39   Cladding Non-circularity:  1%
40   Core to Cladding Offset  0.8 µm
41
42   Fiber Coating Diameter:   245±15µm (primary coating).
43                             900-m (nominal) secondary coating (tight buffer)
44   All coatings shall be mechanically strippable without damaging the optical fiber.
45
46   Cutoff Wavelength (cabled fiber; ccf) < 1260-nm.
47
48   Mode Field Diameter:       8.3 - 9.8 nm at 1300-nm; 10.5±1.0 µm at 1550-nm.
49
50   Zero Dispersion Wavelength (0): 1301.5 nm < 0 < 1321.5 nm
51
52   Zero Dispersion Slope (S0): < 0.092 ps/nm2*km
53   Fiber Attenuation (max. @ 235 C; Backbone):
54                             Intra-Building               Inter-Building
55            @ 1300-nm        1.0 dB/km                    0.5 dB/km
56            @ 1550-nm        1.0 dB/km                    0.5 dB/km
57
58   When tested in accordance with FOTP-3, "Procedure to Measure Temperature Cycling Effects on Optical
59   Fibers, Optical Cable, and Other Passive Fiber Optic Components," the average change in attenuation over
60   the rated temperature range of the cable shall not exceed 0.05 dB/km at 1550 nm for single-mode fiber. The
61   magnitude of the maximum attenuation change of each individual fiber shall not be greater than 0.15
62   dB/km at 1550 nm.
63
64



                                                      27 00 00 - 5
 1   Fiber Dispersion (maximum):
 2            1285-1330-nm 3.2-ps/nm*km
 3            @ 1550-nm           18-ps/nm*km
 4   No single mode optical fiber shall show a point discontinuity greater than 0.1 dB at the specified
 5   wavelengths. Such a discontinuity or any discontinuity showing a reflection at that point shall be cause for
 6   rejection of that fiber by the Owner.
 7
 8   FIBER OPTIC CONNECTORS
 9   All fiber optic cables shall be connectorized using ST type connectors.
10
11   FIBER OPTIC PATCH PANELS
12   All terminated fibers shall be mated. Couplers shall be mounted on a panel that, in turn, snaps into the
13   enclosure. The proposed enclosure shall be designed to accommodate a changing variety of connector
14   types.
15
16   Each fiber cabling segment shall be installed such that odd numbered fibers are Position A at one end and
17   Position B at the other end while the even numbered fibers are Position B at one end and Position A at the
18   other end. See TIA/EIA-568-B.1, section 10.3.2 for further details and diagrams.
19
20   The patch panel enclosure shall be sized to accommodate the total fiber count to be installed at each
21   location as defined in the specifications and drawings - including those not terminated (if applicable).
22   Connector panels and connector couplings (sleeves, bulkheads, etc.) adequate to accommodate the number
23   of fibers to be terminated shall be furnished and installed by the contractor, and/or those included in "Bid
24   Alternates" (if applicable).
25
26   Patch panels shall be enclosed assemblies affording protection to the cable subassemblies and to the
27   terminated ends. The enclosures shall incorporate a hinged or retractable front cover designed to protect
28   the connector couplings and fiber optic jumpers.
29
30   The patch panels enclosure shall provide for strain relief of incoming cables and shall incorporate radius
31   control mechanisms to limit bending of the fiber to the manufacturer’s recommended minimums or 1.2”,
32   which ever is larger.
33
34   Access to the inside of the patch panel enclosure during installation shall be from the front and/or rear.
35   Panels that require any disassembly of the cabinet to gain entry will not be accepted.
36
37   All Patch Panels shall provide protection to both the “facilities” and “user” side of the coupling. The patch
38   panel enclosure shall be configured to require front access only when patching. The incoming cables (e.g.
39   Backbone, Riser, etc.) shall not be accessible from the patching area of the panel. The enclosure shall
40   provide a physical barrier to access of such cables.
41
42   Where “Loose Buffered” cables are installed, the 250 µm coated fibers contained in these cables may be
43   terminated either by (1) splicing of factory-terminated cable assemblies (“pigtails”) or (2) the use of a "fan-
44   out" kit. In the latter approach, individual fibers are to be secured in a protective covering -an Aramid
45   reinforced tube for example - with connectors mated to the resulting assembly. In both instances, the
46   proposed termination hardware shall incorporate a mechanism by which cable and sub-assemblies are
47   secured to prevent damage. Splicing shall be by the “fusion” method. Individual splice loss shall not
48   exceed 0.3 dB for multi-mode fibers. Direct termination of 250 µm coated fibers shall not be permitted.
49   Where splicing of the cabling at system end points is a requirement of the installation, the Termination
50   Enclosure shall incorporate a mechanism for securing the Splice Tray(s) and fiber slack. The Splice Tray
51   and fiber slack shall not be accessible from the "user" side of the enclosure.
52
53   EQUIPMENT RACK
54   Equipment Racks shall be furnished and installed by the contractor to house Cable Termination
55   components (e.g. Fiber Optic) and Network Electronics. Refer to Part 3 ("Execution") of this Section for
56   quantities required at each location. Where additional Equipment Racks are required or where existing
57   racks are in place and none are required, it shall be so noted on the Floorplan Drawings.
58
59            The rack shall conform to the following requirements:
60
61            The rack shall comply with State Building Codes for the seismic area in which it is to be installed.
62            Rack shall be 84"in height and shall be self-supporting.
63
64            Channel uprights shall be spaced to accommodate Industry standard 19” mounting.



                                                      27 00 00 - 6
 1            Rack must be constructed of aluminum and have either a coating or painted surface.
 2
 3            Rack shall be double-side drilled and tapped to accept 12-24 screws. Uprights shall also be drilled
 4            on back to accept cable brackets, clamps, power strip(s), etc. Hole pattern on rack front shall be
 5            per EIA/TIA specifications (5/8"-5/8"-1/2"). Hole pattern on the rear shall be at 3" intervals to
 6            accept cable brackets. Rack should be supplied with a supply of spare screws (minimum of 24).
 7
 8            Base footprint should be no smaller than 15”x20”.
 9
10            Rack should be supplied with power supply strips.
11
12            Rack should be supplied with a ground bar and #6 AWG Ground lug.
13
14   Jumper Management
15   Rack shall be equipped with Vertical and Horizontal Jumper Management Hardware in the form of rings
16   and guides, as to allow an orderly routing of twisted pair, optical fiber and coaxial jumpers from the patch
17   panels to the customer provided network equipment. Jumper management hardware shall be as follows:
18
19            At minimum, horizontal cable management hardware shall be shall be positioned above and below
20            (a) each grouping of two rows of Jacks Data Patch Panels, (b) each grouping of two rows of ":F"
21            connectors on Coaxial Patch Panels and (c) above and below each Fiber Optic Patch Panel.
22
23            Vertical jumper management shall provide for cable routing on front and rear of each rack and be
24            3½" square (minimum). Vertical Jumper Management hardware shall mount on spacers attached
25            to the rack uprights and not on the upright itself. Where multiple racks are to be installed, this
26            hardware shall be mounted between the uprights of adjacent racks. Rack uprights and the spacers
27            shall be secured together per manufacturer recommendations.
28
29            Each rack shall be supplied with a minimum of twelve (12) releasable (e.g. "hook & loop") cable
30            support ties.
31
32   Where Cable Termination Hardware is wall mounted, the contractor shall be responsible for establishing a
33   cable pathway for jumpers routed from the Equipment Rack(s) to the wall. This shall be in the form of
34   slotted ducts, troughs, “D” rings or other means. Routing of jumpers via the overhead ladder rack system is
35   not acceptable. The proposed method shall be included in the submittals required by this document and
36   shall be approved by the Engineer prior to installation.
37
38   EQUIPMENT CABINETS (WALL MOUNT)
39   Where identified on the drawings, wall mounted equipment cabinets shall house all termination
40   components installed under this contract.
41
42   Cabinets shall be “three-section” construction including (a) wall-mount section which incorporates cable
43   entry, (2) center section and (c) door. Each section shall be hinged to facilitate access. Hinges shall be
44   configurable to open LEFT OR RIGHT.
45   The Wall-mounted section shall incorporate knock-outs (top and bottom) for cable access.
46   The Door shall be solid. Door depth shall be 2-inches or greater.
47   Shall be at least 25-inches in width. (It is understood that this may require a custom configuration. Use of
48   standard cabinet designs with extended mounting rails is to be considered).
49   Hardware mounting depth (from front of channel upright to wall) shall be 18-inches (minimum).
50   shall have a load-bearing capacity of 100lbs or greater.
51   The cabinet shall be configured as to allow for adjustment of the channel uprights (front to rear) in 1-inch
52   increments and be space to accommodate industry standard 19-inch mounting and tapped to accept 12-24
53   screws. The cabinet shall be vented to allow for airflow through the cabinet.
54
55   Cabinet(s) shall be equipped with vertical and horizontal cable management hardware, in the form of rings
56   and guides, as to allow an orderly routing of optical fiber and twisted pair jumpers from the patch panel to
57   the customer provided network equipment. At a minimum, one such horizontal jumper management panel
58   shall be provided with each cabinet. Jumper management panels shall be 3-1/2” in height and have a
59   minimum of five (5) jumper distribution rings.
60
61   Each rack shall be supplied with a minimum of twelve (12) releasable (e.g. "hook & loop") cable support
62   ties and shall be supplied with a supply of spare screws (minimum of 24).
63
64



                                                     27 00 00 - 7
 1   FLEXIBLE NONMETALLIC INNERDUCT AND FITTINGS
 2   General
 3   Flexible Non-metallic Innerduct (e.g. “Innerduct”) may be used as follows:
 4            to segment conduit(s), increasing their capacity,
 5            as protection to backbone fiber optic cables when installed in cable tray, and
 6            as protection to fiber optic cable(s) within equipment rooms and Telecommunications Rooms.
 7
 8   Innerduct shall be corrugated.
 9
10   Where not installed in a continuous length, innerduct segments should be spliced using couplings designed
11   for that purpose.
12
13   Any vacant innerduct shall be equipped with a pull cord and capped at all ends to inhibit the entry of water
14   and contaminants.
15
16   Nominal duct size shall be 1-inch (minimum).
17
18   Innerduct should be rated (e.g. General, Flame-retardant, Riser or Plenum) as required by the installation
19   environment. Riser and Plenum innerduct shall be of a color contrasting to that of the “Standard” and
20   Flame-retardant innerduct. The preferred colors are Orange (“Standard & Flame-retardant) and White
21   (Riser and Plenum).
22
23   Flame-retardant Innerduct
24   Innerduct installed within buildings (not including riser paths) or utility tunnels shall meet all of the above
25   General requirements plus:
26
27   be fabricated of flame-retardant materials suitable for installation such environments, and
28
29   meet or exceed all requirements for flame resistant duct as required by BELLCORE TR-NWT-000356
30   (Section 4.33).
31
32   Riser-rated Innerduct
33   Innerduct installed within building riser shafts shall meet all of the above General requirements plus:
34
35       be fabricated of flame-retardant materials suitable for installation such environments, and
36
37       meet or exceed all requirements for flame propagation as specified by test method UL-1666 and
38       referenced by the National Electrical Code (NEC) Section 770-53 for listed optical fiber raceways
39       being installed in vertical runs in a shaft between floors.
40
41   Plenum-rated Innerduct
42       Be fabricated of flame-retardant and smoke inhibiting materials suitable for installation in such
43       environments, and
44
45       Meet or exceed all requirements for flame propagation and emissions as specified by test method UL-
46       910 and referenced by the National Electrical Code (NEC) Section 770-53 for listed optical fiber
47       raceways being installed in ducts, plenums and other areas for environmental air, and
48
49       Meet or exceed all requirements specified by the National Fire Protection Agency (NFPA) 90A and
50       262 for Plenum spaces. Testing for fire and smoke characteristics shall be per UL-910.
51
52   MISCELLANEOUS MATERIALS
53   Fiber Optic Patch Cables
54   The Fiber Optic patch cables shall be single -mode fiber utilizing tight buffer construction. The fiber optic
55   patch cables shall be minimum 1.5 meters in length.
56
57   Fiber Optic jumpers shall incorporate Ceramic or Metallic tipped connectors. Connector body shall be of
58   materials similar to that used in the proposed couplings. Connectors used in fiber optic patch cables shall
59   meet requirements set forth in the Fiber Optic section of this section.
60
61   Provide a fiber optic patch cable for each fiber optic cable connectorized in the system.
62
63
64



                                                       27 00 00 - 8
 1                                              PART 3 - EXECUTION
 2
 3   GENERAL
 4   Optical Fiber and Copper Pair counts of the cables to be supplied are detailed on the Project Drawings.
 5   Contractor shall furnish and install all cables, connectors and equipment as shown on drawings and as
 6   specified above. It shall be noted that all cables shall be installed in continuous lengths from endpoint to
 7   endpoint. No splices shall be allowed unless noted otherwise.
 8
 9   Refer to Project Drawings which indicate the cable routes to follow and the termination location(s) within
10   each building. Duct allocation shall be coordinated as part of the construction.
11
12   It is the contractor's responsibility to survey the site and include all necessary costs to perform the
13   installation as specified. This includes any modifications required to route and conceal horizontal
14   distribution wiring.
15
16   Beginning installation means contractor accepts existing conditions.
17
18   Contractor shall furnish all required installation tools to facilitate cable pulling without damage to the cable
19   jacket. Such equipment is to include, but not limited to, sheaves, winches, cable reels, cable reel jacks, duct
20   entrance tunnels, pulling tension gauge and similar devices. All equipment shall be of substantial
21   construction to allow steady progress once pulling has begun. Makeshift devices, which may move or wear
22   in a manner to pose a hazard to the cable, shall not be used.
23
24   All cable shall be pulled by hand unless installation conditions require mechanical assistance. Where
25   mechanical assistance is used, care shall be taken to insure that the maximum tensile load for the cable as
26   defined by the manufacturer is not exceeded. This may be in the form of continuous monitoring of pulling
27   tension, use of a “break-away” or other approved method.
28
29   The contractor will be responsible for identifying and reporting to the Site Coordinator(s) any existing
30   damage to walls, flooring, tiles and furnishings in the work area prior to start of work. All damage to
31   interior spaces caused by the installation of cable, raceway or other hardware must be repaired by the
32   Contractor. Repairs must match preexisting color and finish of walls, floors and ceilings. Any contractor-
33   damaged ceiling tiles are to be replaced by the contractor to match color, size, style and texture.
34
35   Qualified personnel utilizing state-of-the-art equipment and techniques shall complete all installation work.
36   During pulling operation an adequate number of workers shall be present to allow cable observation at all
37   points of duct entry and exit as well as the feed cable and operate pulling machinery.
38
39   Cable pulling shall be done in accordance with cable manufacturer’s recommendations and ANSI/IEEE C2
40   standards. Manufacturer’s recommendations shall be a part of the cable submittal. Recommended pulling
41   tensions and pulling bending radius shall not be exceeded. Any cable bent or kinked to radius less than
42   recommended dimension shall not be installed. If any installed cable is kinked to a radius less than
43   recommended dimension it shall be replaced by the contractor with no additional cost to the project.
44
45   Avoid abrasion and other damage to cables during installation.
46
47   Pulling Lubricant may be used to ease pulling tensions. Lubricant shall be of a type that is non-injurious to
48   the cable jacket and other materials used. Lubricant shall not harden or become adhesive with age.
49
50   The Cable system will be tested and documented upon completion of the installation as defined in the
51   Section below.
52   A pull cord (nylon; 1/8” minimum) shall be co-installed with all cable installed in any conduit.
53   Should it be found by the Engineer, that the materials or any portion thereof, furnished and installed under
54   this contract, fail to comply with the specifications and drawings, with the respect or regard to the quality,
55   amount of value of materials, appliances or labor used in the work, it shall be rejected and replaced by the
56   Contractor and all work distributed by changes necessitated in consequence of said defects or imperfections
57   shall be made good at the Contractor's expense.
58
59   Cable slack shall be provided in each Backbone fiber optic cable. This slack is exclusive of the length of
60   fiber that is required to accommodate termination requirements and is intended to provide for cable repair
61   and/or equipment relocation. The cable slack shall be stored in a fashion as to protect it from damage and
62   be secured in the termination enclosure or a separate enclosure designed for this purpose. Multiple cables
63   may share a common enclosure. Slack required in the various subsystems is as follows:
64



                                                       27 00 00 - 9
 1   Backbone Intra-Building: A minimum of 5-meters (approx. 15-feet) of slack cable (each cable if
 2   applicable) shall be coiled and secured at one (1) end - preferably at the Entrance Room and/or Main
 3   Equipment Room. Cable slack installed other than at each end of cable run shall not be allowed.
 4
 5   Exact cable termination locations shall be field verified with Owner.
 6
 7   Backbone Fiber Optic Cable shall be installed in protective innerduct. The innerduct should extend into the
 8   termination and/or storage enclosure(s) at system endpoints.
 9
10   INNERDUCT
11   Innerduct shall be riser or plenum rated as required by the installation environment. At minimum, innerduct
12   should extend to the ladder rack above the termination enclosure at system endpoints. Where not installed
13   in a continuous length, innerduct segments should be spliced using couplings designed for that purpose.
14
15   All exposed innerduct is to be labeled at 35-foot (minimum) intervals with tags indicating ownership, the
16   cable type (e.g. "Fiber Optic Cable") and the cables it contains.
17
18   Where required by the project design, fiber optic cable shall be installed in protective innerduct.
19
20   Contractor shall determine optimum size and quantity to satisfy the requirements of the installation insure
21   that the mechanical limitations - including Minimum Bend Radius - of the cable are considered.
22
23   The innerduct should extend into the termination enclosure at system endpoints.
24
25   Where not installed in a continuous length, innerduct segments should be spliced using couplings designed
26   for that purpose.
27
28   CABLE TERMINATION
29   General
30   Termination Hardware (Blocks and Patch Panels) Positioning and Layout must be reviewed and approved
31   by the Engineer prior to construction. The review does not exempt the Contractor from meeting any of the
32   requirements stated in this document.
33
34   Cable Termination - Fiber Optic
35   ALL fibers shall be terminated using the specified connector type.
36
37   Fibers shall be positioned consecutively and mapped "position for position" between patch panels. There
38   shall be no transpositions in the cabling.
39
40   Connectors from two cables shall never share a common coupling panel. Multi-mode and single mode
41   optical fibers (where applicable) shall be segregated on the panels as to clearly identify the distinction
42   between the fiber types.
43
44   All terminated fibers shall be mated to couplings mounted on patch panels. Couplings shall be mounted on
45   a panel that, in turn, snaps into the housing assembly. Any unused panel positions shall be fitted with a
46   blank panel inhibiting access to the fiber optic cable from the front of the housing.
47
48   All couplings shall be fitted with a dust cap.
49
50   Fibers from multiple locations may share a common enclosure, however, they must be segregated on the
51   connector panels and clearly identified. Fibers from multiple destinations may be secured in a common
52   enclosure provided that they are clearly identified as such. Fibers from different locations shall not share a
53   common connector panel (e.g. “insert”).
54
55   Slack in each fiber shall be provided as to allow for future re-termination in the event of connector or fiber
56   end-face damage. Adequate slack shall be retained to allow termination at a 30” high workbench
57   positioned adjacent to the termination enclosure(s). A minimum of 1-meter (~39”) of slack shall be
58   retained regardless of panel position relative to the potential work area.
59
60   Where "Loose Buffered" cables are installed, the 250um coated fibers contained in these cables may be
61   terminated either by 1) splicing of factory terminated cable assemblies ("pigtails") or 2) the use of a "fan-
62   out" kit. In the latter approach, individual fiber are to be secured in a protective covering, an Armid (e.g.
63   Kelvar) reinforced tube for example, with connectors mated to the resulting assembly.
64



                                                      27 00 00 - 10
 1   In both instances, the proposed termination hardware shall incorporate a mechanism by which cable and
 2   sub assemblies are secured to prevent damage. Splicing shall be by the "fusion" method. Individual splice
 3   loss shall not exceed 0.3 dB for multi-mode fibers and 0.1 dB for single mode fibers (if applicable). Direct
 4   termination of 250 um coated fibers shall not be permitted.
 5
 6   Equipment Rack (Free Standing)
 7   The Contractor shall bolt the rack to the floor as recommended by the manufacturer. Multiple racks shall
 8   be joined and the ground made common on each. Rack shall also be stabilized by extending a brace
 9   extending to the wall. Alternately, overhead cable tray over which the cabling accesses the equipment
10   rack(s) shall provide this function.
11
12   A space between the rack upright and the wall (~4") should be planned to allow for cabling in that area.
13   The rear of the rack should be ~40" from the wall to allow for access by maintenance personnel. In all
14   cases, a minimum of 40” workspace in front of the rack is also required. Locations where these guidelines
15   cannot be followed should be brought to the attention of the Engineer for resolution prior to installation.
16
17   All hardware and equipment is to be mounted between 18" and 79" above floor level. This is to afford easy
18   access and, in the case of the lower limit, prevent damage to the components. Positioning of hardware
19   should be reviewed and approved by the Engineer and Site Coordinator(s) prior to installation.
20
21   Equipment Rack shall be equipped with cable management hardware on both the front and back of rack as
22   to allow an orderly and secure routing of twisted pair cabling to the data patch panels. At minimum, one
23   such Horizontal Jumper Management Panel shall be placed below each Fiber Optic Patch Panel installed by
24   the Contractor. Additional Jumper Management panels may be required pending installation of other cable
25   types on the rack. Refer to other sections (in particular 27 00 00 – “Communications Cable & Equipment")
26   for guidance.
27
28   The rack(s) shall be grounded to the Telecommunications Ground Busbar (TGB) using a #6 AWG (or
29   larger) insulated stranded copper conductor (GREEN jacket or GREEN jacket with one or more yellow
30   stripes). (See NEC 2002, section 250.119.)
31
32   Identification and Labeling
33   Prior to installation, the Contractor shall provide samples of all label types planned for the project. These
34   samples shall include examples of the lettering to be used.
35
36   TESTING AND ACCEPTANCE
37   General
38   The contractor is responsible to perform acceptance tests as indicated below for each sub-system (e.g.
39   backbone, station, etc. ) as it is completed
40
41   All tests shall be documented.
42
43   The Contractor is responsible for supplying all equipment and personnel necessary to conduct the
44   acceptance tests. Prior to testing, the Contractor shall provide a summary of the proposed test plan for each
45   cable type including equipment to use used, set-up, test frequencies or wavelengths, results format, etc.
46   The method of testing shall be approved by the Engineer.
47
48   The Contractor shall visually inspect all cabling and termination points to insure that they are complete and
49   conform to the wiring pattern defined herein. The contractor shall provide the Engineer with a written
50   certification that this inspection has been made.
51   The Contractor shall conduct acceptance testing according to a schedule coordinated with the DSF.
52   Representatives of the Owner may be in attendance to witness the test procedures. The contractor shall
53   provide a minimum of one (1) week advance notice to the Engineer as to allow for such participation. The
54   notification shall include a written description of the proposed conduct of the tests including copies of
55   blank test result sheets to be used.
56   IMPORTANT: Failure to provide the above information shall be grounds for the Owner/Engineer to reject
57   any and all Documentation of Results on related testing and to require a repeat of the affected test.
58
59   Tests related to connected equipment of others shall only be done with the permission and presence of
60   Contractor involved. The Contractor shall ascertain that testing only as required to prove the wiring
61   connections are correct.
62




                                                     27 00 00 - 11
 1   The Contractor shall provide test results and describe the conduct of the tests including the date of the tests,
 2   the equipment used and the procedures followed. At the request of the Engineer, the contractor shall
 3   provide copies of the original test results.
 4   All cabling shall be 100% fault free unless noted otherwise. If any cable is found to be outside the
 5   specification defined herein, that cable and the associated termination(s) shall be replaced at the expense of
 6   the contractor. The applicable tests shall then be repeated.
 7
 8   Should it be found by the Engineer that the materials or any portion thereof furnished and installed under
 9   this contract fail to comply with the specifications and drawings, with the respect or regard to the quality,
10   amount of value of materials, appliances or labor used in the work, it shall be rejected and replaced by the
11   Contractor and all work distributed by changes necessitated in consequence of said defects or imperfections
12   shall be made good at the Contractor's expense.
13
14   Fiber Optic Cable
15   General
16   The fibers utilized in the installed cable shall be traceable to the manufacturer. Upon request by the Owner,
17   the Contractor shall provide cable manufacturer’s test report for each reel of cable provided. These test
18   reports shall include (1) manufacturer’s on the reel attenuation test results at the specified wavelengths for
19   each optical fiber of each reel prior to shipment from the manufacturer and (2) on-the-reel Bandwidth
20   performance as tested at the factory.
21
22   Tests Prior to Installation
23   The Contractor, at their discretion and at no additional cost to the Owner, may perform tests deemed
24   necessary by the Contractor to insure integrity of any Owner furnished optical fiber. Tests may range from
25   a simple "flashlight test" to an OTDR of each optical fiber of each cable reel prior to installation. Upon
26   request, the contractor shall supply this test data to the Engineer prior to installation.
27
28   Tests After Installation
29
30   Upon completion of cable installation and termination, the Fiber Optic cabling shall be tested to include:
31
32    Optical Attenuation (“Insertion Loss” Method) and Verification of Link Integrity (OTDR).
33
34   Optical Attenuation Testing
35   Optical Attenuation shall be measured on all terminated optical fibers in both directions of transmission
36   using the “Insertion Loss” method. Measurement shall be inclusive of the optical connectors and couplings
37   installed at the system endpoints. 100 foot access jumpers shall be used at both the transmit and receive
38   ends to insure that an accurate measurement of connector losses is made.
39
40   Multi-mode fibers shall be tested in accordance with the EIA/TIA 526-14A, Method B at 85030 nm.
41   Single mode fibers (if applicable) shall be tested in accordance with the EIA/TIA 526-7-1998. Method A.1.
42   Testing shall be at 130020 nm.
43
44   Attenuation of optical fibers shall not exceed the values calculated at follows:
45                     Attenuation (max.) = 2*C+L*F+S dB
46                     where C is the maximum allowable Connector Loss (in dB), L is the length of the run (in
47                     kilometers) and F is the maximum allowable fiber loss (in dB/km). S is the total splice
48                     loss (# of splices * max. attenuation per splice).
49
50   OTDR Testing
51   All fibers even those that are left unterminated (if applicable) shall be documented in one direction of
52   transmission using an Optical Time Domain Reflectometer (OTDR). Multi-mode fibers shall be tested at
53   850-nm (nominal). Single mode fibers (if applicable) shall be tested at 1300nm (nominal). The OTDR(s)
54   shall incorporate high-resolution optics optimized for viewing of short cable sections. Access jumpers of
55   adequate length to allow viewing of the entire length of the cable, including the connectors at the launch
56   and receive end, shall be used.
57
58   OTDR traces revealing a point discontinuity greater than 0.2-dB in a multi-mode fiber, or 0.1-dB in a
59   single mode fiber (if applicable) at any of the tested wavelengths or any discontinuity showing a reflection
60   at that point shall be a valid basis for rejection of that fiber by the Owner. The installation of that cable
61   shall be reviewed in an effort to remove any external stress that may be causing the fault. If such efforts do
62   not remove the fault, that cable and the associated terminations shall be replaced at the expense of the
63   contractor.
64



                                                      27 00 00 - 12
 1   DOCUMENTATION
 2   General
 3   Upon completion of the installation, the contractor shall provide three (3) full Documentation Sets to the
 4   Engineer for approval. Documentation shall include the items detailed in the sub-sections below.
 5
 6   Documentation of Test Results shall be submitted in hard copy or in electronic form (preferred). Electronic
 7   documents may be submitted on CD-ROM (preferred) or 3½” diskettes for review and distribution. Where
 8   documentation provided in electronic form requires unique software (other than an MS-Word compatible
 9   Word Processor or MS-Excel spreadsheet) for viewing test results, the Contractor shall provide along
10   with the above documentation, one (1) licensed copy of such software. The software shall run on a
11   MICROSOFT Windows-based personal computer supplied by the Owner.
12
13   Documentation shall be submitted within ten (10) working days of the completion of each testing phase
14   (e.g. subsystem, cable type, area, floor, etc.). This is inclusive of all test result and draft as-built drawings.
15   Draft drawings may include annotations done by hand. Machine generated (final) copies of all drawings
16   shall be submitted within 30 working days of the completion of each testing phase.
17
18   The Engineer may request that a 10% random field re-test be conducted on the cable system at no
19   additional cost to verify documented findings. Tests shall be a repeat of those defined above. If findings
20   contradict the documentation submitted by the Contractor, additional testing can be requested to the extent
21   determined necessary by the Engineer, including a 100% re-test. This re-test shall be at no additional cost
22   to the Owner.
23
24   Test Data - Fiber Optic Media
25   Test results shall include a record of test wavelengths, cable type, fiber (or Outlet) I.D., measurement
26   direction, test equipment type, model and serial number, date, reference setup, and crew member name(s).
27
28   OTDR traces of individual optical fiber “signatures” obtained as specified above shall be provided to the
29   A/E for review. Trace files shall be so named as to identify each individual fiber by location in the cable
30   system and fiber number or color.
31
32   AS-BUILT CONSTRUCTION DRAWINGS
33   Drawings included with the specifications set shall be modified by the contractor to denote as-built
34   information.
35
36   The drawings are to include cable routes and outlet locations. Outlet locations shall be identified by their
37   sequential number as defined elsewhere in this document. Numbering, icons and drawing conventions used
38   shall be consistent throughout all documentation provided.
39
40   The Division of State Facilities through the Consultant will provide floor plans in paper and electronic
41   (".dwg", AutoCAD rel. 2006) formats on which as-built construction information can be added. These
42   documents will be modified accordingly by the contractor to denote as-built information as defined above
43   and returned to the Consultant for acceptance. This information shall be supplied to the
44   Consultant/Engineer no later than four (4) weeks prior to the scheduled occupancy of the affected floors.
45
46   The Contractors shall annotate the base drawings and return to the A/E in hard copy (same plot size as
47   originals) and electronic (AutoCAD rel. 2006) form.
48
49   Each drawing submitted by the Contractor as part of the Project Documentation shall be identified as an
50   "As-built" drawing and include the following (1) The Contractor name and/or logo (2) The date of the
51   drawing.
52
53   All fonts, color, layer, Model Space/Paper Space conventions established in the base drawings shall be
54   retained by the Contractor in preparation of the As-built drawings.
55
56   Prior to generation of the drawings, the Contractor shall provide a sample file and test plot to the Engineer
57   for review and approval.
58
59   WARRANTY
60   This Contractor shall guarantee all materials, equipment, etc., two (2) years from date of substantial
61   completion of this work. This guarantee shall include all labor, material and travel time.
62
63                                                 END OF SECTION




                                                       27 00 00 - 13
 1                                         SECTION 27 05 00
 2                                MASTER ANTENNA TELEVISION SYSTEM
 3
 4                                             PART 1 – GENERAL
 5
 6   The complete installation of a fiber optic based Master Antenna Television System (MATV) for the
 7   amplification and distribution of television signals. Provide all labor, materials, equipment and supervision
 8   to install, adjust and calibrate a complete and operational MATV system.
 9
10   WORK INCLUDED
11        Antennas
12        Demodulators
13        Transcoder Chassis
14        Modulators
15        Combiners
16        Amplifiers
17        Equipment housings
18        Splitters
19        Coax cable systems
20        Directional couplers
21        Terminations
22
23   RELATED SECTIONS
24   Applicable provisions of Division 1 govern work under this Section.
25   Section 27 00 00 – Fiber Optic Cable and Equipment
26
27   SYSTEM DESCRIPTION
28   In general the work consists of providing and installing a fiber optic based MATV system at Mendota
29   Mental Health and Central Wisconsin Center. The MATV system components include, but are not limited
30   to, antenna systems, off-the-air headend equipment, local origination equipment, distribution equipment
31   and cable systems. Antennas will be installed on the Mendota Mental Health Administration Building.
32   MATV system headend equipment will be installed in the Administration Buildings at both Mendota
33   Mental Health and Central Wisconsin Center. Project requirements include all terminating and testing for a
34   complete and operational MATV system servicing Mendota Mental Health and Central Wisconsin Center.
35
36                                             PART 2 - PRODUCTS
37
38   ANTENNAS AND ASSOCIATED EQUIPMENT
39   Off-the-air television station reception will be accomplished utilizing standard broadband VHF/UHF
40   antennas. Provide antennas, antenna mounts, freestanding antenna mast, and all necessary equipment as
41   required.
42             Antenna                     Blonder Tongue BTY-LP-BB/BTY-UHF-BB Series
43             Antenna Mast                Taco DMXB Series
44
45   DEMODULATOR
46   The MATV system design shall utilize ATSC/QAM demodulators to decode any off-the-air HDTV to a
47   standard definition format. The demodulator output will be 480i format in 4:3 or 16:9 with closed
48   captioning decoding. The HDTV demodulators shall mounted in a single transcoder chassis. The
49   modulators shall be Blonder-Tongue AQD series or approved equal.
50
51   MODULATOR
52   The MATV system design shall utilize heterodyne modulators to move the decoded HDTV signals to an
53   unused channel in the system. The modulators shall be mounted in a single chassis. The video modulators
54   shall be Blonder-Tongue MICM-45 series or approved equal.
55
56   AGILE MODULATOR
57   The MATV system design shall utilize an audio/video modulators distribute standard local origination
58   audio/video signals. The agile modulator shall be Blonder-Tongue AM series or approved equal.
59
60   COMBINER
61   The processor and modulator output shall be amplified and combined prior to the output to the distribution
62   network. The MATV system combiner shall be Blonder-Tongue OCA series or approved equal.




                                                   DSF Project No.
                                                    27 05 00 - 1
 1   LAUNCH AMPLIFIER
 2   The headend signal output shall be amplified for distribution. The distribution amplifier shall be equipped
 3   with all necessary optional equipment in the quantity/capacity necessary to maintain adequate signal levels
 4   throughout the system. The distribution amplifier shall be Blonder-Tongue RMDA series or approved
 5   equal.
 6
 7   FIBER OPTIC TRANSMITTER
 8   The combined/modulated headend signal output shall be transferred to a fiber optic transmitter for
 9   conversion to an optical output. The fiber optic transmitters shall be Blonder-Tongue FIBT series or
10   approved equal.
11
12   FIBER OPTIC COUPLER
13   The transmitter fiber optic output shall be split into multiple light sources for distribution into the fiber
14   optic network. The fiber optic coupler shall be Blonder-Tongue FOC series or approved equal.
15
16   INTERMEDIATE FIBER OPTIC RECEIVER/AMPLIFIER
17   The optical output signal from the MATV headend shall be received and converted to an electrical signal
18   by fiber optic receivers. The fiber optic signal at a intermediate repeater station shall shall be Blonder-
19   Tongue FRRA series or approved equal.
20
21   INTEGRATED FIBER OPTIC RECEIVER/AMPLIFIER
22   The optical output signal from the MATV system shall be received and converted to an electrical signal by
23   fiber optic receivers. The integrated fiber optic receiver amplifier shall be Blonder-Tongue FRDA series or
24   approved equal.
25
26   HEADEND EQUIPMENT CABINET
27   The headend equipment shall be housed in cabinets designed for mounting standard 19-inch rack
28   components. The headend equipment cabinets shall be Blonder-Tongue RMX series or approved equal
29
30   MISCELLANEOUS EQUIPMENT
31   Following is a list of miscellaneous equipment to be provided as required for a complete and operational
32   system. All equipment listed shall be manufactured by Blonder Tongue or approved equal.
33           Directional couplers:        SRT Series
34           Splitters                    SDS Series
35
36   COAX CABLE
37   Trunking (distribution) cable shall be 75 ohm RG 11/U type having the following characteristics:
38           Center Conductor:            14 Ga. solid copper.
39           Insulation:                  Gas injected foam polyethylene.
40           Shield:                      95% tinned copper braid.
41           Jacket:                      Black PVC.
42
43   Drop cable shall be 75 ohm RG-6/U type having the following characteristics:
44           Center Conductor:        18 Ga. solid copper.
45           Insulation:              Gas injected foam polyethylene
46           Shield:                  95% tinned copper braid.
47           Jacket:                  Black PVC
48
49                                              PART 3 - EXECUTION
50
51   GENERAL
52   The contractor shall furnish and install all cable, equipment, miscellaneous parts and assessories to provide
53   a complete and fully operational MATV system as described herein and as shown on the drawings.
54
55   Refer to drawings for placement of equipment and panels. Coordinate with other trades which impact
56   installation of these systems. Refer to functional and riser diagrams for system interconnections.
57
58   All trunking (distribution) and drop cables shall be furnished and installed as required to support the system
59   as specified.
60
61   System shall be designed and installed such that the nominal signal level at any outlet is 6 dB ± 2 dB.
62
63   The MATV system shall comply with all rules and regulations of FCC-Part76.
64


                                                     DSF Project No.
                                                      27 05 00 - 2
 1   COMPLETION
 2   Upon completion of the work, remove excess debris, materials, equipment, apparatus tools an the like and
 3   leave the premises clean, neat and orderly.
 4
 5   Contractor shall test system completely prior to acceptance tests to confirm that system requirements as
 6   herein specified are met.
 7
 8   TESTING
 9   The contractor shall measure and document the signal level at each building . If the signal level at any
10   location is outside the required level, the contractor shall make necessary adjustments, change values as
11   required to meet this requirement. All signal level tests will be conducted using a field strength meter.
12
13   The contractor shall conduct and document performance tests using a standard television receiver to
14   observe picture quality. No evidence of ghosting, noise beat interference or cross modulation will be
15   accepted. If any of these problems are observed, the contractor shall take corrective action to achieve a
16   quality picture.
17
18                                               END OF SECTION
19
20
21




                                                   DSF Project No.
                                                    27 05 00 - 3

				
DOCUMENT INFO
Shared By:
Categories:
Tags:
Stats:
views:5
posted:8/18/2011
language:English
pages:39