Definition
  Integrate- join two or more objects or make
   something part of a larger whole, or be made part of
   a larger whole.
  For commissioning an integrated system test can be
   defined as: a test that brings previously functionally
   tested systems together and simultaneously will test
   the designed control sequence for all associated
   systems as a whole in various modes.



8/16/2011                                                   2
Examples of Integrated System Test
  I have included 3 examples of types of integrated
     system test.
       Stair pressurization system which could be in most
        buildings
       Hospital considerations that could work for a
        multitude of systems
       Laboratory and/or vivarium considerations that
        become more complex



8/16/2011                                                    3
Examples of Integrated System Test
  This discussion is for only HVAC systems but the
     same type of testing should be considered for life
     safety, security, lighting, plumbing, elevators, and
     any kind of special process systems.




8/16/2011                                                   4
Examples of Integrated System Test
Stairwell Pressurization
  Emergency power system with stair well
   pressurization system.
  In buildings that have floors 75 feet above grade a
   stair pressurization is required. The system will be
   tested under normal power when originally tested.
   When the building looses power and the power is
   transferred to the emergency generator the stair
   pressurization system will be retested, which is an
   integration of the emergency power system with the
   stair pressurization system.

8/16/2011                                                 5
Examples of Integrated System Test
Stairwell Pressurizati
        This test will determine the stairwell pressurization
         fans start after emergency power has been
         established and they are operating with the correct
         rotation.
        This test will also establish the dampers, alarms and
         smoke detectors are operational under emergency
         power.
        The last part of this test will be to verify everything is
         operational after returning to normal power.



8/16/2011                                                             6
Examples of Integrated System Test
Hospitals
  HVAC Systems with Emergency Power the IST
   will verify the following:
        Air Handling Units (AHUs)
               Start under emergency power with correct
                rotation
               All control loops are operational
               All dampers are operational
               All terminal boxes are operational

8/16/2011                                                  7
Examples of Integrated System Test
Hospitals
             Systems returned to normal power
             Restart under normal power, AHUs and fan
              systems should follow the designed start
              sequence
             All control loops are operational

             All systems back to their normal operation

             All dampers are operational and are in the
              correct position

8/16/2011                                                  8
Examples of Integrated System Test
Hospitals
               Exhaust Fans (EFs)
                 Start under emergency power with correct
                  rotation
                 All control loops are operational

                 All dampers are operational

                 All terminal boxes are operational




8/16/2011                                                    9
Examples of Integrated System Test
Hospitals
             Return to normal power
             Restart under normal power

             All control loops are operational

             All dampers are operational

             All terminal boxes are operational




8/16/2011                                          10
Examples of Integrated System Test
Hospitals
               Chilled Water Pumps
                 Start under emergency power with correct
                  rotation
                 All control loops are operational

                 All valves are operational

                 Sufficient coils are operational to properly load
                  system
                 Caution systems with coils may not start at the
                  same time the pump starts.

8/16/2011                                                             11
Examples of Integrated System Test
Hospitals
             Return to normal power
             Restart under normal power

             All control loops are operational

             All valves are operational

             Sufficient coils are operational to properly load
              system
             Caution systems with coils may not start at the
              same time the pump starts.


8/16/2011                                                         12
Examples of Integrated System Test
Hospitals
               Hot Water Pumps
                 Start under emergency power with correct
                  rotation
                 All control loops are operational

                 All valves are operational

                 Sufficient coils are operational to properly load
                  system
                 Caution systems with coils may not start at the
                  same time the pump starts.

8/16/2011                                                             13
Examples of Integrated System Test
Hospitalsst
             Return to normal power
             Restart under normal power

             All control loops are operational

             All valves are operational

             Sufficient coils are operational to properly load
              system
             Caution systems with coils may not start at the
              same time the pump starts.


8/16/2011                                                         14
Examples of Integrated System Test
Hospitals
               Chillers and Heat Exchangers
                 Start under emergency power with correct
                  rotation
                 All control loops are operational

                 All valves are operational

                 Sufficient pumps are operational to properly
                  load system
                 Transfer switches for pumps and systems with
                  coils are sequenced properly

8/16/2011                                                        15
Examples of Integrated System Test
Hospitals
             Return to normal power
             Restart under normal power

             All control loops are operational

             All valves are operational

             Sufficient pumps are operational to properly
              load system
             Transfer switches for pumps and systems with
              coils may not transfer with the chiller’s transfer
              switch

8/16/2011                                                          16
Examples of Integrated System Test
Hospitalst
               Boilers and Heat Exchangers
                 Start under emergency power with correct
                  rotation
                 All control loops are operational

                 All valves are operational

                 Sufficient pumps are operational to properly
                  load system
                 Caution systems with coils may not start at the
                  same time the pump starts.

8/16/2011                                                           17
Examples of Integrated System Test
Hospitals Test
             Return to normal power
             Restart under normal power

             All control loops are operational

             All valves are operational

             Sufficient pumps are operational to properly
              load system
             Caution systems with coils may not start at the
              same time the pump starts.


8/16/2011                                                       18
Examples of Integrated System Test
Hospitals
               Smoke Control Systems Under Emergency Power
                 All fans and AHUs are off or operating as shown
                  on the smoke control matrix
                 All fans start under emergency power with
                  correct rotation as shown on the smoke control
                  matrix
                 All control loops are operational

                 All dampers are operational and are in the
                  correct position as shown on the smoke control
                  matrix

8/16/2011                                                           19
Examples of Integrated System Test
Hospitals
             All fans and AHUs stopping and starting meet
              NFPA 92 and the International Building Code
              time constraints
             All damper opening and closing meet the
              standards mentioned above
             All smoke barriers maintain the correct
              pressure relationships as shown on the smoke
              control matrix




8/16/2011                                                20
Examples of Integrated System Test
Hospitals
               Smoke Control Systems Under Normal
                Power
                 All fans and AHUs return to their normal
                  operation.
                 All dampers return to their normal operation




8/16/2011                                                        21
Examples of Integrated System Test
Laboratories and Vivariums
  Air Handling Units (AHUs) and Exhaust Systems integrated
     at the lab or Vivarium
      Verify all room pressures are stabilized
       HVAC Systems with Emergency Power
          Air Handling Units (AHUs) and associated Exhaust
           systems
            Start under emergency power with correct rotation (If
             the control system has UPS power the control
             program will require additional programming to avoid
             alarms and be able to start the systems)
            Verify all control loops are operational
            Verify all dampers are operational
            Verify all valves are operational


8/16/2011                                                            22
Examples of Integrated System Test
Laboratories and Vivariums
               Verify startup follows the specified start procedure
                and how long it takes to establish all room pressures
                 Review the transfer switch time and which
                  systems are assigned to each transfer switch
                 Be careful with rooms that are to be positive, when
                  the sequence requires the exhaust system to be
                  operational before the supply systems are allowed
                  to start
                 On large manifold systems (both supply and
                  exhaust) trending may be required on all AHUs,
                  EFs, room pressurization, alarms, and control
                  loops
8/16/2011                                                           23
Examples of Integrated System Test
Laboratories and Vivariums
             Return to normal power
             Restart under normal power (If the control
              system has UPS power the control program
              will require additional programming to avoid
              alarms and start the systems)
             All control loops are operational

             All dampers are operational

             All valves are operational




8/16/2011                                                    24
Examples of Integrated System Test
Laboratories and Vivariums
               Chilled Water Pumps
                 Start under emergency power with correct rotation

                 All control loops are operational

                 All valves are operational

                 Sufficient coils are operational to properly load system

                 Return to normal power

                 Restart under normal power

                 All control loops are operational

                 All valves are operational

                 Sufficient coils are operational to properly load system



8/16/2011                                                                    25
Examples of Integrated System Test
Laboratories and Vivariums
               Hot Water Pumps
                 Start under emergency power with correct rotation

                 All control loops are operational

                 All valves are operational

                 Sufficient coils are operational to properly load system ,
                  because transfer switch timing and restart
                 Return to normal power

                 Restart under normal power

                 All control loops are operational

                 All valves are operational

                 Sufficient coils are operational to properly load system ,
                  because transfer switch timing and restart
8/16/2011                                                                  26
Examples of Integrated System Test
Laboratories and Vivariums
               Chillers and Heat Exchangers
                 Start under emergency power with correct rotation

                 All control loops are operational

                 All valves are operational

                 Sufficient pumps are operational to properly load
                  system , because transfer switch timing and restart
                 Return to normal power

                 Restart under normal power

                 All control loops are operational

                 All valves are operational

                 Sufficient pumps are operational to properly load
                  system , because transfer switch timing and restart
8/16/2011                                                               27
Examples of Integrated System Test
Laboratories and Vivariums
               Boilers and Heat Exchangers
                 Start under emergency power with correct rotation
                 All control loops are operational
                 All valves are operational
                 Sufficient pumps are operational to properly load
                  system, because transfer switch timing and restart
                 Return to normal power
                 Restart under normal power
                 All control loops are operational
                 All valves are operational
                 Sufficient pumps are operational to properly load
                  system, because transfer switch timing and restart
8/16/2011                                                              28
Examples of Integrated System Test
Laboratories and Vivariums
        Smoke Control Systems in Labs and Vivariums are
         usually passive, if an AHU goes down because of an
         internal smoke detector the exhaust will remain
         operational but this test should consider the negative
         pressures created in the building
        If there is a smoke control
              Verify which fans and AHUs are off or operating as
               shown on the smoke control matrix
              All control loops are operational
              All dampers are operational and are in the correct
               position as shown on the smoke control matrix



8/16/2011                                                           29
Examples of Integrated System Test
Laboratories and Vivariums
               All fan stopping and starting and damper opening
                and closing meet NFPA 92 time constraints
               All smoke barriers maintain the correct pressure
                relationships as shown on the smoke control
                matrix
               Verify fans and AHUs remain operational under
                emergency power with correct rotation as shown
                on the smoke control matrix




8/16/2011                                                          30
Examples of Integrated System Test
Laboratories and Vivariums
             Verify all control loops remain operational
             Verify dampers are operational and are in the
              correct position as shown on the smoke
              control matrix
             Verify all fan stopping and starting and damper
              opening and closing meet NFPA 92 time
              constraints
             Verify all smoke barriers maintain the correct
              pressure relationships as shown on the smoke
              control matrix and meet the laboratory and
              Vivarium pressure requirements


8/16/2011                                                       31