TVSS INTERNAL

Document Sample
scope of work template
							                             SECTION 26 43 13
       SURGE PROTECTIVE DEVICES FOR LOW-VOLTAGE ELECTRICAL POWER
                                 CIRCUITS
PART 1 - GENERAL

1.1        SCOPE
      A.    This section describes the materials and installation requirements for surge protective devices
            (SPD) for the protection of all AC electrical circuits.
1.2        RELATED DOCUMENTS
      A.    Drawings and general provisions of the Contract, including General and Supplementary
            Conditions and Division 1 Specification Sections, apply to this Section.
      B.    Other sections that may relate to the work in this section include, but are not limited to, the
            following:
            1.     [Section 26 24 13 - Switchboards
            2.     Section 26 24 16 – Panelboards
            3.     Section 26 24 19 – Motor Control Centers
            4.     Section 26 25 00 – Busway]
1.3        SUBMITTALS
      A.    Submit shop drawings and product information for approval and final documentation in the
            quantities listed according to the Conditions of the Contract. All transmittals shall be identified
            by customer name, customer location, and customer order number.
      B.    Submittals shall include UL 1449 Listing documentation verifying:
              1. Short Circuit Current Rating (SCCR)
              2. Voltage Protection Ratings (VPRs) for all modes
              3. Maximum Continuous Operating Voltage rating (MCOV)
              4. I-nominal rating (I-n)
              5. Type 1 or Type 4 Device Listing
              6. VPR, MCOV, I-n, and Type 1 information is posted at www.UL.com, under Certifications,
                 searching using UL Category Code: VZCA. SCCRs are posted in manufacturer’s UL
                 docs.
              7. UL data and visual inspection takes precedence over manufacturer’s published
                 documentation.
      C.    Submittals shall include shop drawings including manufacturer installation instruction manual
            and line drawings detailing dimensions and weight of enclosure, internal wiring diagram
            illustrating all modes of protection in each type of SPD required, wiring diagram showing all field
            connections and manufacturer’s recommended wire and breakers sizes (if required).
      D.    [An unencapsulated and complete surge protective devices shall be presented for visual
            inspection by the consulting engineer, proprietary technology shall be demonstrated.
            MOV type & quantity shall reflect kA ratings on cutsheets, verification of diagnostic
            monitoring, thermal & overcurrent protection, etc.] [Deletable note: You can learn from
            this. Reps will need to ensure the material inside their box, lines up with cutsheets. The
            more they don‟t want to show you – the more you should want see it.]
1.4        RELATED STANDARDS
      A.    IEEE C62.41.1, IEEE Guide on the Surge Environment in Low-Voltage (1000 V and Less) AC
            Power Circuits,
      B.    IEEE C62.41.2, IEEE Recommended Practice on Characterization of Surges in Low-Voltage
            (1000 V and Less) AC Power Circuits,


July 26, 2009                                                                                 [Project Name]
Surge Protective Devices for Low-Voltage Electrical Power Circuits
                                              26 43 13-1
      C.    IEEE C62.45, IEEE Recommended Practice on Surge Testing for Equipment Connected to
            Low-Voltage (1000 V and Less) AC Power Circuits.
      D.    FIPS Pub 94 (1983) - Guide on Electrical Power for ADP Installation
      E.    National Electric Code - Article 285
      F.    National Fire Protection Association - NFPA-20, NFPA-70, NFPA-75, NFPA-78
      G.    UL 1283 - Electromagnetic Interference Filters
      H.    cUL and UL 1449 - Second Edition Revision prior to September 29, 2009
      I.    UL 1449, Third Edition, on and after September 29, 2009 – Surge Protective Devices
1.5        LISTING REQUIREMENTS
           The SPD industry recently revised UL 1449 Third Edition, 2008 NEC Art 285, NEMA LS-1 and
           various other surge standards. UL 1449 Third Edition, effective 9/2009, includes extensive new
           independent performance testing. This specification centers on UL 1449 Third Edition
           certification to ensure comparable test evaluations and accessibility of UL’s website to verify spec
           compliance.
           A. SPD shall bear the UL Mark and shall be Listed to most recent editions of UL 1449 and UL
                1283. “Manufactured in accordance with” is not equivalent to UL listing and does not meet
                the intent of this specification.

           B. SPD and performance parameters shall be posted at www.UL.com under Category Code:
              VZCA. Products or parameters without posting at UL.com shall not be approved. (To access
              UL Category Code VZCA click on Certifications in the left menu bar of UL’s home page.
              Type VZCA into the Category Code search box and click Search.)
1.6        QUALITY ASSURANCE
      A.    Manufacturer Qualifications: Engage a firm with at least 5 years experience in manufacturing
            transient voltage surge suppressors.
      B.    Manufacturer shall be ISO 9001 or 9002 certified.
      C.    The manufacturer of this equipment shall have produced similar electrical equipment for a
            minimum period of five (10) years. When requested by the Engineer, an acceptable list of
            installations with similar equipment shall be provided demonstrating compliance with this
            requirement.
      D.    The SPD shall be compliant with the Restriction of Hazardous Substances (RoHS) Directive
            2002/95/EC.
1.7        DELIVERY, STORAGE AND HANDLING
      A.    Handle and store equipment in accordance with manufacturer’s Installation and Maintenance
            Manuals. One (1) copy of this document to be provided with the equipment at time of shipment.

PART 2 - PRODUCTS

2.1        MANUFACTURERS
      A.    [Provide an internally mounted Transient Voltage Suppressor/Surge Protective Devices
            (SPD) by Siemens Energy and Automation, Inc. (Siemens) or pre-approved equal by:
            1.    SIEMENS.
            2.    .]
2.2        ELECTRICAL DISTRIBUTION EQUIPMENT [Select the sections, A, B and/or C below, which
           applies to your job]
      A.    [[Service Entrance]
            1.    For main disconnect line side installations, SPD shall be UL labeled as Type 1
                  (verifiable at UL.com), intended for use without need for external or supplemental
                  overcurrent controls. Every suppression component of every mode, including N-

July 26, 2009                                                                                  [Project Name]
Surge Protective Devices for Low-Voltage Electrical Power Circuits
                                              26 43 13-2
                G, shall be protected by internal overcurrent and thermal overtemperature
                controls. [Deletable note: Delete the following section if SPD will be included as
                part of UL 96A certification, which requires Type SPDs installed at the incoming
                service.]
         2.     For main disconnect load side installations, SPD shall be UL labeled as Type 4
                (verifiable at UL.com), intended for use without need for external or supplemental
                overcurrent controls. Every suppression component of every mode, including N-
                G, shall be protected by internal overcurrent and thermal overtemperature
                controls.      SPDs relying upon external or supplementary installed safety
                disconnectors do not meet the intent of this specification. [Deletable note: Delete
                the above section if UL 96A certification or line side installation is not required.]
         3.     SPD shall be installed by and shipped from the electrical distribution equipment
                manufacturer‟s factory.
         4.     Type 1 SPD shall be UL labeled with 20kA Inominal (I-n) (verifiable at UL.com) for
                compliance to UL 96A Lightning Protection Master Label and NFPA 780. [Delete if
                line side installation or UL 96A certification is not required.]
         5.     Type 4 SPD shall be UL labeled with 20kA Inominal (I-n) (verifiable at UL.com).
                [Delete if line side installation or UL 96A certification is required.]
         6.     SPD shall be UL labeled with 200kA Short Circuit Current Rating (SCCR). Fuse
                ratings shall not be considered in lieu of demonstrated withstand testing of SPD,
                per NEC 285.6. [Deletable note: Lower SCCR will allow lower end products to bid.]
         7.     Standard 7 Mode Protection paths: SPD shall provide surge current paths for all
                modes of protection: L-N, L-G, and N-G for Wye systems; L-L, L-G in Delta and
                impedance grounded Wye systems. [Delete: If “true 10-mode” protection is
                preferred, then include discrete L-L MOVs.]
         8.     True 10 Mode Protection paths: SPD shall provide surge current paths for all
                modes of protection: L-N, L-G, L-L, and N-G for Wye systems; L-L, L-G in Delta and
                impedance grounded Wye systems. [Deletable note: 10 Mode protection maybe
                selected for projects where discrete L-L MOV protection is preferred. For most
                projects this feature is not required.]
         9.     SPD shall be connected to the buss of the distribution equipment with an
                appropriately sized 200kA SCCR rated disconnect.
         10.    SPD shall meet or exceed the following criteria:
                a.     Maximum 7-Mode surge current capability shall be [300kA] [400kA] [500kA]
                       per phase. [Note: Delete unselected kA ratings.]
                b.     Maximum 10-Mode surge current capability shall be [300kA] [450kA] per
                       phase. [Note: Delete unselected kA ratings.]
                c.     UL 1449 - Third Edition Revision; effective September 29, 2009, where
                       applicable either Type 1 or Type 4 Voltage Protection Ratings shall not
                       exceed the following:
                      VOLTAGE         L-N       L-G     N-G       L-L        MCOV
                      208Y/120        800V      800V    800V      1200V      150V
                      480Y/277        1200V 1200V 1200V 2000V                320V
         11.    UL 1449 Listed Maximum Continuous Operating Voltage (MCOV) (verifiable at
                UL.com):
                   System Voltage           Allowable System Voltage Fluctuation (%)           MCOV
                       208Y/120                                25%                             150V
                       480Y/277                                15%                             320V
         12.    SPD shall have a minimum UL 1283 listed EMI/RFI filter with minimum attenuation
                of - 50dB at 100 kHz.
         13.    [Suppression components shall be heavy duty „large block‟ MOVs, each exceeding
                30mm diameter.]
         14.    [SPD shall include a serviceable, replaceable module (excluding Branch).]
                [Deletable note: Delete or adjust as appropriate.]
         15.    SPD shall be equipped with onboard visual and audible diagnostic monitoring.
                Indicator lights shall provide full time visual diagnostic monitoring of the
July 26, 2009                                                                        [Project Name]
Surge Protective Devices for Low-Voltage Electrical Power Circuits
                                              26 43 13-3
                operational status of each phase of the surge current diversion module. A red
                indicator light will indicate loss of suppression capability. A green indicator light
                will indicate fully operational suppression capability. Audible diagnostic
                monitoring shall be by way of audible alarm. This alarm shall activate upon a fault
                condition. An alarm on/off switch shall be provided to silence the alarm. An alarm
                push to test switch shall be provided. The SPD diagnostic monitoring devices shall
                be mounted on the front of the switchboard or panelboard enclosure. The
                diagnostic monitoring circuits shall continually monitor the operational status of
                the surge current diversion module. A diagnostic system press to test switch shall
                be provided. A set of Form C dry contacts shall be provided for remote
                annunciation. No other test equipment shall be required for SPD monitoring or
                testing before or after installation.
         16.    SPD shall have a response time no greater than 1/2 nanosecond.
         17.    SPD shall have a warranty for a period of ten years, incorporating unlimited
                replacements of suppressor parts if they are destroyed by transients during the
                warranty period. Warranty will be the responsibility of the electrical distribution
                equipment manufacturer.
         18.    SPD shall be equipped with the following optional items:
                a.    Transient event surge counter shall be located on the front cover of the
                      panelboard. The counter shall be equipped with a manual reset and a battery
                      to retain memory upon loss of AC power.]
   B.    [[Distribution Panel] [Motor Control Center] [Busway]
         1.     SPD shall be UL labeled as Type 4 (verifiable at UL.com), intended for use without
                need for external or supplemental overcurrent controls. Every suppression
                component of every mode, including N-G, shall be protected by internal
                overcurrent and thermal overtemperature controls. SPDs relying upon external or
                supplementary installed safety disconnectors do not meet the intent of this
                specification. [Deletable note: Delete the above section if UL 96A certification or
                line side installation is not required.]
         2.     SPD shall be installed by and shipped from the electrical distribution equipment
                manufacturer‟s factory.
         3.     Type 4 SPD shall be UL labeled with 20kA Inominal (I-n) (verifiable at UL.com).
         4.     SPD shall be UL labeled with 200kA Short Circuit Current Rating (SCCR). Fuse
                ratings shall not be considered in lieu of demonstrated withstand testing of SPD,
                per NEC 285.6. [Deletable note: Lower SCCR will allow lower end products to bid.]
         5.     Standard 7 Mode Protection paths: SPD shall provide surge current paths for all
                modes of protection: L-N, L-G, and N-G for Wye systems; L-L, L-G in Delta and
                impedance grounded Wye systems. [Delete: If “true 10-mode” protection is
                preferred, then include discrete L-L MOVs.]
         6.     True 10 Mode Protection paths: SPD shall provide surge current paths for all
                modes of protection: L-N, L-G, L-L, and N-G for Wye systems; L-L, L-G in Delta and
                impedance grounded Wye systems. [Deletable note: 10 Mode protection maybe
                selected for projects where discrete L-L MOV protection is preferred. For most
                projects this feature is not required.]
         7.     SPD shall meet or exceed the following criteria:
                a.     Maximum 7-Mode surge current capability shall be [100kA] [200kA] per
                       phase. [Note: Delete unselected kA ratings.]
                b.     Maximum 10-Mode surge current capability shall be [150kA] [300kA] per
                       phase. [Note: Delete unselected kA ratings.]
                c.     UL 1449 - Third Edition Revision; effective September 29, 2009, where
                       applicable either Type 1 or Type 4 Voltage Protection Ratings shall not
                       exceed the following:
                      VOLTAGE        L-N       L-G       N-G   L-L     MCOV
                      208Y/120       800V      800V      800V  1200V   150V
                      480Y/277       1200V 1200V 1200V 2000V           320V

July 26, 2009                                                                        [Project Name]
Surge Protective Devices for Low-Voltage Electrical Power Circuits
                                              26 43 13-4
         8.     UL 1449 Listed Maximum Continuous Operating Voltage (MCOV) (verifiable at
                UL.com):
                   System Voltage          Allowable System Voltage Fluctuation (%)        MCOV
                      208Y/120                               25%                            150V
                      480Y/277                               15%                            320V
         9.     SPD shall have a minimum UL 1283 listed EMI/RFI filter with minimum attenuation
                of - 50dB at 100 kHz.
         10.    Suppression components shall be heavy duty „large block‟ MOVs, each exceeding
                30mm diameter.]
         11.    [SPD shall include a serviceable, replaceable module (excluding Branch).]
                [Deletable note: Delete or adjust as appropriate.]
         12.    SPD shall be equipped with onboard visual and audible diagnostic monitoring.
                Indicator lights shall provide full time visual diagnostic monitoring of the
                operational status of each phase of the surge current diversion module. A red
                indicator light will indicate loss of suppression capability. A green indicator light
                will indicate fully operational suppression capability. Audible diagnostic
                monitoring shall be by way of audible alarm. This alarm shall activate upon a fault
                condition. An alarm on/off switch shall be provided to silence the alarm. An alarm
                push to test switch shall be provided. The SPD diagnostic monitoring devices shall
                be mounted on the front of the panelboard enclosure. The diagnostic monitoring
                circuits shall continually monitor the operational status of the surge current
                diversion module. A diagnostic system press to test switch shall be provided. A
                set of Form C dry contacts shall be provided for remote annunciation. No other
                test equipment shall be required for SPD monitoring or testing before or after
                installation.
         13.    SPD shall have a response time no greater than 1/2 nanosecond for any of the
                individual protection modes.
         14.    SPD shall have a warranty for a period of ten years, incorporating unlimited
                replacements of suppressor parts if they are destroyed by transients during the
                warranty period. Warranty will be the responsibility of the electrical distribution
                equipment manufacturer.
         15.    SPD shall be equipped with the following optional items:
                a.     Transient event surge counter shall be located on the front cover of the
                       panelboard. The counter shall be equipped with a manual reset and a battery
                       to retain memory upon loss of AC power.]
   C.    [[Branch Panels]
         1.    The panelboard shall be UL 67 Listed and the SPD device shall be UL 1449 Third
               Edition Type 4 Listed.
         2.    The unit shall be top or bottom feed according to requirements. A circuit directory
               shall be located inside the door.
         3.    SPD shall meet or exceed the following criteria:
               a.     Maximum 7-Mode surge current capability shall be [100kA] [200kA] per
                      phase. [Note: Delete unselected kA ratings.]
               b.     Maximum 10-Mode surge current capability shall be [150kA] [300kA] per
                      phase. [Note: Delete unselected kA ratings.]
               c.     UL 1449 - Third Edition Revision; effective September 29, 2009, where
                      applicable either Type 1 or Type 4 Voltage Protection Ratings shall not
                      exceed the following:
                     VOLTAGE       L-N      L-G     N-G       L-L     MCOV
                     208Y/120      800V     800V    800V      1200V   150V
                     480Y/277      1200V 1200V 1200V 2000V            320V
         4.    UL 1449 Listed Maximum Continuous Operating Voltage (MCOV) (verifiable at
               UL.com):
                  System Voltage         Allowable System Voltage Fluctuation (%)        MCOV
                     208Y/120                              25%                            150V

July 26, 2009                                                                        [Project Name]
Surge Protective Devices for Low-Voltage Electrical Power Circuits
                                              26 43 13-5
                        480Y/277                               15%                            320V
            5.    SPD shall have a minimum UL 1283 listed EMI/RFI filter with minimum attenuation
                  of - 50dB at 100 kHz.
            6.    Suppression components shall be heavy duty „large block‟ MOVs, each exceeding
                  30mm diameter.]
            7.    [SPD shall include a serviceable, replaceable module (excluding Branch).]
                  [Deletable note: Delete or adjust as appropriate.]
            8.    SPD shall be equipped with onboard visual and audible diagnostic monitoring.
                  Indicator lights shall provide full time visual diagnostic monitoring of the
                  operational status of each phase of the surge current diversion module. A red
                  indicator light will indicate loss of suppression capability. A green indicator light
                  will indicate fully operational suppression capability. Audible diagnostic
                  monitoring shall be by way of audible alarm. This alarm shall activate upon a fault
                  condition. An alarm on/off switch shall be provided to silence the alarm. An alarm
                  push to test switch shall be provided. The SPD diagnostic monitoring devices shall
                  be mounted on the front of the panelboard enclosure. The diagnostic monitoring
                  circuits shall continually monitor the operational status of the surge current
                  diversion module. A diagnostic system press to test switch shall be provided. A
                  set of Form C dry contacts shall be provided for remote annunciation. No other
                  test equipment shall be required for SPD monitoring or testing before or after
                  installation.
            9.    SPD shall have a response time no greater than 1/2 nanosecond for any of the
                  individual protection modes.
            10.   SPD shall have a warranty for a period of ten years, incorporating unlimited
                  replacements of suppressor parts if they are destroyed by transients during the
                  warranty period. Warranty will be the responsibility of the electrical distribution
                  equipment manufacturer.
            11.   SPD shall be equipped with the following optional items:
                  a.     Transient event surge counter shall be located on the front cover of the
                         panelboard. The counter shall be equipped with a manual reset and a battery
                         to retain memory upon loss of AC power.
            12.   The unit shall have removable interior.
            13.   The main bus shall be [copper] [aluminum] and rated for the load current required.
            14.   The unit shall include a 200% rated neutral assembly with copper neutral bus.
            15.   The unit shall be provided with a safety ground bus.
            16.   The field connections to the panelboard shall be main lug or main breaker.
            17.   The unit shall be constructed with flush or surface mounted trim and shall be in a
                  NEMA Type 1 enclosure.]

PART 3 - EXECUTION

3.1        INSTALLATION
      A.    Install per manufacturer’s recommendations and contract documents.
3.2        ADJUSTMENTS AND CLEANING
      A.    Remove debris from installation site and wipe dust and dirt from all components.
      B.    Repaint marred and scratched surfaces with touch up paint to match original finish.
3.3        TESTING
      A.    Check tightness of all accessible mechanical and electrical connections to assure they are
            torqued to the minimum acceptable manufacture’s recommendations.
      B.    Check all installed panels for proper grounding, fastening and alignment.
3.4        WARRANTY

July 26, 2009                                                                               [Project Name]
Surge Protective Devices for Low-Voltage Electrical Power Circuits
                                              26 43 13-6
   A.    Equipment manufacturer warrants that all goods supplied are free of non-conformities in
         workmanship and materials for ten (10) years from date of shipment.
                                        END OF SECTION




July 26, 2009                                                                           [Project Name]
Surge Protective Devices for Low-Voltage Electrical Power Circuits
                                              26 43 13-7