SIMs iFIX 3.5

Document Sample
SIMs iFIX 3.5 Powered By Docstoc
					                                      SIMs for iFIX 3.5
                                   Last updated 10/19/2006


iFIX 3.5 English

iFIX35_1123523131FixTagGroupDll.dll                          155,769     07/17/2006
                 Fix2DBitmapDll.dll                          192,659     06/28/2006
                 Fix2DBitmap.tlb                             30,196      06/28/2006
                 FixBackgroundServer.exe                     45,138      06/23/2006
                 OpcDataSystem.dll                           450,690     06/20/2006
                 FixEventDll.dll                             155,780     06/07/2006
                 FixAppDll.dll                               209,007     06/07/2006
                 FixPageDll.dll                              352,369     06/07/2006
                 PlugandSolve.fxg                            826,880     05/23/2006
                 FixLookupDll.dll                            172,166     05/23/2006
                 FileTree.ocx                                57,344      05/12/2006
                 WSACTASK.EXE                                53,299      05/08/2006
                 SACDLL.DLL                                  192,561     05/08/2006
                 SecuritySynchronizerDLL.dll                 356,423     04/27/2006
                 SECCFG.exe                                  397,366     04/27/2006
                 SECMGR.dll                                  65,590      04/27/2006
                 VisiconXData.ocx                            413,787     04/21/2006
                 FixChartDlg.dll                             499,792     04/04/2006
                 FixComponentDll.dll                         589,931     03/28/2006
                 AlmSumMgr.DLL                               102,478     03/17/2006
                 AlarmSummaryOCX.ocx                         385,112     03/17/2006
                 AlmSumMgrRes.dll                            20,480      03/17/2006
                 AlarmSummaryOCXRes.dll                      65,654      03/17/2006
                 PictureConverterDll.dll                     495,712     03/02/2006
                 Fix2DTextDll.dll                            290,959     03/02/2006
                 FIXERROR.DLL                                139,264     02/28/2006
                 Fix2DGroupDll.dll                           282,769     01/31/2006
                 Fix2DPenDll.dll                             430,239     01/27/2006
                 FIX.EXE                                     208,946     12/28/2005
                 FIXSRV.exe                                  65,589      12/28/2005
                 FixSchedulerDll.dll                         520,326     12/28/2005
                 FixPictureDll.dll                           438,402     12/28/2005
                 VisiconXGrid.ocx                            114,779     12/25/2005
                 FixGlobalSysInfoDll.dll                     143,491     11/15/2005
                 FCATABLE.DLL                                53,305      11/15/2005
                 LOGIN.EXE                                   143,410     11/12/2005
                 ExpertGlobalRES.dll                         86,016      11/11/2005
                 ALMODBC.exe                                 118,847     11/01/2005
                 FactoryGlobalsRES.dll                       61,440      09/30/2005
                 FixControlContainerDll.dll                  331,939     08/18/2005
                 EnumerationsDLL.dll                         28,672      08/15/2005
                 LDBA.dll                                    299,061     08/15/2005
                 FactoryGlobals.fxg                          1,822,208   07/27/2005
                 CONMGR.exe                                  69,684      07/25/2005
                 FixFileLinkDll.dll                          249,977     04/13/2005
                 WorkSpace.exe                               139,335     03/21/2005
                 FixUserPreferencesManagerRes.dll            20,480      03/16/2005
                 FixFormatDll.dll                            155,782     03/16/2005
                 FixFormat.tlb                               19,432      03/16/2005
                 FixUserPreferencesManagerDll.dll            135,290     03/16/2005
Scripting.dll                  225,356     03/16/2005
ValvesAnim.fds                 222,208     02/14/2005
FixBackgroundServerRes.dll     40,960      02/09/2005
FixPropDlg.dll                 364,622     02/09/2005
Tanks.fds                      269,824     02/09/2005
TanksAnim1.fds                 261,120     02/09/2005
TanksAnim2.fds                 271,872     02/09/2005
PipesAnim.fds                  194,560     02/09/2005
Pipes.fds                      220,672     02/09/2005
ExpertGlobal.fxg               2,712,576   02/09/2005
Fix2DAxisDll.dll               213,153     02/07/2005
Fix2DChartDll.dll              360,611     02/07/2005
Fix2DLegendDll.dll             262,309     02/07/2005
SearchReplace.dll              143,444     02/04/2005
FixDataLinkDll.dll             213,152     02/04/2005
iFixScreenSaver.scr            102,482     02/03/2005
TimerManager.dll               57,426      01/11/2005
FixTimerDll.dll                184,435     01/11/2005
Fix2DShapeDll.dll              434,307     12/28/2004
FixAnimationDll.dll            139,388     12/28/2004
FixLinearDll.dll               139,398     12/28/2004
Fix2DShape.tlb                 30,128      12/28/2004
FixComponentRes.dll            16,384      12/28/2004
SUMQLIB.DLL                    81,975      12/28/2004
SCU.exe                        618,547     12/28/2004
FixErrToHResult.dll            24,664      11/29/2004
WorkSpaceErrorsRes.dll         57,344      11/29/2004
FixShapeDll.dll                110,707     11/08/2004
FixAppServiceDll.dll           102,525     09/27/2004
OpcEdaDll.dll                  143,436     09/21/2004
AlmODBCConfig.exe              159,836     09/17/2004
FixControlContainerRes.dll     32,768      09/10/2004
QUE2LIB.DLL                    61,494      08/16/2004
FixUserPreferencesDll.dll      225,380     07/21/2004
FixPropDlgRes.dll              69,632      07/20/2004
launch.exe                     102,465     07/17/2004
OODBDll.dll                    225,360     07/17/2004
FixDataSystems.ocx             114,797     07/02/2004
OPC20iFIX.exe                  290,887     07/02/2004
WorkSpaceRes.dll               135,168     07/02/2004
FixUserPreferencesResDll.dll   49,288      06/10/2004
NLSAPI.DLL                     41,014      04/12/2004
CrossReference.exe             610,385     03/31/2004
ExpressionEditor.ocx           258,138     03/31/2004
SecuritySynchronizerRes.dll    32,768      02/19/2004
SEC_AF.DLL                     16,384      02/19/2004
FixKeyMacroDll.dll             65,641      02/19/2004
FixKeyMacroHandlerDll.dll      77,943      02/19/2004
XDBA.dll                       53,301      02/13/2004
ExpertGlobals2.fxg             1,610,752   02/04/2004
FixVariableDll.dll             131,193     01/30/2004
FixDynamoSetServer.dll         159,875     01/16/2004
FixGlobalsServer.dll           159,871     01/16/2004
FixPictureServer.dll           159,871     01/16/2004
FixSchedulerServer.dll         159,875     01/16/2004
FixToolbarServer.dll           159,871     01/16/2004
FixToolbarDll.dll                              348,290              01/16/2004
SumqUpdate.exe                                 24,645               12/10/2003
FD_BDW.dll                                     28,672               09/17/2003
launchres.dll                                  49,152               09/15/2003

* Tag group resolution does not work properly if using the DefaultRefreshRate entry in
the Workspace.ini file and resolving tags before switching to Run mode. (1-
123523131)

* Bitmap Pushbutton stays stuck down, when pushbutton is invisible and user clicks
on area where pushbutton exists. (1-162154461)

* FixBackgroundServer events logged in the NT Event Viewer are not mapping with
descriptions.(1-144598020)

* Data in a picture never updates.(1-144898371)

* If Fire DataChange Event is disabled, then global user variable never triggers (1-
155223934)

* In the Chart Group File dialog, the file tree doesn't support Kanji Characters. (1-
112641852)

* Changing the DataSource for the last existing pen in a chart group file using the
Chart Group Wizard causes the values for color and limits to be reset. (1-111307898)

* Color animations using shared threshold table don't work properly if the same
threshold table is used by different pictures and these pictures are all opened in run
mode. (1-147175602)

* In the Chart Group File dialog, the file tree doesn't support Kanji Characters. (1-
112641852)

* It was not possible to use a "_" in a Windows User Name when running
SecuritySynchronizer (1-161443891)

* SQT blocks get stuck in the state of waiting for confirmation once their confirmations
get lost or never happen. (1-97202545A)

* VisiconX data control requires user with local administrative rights to connect to
OLE DB database. (1-110895991)

* Can't set the span interval to be 0 at chart configuration. (1-118948231)

* Workspace OPC client does not display OPC server's error string correctly (1-
126022821)

* Complex expressions fail after installation of sim 1-95976911 on Japanese iFix (1-
116459481)

* Log file and Alarm ODBC database don't capture each unsuccessful login attempt
(1-150615677)

* TX Block's comm. alarm doesn't show up on the AlarmSummary. (1-118034431)

* Alarm Summary OCX doesn't allow user to filter by the ACK column. (1-103547011)
* Picture Converter does not convert command comments correctly. (1-105643029)

* Cannot backspace when adding characters to a datalink. (1-115227146)

* Slow NT authentication for iFIX domain user (1-95990941C)

* Accelerator for Pushbutton doesn't work when Pushbutton is grouped (1-
116290921)

* Pictureconverter leaves unwanted '&' character in button! (1-116895871)

* Datalinks converted from FIX32 will highlight even though they were not
highlightable in the FIX32 picture.(1-127653268)

* Chart does not update correctly when changing tag group file that references t_data
(1-108273211)

* Automation error occurs when the DBDisconnect method is used in the
ExecuteComplete event of the VXDATA control. (1-119581251)

* iFix can't shut down ALMODBC and WSQLODC if they connect to a Sybase 9.xx
database on French OS. (1-105652516)

* Zooming a chart causes value ranges displayed on the Y axis of the chart to go
beyond its pens' EGU limits.(1-93670101)

* Encounter error when trying to modify schedule that has been set to run in
background (1-100502591)

* Unable to enter the Slash(/) from numeric pad in a Datalink. (1-112641841)*
Datalink doesn't support supressing character entry (1-116023901)

* Commandbutton no longer highlights in run mode after undoing a delete in
Configuration mode (1-115514116)

* Autoresize property of VisiconXData control doesn't resize columns after fetching
data.(1-113180591)

* Workspace intermittently disappears\access violation when running on RDP clients
(1-36959520)

* Advanced animation with TagGroup expressions containing complex expressions
no longer worked after installation of sim (1-100954501)

* Logging out of windows causes Fix service to goto stopping (1-100137961)

* ALT-TAB permissions not restored properly when using stacked logged in users (1-
109910701)

* "User Defined Fields" work differently for Alarms vs Events (1-106088924)

* Blinking property of an animated object using Dynamos is not working properly. (1-
99874598)
* Fonts stop changing horizontally in proportion to vertical changes if you change the
resolution of the screen while configuring a chart. (1-99237697)

* CommandButton script isn't recorded on basic animation dialog (1-106169060)

* Get error message "Expressions containing Historical items is not allowed" when
adding a pen that references to a iHistorian tag to a chart group file, if the pen name
matchs the pattern of "*.*.*.*.*". (1-71329801)

* Get error message "Secure Containment Detected Bad Control ..." and Workspace
crash while configuring a VisiconX data control to use Microsoft OLE DB Provider for
SQL Server as data provider, if more than 255 SQL servers are available in the
network.(1-99995157)

* Application crash when writing to A_ENAB field using EDA (1104354604)

* Alarm Acknowledge messages are being sent to the AA/DA block alarm areas
instead of the alarm areas for operator messages. (1-101856381)

* OnDataChange Event Does not Fire first time value changes (197333581)

* AcknowledgeAnAlarm can't acknowledge an alarm using a tag group symbol.(1-
95001621)

* Double byte dash "-" is not recognized for a object name in iFIX 3.5 Japanese. (1-
95976911)

* The GetFullName method of the ESignature object doesn't work if the Windows
user is a local user and the method is used to get a domain user's full name.(1-
52405328)

* MouseUp and MouseUpOffObject scripts do not work properly. (1-91893091)

* Find operation in workspace always sets dirty flag (1-101005761)

* AlmODBC crashes with STK Userfield and STK alm extension field being truncated
(142562201)

* When selecting text in a datalink that has "Leading Spaces" enabled, the text
highlight strips of the leading spaces (1-37828101)

* Workspace application crash when closing a picture that was created on a machine
with FIXDesktop installed and run on a machine without FIXDesktop installed. (1-
94231958)

* The Workspace application object does not properly accept negative values for the
TOP and LEFT properties. (1-90865926)

* Alarming-suspended/resumed messages are being sent to the AA/DA block alarm
areas instead of the alarm areas for operator messages. (1-91722901)

* Can't type in a space in editing mode of the standard text tool after installing
iFIX35_281537 or a later workspace SIM and having selected the Remove Leading
and Trailing Spaces option for text in the User Preferences.(1-83444001)
* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* Workspace crashes when switching between pictures using ReplacePicture
subroutine, if picture caching is enabled and the new picture names passed in
ReplacePicture are"xxxxx.grf" and "xxxxx.grf "(i.e. file names with trailing whitespace
characters).                                (288907)

* Read-write access to the security path is needed in order to use the security
configurator. (1-83519101)

* After installing iFIX35_294859, when Workspace is started, it is not restored at the
size that it was last closed. (1-85376901)

* Find function in VBE of Workspace does not handle inputting double byte characters
correctly. (1-79830201)

* Precision adjustment for a float-value datalink causes the value sometimes being
displayed with a different rounding from the Curr Value field in the Database
Manager. (1-43322301)

* The Timer Cursor shows no data for the last sample using SetPenDataArray
method. (1-79315501)

* FIXbackgroundServer Event ID 103, 107, 108, 111 messages appear erroneously in
the Event log (266950)

* Custom color palettes do not work using tank, valve and pipe dynamo's. (272910)

* Ramp Expert doesn't set the value to the low/high limit, when the new value
exceedes the limit.(270674)

* Some automation subroutines (AcknowledgeAnAlarm, RampValue, SetManual,
SetAuto, ToggleManual) change the values of parameters passed to them.(273349)

* The WriteValue VBA method sent an incorrectly formatted operator message if the
data source had a "%" in it.             (264630)

* Added Interval Field to Chart Group Wizard (274023)

* Chart group methods are not accessible in the background task.(272466)

* The Visibility Expert adds lookup levels in the descending order of input values
when configuring, which causes visibility animations to be converted incorrectly as the
Web Converter is expecting all lookup levels in the ascending order of input
values.(276784)

* A visibility animation created with a range, will not be edited correctly with the
visibility expert. (274718)

* FixBackgroundServer can't monitor running schedules, when run as a service on
WIN2000. (287836)

* Custom color palettes don't work in a pen's color. (262282)
* After opening and closing the VBA property window, a pen can't be deleted from a
chart properly. (268805)

* Using ModifyColumnLength VBA method to change the Chart's legend column
length, causes the legend text to grow and stretch. (271284)

* VisiconX Grid time field displays both system date and time. (279234)

* Can't open a .csv file by using VisiconX and OleDB provider for ODBC. (259313)

* Find and Replace messes up script.(273672)

* Changing the Object Name and Description on the Basic Animation Dialog does not
dirty the containing picture. (277534)

* Close and Save method of Document(s) allow document(s) to be saved during
mode switch, which sometimes causes the document(s) to be corrupted.(267849)

* FixBackground Server crashes while running iFIX as a service. (272155)

* "Invalid Handle" message is given when a "Delete All" is executed on the Alarm
Summary OCX.(260452)

* Datalink raw format resets when changing the datasource. (264403)

* The current alarm index would intermittedly get stuck on last alarm acknowledge
when scroll bars are enabled and ACK/PRIORITY descending. (272349)

* Alarm Summary's status bar prints black when using XP themes. (278401)

* iFixScreenSaver will hang if Login.exe is already opened (295038)

* AlmODBC crash when STK Userfield lengths exceed 79 characters and also STK
alarm extension field was being truncated. (142562201)

* TagGroup expressions containing complex expressions cause high message rate
(264443)

* Initial update of datalink values is slow when first opening a picture (1-19756822)

* Users get 'Invalid qualifier' error on data entry form after installing iFIX35_292319B
SIM.(1-42578390)

* Daily schedules running in the background skip firing every other day and double
firing at midnight when using New Zealand regional settings and time zone.(263814)

* Using the ToggleDigitalPoint expert and then running the Tag Group Editor (Get
Symbols From Picture), will not get all of the Tag Group Symbols that are eligible in
the picture.(274890)

* In datalink and some animation experts, if the data source is a single source, not an
expression, the tolerance gets reset to default.(276128)

* Remove Level automation method causes a memory leak. (273677)
* Dashed lines are printed as solid. (272979)

* Bitmap Pushbutton stays stuck down, when using a mouse down event that
launches a modal dialog. (278520)

* Tooltip would intermittedly flash on select PC's (266730)

* Can't get a property name correctly using the property dispatch ID, if the dispatch ID
is zero.(272807)

* When implementing the same VBA procedure in a picture and in a group (of objects
contained) as well, the VBA procedure was disabled at the picture level after
renaming the group. (275682)

* When using automation SelectObject method to select multiple objects, the color
property was only being set on the last selected object. (279699)

* MDI->EV->DA chain goes off-scan on iFIX re-start or database reload. (269246)

* More than 20 consecutive calls                 to   FixGetUserInfo     would    return
"smo_replace_profile: bad index". (273300)

* Tag description not being written to RDBM from AlarmODBC (268799)

* When using the sa_almmsg_cb and passing in the timestamp for the alarm, the
TimeIn on view nodes would not get updated if there was an existing alarm. (277780)

* AAD file cannot be accessed from VIEW node. (269866)

* Random "iFIX Detected a Serious Problem. Please Shut Down Restart iFIX" errors
(1-52135901)

* Text object has no space in between multiple lines of text. (1-34485756)

* Pressing the CTRL and then the TAB keys repeatedly causes the Workspace to
consume 100% CPU usage and makes the workspace unresponsive. (141913801)

* Some methods of Alarm Summary cause memory leak. (266745)

* Datalinks not retaining\displaying leading\trailing spaces when writing to TX Blocks
(1-37828101)

* After choosing a color from a custom color set, a foreground color animation
configured with the Foreground Color Expert cannot retain any new color selection
from the system default color set. (1-32449601)

* Deleting the Enabled animation of a push button from the system tree causes the
push button disabled.(1-34153301)

* Applying a chart group file that has an interval greater than 1 minute to an iFix chart
results in an error message "FIX2DPen invalid parameter".(1-32281101)

* Turning on data system prematurely causes some animations to work incorrectly.(1-
27285016)
* Unusual Behavior when pictures are saved outside the PIC directory and switched
to Run mode (1-32486401)

* Added a configuration setting to the .ini file to allow the user to specify the method
iFIX uses to open picture (290712)

* Animation data error doesn't work properly after installing iFIX35_SP1. (1-
32916701)

* The "Blink on New Alarm" checkbox will not stay checked the datasource is a tag
group and the animation is opened using the wizard. (132796801)

* The a F_CV value on RealTime Chart will cause the chart to blank and restart when
duration is changed (294512)

* The basic animation table settings are lost when using an undefined user global
variable as the data source in the basic animation dialogs.(1-21409801)

* Data Type mismatch error on automation method "AcknowledgeAllAlarms" when the
picture contains an object with an animation with a datasource equal to a constant.
(1-25827301)

* An event based schedule doesn't fire if it is using the System.CurrentTime property
in its data source and run in the background.(294413)

* Shape animation is no longer valid after a global Search and Replace (292319)

* Additional OPC Refresh configuration option. (119237501)

* Increased the maximum limit of the number of records to read from the User queue
before writing to the relational database for AlarmODBC. (280263)

* The Address fields in Device Control (DC) block does not accept syntax for OPC
Client driver. (290932)

* Digital Input block's alarm for the Close state, goes away on database reload.
(122925753)

* The MS Forms 2.0 Textbox control was not scrolling text properly. (292395)

* Workspace.exe in the SCU tasklist did not startup in the mode indicated by the
mode settings.(294859)

* Find & Replace failed with access exception (119739601)

* SetTimeCursorTime Method does not work properly.(292789)

* When using flexdata and thousands of alarms, the AlarmSummaryOCX was slow in
responding to subsequent Workspace user actions after the AlarmSummaryOCX was
initially opened in Workspace Run. (293322)

* An iHistorian Calculator Collector stop\re-start in the iHistorian Administrator would
cause the tag calculation to fail, "Object is not connected to the server". (290840)

* Down arrow key does not work if first datalink is invisible. (293910)
* Grouped Datalink sourced from a Global variable displays the stale data value if the
picture cache is enabled. (291986)

* SetTimeCursorTime Method does not work properly.(292789)

* Cannot de-select "Remove Trailing and Leading Spaces" for text objects in User
Preferences.(17410327)

* The animation table settings are lost when Using a undefined User Global Variable
in the Advanced Animation dialog. (288314)

* AlmODBC doesn't insert multiple records into SQL. (292290)

* Duplicate Logical Nodename error when using Launch with command line
parmeters /s /l /n (288317)

* License Error - iFIX has detected a serious problem. Please shutdown and restart
iFIX" generated when there was an invalid path or entry in the task list. (292781)

* Can not switch to run between iFIX and Sample System (NLS) (279886)

* NLS Translation issues (279280)

* AcknowledgeAllAlarms subroutine doesn't work for tag groups after migrating the
picture created with iFIX 2.6 to iFIX 3.5.(293393)

* Nudge settings not reflecting settings from the Fixuserpreferences.ini (294535)

* Added the ability to suppress RANGE, UNDER RANGE, and NODATA alarms.
(290732)

* Fix Data System OCX not working (294185)

* Spacing between lines in a multiple-line datalink changes when the last few lines are
blank.(292544)

* XYHistTest Method returns error (292899)

* Dead lock condition using OPCEDA asynchronously. (283840)

* OpciFix OPC server doesn't browse STK tags. (290388)

* Pictures are resized when the workspace opens after it was last closed in the
minimized or restored state.(292398)

* Duplication turns PushButton to FixOLEControl.(292381)

* Legend object get_LegendHeadingLine() is not returning Interval column name and
GetColumnInfo() method is returning empty column name.(294667)

* If the AlarmSummaryOCX is scrolled, and a new alarm comes in, the visible viewing
area is reset to the new end rows. (292610)

* SecuritySynchronizer crashes when logging oversized message.(292169)

* Added automation properties to support infoAgent 2.0 (293871)
* Clicking the Cancel button when configuring a schedule item causes some scripts
removed if the beginning of the names are the same for the timer and event schedule
items and the underscore character is used.(290611)

* Text object doesn't go to the next line when exceeding MaxCharactersPerLine.
(291537)

* Duplication of dynamo generates objects with same name.(290257)

* Applying a chart group file to a chart sometimes doesn't set EGU limits
correctly.(288261)

* VisiconX shows no data in the VisiconX Grid when opening a picture that has been
cached. (289291)

* Build Dynamo Wizard: Partial substitution for a dynamo property value does not
work properly if there is a decimal point in the animation data source.(290242)

* Animations don't work using constant numerical datasources. (288963)

* DBASRV inadvertently starts running when during iFIX startup. (291346)

* When using a long datatype datablock from an OPC server as the datasource in a
datalink, the value was different in the iFIX database and the datalink by 1. (292059)

* Alarms with the same Time In and Time Last are sometimes displayed in a different
order depending on the Sort Key. (289889)

* Script events created with the VBA FindReplaceInObject automation method do not
fire. (287883)

* Using NT security with iFix security, password expires error message occurs, even
though the user account is set to password never expires. (288005)

* Animated Text object caption doesn't work, if the datasource is static text. (286466)

* A chart does not display axes and grids after setting its current pen to be not
visible.(287462)

* Bad event message being sent to alarm typers, when user tries to set alarm values
of block higher then Egu Hi (290559)

* VBA Errors on install when installing to a machine with XP machine that has
sublanguages installed. (289295)

* Color animation's table resets when leaving expression editor, using the color
experts. (290442)

* Group click events do not fire when clicking on a control with no events. (285712)

* RetrieveTagGroupVariable method leaks memory.(287253)

* Acknowledged Alarms were being dropped from alarm synchronization (288698)
                 * The property name gets stripped from animation data source when reentering the
                 animation dialog, if the data source is an OLE object's default property.(287357)


iFIX35_1112501941 VDBA.DLL                                    41,014              11/28/2005
                 EDA.dll                                       86,067             10/24/2005
                 DDECLNT.EXE                                   188,471            10/24/2005
                 etr.gov                                       978                08/15/2005
                 pa.gov                                        2,112              08/15/2005
                 tr.gov                                        978                08/15/2005
                 hs.gov                                        978                08/15/2005
                 ev.gov                                        978                08/15/2005
                 dt.gov                                        870                08/15/2005
                 DataBaseManager.exe                           663,635            07/27/2005
                 FixDB32_DO.dll                                57,430             07/14/2005
                 FixDB32_AO.dll                                65,622             07/14/2005
                 FixDB32_DI.dll                                65,622             09/07/2004
                 FixDB32_DR.dll                                53,334             09/07/2004
                 FixDB32_DA.dll                                73,814             09/07/2004
                 FixDB32_BLRes.dll                             16,495             06/14/2004
                 FixDB32_DIRes.dll                             16,495             06/14/2004
                 FixDB32_DORes.dll                             16,495             06/14/2004
                 FixDB32_DARes.dll                             16,384             06/14/2004
                 FixDB32_DRRes.dll                             12,288             06/14/2004
                 DatabaseManagerRes.dll                        204,800            06/10/2004

                 * iFix Database Toolkit gives it 4293 string in alarm status when the alarm is COMM
                 (1-112501941)

                 * NETDDE cannot get remote Excel data in view on Win 2000 machine. (1-
                 115030351)

                 * Alarm Extension fields not being exported for some blocks (1-103966121)

                 * Low EGU limit of 0.000001 causes error on import of database (187182953)

                 * Event messaging no longer works on AO and DO blocks (186558030)

                 * Database Manager will not start on machines with large registry files (1-86803501)

                 * The Database Management spreadsheet displays incorrectly if a tag is imported that
                 has double byte and regular characters that exceed the length limit of a field. (1-
                 79830256)

                 * PDB queries not working when there is no SORT order criteria (1-19734301)

                 * Open/Close labels do not change case on Digital blocks (293103)

                 * DB Manager EXPORT problem with Large Loadable Block (292393)

                 * Database Manager doesn't allow lowercase for digital and boolean block
                 labels.(277527)

                 * Importing a CSV file into Database Manager that contains an equal sign(=) in the
                 description field, without single quotes surrounding it, causes the block to import
                 incorrectly without error.(269981)
                * The DA block's alarm mode switch's to NEVER from ACK, if no option is selected.
                (283296)

                * Database Manager only shows first 50 tags upon initial startup. (286760)

                * DatabaseManager crash while opening on a machine with Windows Server 2003,
                iFix 3.5, and iHistorian 2.0 installed. (283446)

                * Database Manager could not modify values in certain fields (Init Alarm, etc.)
                (286209)

                * Database Manager could not load queries if the extension was capitalized (i.e.
                *.QRY) (283131)


iFIX35_1174403491NAC.exe                                    53,299               08/14/2006
                 NA_ANALZ.dll                               53,308               06/03/2004

                * Alarms no longer synchronize properly on some redundant systems after installing
                iFIX35_288678. (1-174403491)

                * Login message initiated on Client is not sent to backup SCADA node, when client is
                looking at Backup SCADA as active node. (288678)


iFIX35_1103329301 VIEW.EXE                                  1,634,370            05/12/2006
                 WSProxy.EXE                                106,560              09/01/2004
                 DRAW.EXE                                   2,404,418            08/11/2004
                 SUMQLIB_FIX32.DLL                          77,895               08/11/2004
                 HTD.EXE                                    1,060,928            08/11/2004

                * Thousands separators are placed incorrectly for some negative values of FIX
                Desktop datalinks. (1-103329301)

                * When trying to open a .grf picture through WSProxy and the picture does not exist,
                "Untitled1.grf" was not closed in WorkSpace on NLS product versions. (1-24827620)

                * Reinitialize File Dates for iFix35_294534 for NLS. Also new SIM numbering scheme
                for Desktop.

                * Buffer overrun when using View.exe in Async mode. (294534)

                * Alarms indicated with area "ALL" were not being displayed in the Alarm Summary in
                View, when the AlarmSummaryOCX was set up to filter area "A" only. (292441)


iFIX35_199756141 NAM.exe                                    61,491               03/01/2006

                * Alarms were being sent to clients even though NONE is set in Filteralm.ini when
                using non-english versions (1-99756141)

                * NAM is only dispersing about 10+ alarms per second to attached NAC's (289755)


iFIX35_1145497751 NETDIAG.EXE                               196,671              03/02/2006
                   SKT.DLL                                        188,473               07/07/2005
                   TCPDUMP.EXE                                    61,501                07/07/2005
                   TCPTASK.EXE                                    167,997               07/07/2005

                   * "Out Of Sync In Use" Error In Netdiag. (1-145497751)

                   * Netdiag diagnostic tool fails to return valid information for the Socket Tables. (1-
                   114583744)

                   * SocketRec and Trace Tabs in Netdiag are not functional. (1-99199716)

                   * Terminal Server clients cannot connect to the SCADA node after installing
                   iFIX35_SP1. (295207A)

                   * iFIX event file filled up with assertion messages like "assertion failed (ulLocalIpAddr
                   != 0) && (ulLocalIpAddr != INADDR_NONE)" (1-99234191)

                   * An iClient cannot connect thru the RAS client connection if iFIX was already running
                   on the RAS server (SCADA) when the RAS connection was made and the user was
                   somehow able to disable all of the local IP addresses. (277339)

                   * An iClient cannot connect thru the RAS client connection if iFIX was already running
                   on the RAS server (SCADA) when the RAS connection was made. (269268)


iFIX35_155232834 OSXLIB.dll                                       49,206                04/13/2005

                   * When running the FixbackgroundServer in the background and writing a value to an
                   iFIX tag in the schedule and 8.3 format is disabled on the file system, user receives a
                   "Server automation" error. (1-55232834)


iFIX35_189034472 ElectronicSignature.dll                          184,427               05/04/2005

                   * Workspace leaks memory when using WriteValue method with security enabled.(1-
                   89034472)

                   * Workspace would crash if Esignature Dialog was open and script in background
                   closes picture (293354)

                   * E-Sig writes values with improper precision.(285358)


iFIX35_191893246 HDAODBC.dll                                      262,231               07/11/2005

                   * Memory handling error in Historical ODBC driver. (1-91893246)

                   * Fix Dynamics Historical Data - memory leak (268129)

                   * Problem with select Distinct in query when using Historical Data ODBC driver
                   (271969)


iFIX35_122718147 IHHDA.dll                                         81,984               12/01/2004
                 IHHDA3.dll                                        81,986               12/01/2004
                 FIXTOOLS.dll                                      69,693               10/27/2004
                 FixHdaDll.dll                                    73,804               05/17/2004

                 * Expression Builder iHistorian tag browse fails to display the tags associated with iFix
                 collectors but not having a node name as prefix or missing a "." in their tag names. (1-
                 22718147)

                 * Running iHistorian 3.0, when iFIX connects to the Server to get data, a Client
                 Access License (CAL) should not be used. (133962334)

                 * The filtered errors.ini file doesn't work correctly for iHistorian errors and enables
                 iHistorian API timeout to be configurable. (277122)


iFIX35_292646    IOCNTRL.exe                                     57,406                05/27/2004

                 * D parameter for IOCNTRL does not delay driver when used with /S parameter.
                 (292646)


iFIX35_121207706 ALMLIB.DLL.dll                                  86,070                12/28/2004
                 ALM_SYNC.EXE                                    45,112                12/28/2004

                 * Dates are missing from alarm messages sent from an iFix node to a Fix32 node .
                 (1-21207706)

                 * The primary SCADA (of a redundancy pair) logged in user could not write to the
                 A_NALM field even though the alarm was properly acknowledged and A_NALM
                 updated on the backup SCADA.(270021)

                 * eda_alm_get_user_que returned internal alarm acknowledgement messages (1-
                 18722801)


iFIX35_147803764 RCPUP.EXE                                       380,980               12/22/2004
                 RCPDOWN.EXE                                     389,174               12/22/2004
                 RCP.EXE                                         643,122               12/22/2004

                 * Recipe upload stops execution script when encountering a database error.(1-
                 47803764)

                 * Recipe executed using shell command inside VBA takes long time to execute
                 because the dialog stays on for about 5 seconds for each recipe. (282412)


iFIX35_122517301 BackupRestoreDll.dll                            270,426               09/10/2004
                 BackupRestoreRes.dll NLS:English                86,016                09/11/2003
                 BackupRestore.exe                               32,847                09/11/2003

                 * Problem with Backup And Restore wizard when restoring individual file (122517301)

                 * New command line options for backup/restore.


iFIX35_SP1       FIX.EXE                                          208,946              04/19/2004
                 WSACTASK.EXE                                     53,299               04/19/2004
                 CONMGR.exe                                       86,068               04/19/2004
SACDLL.DLL                                 188,465     04/19/2004
FixFileLinkDll.dll                         249,977     04/16/2004
FixPropDlg.dll                             364,622     04/15/2004
FixPropDlgRes.dll NLS:English              69,632      04/15/2004
NLSAPI.DLL                                 41,014      04/12/2004
LDBA.dll                                   299,061     04/12/2004
ExpertGlobal.fxg                           2,700,800   04/12/2004
Fix2DShapeDll.dll                          434,307     04/12/2004
FixShapeDll.dll                            110,707     04/12/2004
Fix2DShape.tlb                             30,128      04/12/2004
FixDataLinkDll.dll                         213,152     04/12/2004
ElectronicSignature.dll                    184,427     04/12/2004
Fix2DPenDll.dll                            430,239     04/08/2004
FixBackgroundServer.exe                    45,138      04/02/2004
FixEventDll.dll                            155,780     04/02/2004
OpcDataSystem.dll                          450,690     04/02/2004
Fix2DChartDll.dll                          360,611     04/02/2004
IHHDA.dll                                  86,080      04/01/2004
ALMLIB.DLL                                 86,070      03/31/2004
SUMQLIB.DLL                                81,975      03/31/2004
CrossReference.exe                         610,385     03/31/2004
PictureConverterDll.dll                    491,616     03/31/2004
SecuritySynchronizerDLL.dll                356,423     03/31/2004
SECMGR.dll                                 61,494      03/31/2004
SECCFG.exe                                 401,462     03/31/2004
ExpressionEditor.ocx                       258,138     03/31/2004
NAM.exe                                    61,491      03/24/2004
SKT.DLL                                    188,473     03/22/2004
TCPTASK.EXE                                167,997     03/22/2004
FixDB32_DA.dll                             73,814      03/12/2004
Fix2DTextDll.dll                           290,959     03/12/2004
FixUserPreferencesResDll.dll NLS:English   49,288      03/12/2004
FIXERROR.DLL                               139,264     03/03/2004
PlugandSolve.fxg                           840,192     03/02/2004
DataBaseManager.exe                        663,635     03/01/2004
Fix2DGroupDll.dll                          282,769     02/23/2004
SEC_AF.DLL                                 16,384      02/19/2004
SecuritySynchronizerRes.dll                32,768      02/19/2004
AlarmSummaryOCX.ocx                        385,112     02/19/2004
FixSchedulerDll.dll                        520,326     02/19/2004
FixKeyMacroDll.dll                         65,641      02/19/2004
FixKeyMacroHandlerDll.dll                  77,943      02/19/2004
XDBA.dll                                   53,301      02/13/2004
AlmODBCConfig.exe                          159,836     02/04/2004
ALMODBC.exe                                118,847     02/04/2004
ExpertGlobals2.fxg                         1,610,752   02/04/2004
FixVariableDll.dll                         131,193     01/30/2004
Fix2DLegendDll.dll                         262,309     01/28/2004
Fix2DAxisDll.dll                           213,153     01/28/2004
FixAnimationDll.dll                        139,388     01/21/2004
FixAppDll.dll                              209,007     01/19/2004
FixPictureDll.dll                          438,402     01/19/2004
VisiconXData.ocx                           413,787     01/16/2004
FixDynamoSetServer.dll                     159,875     01/16/2004
FixGlobalsServer.dll                       159,871     01/16/2004
FixPictureServer.dll                       159,871     01/16/2004
FixSchedulerServer.dll                          159,875              01/16/2004
FixToolbarServer.dll                            159,871              01/16/2004
FixToolbarDll.dll                               348,290              01/16/2004
SIMUninstall.dll                                217,159              12/31/2003
SumqUpdate.exe                                  24,645               12/10/2003
LOGIN.EXE                                       143,410              11/21/2003
Scripting.dll                                   225,356              11/20/2003
QUE2LIB.DLL                                     61,494               11/17/2003
Fix2DBitmapDll.dll                              192,659              11/10/2003
FixComponentDll.dll                             589,931              11/10/2003
Fix2DBitmap.tlb NLS:English                     30,196               11/10/2003
FixControlContainerDll.dll                      327,843              09/26/2003
launch.exe                                      102,465              09/24/2003
ExpertGlobalRES.dll NLS:English                 86,016               09/23/2003
FD_BDW.dll NLS:English                          28,672               09/17/2003
AppValidator.exe                                241,741              09/17/2003
AppValidatorRes.dll NLS:English                 77,824               09/17/2003
launchres.dll NLS:English                       49,152               09/15/2003
StartupProfileMgrRes.dll NLS:English            40,960               09/12/2003
StartupProfileMgr.exe                           94,295               09/12/2003
BackupRestoreRes.dll NLS:English                86,016               09/11/2003
BackupRestoreDll.dll                            270,426              09/11/2003
BackupRestore.exe                               32,847               09/11/2003
TimerManager.dll                                57,426               09/08/2003
FixDB32_DARes.dll NLS:English                   16,384               07/14/2003

* Can not switch to run between iFIX and Sample System (NLS) (279886)

* NLS Translation issues (279280)

* New command line options for backup/restore.

* The DA block's alarm mode switch's to NEVER from ACK, if no option is selected.
(283296)

* Database Manager only shows first 50 tags upon initial startup. (286760)

* DatabaseManager crash while opening on a machine with Windows Server 2003,
iFix 3.5, and iHistorian 2.0 installed. (283446)

* Database Manager could not modify values in certain fields (Init Alarm, etc.)
(286209)

* Database Manager could not load queries if the extension was capitalized (i.e.
*.QRY) (283131)

* E-Sig writes values with improper precision.(285358)

* Added a configuration setting to the .ini file to allow the user to specify the method
iFIX uses to open picture (290712)

* Cannot translate main window title, Detail Report window (Row Count) , Auto Report
Naming (Browse dir window - "Select a directory")

* Double bytes strings are not displayed correctly in Application Validator main dialog,
Comparison Detail Report dialog, and Print Preview dialog. (278413)
* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* Increased range of Help context ID values to support values between -
2,147,483,648 and -2,147,483,647 (290334)

* Some EGU values entered as scientific notation would trigger an "out of range" error
(283944B)

* Reentering the Color Expert dialog and then moving the focus off the Data Source
field causes the Color Threshold Table to be reset to the default if the data source
contains multiple tags.(286911)

* Object becomes invisible in run mode when animation is deleted from iFix Browser
Tree (283047)

* Inserting a datalink and setting a historical datasource, then get an error, and setting
a realtime datasource results in a WorkSpace crash. (286063)

* Workspace crash in PTimeDll when pictures containing charts were repeatedly
opened and closed and modified the time range of the charts. (287787)

* CrossReference tool doesn't use regional settings when saving a file as CSV.
(284883)

* FixBackgroundServer can't monitor running schedules, when run as a service.
(287836)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* RAMP block does not ramp down when low EGU is greater then hi EGU (288563)

* Unable to log into iFix when connection to primary domain controller is lost (267542)

* Security Configuration Modifications to support Classic Desktop. (287808)

* SAC would not start up for 20 seconds, when using a large database. (257584)

* sq_remove() error thrown when trying to modify an AIS block thru the
DatabaseManager. (257625)

* SAC slows down after changing 200 AO blocks current mode from AUTO to MANL.
(269990)

* Added "iBatch - Start iWorkInstruction Editor" to iFIX application security areas
(280371)

* Added command line parameter to suppress ORNG (OverRange) Alarm.(273507)

* SecuritySynchronizer /R removes RECIPE User Account from iFix Security
(281002)

* SecurityArea in Picture Properties will not allow you to assign a area name of 22B, if
you have already assigned a security area 22A to a previous picture (264728)
* iFIX - Windows security it was not possible to use a "." or "'" in the NT user name
(275124)

* Incorrect License Error: iFix has detected a serious problem please shutdown iFix.
(278711)

* OnTrue/OnFalse scheduled events fire on startup even when "Fire DataChange
Event on Startup" is deselected. (285575)

* While trending with T_DATA pens on Terminal Server, a random crash occurs.
(279198)

* Charts created using iFix automation interface get abnormal Width and Height
properties.(285999)

* ETR data doesn't show up correctly when changing the pen's Duration in Run
mode.(285687)

* Picture Conversion causing datalink font size to increase drastically. (288371)

* Object animations and data links not updating because of faulty hardware HAL or
BIOS. (269172)

* Foreground color animation doesn't work until the data source changes its value if
the picture is opened in Run mode. (282461)

* Leading and Trailing spaces for Text objects are being deleted. (283218)

* Setting a pen's fixed start time with only time in a chart group file causes a type
mismatch error when you apply the chart group file.(284209)

* Deleting animations with the Basic Animations dialog will result in the animation
being deleted from the object, but it remains in the system tree. (280962)

* Incorrect datalink format when migrating from fix 32 with a symbol from a tag group
(277426)

* Converting pictures from Fix32 and then trying to rotate objects in iFix would not
work correctly. (272793)

* Picture Converter was not converting a text object's visibility animation exact match
tolerance correctly. (273899)

* Picture converter does not convert expressions for visibility correctly when regional
setting is something other than English (272789)

* Picture converter does not make first line of command script a comment when that
first line is a comment. (262514)

* Picture converter doesn't convert chart's, when the pen's datasource doesn't exist.
(263527)

* If an object is nested in two groups, the size or position animations of that object do
not initialize correctly.(278574)
* If a grouped object has been highlighted and selected and then its group or itself
becomes invisible, the highlight of the object remains on the screen despite the object
being invisible.(277979)

* "invalid argument was encountered..." error while adding pen using WIN2003, iFIX
3.5 and iHistorian. (287196)

* Converted Fix32 datalink with taggroup symbol displays drop down combo box as
alpha-numberic instead of numeric in iFix Datalink Custom Dialog (287172)

* AlarmSummaryOCX not sorting correctly when sort order is set using VB
automation properties (285530)

* Error in setting timer interval, when using Italy regional settings & time separator of
':' (286249)

* Using Key Macros causes memory leak.(283043)

* A global variable's value, when animated to a database tag, is set to zero when
communication is lost to that tag. (284423)

* iFIX Workspace crash showing a memory access violation in PTimedll.dll. when
using a schedule and also picture initialization code to modify Pens in a chart on the
picture. (284593)

* In Build Dynamo Wizard, partial substitution for a dynamo property value does not
work properly if multiple occurences needed. (283379)

* AlarmODBC unable to handle schema name when defined in tablename when
writing to ORACLE (286150)

* Widened fields to support NLS strings (286795)

* Cannot edit a Chart Group File in run mode, using Chart Group Wizard. (285935)

* Opening or replacing a picture containing charts displaying ETR data or other real
time data is slow at iClient nodes. (281963)

* A historical trend chart shows a wrong value for the average over range if only part
of the chart is filled with data. (265305)

* 'High over range' value in charts is 0 if high is a negative number. (275225)

* Pen in Average Hist mode displays line after last known Good value in Chart
(273503)

* Corrected field truncations in Create Picture Wizard and Print Crystal report wizard
forms (285441)

* PictureConverter crash when using DDE links as source of Dynamic Coloring
Property (285824)

* Event firing was inconsistent when using picture caching. (278187)

* Opc datasources used in TagGroup datalinks do not re-connect when the OPC
Server is shutdown and re-started. (282205)
* ETR data doesn't display in charts when opening or replacing the containing
picture.(283572)

* VisiconX Data object would reset back to first record after a query. (284551)

* Workspace temporarily freezes when pictures directly access OPC data points
(285074)

* AlarmODBC.cfg become corrupt if tablename is changed to a shorter name
(284313)

* Security Issue (283386)

* Data Source gets changed from F_# to F_CV if tag does not exist prior to using
color expert (282956)

* Login.exe dialog closes when pressing ESC if opened by iFixScreenSaver (281132)

* When using the iFIX Screensaver, users are unable to change password if expired
(274065)

* F10 Key Macro does not work correctly (263027)

* Tolerance is not being saved using datalinks. (282037)

* Create Picture expert inserts incorrect sizes, using predefined configuration.
(282124)

* MouseUp events do not fire if the mouse button is released off the object. (281070)

* Picture Converter doesn't set MaxCharactersPerLine property to 80 for text objects
less than 80, also AutoSize is set to false. (279003)

* Picture converter corrupts Kanji characters, when converting small Push Buttons.
(278656)

* Table animation entries are not saved when using tag groups as the datasource on
a datalink caption animation. (279936)

* Fix.exe will hang on the shutdown waiting for third-party application which was
registered with iFix using FixRegisterConsole() helper function (277058)

* Cannot set Column widths to stay persistent for alarm summary in configure mode
(279311)

* Cannot translate Build Dynamo Wizard dialog (279274)

* Cannot translate "Use Pixel Coordinates" and "Use Percentage Coordinates"
checkboxes in "In Enter New Configuration Name" dialog (279273)

* Create Picture Wizard NLS: String ID in Tag property were missing in
btnDeleteConfig, pgStyles, pgSizes, btnSave control (278561)

* Continuous iFix Timers would occasionally fire 1 second early. (277455)
                   * Toolbar buttons are missing from the toolbar, during a mode switch. (276640)

                   * Double bytes strings are not displayed correctly in Server selection ComboBox and
                   Item browsing spread control. (NLS) (280803)

                   * AlmSum.exe was hogging 100% CPU for an indefinite period of time. (252294)

                   * Alarm Summary Sorting Problem when using LIN driver and there is no PDB and
                   WSACTASK being used (276687)

                   * Unable to remove user created alarm queue when started by background schedule
                   (276672)

                   * Alarm ODBC service did not log double bytes operator message correctly with
                   calling SendSignedOperatorMessage function when the message is over 82 bytes.
                   (282253 NLS)

                   * Double bytes strings are not displayed correctly in Startup Profile Mgr main dialog.
                   (278412)

                   * NAM is only dispersing about 10+ alarms per second to attached NAC's (289755)

                   * Enables iHistorian API timeout to be configurable (277122)

                   * Allows throttling of the frequency of alarm cycles for the thread that moves alarms
                   from the SAC queue to the Summary queue. (268948)

                   * An iClient cannot connect thru the RAS client connection if iFIX was already running
                   on the RAS server (SCADA) when the RAS connection was made. (269268)


iFIX35_149769164 (Requires iFIX_117410305 - Proficy Portal Picture Conversion Tool)

                   IFIXPictureExport.dll                         295,004              12/17/2004

                   * iFIX Workspace crash using iFIX - Proficy Portal Picture Conversion Utility (1-
                   49769164)


iFIX35_117410305 (iFIX - Proficy Portal Picture Conversion Tool)

                   PictureExportToolbar.tbx                                           07/16/2004
                   PictureExportToolbar.tbc                                           07/16/2004
                   IFIXPictureExport.dll                      295,004                 07/26/2004
                   iFIXPictureExportRes.dll NLS:English       16,384                  07/26/2004
                   IFIXPictureExportWizardRes.dll NLS:English 40,960                  07/26/2004
                   JumpStart.chm                              136,154                 07/26/2004

                   * The wizard exports iFIX picture as SVG format.


iFIX35_AESrv       (iFIX OPC Alarm and Events Server)

                   iFixOPCAESrv.exe                              139,338                  09/20/04
                   OPCiFIXAERes.dll NLS:English                  40,960                   09/20/04
                   Opccomn_ps.dll                                61,440                   06/16/04
                   OPC_AEPS.DLL                                  45,056                    06/16/04
                   NDIAEErrors.dll                               45,056                    06/16/04
                   NDIAESERVER.DLL                               540,672                   09/24/04
                   MSVCP60.DLL                                   401,462                   08/29/00
                   opcaesvr.chm                                  234,692                   09/28/04

                   The main features provided by the Proficy iFIX OPC A&E Server include:

                   - Support for the OPC A&E Server specification (v1.02) for iFIX alarms and events.

                   - Ability to send standard properties of iFIX alarms and events to the Proficy Historian
                   archive.

                   - Configuration of      the   iFIX   OPC    A&E    Server   from    a   user    interface
                   (iFixOPCAESrv.exe).

                   - Ability to report the complete lifetime for almost all iFIX alarms in the OPC A&E
                   client. For more information on doing so with Proficy Historian OPC A&E Collector,
                   refer to the Historian online help.

                   NOTE: Exceptions include acknowledgements not done through the iFIX Workspace,
                   some FIX32 alarms, any connection loss to a block in alarm, and manual deletions.

                   - Support for area and source browsing.

                   - Filtering of OPC A&E event types, event categories, severities, areas, and sources.
                   In addition to these OPC defined filtering techniques, you can also filter alarms and
                   events by the node name.


iFIX 3.5 Chinese

iFIX35_1123523131FixTagGroupDll.dll                              155,769              07/17/2006
                 Fix2DBitmapDll.dll                              192,659              06/28/2006
                 Fix2DBitmap.tlb                                 30,196               06/28/2006
                 FixBackgroundServer.exe                         45,138               06/23/2006
                 OpcDataSystem.dll                               450,690              06/20/2006
                 FixEventDll.dll                                 155,780              06/07/2006
                 FixAppDll.dll                                   209,007              06/07/2006
                 FixPageDll.dll                                  352,369              06/07/2006
                 PlugandSolve.fxg                                826,880              05/23/2006
                 FixLookupDll.dll                                172,166              05/23/2006
                 FileTree.ocx                                    57,344               05/12/2006
                 WSACTASK.EXE                                    53,299               05/08/2006
                 SACDLL.DLL                                      192,561              05/08/2006
                 SecuritySynchronizerDLL.dll                     356,423              04/27/2006
                 SECCFG.exe                                      397,366              04/27/2006
                 SECMGR.dll                                      65,590               04/27/2006
                 VisiconXData.ocx                                413,787              04/21/2006
                 FixChartDlg.dll                                 499,792              04/04/2006
                 FixComponentDll.dll                             589,931              03/28/2006
                 AlmSumMgr.DLL                                   102,478              03/17/2006
                 AlarmSummaryOCX.ocx                             385,112              03/17/2006
                 AlmSumMgrRes.dll                                20,480               03/17/2006
                 AlarmSummaryOCXRes.dll                          65,654               03/17/2006
                 PictureConverterDll.dll                         495,712              03/02/2006
Fix2DTextDll.dll                   290,959     03/02/2006
FIXERROR.DLL                       139,264     02/28/2006
Fix2DGroupDll.dll                  282,769     01/31/2006
Fix2DPenDll.dll                    430,239     01/27/2006
FIX.EXE                            208,946     12/28/2005
FIXSRV.exe                         65,589      12/28/2005
FixSchedulerDll.dll                520,326     12/28/2005
FixPictureDll.dll                  438,402     12/28/2005
VisiconXGrid.ocx                   114,779     12/25/2005
FixGlobalSysInfoDll.dll            143,491     11/15/2005
FCATABLE.DLL                       53,305      11/15/2005
LOGIN.EXE                          143,410     11/12/2005
ExpertGlobalRES.dll                86,016      11/11/2005
ALMODBC.exe                        118,847     11/01/2005
FactoryGlobalsRES.dll              61,440      09/30/2005
FixControlContainerDll.dll         331,939     08/18/2005
EnumerationsDLL.dll                28,672      08/15/2005
LDBA.dll                           299,061     08/15/2005
FactoryGlobals.fxg                 1,822,208   07/27/2005
CONMGR.exe                         69,684      07/25/2005
FixFileLinkDll.dll                 249,977     04/13/2005
WorkSpace.exe                      139,335     03/21/2005
FixUserPreferencesManagerRes.dll   20,480      03/16/2005
FixFormatDll.dll                   155,782     03/16/2005
FixFormat.tlb                      19,432      03/16/2005
FixUserPreferencesManagerDll.dll   135,290     03/16/2005
Scripting.dll                      225,356     03/16/2005
ValvesAnim.fds                     222,208     02/14/2005
FixBackgroundServerRes.dll         40,960      02/09/2005
FixPropDlg.dll                     364,622     02/09/2005
Tanks.fds                          269,824     02/09/2005
TanksAnim1.fds                     261,120     02/09/2005
TanksAnim2.fds                     271,872     02/09/2005
PipesAnim.fds                      194,560     02/09/2005
Pipes.fds                          220,672     02/09/2005
ExpertGlobal.fxg                   2,712,576   02/09/2005
Fix2DAxisDll.dll                   213,153     02/07/2005
Fix2DChartDll.dll                  360,611     02/07/2005
Fix2DLegendDll.dll                 262,309     02/07/2005
SearchReplace.dll                  143,444     02/04/2005
FixDataLinkDll.dll                 213,152     02/04/2005
iFixScreenSaver.scr                102,482     02/03/2005
TimerManager.dll                   57,426      01/11/2005
FixTimerDll.dll                    184,435     01/11/2005
Fix2DShapeDll.dll                  434,307     12/28/2004
FixAnimationDll.dll                139,388     12/28/2004
FixLinearDll.dll                   139,398     12/28/2004
Fix2DShape.tlb                     30,128      12/28/2004
FixComponentRes.dll                16,384      12/28/2004
SUMQLIB.DLL                        81,975      12/28/2004
SCU.exe                            618,547     12/28/2004
FixErrToHResult.dll                24,664      11/29/2004
WorkSpaceErrorsRes.dll             57,344      11/29/2004
FixShapeDll.dll                    110,707     11/08/2004
FixAppServiceDll.dll               102,525     09/27/2004
OpcEdaDll.dll                      143,436     09/21/2004
AlmODBCConfig.exe                              159,836              09/17/2004
FixControlContainerRes.dll                     32,768               09/10/2004
QUE2LIB.DLL                                    61,494               08/16/2004
FixUserPreferencesDll.dll                      225,380              07/21/2004
FixPropDlgRes.dll                              69,632               07/20/2004
launch.exe                                     102,465              07/17/2004
OODBDll.dll                                    225,360              07/17/2004
FixDataSystems.ocx                             114,797              07/02/2004
OPC20iFIX.exe                                  290,887              07/02/2004
WorkSpaceRes.dll                               135,168              07/02/2004
FixUserPreferencesResDll.dll                   49,288               06/10/2004
NLSAPI.DLL                                     41,014               04/12/2004
CrossReference.exe                             610,385              03/31/2004
ExpressionEditor.ocx                           258,138              03/31/2004
SecuritySynchronizerRes.dll                    32,768               02/19/2004
SEC_AF.DLL                                     16,384               02/19/2004
FixKeyMacroDll.dll                             65,641               02/19/2004
FixKeyMacroHandlerDll.dll                      77,943               02/19/2004
XDBA.dll                                       53,301               02/13/2004
ExpertGlobals2.fxg                             1,610,752            02/04/2004
FixVariableDll.dll                             131,193              01/30/2004
FixDynamoSetServer.dll                         159,875              01/16/2004
FixGlobalsServer.dll                           159,871              01/16/2004
FixPictureServer.dll                           159,871              01/16/2004
FixSchedulerServer.dll                         159,875              01/16/2004
FixToolbarServer.dll                           159,871              01/16/2004
FixToolbarDll.dll                              348,290              01/16/2004
SumqUpdate.exe                                 24,645               12/10/2003
FD_BDW.dll                                     28,672               09/17/2003
launchres.dll                                  49,152               09/15/2003

* Tag group resolution does not work properly if using the DefaultRefreshRate entry in
the Workspace.ini file and resolving tags before switching to Run mode. (1-
123523131)

* Bitmap Pushbutton stays stuck down, when pushbutton is invisible and user clicks
on area where pushbutton exists. (1-162154461)

* FixBackgroundServer events logged in the NT Event Viewer are not mapping with
descriptions.(1-144598020)

* Data in a picture never updates.(1-144898371)

* If Fire DataChange Event is disabled, then global user variable never triggers (1-
155223934)

* In the Chart Group File dialog, the file tree doesn't support Kanji Characters. (1-
112641852)

* Changing the DataSource for the last existing pen in a chart group file using the
Chart Group Wizard causes the values for color and limits to be reset. (1-111307898)

* Color animations using shared threshold table don't work properly if the same
threshold table is used by different pictures and these pictures are all opened in run
mode. (1-147175602)
* In the Chart Group File dialog, the file tree doesn't support Kanji Characters. (1-
112641852)

* It was not possible to use a "_" in a Windows User Name when running
SecuritySynchronizer (1-161443891)

* SQT blocks get stuck in the state of waiting for confirmation once their confirmations
get lost or never happen. (1-97202545A)

* VisiconX data control requires user with local administrative rights to connect to
OLE DB database. (1-110895991)

* Can't set the span interval to be 0 at chart configuration. (1-118948231)

* Workspace OPC client does not display OPC server's error string correctly (1-
126022821)

* Complex expressions fail after installation of sim 1-95976911 on Japanese iFix (1-
116459481)

* Log file and Alarm ODBC database don't capture each unsuccessful login attempt
(1-150615677)

* TX Block's comm. alarm doesn't show up on the AlarmSummary. (1-118034431)

* Alarm Summary OCX doesn't allow user to filter by the ACK column. (1-103547011)

* Picture Converter does not convert command comments correctly. (1-105643029)

* Cannot backspace when adding characters to a datalink. (1-115227146)

* Slow NT authentication for iFIX domain user (1-95990941C)

* Accelerator for Pushbutton doesn't work when Pushbutton is grouped (1-
116290921)

* Pictureconverter leaves unwanted '&' character in button! (1-116895871)

* Datalinks converted from FIX32 will highlight even though they were not
highlightable in the FIX32 picture.(1-127653268)

* Chart does not update correctly when changing tag group file that references t_data
(1-108273211)

* Automation error occurs when the DBDisconnect method is used in the
ExecuteComplete event of the VXDATA control. (1-119581251)

* iFix can't shut down ALMODBC and WSQLODC if they connect to a Sybase 9.xx
database on French OS. (1-105652516)

* Zooming a chart causes value ranges displayed on the Y axis of the chart to go
beyond its pens' EGU limits.(1-93670101)

* Encounter error when trying to modify schedule that has been set to run in
background (1-100502591)
* Unable to enter the Slash(/) from numeric pad in a Datalink. (1-112641841)*
Datalink doesn't support supressing character entry (1-116023901)

* Commandbutton no longer highlights in run mode after undoing a delete in
Configuration mode (1-115514116)

* Autoresize property of VisiconXData control doesn't resize columns after fetching
data.(1-113180591)

* Workspace intermittently disappears\access violation when running on RDP clients
(1-36959520)

* Advanced animation with TagGroup expressions containing complex expressions
no longer worked after installation of sim (1-100954501)

* Logging out of windows causes Fix service to goto stopping (1-100137961)

* ALT-TAB permissions not restored properly when using stacked logged in users (1-
109910701)

* "User Defined Fields" work differently for Alarms vs Events (1-106088924)

* Blinking property of an animated object using Dynamos is not working properly. (1-
99874598)

* Fonts stop changing horizontally in proportion to vertical changes if you change the
resolution of the screen while configuring a chart. (1-99237697)

* CommandButton script isn't recorded on basic animation dialog (1-106169060)

* Get error message "Expressions containing Historical items is not allowed" when
adding a pen that references to a iHistorian tag to a chart group file, if the pen name
matchs the pattern of "*.*.*.*.*". (1-71329801)

* Get error message "Secure Containment Detected Bad Control ..." and Workspace
crash while configuring a VisiconX data control to use Microsoft OLE DB Provider for
SQL Server as data provider, if more than 255 SQL servers are available in the
network.(1-99995157)

* Application crash when writing to A_ENAB field using EDA (1104354604)

* Alarm Acknowledge messages are being sent to the AA/DA block alarm areas
instead of the alarm areas for operator messages. (1-101856381)

* OnDataChange Event Does not Fire first time value changes (197333581)

* AcknowledgeAnAlarm can't acknowledge an alarm using a tag group symbol.(1-
95001621)

* Double byte dash "-" is not recognized for a object name in iFIX 3.5 Japanese. (1-
95976911)

* The GetFullName method of the ESignature object doesn't work if the Windows
user is a local user and the method is used to get a domain user's full name.(1-
52405328)
* MouseUp and MouseUpOffObject scripts do not work properly. (1-91893091)

* Find operation in workspace always sets dirty flag (1-101005761)

* AlmODBC crashes with STK Userfield and STK alm extension field being truncated
(142562201)

* When selecting text in a datalink that has "Leading Spaces" enabled, the text
highlight strips of the leading spaces (1-37828101)

* Workspace application crash when closing a picture that was created on a machine
with FIXDesktop installed and run on a machine without FIXDesktop installed. (1-
94231958)

* The Workspace application object does not properly accept negative values for the
TOP and LEFT properties. (1-90865926)

* Alarming-suspended/resumed messages are being sent to the AA/DA block alarm
areas instead of the alarm areas for operator messages. (1-91722901)

* Can't type in a space in editing mode of the standard text tool after installing
iFIX35_281537 or a later workspace SIM and having selected the Remove Leading
and Trailing Spaces option for text in the User Preferences.(1-83444001)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* Workspace crashes when switching between pictures using ReplacePicture
subroutine, if picture caching is enabled and the new picture names passed in
ReplacePicture are"xxxxx.grf" and "xxxxx.grf "(i.e. file names with trailing whitespace
characters).                                (288907)

* Read-write access to the security path is needed in order to use the security
configurator. (1-83519101)

* After installing iFIX35_294859, when Workspace is started, it is not restored at the
size that it was last closed. (1-85376901)

* Find function in VBE of Workspace does not handle inputting double byte characters
correctly. (1-79830201)

* Precision adjustment for a float-value datalink causes the value sometimes being
displayed with a different rounding from the Curr Value field in the Database
Manager. (1-43322301)

* The Timer Cursor shows no data for the last sample using SetPenDataArray
method. (1-79315501)

* FIXbackgroundServer Event ID 103, 107, 108, 111 messages appear erroneously in
the Event log (266950)

* Custom color palettes do not work using tank, valve and pipe dynamo's. (272910)

* Ramp Expert doesn't set the value to the low/high limit, when the new value
exceedes the limit.(270674)
* Some automation subroutines (AcknowledgeAnAlarm, RampValue, SetManual,
SetAuto, ToggleManual) change the values of parameters passed to them.(273349)

* The WriteValue VBA method sent an incorrectly formatted operator message if the
data source had a "%" in it.             (264630)

* Added Interval Field to Chart Group Wizard (274023)

* Chart group methods are not accessible in the background task.(272466)

* The Visibility Expert adds lookup levels in the descending order of input values
when configuring, which causes visibility animations to be converted incorrectly as the
Web Converter is expecting all lookup levels in the ascending order of input
values.(276784)

* A visibility animation created with a range, will not be edited correctly with the
visibility expert. (274718)

* FixBackgroundServer can't monitor running schedules, when run as a service on
WIN2000. (287836)

* Custom color palettes don't work in a pen's color. (262282)

* After opening and closing the VBA property window, a pen can't be deleted from a
chart properly. (268805)

* Using ModifyColumnLength VBA method to change the Chart's legend column
length, causes the legend text to grow and stretch. (271284)

* VisiconX Grid time field displays both system date and time. (279234)

* Can't open a .csv file by using VisiconX and OleDB provider for ODBC. (259313)

* Find and Replace messes up script.(273672)

* Changing the Object Name and Description on the Basic Animation Dialog does not
dirty the containing picture. (277534)

* Close and Save method of Document(s) allow document(s) to be saved during
mode switch, which sometimes causes the document(s) to be corrupted.(267849)

* FixBackground Server crashes while running iFIX as a service. (272155)

* "Invalid Handle" message is given when a "Delete All" is executed on the Alarm
Summary OCX.(260452)

* Datalink raw format resets when changing the datasource. (264403)

* The current alarm index would intermittedly get stuck on last alarm acknowledge
when scroll bars are enabled and ACK/PRIORITY descending. (272349)

* Alarm Summary's status bar prints black when using XP themes. (278401)

* iFixScreenSaver will hang if Login.exe is already opened (295038)
* AlmODBC crash when STK Userfield lengths exceed 79 characters and also STK
alarm extension field was being truncated. (142562201)

* TagGroup expressions containing complex expressions cause high message rate
(264443)

* Initial update of datalink values is slow when first opening a picture (1-19756822)

* Users get 'Invalid qualifier' error on data entry form after installing iFIX35_292319B
SIM.(1-42578390)

* Daily schedules running in the background skip firing every other day and double
firing at midnight when using New Zealand regional settings and time zone.(263814)

* Using the ToggleDigitalPoint expert and then running the Tag Group Editor (Get
Symbols From Picture), will not get all of the Tag Group Symbols that are eligible in
the picture.(274890)

* In datalink and some animation experts, if the data source is a single source, not an
expression, the tolerance gets reset to default.(276128)

* Remove Level automation method causes a memory leak. (273677)

* Dashed lines are printed as solid. (272979)

* Bitmap Pushbutton stays stuck down, when using a mouse down event that
launches a modal dialog. (278520)

* Tooltip would intermittedly flash on select PC's (266730)

* Can't get a property name correctly using the property dispatch ID, if the dispatch ID
is zero.(272807)

* When implementing the same VBA procedure in a picture and in a group (of objects
contained) as well, the VBA procedure was disabled at the picture level after
renaming the group. (275682)

* When using automation SelectObject method to select multiple objects, the color
property was only being set on the last selected object. (279699)

* MDI->EV->DA chain goes off-scan on iFIX re-start or database reload. (269246)

* More than 20 consecutive calls                 to   FixGetUserInfo     would    return
"smo_replace_profile: bad index". (273300)

* Tag description not being written to RDBM from AlarmODBC (268799)

* When using the sa_almmsg_cb and passing in the timestamp for the alarm, the
TimeIn on view nodes would not get updated if there was an existing alarm. (277780)

* AAD file cannot be accessed from VIEW node. (269866)

* Random "iFIX Detected a Serious Problem. Please Shut Down Restart iFIX" errors
(1-52135901)

* Text object has no space in between multiple lines of text. (1-34485756)
* Pressing the CTRL and then the TAB keys repeatedly causes the Workspace to
consume 100% CPU usage and makes the workspace unresponsive. (141913801)

* Some methods of Alarm Summary cause memory leak. (266745)

* Datalinks not retaining\displaying leading\trailing spaces when writing to TX Blocks
(1-37828101)

* After choosing a color from a custom color set, a foreground color animation
configured with the Foreground Color Expert cannot retain any new color selection
from the system default color set. (1-32449601)

* Deleting the Enabled animation of a push button from the system tree causes the
push button disabled.(1-34153301)

* Applying a chart group file that has an interval greater than 1 minute to an iFix chart
results in an error message "FIX2DPen invalid parameter".(1-32281101)

* Turning on data system prematurely causes some animations to work incorrectly.(1-
27285016)

* Unusual Behavior when pictures are saved outside the PIC directory and switched
to Run mode (1-32486401)

* Added a configuration setting to the .ini file to allow the user to specify the method
iFIX uses to open picture (290712)

* Animation data error doesn't work properly after installing iFIX35_SP1. (1-
32916701)

* The "Blink on New Alarm" checkbox will not stay checked the datasource is a tag
group and the animation is opened using the wizard. (132796801)

* The a F_CV value on RealTime Chart will cause the chart to blank and restart when
duration is changed (294512)

* The basic animation table settings are lost when using an undefined user global
variable as the data source in the basic animation dialogs.(1-21409801)

* Data Type mismatch error on automation method "AcknowledgeAllAlarms" when the
picture contains an object with an animation with a datasource equal to a constant.
(1-25827301)

* An event based schedule doesn't fire if it is using the System.CurrentTime property
in its data source and run in the background.(294413)

* Shape animation is no longer valid after a global Search and Replace (292319)

* Additional OPC Refresh configuration option. (119237501)

* Increased the maximum limit of the number of records to read from the User queue
before writing to the relational database for AlarmODBC. (280263)

* The Address fields in Device Control (DC) block does not accept syntax for OPC
Client driver. (290932)
* Digital Input block's alarm for the Close state, goes away on database reload.
(122925753)

* The MS Forms 2.0 Textbox control was not scrolling text properly. (292395)

* Workspace.exe in the SCU tasklist did not startup in the mode indicated by the
mode settings.(294859)

* Find & Replace failed with access exception (119739601)

* SetTimeCursorTime Method does not work properly.(292789)

* When using flexdata and thousands of alarms, the AlarmSummaryOCX was slow in
responding to subsequent Workspace user actions after the AlarmSummaryOCX was
initially opened in Workspace Run. (293322)

* An iHistorian Calculator Collector stop\re-start in the iHistorian Administrator would
cause the tag calculation to fail, "Object is not connected to the server". (290840)

* Down arrow key does not work if first datalink is invisible. (293910)

* Grouped Datalink sourced from a Global variable displays the stale data value if the
picture cache is enabled. (291986)

* SetTimeCursorTime Method does not work properly.(292789)

* Cannot de-select "Remove Trailing and Leading Spaces" for text objects in User
Preferences.(17410327)

* The animation table settings are lost when Using a undefined User Global Variable
in the Advanced Animation dialog. (288314)

* AlmODBC doesn't insert multiple records into SQL. (292290)

* Duplicate Logical Nodename error when using Launch with command line
parmeters /s /l /n (288317)

* License Error - iFIX has detected a serious problem. Please shutdown and restart
iFIX" generated when there was an invalid path or entry in the task list. (292781)

* Can not switch to run between iFIX and Sample System (NLS) (279886)

* NLS Translation issues (279280)

* AcknowledgeAllAlarms subroutine doesn't work for tag groups after migrating the
picture created with iFIX 2.6 to iFIX 3.5.(293393)

* Nudge settings not reflecting settings from the Fixuserpreferences.ini (294535)

* Added the ability to suppress RANGE, UNDER RANGE, and NODATA alarms.
(290732)

* Fix Data System OCX not working (294185)
* Spacing between lines in a multiple-line datalink changes when the last few lines are
blank.(292544)

* XYHistTest Method returns error (292899)

* Dead lock condition using OPCEDA asynchronously. (283840)

* OpciFix OPC server doesn't browse STK tags. (290388)

* Pictures are resized when the workspace opens after it was last closed in the
minimized or restored state.(292398)

* Duplication turns PushButton to FixOLEControl.(292381)

* Legend object get_LegendHeadingLine() is not returning Interval column name and
GetColumnInfo() method is returning empty column name.(294667)

* If the AlarmSummaryOCX is scrolled, and a new alarm comes in, the visible viewing
area is reset to the new end rows. (292610)

* SecuritySynchronizer crashes when logging oversized message.(292169)

* Added automation properties to support infoAgent 2.0 (293871)

* Clicking the Cancel button when configuring a schedule item causes some scripts
removed if the beginning of the names are the same for the timer and event schedule
items and the underscore character is used.(290611)

* Text object doesn't go to the next line when exceeding MaxCharactersPerLine.
(291537)

* Duplication of dynamo generates objects with same name.(290257)

* Applying a chart group file to a chart sometimes doesn't set EGU limits
correctly.(288261)

* VisiconX shows no data in the VisiconX Grid when opening a picture that has been
cached. (289291)

* Build Dynamo Wizard: Partial substitution for a dynamo property value does not
work properly if there is a decimal point in the animation data source.(290242)

* Animations don't work using constant numerical datasources. (288963)

* DBASRV inadvertently starts running when during iFIX startup. (291346)

* When using a long datatype datablock from an OPC server as the datasource in a
datalink, the value was different in the iFIX database and the datalink by 1. (292059)

* Alarms with the same Time In and Time Last are sometimes displayed in a different
order depending on the Sort Key. (289889)

* Script events created with the VBA FindReplaceInObject automation method do not
fire. (287883)
                 * Using NT security with iFix security, password expires error message occurs, even
                 though the user account is set to password never expires. (288005)

                 * Animated Text object caption doesn't work, if the datasource is static text. (286466)

                 * A chart does not display axes and grids after setting its current pen to be not
                 visible.(287462)

                 * Bad event message being sent to alarm typers, when user tries to set alarm values
                 of block higher then Egu Hi (290559)

                 * VBA Errors on install when installing to a machine with XP machine that has
                 sublanguages installed. (289295)

                 * Color animation's table resets when leaving expression editor, using the color
                 experts. (290442)

                 * Group click events do not fire when clicking on a control with no events. (285712)

                 * RetrieveTagGroupVariable method leaks memory.(287253)

                 * Acknowledged Alarms were being dropped from alarm synchronization (288698)

                 * The property name gets stripped from animation data source when reentering the
                 animation dialog, if the data source is an OLE object's default property.(287357)


iFIX35_1112501941 VDBA.DLL                                     41,014               11/28/2005
                 EDA.dll                                        86,067              10/24/2005
                 DDECLNT.EXE                                    188,471             10/24/2005
                 etr.gov                                        978                 08/15/2005
                 pa.gov                                         2,112               08/15/2005
                 tr.gov                                         978                 08/15/2005
                 hs.gov                                         978                 08/15/2005
                 ev.gov                                         978                 08/15/2005
                 dt.gov                                         870                 08/15/2005
                 DataBaseManager.exe                            663,635             07/27/2005
                 FixDB32_DO.dll                                 57,430              07/14/2005
                 FixDB32_AO.dll                                 65,622              07/14/2005
                 FixDB32_DI.dll                                 65,622              09/07/2004
                 FixDB32_DR.dll                                 53,334              09/07/2004
                 FixDB32_DA.dll                                 73,814              09/07/2004
                 FixDB32_BLRes.dll                              16,495              06/14/2004
                 FixDB32_DIRes.dll                              16,495              06/14/2004
                 FixDB32_DORes.dll                              16,495              06/14/2004
                 FixDB32_DARes.dll                              16,384              06/14/2004
                 FixDB32_DRRes.dll                              12,288              06/14/2004
                 DatabaseManagerRes.dll                         204,800             06/10/2004

                 * iFix Database Toolkit gives it 4293 string in alarm status when the alarm is COMM
                 (1-112501941)

                 * NETDDE cannot get remote Excel data in view on Win 2000 machine. (1-
                 115030351)

                 * Alarm Extension fields not being exported for some blocks (1-103966121)
                * Low EGU limit of 0.000001 causes error on import of database (187182953)

                * Event messaging no longer works on AO and DO blocks (186558030)

                * Database Manager will not start on machines with large registry files (1-86803501)

                * The Database Management spreadsheet displays incorrectly if a tag is imported that
                has double byte and regular characters that exceed the length limit of a field. (1-
                79830256)

                * PDB queries not working when there is no SORT order criteria (1-19734301)

                * Open/Close labels do not change case on Digital blocks (293103)

                * DB Manager EXPORT problem with Large Loadable Block (292393)

                * Database Manager doesn't allow lowercase for digital and boolean block
                labels.(277527)

                * Importing a CSV file into Database Manager that contains an equal sign(=) in the
                description field, without single quotes surrounding it, causes the block to import
                incorrectly without error.(269981)

                * The DA block's alarm mode switch's to NEVER from ACK, if no option is selected.
                (283296)

                * Database Manager only shows first 50 tags upon initial startup. (286760)

                * DatabaseManager crash while opening on a machine with Windows Server 2003,
                iFix 3.5, and iHistorian 2.0 installed. (283446)

                * Database Manager could not modify values in certain fields (Init Alarm, etc.)
                (286209)

                * Database Manager could not load queries if the extension was capitalized (i.e.
                *.QRY) (283131)


iFIX35_1174403491NAC.exe                                     53,299              08/14/2006
                 NA_ANALZ.dll                                53,308              06/03/2004

                * Alarms no longer synchronize properly on some redundant systems after installing
                iFIX35_288678. (1-174403491)

                * Login message initiated on Client is not sent to backup SCADA node, when client is
                looking at Backup SCADA as active node. (288678)


iFIX35_1103329301 VIEW.EXE                                   1,634,370           05/12/2006
                 WSProxy.EXE                                 106,560             09/01/2004
                 DRAW.EXE                                    2,404,418           08/11/2004
                 SUMQLIB_FIX32.DLL                           77,895              08/11/2004
                 HTD.EXE                                     1,060,928           08/11/2004
                 * Thousands separators are placed incorrectly for some negative values of FIX
                 Desktop datalinks. (1-103329301)

                 * When trying to open a .grf picture through WSProxy and the picture does not exist,
                 "Untitled1.grf" was not closed in WorkSpace on NLS product versions. (1-24827620)

                 * Reinitialize File Dates for iFix35_294534 for NLS. Also new SIM numbering scheme
                 for Desktop.

                 * Buffer overrun when using View.exe in Async mode. (294534)

                 * Alarms indicated with area "ALL" were not being displayed in the Alarm Summary in
                 View, when the AlarmSummaryOCX was set up to filter area "A" only. (292441)


iFIX35_199756141 NAM.exe                                        61,491                03/01/2006

                 * Alarms were being sent to clients even though NONE is set in Filteralm.ini when
                 using non-english versions (1-99756141)

                 * NAM is only dispersing about 10+ alarms per second to attached NAC's (289755)


iFIX35_1145497751 NETDIAG.EXE                                   196,671               03/02/2006
                 SKT.DLL                                        188,473               07/07/2005
                 TCPDUMP.EXE                                    61,501                07/07/2005
                 TCPTASK.EXE                                    167,997               07/07/2005

                 * "Out Of Sync In Use" Error In Netdiag. (1-145497751)

                 * Netdiag diagnostic tool fails to return valid information for the Socket Tables. (1-
                 114583744)

                 * SocketRec and Trace Tabs in Netdiag are not functional. (1-99199716)

                 * Terminal Server clients cannot connect to the SCADA node after installing
                 iFIX35_SP1. (295207A)

                 * iFIX event file filled up with assertion messages like "assertion failed (ulLocalIpAddr
                 != 0) && (ulLocalIpAddr != INADDR_NONE)" (1-99234191)

                 * An iClient cannot connect thru the RAS client connection if iFIX was already running
                 on the RAS server (SCADA) when the RAS connection was made and the user was
                 somehow able to disable all of the local IP addresses. (277339)

                 * An iClient cannot connect thru the RAS client connection if iFIX was already running
                 on the RAS server (SCADA) when the RAS connection was made. (269268)


iFIX35_155232834 OSXLIB.dll                                     49,206                04/13/2005

                 * When running the FixbackgroundServer in the background and writing a value to an
                 iFIX tag in the schedule and 8.3 format is disabled on the file system, user receives a
                 "Server automation" error. (1-55232834)
iFIX35_189034472 ElectronicSignature.dll                           184,427               05/04/2005

                   * Workspace leaks memory when using WriteValue method with security enabled.(1-
                   89034472)

                   * Workspace would crash if Esignature Dialog was open and script in background
                   closes picture (293354)

                   * E-Sig writes values with improper precision.(285358)


iFIX35_191893246 HDAODBC.dll                                       262,231               07/11/2005

                   * Memory handling error in Historical ODBC driver. (1-91893246)

                   * Fix Dynamics Historical Data - memory leak (268129)

                   * Problem with select Distinct in query when using Historical Data ODBC driver
                   (271969)


iFIX35_122718147 IHHDA.dll                                         81,984                12/01/2004
                 IHHDA3.dll                                        81,986                12/01/2004
                 FIXTOOLS.dll                                      69,693                10/27/2004
                 FixHdaDll.dll                                     73,804                05/17/2004

                   * Expression Builder iHistorian tag browse fails to display the tags associated with iFix
                   collectors but not having a node name as prefix or missing a "." in their tag names. (1-
                   22718147)

                   * Running iHistorian 3.0, when iFIX connects to the Server to get data, a Client
                   Access License (CAL) should not be used. (133962334)

                   * The filtered errors.ini file doesn't work correctly for iHistorian errors and enables
                   iHistorian API timeout to be configurable. (277122)


iFIX35_292646      IOCNTRL.exe                                     57,406                05/27/2004

                   * D parameter for IOCNTRL does not delay driver when used with /S parameter.
                   (292646)


iFIX35_121207706 ALMLIB.DLL.dll                                    86,070                12/28/2004
                 ALM_SYNC.EXE                                      45,112                12/28/2004

                   * Dates are missing from alarm messages sent from an iFix node to a Fix32 node .
                   (1-21207706)

                   * The primary SCADA (of a redundancy pair) logged in user could not write to the
                   A_NALM field even though the alarm was properly acknowledged and A_NALM
                   updated on the backup SCADA.(270021)

                   * eda_alm_get_user_que returned internal alarm acknowledgement messages (1-
                   18722801)
iFIX35_147803764 RCPUP.EXE                                   380,980             12/22/2004
                 RCPDOWN.EXE                                 389,174             12/22/2004
                 RCP.EXE                                     643,122             12/22/2004

                 * Recipe upload stops execution script when encountering a database error.(1-
                 47803764)

                 * Recipe executed using shell command inside VBA takes long time to execute
                 because the dialog stays on for about 5 seconds for each recipe. (282412)


iFIX35_122517301 BackupRestoreDll.dll                        270,426             09/10/2004
                 BackupRestoreRes.dll NLS:English            86,016              09/11/2003
                 BackupRestore.exe                           32,847              09/11/2003

                 * Problem with Backup And Restore wizard when restoring individual file (122517301)

                 * New command line options for backup/restore.


iFIX35_SP1       FIX.EXE                                     208,946             04/19/2004
                 WSACTASK.EXE                                53,299              04/19/2004
                 CONMGR.exe                                  86,068              04/19/2004
                 SACDLL.DLL                                  188,465             04/19/2004
                 FixFileLinkDll.dll                          249,977             04/16/2004
                 FixPropDlg.dll                              364,622             04/15/2004
                 FixPropDlgRes.dll NLS:English               69,632              04/15/2004
                 NLSAPI.DLL                                  41,014              04/12/2004
                 LDBA.dll                                    299,061             04/12/2004
                 ExpertGlobal.fxg                            2,700,800           04/12/2004
                 Fix2DShapeDll.dll                           434,307             04/12/2004
                 FixShapeDll.dll                             110,707             04/12/2004
                 Fix2DShape.tlb                              30,128              04/12/2004
                 FixDataLinkDll.dll                          213,152             04/12/2004
                 ElectronicSignature.dll                     184,427             04/12/2004
                 Fix2DPenDll.dll                             430,239             04/08/2004
                 FixBackgroundServer.exe                     45,138              04/02/2004
                 FixEventDll.dll                             155,780             04/02/2004
                 OpcDataSystem.dll                           450,690             04/02/2004
                 Fix2DChartDll.dll                           360,611             04/02/2004
                 IHHDA.dll                                   86,080              04/01/2004
                 ALMLIB.DLL                                  86,070              03/31/2004
                 SUMQLIB.DLL                                 81,975              03/31/2004
                 CrossReference.exe                          610,385             03/31/2004
                 PictureConverterDll.dll                     491,616             03/31/2004
                 SecuritySynchronizerDLL.dll                 356,423             03/31/2004
                 SECMGR.dll                                  61,494              03/31/2004
                 SECCFG.exe                                  401,462             03/31/2004
                 ExpressionEditor.ocx                        258,138             03/31/2004
                 NAM.exe                                     61,491              03/24/2004
                 SKT.DLL                                     188,473             03/22/2004
                 TCPTASK.EXE                                 167,997             03/22/2004
                 FixDB32_DA.dll                              73,814              03/12/2004
                 Fix2DTextDll.dll                            290,959             03/12/2004
                 FixUserPreferencesResDll.dll NLS:English    49,288              03/12/2004
FIXERROR.DLL                               139,264           03/03/2004
PlugandSolve.fxg                           840,192           03/02/2004
DataBaseManager.exe                        663,635           03/01/2004
Fix2DGroupDll.dll                          282,769           02/23/2004
SEC_AF.DLL                                 16,384            02/19/2004
SecuritySynchronizerRes.dll                32,768            02/19/2004
AlarmSummaryOCX.ocx                        385,112           02/19/2004
FixSchedulerDll.dll                        520,326           02/19/2004
FixKeyMacroDll.dll                         65,641            02/19/2004
FixKeyMacroHandlerDll.dll                  77,943            02/19/2004
XDBA.dll                                   53,301            02/13/2004
AlmODBCConfig.exe                          159,836           02/04/2004
ALMODBC.exe                                118,847           02/04/2004
ExpertGlobals2.fxg                         1,610,752         02/04/2004
FixVariableDll.dll                         131,193           01/30/2004
Fix2DLegendDll.dll                         262,309           01/28/2004
Fix2DAxisDll.dll                           213,153           01/28/2004
FixAnimationDll.dll                        139,388           01/21/2004
FixAppDll.dll                              209,007           01/19/2004
FixPictureDll.dll                          438,402           01/19/2004
VisiconXData.ocx                           413,787           01/16/2004
FixDynamoSetServer.dll                     159,875           01/16/2004
FixGlobalsServer.dll                       159,871           01/16/2004
FixPictureServer.dll                       159,871           01/16/2004
FixSchedulerServer.dll                     159,875           01/16/2004
FixToolbarServer.dll                       159,871           01/16/2004
FixToolbarDll.dll                          348,290           01/16/2004
SIMUninstall.dll                           217,159           12/31/2003
SumqUpdate.exe                             24,645            12/10/2003
LOGIN.EXE                                  143,410           11/21/2003
Scripting.dll                              225,356           11/20/2003
QUE2LIB.DLL                                61,494            11/17/2003
Fix2DBitmapDll.dll                         192,659           11/10/2003
FixComponentDll.dll                        589,931           11/10/2003
Fix2DBitmap.tlb NLS:English                30,196            11/10/2003
FixControlContainerDll.dll                 327,843           09/26/2003
launch.exe                                 102,465           09/24/2003
ExpertGlobalRES.dll NLS:English            86,016            09/23/2003
FD_BDW.dll NLS:English                     28,672            09/17/2003
AppValidator.exe                           241,741           09/17/2003
AppValidatorRes.dll NLS:English            77,824            09/17/2003
launchres.dll NLS:English                  49,152            09/15/2003
StartupProfileMgrRes.dll NLS:English       40,960            09/12/2003
StartupProfileMgr.exe                      94,295            09/12/2003
BackupRestoreRes.dll NLS:English           86,016            09/11/2003
BackupRestoreDll.dll                       270,426           09/11/2003
BackupRestore.exe                          32,847            09/11/2003
TimerManager.dll                           57,426            09/08/2003
FixDB32_DARes.dll NLS:English              16,384            07/14/2003

* Can not switch to run between iFIX and Sample System (NLS) (279886)

* NLS Translation issues (279280)

* New command line options for backup/restore.
* The DA block's alarm mode switch's to NEVER from ACK, if no option is selected.
(283296)

* Database Manager only shows first 50 tags upon initial startup. (286760)

* DatabaseManager crash while opening on a machine with Windows Server 2003,
iFix 3.5, and iHistorian 2.0 installed. (283446)

* Database Manager could not modify values in certain fields (Init Alarm, etc.)
(286209)

* Database Manager could not load queries if the extension was capitalized (i.e.
*.QRY) (283131)

* E-Sig writes values with improper precision.(285358)

* Added a configuration setting to the .ini file to allow the user to specify the method
iFIX uses to open picture (290712)

* Cannot translate main window title, Detail Report window (Row Count) , Auto Report
Naming (Browse dir window - "Select a directory")

* Double bytes strings are not displayed correctly in Application Validator main dialog,
Comparison Detail Report dialog, and Print Preview dialog. (278413)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* Increased range of Help context ID values to support values between -
2,147,483,648 and -2,147,483,647 (290334)

* Some EGU values entered as scientific notation would trigger an "out of range" error
(283944B)

* Reentering the Color Expert dialog and then moving the focus off the Data Source
field causes the Color Threshold Table to be reset to the default if the data source
contains multiple tags.(286911)

* Object becomes invisible in run mode when animation is deleted from iFix Browser
Tree (283047)

* Inserting a datalink and setting a historical datasource, then get an error, and setting
a realtime datasource results in a WorkSpace crash. (286063)

* Workspace crash in PTimeDll when pictures containing charts were repeatedly
opened and closed and modified the time range of the charts. (287787)

* CrossReference tool doesn't use regional settings when saving a file as CSV.
(284883)

* FixBackgroundServer can't monitor running schedules, when run as a service.
(287836)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)
* RAMP block does not ramp down when low EGU is greater then hi EGU (288563)

* Unable to log into iFix when connection to primary domain controller is lost (267542)

* Security Configuration Modifications to support Classic Desktop. (287808)

* SAC would not start up for 20 seconds, when using a large database. (257584)

* sq_remove() error thrown when trying to modify an AIS block thru the
DatabaseManager. (257625)

* SAC slows down after changing 200 AO blocks current mode from AUTO to MANL.
(269990)

* Added "iBatch - Start iWorkInstruction Editor" to iFIX application security areas
(280371)

* Added command line parameter to suppress ORNG (OverRange) Alarm.(273507)

* SecuritySynchronizer /R removes RECIPE User Account from iFix Security
(281002)

* SecurityArea in Picture Properties will not allow you to assign a area name of 22B, if
you have already assigned a security area 22A to a previous picture (264728)

* iFIX - Windows security it was not possible to use a "." or "'" in the NT user name
(275124)

* Incorrect License Error: iFix has detected a serious problem please shutdown iFix.
(278711)

* OnTrue/OnFalse scheduled events fire on startup even when "Fire DataChange
Event on Startup" is deselected. (285575)

* While trending with T_DATA pens on Terminal Server, a random crash occurs.
(279198)

* Charts created using iFix automation interface get abnormal Width and Height
properties.(285999)

* ETR data doesn't show up correctly when changing the pen's Duration in Run
mode.(285687)

* Picture Conversion causing datalink font size to increase drastically. (288371)

* Object animations and data links not updating because of faulty hardware HAL or
BIOS. (269172)

* Foreground color animation doesn't work until the data source changes its value if
the picture is opened in Run mode. (282461)

* Leading and Trailing spaces for Text objects are being deleted. (283218)

* Setting a pen's fixed start time with only time in a chart group file causes a type
mismatch error when you apply the chart group file.(284209)
* Deleting animations with the Basic Animations dialog will result in the animation
being deleted from the object, but it remains in the system tree. (280962)

* Incorrect datalink format when migrating from fix 32 with a symbol from a tag group
(277426)

* Converting pictures from Fix32 and then trying to rotate objects in iFix would not
work correctly. (272793)

* Picture Converter was not converting a text object's visibility animation exact match
tolerance correctly. (273899)

* Picture converter does not convert expressions for visibility correctly when regional
setting is something other than English (272789)

* Picture converter does not make first line of command script a comment when that
first line is a comment. (262514)

* Picture converter doesn't convert chart's, when the pen's datasource doesn't exist.
(263527)

* If an object is nested in two groups, the size or position animations of that object do
not initialize correctly.(278574)

* If a grouped object has been highlighted and selected and then its group or itself
becomes invisible, the highlight of the object remains on the screen despite the object
being invisible.(277979)

* "invalid argument was encountered..." error while adding pen using WIN2003, iFIX
3.5 and iHistorian. (287196)

* Converted Fix32 datalink with taggroup symbol displays drop down combo box as
alpha-numberic instead of numeric in iFix Datalink Custom Dialog (287172)

* AlarmSummaryOCX not sorting correctly when sort order is set using VB
automation properties (285530)

* Error in setting timer interval, when using Italy regional settings & time separator of
':' (286249)

* Using Key Macros causes memory leak.(283043)

* A global variable's value, when animated to a database tag, is set to zero when
communication is lost to that tag. (284423)* iFIX Workspace crash showing a
memory access violation in PTimedll.dll. when using a schedule and also picture
initialization code to modify Pens in a chart on the picture. (284593)

* In Build Dynamo Wizard, partial substitution for a dynamo property value does not
work properly if multiple occurences needed. (283379)

* AlarmODBC unable to handle schema name when defined in tablename when
writing to ORACLE (286150)

* Widened fields to support NLS strings (286795)

* Cannot edit a Chart Group File in run mode, using Chart Group Wizard. (285935)
* Opening or replacing a picture containing charts displaying ETR data or other real
time data is slow at iClient nodes. (281963)

* A historical trend chart shows a wrong value for the average over range if only part
of the chart is filled with data. (265305)

* 'High over range' value in charts is 0 if high is a negative number. (275225)

* Pen in Average Hist mode displays line after last known Good value in Chart
(273503)

* Corrected field truncations in Create Picture Wizard and Print Crystal report wizard
forms (285441)

* PictureConverter crash when using DDE links as source of Dynamic Coloring
Property (285824)

* Event firing was inconsistent when using picture caching. (278187)

* Opc datasources used in TagGroup datalinks do not re-connect when the OPC
Server is shutdown and re-started. (282205)

* ETR data doesn't display in charts when opening or replacing the containing
picture.(283572)

* VisiconX Data object would reset back to first record after a query. (284551)

* Workspace temporarily freezes when pictures directly access OPC data points
(285074)

* AlarmODBC.cfg become corrupt if tablename is changed to a shorter name
(284313)

* Security Issue (283386)

* Data Source gets changed from F_# to F_CV if tag does not exist prior to using
color expert (282956)

* Login.exe dialog closes when pressing ESC if opened by iFixScreenSaver (281132)

* When using the iFIX Screensaver, users are unable to change password if expired
(274065)

* F10 Key Macro does not work correctly (263027)

* Tolerance is not being saved using datalinks. (282037)

* Create Picture expert inserts incorrect sizes, using predefined configuration.
(282124)

* MouseUp events do not fire if the mouse button is released off the object. (281070)

* Picture Converter doesn't set MaxCharactersPerLine property to 80 for text objects
less than 80, also AutoSize is set to false. (279003)
                  * Picture converter corrupts Kanji characters, when converting small Push Buttons.
                  (278656)

                  * Table animation entries are not saved when using tag groups as the datasource on
                  a datalink caption animation. (279936)

                  * Fix.exe will hang on the shutdown waiting for third-party application which was
                  registered with iFix using FixRegisterConsole() helper function (277058)

                  * Cannot set Column widths to stay persistent for alarm summary in configure mode
                  (279311)

                  * Cannot translate Build Dynamo Wizard dialog (279274)

                  * Cannot translate "Use Pixel Coordinates" and "Use Percentage Coordinates"
                  checkboxes in "In Enter New Configuration Name" dialog (279273)

                  * Create Picture Wizard NLS: String ID in Tag property were missing in
                  btnDeleteConfig, pgStyles, pgSizes, btnSave control (278561)

                  * Continuous iFix Timers would occasionally fire 1 second early. (277455)

                  * Toolbar buttons are missing from the toolbar, during a mode switch. (276640)

                  * Double bytes strings are not displayed correctly in Server selection ComboBox and
                  Item browsing spread control. (NLS) (280803)

                  * AlmSum.exe was hogging 100% CPU for an indefinite period of time. (252294)

                  * Alarm Summary Sorting Problem when using LIN driver and there is no PDB and
                  WSACTASK being used (276687)

                  * Unable to remove user created alarm queue when started by background schedule
                  (276672)

                  * Alarm ODBC service did not log double bytes operator message correctly with
                  calling SendSignedOperatorMessage function when the message is over 82 bytes.
                  (282253 NLS)

                  * Double bytes strings are not displayed correctly in Startup Profile Mgr main dialog.
                  (278412)

                  * NAM is only dispersing about 10+ alarms per second to attached NAC's (289755)

                  * Enables iHistorian API timeout to be configurable (277122)

                  * Allows throttling of the frequency of alarm cycles for the thread that moves alarms
                  from the SAC queue to the Summary queue. (268948)

                  * An iClient cannot connect thru the RAS client connection if iFIX was already running
                  on the RAS server (SCADA) when the RAS connection was made. (269268)


iFIX 3.5 French

iFIX35_1123523131FixTagGroupDll.dll                              155,769             07/17/2006
Fix2DBitmapDll.dll                 192,659     06/28/2006
Fix2DBitmap.tlb                    30,196      06/28/2006
FixBackgroundServer.exe            45,138      06/23/2006
OpcDataSystem.dll                  450,690     06/20/2006
FixEventDll.dll                    155,780     06/07/2006
FixAppDll.dll                      209,007     06/07/2006
FixPageDll.dll                     352,369     06/07/2006
PlugandSolve.fxg                   826,880     05/23/2006
FixLookupDll.dll                   172,166     05/23/2006
FileTree.ocx                       57,344      05/12/2006
WSACTASK.EXE                       53,299      05/08/2006
SACDLL.DLL                         192,561     05/08/2006
SecuritySynchronizerDLL.dll        356,423     04/27/2006
SECCFG.exe                         397,366     04/27/2006
SECMGR.dll                         65,590      04/27/2006
VisiconXData.ocx                   413,787     04/21/2006
FixChartDlg.dll                    499,792     04/04/2006
FixComponentDll.dll                589,931     03/28/2006
AlmSumMgr.DLL                      102,478     03/17/2006
AlarmSummaryOCX.ocx                385,112     03/17/2006
AlmSumMgrRes.dll                   20,480      03/17/2006
AlarmSummaryOCXRes.dll             65,654      03/17/2006
PictureConverterDll.dll            495,712     03/02/2006
Fix2DTextDll.dll                   290,959     03/02/2006
FIXERROR.DLL                       139,264     02/28/2006
Fix2DGroupDll.dll                  282,769     01/31/2006
Fix2DPenDll.dll                    430,239     01/27/2006
FIX.EXE                            208,946     12/28/2005
FIXSRV.exe                         65,589      12/28/2005
FixSchedulerDll.dll                520,326     12/28/2005
FixPictureDll.dll                  438,402     12/28/2005
VisiconXGrid.ocx                   114,779     12/25/2005
FixGlobalSysInfoDll.dll            143,491     11/15/2005
FCATABLE.DLL                       53,305      11/15/2005
LOGIN.EXE                          143,410     11/12/2005
ExpertGlobalRES.dll                86,016      11/11/2005
ALMODBC.exe                        118,847     11/01/2005
FactoryGlobalsRES.dll              61,440      09/30/2005
FixControlContainerDll.dll         331,939     08/18/2005
EnumerationsDLL.dll                28,672      08/15/2005
LDBA.dll                           299,061     08/15/2005
FactoryGlobals.fxg                 1,822,208   07/27/2005
CONMGR.exe                         69,684      07/25/2005
FixFileLinkDll.dll                 249,977     04/13/2005
WorkSpace.exe                      139,335     03/21/2005
FixUserPreferencesManagerRes.dll   20,480      03/16/2005
FixFormatDll.dll                   155,782     03/16/2005
FixFormat.tlb                      19,432      03/16/2005
FixUserPreferencesManagerDll.dll   135,290     03/16/2005
Scripting.dll                      225,356     03/16/2005
ValvesAnim.fds                     222,208     02/14/2005
FixBackgroundServerRes.dll         40,960      02/09/2005
FixPropDlg.dll                     364,622     02/09/2005
Tanks.fds                          269,824     02/09/2005
TanksAnim1.fds                     261,120     02/09/2005
TanksAnim2.fds                     271,872     02/09/2005
PipesAnim.fds                                194,560             02/09/2005
Pipes.fds                                    220,672             02/09/2005
ExpertGlobal.fxg                             2,712,576           02/09/2005
Fix2DAxisDll.dll                             213,153             02/07/2005
Fix2DChartDll.dll                            360,611             02/07/2005
Fix2DLegendDll.dll                           262,309             02/07/2005
SearchReplace.dll                            143,444             02/04/2005
FixDataLinkDll.dll                           213,152             02/04/2005
iFixScreenSaver.scr                          102,482             02/03/2005
TimerManager.dll                             57,426              01/11/2005
FixTimerDll.dll                              184,435             01/11/2005
Fix2DShapeDll.dll                            434,307             12/28/2004
FixAnimationDll.dll                          139,388             12/28/2004
FixLinearDll.dll                             139,398             12/28/2004
Fix2DShape.tlb                               30,128              12/28/2004
FixComponentRes.dll                          16,384              12/28/2004
SUMQLIB.DLL                                  81,975              12/28/2004
SCU.exe                                      618,547             12/28/2004
FixErrToHResult.dll                          24,664              11/29/2004
WorkSpaceErrorsRes.dll                       57,344              11/29/2004
FixShapeDll.dll                              110,707             11/08/2004
FixAppServiceDll.dll                         102,525             09/27/2004
OpcEdaDll.dll                                143,436             09/21/2004
AlmODBCConfig.exe                            159,836             09/17/2004
FixControlContainerRes.dll                   32,768              09/10/2004
QUE2LIB.DLL                                  61,494              08/16/2004
FixUserPreferencesDll.dll                    225,380             07/21/2004
FixPropDlgRes.dll                            69,632              07/20/2004
launch.exe                                   102,465             07/17/2004
OODBDll.dll                                  225,360             07/17/2004
FixDataSystems.ocx                           114,797             07/02/2004
OPC20iFIX.exe                                290,887             07/02/2004
WorkSpaceRes.dll                             135,168             07/02/2004
FixUserPreferencesResDll.dll                 49,288              06/10/2004
NLSAPI.DLL                                   41,014              04/12/2004
CrossReference.exe                           610,385             03/31/2004
ExpressionEditor.ocx                         258,138             03/31/2004
SecuritySynchronizerRes.dll                  32,768              02/19/2004
SEC_AF.DLL                                   16,384              02/19/2004
FixKeyMacroDll.dll                           65,641              02/19/2004
FixKeyMacroHandlerDll.dll                    77,943              02/19/2004
XDBA.dll                                     53,301              02/13/2004
ExpertGlobals2.fxg                           1,610,752           02/04/2004
FixVariableDll.dll                           131,193             01/30/2004
FixDynamoSetServer.dll                       159,875             01/16/2004
FixGlobalsServer.dll                         159,871             01/16/2004
FixPictureServer.dll                         159,871             01/16/2004
FixSchedulerServer.dll                       159,875             01/16/2004
FixToolbarServer.dll                         159,871             01/16/2004
FixToolbarDll.dll                            348,290             01/16/2004
SumqUpdate.exe                               24,645              12/10/2003
FD_BDW.dll                                   28,672              09/17/2003
launchres.dll                                49,152              09/15/2003

* Tag group resolution does not work properly if using the DefaultRefreshRate entry in
the Workspace.ini file and resolving tags before switching to Run mode. (1-
123523131)

* Bitmap Pushbutton stays stuck down, when pushbutton is invisible and user clicks
on area where pushbutton exists. (1-162154461)

* FixBackgroundServer events logged in the NT Event Viewer are not mapping with
descriptions.(1-144598020)

* Data in a picture never updates.(1-144898371)

* If Fire DataChange Event is disabled, then global user variable never triggers (1-
155223934)

* In the Chart Group File dialog, the file tree doesn't support Kanji Characters. (1-
112641852)

* Changing the DataSource for the last existing pen in a chart group file using the
Chart Group Wizard causes the values for color and limits to be reset. (1-111307898)

* Color animations using shared threshold table don't work properly if the same
threshold table is used by different pictures and these pictures are all opened in run
mode. (1-147175602)

* In the Chart Group File dialog, the file tree doesn't support Kanji Characters. (1-
112641852)

* It was not possible to use a "_" in a Windows User Name when running
SecuritySynchronizer (1-161443891)

* SQT blocks get stuck in the state of waiting for confirmation once their confirmations
get lost or never happen. (1-97202545A)

* VisiconX data control requires user with local administrative rights to connect to
OLE DB database. (1-110895991)

* Can't set the span interval to be 0 at chart configuration. (1-118948231)

* Workspace OPC client does not display OPC server's error string correctly (1-
126022821)

* Complex expressions fail after installation of sim 1-95976911 on Japanese iFix (1-
116459481)

* Log file and Alarm ODBC database don't capture each unsuccessful login attempt
(1-150615677)

* TX Block's comm. alarm doesn't show up on the AlarmSummary. (1-118034431)

* Alarm Summary OCX doesn't allow user to filter by the ACK column. (1-103547011)

* Picture Converter does not convert command comments correctly. (1-105643029)

* Cannot backspace when adding characters to a datalink. (1-115227146)

* Slow NT authentication for iFIX domain user (1-95990941C)
* Accelerator for Pushbutton doesn't work when Pushbutton is grouped (1-
116290921)

* Pictureconverter leaves unwanted '&' character in button! (1-116895871)

* Datalinks converted from FIX32 will highlight even though they were not
highlightable in the FIX32 picture.(1-127653268)

* Chart does not update correctly when changing tag group file that references t_data
(1-108273211)

* Automation error occurs when the DBDisconnect method is used in the
ExecuteComplete event of the VXDATA control. (1-119581251)

* iFix can't shut down ALMODBC and WSQLODC if they connect to a Sybase 9.xx
database on French OS. (1-105652516)

* Zooming a chart causes value ranges displayed on the Y axis of the chart to go
beyond its pens' EGU limits.(1-93670101)

* Encounter error when trying to modify schedule that has been set to run in
background (1-100502591)

* Unable to enter the Slash(/) from numeric pad in a Datalink. (1-112641841)*
Datalink doesn't support supressing character entry (1-116023901)

* Commandbutton no longer highlights in run mode after undoing a delete in
Configuration mode (1-115514116)

* Autoresize property of VisiconXData control doesn't resize columns after fetching
data.(1-113180591)

* Workspace intermittently disappears\access violation when running on RDP clients
(1-36959520)

* Advanced animation with TagGroup expressions containing complex expressions
no longer worked after installation of sim (1-100954501)

* Logging out of windows causes Fix service to goto stopping (1-100137961)

* ALT-TAB permissions not restored properly when using stacked logged in users (1-
109910701)

* "User Defined Fields" work differently for Alarms vs Events (1-106088924)

* Blinking property of an animated object using Dynamos is not working properly. (1-
99874598)

* Fonts stop changing horizontally in proportion to vertical changes if you change the
resolution of the screen while configuring a chart. (1-99237697)

* CommandButton script isn't recorded on basic animation dialog (1-106169060)

* Get error message "Expressions containing Historical items is not allowed" when
adding a pen that references to a iHistorian tag to a chart group file, if the pen name
matchs the pattern of "*.*.*.*.*". (1-71329801)
* Get error message "Secure Containment Detected Bad Control ..." and Workspace
crash while configuring a VisiconX data control to use Microsoft OLE DB Provider for
SQL Server as data provider, if more than 255 SQL servers are available in the
network.(1-99995157)

* Application crash when writing to A_ENAB field using EDA (1104354604)

* Alarm Acknowledge messages are being sent to the AA/DA block alarm areas
instead of the alarm areas for operator messages. (1-101856381)

* OnDataChange Event Does not Fire first time value changes (197333581)

* AcknowledgeAnAlarm can't acknowledge an alarm using a tag group symbol.(1-
95001621)

* Double byte dash "-" is not recognized for a object name in iFIX 3.5 Japanese. (1-
95976911)

* The GetFullName method of the ESignature object doesn't work if the Windows
user is a local user and the method is used to get a domain user's full name.(1-
52405328)

* MouseUp and MouseUpOffObject scripts do not work properly. (1-91893091)

* Find operation in workspace always sets dirty flag (1-101005761)

* AlmODBC crashes with STK Userfield and STK alm extension field being truncated
(142562201)

* When selecting text in a datalink that has "Leading Spaces" enabled, the text
highlight strips of the leading spaces (1-37828101)

* Workspace application crash when closing a picture that was created on a machine
with FIXDesktop installed and run on a machine without FIXDesktop installed. (1-
94231958)

* The Workspace application object does not properly accept negative values for the
TOP and LEFT properties. (1-90865926)

* Alarming-suspended/resumed messages are being sent to the AA/DA block alarm
areas instead of the alarm areas for operator messages. (1-91722901)



* Can't type in a space in editing mode of the standard text tool after installing
iFIX35_281537 or a later workspace SIM and having selected the Remove Leading
and Trailing Spaces option for text in the User Preferences.(1-83444001)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* Workspace crashes when switching between pictures using ReplacePicture
subroutine, if picture caching is enabled and the new picture names passed in
ReplacePicture are"xxxxx.grf" and "xxxxx.grf "(i.e. file names with trailing whitespace
characters).                                (288907)
* Read-write access to the security path is needed in order to use the security
configurator. (1-83519101)

* After installing iFIX35_294859, when Workspace is started, it is not restored at the
size that it was last closed. (1-85376901)

* Find function in VBE of Workspace does not handle inputting double byte characters
correctly. (1-79830201)

* Precision adjustment for a float-value datalink causes the value sometimes being
displayed with a different rounding from the Curr Value field in the Database
Manager. (1-43322301)

* The Timer Cursor shows no data for the last sample using SetPenDataArray
method. (1-79315501)

* FIXbackgroundServer Event ID 103, 107, 108, 111 messages appear erroneously in
the Event log (266950)

* Custom color palettes do not work using tank, valve and pipe dynamo's. (272910)

* Ramp Expert doesn't set the value to the low/high limit, when the new value
exceedes the limit.(270674)

* Some automation subroutines (AcknowledgeAnAlarm, RampValue, SetManual,
SetAuto, ToggleManual) change the values of parameters passed to them.(273349)

* The WriteValue VBA method sent an incorrectly formatted operator message if the
data source had a "%" in it.             (264630)

* Added Interval Field to Chart Group Wizard (274023)

* Chart group methods are not accessible in the background task.(272466)

* The Visibility Expert adds lookup levels in the descending order of input values
when configuring, which causes visibility animations to be converted incorrectly as the
Web Converter is expecting all lookup levels in the ascending order of input
values.(276784)

* A visibility animation created with a range, will not be edited correctly with the
visibility expert. (274718)

* FixBackgroundServer can't monitor running schedules, when run as a service on
WIN2000. (287836)

* Custom color palettes don't work in a pen's color. (262282)

* After opening and closing the VBA property window, a pen can't be deleted from a
chart properly. (268805)

* Using ModifyColumnLength VBA method to change the Chart's legend column
length, causes the legend text to grow and stretch. (271284)

* VisiconX Grid time field displays both system date and time. (279234)
* Can't open a .csv file by using VisiconX and OleDB provider for ODBC. (259313)

* Find and Replace messes up script.(273672)

* Changing the Object Name and Description on the Basic Animation Dialog does not
dirty the containing picture. (277534)

* Close and Save method of Document(s) allow document(s) to be saved during
mode switch, which sometimes causes the document(s) to be corrupted.(267849)

* FixBackground Server crashes while running iFIX as a service. (272155)

* "Invalid Handle" message is given when a "Delete All" is executed on the Alarm
Summary OCX.(260452)

* Datalink raw format resets when changing the datasource. (264403)

* The current alarm index would intermittedly get stuck on last alarm acknowledge
when scroll bars are enabled and ACK/PRIORITY descending. (272349)

* Alarm Summary's status bar prints black when using XP themes. (278401)

* iFixScreenSaver will hang if Login.exe is already opened (295038)

* AlmODBC crash when STK Userfield lengths exceed 79 characters and also STK
alarm extension field was being truncated. (142562201)

* TagGroup expressions containing complex expressions cause high message rate
(264443)

* Initial update of datalink values is slow when first opening a picture (1-19756822)

* Users get 'Invalid qualifier' error on data entry form after installing iFIX35_292319B
SIM.(1-42578390)

* Daily schedules running in the background skip firing every other day and double
firing at midnight when using New Zealand regional settings and time zone.(263814)

* Using the ToggleDigitalPoint expert and then running the Tag Group Editor (Get
Symbols From Picture), will not get all of the Tag Group Symbols that are eligible in
the picture.(274890)

* In datalink and some animation experts, if the data source is a single source, not an
expression, the tolerance gets reset to default.(276128)

* Remove Level automation method causes a memory leak. (273677)

* Dashed lines are printed as solid. (272979)

* Bitmap Pushbutton stays stuck down, when using a mouse down event that
launches a modal dialog. (278520)

* Tooltip would intermittedly flash on select PC's (266730)
* Can't get a property name correctly using the property dispatch ID, if the dispatch ID
is zero.(272807)

* When implementing the same VBA procedure in a picture and in a group (of objects
contained) as well, the VBA procedure was disabled at the picture level after
renaming the group. (275682)

* When using automation SelectObject method to select multiple objects, the color
property was only being set on the last selected object. (279699)

* MDI->EV->DA chain goes off-scan on iFIX re-start or database reload. (269246)

* More than 20 consecutive calls                 to   FixGetUserInfo     would    return
"smo_replace_profile: bad index". (273300)

* Tag description not being written to RDBM from AlarmODBC (268799)

* When using the sa_almmsg_cb and passing in the timestamp for the alarm, the
TimeIn on view nodes would not get updated if there was an existing alarm. (277780)

* AAD file cannot be accessed from VIEW node. (269866)

* Random "iFIX Detected a Serious Problem. Please Shut Down Restart iFIX" errors
(1-52135901)

* Text object has no space in between multiple lines of text. (1-34485756)

* Pressing the CTRL and then the TAB keys repeatedly causes the Workspace to
consume 100% CPU usage and makes the workspace unresponsive. (141913801)

* Some methods of Alarm Summary cause memory leak. (266745)

* Datalinks not retaining\displaying leading\trailing spaces when writing to TX Blocks
(1-37828101)

* After choosing a color from a custom color set, a foreground color animation
configured with the Foreground Color Expert cannot retain any new color selection
from the system default color set. (1-32449601)

* Deleting the Enabled animation of a push button from the system tree causes the
push button disabled.(1-34153301)

* Applying a chart group file that has an interval greater than 1 minute to an iFix chart
results in an error message "FIX2DPen invalid parameter".(1-32281101)

* Turning on data system prematurely causes some animations to work incorrectly.(1-
27285016)

* Unusual Behavior when pictures are saved outside the PIC directory and switched
to Run mode (1-32486401)

* Added a configuration setting to the .ini file to allow the user to specify the method
iFIX uses to open picture (290712)
* Animation data error doesn't work properly after installing iFIX35_SP1. (1-
32916701)

* The "Blink on New Alarm" checkbox will not stay checked the datasource is a tag
group and the animation is opened using the wizard. (132796801)

* The a F_CV value on RealTime Chart will cause the chart to blank and restart when
duration is changed (294512)

* The basic animation table settings are lost when using an undefined user global
variable as the data source in the basic animation dialogs.(1-21409801)

* Data Type mismatch error on automation method "AcknowledgeAllAlarms" when the
picture contains an object with an animation with a datasource equal to a constant.
(1-25827301)

* An event based schedule doesn't fire if it is using the System.CurrentTime property
in its data source and run in the background.(294413)

* Shape animation is no longer valid after a global Search and Replace (292319)

* Additional OPC Refresh configuration option. (119237501)

* Increased the maximum limit of the number of records to read from the User queue
before writing to the relational database for AlarmODBC. (280263)

* The Address fields in Device Control (DC) block does not accept syntax for OPC
Client driver. (290932)

* Digital Input block's alarm for the Close state, goes away on database reload.
(122925753)

* The MS Forms 2.0 Textbox control was not scrolling text properly. (292395)

* Workspace.exe in the SCU tasklist did not startup in the mode indicated by the
mode settings.(294859)

* Find & Replace failed with access exception (119739601)

* SetTimeCursorTime Method does not work properly.(292789)

* When using flexdata and thousands of alarms, the AlarmSummaryOCX was slow in
responding to subsequent Workspace user actions after the AlarmSummaryOCX was
initially opened in Workspace Run. (293322)

* An iHistorian Calculator Collector stop\re-start in the iHistorian Administrator would
cause the tag calculation to fail, "Object is not connected to the server". (290840)

* Down arrow key does not work if first datalink is invisible. (293910)

* Grouped Datalink sourced from a Global variable displays the stale data value if the
picture cache is enabled. (291986)

* SetTimeCursorTime Method does not work properly.(292789)
* Cannot de-select "Remove Trailing and Leading Spaces" for text objects in User
Preferences.(17410327)

* The animation table settings are lost when Using a undefined User Global Variable
in the Advanced Animation dialog. (288314)

* AlmODBC doesn't insert multiple records into SQL. (292290)

* Duplicate Logical Nodename error when using Launch with command line
parmeters /s /l /n (288317)

* License Error - iFIX has detected a serious problem. Please shutdown and restart
iFIX" generated when there was an invalid path or entry in the task list. (292781)

* Can not switch to run between iFIX and Sample System (NLS) (279886)

* NLS Translation issues (279280)

* AcknowledgeAllAlarms subroutine doesn't work for tag groups after migrating the
picture created with iFIX 2.6 to iFIX 3.5.(293393)

* Nudge settings not reflecting settings from the Fixuserpreferences.ini (294535)

* Added the ability to suppress RANGE, UNDER RANGE, and NODATA alarms.
(290732)

* Fix Data System OCX not working (294185)

* Spacing between lines in a multiple-line datalink changes when the last few lines are
blank.(292544)

* XYHistTest Method returns error (292899)

* Dead lock condition using OPCEDA asynchronously. (283840)

* OpciFix OPC server doesn't browse STK tags. (290388)

* Pictures are resized when the workspace opens after it was last closed in the
minimized or restored state.(292398)

* Duplication turns PushButton to FixOLEControl.(292381)

* Legend object get_LegendHeadingLine() is not returning Interval column name and
GetColumnInfo() method is returning empty column name.(294667)

* If the AlarmSummaryOCX is scrolled, and a new alarm comes in, the visible viewing
area is reset to the new end rows. (292610)

* SecuritySynchronizer crashes when logging oversized message.(292169)

* Added automation properties to support infoAgent 2.0 (293871)

* Clicking the Cancel button when configuring a schedule item causes some scripts
removed if the beginning of the names are the same for the timer and event schedule
items and the underscore character is used.(290611)
                * Text object doesn't go to the next line when exceeding MaxCharactersPerLine.
                (291537)

                * Duplication of dynamo generates objects with same name.(290257)

                * Applying a chart group file to a chart sometimes doesn't set EGU limits
                correctly.(288261)

                * VisiconX shows no data in the VisiconX Grid when opening a picture that has been
                cached. (289291)

                * Build Dynamo Wizard: Partial substitution for a dynamo property value does not
                work properly if there is a decimal point in the animation data source.(290242)

                * Animations don't work using constant numerical datasources. (288963)

                * DBASRV inadvertently starts running when during iFIX startup. (291346)

                * When using a long datatype datablock from an OPC server as the datasource in a
                datalink, the value was different in the iFIX database and the datalink by 1. (292059)

                * Alarms with the same Time In and Time Last are sometimes displayed in a different
                order depending on the Sort Key. (289889)

                * Script events created with the VBA FindReplaceInObject automation method do not
                fire. (287883)

                * Using NT security with iFix security, password expires error message occurs, even
                though the user account is set to password never expires. (288005)

                * Animated Text object caption doesn't work, if the datasource is static text. (286466)

                * A chart does not display axes and grids after setting its current pen to be not
                visible.(287462)

                * Bad event message being sent to alarm typers, when user tries to set alarm values
                of block higher then Egu Hi (290559)

                * VBA Errors on install when installing to a machine with XP machine that has
                sublanguages installed. (289295)

                * Color animation's table resets when leaving expression editor, using the color
                experts. (290442)

                * Group click events do not fire when clicking on a control with no events. (285712)

                * RetrieveTagGroupVariable method leaks memory.(287253)

                * Acknowledged Alarms were being dropped from alarm synchronization (288698)

                * The property name gets stripped from animation data source when reentering the
                animation dialog, if the data source is an OLE object's default property.(287357)


iFIX35_1112501941 VDBA.DLL                                    41,014               11/28/2005
                 EDA.dll                                       86,067              10/24/2005
DDECLNT.EXE                                  188,471             10/24/2005
etr.gov                                      978                 08/15/2005
pa.gov                                       2,112               08/15/2005
tr.gov                                       978                 08/15/2005
hs.gov                                       978                 08/15/2005
ev.gov                                       978                 08/15/2005
dt.gov                                       870                 08/15/2005
DataBaseManager.exe                          663,635             07/27/2005
FixDB32_DO.dll                               57,430              07/14/2005
FixDB32_AO.dll                               65,622              07/14/2005
FixDB32_DI.dll                               65,622              09/07/2004
FixDB32_DR.dll                               53,334              09/07/2004
FixDB32_DA.dll                               73,814              09/07/2004
FixDB32_BLRes.dll                            16,495              06/14/2004
FixDB32_DIRes.dll                            16,495              06/14/2004
FixDB32_DORes.dll                            16,495              06/14/2004
FixDB32_DARes.dll                            16,384              06/14/2004
FixDB32_DRRes.dll                            12,288              06/14/2004
DatabaseManagerRes.dll                       204,800             06/10/2004

* iFix Database Toolkit gives it 4293 string in alarm status when the alarm is COMM
(1-112501941)

* NETDDE cannot get remote Excel data in view on Win 2000 machine. (1-
115030351)

* Alarm Extension fields not being exported for some blocks (1-103966121)

* Low EGU limit of 0.000001 causes error on import of database (187182953)

* Event messaging no longer works on AO and DO blocks (186558030)

* Database Manager will not start on machines with large registry files (1-86803501)

* The Database Management spreadsheet displays incorrectly if a tag is imported that
has double byte and regular characters that exceed the length limit of a field. (1-
79830256)

* PDB queries not working when there is no SORT order criteria (1-19734301)

* Open/Close labels do not change case on Digital blocks (293103)

* DB Manager EXPORT problem with Large Loadable Block (292393)

* Database Manager doesn't allow lowercase for digital and boolean block
labels.(277527)

* Importing a CSV file into Database Manager that contains an equal sign(=) in the
description field, without single quotes surrounding it, causes the block to import
incorrectly without error.(269981)

* The DA block's alarm mode switch's to NEVER from ACK, if no option is selected.
(283296)

* Database Manager only shows first 50 tags upon initial startup. (286760)
                * DatabaseManager crash while opening on a machine with Windows Server 2003,
                iFix 3.5, and iHistorian 2.0 installed. (283446)

                * Database Manager could not modify values in certain fields (Init Alarm, etc.)
                (286209)

                * Database Manager could not load queries if the extension was capitalized (i.e.
                *.QRY) (283131)


iFIX35_1174403491NAC.exe                                    53,299               08/14/2006
                 NA_ANALZ.dll                               53,308               06/03/2004

                * Alarms no longer synchronize properly on some redundant systems after installing
                iFIX35_288678. (1-174403491)

                * Login message initiated on Client is not sent to backup SCADA node, when client is
                looking at Backup SCADA as active node. (288678)


iFIX35_1103329301 VIEW.EXE                                  1,634,370            05/12/2006
                 WSProxy.EXE                                106,560              09/01/2004
                 DRAW.EXE                                   2,404,418            08/11/2004
                 SUMQLIB_FIX32.DLL                          77,895               08/11/2004
                 HTD.EXE                                    1,060,928            08/11/2004

                * Thousands separators are placed incorrectly for some negative values of FIX
                Desktop datalinks. (1-103329301)

                * When trying to open a .grf picture through WSProxy and the picture does not exist,
                "Untitled1.grf" was not closed in WorkSpace on NLS product versions. (1-24827620)

                * Reinitialize File Dates for iFix35_294534 for NLS. Also new SIM numbering scheme
                for Desktop.

                * Buffer overrun when using View.exe in Async mode. (294534)

                * Alarms indicated with area "ALL" were not being displayed in the Alarm Summary in
                View, when the AlarmSummaryOCX was set up to filter area "A" only. (292441)


iFIX35_199756141 NAM.exe                                    61,491               03/01/2006

                * Alarms were being sent to clients even though NONE is set in Filteralm.ini when
                using non-english versions (1-99756141)

                * NAM is only dispersing about 10+ alarms per second to attached NAC's (289755)


iFIX35_1145497751 NETDIAG.EXE                               196,671              03/02/2006
                 SKT.DLL                                    188,473              07/07/2005
                 TCPDUMP.EXE                                61,501               07/07/2005
                 TCPTASK.EXE                                167,997              07/07/2005

                * "Out Of Sync In Use" Error In Netdiag. (1-145497751)
                   * Netdiag diagnostic tool fails to return valid information for the Socket Tables. (1-
                   114583744)

                   * SocketRec and Trace Tabs in Netdiag are not functional. (1-99199716)

                   * Terminal Server clients cannot connect to the SCADA node after installing
                   iFIX35_SP1. (295207A)

                   * iFIX event file filled up with assertion messages like "assertion failed (ulLocalIpAddr
                   != 0) && (ulLocalIpAddr != INADDR_NONE)" (1-99234191)

                   * An iClient cannot connect thru the RAS client connection if iFIX was already running
                   on the RAS server (SCADA) when the RAS connection was made and the user was
                   somehow able to disable all of the local IP addresses. (277339)

                   * An iClient cannot connect thru the RAS client connection if iFIX was already running
                   on the RAS server (SCADA) when the RAS connection was made. (269268)


iFIX35_155232834 OSXLIB.dll                                       49,206                04/13/2005

                   * When running the FixbackgroundServer in the background and writing a value to an
                   iFIX tag in the schedule and 8.3 format is disabled on the file system, user receives a
                   "Server automation" error. (1-55232834)


iFIX35_189034472 ElectronicSignature.dll                          184,427               05/04/2005

                   * Workspace leaks memory when using WriteValue method with security enabled.(1-
                   89034472)

                   * Workspace would crash if Esignature Dialog was open and script in background
                   closes picture (293354)

                   * E-Sig writes values with improper precision.(285358)


iFIX35_191893246 HDAODBC.dll                                      262,231               07/11/2005

                   * Memory handling error in Historical ODBC driver. (1-91893246)

                   * Fix Dynamics Historical Data - memory leak (268129)

                   * Problem with select Distinct in query when using Historical Data ODBC driver
                   (271969)


iFIX35_122718147 IHHDA.dll                                         81,984               12/01/2004
                 IHHDA3.dll                                        81,986               12/01/2004
                 FIXTOOLS.dll                                      69,693               10/27/2004
                 FixHdaDll.dll                                     73,804               05/17/2004

                   * Expression Builder iHistorian tag browse fails to display the tags associated with iFix
                   collectors but not having a node name as prefix or missing a "." in their tag names. (1-
                   22718147)
                 * Running iHistorian 3.0, when iFIX connects to the Server to get data, a Client
                 Access License (CAL) should not be used. (133962334)

                 * The filtered errors.ini file doesn't work correctly for iHistorian errors and enables
                 iHistorian API timeout to be configurable. (277122)


iFIX35_292646    IOCNTRL.exe                                     57,406                05/27/2004

                 * D parameter for IOCNTRL does not delay driver when used with /S parameter.
                 (292646)


iFIX35_121207706 ALMLIB.DLL.dll                                  86,070                12/28/2004
                 ALM_SYNC.EXE                                    45,112                12/28/2004

                 * Dates are missing from alarm messages sent from an iFix node to a Fix32 node .
                 (1-21207706)

                 * The primary SCADA (of a redundancy pair) logged in user could not write to the
                 A_NALM field even though the alarm was properly acknowledged and A_NALM
                 updated on the backup SCADA.(270021)

                 * eda_alm_get_user_que returned internal alarm acknowledgement messages (1-
                 18722801)


iFIX35_147803764 RCPUP.EXE                                       380,980               12/22/2004
                 RCPDOWN.EXE                                     389,174               12/22/2004
                 RCP.EXE                                         643,122               12/22/2004

                 * Recipe upload stops execution script when encountering a database error.(1-
                 47803764)

                 * Recipe executed using shell command inside VBA takes long time to execute
                 because the dialog stays on for about 5 seconds for each recipe. (282412)


iFIX35_122517301 BackupRestoreDll.dll                            270,426               09/10/2004
                 BackupRestoreRes.dll NLS:English                86,016                09/11/2003
                 BackupRestore.exe                               32,847                09/11/2003

                 * Problem with Backup And Restore wizard when restoring individual file (122517301)

                 * New command line options for backup/restore.


iFIX35_SP1       FIX.EXE                                          208,946              04/19/2004
                 WSACTASK.EXE                                     53,299               04/19/2004
                 CONMGR.exe                                       86,068               04/19/2004
                 SACDLL.DLL                                       188,465              04/19/2004
                 FixFileLinkDll.dll                               249,977              04/16/2004
                 FixPropDlg.dll                                   364,622              04/15/2004
                 FixPropDlgRes.dll NLS:English                    69,632               04/15/2004
                 NLSAPI.DLL                                       41,014               04/12/2004
                 LDBA.dll                                         299,061              04/12/2004
ExpertGlobal.fxg                           2,700,800   04/12/2004
Fix2DShapeDll.dll                          434,307     04/12/2004
FixShapeDll.dll                            110,707     04/12/2004
Fix2DShape.tlb                             30,128      04/12/2004
FixDataLinkDll.dll                         213,152     04/12/2004
ElectronicSignature.dll                    184,427     04/12/2004
Fix2DPenDll.dll                            430,239     04/08/2004
FixBackgroundServer.exe                    45,138      04/02/2004
FixEventDll.dll                            155,780     04/02/2004
OpcDataSystem.dll                          450,690     04/02/2004
Fix2DChartDll.dll                          360,611     04/02/2004
IHHDA.dll                                  86,080      04/01/2004
ALMLIB.DLL                                 86,070      03/31/2004
SUMQLIB.DLL                                81,975      03/31/2004
CrossReference.exe                         610,385     03/31/2004
PictureConverterDll.dll                    491,616     03/31/2004
SecuritySynchronizerDLL.dll                356,423     03/31/2004
SECMGR.dll                                 61,494      03/31/2004
SECCFG.exe                                 401,462     03/31/2004
ExpressionEditor.ocx                       258,138     03/31/2004
NAM.exe                                    61,491      03/24/2004
SKT.DLL                                    188,473     03/22/2004
TCPTASK.EXE                                167,997     03/22/2004
FixDB32_DA.dll                             73,814      03/12/2004
Fix2DTextDll.dll                           290,959     03/12/2004
FixUserPreferencesResDll.dll NLS:English   49,288      03/12/2004
FIXERROR.DLL                               139,264     03/03/2004
PlugandSolve.fxg                           840,192     03/02/2004
DataBaseManager.exe                        663,635     03/01/2004
Fix2DGroupDll.dll                          282,769     02/23/2004
SEC_AF.DLL                                 16,384      02/19/2004
SecuritySynchronizerRes.dll                32,768      02/19/2004
AlarmSummaryOCX.ocx                        385,112     02/19/2004
FixSchedulerDll.dll                        520,326     02/19/2004
FixKeyMacroDll.dll                         65,641      02/19/2004
FixKeyMacroHandlerDll.dll                  77,943      02/19/2004
XDBA.dll                                   53,301      02/13/2004
AlmODBCConfig.exe                          159,836     02/04/2004
ALMODBC.exe                                118,847     02/04/2004
ExpertGlobals2.fxg                         1,610,752   02/04/2004
FixVariableDll.dll                         131,193     01/30/2004
Fix2DLegendDll.dll                         262,309     01/28/2004
Fix2DAxisDll.dll                           213,153     01/28/2004
FixAnimationDll.dll                        139,388     01/21/2004
FixAppDll.dll                              209,007     01/19/2004
FixPictureDll.dll                          438,402     01/19/2004
VisiconXData.ocx                           413,787     01/16/2004
FixDynamoSetServer.dll                     159,875     01/16/2004
FixGlobalsServer.dll                       159,871     01/16/2004
FixPictureServer.dll                       159,871     01/16/2004
FixSchedulerServer.dll                     159,875     01/16/2004
FixToolbarServer.dll                       159,871     01/16/2004
FixToolbarDll.dll                          348,290     01/16/2004
SIMUninstall.dll                           217,159     12/31/2003
SumqUpdate.exe                             24,645      12/10/2003
LOGIN.EXE                                  143,410     11/21/2003
Scripting.dll                                   225,356              11/20/2003
QUE2LIB.DLL                                     61,494               11/17/2003
Fix2DBitmapDll.dll                              192,659              11/10/2003
FixComponentDll.dll                             589,931              11/10/2003
Fix2DBitmap.tlb NLS:English                     30,196               11/10/2003
FixControlContainerDll.dll                      327,843              09/26/2003
launch.exe                                      102,465              09/24/2003
ExpertGlobalRES.dll NLS:English                 86,016               09/23/2003
FD_BDW.dll NLS:English                          28,672               09/17/2003
AppValidator.exe                                241,741              09/17/2003
AppValidatorRes.dll NLS:English                 77,824               09/17/2003
launchres.dll NLS:English                       49,152               09/15/2003
StartupProfileMgrRes.dll NLS:English            40,960               09/12/2003
StartupProfileMgr.exe                           94,295               09/12/2003
BackupRestoreRes.dll NLS:English                86,016               09/11/2003
BackupRestoreDll.dll                            270,426              09/11/2003
BackupRestore.exe                               32,847               09/11/2003
TimerManager.dll                                57,426               09/08/2003
FixDB32_DARes.dll NLS:English                   16,384               07/14/2003

* Can not switch to run between iFIX and Sample System (NLS) (279886)

* NLS Translation issues (279280)

* New command line options for backup/restore.

* The DA block's alarm mode switch's to NEVER from ACK, if no option is selected.
(283296)

* Database Manager only shows first 50 tags upon initial startup. (286760)

* DatabaseManager crash while opening on a machine with Windows Server 2003,
iFix 3.5, and iHistorian 2.0 installed. (283446)

* Database Manager could not modify values in certain fields (Init Alarm, etc.)
(286209)

* Database Manager could not load queries if the extension was capitalized (i.e.
*.QRY) (283131)

* E-Sig writes values with improper precision.(285358)

* Added a configuration setting to the .ini file to allow the user to specify the method
iFIX uses to open picture (290712)

* Cannot translate main window title, Detail Report window (Row Count) , Auto Report
Naming (Browse dir window - "Select a directory")

* Double bytes strings are not displayed correctly in Application Validator main dialog,
Comparison Detail Report dialog, and Print Preview dialog. (278413)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* Increased range of Help context ID values to support values between -
2,147,483,648 and -2,147,483,647 (290334)
* Some EGU values entered as scientific notation would trigger an "out of range" error
(283944B)

* Reentering the Color Expert dialog and then moving the focus off the Data Source
field causes the Color Threshold Table to be reset to the default if the data source
contains multiple tags.(286911)

* Object becomes invisible in run mode when animation is deleted from iFix Browser
Tree (283047)

* Inserting a datalink and setting a historical datasource, then get an error, and setting
a realtime datasource results in a WorkSpace crash. (286063)

* Workspace crash in PTimeDll when pictures containing charts were repeatedly
opened and closed and modified the time range of the charts. (287787)

* CrossReference tool doesn't use regional settings when saving a file as CSV.
(284883)

* FixBackgroundServer can't monitor running schedules, when run as a service.
(287836)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* RAMP block does not ramp down when low EGU is greater then hi EGU (288563)

* Unable to log into iFix when connection to primary domain controller is lost (267542)

* Security Configuration Modifications to support Classic Desktop. (287808)

* SAC would not start up for 20 seconds, when using a large database. (257584)

* sq_remove() error thrown when trying to modify an AIS block thru the
DatabaseManager. (257625)

* SAC slows down after changing 200 AO blocks current mode from AUTO to MANL.
(269990)

* Added "iBatch - Start iWorkInstruction Editor" to iFIX application security areas
(280371)

* Added command line parameter to suppress ORNG (OverRange) Alarm.(273507)

* SecuritySynchronizer /R removes RECIPE User Account from iFix Security
(281002)

* SecurityArea in Picture Properties will not allow you to assign a area name of 22B, if
you have already assigned a security area 22A to a previous picture (264728)

* iFIX - Windows security it was not possible to use a "." or "'" in the NT user name
(275124)

* Incorrect License Error: iFix has detected a serious problem please shutdown iFix.
(278711)
* OnTrue/OnFalse scheduled events fire on startup even when "Fire DataChange
Event on Startup" is deselected. (285575)

* While trending with T_DATA pens on Terminal Server, a random crash occurs.
(279198)

* Charts created using iFix automation interface get abnormal Width and Height
properties.(285999)

* ETR data doesn't show up correctly when changing the pen's Duration in Run
mode.(285687)

* Picture Conversion causing datalink font size to increase drastically. (288371)

* Object animations and data links not updating because of faulty hardware HAL or
BIOS. (269172)

* Foreground color animation doesn't work until the data source changes its value if
the picture is opened in Run mode. (282461)

* Leading and Trailing spaces for Text objects are being deleted. (283218)

* Setting a pen's fixed start time with only time in a chart group file causes a type
mismatch error when you apply the chart group file.(284209)

* Deleting animations with the Basic Animations dialog will result in the animation
being deleted from the object, but it remains in the system tree. (280962)

* Incorrect datalink format when migrating from fix 32 with a symbol from a tag group
(277426)

* Converting pictures from Fix32 and then trying to rotate objects in iFix would not
work correctly. (272793)

* Picture Converter was not converting a text object's visibility animation exact match
tolerance correctly. (273899)

* Picture converter does not convert expressions for visibility correctly when regional
setting is something other than English (272789)

* Picture converter does not make first line of command script a comment when that
first line is a comment. (262514)

* Picture converter doesn't convert chart's, when the pen's datasource doesn't exist.
(263527)

* If an object is nested in two groups, the size or position animations of that object do
not initialize correctly.(278574)

* If a grouped object has been highlighted and selected and then its group or itself
becomes invisible, the highlight of the object remains on the screen despite the object
being invisible.(277979)

* "invalid argument was encountered..." error while adding pen using WIN2003, iFIX
3.5 and iHistorian. (287196)
* Converted Fix32 datalink with taggroup symbol displays drop down combo box as
alpha-numberic instead of numeric in iFix Datalink Custom Dialog (287172)

* AlarmSummaryOCX not sorting correctly when sort order is set using VB
automation properties (285530)

* Error in setting timer interval, when using Italy regional settings & time separator of
':' (286249)

* Using Key Macros causes memory leak.(283043)

* A global variable's value, when animated to a database tag, is set to zero when
communication is lost to that tag. (284423)

* iFIX Workspace crash showing a memory access violation in PTimedll.dll. when
using a schedule and also picture initialization code to modify Pens in a chart on the
picture. (284593)

* In Build Dynamo Wizard, partial substitution for a dynamo property value does not
work properly if multiple occurences needed. (283379)

* AlarmODBC unable to handle schema name when defined in tablename when
writing to ORACLE (286150)

* Widened fields to support NLS strings (286795)

* Cannot edit a Chart Group File in run mode, using Chart Group Wizard. (285935)

* Opening or replacing a picture containing charts displaying ETR data or other real
time data is slow at iClient nodes. (281963)

* A historical trend chart shows a wrong value for the average over range if only part
of the chart is filled with data. (265305)

* 'High over range' value in charts is 0 if high is a negative number. (275225)

* Pen in Average Hist mode displays line after last known Good value in Chart
(273503)

* Corrected field truncations in Create Picture Wizard and Print Crystal report wizard
forms (285441)

* PictureConverter crash when using DDE links as source of Dynamic Coloring
Property (285824)

* Event firing was inconsistent when using picture caching. (278187)

* Opc datasources used in TagGroup datalinks do not re-connect when the OPC
Server is shutdown and re-started. (282205)

* ETR data doesn't display in charts when opening or replacing the containing
picture.(283572)

* VisiconX Data object would reset back to first record after a query. (284551)
* Workspace temporarily freezes when pictures directly access OPC data points
(285074)

* AlarmODBC.cfg become corrupt if tablename is changed to a shorter name
(284313)

* Security Issue (283386)

* Data Source gets changed from F_# to F_CV if tag does not exist prior to using
color expert (282956)

* Login.exe dialog closes when pressing ESC if opened by iFixScreenSaver (281132)

* When using the iFIX Screensaver, users are unable to change password if expired
(274065)

* F10 Key Macro does not work correctly (263027)

* Tolerance is not being saved using datalinks. (282037)

* Create Picture expert inserts incorrect sizes, using predefined configuration.
(282124)

* MouseUp events do not fire if the mouse button is released off the object. (281070)

* Picture Converter doesn't set MaxCharactersPerLine property to 80 for text objects
less than 80, also AutoSize is set to false. (279003)

* Picture converter corrupts Kanji characters, when converting small Push Buttons.
(278656)

* Table animation entries are not saved when using tag groups as the datasource on
a datalink caption animation. (279936)

* Fix.exe will hang on the shutdown waiting for third-party application which was
registered with iFix using FixRegisterConsole() helper function (277058)

* Cannot set Column widths to stay persistent for alarm summary in configure mode
(279311)

* Cannot translate Build Dynamo Wizard dialog (279274)

* Cannot translate "Use Pixel Coordinates" and "Use Percentage Coordinates"
checkboxes in "In Enter New Configuration Name" dialog (279273)

* Create Picture Wizard NLS: String ID in Tag property were missing in
btnDeleteConfig, pgStyles, pgSizes, btnSave control (278561)

* Continuous iFix Timers would occasionally fire 1 second early. (277455)

* Toolbar buttons are missing from the toolbar, during a mode switch. (276640)

* Double bytes strings are not displayed correctly in Server selection ComboBox and
Item browsing spread control. (NLS) (280803)

* AlmSum.exe was hogging 100% CPU for an indefinite period of time. (252294)
                  * Alarm Summary Sorting Problem when using LIN driver and there is no PDB and
                  WSACTASK being used (276687)

                  * Unable to remove user created alarm queue when started by background schedule
                  (276672)

                  * Alarm ODBC service did not log double bytes operator message correctly with
                  calling SendSignedOperatorMessage function when the message is over 82 bytes.
                  (282253 NLS)

                  * Double bytes strings are not displayed correctly in Startup Profile Mgr main dialog.
                  (278412)

                  * NAM is only dispersing about 10+ alarms per second to attached NAC's (289755)

                  * Enables iHistorian API timeout to be configurable (277122)

                  * Allows throttling of the frequency of alarm cycles for the thread that moves alarms
                  from the SAC queue to the Summary queue. (268948)

                  * An iClient cannot connect thru the RAS client connection if iFIX was already running
                  on the RAS server (SCADA) when the RAS connection was made. (269268)


iFIX 3.5 German

iFIX35_1123523131FixTagGroupDll.dll                              155,769             07/17/2006
                 Fix2DBitmapDll.dll                              192,659             06/28/2006
                 Fix2DBitmap.tlb                                 30,196              06/28/2006
                 FixBackgroundServer.exe                         45,138              06/23/2006
                 OpcDataSystem.dll                               450,690             06/20/2006
                 FixEventDll.dll                                 155,780             06/07/2006
                 FixAppDll.dll                                   209,007             06/07/2006
                 FixPageDll.dll                                  352,369             06/07/2006
                 PlugandSolve.fxg                                826,880             05/23/2006
                 FixLookupDll.dll                                172,166             05/23/2006
                 FileTree.ocx                                    57,344              05/12/2006
                 WSACTASK.EXE                                    53,299              05/08/2006
                 SACDLL.DLL                                      192,561             05/08/2006
                 SecuritySynchronizerDLL.dll                     356,423             04/27/2006
                 SECCFG.exe                                      397,366             04/27/2006
                 SECMGR.dll                                      65,590              04/27/2006
                 VisiconXData.ocx                                413,787             04/21/2006
                 FixChartDlg.dll                                 499,792             04/04/2006
                 FixComponentDll.dll                             589,931             03/28/2006
                 AlmSumMgr.DLL                                   102,478             03/17/2006
                 AlarmSummaryOCX.ocx                             385,112             03/17/2006
                 AlmSumMgrRes.dll                                20,480              03/17/2006
                 AlarmSummaryOCXRes.dll                          65,654              03/17/2006
                 PictureConverterDll.dll                         495,712             03/02/2006
                 Fix2DTextDll.dll                                290,959             03/02/2006
                 FIXERROR.DLL                                    139,264             02/28/2006
                 Fix2DGroupDll.dll                               282,769             01/31/2006
                 Fix2DPenDll.dll                                 430,239             01/27/2006
                 FIX.EXE                                         208,946             12/28/2005
FIXSRV.exe                         65,589      12/28/2005
FixSchedulerDll.dll                520,326     12/28/2005
FixPictureDll.dll                  438,402     12/28/2005
VisiconXGrid.ocx                   114,779     12/25/2005
FixGlobalSysInfoDll.dll            143,491     11/15/2005
FCATABLE.DLL                       53,305      11/15/2005
LOGIN.EXE                          143,410     11/12/2005
ExpertGlobalRES.dll                86,016      11/11/2005
ALMODBC.exe                        118,847     11/01/2005
FactoryGlobalsRES.dll              61,440      09/30/2005
FixControlContainerDll.dll         331,939     08/18/2005
EnumerationsDLL.dll                28,672      08/15/2005
LDBA.dll                           299,061     08/15/2005
FactoryGlobals.fxg                 1,822,208   07/27/2005
CONMGR.exe                         69,684      07/25/2005
FixFileLinkDll.dll                 249,977     04/13/2005
WorkSpace.exe                      139,335     03/21/2005
FixUserPreferencesManagerRes.dll   20,480      03/16/2005
FixFormatDll.dll                   155,782     03/16/2005
FixFormat.tlb                      19,432      03/16/2005
FixUserPreferencesManagerDll.dll   135,290     03/16/2005
Scripting.dll                      225,356     03/16/2005
ValvesAnim.fds                     222,208     02/14/2005
FixBackgroundServerRes.dll         40,960      02/09/2005
FixPropDlg.dll                     364,622     02/09/2005
Tanks.fds                          269,824     02/09/2005
TanksAnim1.fds                     261,120     02/09/2005
TanksAnim2.fds                     271,872     02/09/2005
PipesAnim.fds                      194,560     02/09/2005
Pipes.fds                          220,672     02/09/2005
ExpertGlobal.fxg                   2,712,576   02/09/2005
Fix2DAxisDll.dll                   213,153     02/07/2005
Fix2DChartDll.dll                  360,611     02/07/2005
Fix2DLegendDll.dll                 262,309     02/07/2005
SearchReplace.dll                  143,444     02/04/2005
FixDataLinkDll.dll                 213,152     02/04/2005
iFixScreenSaver.scr                102,482     02/03/2005
TimerManager.dll                   57,426      01/11/2005
FixTimerDll.dll                    184,435     01/11/2005
Fix2DShapeDll.dll                  434,307     12/28/2004
FixAnimationDll.dll                139,388     12/28/2004
FixLinearDll.dll                   139,398     12/28/2004
Fix2DShape.tlb                     30,128      12/28/2004
FixComponentRes.dll                16,384      12/28/2004
SUMQLIB.DLL                        81,975      12/28/2004
SCU.exe                            618,547     12/28/2004
FixErrToHResult.dll                24,664      11/29/2004
WorkSpaceErrorsRes.dll             57,344      11/29/2004
FixShapeDll.dll                    110,707     11/08/2004
FixAppServiceDll.dll               102,525     09/27/2004
OpcEdaDll.dll                      143,436     09/21/2004
AlmODBCConfig.exe                  159,836     09/17/2004
FixControlContainerRes.dll         32,768      09/10/2004
QUE2LIB.DLL                        61,494      08/16/2004
FixUserPreferencesDll.dll          225,380     07/21/2004
FixPropDlgRes.dll                  69,632      07/20/2004
launch.exe                                     102,465              07/17/2004
OODBDll.dll                                    225,360              07/17/2004
FixDataSystems.ocx                             114,797              07/02/2004
OPC20iFIX.exe                                  290,887              07/02/2004
WorkSpaceRes.dll                               135,168              07/02/2004
FixUserPreferencesResDll.dll                   49,288               06/10/2004
NLSAPI.DLL                                     41,014               04/12/2004
CrossReference.exe                             610,385              03/31/2004
ExpressionEditor.ocx                           258,138              03/31/2004
SecuritySynchronizerRes.dll                    32,768               02/19/2004
SEC_AF.DLL                                     16,384               02/19/2004
FixKeyMacroDll.dll                             65,641               02/19/2004
FixKeyMacroHandlerDll.dll                      77,943               02/19/2004
XDBA.dll                                       53,301               02/13/2004
ExpertGlobals2.fxg                             1,610,752            02/04/2004
FixVariableDll.dll                             131,193              01/30/2004
FixDynamoSetServer.dll                         159,875              01/16/2004
FixGlobalsServer.dll                           159,871              01/16/2004
FixPictureServer.dll                           159,871              01/16/2004
FixSchedulerServer.dll                         159,875              01/16/2004
FixToolbarServer.dll                           159,871              01/16/2004
FixToolbarDll.dll                              348,290              01/16/2004
SumqUpdate.exe                                 24,645               12/10/2003
FD_BDW.dll                                     28,672               09/17/2003
launchres.dll                                  49,152               09/15/2003

* Tag group resolution does not work properly if using the DefaultRefreshRate entry in
the Workspace.ini file and resolving tags before switching to Run mode. (1-
123523131)

* Bitmap Pushbutton stays stuck down, when pushbutton is invisible and user clicks
on area where pushbutton exists. (1-162154461)

* FixBackgroundServer events logged in the NT Event Viewer are not mapping with
descriptions.(1-144598020)

* Data in a picture never updates.(1-144898371)

* If Fire DataChange Event is disabled, then global user variable never triggers (1-
155223934)

* In the Chart Group File dialog, the file tree doesn't support Kanji Characters. (1-
112641852)

* Changing the DataSource for the last existing pen in a chart group file using the
Chart Group Wizard causes the values for color and limits to be reset. (1-111307898)

* Color animations using shared threshold table don't work properly if the same
threshold table is used by different pictures and these pictures are all opened in run
mode. (1-147175602)

* In the Chart Group File dialog, the file tree doesn't support Kanji Characters. (1-
112641852)
* It was not possible to use a "_" in a Windows User Name when running
SecuritySynchronizer (1-161443891)

* SQT blocks get stuck in the state of waiting for confirmation once their confirmations
get lost or never happen. (1-97202545A)

* VisiconX data control requires user with local administrative rights to connect to
OLE DB database. (1-110895991)

* Can't set the span interval to be 0 at chart configuration. (1-118948231)

* Workspace OPC client does not display OPC server's error string correctly (1-
126022821)

* Complex expressions fail after installation of sim 1-95976911 on Japanese iFix (1-
116459481)

* Log file and Alarm ODBC database don't capture each unsuccessful login attempt
(1-150615677)

* TX Block's comm. alarm doesn't show up on the AlarmSummary. (1-118034431)

* Alarm Summary OCX doesn't allow user to filter by the ACK column. (1-103547011)

* Picture Converter does not convert command comments correctly. (1-105643029)

* Cannot backspace when adding characters to a datalink. (1-115227146)

* Slow NT authentication for iFIX domain user (1-95990941C)

* Accelerator for Pushbutton doesn't work when Pushbutton is grouped (1-
116290921)

* Pictureconverter leaves unwanted '&' character in button! (1-116895871)

* Datalinks converted from FIX32 will highlight even though they were not
highlightable in the FIX32 picture.(1-127653268)

* Chart does not update correctly when changing tag group file that references t_data
(1-108273211)

* Automation error occurs when the DBDisconnect method is used in the
ExecuteComplete event of the VXDATA control. (1-119581251)

* iFix can't shut down ALMODBC and WSQLODC if they connect to a Sybase 9.xx
database on French OS. (1-105652516)

* Zooming a chart causes value ranges displayed on the Y axis of the chart to go
beyond its pens' EGU limits.(1-93670101)

* Encounter error when trying to modify schedule that has been set to run in
background (1-100502591)

* Unable to enter the Slash(/) from numeric pad in a Datalink. (1-112641841)*
Datalink doesn't support supressing character entry (1-116023901)
* Commandbutton no longer highlights in run mode after undoing a delete in
Configuration mode (1-115514116)

* Autoresize property of VisiconXData control doesn't resize columns after fetching
data.(1-113180591)

* Workspace intermittently disappears\access violation when running on RDP clients
(1-36959520)

* Advanced animation with TagGroup expressions containing complex expressions
no longer worked after installation of sim (1-100954501)

* Logging out of windows causes Fix service to goto stopping (1-100137961)

* ALT-TAB permissions not restored properly when using stacked logged in users (1-
109910701)

* "User Defined Fields" work differently for Alarms vs Events (1-106088924)

* Blinking property of an animated object using Dynamos is not working properly. (1-
99874598)

* Fonts stop changing horizontally in proportion to vertical changes if you change the
resolution of the screen while configuring a chart. (1-99237697)

* CommandButton script isn't recorded on basic animation dialog (1-106169060)

* Get error message "Expressions containing Historical items is not allowed" when
adding a pen that references to a iHistorian tag to a chart group file, if the pen name
matchs the pattern of "*.*.*.*.*". (1-71329801)

* Get error message "Secure Containment Detected Bad Control ..." and Workspace
crash while configuring a VisiconX data control to use Microsoft OLE DB Provider for
SQL Server as data provider, if more than 255 SQL servers are available in the
network.(1-99995157)

* Application crash when writing to A_ENAB field using EDA (1104354604)

* Alarm Acknowledge messages are being sent to the AA/DA block alarm areas
instead of the alarm areas for operator messages. (1-101856381)

* OnDataChange Event Does not Fire first time value changes (197333581)

* AcknowledgeAnAlarm can't acknowledge an alarm using a tag group symbol.(1-
95001621)

* Double byte dash "-" is not recognized for a object name in iFIX 3.5 Japanese. (1-
95976911)

* The GetFullName method of the ESignature object doesn't work if the Windows
user is a local user and the method is used to get a domain user's full name.(1-
52405328)

* MouseUp and MouseUpOffObject scripts do not work properly. (1-91893091)

* Find operation in workspace always sets dirty flag (1-101005761)
* AlmODBC crashes with STK Userfield and STK alm extension field being truncated
(142562201)

* When selecting text in a datalink that has "Leading Spaces" enabled, the text
highlight strips of the leading spaces (1-37828101)

* Workspace application crash when closing a picture that was created on a machine
with FIXDesktop installed and run on a machine without FIXDesktop installed. (1-
94231958)

* The Workspace application object does not properly accept negative values for the
TOP and LEFT properties. (1-90865926)

* Alarming-suspended/resumed messages are being sent to the AA/DA block alarm
areas instead of the alarm areas for operator messages. (1-91722901)



* Can't type in a space in editing mode of the standard text tool after installing
iFIX35_281537 or a later workspace SIM and having selected the Remove Leading
and Trailing Spaces option for text in the User Preferences.(1-83444001)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* Workspace crashes when switching between pictures using ReplacePicture
subroutine, if picture caching is enabled and the new picture names passed in
ReplacePicture are"xxxxx.grf" and "xxxxx.grf "(i.e. file names with trailing whitespace
characters).                                (288907)

* Read-write access to the security path is needed in order to use the security
configurator. (1-83519101)

* After installing iFIX35_294859, when Workspace is started, it is not restored at the
size that it was last closed. (1-85376901)

* Find function in VBE of Workspace does not handle inputting double byte characters
correctly. (1-79830201)

* Precision adjustment for a float-value datalink causes the value sometimes being
displayed with a different rounding from the Curr Value field in the Database
Manager. (1-43322301)

* The Timer Cursor shows no data for the last sample using SetPenDataArray
method. (1-79315501)

* FIXbackgroundServer Event ID 103, 107, 108, 111 messages appear erroneously in
the Event log (266950)

* Custom color palettes do not work using tank, valve and pipe dynamo's. (272910)

* Ramp Expert doesn't set the value to the low/high limit, when the new value
exceedes the limit.(270674)
* Some automation subroutines (AcknowledgeAnAlarm, RampValue, SetManual,
SetAuto, ToggleManual) change the values of parameters passed to them.(273349)

* The WriteValue VBA method sent an incorrectly formatted operator message if the
data source had a "%" in it.             (264630)

* Added Interval Field to Chart Group Wizard (274023)

* Chart group methods are not accessible in the background task.(272466)

* The Visibility Expert adds lookup levels in the descending order of input values
when configuring, which causes visibility animations to be converted incorrectly as the
Web Converter is expecting all lookup levels in the ascending order of input
values.(276784)

* A visibility animation created with a range, will not be edited correctly with the
visibility expert. (274718)

* FixBackgroundServer can't monitor running schedules, when run as a service on
WIN2000. (287836)

* Custom color palettes don't work in a pen's color. (262282)

* After opening and closing the VBA property window, a pen can't be deleted from a
chart properly. (268805)

* Using ModifyColumnLength VBA method to change the Chart's legend column
length, causes the legend text to grow and stretch. (271284)

* VisiconX Grid time field displays both system date and time. (279234)

* Can't open a .csv file by using VisiconX and OleDB provider for ODBC. (259313)

* Find and Replace messes up script.(273672)

* Changing the Object Name and Description on the Basic Animation Dialog does not
dirty the containing picture. (277534)

* Close and Save method of Document(s) allow document(s) to be saved during
mode switch, which sometimes causes the document(s) to be corrupted.(267849)

* FixBackground Server crashes while running iFIX as a service. (272155)

* "Invalid Handle" message is given when a "Delete All" is executed on the Alarm
Summary OCX.(260452)

* Datalink raw format resets when changing the datasource. (264403)

* The current alarm index would intermittedly get stuck on last alarm acknowledge
when scroll bars are enabled and ACK/PRIORITY descending. (272349)

* Alarm Summary's status bar prints black when using XP themes. (278401)

* iFixScreenSaver will hang if Login.exe is already opened (295038)
* AlmODBC crash when STK Userfield lengths exceed 79 characters and also STK
alarm extension field was being truncated. (142562201)

* TagGroup expressions containing complex expressions cause high message rate
(264443)

* Initial update of datalink values is slow when first opening a picture (1-19756822)

* Users get 'Invalid qualifier' error on data entry form after installing iFIX35_292319B
SIM.(1-42578390)

* Daily schedules running in the background skip firing every other day and double
firing at midnight when using New Zealand regional settings and time zone.(263814)

* Using the ToggleDigitalPoint expert and then running the Tag Group Editor (Get
Symbols From Picture), will not get all of the Tag Group Symbols that are eligible in
the picture.(274890)

* In datalink and some animation experts, if the data source is a single source, not an
expression, the tolerance gets reset to default.(276128)

* Remove Level automation method causes a memory leak. (273677)

* Dashed lines are printed as solid. (272979)

* Bitmap Pushbutton stays stuck down, when using a mouse down event that
launches a modal dialog. (278520)

* Tooltip would intermittedly flash on select PC's (266730)

* Can't get a property name correctly using the property dispatch ID, if the dispatch ID
is zero.(272807)

* When implementing the same VBA procedure in a picture and in a group (of objects
contained) as well, the VBA procedure was disabled at the picture level after
renaming the group. (275682)

* When using automation SelectObject method to select multiple objects, the color
property was only being set on the last selected object. (279699)

* MDI->EV->DA chain goes off-scan on iFIX re-start or database reload. (269246)

* More than 20 consecutive calls                 to   FixGetUserInfo     would    return
"smo_replace_profile: bad index". (273300)

* Tag description not being written to RDBM from AlarmODBC (268799)

* When using the sa_almmsg_cb and passing in the timestamp for the alarm, the
TimeIn on view nodes would not get updated if there was an existing alarm. (277780)

* AAD file cannot be accessed from VIEW node. (269866)

* Random "iFIX Detected a Serious Problem. Please Shut Down Restart iFIX" errors
(1-52135901)

* Text object has no space in between multiple lines of text. (1-34485756)
* Pressing the CTRL and then the TAB keys repeatedly causes the Workspace to
consume 100% CPU usage and makes the workspace unresponsive. (141913801)

* Some methods of Alarm Summary cause memory leak. (266745)

* Datalinks not retaining\displaying leading\trailing spaces when writing to TX Blocks
(1-37828101)

* After choosing a color from a custom color set, a foreground color animation
configured with the Foreground Color Expert cannot retain any new color selection
from the system default color set. (1-32449601)

* Deleting the Enabled animation of a push button from the system tree causes the
push button disabled.(1-34153301)

* Applying a chart group file that has an interval greater than 1 minute to an iFix chart
results in an error message "FIX2DPen invalid parameter".(1-32281101)

* Turning on data system prematurely causes some animations to work incorrectly.(1-
27285016)

* Unusual Behavior when pictures are saved outside the PIC directory and switched
to Run mode (1-32486401)

* Added a configuration setting to the .ini file to allow the user to specify the method
iFIX uses to open picture (290712)

* Animation data error doesn't work properly after installing iFIX35_SP1. (1-
32916701)

* The "Blink on New Alarm" checkbox will not stay checked the datasource is a tag
group and the animation is opened using the wizard. (132796801)

* The a F_CV value on RealTime Chart will cause the chart to blank and restart when
duration is changed (294512)

* The basic animation table settings are lost when using an undefined user global
variable as the data source in the basic animation dialogs.(1-21409801)

* Data Type mismatch error on automation method "AcknowledgeAllAlarms" when the
picture contains an object with an animation with a datasource equal to a constant.
(1-25827301)

* An event based schedule doesn't fire if it is using the System.CurrentTime property
in its data source and run in the background.(294413)

* Shape animation is no longer valid after a global Search and Replace (292319)

* Additional OPC Refresh configuration option. (119237501)

* Increased the maximum limit of the number of records to read from the User queue
before writing to the relational database for AlarmODBC. (280263)

* The Address fields in Device Control (DC) block does not accept syntax for OPC
Client driver. (290932)
* Digital Input block's alarm for the Close state, goes away on database reload.
(122925753)

* The MS Forms 2.0 Textbox control was not scrolling text properly. (292395)

* Workspace.exe in the SCU tasklist did not startup in the mode indicated by the
mode settings.(294859)

* Find & Replace failed with access exception (119739601)

* SetTimeCursorTime Method does not work properly.(292789)

* When using flexdata and thousands of alarms, the AlarmSummaryOCX was slow in
responding to subsequent Workspace user actions after the AlarmSummaryOCX was
initially opened in Workspace Run. (293322)

* An iHistorian Calculator Collector stop\re-start in the iHistorian Administrator would
cause the tag calculation to fail, "Object is not connected to the server". (290840)

* Down arrow key does not work if first datalink is invisible. (293910)

* Grouped Datalink sourced from a Global variable displays the stale data value if the
picture cache is enabled. (291986)

* SetTimeCursorTime Method does not work properly.(292789)

* Cannot de-select "Remove Trailing and Leading Spaces" for text objects in User
Preferences.(17410327)

* The animation table settings are lost when Using a undefined User Global Variable
in the Advanced Animation dialog. (288314)

* AlmODBC doesn't insert multiple records into SQL. (292290)

* Duplicate Logical Nodename error when using Launch with command line
parmeters /s /l /n (288317)

* License Error - iFIX has detected a serious problem. Please shutdown and restart
iFIX" generated when there was an invalid path or entry in the task list. (292781)

* Can not switch to run between iFIX and Sample System (NLS) (279886)

* NLS Translation issues (279280)

* AcknowledgeAllAlarms subroutine doesn't work for tag groups after migrating the
picture created with iFIX 2.6 to iFIX 3.5.(293393)

* Nudge settings not reflecting settings from the Fixuserpreferences.ini (294535)

* Added the ability to suppress RANGE, UNDER RANGE, and NODATA alarms.
(290732)

* Fix Data System OCX not working (294185)
* Spacing between lines in a multiple-line datalink changes when the last few lines are
blank.(292544)

* XYHistTest Method returns error (292899)

* Dead lock condition using OPCEDA asynchronously. (283840)

* OpciFix OPC server doesn't browse STK tags. (290388)

* Pictures are resized when the workspace opens after it was last closed in the
minimized or restored state.(292398)

* Duplication turns PushButton to FixOLEControl.(292381)

* Legend object get_LegendHeadingLine() is not returning Interval column name and
GetColumnInfo() method is returning empty column name.(294667)

* If the AlarmSummaryOCX is scrolled, and a new alarm comes in, the visible viewing
area is reset to the new end rows. (292610)

* SecuritySynchronizer crashes when logging oversized message.(292169)

* Added automation properties to support infoAgent 2.0 (293871)

* Clicking the Cancel button when configuring a schedule item causes some scripts
removed if the beginning of the names are the same for the timer and event schedule
items and the underscore character is used.(290611)

* Text object doesn't go to the next line when exceeding MaxCharactersPerLine.
(291537)

* Duplication of dynamo generates objects with same name.(290257)

* Applying a chart group file to a chart sometimes doesn't set EGU limits
correctly.(288261)

* VisiconX shows no data in the VisiconX Grid when opening a picture that has been
cached. (289291)

* Build Dynamo Wizard: Partial substitution for a dynamo property value does not
work properly if there is a decimal point in the animation data source.(290242)

* Animations don't work using constant numerical datasources. (288963)

* DBASRV inadvertently starts running when during iFIX startup. (291346)

* When using a long datatype datablock from an OPC server as the datasource in a
datalink, the value was different in the iFIX database and the datalink by 1. (292059)

* Alarms with the same Time In and Time Last are sometimes displayed in a different
order depending on the Sort Key. (289889)

* Script events created with the VBA FindReplaceInObject automation method do not
fire. (287883)
                 * Using NT security with iFix security, password expires error message occurs, even
                 though the user account is set to password never expires. (288005)

                 * Animated Text object caption doesn't work, if the datasource is static text. (286466)

                 * A chart does not display axes and grids after setting its current pen to be not
                 visible.(287462)

                 * Bad event message being sent to alarm typers, when user tries to set alarm values
                 of block higher then Egu Hi (290559)

                 * VBA Errors on install when installing to a machine with XP machine that has
                 sublanguages installed. (289295)

                 * Color animation's table resets when leaving expression editor, using the color
                 experts. (290442)

                 * Group click events do not fire when clicking on a control with no events. (285712)

                 * RetrieveTagGroupVariable method leaks memory.(287253)

                 * Acknowledged Alarms were being dropped from alarm synchronization (288698)

                 * The property name gets stripped from animation data source when reentering the
                 animation dialog, if the data source is an OLE object's default property.(287357)


iFIX35_1112501941 VDBA.DLL                                     41,014               11/28/2005
                 EDA.dll                                        86,067              10/24/2005
                 DDECLNT.EXE                                    188,471             10/24/2005
                 etr.gov                                        978                 08/15/2005
                 pa.gov                                         2,112               08/15/2005
                 tr.gov                                         978                 08/15/2005
                 hs.gov                                         978                 08/15/2005
                 ev.gov                                         978                 08/15/2005
                 dt.gov                                         870                 08/15/2005
                 DataBaseManager.exe                            663,635             07/27/2005
                 FixDB32_DO.dll                                 57,430              07/14/2005
                 FixDB32_AO.dll                                 65,622              07/14/2005
                 FixDB32_DI.dll                                 65,622              09/07/2004
                 FixDB32_DR.dll                                 53,334              09/07/2004
                 FixDB32_DA.dll                                 73,814              09/07/2004
                 FixDB32_BLRes.dll                              16,495              06/14/2004
                 FixDB32_DIRes.dll                              16,495              06/14/2004
                 FixDB32_DORes.dll                              16,495              06/14/2004
                 FixDB32_DARes.dll                              16,384              06/14/2004
                 FixDB32_DRRes.dll                              12,288              06/14/2004
                 DatabaseManagerRes.dll                         204,800             06/10/2004

                 * iFix Database Toolkit gives it 4293 string in alarm status when the alarm is COMM
                 (1-112501941)

                 * NETDDE cannot get remote Excel data in view on Win 2000 machine. (1-
                 115030351)

                 * Alarm Extension fields not being exported for some blocks (1-103966121)
                * Low EGU limit of 0.000001 causes error on import of database (187182953)

                * Event messaging no longer works on AO and DO blocks (186558030)

                * Database Manager will not start on machines with large registry files (1-86803501)

                * The Database Management spreadsheet displays incorrectly if a tag is imported that
                has double byte and regular characters that exceed the length limit of a field. (1-
                79830256)

                * PDB queries not working when there is no SORT order criteria (1-19734301)

                * Open/Close labels do not change case on Digital blocks (293103)

                * DB Manager EXPORT problem with Large Loadable Block (292393)

                * Database Manager doesn't allow lowercase for digital and boolean block
                labels.(277527)

                * Importing a CSV file into Database Manager that contains an equal sign(=) in the
                description field, without single quotes surrounding it, causes the block to import
                incorrectly without error.(269981)

                * The DA block's alarm mode switch's to NEVER from ACK, if no option is selected.
                (283296)

                * Database Manager only shows first 50 tags upon initial startup. (286760)

                * DatabaseManager crash while opening on a machine with Windows Server 2003,
                iFix 3.5, and iHistorian 2.0 installed. (283446)

                * Database Manager could not modify values in certain fields (Init Alarm, etc.)
                (286209)

                * Database Manager could not load queries if the extension was capitalized (i.e.
                *.QRY) (283131)


iFIX35_1174403491NAC.exe                                     53,299              08/14/2006
                 NA_ANALZ.dll                                53,308              06/03/2004

                * Alarms no longer synchronize properly on some redundant systems after installing
                iFIX35_288678. (1-174403491)

                * Login message initiated on Client is not sent to backup SCADA node, when client is
                looking at Backup SCADA as active node. (288678)


iFIX35_1103329301 VIEW.EXE                                   1,634,370           05/12/2006
                 WSProxy.EXE                                 106,560             09/01/2004
                 DRAW.EXE                                    2,404,418           08/11/2004
                 SUMQLIB_FIX32.DLL                           77,895              08/11/2004
                 HTD.EXE                                     1,060,928           08/11/2004
                 * Thousands separators are placed incorrectly for some negative values of FIX
                 Desktop datalinks. (1-103329301)

                 * When trying to open a .grf picture through WSProxy and the picture does not exist,
                 "Untitled1.grf" was not closed in WorkSpace on NLS product versions. (1-24827620)

                 * Reinitialize File Dates for iFix35_294534 for NLS. Also new SIM numbering scheme
                 for Desktop.

                 * Buffer overrun when using View.exe in Async mode. (294534)

                 * Alarms indicated with area "ALL" were not being displayed in the Alarm Summary in
                 View, when the AlarmSummaryOCX was set up to filter area "A" only. (292441)


iFIX35_199756141 NAM.exe                                        61,491                03/01/2006

                 * Alarms were being sent to clients even though NONE is set in Filteralm.ini when
                 using non-english versions (1-99756141)

                 * NAM is only dispersing about 10+ alarms per second to attached NAC's (289755)


iFIX35_1145497751 NETDIAG.EXE                                   196,671               03/02/2006
                 SKT.DLL                                        188,473               07/07/2005
                 TCPDUMP.EXE                                    61,501                07/07/2005
                 TCPTASK.EXE                                    167,997               07/07/2005

                 * "Out Of Sync In Use" Error In Netdiag. (1-145497751)

                 * Netdiag diagnostic tool fails to return valid information for the Socket Tables. (1-
                 114583744)

                 * SocketRec and Trace Tabs in Netdiag are not functional. (1-99199716)

                 * Terminal Server clients cannot connect to the SCADA node after installing
                 iFIX35_SP1. (295207A)

                 * iFIX event file filled up with assertion messages like "assertion failed (ulLocalIpAddr
                 != 0) && (ulLocalIpAddr != INADDR_NONE)" (1-99234191)

                 * An iClient cannot connect thru the RAS client connection if iFIX was already running
                 on the RAS server (SCADA) when the RAS connection was made and the user was
                 somehow able to disable all of the local IP addresses. (277339)

                 * An iClient cannot connect thru the RAS client connection if iFIX was already running
                 on the RAS server (SCADA) when the RAS connection was made. (269268)


iFIX35_155232834 OSXLIB.dll                                     49,206                04/13/2005

                 * When running the FixbackgroundServer in the background and writing a value to an
                 iFIX tag in the schedule and 8.3 format is disabled on the file system, user receives a
                 "Server automation" error. (1-55232834)
iFIX35_189034472 ElectronicSignature.dll                           184,427               05/04/2005

                   * Workspace leaks memory when using WriteValue method with security enabled.(1-
                   89034472)

                   * Workspace would crash if Esignature Dialog was open and script in background
                   closes picture (293354)

                   * E-Sig writes values with improper precision.(285358)


iFIX35_191893246 HDAODBC.dll                                       262,231               07/11/2005

                   * Memory handling error in Historical ODBC driver. (1-91893246)

                   * Fix Dynamics Historical Data - memory leak (268129)

                   * Problem with select Distinct in query when using Historical Data ODBC driver
                   (271969)

iFIX35_122718147 IHHDA.dll                                          81,984               12/01/2004
                 IHHDA3.dll                                         81,986               12/01/2004
                 FIXTOOLS.dll                                       69,693               10/27/2004
                 FixHdaDll.dll                                      73,804               05/17/2004

                   * Expression Builder iHistorian tag browse fails to display the tags associated with iFix
                   collectors but not having a node name as prefix or missing a "." in their tag names. (1-
                   22718147)

                   * Running iHistorian 3.0, when iFIX connects to the Server to get data, a Client
                   Access License (CAL) should not be used. (133962334)

                   * The filtered errors.ini file doesn't work correctly for iHistorian errors and enables
                   iHistorian API timeout to be configurable. (277122)


iFIX35_292646      IOCNTRL.exe                                     57,406                05/27/2004

                   * D parameter for IOCNTRL does not delay driver when used with /S parameter.
                   (292646)


iFIX35_121207706 ALMLIB.DLL.dll                                    86,070                12/28/2004
                 ALM_SYNC.EXE                                      45,112                12/28/2004

                   * Dates are missing from alarm messages sent from an iFix node to a Fix32 node .
                   (1-21207706)

                   * The primary SCADA (of a redundancy pair) logged in user could not write to the
                   A_NALM field even though the alarm was properly acknowledged and A_NALM
                   updated on the backup SCADA.(270021)

                   * eda_alm_get_user_que returned internal alarm acknowledgement messages (1-
                   18722801)
iFIX35_147803764 RCPUP.EXE                                   380,980             12/22/2004
                 RCPDOWN.EXE                                 389,174             12/22/2004
                 RCP.EXE                                     643,122             12/22/2004

                 * Recipe upload stops execution script when encountering a database error.(1-
                 47803764)

                 * Recipe executed using shell command inside VBA takes long time to execute
                 because the dialog stays on for about 5 seconds for each recipe. (282412)


iFIX35_122517301 BackupRestoreDll.dll                        270,426             09/10/2004
                 BackupRestoreRes.dll NLS:English            86,016              09/11/2003
                 BackupRestore.exe                           32,847              09/11/2003

                 * Problem with Backup And Restore wizard when restoring individual file (122517301)

                 * New command line options for backup/restore.


iFIX35_SP1       FIX.EXE                                     208,946             04/19/2004
                 WSACTASK.EXE                                53,299              04/19/2004
                 CONMGR.exe                                  86,068              04/19/2004
                 SACDLL.DLL                                  188,465             04/19/2004
                 FixFileLinkDll.dll                          249,977             04/16/2004
                 FixPropDlg.dll                              364,622             04/15/2004
                 FixPropDlgRes.dll NLS:English               69,632              04/15/2004
                 NLSAPI.DLL                                  41,014              04/12/2004
                 LDBA.dll                                    299,061             04/12/2004
                 ExpertGlobal.fxg                            2,700,800           04/12/2004
                 Fix2DShapeDll.dll                           434,307             04/12/2004
                 FixShapeDll.dll                             110,707             04/12/2004
                 Fix2DShape.tlb                              30,128              04/12/2004
                 FixDataLinkDll.dll                          213,152             04/12/2004
                 ElectronicSignature.dll                     184,427             04/12/2004
                 Fix2DPenDll.dll                             430,239             04/08/2004
                 FixBackgroundServer.exe                     45,138              04/02/2004
                 FixEventDll.dll                             155,780             04/02/2004
                 OpcDataSystem.dll                           450,690             04/02/2004
                 Fix2DChartDll.dll                           360,611             04/02/2004
                 IHHDA.dll                                   86,080              04/01/2004
                 ALMLIB.DLL                                  86,070              03/31/2004
                 SUMQLIB.DLL                                 81,975              03/31/2004
                 CrossReference.exe                          610,385             03/31/2004
                 PictureConverterDll.dll                     491,616             03/31/2004
                 SecuritySynchronizerDLL.dll                 356,423             03/31/2004
                 SECMGR.dll                                  61,494              03/31/2004
                 SECCFG.exe                                  401,462             03/31/2004
                 ExpressionEditor.ocx                        258,138             03/31/2004
                 NAM.exe                                     61,491              03/24/2004
                 SKT.DLL                                     188,473             03/22/2004
                 TCPTASK.EXE                                 167,997             03/22/2004
                 FixDB32_DA.dll                              73,814              03/12/2004
                 Fix2DTextDll.dll                            290,959             03/12/2004
                 FixUserPreferencesResDll.dll NLS:English    49,288              03/12/2004
                 FIXERROR.DLL                                139,264             03/03/2004
PlugandSolve.fxg                           840,192           03/02/2004
DataBaseManager.exe                        663,635           03/01/2004
Fix2DGroupDll.dll                          282,769           02/23/2004
SEC_AF.DLL                                 16,384            02/19/2004
SecuritySynchronizerRes.dll                32,768            02/19/2004
AlarmSummaryOCX.ocx                        385,112           02/19/2004
FixSchedulerDll.dll                        520,326           02/19/2004
FixKeyMacroDll.dll                         65,641            02/19/2004
FixKeyMacroHandlerDll.dll                  77,943            02/19/2004
XDBA.dll                                   53,301            02/13/2004
AlmODBCConfig.exe                          159,836           02/04/2004
ALMODBC.exe                                118,847           02/04/2004
ExpertGlobals2.fxg                         1,610,752         02/04/2004
FixVariableDll.dll                         131,193           01/30/2004
Fix2DLegendDll.dll                         262,309           01/28/2004
Fix2DAxisDll.dll                           213,153           01/28/2004
FixAnimationDll.dll                        139,388           01/21/2004
FixAppDll.dll                              209,007           01/19/2004
FixPictureDll.dll                          438,402           01/19/2004
VisiconXData.ocx                           413,787           01/16/2004
FixDynamoSetServer.dll                     159,875           01/16/2004
FixGlobalsServer.dll                       159,871           01/16/2004
FixPictureServer.dll                       159,871           01/16/2004
FixSchedulerServer.dll                     159,875           01/16/2004
FixToolbarServer.dll                       159,871           01/16/2004
FixToolbarDll.dll                          348,290           01/16/2004
SIMUninstall.dll                           217,159           12/31/2003
SumqUpdate.exe                             24,645            12/10/2003
LOGIN.EXE                                  143,410           11/21/2003
Scripting.dll                              225,356           11/20/2003
QUE2LIB.DLL                                61,494            11/17/2003
Fix2DBitmapDll.dll                         192,659           11/10/2003
FixComponentDll.dll                        589,931           11/10/2003
Fix2DBitmap.tlb NLS:English                30,196            11/10/2003
FixControlContainerDll.dll                 327,843           09/26/2003
launch.exe                                 102,465           09/24/2003
ExpertGlobalRES.dll NLS:English            86,016            09/23/2003
FD_BDW.dll NLS:English                     28,672            09/17/2003
AppValidator.exe                           241,741           09/17/2003
AppValidatorRes.dll NLS:English            77,824            09/17/2003
launchres.dll NLS:English                  49,152            09/15/2003
StartupProfileMgrRes.dll NLS:English       40,960            09/12/2003
StartupProfileMgr.exe                      94,295            09/12/2003
BackupRestoreRes.dll NLS:English           86,016            09/11/2003
BackupRestoreDll.dll                       270,426           09/11/2003
BackupRestore.exe                          32,847            09/11/2003
TimerManager.dll                           57,426            09/08/2003
FixDB32_DARes.dll NLS:English              16,384            07/14/2003

* Can not switch to run between iFIX and Sample System (NLS) (279886)

* NLS Translation issues (279280)

* New command line options for backup/restore.
* The DA block's alarm mode switch's to NEVER from ACK, if no option is selected.
(283296)

* Database Manager only shows first 50 tags upon initial startup. (286760)

* DatabaseManager crash while opening on a machine with Windows Server 2003,
iFix 3.5, and iHistorian 2.0 installed. (283446)

* Database Manager could not modify values in certain fields (Init Alarm, etc.)
(286209)

* Database Manager could not load queries if the extension was capitalized (i.e.
*.QRY) (283131)

* E-Sig writes values with improper precision.(285358)

* Added a configuration setting to the .ini file to allow the user to specify the method
iFIX uses to open picture (290712)

* Cannot translate main window title, Detail Report window (Row Count) , Auto Report
Naming (Browse dir window - "Select a directory")

* Double bytes strings are not displayed correctly in Application Validator main dialog,
Comparison Detail Report dialog, and Print Preview dialog. (278413)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* Increased range of Help context ID values to support values between -
2,147,483,648 and -2,147,483,647 (290334)

* Some EGU values entered as scientific notation would trigger an "out of range" error
(283944B)

* Reentering the Color Expert dialog and then moving the focus off the Data Source
field causes the Color Threshold Table to be reset to the default if the data source
contains multiple tags.(286911)

* Object becomes invisible in run mode when animation is deleted from iFix Browser
Tree (283047)

* Inserting a datalink and setting a historical datasource, then get an error, and setting
a realtime datasource results in a WorkSpace crash. (286063)

* Workspace crash in PTimeDll when pictures containing charts were repeatedly
opened and closed and modified the time range of the charts. (287787)

* CrossReference tool doesn't use regional settings when saving a file as CSV.
(284883)

* FixBackgroundServer can't monitor running schedules, when run as a service.
(287836)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)
* RAMP block does not ramp down when low EGU is greater then hi EGU (288563)

* Unable to log into iFix when connection to primary domain controller is lost (267542)

* Security Configuration Modifications to support Classic Desktop. (287808)

* SAC would not start up for 20 seconds, when using a large database. (257584)

* sq_remove() error thrown when trying to modify an AIS block thru the
DatabaseManager. (257625)

* SAC slows down after changing 200 AO blocks current mode from AUTO to MANL.
(269990)

* Added "iBatch - Start iWorkInstruction Editor" to iFIX application security areas
(280371)

* Added command line parameter to suppress ORNG (OverRange) Alarm.(273507)

* SecuritySynchronizer /R removes RECIPE User Account from iFix Security
(281002)

* SecurityArea in Picture Properties will not allow you to assign a area name of 22B, if
you have already assigned a security area 22A to a previous picture (264728)

* iFIX - Windows security it was not possible to use a "." or "'" in the NT user name
(275124)

* Incorrect License Error: iFix has detected a serious problem please shutdown iFix.
(278711)

* OnTrue/OnFalse scheduled events fire on startup even when "Fire DataChange
Event on Startup" is deselected. (285575)

* While trending with T_DATA pens on Terminal Server, a random crash occurs.
(279198)

* Charts created using iFix automation interface get abnormal Width and Height
properties.(285999)

* ETR data doesn't show up correctly when changing the pen's Duration in Run
mode.(285687)

* Picture Conversion causing datalink font size to increase drastically. (288371)

* Object animations and data links not updating because of faulty hardware HAL or
BIOS. (269172)

* Foreground color animation doesn't work until the data source changes its value if
the picture is opened in Run mode. (282461)

* Leading and Trailing spaces for Text objects are being deleted. (283218)

* Setting a pen's fixed start time with only time in a chart group file causes a type
mismatch error when you apply the chart group file.(284209)
* Deleting animations with the Basic Animations dialog will result in the animation
being deleted from the object, but it remains in the system tree. (280962)

* Incorrect datalink format when migrating from fix 32 with a symbol from a tag group
(277426)

* Converting pictures from Fix32 and then trying to rotate objects in iFix would not
work correctly. (272793)

* Picture Converter was not converting a text object's visibility animation exact match
tolerance correctly. (273899)

* Picture converter does not convert expressions for visibility correctly when regional
setting is something other than English (272789)

* Picture converter does not make first line of command script a comment when that
first line is a comment. (262514)

* Picture converter doesn't convert chart's, when the pen's datasource doesn't exist.
(263527)

* If an object is nested in two groups, the size or position animations of that object do
not initialize correctly.(278574)

* If a grouped object has been highlighted and selected and then its group or itself
becomes invisible, the highlight of the object remains on the screen despite the object
being invisible.(277979)

* "invalid argument was encountered..." error while adding pen using WIN2003, iFIX
3.5 and iHistorian. (287196)

* Converted Fix32 datalink with taggroup symbol displays drop down combo box as
alpha-numberic instead of numeric in iFix Datalink Custom Dialog (287172)

* AlarmSummaryOCX not sorting correctly when sort order is set using VB
automation properties (285530)

* Error in setting timer interval, when using Italy regional settings & time separator of
':' (286249)

* Using Key Macros causes memory leak.(283043)

* A global variable's value, when animated to a database tag, is set to zero when
communication is lost to that tag. (284423)

* iFIX Workspace crash showing a memory access violation in PTimedll.dll. when
using a schedule and also picture initialization code to modify Pens in a chart on the
picture. (284593)

* In Build Dynamo Wizard, partial substitution for a dynamo property value does not
work properly if multiple occurences needed. (283379)

* AlarmODBC unable to handle schema name when defined in tablename when
writing to ORACLE (286150)

* Widened fields to support NLS strings (286795)
* Cannot edit a Chart Group File in run mode, using Chart Group Wizard. (285935)

* Opening or replacing a picture containing charts displaying ETR data or other real
time data is slow at iClient nodes. (281963)

* A historical trend chart shows a wrong value for the average over range if only part
of the chart is filled with data. (265305)

* 'High over range' value in charts is 0 if high is a negative number. (275225)

* Pen in Average Hist mode displays line after last known Good value in Chart
(273503)

* Corrected field truncations in Create Picture Wizard and Print Crystal report wizard
forms (285441)

* PictureConverter crash when using DDE links as source of Dynamic Coloring
Property (285824)

* Event firing was inconsistent when using picture caching. (278187)

* Opc datasources used in TagGroup datalinks do not re-connect when the OPC
Server is shutdown and re-started. (282205)

* ETR data doesn't display in charts when opening or replacing the containing
picture.(283572)

* VisiconX Data object would reset back to first record after a query. (284551)

* Workspace temporarily freezes when pictures directly access OPC data points
(285074)

* AlarmODBC.cfg become corrupt if tablename is changed to a shorter name
(284313)

* Security Issue (283386)

* Data Source gets changed from F_# to F_CV if tag does not exist prior to using
color expert (282956)

* Login.exe dialog closes when pressing ESC if opened by iFixScreenSaver (281132)

* When using the iFIX Screensaver, users are unable to change password if expired
(274065)

* F10 Key Macro does not work correctly (263027)

* Tolerance is not being saved using datalinks. (282037)

* Create Picture expert inserts incorrect sizes, using predefined configuration.
(282124)

* MouseUp events do not fire if the mouse button is released off the object. (281070)
* Picture Converter doesn't set MaxCharactersPerLine property to 80 for text objects
less than 80, also AutoSize is set to false. (279003)

* Picture converter corrupts Kanji characters, when converting small Push Buttons.
(278656)

* Table animation entries are not saved when using tag groups as the datasource on
a datalink caption animation. (279936)

* Fix.exe will hang on the shutdown waiting for third-party application which was
registered with iFix using FixRegisterConsole() helper function (277058)

* Cannot set Column widths to stay persistent for alarm summary in configure mode
(279311)

* Cannot translate Build Dynamo Wizard dialog (279274)

* Cannot translate "Use Pixel Coordinates" and "Use Percentage Coordinates"
checkboxes in "In Enter New Configuration Name" dialog (279273)

* Create Picture Wizard NLS: String ID in Tag property were missing in
btnDeleteConfig, pgStyles, pgSizes, btnSave control (278561)

* Continuous iFix Timers would occasionally fire 1 second early. (277455)

* Toolbar buttons are missing from the toolbar, during a mode switch. (276640)

* Double bytes strings are not displayed correctly in Server selection ComboBox and
Item browsing spread control. (NLS) (280803)

* AlmSum.exe was hogging 100% CPU for an indefinite period of time. (252294)

* Alarm Summary Sorting Problem when using LIN driver and there is no PDB and
WSACTASK being used (276687)

* Unable to remove user created alarm queue when started by background schedule
(276672)

* Alarm ODBC service did not log double bytes operator message correctly with
calling SendSignedOperatorMessage function when the message is over 82 bytes.
(282253 NLS)

* Double bytes strings are not displayed correctly in Startup Profile Mgr main dialog.
(278412)

* NAM is only dispersing about 10+ alarms per second to attached NAC's (289755)

* Enables iHistorian API timeout to be configurable (277122)

* Allows throttling of the frequency of alarm cycles for the thread that moves alarms
from the SAC queue to the Summary queue. (268948)

* An iClient cannot connect thru the RAS client connection if iFIX was already running
on the RAS server (SCADA) when the RAS connection was made. (269268)
iFIX 3.5 Japanese

iFIX35_1123523131FixTagGroupDll.dll                 155,769     07/17/2006
                 Fix2DBitmapDll.dll                 192,659     06/28/2006
                 Fix2DBitmap.tlb                    30,196      06/28/2006
                 FixBackgroundServer.exe            45,138      06/23/2006
                 OpcDataSystem.dll                  450,690     06/20/2006
                 FixEventDll.dll                    155,780     06/07/2006
                 FixAppDll.dll                      209,007     06/07/2006
                 FixPageDll.dll                     352,369     06/07/2006
                 PlugandSolve.fxg                   826,880     05/23/2006
                 FixLookupDll.dll                   172,166     05/23/2006
                 FileTree.ocx                       57,344      05/12/2006
                 WSACTASK.EXE                       53,299      05/08/2006
                 SACDLL.DLL                         192,561     05/08/2006
                 SecuritySynchronizerDLL.dll        356,423     04/27/2006
                 SECCFG.exe                         397,366     04/27/2006
                 SECMGR.dll                         65,590      04/27/2006
                 VisiconXData.ocx                   413,787     04/21/2006
                 FixChartDlg.dll                    499,792     04/04/2006
                 FixComponentDll.dll                589,931     03/28/2006
                 AlmSumMgr.DLL                      102,478     03/17/2006
                 AlarmSummaryOCX.ocx                385,112     03/17/2006
                 AlmSumMgrRes.dll                   20,480      03/17/2006
                 AlarmSummaryOCXRes.dll             65,654      03/17/2006
                 PictureConverterDll.dll            495,712     03/02/2006
                 Fix2DTextDll.dll                   290,959     03/02/2006
                 FIXERROR.DLL                       139,264     02/28/2006
                 Fix2DGroupDll.dll                  282,769     01/31/2006
                 Fix2DPenDll.dll                    430,239     01/27/2006
                 FIX.EXE                            208,946     12/28/2005
                 FIXSRV.exe                         65,589      12/28/2005
                 FixSchedulerDll.dll                520,326     12/28/2005
                 FixPictureDll.dll                  438,402     12/28/2005
                 VisiconXGrid.ocx                   114,779     12/25/2005
                 FixGlobalSysInfoDll.dll            143,491     11/15/2005
                 FCATABLE.DLL                       53,305      11/15/2005
                 LOGIN.EXE                          143,410     11/12/2005
                 ExpertGlobalRES.dll                86,016      11/11/2005
                 ALMODBC.exe                        118,847     11/01/2005
                 FactoryGlobalsRES.dll              61,440      09/30/2005
                 FixControlContainerDll.dll         331,939     08/18/2005
                 EnumerationsDLL.dll                28,672      08/15/2005
                 LDBA.dll                           299,061     08/15/2005
                 FactoryGlobals.fxg                 1,822,208   07/27/2005
                 CONMGR.exe                         69,684      07/25/2005
                 FixFileLinkDll.dll                 249,977     04/13/2005
                 WorkSpace.exe                      139,335     03/21/2005
                 FixUserPreferencesManagerRes.dll   20,480      03/16/2005
                 FixFormatDll.dll                   155,782     03/16/2005
                 FixFormat.tlb                      19,432      03/16/2005
                 FixUserPreferencesManagerDll.dll   135,290     03/16/2005
                 Scripting.dll                      225,356     03/16/2005
                 ValvesAnim.fds                     222,208     02/14/2005
                 FixBackgroundServerRes.dll         40,960      02/09/2005
                 FixPropDlg.dll                     364,622     02/09/2005
Tanks.fds                      269,824     02/09/2005
TanksAnim1.fds                 261,120     02/09/2005
TanksAnim2.fds                 271,872     02/09/2005
PipesAnim.fds                  194,560     02/09/2005
Pipes.fds                      220,672     02/09/2005
ExpertGlobal.fxg               2,712,576   02/09/2005
Fix2DAxisDll.dll               213,153     02/07/2005
Fix2DChartDll.dll              360,611     02/07/2005
Fix2DLegendDll.dll             262,309     02/07/2005
SearchReplace.dll              143,444     02/04/2005
FixDataLinkDll.dll             213,152     02/04/2005
iFixScreenSaver.scr            102,482     02/03/2005
TimerManager.dll               57,426      01/11/2005
FixTimerDll.dll                184,435     01/11/2005
Fix2DShapeDll.dll              434,307     12/28/2004
FixAnimationDll.dll            139,388     12/28/2004
FixLinearDll.dll               139,398     12/28/2004
Fix2DShape.tlb                 30,128      12/28/2004
FixComponentRes.dll            16,384      12/28/2004
SUMQLIB.DLL                    81,975      12/28/2004
SCU.exe                        618,547     12/28/2004
FixErrToHResult.dll            24,664      11/29/2004
WorkSpaceErrorsRes.dll         57,344      11/29/2004
FixShapeDll.dll                110,707     11/08/2004
FixAppServiceDll.dll           102,525     09/27/2004
OpcEdaDll.dll                  143,436     09/21/2004
AlmODBCConfig.exe              159,836     09/17/2004
FixControlContainerRes.dll     32,768      09/10/2004
QUE2LIB.DLL                    61,494      08/16/2004
FixUserPreferencesDll.dll      225,380     07/21/2004
FixPropDlgRes.dll              69,632      07/20/2004
launch.exe                     102,465     07/17/2004
OODBDll.dll                    225,360     07/17/2004
FixDataSystems.ocx             114,797     07/02/2004
OPC20iFIX.exe                  290,887     07/02/2004
WorkSpaceRes.dll               135,168     07/02/2004
FixUserPreferencesResDll.dll   49,288      06/10/2004
NLSAPI.DLL                     41,014      04/12/2004
CrossReference.exe             610,385     03/31/2004
ExpressionEditor.ocx           258,138     03/31/2004
SecuritySynchronizerRes.dll    32,768      02/19/2004
SEC_AF.DLL                     16,384      02/19/2004
FixKeyMacroDll.dll             65,641      02/19/2004
FixKeyMacroHandlerDll.dll      77,943      02/19/2004
XDBA.dll                       53,301      02/13/2004
ExpertGlobals2.fxg             1,610,752   02/04/2004
FixVariableDll.dll             131,193     01/30/2004
FixDynamoSetServer.dll         159,875     01/16/2004
FixGlobalsServer.dll           159,871     01/16/2004
FixPictureServer.dll           159,871     01/16/2004
FixSchedulerServer.dll         159,875     01/16/2004
FixToolbarServer.dll           159,871     01/16/2004
FixToolbarDll.dll              348,290     01/16/2004
SumqUpdate.exe                 24,645      12/10/2003
FD_BDW.dll                     28,672      09/17/2003
launchres.dll                                  49,152               09/15/2003

* Tag group resolution does not work properly if using the DefaultRefreshRate entry in
the Workspace.ini file and resolving tags before switching to Run mode. (1-
123523131)

* Bitmap Pushbutton stays stuck down, when pushbutton is invisible and user clicks
on area where pushbutton exists. (1-162154461)

* FixBackgroundServer events logged in the NT Event Viewer are not mapping with
descriptions.(1-144598020)

* Data in a picture never updates.(1-144898371)

* If Fire DataChange Event is disabled, then global user variable never triggers (1-
155223934)

* In the Chart Group File dialog, the file tree doesn't support Kanji Characters. (1-
112641852)

* Changing the DataSource for the last existing pen in a chart group file using the
Chart Group Wizard causes the values for color and limits to be reset. (1-111307898)

* Color animations using shared threshold table don't work properly if the same
threshold table is used by different pictures and these pictures are all opened in run
mode. (1-147175602)

* In the Chart Group File dialog, the file tree doesn't support Kanji Characters. (1-
112641852)

* It was not possible to use a "_" in a Windows User Name when running
SecuritySynchronizer (1-161443891)

* SQT blocks get stuck in the state of waiting for confirmation once their confirmations
get lost or never happen. (1-97202545A)

* VisiconX data control requires user with local administrative rights to connect to
OLE DB database. (1-110895991)

* Can't set the span interval to be 0 at chart configuration. (1-118948231)

* Workspace OPC client does not display OPC server's error string correctly (1-
126022821)

* Complex expressions fail after installation of sim 1-95976911 on Japanese iFix (1-
116459481)

* Log file and Alarm ODBC database don't capture each unsuccessful login attempt
(1-150615677)

* TX Block's comm. alarm doesn't show up on the AlarmSummary. (1-118034431)

* Alarm Summary OCX doesn't allow user to filter by the ACK column. (1-103547011)

* Picture Converter does not convert command comments correctly. (1-105643029)
* Cannot backspace when adding characters to a datalink. (1-115227146)

* Slow NT authentication for iFIX domain user (1-95990941C)

* Accelerator for Pushbutton doesn't work when Pushbutton is grouped (1-
116290921)

* Pictureconverter leaves unwanted '&' character in button! (1-116895871)

* Datalinks converted from FIX32 will highlight even though they were not
highlightable in the FIX32 picture.(1-127653268)

* Chart does not update correctly when changing tag group file that references t_data
(1-108273211)

* Automation error occurs when the DBDisconnect method is used in the
ExecuteComplete event of the VXDATA control. (1-119581251)

* iFix can't shut down ALMODBC and WSQLODC if they connect to a Sybase 9.xx
database on French OS. (1-105652516)

* Zooming a chart causes value ranges displayed on the Y axis of the chart to go
beyond its pens' EGU limits.(1-93670101)

* Encounter error when trying to modify schedule that has been set to run in
background (1-100502591)

* Unable to enter the Slash(/) from numeric pad in a Datalink. (1-112641841)*
Datalink doesn't support supressing character entry (1-116023901)

* Commandbutton no longer highlights in run mode after undoing a delete in
Configuration mode (1-115514116)

* Autoresize property of VisiconXData control doesn't resize columns after fetching
data.(1-113180591)

* Workspace intermittently disappears\access violation when running on RDP clients
(1-36959520)

* Advanced animation with TagGroup expressions containing complex expressions
no longer worked after installation of sim (1-100954501)

* Logging out of windows causes Fix service to goto stopping (1-100137961)

* ALT-TAB permissions not restored properly when using stacked logged in users (1-
109910701)

* "User Defined Fields" work differently for Alarms vs Events (1-106088924)

* Blinking property of an animated object using Dynamos is not working properly. (1-
99874598)

* Fonts stop changing horizontally in proportion to vertical changes if you change the
resolution of the screen while configuring a chart. (1-99237697)

* CommandButton script isn't recorded on basic animation dialog (1-106169060)
* Get error message "Expressions containing Historical items is not allowed" when
adding a pen that references to a iHistorian tag to a chart group file, if the pen name
matchs the pattern of "*.*.*.*.*". (1-71329801)

* Get error message "Secure Containment Detected Bad Control ..." and Workspace
crash while configuring a VisiconX data control to use Microsoft OLE DB Provider for
SQL Server as data provider, if more than 255 SQL servers are available in the
network.(1-99995157)

* Application crash when writing to A_ENAB field using EDA (1104354604)

* Alarm Acknowledge messages are being sent to the AA/DA block alarm areas
instead of the alarm areas for operator messages. (1-101856381)

* OnDataChange Event Does not Fire first time value changes (197333581)

* AcknowledgeAnAlarm can't acknowledge an alarm using a tag group symbol.(1-
95001621)

* Double byte dash "-" is not recognized for a object name in iFIX 3.5 Japanese. (1-
95976911)

* The GetFullName method of the ESignature object doesn't work if the Windows
user is a local user and the method is used to get a domain user's full name.(1-
52405328)

* MouseUp and MouseUpOffObject scripts do not work properly. (1-91893091)

* Find operation in workspace always sets dirty flag (1-101005761)

* AlmODBC crashes with STK Userfield and STK alm extension field being truncated
(142562201)

* When selecting text in a datalink that has "Leading Spaces" enabled, the text
highlight strips of the leading spaces (1-37828101)

* Workspace application crash when closing a picture that was created on a machine
with FIXDesktop installed and run on a machine without FIXDesktop installed. (1-
94231958)

* The Workspace application object does not properly accept negative values for the
TOP and LEFT properties. (1-90865926)

* Alarming-suspended/resumed messages are being sent to the AA/DA block alarm
areas instead of the alarm areas for operator messages. (1-91722901)



* Can't type in a space in editing mode of the standard text tool after installing
iFIX35_281537 or a later workspace SIM and having selected the Remove Leading
and Trailing Spaces option for text in the User Preferences.(1-83444001)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)
* Workspace crashes when switching between pictures using ReplacePicture
subroutine, if picture caching is enabled and the new picture names passed in
ReplacePicture are"xxxxx.grf" and "xxxxx.grf "(i.e. file names with trailing whitespace
characters).                                (288907)

* Read-write access to the security path is needed in order to use the security
configurator. (1-83519101)

* After installing iFIX35_294859, when Workspace is started, it is not restored at the
size that it was last closed. (1-85376901)

* Find function in VBE of Workspace does not handle inputting double byte characters
correctly. (1-79830201)

* Precision adjustment for a float-value datalink causes the value sometimes being
displayed with a different rounding from the Curr Value field in the Database
Manager. (1-43322301)

* The Timer Cursor shows no data for the last sample using SetPenDataArray
method. (1-79315501)

* FIXbackgroundServer Event ID 103, 107, 108, 111 messages appear erroneously in
the Event log (266950)

* Custom color palettes do not work using tank, valve and pipe dynamo's. (272910)

* Ramp Expert doesn't set the value to the low/high limit, when the new value
exceedes the limit.(270674)

* Some automation subroutines (AcknowledgeAnAlarm, RampValue, SetManual,
SetAuto, ToggleManual) change the values of parameters passed to them.(273349)

* The WriteValue VBA method sent an incorrectly formatted operator message if the
data source had a "%" in it.             (264630)

* Added Interval Field to Chart Group Wizard (274023)

* Chart group methods are not accessible in the background task.(272466)

* The Visibility Expert adds lookup levels in the descending order of input values
when configuring, which causes visibility animations to be converted incorrectly as the
Web Converter is expecting all lookup levels in the ascending order of input
values.(276784)

* A visibility animation created with a range, will not be edited correctly with the
visibility expert. (274718)

* FixBackgroundServer can't monitor running schedules, when run as a service on
WIN2000. (287836)

* Custom color palettes don't work in a pen's color. (262282)

* After opening and closing the VBA property window, a pen can't be deleted from a
chart properly. (268805)
* Using ModifyColumnLength VBA method to change the Chart's legend column
length, causes the legend text to grow and stretch. (271284)

* VisiconX Grid time field displays both system date and time. (279234)

* Can't open a .csv file by using VisiconX and OleDB provider for ODBC. (259313)

* Find and Replace messes up script.(273672)

* Changing the Object Name and Description on the Basic Animation Dialog does not
dirty the containing picture. (277534)

* Close and Save method of Document(s) allow document(s) to be saved during
mode switch, which sometimes causes the document(s) to be corrupted.(267849)

* FixBackground Server crashes while running iFIX as a service. (272155)

* "Invalid Handle" message is given when a "Delete All" is executed on the Alarm
Summary OCX.(260452)

* Datalink raw format resets when changing the datasource. (264403)

* The current alarm index would intermittedly get stuck on last alarm acknowledge
when scroll bars are enabled and ACK/PRIORITY descending. (272349)

* Alarm Summary's status bar prints black when using XP themes. (278401)

* iFixScreenSaver will hang if Login.exe is already opened (295038)

* AlmODBC crash when STK Userfield lengths exceed 79 characters and also STK
alarm extension field was being truncated. (142562201)

* TagGroup expressions containing complex expressions cause high message rate
(264443)

* Initial update of datalink values is slow when first opening a picture (1-19756822)

* Users get 'Invalid qualifier' error on data entry form after installing iFIX35_292319B
SIM.(1-42578390)

* Daily schedules running in the background skip firing every other day and double
firing at midnight when using New Zealand regional settings and time zone.(263814)

* Using the ToggleDigitalPoint expert and then running the Tag Group Editor (Get
Symbols From Picture), will not get all of the Tag Group Symbols that are eligible in
the picture.(274890)

* In datalink and some animation experts, if the data source is a single source, not an
expression, the tolerance gets reset to default.(276128)

* Remove Level automation method causes a memory leak. (273677)

* Dashed lines are printed as solid. (272979)
* Bitmap Pushbutton stays stuck down, when using a mouse down event that
launches a modal dialog. (278520)

* Tooltip would intermittedly flash on select PC's (266730)

* Can't get a property name correctly using the property dispatch ID, if the dispatch ID
is zero.(272807)

* When implementing the same VBA procedure in a picture and in a group (of objects
contained) as well, the VBA procedure was disabled at the picture level after
renaming the group. (275682)

* When using automation SelectObject method to select multiple objects, the color
property was only being set on the last selected object. (279699)

* MDI->EV->DA chain goes off-scan on iFIX re-start or database reload. (269246)

* More than 20 consecutive calls                 to   FixGetUserInfo     would    return
"smo_replace_profile: bad index". (273300)

* Tag description not being written to RDBM from AlarmODBC (268799)

* When using the sa_almmsg_cb and passing in the timestamp for the alarm, the
TimeIn on view nodes would not get updated if there was an existing alarm. (277780)

* AAD file cannot be accessed from VIEW node. (269866)

* Random "iFIX Detected a Serious Problem. Please Shut Down Restart iFIX" errors
(1-52135901)

* Text object has no space in between multiple lines of text. (1-34485756)

* Pressing the CTRL and then the TAB keys repeatedly causes the Workspace to
consume 100% CPU usage and makes the workspace unresponsive. (141913801)

* Some methods of Alarm Summary cause memory leak. (266745)

* Datalinks not retaining\displaying leading\trailing spaces when writing to TX Blocks
(1-37828101)

* After choosing a color from a custom color set, a foreground color animation
configured with the Foreground Color Expert cannot retain any new color selection
from the system default color set. (1-32449601)

* Deleting the Enabled animation of a push button from the system tree causes the
push button disabled.(1-34153301)

* Applying a chart group file that has an interval greater than 1 minute to an iFix chart
results in an error message "FIX2DPen invalid parameter".(1-32281101)

* Turning on data system prematurely causes some animations to work incorrectly.(1-
27285016)

* Unusual Behavior when pictures are saved outside the PIC directory and switched
to Run mode (1-32486401)
* Added a configuration setting to the .ini file to allow the user to specify the method
iFIX uses to open picture (290712)

* Animation data error doesn't work properly after installing iFIX35_SP1. (1-
32916701)

* The "Blink on New Alarm" checkbox will not stay checked the datasource is a tag
group and the animation is opened using the wizard. (132796801)

* The a F_CV value on RealTime Chart will cause the chart to blank and restart when
duration is changed (294512)

* The basic animation table settings are lost when using an undefined user global
variable as the data source in the basic animation dialogs.(1-21409801)

* Data Type mismatch error on automation method "AcknowledgeAllAlarms" when the
picture contains an object with an animation with a datasource equal to a constant.
(1-25827301)

* An event based schedule doesn't fire if it is using the System.CurrentTime property
in its data source and run in the background.(294413)

* Shape animation is no longer valid after a global Search and Replace (292319)

* Additional OPC Refresh configuration option. (119237501)

* Increased the maximum limit of the number of records to read from the User queue
before writing to the relational database for AlarmODBC. (280263)

* The Address fields in Device Control (DC) block does not accept syntax for OPC
Client driver. (290932)

* Digital Input block's alarm for the Close state, goes away on database reload.
(122925753)

* The MS Forms 2.0 Textbox control was not scrolling text properly. (292395)

* Workspace.exe in the SCU tasklist did not startup in the mode indicated by the
mode settings.(294859)

* Find & Replace failed with access exception (119739601)

* SetTimeCursorTime Method does not work properly.(292789)

* When using flexdata and thousands of alarms, the AlarmSummaryOCX was slow in
responding to subsequent Workspace user actions after the AlarmSummaryOCX was
initially opened in Workspace Run. (293322)

* An iHistorian Calculator Collector stop\re-start in the iHistorian Administrator would
cause the tag calculation to fail, "Object is not connected to the server". (290840)

* Down arrow key does not work if first datalink is invisible. (293910)

* Grouped Datalink sourced from a Global variable displays the stale data value if the
picture cache is enabled. (291986)
* SetTimeCursorTime Method does not work properly.(292789)

* Cannot de-select "Remove Trailing and Leading Spaces" for text objects in User
Preferences.(17410327)

* The animation table settings are lost when Using a undefined User Global Variable
in the Advanced Animation dialog. (288314)

* AlmODBC doesn't insert multiple records into SQL. (292290)

* Duplicate Logical Nodename error when using Launch with command line
parmeters /s /l /n (288317)

* License Error - iFIX has detected a serious problem. Please shutdown and restart
iFIX" generated when there was an invalid path or entry in the task list. (292781)

* Can not switch to run between iFIX and Sample System (NLS) (279886)

* NLS Translation issues (279280)

* AcknowledgeAllAlarms subroutine doesn't work for tag groups after migrating the
picture created with iFIX 2.6 to iFIX 3.5.(293393)

* Nudge settings not reflecting settings from the Fixuserpreferences.ini (294535)

* Added the ability to suppress RANGE, UNDER RANGE, and NODATA alarms.
(290732)

* Fix Data System OCX not working (294185)

* Spacing between lines in a multiple-line datalink changes when the last few lines are
blank.(292544)

* XYHistTest Method returns error (292899)

* Dead lock condition using OPCEDA asynchronously. (283840)

* OpciFix OPC server doesn't browse STK tags. (290388)

* Pictures are resized when the workspace opens after it was last closed in the
minimized or restored state.(292398)

* Duplication turns PushButton to FixOLEControl.(292381)

* Legend object get_LegendHeadingLine() is not returning Interval column name and
GetColumnInfo() method is returning empty column name.(294667)

* If the AlarmSummaryOCX is scrolled, and a new alarm comes in, the visible viewing
area is reset to the new end rows. (292610)

* SecuritySynchronizer crashes when logging oversized message.(292169)

* Added automation properties to support infoAgent 2.0 (293871)
* Clicking the Cancel button when configuring a schedule item causes some scripts
removed if the beginning of the names are the same for the timer and event schedule
items and the underscore character is used.(290611)

* Text object doesn't go to the next line when exceeding MaxCharactersPerLine.
(291537)

* Duplication of dynamo generates objects with same name.(290257)

* Applying a chart group file to a chart sometimes doesn't set EGU limits
correctly.(288261)

* VisiconX shows no data in the VisiconX Grid when opening a picture that has been
cached. (289291)

* Build Dynamo Wizard: Partial substitution for a dynamo property value does not
work properly if there is a decimal point in the animation data source.(290242)

* Animations don't work using constant numerical datasources. (288963)

* DBASRV inadvertently starts running when during iFIX startup. (291346)

* When using a long datatype datablock from an OPC server as the datasource in a
datalink, the value was different in the iFIX database and the datalink by 1. (292059)

* Alarms with the same Time In and Time Last are sometimes displayed in a different
order depending on the Sort Key. (289889)

* Script events created with the VBA FindReplaceInObject automation method do not
fire. (287883)

* Using NT security with iFix security, password expires error message occurs, even
though the user account is set to password never expires. (288005)

* Animated Text object caption doesn't work, if the datasource is static text. (286466)

* A chart does not display axes and grids after setting its current pen to be not
visible.(287462)

* Bad event message being sent to alarm typers, when user tries to set alarm values
of block higher then Egu Hi (290559)

* VBA Errors on install when installing to a machine with XP machine that has
sublanguages installed. (289295)

* Color animation's table resets when leaving expression editor, using the color
experts. (290442)

* Group click events do not fire when clicking on a control with no events. (285712)

* RetrieveTagGroupVariable method leaks memory.(287253)

* Acknowledged Alarms were being dropped from alarm synchronization (288698)

* The property name gets stripped from animation data source when reentering the
animation dialog, if the data source is an OLE object's default property.(287357)
iFIX35_1112501941 VDBA.DLL                                    41,014              11/28/2005
                 EDA.dll                                       86,067             10/24/2005
                 DDECLNT.EXE                                   188,471            10/24/2005
                 etr.gov                                       978                08/15/2005
                 pa.gov                                        2,112              08/15/2005
                 tr.gov                                        978                08/15/2005
                 hs.gov                                        978                08/15/2005
                 ev.gov                                        978                08/15/2005
                 dt.gov                                        870                08/15/2005
                 DataBaseManager.exe                           663,635            07/27/2005
                 FixDB32_DO.dll                                57,430             07/14/2005
                 FixDB32_AO.dll                                65,622             07/14/2005
                 FixDB32_DI.dll                                65,622             09/07/2004
                 FixDB32_DR.dll                                53,334             09/07/2004
                 FixDB32_DA.dll                                73,814             09/07/2004
                 FixDB32_BLRes.dll                             16,495             06/14/2004
                 FixDB32_DIRes.dll                             16,495             06/14/2004
                 FixDB32_DORes.dll                             16,495             06/14/2004
                 FixDB32_DARes.dll                             16,384             06/14/2004
                 FixDB32_DRRes.dll                             12,288             06/14/2004
                 DatabaseManagerRes.dll                        204,800            06/10/2004

                 * iFix Database Toolkit gives it 4293 string in alarm status when the alarm is COMM
                 (1-112501941)

                 * NETDDE cannot get remote Excel data in view on Win 2000 machine. (1-
                 115030351)

                 * Alarm Extension fields not being exported for some blocks (1-103966121)

                 * Low EGU limit of 0.000001 causes error on import of database (187182953)

                 * Event messaging no longer works on AO and DO blocks (186558030)

                 * Database Manager will not start on machines with large registry files (1-86803501)

                 * The Database Management spreadsheet displays incorrectly if a tag is imported that
                 has double byte and regular characters that exceed the length limit of a field. (1-
                 79830256)

                 * PDB queries not working when there is no SORT order criteria (1-19734301)

                 * Open/Close labels do not change case on Digital blocks (293103)

                 * DB Manager EXPORT problem with Large Loadable Block (292393)

                 * Database Manager doesn't allow lowercase for digital and boolean block
                 labels.(277527)

                 * Importing a CSV file into Database Manager that contains an equal sign(=) in the
                 description field, without single quotes surrounding it, causes the block to import
                 incorrectly without error.(269981)
                * The DA block's alarm mode switch's to NEVER from ACK, if no option is selected.
                (283296)

                * Database Manager only shows first 50 tags upon initial startup. (286760)

                * DatabaseManager crash while opening on a machine with Windows Server 2003,
                iFix 3.5, and iHistorian 2.0 installed. (283446)

                * Database Manager could not modify values in certain fields (Init Alarm, etc.)
                (286209)

                * Database Manager could not load queries if the extension was capitalized (i.e.
                *.QRY) (283131)


iFIX35_1174403491NAC.exe                                     53,299              08/14/2006
                 NA_ANALZ.dll                                53,308              06/03/2004

                * Alarms no longer synchronize properly on some redundant systems after installing
                iFIX35_288678. (1-174403491)

                * Login message initiated on Client is not sent to backup SCADA node, when client is
                looking at Backup SCADA as active node. (288678)


iFIX35_1103329301 VIEW.EXE                                   1,634,370           05/12/2006
                 WSProxy.EXE                                 106,560             09/01/2004
                 DRAW.EXE                                    2,404,418           08/11/2004
                 SUMQLIB_FIX32.DLL                           77,895              08/11/2004
                 HTD.EXE                                     1,060,928           08/11/2004

                * Thousands separators are placed incorrectly for some negative values of FIX
                Desktop datalinks. (1-103329301)

                * When trying to open a .grf picture through WSProxy and the picture does not exist,
                "Untitled1.grf" was not closed in WorkSpace on NLS product versions. (1-24827620)

                * Reinitialize File Dates for iFix35_294534 for NLS. Also new SIM numbering scheme
                for Desktop.

                * Buffer overrun when using View.exe in Async mode. (294534)

                * Alarms indicated with area "ALL" were not being displayed in the Alarm Summary in
                View, when the AlarmSummaryOCX was set up to filter area "A" only. (292441)


iFIX35_199756141 NAM.exe                                     61,491              03/01/2006

                * Alarms were being sent to clients even though NONE is set in Filteralm.ini when
                using non-english versions (1-99756141)

                * NAM is only dispersing about 10+ alarms per second to attached NAC's (289755)


iFIX35_1145497751 NETDIAG.EXE                                196,671             03/02/2006
                 SKT.DLL                                     188,473             07/07/2005
                   TCPDUMP.EXE                                    61,501                07/07/2005
                   TCPTASK.EXE                                    167,997               07/07/2005

                   * "Out Of Sync In Use" Error In Netdiag. (1-145497751)

                   * Netdiag diagnostic tool fails to return valid information for the Socket Tables. (1-
                   114583744)

                   * SocketRec and Trace Tabs in Netdiag are not functional. (1-99199716)

                   * Terminal Server clients cannot connect to the SCADA node after installing
                   iFIX35_SP1. (295207A)

                   * iFIX event file filled up with assertion messages like "assertion failed (ulLocalIpAddr
                   != 0) && (ulLocalIpAddr != INADDR_NONE)" (1-99234191)

                   * An iClient cannot connect thru the RAS client connection if iFIX was already running
                   on the RAS server (SCADA) when the RAS connection was made and the user was
                   somehow able to disable all of the local IP addresses. (277339)

                   * An iClient cannot connect thru the RAS client connection if iFIX was already running
                   on the RAS server (SCADA) when the RAS connection was made. (269268)


iFIX35_155232834 OSXLIB.dll                                       49,206                04/13/2005

                   * When running the FixbackgroundServer in the background and writing a value to an
                   iFIX tag in the schedule and 8.3 format is disabled on the file system, user receives a
                   "Server automation" error. (1-55232834)


iFIX35_189034472 ElectronicSignature.dll                          184,427               05/04/2005

                   * Workspace leaks memory when using WriteValue method with security enabled.(1-
                   89034472)

                   * Workspace would crash if Esignature Dialog was open and script in background
                   closes picture (293354)

                   * E-Sig writes values with improper precision.(285358)


iFIX35_191893246 HDAODBC.dll                                      262,231               07/11/2005

                   * Memory handling error in Historical ODBC driver. (1-91893246)

                   * Fix Dynamics Historical Data - memory leak (268129)

                   * Problem with select Distinct in query when using Historical Data ODBC driver
                   (271969)


iFIX35_122718147 IHHDA.dll                                         81,984               12/01/2004
                 IHHDA3.dll                                        81,986               12/01/2004
                 FIXTOOLS.dll                                      69,693               10/27/2004
                 FixHdaDll.dll                                     73,804               05/17/2004
                 * Expression Builder iHistorian tag browse fails to display the tags associated with iFix
                 collectors but not having a node name as prefix or missing a "." in their tag names. (1-
                 22718147)

                 * Running iHistorian 3.0, when iFIX connects to the Server to get data, a Client
                 Access License (CAL) should not be used. (133962334)

                 * The filtered errors.ini file doesn't work correctly for iHistorian errors and enables
                 iHistorian API timeout to be configurable. (277122)


iFIX35_292646    IOCNTRL.exe                                     57,406                05/27/2004

                 * D parameter for IOCNTRL does not delay driver when used with /S parameter.
                 (292646)


iFIX35_121207706 ALMLIB.DLL.dll                                  86,070                12/28/2004
                 ALM_SYNC.EXE                                    45,112                12/28/2004

                 * Dates are missing from alarm messages sent from an iFix node to a Fix32 node .
                 (1-21207706)

                 * The primary SCADA (of a redundancy pair) logged in user could not write to the
                 A_NALM field even though the alarm was properly acknowledged and A_NALM
                 updated on the backup SCADA.(270021)

                 * eda_alm_get_user_que returned internal alarm acknowledgement messages (1-
                 18722801)


iFIX35_147803764 RCPUP.EXE                                       380,980               12/22/2004
                 RCPDOWN.EXE                                     389,174               12/22/2004
                 RCP.EXE                                         643,122               12/22/2004

                 * Recipe upload stops execution script when encountering a database error.(1-
                 47803764)

                 * Recipe executed using shell command inside VBA takes long time to execute
                 because the dialog stays on for about 5 seconds for each recipe. (282412)


iFIX35_122517301 BackupRestoreDll.dll                            270,426               09/10/2004
                 BackupRestoreRes.dll NLS:English                86,016                09/11/2003
                 BackupRestore.exe                               32,847                09/11/2003

                 * Problem with Backup And Restore wizard when restoring individual file (122517301)

                 * New command line options for backup/restore.


iFIX35_SP1       FIX.EXE                                          208,946              04/19/2004
                 WSACTASK.EXE                                     53,299               04/19/2004
                 CONMGR.exe                                       86,068               04/19/2004
                 SACDLL.DLL                                       188,465              04/19/2004
FixFileLinkDll.dll                         249,977     04/16/2004
FixPropDlg.dll                             364,622     04/15/2004
FixPropDlgRes.dll NLS:English              69,632      04/15/2004
NLSAPI.DLL                                 41,014      04/12/2004
LDBA.dll                                   299,061     04/12/2004
ExpertGlobal.fxg                           2,700,800   04/12/2004
Fix2DShapeDll.dll                          434,307     04/12/2004
FixShapeDll.dll                            110,707     04/12/2004
Fix2DShape.tlb                             30,128      04/12/2004
FixDataLinkDll.dll                         213,152     04/12/2004
ElectronicSignature.dll                    184,427     04/12/2004
Fix2DPenDll.dll                            430,239     04/08/2004
FixBackgroundServer.exe                    45,138      04/02/2004
FixEventDll.dll                            155,780     04/02/2004
OpcDataSystem.dll                          450,690     04/02/2004
Fix2DChartDll.dll                          360,611     04/02/2004
IHHDA.dll                                  86,080      04/01/2004
ALMLIB.DLL                                 86,070      03/31/2004
SUMQLIB.DLL                                81,975      03/31/2004
CrossReference.exe                         610,385     03/31/2004
PictureConverterDll.dll                    491,616     03/31/2004
SecuritySynchronizerDLL.dll                356,423     03/31/2004
SECMGR.dll                                 61,494      03/31/2004
SECCFG.exe                                 401,462     03/31/2004
ExpressionEditor.ocx                       258,138     03/31/2004
NAM.exe                                    61,491      03/24/2004
SKT.DLL                                    188,473     03/22/2004
TCPTASK.EXE                                167,997     03/22/2004
FixDB32_DA.dll                             73,814      03/12/2004
Fix2DTextDll.dll                           290,959     03/12/2004
FixUserPreferencesResDll.dll NLS:English   49,288      03/12/2004
FIXERROR.DLL                               139,264     03/03/2004
PlugandSolve.fxg                           840,192     03/02/2004
DataBaseManager.exe                        663,635     03/01/2004
Fix2DGroupDll.dll                          282,769     02/23/2004
SEC_AF.DLL                                 16,384      02/19/2004
SecuritySynchronizerRes.dll                32,768      02/19/2004
AlarmSummaryOCX.ocx                        385,112     02/19/2004
FixSchedulerDll.dll                        520,326     02/19/2004
FixKeyMacroDll.dll                         65,641      02/19/2004
FixKeyMacroHandlerDll.dll                  77,943      02/19/2004
XDBA.dll                                   53,301      02/13/2004
AlmODBCConfig.exe                          159,836     02/04/2004
ALMODBC.exe                                118,847     02/04/2004
ExpertGlobals2.fxg                         1,610,752   02/04/2004
FixVariableDll.dll                         131,193     01/30/2004
Fix2DLegendDll.dll                         262,309     01/28/2004
Fix2DAxisDll.dll                           213,153     01/28/2004
FixAnimationDll.dll                        139,388     01/21/2004
FixAppDll.dll                              209,007     01/19/2004
FixPictureDll.dll                          438,402     01/19/2004
VisiconXData.ocx                           413,787     01/16/2004
FixDynamoSetServer.dll                     159,875     01/16/2004
FixGlobalsServer.dll                       159,871     01/16/2004
FixPictureServer.dll                       159,871     01/16/2004
FixSchedulerServer.dll                     159,875     01/16/2004
FixToolbarServer.dll                            159,871              01/16/2004
FixToolbarDll.dll                               348,290              01/16/2004
SIMUninstall.dll                                217,159              12/31/2003
SumqUpdate.exe                                  24,645               12/10/2003
LOGIN.EXE                                       143,410              11/21/2003
Scripting.dll                                   225,356              11/20/2003
QUE2LIB.DLL                                     61,494               11/17/2003
Fix2DBitmapDll.dll                              192,659              11/10/2003
FixComponentDll.dll                             589,931              11/10/2003
Fix2DBitmap.tlb NLS:English                     30,196               11/10/2003
FixControlContainerDll.dll                      327,843              09/26/2003
launch.exe                                      102,465              09/24/2003
ExpertGlobalRES.dll NLS:English                 86,016               09/23/2003
FD_BDW.dll NLS:English                          28,672               09/17/2003
AppValidator.exe                                241,741              09/17/2003
AppValidatorRes.dll NLS:English                 77,824               09/17/2003
launchres.dll NLS:English                       49,152               09/15/2003
StartupProfileMgrRes.dll NLS:English            40,960               09/12/2003
StartupProfileMgr.exe                           94,295               09/12/2003
BackupRestoreRes.dll NLS:English                86,016               09/11/2003
BackupRestoreDll.dll                            270,426              09/11/2003
BackupRestore.exe                               32,847               09/11/2003
TimerManager.dll                                57,426               09/08/2003
FixDB32_DARes.dll NLS:English                   16,384               07/14/2003

* Can not switch to run between iFIX and Sample System (NLS) (279886)

* NLS Translation issues (279280)

* New command line options for backup/restore.

* The DA block's alarm mode switch's to NEVER from ACK, if no option is selected.
(283296)

* Database Manager only shows first 50 tags upon initial startup. (286760)

* DatabaseManager crash while opening on a machine with Windows Server 2003,
iFix 3.5, and iHistorian 2.0 installed. (283446)

* Database Manager could not modify values in certain fields (Init Alarm, etc.)
(286209)

* Database Manager could not load queries if the extension was capitalized (i.e.
*.QRY) (283131)

* E-Sig writes values with improper precision.(285358)

* Added a configuration setting to the .ini file to allow the user to specify the method
iFIX uses to open picture (290712)

* Cannot translate main window title, Detail Report window (Row Count) , Auto Report
Naming (Browse dir window - "Select a directory")

* Double bytes strings are not displayed correctly in Application Validator main dialog,
Comparison Detail Report dialog, and Print Preview dialog. (278413)
* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* Increased range of Help context ID values to support values between -
2,147,483,648 and -2,147,483,647 (290334)

* Some EGU values entered as scientific notation would trigger an "out of range" error
(283944B)

* Reentering the Color Expert dialog and then moving the focus off the Data Source
field causes the Color Threshold Table to be reset to the default if the data source
contains multiple tags.(286911)

* Object becomes invisible in run mode when animation is deleted from iFix Browser
Tree (283047)

* Inserting a datalink and setting a historical datasource, then get an error, and setting
a realtime datasource results in a WorkSpace crash. (286063)

* Workspace crash in PTimeDll when pictures containing charts were repeatedly
opened and closed and modified the time range of the charts. (287787)

* CrossReference tool doesn't use regional settings when saving a file as CSV.
(284883)

* FixBackgroundServer can't monitor running schedules, when run as a service.
(287836)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* RAMP block does not ramp down when low EGU is greater then hi EGU (288563)

* Unable to log into iFix when connection to primary domain controller is lost (267542)

* Security Configuration Modifications to support Classic Desktop. (287808)

* SAC would not start up for 20 seconds, when using a large database. (257584)

* sq_remove() error thrown when trying to modify an AIS block thru the
DatabaseManager. (257625)

* SAC slows down after changing 200 AO blocks current mode from AUTO to MANL.
(269990)

* Added "iBatch - Start iWorkInstruction Editor" to iFIX application security areas
(280371)

* Added command line parameter to suppress ORNG (OverRange) Alarm.(273507)

* SecuritySynchronizer /R removes RECIPE User Account from iFix Security
(281002)

* SecurityArea in Picture Properties will not allow you to assign a area name of 22B, if
you have already assigned a security area 22A to a previous picture (264728)
* iFIX - Windows security it was not possible to use a "." or "'" in the NT user name
(275124)

* Incorrect License Error: iFix has detected a serious problem please shutdown iFix.
(278711)

* OnTrue/OnFalse scheduled events fire on startup even when "Fire DataChange
Event on Startup" is deselected. (285575)

* While trending with T_DATA pens on Terminal Server, a random crash occurs.
(279198)

* Charts created using iFix automation interface get abnormal Width and Height
properties.(285999)

* ETR data doesn't show up correctly when changing the pen's Duration in Run
mode.(285687)

* Picture Conversion causing datalink font size to increase drastically. (288371)

* Object animations and data links not updating because of faulty hardware HAL or
BIOS. (269172)

* Foreground color animation doesn't work until the data source changes its value if
the picture is opened in Run mode. (282461)

* Leading and Trailing spaces for Text objects are being deleted. (283218)

* Setting a pen's fixed start time with only time in a chart group file causes a type
mismatch error when you apply the chart group file.(284209)

* Deleting animations with the Basic Animations dialog will result in the animation
being deleted from the object, but it remains in the system tree. (280962)

* Incorrect datalink format when migrating from fix 32 with a symbol from a tag group
(277426)

* Converting pictures from Fix32 and then trying to rotate objects in iFix would not
work correctly. (272793)

* Picture Converter was not converting a text object's visibility animation exact match
tolerance correctly. (273899)

* Picture converter does not convert expressions for visibility correctly when regional
setting is something other than English (272789)

* Picture converter does not make first line of command script a comment when that
first line is a comment. (262514)

* Picture converter doesn't convert chart's, when the pen's datasource doesn't exist.
(263527)

* If an object is nested in two groups, the size or position animations of that object do
not initialize correctly.(278574)
* If a grouped object has been highlighted and selected and then its group or itself
becomes invisible, the highlight of the object remains on the screen despite the object
being invisible.(277979)

* "invalid argument was encountered..." error while adding pen using WIN2003, iFIX
3.5 and iHistorian. (287196)

* Converted Fix32 datalink with taggroup symbol displays drop down combo box as
alpha-numberic instead of numeric in iFix Datalink Custom Dialog (287172)

* AlarmSummaryOCX not sorting correctly when sort order is set using VB
automation properties (285530)

* Error in setting timer interval, when using Italy regional settings & time separator of
':' (286249)

* Using Key Macros causes memory leak.(283043)

* A global variable's value, when animated to a database tag, is set to zero when
communication is lost to that tag. (284423)

* iFIX Workspace crash showing a memory access violation in PTimedll.dll. when
using a schedule and also picture initialization code to modify Pens in a chart on the
picture. (284593)

* In Build Dynamo Wizard, partial substitution for a dynamo property value does not
work properly if multiple occurences needed. (283379)

* AlarmODBC unable to handle schema name when defined in tablename when
writing to ORACLE (286150)

* Widened fields to support NLS strings (286795)

* Cannot edit a Chart Group File in run mode, using Chart Group Wizard. (285935)

* Opening or replacing a picture containing charts displaying ETR data or other real
time data is slow at iClient nodes. (281963)

* A historical trend chart shows a wrong value for the average over range if only part
of the chart is filled with data. (265305)

* 'High over range' value in charts is 0 if high is a negative number. (275225)

* Pen in Average Hist mode displays line after last known Good value in Chart
(273503)

* Corrected field truncations in Create Picture Wizard and Print Crystal report wizard
forms (285441)

* PictureConverter crash when using DDE links as source of Dynamic Coloring
Property (285824)

* Event firing was inconsistent when using picture caching. (278187)

* Opc datasources used in TagGroup datalinks do not re-connect when the OPC
Server is shutdown and re-started. (282205)
* ETR data doesn't display in charts when opening or replacing the containing
picture.(283572)

* VisiconX Data object would reset back to first record after a query. (284551)

* Workspace temporarily freezes when pictures directly access OPC data points
(285074)

* AlarmODBC.cfg become corrupt if tablename is changed to a shorter name
(284313)

* Security Issue (283386)

* Data Source gets changed from F_# to F_CV if tag does not exist prior to using
color expert (282956)

* Login.exe dialog closes when pressing ESC if opened by iFixScreenSaver (281132)

* When using the iFIX Screensaver, users are unable to change password if expired
(274065)

* F10 Key Macro does not work correctly (263027)

* Tolerance is not being saved using datalinks. (282037)

* Create Picture expert inserts incorrect sizes, using predefined configuration.
(282124)

* MouseUp events do not fire if the mouse button is released off the object. (281070)

* Picture Converter doesn't set MaxCharactersPerLine property to 80 for text objects
less than 80, also AutoSize is set to false. (279003)

* Picture converter corrupts Kanji characters, when converting small Push Buttons.
(278656)

* Table animation entries are not saved when using tag groups as the datasource on
a datalink caption animation. (279936)

* Fix.exe will hang on the shutdown waiting for third-party application which was
registered with iFix using FixRegisterConsole() helper function (277058)

* Cannot set Column widths to stay persistent for alarm summary in configure mode
(279311)

* Cannot translate Build Dynamo Wizard dialog (279274)

* Cannot translate "Use Pixel Coordinates" and "Use Percentage Coordinates"
checkboxes in "In Enter New Configuration Name" dialog (279273)

* Create Picture Wizard NLS: String ID in Tag property were missing in
btnDeleteConfig, pgStyles, pgSizes, btnSave control (278561)

* Continuous iFix Timers would occasionally fire 1 second early. (277455)
                  * Toolbar buttons are missing from the toolbar, during a mode switch. (276640)

                  * Double bytes strings are not displayed correctly in Server selection ComboBox and
                  Item browsing spread control. (NLS) (280803)

                  * AlmSum.exe was hogging 100% CPU for an indefinite period of time. (252294)

                  * Alarm Summary Sorting Problem when using LIN driver and there is no PDB and
                  WSACTASK being used (276687)

                  * Unable to remove user created alarm queue when started by background schedule
                  (276672)

                  * Alarm ODBC service did not log double bytes operator message correctly with
                  calling SendSignedOperatorMessage function when the message is over 82 bytes.
                  (282253 NLS)

                  * Double bytes strings are not displayed correctly in Startup Profile Mgr main dialog.
                  (278412)

                  * NAM is only dispersing about 10+ alarms per second to attached NAC's (289755)

                  * Enables iHistorian API timeout to be configurable (277122)

                  * Allows throttling of the frequency of alarm cycles for the thread that moves alarms
                  from the SAC queue to the Summary queue. (268948)

                  * An iClient cannot connect thru the RAS client connection if iFIX was already running
                  on the RAS server (SCADA) when the RAS connection was made. (269268)


iFIX 3.5 Polish

iFIX35_1123523131FixTagGroupDll.dll                              155,769             07/17/2006
                 Fix2DBitmapDll.dll                              192,659             06/28/2006
                 Fix2DBitmap.tlb                                 30,196              06/28/2006
                 FixBackgroundServer.exe                         45,138              06/23/2006
                 OpcDataSystem.dll                               450,690             06/20/2006
                 FixEventDll.dll                                 155,780             06/07/2006
                 FixAppDll.dll                                   209,007             06/07/2006
                 FixPageDll.dll                                  352,369             06/07/2006
                 PlugandSolve.fxg                                826,880             05/23/2006
                 FixLookupDll.dll                                172,166             05/23/2006
                 FileTree.ocx                                    57,344              05/12/2006
                 WSACTASK.EXE                                    53,299              05/08/2006
                 SACDLL.DLL                                      192,561             05/08/2006
                 SecuritySynchronizerDLL.dll                     356,423             04/27/2006
                 SECCFG.exe                                      397,366             04/27/2006
                 SECMGR.dll                                      65,590              04/27/2006
                 VisiconXData.ocx                                413,787             04/21/2006
                 FixChartDlg.dll                                 499,792             04/04/2006
                 FixComponentDll.dll                             589,931             03/28/2006
                 AlmSumMgr.DLL                                   102,478             03/17/2006
                 AlarmSummaryOCX.ocx                             385,112             03/17/2006
                 AlmSumMgrRes.dll                                20,480              03/17/2006
                 AlarmSummaryOCXRes.dll                          65,654              03/17/2006
PictureConverterDll.dll            495,712     03/02/2006
Fix2DTextDll.dll                   290,959     03/02/2006
FIXERROR.DLL                       139,264     02/28/2006
Fix2DGroupDll.dll                  282,769     01/31/2006
Fix2DPenDll.dll                    430,239     01/27/2006
FIX.EXE                            208,946     12/28/2005
FIXSRV.exe                         65,589      12/28/2005
FixSchedulerDll.dll                520,326     12/28/2005
FixPictureDll.dll                  438,402     12/28/2005
VisiconXGrid.ocx                   114,779     12/25/2005
FixGlobalSysInfoDll.dll            143,491     11/15/2005
FCATABLE.DLL                       53,305      11/15/2005
LOGIN.EXE                          143,410     11/12/2005
ExpertGlobalRES.dll                86,016      11/11/2005
ALMODBC.exe                        118,847     11/01/2005
FactoryGlobalsRES.dll              61,440      09/30/2005
FixControlContainerDll.dll         331,939     08/18/2005
EnumerationsDLL.dll                28,672      08/15/2005
LDBA.dll                           299,061     08/15/2005
FactoryGlobals.fxg                 1,822,208   07/27/2005
CONMGR.exe                         69,684      07/25/2005
FixFileLinkDll.dll                 249,977     04/13/2005
WorkSpace.exe                      139,335     03/21/2005
FixUserPreferencesManagerRes.dll   20,480      03/16/2005
FixFormatDll.dll                   155,782     03/16/2005
FixFormat.tlb                      19,432      03/16/2005
FixUserPreferencesManagerDll.dll   135,290     03/16/2005
Scripting.dll                      225,356     03/16/2005
ValvesAnim.fds                     222,208     02/14/2005
FixBackgroundServerRes.dll         40,960      02/09/2005
FixPropDlg.dll                     364,622     02/09/2005
Tanks.fds                          269,824     02/09/2005
TanksAnim1.fds                     261,120     02/09/2005
TanksAnim2.fds                     271,872     02/09/2005
PipesAnim.fds                      194,560     02/09/2005
Pipes.fds                          220,672     02/09/2005
ExpertGlobal.fxg                   2,712,576   02/09/2005
Fix2DAxisDll.dll                   213,153     02/07/2005
Fix2DChartDll.dll                  360,611     02/07/2005
Fix2DLegendDll.dll                 262,309     02/07/2005
SearchReplace.dll                  143,444     02/04/2005
FixDataLinkDll.dll                 213,152     02/04/2005
iFixScreenSaver.scr                102,482     02/03/2005
TimerManager.dll                   57,426      01/11/2005
FixTimerDll.dll                    184,435     01/11/2005
Fix2DShapeDll.dll                  434,307     12/28/2004
FixAnimationDll.dll                139,388     12/28/2004
FixLinearDll.dll                   139,398     12/28/2004
Fix2DShape.tlb                     30,128      12/28/2004
FixComponentRes.dll                16,384      12/28/2004
SUMQLIB.DLL                        81,975      12/28/2004
SCU.exe                            618,547     12/28/2004
FixErrToHResult.dll                24,664      11/29/2004
WorkSpaceErrorsRes.dll             57,344      11/29/2004
FixShapeDll.dll                    110,707     11/08/2004
FixAppServiceDll.dll               102,525     09/27/2004
OpcEdaDll.dll                                  143,436              09/21/2004
AlmODBCConfig.exe                              159,836              09/17/2004
FixControlContainerRes.dll                     32,768               09/10/2004
QUE2LIB.DLL                                    61,494               08/16/2004
FixUserPreferencesDll.dll                      225,380              07/21/2004
FixPropDlgRes.dll                              69,632               07/20/2004
launch.exe                                     102,465              07/17/2004
OODBDll.dll                                    225,360              07/17/2004
FixDataSystems.ocx                             114,797              07/02/2004
OPC20iFIX.exe                                  290,887              07/02/2004
WorkSpaceRes.dll                               135,168              07/02/2004
FixUserPreferencesResDll.dll                   49,288               06/10/2004
NLSAPI.DLL                                     41,014               04/12/2004
CrossReference.exe                             610,385              03/31/2004
ExpressionEditor.ocx                           258,138              03/31/2004
SecuritySynchronizerRes.dll                    32,768               02/19/2004
SEC_AF.DLL                                     16,384               02/19/2004
FixKeyMacroDll.dll                             65,641               02/19/2004
FixKeyMacroHandlerDll.dll                      77,943               02/19/2004
XDBA.dll                                       53,301               02/13/2004
ExpertGlobals2.fxg                             1,610,752            02/04/2004
FixVariableDll.dll                             131,193              01/30/2004
FixDynamoSetServer.dll                         159,875              01/16/2004
FixGlobalsServer.dll                           159,871              01/16/2004
FixPictureServer.dll                           159,871              01/16/2004
FixSchedulerServer.dll                         159,875              01/16/2004
FixToolbarServer.dll                           159,871              01/16/2004
FixToolbarDll.dll                              348,290              01/16/2004
SumqUpdate.exe                                 24,645               12/10/2003
FD_BDW.dll                                     28,672               09/17/2003
launchres.dll                                  49,152               09/15/2003

* Tag group resolution does not work properly if using the DefaultRefreshRate entry in
the Workspace.ini file and resolving tags before switching to Run mode. (1-
123523131)

* Bitmap Pushbutton stays stuck down, when pushbutton is invisible and user clicks
on area where pushbutton exists. (1-162154461)

* FixBackgroundServer events logged in the NT Event Viewer are not mapping with
descriptions.(1-144598020)

* Data in a picture never updates.(1-144898371)

* If Fire DataChange Event is disabled, then global user variable never triggers (1-
155223934)

* In the Chart Group File dialog, the file tree doesn't support Kanji Characters. (1-
112641852)

* Changing the DataSource for the last existing pen in a chart group file using the
Chart Group Wizard causes the values for color and limits to be reset. (1-111307898)

* Color animations using shared threshold table don't work properly if the same
threshold table is used by different pictures and these pictures are all opened in run
mode. (1-147175602)
* In the Chart Group File dialog, the file tree doesn't support Kanji Characters. (1-
112641852)

* It was not possible to use a "_" in a Windows User Name when running
SecuritySynchronizer (1-161443891)

* SQT blocks get stuck in the state of waiting for confirmation once their confirmations
get lost or never happen. (1-97202545A)

* VisiconX data control requires user with local administrative rights to connect to
OLE DB database. (1-110895991)

* Can't set the span interval to be 0 at chart configuration. (1-118948231)

* Workspace OPC client does not display OPC server's error string correctly (1-
126022821)

* Complex expressions fail after installation of sim 1-95976911 on Japanese iFix (1-
116459481)

* Log file and Alarm ODBC database don't capture each unsuccessful login attempt
(1-150615677)

* TX Block's comm. alarm doesn't show up on the AlarmSummary. (1-118034431)

* Alarm Summary OCX doesn't allow user to filter by the ACK column. (1-103547011)

* Picture Converter does not convert command comments correctly. (1-105643029)

* Cannot backspace when adding characters to a datalink. (1-115227146)

* Slow NT authentication for iFIX domain user (1-95990941C)

* Accelerator for Pushbutton doesn't work when Pushbutton is grouped (1-
116290921)

* Pictureconverter leaves unwanted '&' character in button! (1-116895871)

* Datalinks converted from FIX32 will highlight even though they were not
highlightable in the FIX32 picture.(1-127653268)

* Chart does not update correctly when changing tag group file that references t_data
(1-108273211)

* Automation error occurs when the DBDisconnect method is used in the
ExecuteComplete event of the VXDATA control. (1-119581251)

* iFix can't shut down ALMODBC and WSQLODC if they connect to a Sybase 9.xx
database on French OS. (1-105652516)

* Zooming a chart causes value ranges displayed on the Y axis of the chart to go
beyond its pens' EGU limits.(1-93670101)

* Encounter error when trying to modify schedule that has been set to run in
background (1-100502591)
* Unable to enter the Slash(/) from numeric pad in a Datalink. (1-112641841)*
Datalink doesn't support supressing character entry (1-116023901)

* Commandbutton no longer highlights in run mode after undoing a delete in
Configuration mode (1-115514116)

* Autoresize property of VisiconXData control doesn't resize columns after fetching
data.(1-113180591)

* Workspace intermittently disappears\access violation when running on RDP clients
(1-36959520)

* Advanced animation with TagGroup expressions containing complex expressions
no longer worked after installation of sim (1-100954501)

* Logging out of windows causes Fix service to goto stopping (1-100137961)

* ALT-TAB permissions not restored properly when using stacked logged in users (1-
109910701)

* "User Defined Fields" work differently for Alarms vs Events (1-106088924)

* Blinking property of an animated object using Dynamos is not working properly. (1-
99874598)

* Fonts stop changing horizontally in proportion to vertical changes if you change the
resolution of the screen while configuring a chart. (1-99237697)

* CommandButton script isn't recorded on basic animation dialog (1-106169060)

* Get error message "Expressions containing Historical items is not allowed" when
adding a pen that references to a iHistorian tag to a chart group file, if the pen name
matchs the pattern of "*.*.*.*.*". (1-71329801)

* Get error message "Secure Containment Detected Bad Control ..." and Workspace
crash while configuring a VisiconX data control to use Microsoft OLE DB Provider for
SQL Server as data provider, if more than 255 SQL servers are available in the
network.(1-99995157)

* Application crash when writing to A_ENAB field using EDA (1104354604)

* Alarm Acknowledge messages are being sent to the AA/DA block alarm areas
instead of the alarm areas for operator messages. (1-101856381)

* OnDataChange Event Does not Fire first time value changes (197333581)

* AcknowledgeAnAlarm can't acknowledge an alarm using a tag group symbol.(1-
95001621)

* Double byte dash "-" is not recognized for a object name in iFIX 3.5 Japanese. (1-
95976911)

* The GetFullName method of the ESignature object doesn't work if the Windows
user is a local user and the method is used to get a domain user's full name.(1-
52405328)
* MouseUp and MouseUpOffObject scripts do not work properly. (1-91893091)

* Find operation in workspace always sets dirty flag (1-101005761)

* AlmODBC crashes with STK Userfield and STK alm extension field being truncated
(142562201)

* When selecting text in a datalink that has "Leading Spaces" enabled, the text
highlight strips of the leading spaces (1-37828101)

* Workspace application crash when closing a picture that was created on a machine
with FIXDesktop installed and run on a machine without FIXDesktop installed. (1-
94231958)

* The Workspace application object does not properly accept negative values for the
TOP and LEFT properties. (1-90865926)

* Alarming-suspended/resumed messages are being sent to the AA/DA block alarm
areas instead of the alarm areas for operator messages. (1-91722901)

* Can't type in a space in editing mode of the standard text tool after installing
iFIX35_281537 or a later workspace SIM and having selected the Remove Leading
and Trailing Spaces option for text in the User Preferences.(1-83444001)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* Workspace crashes when switching between pictures using ReplacePicture
subroutine, if picture caching is enabled and the new picture names passed in
ReplacePicture are"xxxxx.grf" and "xxxxx.grf "(i.e. file names with trailing whitespace
characters).                                (288907)

* Read-write access to the security path is needed in order to use the security
configurator. (1-83519101)

* After installing iFIX35_294859, when Workspace is started, it is not restored at the
size that it was last closed. (1-85376901)

* Find function in VBE of Workspace does not handle inputting double byte characters
correctly. (1-79830201)

* Precision adjustment for a float-value datalink causes the value sometimes being
displayed with a different rounding from the Curr Value field in the Database
Manager. (1-43322301)

* The Timer Cursor shows no data for the last sample using SetPenDataArray
method. (1-79315501)

* FIXbackgroundServer Event ID 103, 107, 108, 111 messages appear erroneously in
the Event log (266950)

* Custom color palettes do not work using tank, valve and pipe dynamo's. (272910)

* Ramp Expert doesn't set the value to the low/high limit, when the new value
exceedes the limit.(270674)
* Some automation subroutines (AcknowledgeAnAlarm, RampValue, SetManual,
SetAuto, ToggleManual) change the values of parameters passed to them.(273349)

* The WriteValue VBA method sent an incorrectly formatted operator message if the
data source had a "%" in it.             (264630)

* Added Interval Field to Chart Group Wizard (274023)

* Chart group methods are not accessible in the background task.(272466)

* The Visibility Expert adds lookup levels in the descending order of input values
when configuring, which causes visibility animations to be converted incorrectly as the
Web Converter is expecting all lookup levels in the ascending order of input
values.(276784)

* A visibility animation created with a range, will not be edited correctly with the
visibility expert. (274718)

* FixBackgroundServer can't monitor running schedules, when run as a service on
WIN2000. (287836)

* Custom color palettes don't work in a pen's color. (262282)

* After opening and closing the VBA property window, a pen can't be deleted from a
chart properly. (268805)

* Using ModifyColumnLength VBA method to change the Chart's legend column
length, causes the legend text to grow and stretch. (271284)

* VisiconX Grid time field displays both system date and time. (279234)

* Can't open a .csv file by using VisiconX and OleDB provider for ODBC. (259313)

* Find and Replace messes up script.(273672)

* Changing the Object Name and Description on the Basic Animation Dialog does not
dirty the containing picture. (277534)

* Close and Save method of Document(s) allow document(s) to be saved during
mode switch, which sometimes causes the document(s) to be corrupted.(267849)

* FixBackground Server crashes while running iFIX as a service. (272155)

* "Invalid Handle" message is given when a "Delete All" is executed on the Alarm
Summary OCX.(260452)

* Datalink raw format resets when changing the datasource. (264403)

* The current alarm index would intermittedly get stuck on last alarm acknowledge
when scroll bars are enabled and ACK/PRIORITY descending. (272349)

* Alarm Summary's status bar prints black when using XP themes. (278401)

* iFixScreenSaver will hang if Login.exe is already opened (295038)
* AlmODBC crash when STK Userfield lengths exceed 79 characters and also STK
alarm extension field was being truncated. (142562201)

* TagGroup expressions containing complex expressions cause high message rate
(264443)

* Initial update of datalink values is slow when first opening a picture (1-19756822)

* Users get 'Invalid qualifier' error on data entry form after installing iFIX35_292319B
SIM.(1-42578390)

* Daily schedules running in the background skip firing every other day and double
firing at midnight when using New Zealand regional settings and time zone.(263814)

* Using the ToggleDigitalPoint expert and then running the Tag Group Editor (Get
Symbols From Picture), will not get all of the Tag Group Symbols that are eligible in
the picture.(274890)

* In datalink and some animation experts, if the data source is a single source, not an
expression, the tolerance gets reset to default.(276128)

* Remove Level automation method causes a memory leak. (273677)

* Dashed lines are printed as solid. (272979)

* Bitmap Pushbutton stays stuck down, when using a mouse down event that
launches a modal dialog. (278520)

* Tooltip would intermittedly flash on select PC's (266730)

* Can't get a property name correctly using the property dispatch ID, if the dispatch ID
is zero.(272807)

* When implementing the same VBA procedure in a picture and in a group (of objects
contained) as well, the VBA procedure was disabled at the picture level after
renaming the group. (275682)

* When using automation SelectObject method to select multiple objects, the color
property was only being set on the last selected object. (279699)

* MDI->EV->DA chain goes off-scan on iFIX re-start or database reload. (269246)

* More than 20 consecutive calls                 to   FixGetUserInfo     would    return
"smo_replace_profile: bad index". (273300)

* Tag description not being written to RDBM from AlarmODBC (268799)

* When using the sa_almmsg_cb and passing in the timestamp for the alarm, the
TimeIn on view nodes would not get updated if there was an existing alarm. (277780)

* AAD file cannot be accessed from VIEW node. (269866)

* Random "iFIX Detected a Serious Problem. Please Shut Down Restart iFIX" errors
(1-52135901)

* Text object has no space in between multiple lines of text. (1-34485756)
* Pressing the CTRL and then the TAB keys repeatedly causes the Workspace to
consume 100% CPU usage and makes the workspace unresponsive. (141913801)

* Some methods of Alarm Summary cause memory leak. (266745)

* Datalinks not retaining\displaying leading\trailing spaces when writing to TX Blocks
(1-37828101)

* After choosing a color from a custom color set, a foreground color animation
configured with the Foreground Color Expert cannot retain any new color selection
from the system default color set. (1-32449601)

* Deleting the Enabled animation of a push button from the system tree causes the
push button disabled.(1-34153301)

* Applying a chart group file that has an interval greater than 1 minute to an iFix chart
results in an error message "FIX2DPen invalid parameter".(1-32281101)

* Turning on data system prematurely causes some animations to work incorrectly.(1-
27285016)

* Unusual Behavior when pictures are saved outside the PIC directory and switched
to Run mode (1-32486401)

* Added a configuration setting to the .ini file to allow the user to specify the method
iFIX uses to open picture (290712)

* Animation data error doesn't work properly after installing iFIX35_SP1. (1-
32916701)

* The "Blink on New Alarm" checkbox will not stay checked the datasource is a tag
group and the animation is opened using the wizard. (132796801)

* The a F_CV value on RealTime Chart will cause the chart to blank and restart when
duration is changed (294512)

* The basic animation table settings are lost when using an undefined user global
variable as the data source in the basic animation dialogs.(1-21409801)

* Data Type mismatch error on automation method "AcknowledgeAllAlarms" when the
picture contains an object with an animation with a datasource equal to a constant.
(1-25827301)

* An event based schedule doesn't fire if it is using the System.CurrentTime property
in its data source and run in the background.(294413)

* Shape animation is no longer valid after a global Search and Replace (292319)

* Additional OPC Refresh configuration option. (119237501)

* Increased the maximum limit of the number of records to read from the User queue
before writing to the relational database for AlarmODBC. (280263)

* The Address fields in Device Control (DC) block does not accept syntax for OPC
Client driver. (290932)
* Digital Input block's alarm for the Close state, goes away on database reload.
(122925753)

* The MS Forms 2.0 Textbox control was not scrolling text properly. (292395)

* Workspace.exe in the SCU tasklist did not startup in the mode indicated by the
mode settings.(294859)

* Find & Replace failed with access exception (119739601)

* SetTimeCursorTime Method does not work properly.(292789)

* When using flexdata and thousands of alarms, the AlarmSummaryOCX was slow in
responding to subsequent Workspace user actions after the AlarmSummaryOCX was
initially opened in Workspace Run. (293322)

* An iHistorian Calculator Collector stop\re-start in the iHistorian Administrator would
cause the tag calculation to fail, "Object is not connected to the server". (290840)

* Down arrow key does not work if first datalink is invisible. (293910)

* Grouped Datalink sourced from a Global variable displays the stale data value if the
picture cache is enabled. (291986)

* SetTimeCursorTime Method does not work properly.(292789)

* Cannot de-select "Remove Trailing and Leading Spaces" for text objects in User
Preferences.(17410327)

* The animation table settings are lost when Using a undefined User Global Variable
in the Advanced Animation dialog. (288314)

* AlmODBC doesn't insert multiple records into SQL. (292290)

* Duplicate Logical Nodename error when using Launch with command line
parmeters /s /l /n (288317)

* License Error - iFIX has detected a serious problem. Please shutdown and restart
iFIX" generated when there was an invalid path or entry in the task list. (292781)

* Can not switch to run between iFIX and Sample System (NLS) (279886)

* NLS Translation issues (279280)

* AcknowledgeAllAlarms subroutine doesn't work for tag groups after migrating the
picture created with iFIX 2.6 to iFIX 3.5.(293393)

* Nudge settings not reflecting settings from the Fixuserpreferences.ini (294535)

* Added the ability to suppress RANGE, UNDER RANGE, and NODATA alarms.
(290732)

* Fix Data System OCX not working (294185)
* Spacing between lines in a multiple-line datalink changes when the last few lines are
blank.(292544)

* XYHistTest Method returns error (292899)

* Dead lock condition using OPCEDA asynchronously. (283840)

* OpciFix OPC server doesn't browse STK tags. (290388)

* Pictures are resized when the workspace opens after it was last closed in the
minimized or restored state.(292398)

* Duplication turns PushButton to FixOLEControl.(292381)

* Legend object get_LegendHeadingLine() is not returning Interval column name and
GetColumnInfo() method is returning empty column name.(294667)

* If the AlarmSummaryOCX is scrolled, and a new alarm comes in, the visible viewing
area is reset to the new end rows. (292610)

* SecuritySynchronizer crashes when logging oversized message.(292169)

* Added automation properties to support infoAgent 2.0 (293871)

* Clicking the Cancel button when configuring a schedule item causes some scripts
removed if the beginning of the names are the same for the timer and event schedule
items and the underscore character is used.(290611)

* Text object doesn't go to the next line when exceeding MaxCharactersPerLine.
(291537)

* Duplication of dynamo generates objects with same name.(290257)

* Applying a chart group file to a chart sometimes doesn't set EGU limits
correctly.(288261)

* VisiconX shows no data in the VisiconX Grid when opening a picture that has been
cached. (289291)

* Build Dynamo Wizard: Partial substitution for a dynamo property value does not
work properly if there is a decimal point in the animation data source.(290242)

* Animations don't work using constant numerical datasources. (288963)

* DBASRV inadvertently starts running when during iFIX startup. (291346)

* When using a long datatype datablock from an OPC server as the datasource in a
datalink, the value was different in the iFIX database and the datalink by 1. (292059)

* Alarms with the same Time In and Time Last are sometimes displayed in a different
order depending on the Sort Key. (289889)

* Script events created with the VBA FindReplaceInObject automation method do not
fire. (287883)
                 * Using NT security with iFix security, password expires error message occurs, even
                 though the user account is set to password never expires. (288005)

                 * Animated Text object caption doesn't work, if the datasource is static text. (286466)

                 * A chart does not display axes and grids after setting its current pen to be not
                 visible.(287462)

                 * Bad event message being sent to alarm typers, when user tries to set alarm values
                 of block higher then Egu Hi (290559)

                 * VBA Errors on install when installing to a machine with XP machine that has
                 sublanguages installed. (289295)

                 * Color animation's table resets when leaving expression editor, using the color
                 experts. (290442)

                 * Group click events do not fire when clicking on a control with no events. (285712)

                 * RetrieveTagGroupVariable method leaks memory.(287253)

                 * Acknowledged Alarms were being dropped from alarm synchronization (288698)

                 * The property name gets stripped from animation data source when reentering the
                 animation dialog, if the data source is an OLE object's default property.(287357)


iFIX35_1112501941 VDBA.DLL                                     41,014               11/28/2005
                 EDA.dll                                        86,067              10/24/2005
                 DDECLNT.EXE                                    188,471             10/24/2005
                 etr.gov                                        978                 08/15/2005
                 pa.gov                                         2,112               08/15/2005
                 tr.gov                                         978                 08/15/2005
                 hs.gov                                         978                 08/15/2005
                 ev.gov                                         978                 08/15/2005
                 dt.gov                                         870                 08/15/2005
                 DataBaseManager.exe                            663,635             07/27/2005
                 FixDB32_DO.dll                                 57,430              07/14/2005
                 FixDB32_AO.dll                                 65,622              07/14/2005
                 FixDB32_DI.dll                                 65,622              09/07/2004
                 FixDB32_DR.dll                                 53,334              09/07/2004
                 FixDB32_DA.dll                                 73,814              09/07/2004
                 FixDB32_BLRes.dll                              16,495              06/14/2004
                 FixDB32_DIRes.dll                              16,495              06/14/2004
                 FixDB32_DORes.dll                              16,495              06/14/2004
                 FixDB32_DARes.dll                              16,384              06/14/2004
                 FixDB32_DRRes.dll                              12,288              06/14/2004
                 DatabaseManagerRes.dll                         204,800             06/10/2004

                 * iFix Database Toolkit gives it 4293 string in alarm status when the alarm is COMM
                 (1-112501941)

                 * NETDDE cannot get remote Excel data in view on Win 2000 machine. (1-
                 115030351)

                 * Alarm Extension fields not being exported for some blocks (1-103966121)
                * Low EGU limit of 0.000001 causes error on import of database (187182953)

                * Event messaging no longer works on AO and DO blocks (186558030)

                * Database Manager will not start on machines with large registry files (1-86803501)

                * The Database Management spreadsheet displays incorrectly if a tag is imported that
                has double byte and regular characters that exceed the length limit of a field. (1-
                79830256)

                * PDB queries not working when there is no SORT order criteria (1-19734301)

                * Open/Close labels do not change case on Digital blocks (293103)

                * DB Manager EXPORT problem with Large Loadable Block (292393)

                * Database Manager doesn't allow lowercase for digital and boolean block
                labels.(277527)

                * Importing a CSV file into Database Manager that contains an equal sign(=) in the
                description field, without single quotes surrounding it, causes the block to import
                incorrectly without error.(269981)

                * The DA block's alarm mode switch's to NEVER from ACK, if no option is selected.
                (283296)

                * Database Manager only shows first 50 tags upon initial startup. (286760)

                * DatabaseManager crash while opening on a machine with Windows Server 2003,
                iFix 3.5, and iHistorian 2.0 installed. (283446)

                * Database Manager could not modify values in certain fields (Init Alarm, etc.)
                (286209)

                * Database Manager could not load queries if the extension was capitalized (i.e.
                *.QRY) (283131)


iFIX35_1174403491NAC.exe                                     53,299              08/14/2006
                 NA_ANALZ.dll                                53,308              06/03/2004

                * Alarms no longer synchronize properly on some redundant systems after installing
                iFIX35_288678. (1-174403491)

                * Login message initiated on Client is not sent to backup SCADA node, when client is
                looking at Backup SCADA as active node. (288678)


iFIX35_199756141 NAM.exe                                     61,491              03/01/2006

                * Alarms were being sent to clients even though NONE is set in Filteralm.ini when
                using non-english versions (1-99756141)

                * NAM is only dispersing about 10+ alarms per second to attached NAC's (289755)
iFIX35_1145497751 NETDIAG.EXE                                     196,671               03/02/2006
                 SKT.DLL                                          188,473               07/07/2005
                 TCPDUMP.EXE                                      61,501                07/07/2005
                 TCPTASK.EXE                                      167,997               07/07/2005

                   * "Out Of Sync In Use" Error In Netdiag. (1-145497751)

                   * Netdiag diagnostic tool fails to return valid information for the Socket Tables. (1-
                   114583744)

                   * SocketRec and Trace Tabs in Netdiag are not functional. (1-99199716)

                   * Terminal Server clients cannot connect to the SCADA node after installing
                   iFIX35_SP1. (295207A)

                   * iFIX event file filled up with assertion messages like "assertion failed (ulLocalIpAddr
                   != 0) && (ulLocalIpAddr != INADDR_NONE)" (1-99234191)

                   * An iClient cannot connect thru the RAS client connection if iFIX was already running
                   on the RAS server (SCADA) when the RAS connection was made and the user was
                   somehow able to disable all of the local IP addresses. (277339)

                   * An iClient cannot connect thru the RAS client connection if iFIX was already running
                   on the RAS server (SCADA) when the RAS connection was made. (269268)


iFIX35_155232834 OSXLIB.dll                                       49,206                04/13/2005

                   * When running the FixbackgroundServer in the background and writing a value to an
                   iFIX tag in the schedule and 8.3 format is disabled on the file system, user receives a
                   "Server automation" error. (1-55232834)


iFIX35_189034472 ElectronicSignature.dll                          184,427               05/04/2005

                   * Workspace leaks memory when using WriteValue method with security enabled.(1-
                   89034472)

                   * Workspace would crash if Esignature Dialog was open and script in background
                   closes picture (293354)

                   * E-Sig writes values with improper precision.(285358)


iFIX35_191893246 HDAODBC.dll                                      262,231               07/11/2005

                   * Memory handling error in Historical ODBC driver. (1-91893246)

                   * Fix Dynamics Historical Data - memory leak (268129)

                   * Problem with select Distinct in query when using Historical Data ODBC driver
                   (271969)


iFIX35_122718147 IHHDA.dll                                         81,984               12/01/2004
                 IHHDA3.dll                                       81,986               12/01/2004
                 FIXTOOLS.dll                                     69,693               10/27/2004
                 FixHdaDll.dll                                    73,804               05/17/2004

                 * Expression Builder iHistorian tag browse fails to display the tags associated with iFix
                 collectors but not having a node name as prefix or missing a "." in their tag names. (1-
                 22718147)

                 * Running iHistorian 3.0, when iFIX connects to the Server to get data, a Client
                 Access License (CAL) should not be used. (133962334)

                 * The filtered errors.ini file doesn't work correctly for iHistorian errors and enables
                 iHistorian API timeout to be configurable. (277122)


iFIX35_292646    IOCNTRL.exe                                     57,406                05/27/2004

                 * D parameter for IOCNTRL does not delay driver when used with /S parameter.
                 (292646)


iFIX35_121207706 ALMLIB.DLL.dll                                  86,070                12/28/2004
                 ALM_SYNC.EXE                                    45,112                12/28/2004

                 * Dates are missing from alarm messages sent from an iFix node to a Fix32 node .
                 (1-21207706)

                 * The primary SCADA (of a redundancy pair) logged in user could not write to the
                 A_NALM field even though the alarm was properly acknowledged and A_NALM
                 updated on the backup SCADA.(270021)

                 * eda_alm_get_user_que returned internal alarm acknowledgement messages (1-
                 18722801)


iFIX35_147803764 RCPUP.EXE                                       380,980               12/22/2004
                 RCPDOWN.EXE                                     389,174               12/22/2004
                 RCP.EXE                                         643,122               12/22/2004

                 * Recipe upload stops execution script when encountering a database error.(1-
                 47803764)

                 * Recipe executed using shell command inside VBA takes long time to execute
                 because the dialog stays on for about 5 seconds for each recipe. (282412)


iFIX35_122517301 BackupRestoreDll.dll                            270,426               09/10/2004
                 BackupRestoreRes.dll NLS:English                86,016                09/11/2003
                 BackupRestore.exe                               32,847                09/11/2003

                 * Problem with Backup And Restore wizard when restoring individual file (122517301)

                 * New command line options for backup/restore.


iFIX35_SP1       FIX.EXE                                          208,946              04/19/2004
WSACTASK.EXE                               53,299      04/19/2004
CONMGR.exe                                 86,068      04/19/2004
SACDLL.DLL                                 188,465     04/19/2004
FixFileLinkDll.dll                         249,977     04/16/2004
FixPropDlg.dll                             364,622     04/15/2004
FixPropDlgRes.dll NLS:English              69,632      04/15/2004
NLSAPI.DLL                                 41,014      04/12/2004
LDBA.dll                                   299,061     04/12/2004
ExpertGlobal.fxg                           2,700,800   04/12/2004
Fix2DShapeDll.dll                          434,307     04/12/2004
FixShapeDll.dll                            110,707     04/12/2004
Fix2DShape.tlb                             30,128      04/12/2004
FixDataLinkDll.dll                         213,152     04/12/2004
ElectronicSignature.dll                    184,427     04/12/2004
Fix2DPenDll.dll                            430,239     04/08/2004
FixBackgroundServer.exe                    45,138      04/02/2004
FixEventDll.dll                            155,780     04/02/2004
OpcDataSystem.dll                          450,690     04/02/2004
Fix2DChartDll.dll                          360,611     04/02/2004
IHHDA.dll                                  86,080      04/01/2004
ALMLIB.DLL                                 86,070      03/31/2004
SUMQLIB.DLL                                81,975      03/31/2004
CrossReference.exe                         610,385     03/31/2004
PictureConverterDll.dll                    491,616     03/31/2004
SecuritySynchronizerDLL.dll                356,423     03/31/2004
SECMGR.dll                                 61,494      03/31/2004
SECCFG.exe                                 401,462     03/31/2004
ExpressionEditor.ocx                       258,138     03/31/2004
NAM.exe                                    61,491      03/24/2004
SKT.DLL                                    188,473     03/22/2004
TCPTASK.EXE                                167,997     03/22/2004
FixDB32_DA.dll                             73,814      03/12/2004
Fix2DTextDll.dll                           290,959     03/12/2004
FixUserPreferencesResDll.dll NLS:English   49,288      03/12/2004
FIXERROR.DLL                               139,264     03/03/2004
PlugandSolve.fxg                           840,192     03/02/2004
DataBaseManager.exe                        663,635     03/01/2004
Fix2DGroupDll.dll                          282,769     02/23/2004
SEC_AF.DLL                                 16,384      02/19/2004
SecuritySynchronizerRes.dll                32,768      02/19/2004
AlarmSummaryOCX.ocx                        385,112     02/19/2004
FixSchedulerDll.dll                        520,326     02/19/2004
FixKeyMacroDll.dll                         65,641      02/19/2004
FixKeyMacroHandlerDll.dll                  77,943      02/19/2004
XDBA.dll                                   53,301      02/13/2004
AlmODBCConfig.exe                          159,836     02/04/2004
ALMODBC.exe                                118,847     02/04/2004
ExpertGlobals2.fxg                         1,610,752   02/04/2004
FixVariableDll.dll                         131,193     01/30/2004
Fix2DLegendDll.dll                         262,309     01/28/2004
Fix2DAxisDll.dll                           213,153     01/28/2004
FixAnimationDll.dll                        139,388     01/21/2004
FixAppDll.dll                              209,007     01/19/2004
FixPictureDll.dll                          438,402     01/19/2004
VisiconXData.ocx                           413,787     01/16/2004
FixDynamoSetServer.dll                     159,875     01/16/2004
FixGlobalsServer.dll                            159,871              01/16/2004
FixPictureServer.dll                            159,871              01/16/2004
FixSchedulerServer.dll                          159,875              01/16/2004
FixToolbarServer.dll                            159,871              01/16/2004
FixToolbarDll.dll                               348,290              01/16/2004
SIMUninstall.dll                                217,159              12/31/2003
SumqUpdate.exe                                  24,645               12/10/2003
LOGIN.EXE                                       143,410              11/21/2003
Scripting.dll                                   225,356              11/20/2003
QUE2LIB.DLL                                     61,494               11/17/2003
Fix2DBitmapDll.dll                              192,659              11/10/2003
FixComponentDll.dll                             589,931              11/10/2003
Fix2DBitmap.tlb NLS:English                     30,196               11/10/2003
FixControlContainerDll.dll                      327,843              09/26/2003
launch.exe                                      102,465              09/24/2003
ExpertGlobalRES.dll NLS:English                 86,016               09/23/2003
FD_BDW.dll NLS:English                          28,672               09/17/2003
AppValidator.exe                                241,741              09/17/2003
AppValidatorRes.dll NLS:English                 77,824               09/17/2003
launchres.dll NLS:English                       49,152               09/15/2003
StartupProfileMgrRes.dll NLS:English            40,960               09/12/2003
StartupProfileMgr.exe                           94,295               09/12/2003
BackupRestoreRes.dll NLS:English                86,016               09/11/2003
BackupRestoreDll.dll                            270,426              09/11/2003
BackupRestore.exe                               32,847               09/11/2003
TimerManager.dll                                57,426               09/08/2003
FixDB32_DARes.dll NLS:English                   16,384               07/14/2003

* Can not switch to run between iFIX and Sample System (NLS) (279886)

* NLS Translation issues (279280)

* New command line options for backup/restore.

* The DA block's alarm mode switch's to NEVER from ACK, if no option is selected.
(283296)

* Database Manager only shows first 50 tags upon initial startup. (286760)

* DatabaseManager crash while opening on a machine with Windows Server 2003,
iFix 3.5, and iHistorian 2.0 installed. (283446)

* Database Manager could not modify values in certain fields (Init Alarm, etc.)
(286209)

* Database Manager could not load queries if the extension was capitalized (i.e.
*.QRY) (283131)

* E-Sig writes values with improper precision.(285358)

* Added a configuration setting to the .ini file to allow the user to specify the method
iFIX uses to open picture (290712)

* Cannot translate main window title, Detail Report window (Row Count) , Auto Report
Naming (Browse dir window - "Select a directory")
* Double bytes strings are not displayed correctly in Application Validator main dialog,
Comparison Detail Report dialog, and Print Preview dialog. (278413)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* Increased range of Help context ID values to support values between -
2,147,483,648 and -2,147,483,647 (290334)

* Some EGU values entered as scientific notation would trigger an "out of range" error
(283944B)

* Reentering the Color Expert dialog and then moving the focus off the Data Source
field causes the Color Threshold Table to be reset to the default if the data source
contains multiple tags.(286911)

* Object becomes invisible in run mode when animation is deleted from iFix Browser
Tree (283047)

* Inserting a datalink and setting a historical datasource, then get an error, and setting
a realtime datasource results in a WorkSpace crash. (286063)

* Workspace crash in PTimeDll when pictures containing charts were repeatedly
opened and closed and modified the time range of the charts. (287787)

* CrossReference tool doesn't use regional settings when saving a file as CSV.
(284883)

* FixBackgroundServer can't monitor running schedules, when run as a service.
(287836)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* RAMP block does not ramp down when low EGU is greater then hi EGU (288563)

* Unable to log into iFix when connection to primary domain controller is lost (267542)

* Security Configuration Modifications to support Classic Desktop. (287808)

* SAC would not start up for 20 seconds, when using a large database. (257584)

* sq_remove() error thrown when trying to modify an AIS block thru the
DatabaseManager. (257625)

* SAC slows down after changing 200 AO blocks current mode from AUTO to MANL.
(269990)

* Added "iBatch - Start iWorkInstruction Editor" to iFIX application security areas
(280371)

* Added command line parameter to suppress ORNG (OverRange) Alarm.(273507)

* SecuritySynchronizer /R removes RECIPE User Account from iFix Security
(281002)
* SecurityArea in Picture Properties will not allow you to assign a area name of 22B, if
you have already assigned a security area 22A to a previous picture (264728)

* iFIX - Windows security it was not possible to use a "." or "'" in the NT user name
(275124)

* Incorrect License Error: iFix has detected a serious problem please shutdown iFix.
(278711)

* OnTrue/OnFalse scheduled events fire on startup even when "Fire DataChange
Event on Startup" is deselected. (285575)

* While trending with T_DATA pens on Terminal Server, a random crash occurs.
(279198)

* Charts created using iFix automation interface get abnormal Width and Height
properties.(285999)

* ETR data doesn't show up correctly when changing the pen's Duration in Run
mode.(285687)

* Picture Conversion causing datalink font size to increase drastically. (288371)

* Object animations and data links not updating because of faulty hardware HAL or
BIOS. (269172)

* Foreground color animation doesn't work until the data source changes its value if
the picture is opened in Run mode. (282461)

* Leading and Trailing spaces for Text objects are being deleted. (283218)

* Setting a pen's fixed start time with only time in a chart group file causes a type
mismatch error when you apply the chart group file.(284209)

* Deleting animations with the Basic Animations dialog will result in the animation
being deleted from the object, but it remains in the system tree. (280962)

* Incorrect datalink format when migrating from fix 32 with a symbol from a tag group
(277426)

* Converting pictures from Fix32 and then trying to rotate objects in iFix would not
work correctly. (272793)

* Picture Converter was not converting a text object's visibility animation exact match
tolerance correctly. (273899)

* Picture converter does not convert expressions for visibility correctly when regional
setting is something other than English (272789)

* Picture converter does not make first line of command script a comment when that
first line is a comment. (262514)

* Picture converter doesn't convert chart's, when the pen's datasource doesn't exist.
(263527)
* If an object is nested in two groups, the size or position animations of that object do
not initialize correctly.(278574)

* If a grouped object has been highlighted and selected and then its group or itself
becomes invisible, the highlight of the object remains on the screen despite the object
being invisible.(277979)

* "invalid argument was encountered..." error while adding pen using WIN2003, iFIX
3.5 and iHistorian. (287196)

* Converted Fix32 datalink with taggroup symbol displays drop down combo box as
alpha-numberic instead of numeric in iFix Datalink Custom Dialog (287172)

* AlarmSummaryOCX not sorting correctly when sort order is set using VB
automation properties (285530)

* Error in setting timer interval, when using Italy regional settings & time separator of
':' (286249)

* Using Key Macros causes memory leak.(283043)

* A global variable's value, when animated to a database tag, is set to zero when
communication is lost to that tag. (284423)

* iFIX Workspace crash showing a memory access violation in PTimedll.dll. when
using a schedule and also picture initialization code to modify Pens in a chart on the
picture. (284593)

* In Build Dynamo Wizard, partial substitution for a dynamo property value does not
work properly if multiple occurences needed. (283379)

* AlarmODBC unable to handle schema name when defined in tablename when
writing to ORACLE (286150)

* Widened fields to support NLS strings (286795)

* Cannot edit a Chart Group File in run mode, using Chart Group Wizard. (285935)

* Opening or replacing a picture containing charts displaying ETR data or other real
time data is slow at iClient nodes. (281963)

* A historical trend chart shows a wrong value for the average over range if only part
of the chart is filled with data. (265305)

* 'High over range' value in charts is 0 if high is a negative number. (275225)

* Pen in Average Hist mode displays line after last known Good value in Chart
(273503)

* Corrected field truncations in Create Picture Wizard and Print Crystal report wizard
forms (285441)

* PictureConverter crash when using DDE links as source of Dynamic Coloring
Property (285824)

* Event firing was inconsistent when using picture caching. (278187)
* Opc datasources used in TagGroup datalinks do not re-connect when the OPC
Server is shutdown and re-started. (282205)

* ETR data doesn't display in charts when opening or replacing the containing
picture.(283572)

* VisiconX Data object would reset back to first record after a query. (284551)

* Workspace temporarily freezes when pictures directly access OPC data points
(285074)

* AlarmODBC.cfg become corrupt if tablename is changed to a shorter name
(284313)

* Security Issue (283386)

* Data Source gets changed from F_# to F_CV if tag does not exist prior to using
color expert (282956)

* Login.exe dialog closes when pressing ESC if opened by iFixScreenSaver (281132)

* When using the iFIX Screensaver, users are unable to change password if expired
(274065)

* F10 Key Macro does not work correctly (263027)

* Tolerance is not being saved using datalinks. (282037)

* Create Picture expert inserts incorrect sizes, using predefined configuration.
(282124)

* MouseUp events do not fire if the mouse button is released off the object. (281070)

* Picture Converter doesn't set MaxCharactersPerLine property to 80 for text objects
less than 80, also AutoSize is set to false. (279003)

* Picture converter corrupts Kanji characters, when converting small Push Buttons.
(278656)

* Table animation entries are not saved when using tag groups as the datasource on
a datalink caption animation. (279936)

* Fix.exe will hang on the shutdown waiting for third-party application which was
registered with iFix using FixRegisterConsole() helper function (277058)

* Cannot set Column widths to stay persistent for alarm summary in configure mode
(279311)

* Cannot translate Build Dynamo Wizard dialog (279274)

* Cannot translate "Use Pixel Coordinates" and "Use Percentage Coordinates"
checkboxes in "In Enter New Configuration Name" dialog (279273)

* Create Picture Wizard NLS: String ID in Tag property were missing in
btnDeleteConfig, pgStyles, pgSizes, btnSave control (278561)
                   * Continuous iFix Timers would occasionally fire 1 second early. (277455)

                   * Toolbar buttons are missing from the toolbar, during a mode switch. (276640)

                   * Double bytes strings are not displayed correctly in Server selection ComboBox and
                   Item browsing spread control. (NLS) (280803)

                   * AlmSum.exe was hogging 100% CPU for an indefinite period of time. (252294)

                   * Alarm Summary Sorting Problem when using LIN driver and there is no PDB and
                   WSACTASK being used (276687)

                   * Unable to remove user created alarm queue when started by background schedule
                   (276672)

                   * Alarm ODBC service did not log double bytes operator message correctly with
                   calling SendSignedOperatorMessage function when the message is over 82 bytes.
                   (282253 NLS)

                   * Double bytes strings are not displayed correctly in Startup Profile Mgr main dialog.
                   (278412)

                   * NAM is only dispersing about 10+ alarms per second to attached NAC's (289755)

                   * Enables iHistorian API timeout to be configurable (277122)

                   * Allows throttling of the frequency of alarm cycles for the thread that moves alarms
                   from the SAC queue to the Summary queue. (268948)

                   * An iClient cannot connect thru the RAS client connection if iFIX was already running
                   on the RAS server (SCADA) when the RAS connection was made. (269268)


iFIX 3.5 Russian

iFIX35_1123523131FixTagGroupDll.dll                               155,769             07/17/2006
                 Fix2DBitmapDll.dll                               192,659             06/28/2006
                 Fix2DBitmap.tlb                                  30,196              06/28/2006
                 FixBackgroundServer.exe                          45,138              06/23/2006
                 OpcDataSystem.dll                                450,690             06/20/2006
                 FixEventDll.dll                                  155,780             06/07/2006
                 FixAppDll.dll                                    209,007             06/07/2006
                 FixPageDll.dll                                   352,369             06/07/2006
                 PlugandSolve.fxg                                 826,880             05/23/2006
                 FixLookupDll.dll                                 172,166             05/23/2006
                 FileTree.ocx                                     57,344              05/12/2006
                 WSACTASK.EXE                                     53,299              05/08/2006
                 SACDLL.DLL                                       192,561             05/08/2006
                 SecuritySynchronizerDLL.dll                      356,423             04/27/2006
                 SECCFG.exe                                       397,366             04/27/2006
                 SECMGR.dll                                       65,590              04/27/2006
                 VisiconXData.ocx                                 413,787             04/21/2006
                 FixChartDlg.dll                                  499,792             04/04/2006
                 FixComponentDll.dll                              589,931             03/28/2006
                 AlmSumMgr.DLL                                    102,478             03/17/2006
AlarmSummaryOCX.ocx                385,112     03/17/2006
AlmSumMgrRes.dll                   20,480      03/17/2006
AlarmSummaryOCXRes.dll             65,654      03/17/2006
PictureConverterDll.dll            495,712     03/02/2006
Fix2DTextDll.dll                   290,959     03/02/2006
FIXERROR.DLL                       139,264     02/28/2006
Fix2DGroupDll.dll                  282,769     01/31/2006
Fix2DPenDll.dll                    430,239     01/27/2006
FIX.EXE                            208,946     12/28/2005
FIXSRV.exe                         65,589      12/28/2005
FixSchedulerDll.dll                520,326     12/28/2005
FixPictureDll.dll                  438,402     12/28/2005
VisiconXGrid.ocx                   114,779     12/25/2005
FixGlobalSysInfoDll.dll            143,491     11/15/2005
FCATABLE.DLL                       53,305      11/15/2005
LOGIN.EXE                          143,410     11/12/2005
ExpertGlobalRES.dll                86,016      11/11/2005
ALMODBC.exe                        118,847     11/01/2005
FactoryGlobalsRES.dll              61,440      09/30/2005
FixControlContainerDll.dll         331,939     08/18/2005
EnumerationsDLL.dll                28,672      08/15/2005
LDBA.dll                           299,061     08/15/2005
FactoryGlobals.fxg                 1,822,208   07/27/2005
CONMGR.exe                         69,684      07/25/2005
FixFileLinkDll.dll                 249,977     04/13/2005
WorkSpace.exe                      139,335     03/21/2005
FixUserPreferencesManagerRes.dll   20,480      03/16/2005
FixFormatDll.dll                   155,782     03/16/2005
FixFormat.tlb                      19,432      03/16/2005
FixUserPreferencesManagerDll.dll   135,290     03/16/2005
Scripting.dll                      225,356     03/16/2005
ValvesAnim.fds                     222,208     02/14/2005
FixBackgroundServerRes.dll         40,960      02/09/2005
FixPropDlg.dll                     364,622     02/09/2005
Tanks.fds                          269,824     02/09/2005
TanksAnim1.fds                     261,120     02/09/2005
TanksAnim2.fds                     271,872     02/09/2005
PipesAnim.fds                      194,560     02/09/2005
Pipes.fds                          220,672     02/09/2005
ExpertGlobal.fxg                   2,712,576   02/09/2005
Fix2DAxisDll.dll                   213,153     02/07/2005
Fix2DChartDll.dll                  360,611     02/07/2005
Fix2DLegendDll.dll                 262,309     02/07/2005
SearchReplace.dll                  143,444     02/04/2005
FixDataLinkDll.dll                 213,152     02/04/2005
iFixScreenSaver.scr                102,482     02/03/2005
TimerManager.dll                   57,426      01/11/2005
FixTimerDll.dll                    184,435     01/11/2005
Fix2DShapeDll.dll                  434,307     12/28/2004
FixAnimationDll.dll                139,388     12/28/2004
FixLinearDll.dll                   139,398     12/28/2004
Fix2DShape.tlb                     30,128      12/28/2004
FixComponentRes.dll                16,384      12/28/2004
SUMQLIB.DLL                        81,975      12/28/2004
SCU.exe                            618,547     12/28/2004
FixErrToHResult.dll                24,664      11/29/2004
WorkSpaceErrorsRes.dll                         57,344               11/29/2004
FixShapeDll.dll                                110,707              11/08/2004
FixAppServiceDll.dll                           102,525              09/27/2004
OpcEdaDll.dll                                  143,436              09/21/2004
AlmODBCConfig.exe                              159,836              09/17/2004
FixControlContainerRes.dll                     32,768               09/10/2004
QUE2LIB.DLL                                    61,494               08/16/2004
FixUserPreferencesDll.dll                      225,380              07/21/2004
FixPropDlgRes.dll                              69,632               07/20/2004
launch.exe                                     102,465              07/17/2004
OODBDll.dll                                    225,360              07/17/2004
FixDataSystems.ocx                             114,797              07/02/2004
OPC20iFIX.exe                                  290,887              07/02/2004
WorkSpaceRes.dll                               135,168              07/02/2004
FixUserPreferencesResDll.dll                   49,288               06/10/2004
NLSAPI.DLL                                     41,014               04/12/2004
CrossReference.exe                             610,385              03/31/2004
ExpressionEditor.ocx                           258,138              03/31/2004
SecuritySynchronizerRes.dll                    32,768               02/19/2004
SEC_AF.DLL                                     16,384               02/19/2004
FixKeyMacroDll.dll                             65,641               02/19/2004
FixKeyMacroHandlerDll.dll                      77,943               02/19/2004
XDBA.dll                                       53,301               02/13/2004
ExpertGlobals2.fxg                             1,610,752            02/04/2004
FixVariableDll.dll                             131,193              01/30/2004
FixDynamoSetServer.dll                         159,875              01/16/2004
FixGlobalsServer.dll                           159,871              01/16/2004
FixPictureServer.dll                           159,871              01/16/2004
FixSchedulerServer.dll                         159,875              01/16/2004
FixToolbarServer.dll                           159,871              01/16/2004
FixToolbarDll.dll                              348,290              01/16/2004
SumqUpdate.exe                                 24,645               12/10/2003
FD_BDW.dll                                     28,672               09/17/2003
launchres.dll                                  49,152               09/15/2003

* Tag group resolution does not work properly if using the DefaultRefreshRate entry in
the Workspace.ini file and resolving tags before switching to Run mode. (1-
123523131)

* Bitmap Pushbutton stays stuck down, when pushbutton is invisible and user clicks
on area where pushbutton exists. (1-162154461)

* FixBackgroundServer events logged in the NT Event Viewer are not mapping with
descriptions.(1-144598020)

* Data in a picture never updates.(1-144898371)

* If Fire DataChange Event is disabled, then global user variable never triggers (1-
155223934)

* In the Chart Group File dialog, the file tree doesn't support Kanji Characters. (1-
112641852)

* Changing the DataSource for the last existing pen in a chart group file using the
Chart Group Wizard causes the values for color and limits to be reset. (1-111307898)
* Color animations using shared threshold table don't work properly if the same
threshold table is used by different pictures and these pictures are all opened in run
mode. (1-147175602)

* In the Chart Group File dialog, the file tree doesn't support Kanji Characters. (1-
112641852)

* It was not possible to use a "_" in a Windows User Name when running
SecuritySynchronizer (1-161443891)

* SQT blocks get stuck in the state of waiting for confirmation once their confirmations
get lost or never happen. (1-97202545A)

* VisiconX data control requires user with local administrative rights to connect to
OLE DB database. (1-110895991)

* Can't set the span interval to be 0 at chart configuration. (1-118948231)

* Workspace OPC client does not display OPC server's error string correctly (1-
126022821)

* Complex expressions fail after installation of sim 1-95976911 on Japanese iFix (1-
116459481)

* Log file and Alarm ODBC database don't capture each unsuccessful login attempt
(1-150615677)

* TX Block's comm. alarm doesn't show up on the AlarmSummary. (1-118034431)

* Alarm Summary OCX doesn't allow user to filter by the ACK column. (1-103547011)

* Picture Converter does not convert command comments correctly. (1-105643029)

* Cannot backspace when adding characters to a datalink. (1-115227146)

* Slow NT authentication for iFIX domain user (1-95990941C)

* Accelerator for Pushbutton doesn't work when Pushbutton is grouped (1-
116290921)

* Pictureconverter leaves unwanted '&' character in button! (1-116895871)

* Datalinks converted from FIX32 will highlight even though they were not
highlightable in the FIX32 picture.(1-127653268)

* Chart does not update correctly when changing tag group file that references t_data
(1-108273211)

* Automation error occurs when the DBDisconnect method is used in the
ExecuteComplete event of the VXDATA control. (1-119581251)

* iFix can't shut down ALMODBC and WSQLODC if they connect to a Sybase 9.xx
database on French OS. (1-105652516)

* Zooming a chart causes value ranges displayed on the Y axis of the chart to go
beyond its pens' EGU limits.(1-93670101)
* Encounter error when trying to modify schedule that has been set to run in
background (1-100502591)

* Unable to enter the Slash(/) from numeric pad in a Datalink. (1-112641841)*
Datalink doesn't support supressing character entry (1-116023901)

* Commandbutton no longer highlights in run mode after undoing a delete in
Configuration mode (1-115514116)

* Autoresize property of VisiconXData control doesn't resize columns after fetching
data.(1-113180591)

* Workspace intermittently disappears\access violation when running on RDP clients
(1-36959520)

* Advanced animation with TagGroup expressions containing complex expressions
no longer worked after installation of sim (1-100954501)

* Logging out of windows causes Fix service to goto stopping (1-100137961)

* ALT-TAB permissions not restored properly when using stacked logged in users (1-
109910701)

* "User Defined Fields" work differently for Alarms vs Events (1-106088924)

* Blinking property of an animated object using Dynamos is not working properly. (1-
99874598)

* Fonts stop changing horizontally in proportion to vertical changes if you change the
resolution of the screen while configuring a chart. (1-99237697)

* CommandButton script isn't recorded on basic animation dialog (1-106169060)

* Get error message "Expressions containing Historical items is not allowed" when
adding a pen that references to a iHistorian tag to a chart group file, if the pen name
matchs the pattern of "*.*.*.*.*". (1-71329801)

* Get error message "Secure Containment Detected Bad Control ..." and Workspace
crash while configuring a VisiconX data control to use Microsoft OLE DB Provider for
SQL Server as data provider, if more than 255 SQL servers are available in the
network.(1-99995157)

* Application crash when writing to A_ENAB field using EDA (1104354604)

* Alarm Acknowledge messages are being sent to the AA/DA block alarm areas
instead of the alarm areas for operator messages. (1-101856381)

* OnDataChange Event Does not Fire first time value changes (197333581)

* AcknowledgeAnAlarm can't acknowledge an alarm using a tag group symbol.(1-
95001621)

* Double byte dash "-" is not recognized for a object name in iFIX 3.5 Japanese. (1-
95976911)
* The GetFullName method of the ESignature object doesn't work if the Windows
user is a local user and the method is used to get a domain user's full name.(1-
52405328)

* MouseUp and MouseUpOffObject scripts do not work properly. (1-91893091)

* Find operation in workspace always sets dirty flag (1-101005761)

* AlmODBC crashes with STK Userfield and STK alm extension field being truncated
(142562201)

* When selecting text in a datalink that has "Leading Spaces" enabled, the text
highlight strips of the leading spaces (1-37828101)

* Workspace application crash when closing a picture that was created on a machine
with FIXDesktop installed and run on a machine without FIXDesktop installed. (1-
94231958)

* The Workspace application object does not properly accept negative values for the
TOP and LEFT properties. (1-90865926)

* Alarming-suspended/resumed messages are being sent to the AA/DA block alarm
areas instead of the alarm areas for operator messages. (1-91722901)



* Can't type in a space in editing mode of the standard text tool after installing
iFIX35_281537 or a later workspace SIM and having selected the Remove Leading
and Trailing Spaces option for text in the User Preferences.(1-83444001)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* Workspace crashes when switching between pictures using ReplacePicture
subroutine, if picture caching is enabled and the new picture names passed in
ReplacePicture are"xxxxx.grf" and "xxxxx.grf "(i.e. file names with trailing whitespace
characters).                                (288907)

* Read-write access to the security path is needed in order to use the security
configurator. (1-83519101)

* After installing iFIX35_294859, when Workspace is started, it is not restored at the
size that it was last closed. (1-85376901)

* Find function in VBE of Workspace does not handle inputting double byte characters
correctly. (1-79830201)

* Precision adjustment for a float-value datalink causes the value sometimes being
displayed with a different rounding from the Curr Value field in the Database
Manager. (1-43322301)

* The Timer Cursor shows no data for the last sample using SetPenDataArray
method. (1-79315501)

* FIXbackgroundServer Event ID 103, 107, 108, 111 messages appear erroneously in
the Event log (266950)
* Custom color palettes do not work using tank, valve and pipe dynamo's. (272910)

* Ramp Expert doesn't set the value to the low/high limit, when the new value
exceedes the limit.(270674)

* Some automation subroutines (AcknowledgeAnAlarm, RampValue, SetManual,
SetAuto, ToggleManual) change the values of parameters passed to them.(273349)

* The WriteValue VBA method sent an incorrectly formatted operator message if the
data source had a "%" in it.             (264630)

* Added Interval Field to Chart Group Wizard (274023)

* Chart group methods are not accessible in the background task.(272466)

* The Visibility Expert adds lookup levels in the descending order of input values
when configuring, which causes visibility animations to be converted incorrectly as the
Web Converter is expecting all lookup levels in the ascending order of input
values.(276784)

* A visibility animation created with a range, will not be edited correctly with the
visibility expert. (274718)

* FixBackgroundServer can't monitor running schedules, when run as a service on
WIN2000. (287836)

* Custom color palettes don't work in a pen's color. (262282)

* After opening and closing the VBA property window, a pen can't be deleted from a
chart properly. (268805)

* Using ModifyColumnLength VBA method to change the Chart's legend column
length, causes the legend text to grow and stretch. (271284)

* VisiconX Grid time field displays both system date and time. (279234)

* Can't open a .csv file by using VisiconX and OleDB provider for ODBC. (259313)

* Find and Replace messes up script.(273672)

* Changing the Object Name and Description on the Basic Animation Dialog does not
dirty the containing picture. (277534)

* Close and Save method of Document(s) allow document(s) to be saved during
mode switch, which sometimes causes the document(s) to be corrupted.(267849)

* FixBackground Server crashes while running iFIX as a service. (272155)

* "Invalid Handle" message is given when a "Delete All" is executed on the Alarm
Summary OCX.(260452)

* Datalink raw format resets when changing the datasource. (264403)

* The current alarm index would intermittedly get stuck on last alarm acknowledge
when scroll bars are enabled and ACK/PRIORITY descending. (272349)
* Alarm Summary's status bar prints black when using XP themes. (278401)

* iFixScreenSaver will hang if Login.exe is already opened (295038)

* AlmODBC crash when STK Userfield lengths exceed 79 characters and also STK
alarm extension field was being truncated. (142562201)

* TagGroup expressions containing complex expressions cause high message rate
(264443)

* Initial update of datalink values is slow when first opening a picture (1-19756822)

* Users get 'Invalid qualifier' error on data entry form after installing iFIX35_292319B
SIM.(1-42578390)

* Daily schedules running in the background skip firing every other day and double
firing at midnight when using New Zealand regional settings and time zone.(263814)

* Using the ToggleDigitalPoint expert and then running the Tag Group Editor (Get
Symbols From Picture), will not get all of the Tag Group Symbols that are eligible in
the picture.(274890)

* In datalink and some animation experts, if the data source is a single source, not an
expression, the tolerance gets reset to default.(276128)

* Remove Level automation method causes a memory leak. (273677)

* Dashed lines are printed as solid. (272979)

* Bitmap Pushbutton stays stuck down, when using a mouse down event that
launches a modal dialog. (278520)

* Tooltip would intermittedly flash on select PC's (266730)

* Can't get a property name correctly using the property dispatch ID, if the dispatch ID
is zero.(272807)

* When implementing the same VBA procedure in a picture and in a group (of objects
contained) as well, the VBA procedure was disabled at the picture level after
renaming the group. (275682)

* When using automation SelectObject method to select multiple objects, the color
property was only being set on the last selected object. (279699)

* MDI->EV->DA chain goes off-scan on iFIX re-start or database reload. (269246)

* More than 20 consecutive calls                 to   FixGetUserInfo     would    return
"smo_replace_profile: bad index". (273300)

* Tag description not being written to RDBM from AlarmODBC (268799)

* When using the sa_almmsg_cb and passing in the timestamp for the alarm, the
TimeIn on view nodes would not get updated if there was an existing alarm. (277780)

* AAD file cannot be accessed from VIEW node. (269866)
* Random "iFIX Detected a Serious Problem. Please Shut Down Restart iFIX" errors
(1-52135901)

* Text object has no space in between multiple lines of text. (1-34485756)

* Pressing the CTRL and then the TAB keys repeatedly causes the Workspace to
consume 100% CPU usage and makes the workspace unresponsive. (141913801)

* Some methods of Alarm Summary cause memory leak. (266745)

* Datalinks not retaining\displaying leading\trailing spaces when writing to TX Blocks
(1-37828101)

* After choosing a color from a custom color set, a foreground color animation
configured with the Foreground Color Expert cannot retain any new color selection
from the system default color set. (1-32449601)

* Deleting the Enabled animation of a push button from the system tree causes the
push button disabled.(1-34153301)

* Applying a chart group file that has an interval greater than 1 minute to an iFix chart
results in an error message "FIX2DPen invalid parameter".(1-32281101)

* Turning on data system prematurely causes some animations to work incorrectly.(1-
27285016)

* Unusual Behavior when pictures are saved outside the PIC directory and switched
to Run mode (1-32486401)

* Added a configuration setting to the .ini file to allow the user to specify the method
iFIX uses to open picture (290712)

* Animation data error doesn't work properly after installing iFIX35_SP1. (1-
32916701)

* The "Blink on New Alarm" checkbox will not stay checked the datasource is a tag
group and the animation is opened using the wizard. (132796801)

* The a F_CV value on RealTime Chart will cause the chart to blank and restart when
duration is changed (294512)

* The basic animation table settings are lost when using an undefined user global
variable as the data source in the basic animation dialogs.(1-21409801)

* Data Type mismatch error on automation method "AcknowledgeAllAlarms" when the
picture contains an object with an animation with a datasource equal to a constant.
(1-25827301)

* An event based schedule doesn't fire if it is using the System.CurrentTime property
in its data source and run in the background.(294413)

* Shape animation is no longer valid after a global Search and Replace (292319)

* Additional OPC Refresh configuration option. (119237501)
* Increased the maximum limit of the number of records to read from the User queue
before writing to the relational database for AlarmODBC. (280263)

* The Address fields in Device Control (DC) block does not accept syntax for OPC
Client driver. (290932)

* Digital Input block's alarm for the Close state, goes away on database reload.
(122925753)

* The MS Forms 2.0 Textbox control was not scrolling text properly. (292395)

* Workspace.exe in the SCU tasklist did not startup in the mode indicated by the
mode settings.(294859)

* Find & Replace failed with access exception (119739601)

* SetTimeCursorTime Method does not work properly.(292789)

* When using flexdata and thousands of alarms, the AlarmSummaryOCX was slow in
responding to subsequent Workspace user actions after the AlarmSummaryOCX was
initially opened in Workspace Run. (293322)

* An iHistorian Calculator Collector stop\re-start in the iHistorian Administrator would
cause the tag calculation to fail, "Object is not connected to the server". (290840)

* Down arrow key does not work if first datalink is invisible. (293910)

* Grouped Datalink sourced from a Global variable displays the stale data value if the
picture cache is enabled. (291986)

* SetTimeCursorTime Method does not work properly.(292789)

* Cannot de-select "Remove Trailing and Leading Spaces" for text objects in User
Preferences.(17410327)

* The animation table settings are lost when Using a undefined User Global Variable
in the Advanced Animation dialog. (288314)

* AlmODBC doesn't insert multiple records into SQL. (292290)

* Duplicate Logical Nodename error when using Launch with command line
parmeters /s /l /n (288317)

* License Error - iFIX has detected a serious problem. Please shutdown and restart
iFIX" generated when there was an invalid path or entry in the task list. (292781)

* Can not switch to run between iFIX and Sample System (NLS) (279886)

* NLS Translation issues (279280)

* AcknowledgeAllAlarms subroutine doesn't work for tag groups after migrating the
picture created with iFIX 2.6 to iFIX 3.5.(293393)

* Nudge settings not reflecting settings from the Fixuserpreferences.ini (294535)
* Added the ability to suppress RANGE, UNDER RANGE, and NODATA alarms.
(290732)

* Fix Data System OCX not working (294185)

* Spacing between lines in a multiple-line datalink changes when the last few lines are
blank.(292544)

* XYHistTest Method returns error (292899)

* Dead lock condition using OPCEDA asynchronously. (283840)

* OpciFix OPC server doesn't browse STK tags. (290388)

* Pictures are resized when the workspace opens after it was last closed in the
minimized or restored state.(292398)

* Duplication turns PushButton to FixOLEControl.(292381)

* Legend object get_LegendHeadingLine() is not returning Interval column name and
GetColumnInfo() method is returning empty column name.(294667)

* If the AlarmSummaryOCX is scrolled, and a new alarm comes in, the visible viewing
area is reset to the new end rows. (292610)

* SecuritySynchronizer crashes when logging oversized message.(292169)

* Added automation properties to support infoAgent 2.0 (293871)

* Clicking the Cancel button when configuring a schedule item causes some scripts
removed if the beginning of the names are the same for the timer and event schedule
items and the underscore character is used.(290611)

* Text object doesn't go to the next line when exceeding MaxCharactersPerLine.
(291537)

* Duplication of dynamo generates objects with same name.(290257)

* Applying a chart group file to a chart sometimes doesn't set EGU limits
correctly.(288261)

* VisiconX shows no data in the VisiconX Grid when opening a picture that has been
cached. (289291)

* Build Dynamo Wizard: Partial substitution for a dynamo property value does not
work properly if there is a decimal point in the animation data source.(290242)

* Animations don't work using constant numerical datasources. (288963)

* DBASRV inadvertently starts running when during iFIX startup. (291346)

* When using a long datatype datablock from an OPC server as the datasource in a
datalink, the value was different in the iFIX database and the datalink by 1. (292059)

* Alarms with the same Time In and Time Last are sometimes displayed in a different
order depending on the Sort Key. (289889)
                 * Script events created with the VBA FindReplaceInObject automation method do not
                 fire. (287883)

                 * Using NT security with iFix security, password expires error message occurs, even
                 though the user account is set to password never expires. (288005)

                 * Animated Text object caption doesn't work, if the datasource is static text. (286466)

                 * A chart does not display axes and grids after setting its current pen to be not
                 visible.(287462)

                 * Bad event message being sent to alarm typers, when user tries to set alarm values
                 of block higher then Egu Hi (290559)

                 * VBA Errors on install when installing to a machine with XP machine that has
                 sublanguages installed. (289295)

                 * Color animation's table resets when leaving expression editor, using the color
                 experts. (290442)

                 * Group click events do not fire when clicking on a control with no events. (285712)

                 * RetrieveTagGroupVariable method leaks memory.(287253)

                 * Acknowledged Alarms were being dropped from alarm synchronization (288698)

                 * The property name gets stripped from animation data source when reentering the
                 animation dialog, if the data source is an OLE object's default property.(287357)


iFIX35_1112501941 VDBA.DLL                                     41,014               11/28/2005
                 EDA.dll                                        86,067              10/24/2005
                 DDECLNT.EXE                                    188,471             10/24/2005
                 etr.gov                                        978                 08/15/2005
                 pa.gov                                         2,112               08/15/2005
                 tr.gov                                         978                 08/15/2005
                 hs.gov                                         978                 08/15/2005
                 ev.gov                                         978                 08/15/2005
                 dt.gov                                         870                 08/15/2005
                 DataBaseManager.exe                            663,635             07/27/2005
                 FixDB32_DO.dll                                 57,430              07/14/2005
                 FixDB32_AO.dll                                 65,622              07/14/2005
                 FixDB32_DI.dll                                 65,622              09/07/2004
                 FixDB32_DR.dll                                 53,334              09/07/2004
                 FixDB32_DA.dll                                 73,814              09/07/2004
                 FixDB32_BLRes.dll                              16,495              06/14/2004
                 FixDB32_DIRes.dll                              16,495              06/14/2004
                 FixDB32_DORes.dll                              16,495              06/14/2004
                 FixDB32_DARes.dll                              16,384              06/14/2004
                 FixDB32_DRRes.dll                              12,288              06/14/2004
                 DatabaseManagerRes.dll                         204,800             06/10/2004

                 * iFix Database Toolkit gives it 4293 string in alarm status when the alarm is COMM
                 (1-112501941)
                * NETDDE cannot get remote Excel data in view on Win 2000 machine. (1-
                115030351)

                * Alarm Extension fields not being exported for some blocks (1-103966121)

                * Low EGU limit of 0.000001 causes error on import of database (187182953)

                * Event messaging no longer works on AO and DO blocks (186558030)

                * Database Manager will not start on machines with large registry files (1-86803501)

                * The Database Management spreadsheet displays incorrectly if a tag is imported that
                has double byte and regular characters that exceed the length limit of a field. (1-
                79830256)

                * PDB queries not working when there is no SORT order criteria (1-19734301)

                * Open/Close labels do not change case on Digital blocks (293103)

                * DB Manager EXPORT problem with Large Loadable Block (292393)

                * Database Manager doesn't allow lowercase for digital and boolean block
                labels.(277527)

                * Importing a CSV file into Database Manager that contains an equal sign(=) in the
                description field, without single quotes surrounding it, causes the block to import
                incorrectly without error.(269981)

                * The DA block's alarm mode switch's to NEVER from ACK, if no option is selected.
                (283296)

                * Database Manager only shows first 50 tags upon initial startup. (286760)

                * DatabaseManager crash while opening on a machine with Windows Server 2003,
                iFix 3.5, and iHistorian 2.0 installed. (283446)

                * Database Manager could not modify values in certain fields (Init Alarm, etc.)
                (286209)

                * Database Manager could not load queries if the extension was capitalized (i.e.
                *.QRY) (283131)


iFIX35_1174403491NAC.exe                                     53,299              08/14/2006
                 NA_ANALZ.dll                                53,308              06/03/2004

                * Alarms no longer synchronize properly on some redundant systems after installing
                iFIX35_288678. (1-174403491)

                * Login message initiated on Client is not sent to backup SCADA node, when client is
                looking at Backup SCADA as active node. (288678)


iFIX35_199756141 NAM.exe                                     61,491              03/01/2006
                   * Alarms were being sent to clients even though NONE is set in Filteralm.ini when
                   using non-english versions (1-99756141)

                   * NAM is only dispersing about 10+ alarms per second to attached NAC's (289755)


iFIX35_1145497751 NETDIAG.EXE                                     196,671               03/02/2006
                 SKT.DLL                                          188,473               07/07/2005
                 TCPDUMP.EXE                                      61,501                07/07/2005
                 TCPTASK.EXE                                      167,997               07/07/2005

                   * "Out Of Sync In Use" Error In Netdiag. (1-145497751)

                   * Netdiag diagnostic tool fails to return valid information for the Socket Tables. (1-
                   114583744)

                   * SocketRec and Trace Tabs in Netdiag are not functional. (1-99199716)

                   * Terminal Server clients cannot connect to the SCADA node after installing
                   iFIX35_SP1. (295207A)

                   * iFIX event file filled up with assertion messages like "assertion failed (ulLocalIpAddr
                   != 0) && (ulLocalIpAddr != INADDR_NONE)" (1-99234191)

                   * An iClient cannot connect thru the RAS client connection if iFIX was already running
                   on the RAS server (SCADA) when the RAS connection was made and the user was
                   somehow able to disable all of the local IP addresses. (277339)

                   * An iClient cannot connect thru the RAS client connection if iFIX was already running
                   on the RAS server (SCADA) when the RAS connection was made. (269268)


iFIX35_155232834 OSXLIB.dll                                       49,206                04/13/2005

                   * When running the FixbackgroundServer in the background and writing a value to an
                   iFIX tag in the schedule and 8.3 format is disabled on the file system, user receives a
                   "Server automation" error. (1-55232834)


iFIX35_189034472 ElectronicSignature.dll                          184,427               05/04/2005

                   * Workspace leaks memory when using WriteValue method with security enabled.(1-
                   89034472)

                   * Workspace would crash if Esignature Dialog was open and script in background
                   closes picture (293354)

                   * E-Sig writes values with improper precision.(285358)


iFIX35_191893246 HDAODBC.dll                                      262,231               07/11/2005

                   * Memory handling error in Historical ODBC driver. (1-91893246)

                   * Fix Dynamics Historical Data - memory leak (268129)
                 * Problem with select Distinct in query when using Historical Data ODBC driver
                 (271969)


iFIX35_122718147 IHHDA.dll                                        81,984               12/01/2004
                 IHHDA3.dll                                       81,986               12/01/2004
                 FIXTOOLS.dll                                     69,693               10/27/2004
                 FixHdaDll.dll                                    73,804               05/17/2004

                 * Expression Builder iHistorian tag browse fails to display the tags associated with iFix
                 collectors but not having a node name as prefix or missing a "." in their tag names. (1-
                 22718147)

                 * Running iHistorian 3.0, when iFIX connects to the Server to get data, a Client
                 Access License (CAL) should not be used. (133962334)

                 * The filtered errors.ini file doesn't work correctly for iHistorian errors and enables
                 iHistorian API timeout to be configurable. (277122)


iFIX35_292646    IOCNTRL.exe                                     57,406                05/27/2004

                 * D parameter for IOCNTRL does not delay driver when used with /S parameter.
                 (292646)


iFIX35_121207706 ALMLIB.DLL.dll                                  86,070                12/28/2004
                 ALM_SYNC.EXE                                    45,112                12/28/2004

                 * Dates are missing from alarm messages sent from an iFix node to a Fix32 node .
                 (1-21207706)

                 * The primary SCADA (of a redundancy pair) logged in user could not write to the
                 A_NALM field even though the alarm was properly acknowledged and A_NALM
                 updated on the backup SCADA.(270021)

                 * eda_alm_get_user_que returned internal alarm acknowledgement messages (1-
                 18722801)


iFIX35_147803764 RCPUP.EXE                                       380,980               12/22/2004
                 RCPDOWN.EXE                                     389,174               12/22/2004
                 RCP.EXE                                         643,122               12/22/2004

                 * Recipe upload stops execution script when encountering a database error.(1-
                 47803764)

                 * Recipe executed using shell command inside VBA takes long time to execute
                 because the dialog stays on for about 5 seconds for each recipe. (282412)


iFIX35_122517301 BackupRestoreDll.dll                            270,426               09/10/2004
                 BackupRestoreRes.dll NLS:English                86,016                09/11/2003
                 BackupRestore.exe                               32,847                09/11/2003

                 * Problem with Backup And Restore wizard when restoring individual file (122517301)
             * New command line options for backup/restore.


iFIX35_SP1   FIX.EXE                                    208,946     04/19/2004
             WSACTASK.EXE                               53,299      04/19/2004
             CONMGR.exe                                 86,068      04/19/2004
             SACDLL.DLL                                 188,465     04/19/2004
             FixFileLinkDll.dll                         249,977     04/16/2004
             FixPropDlg.dll                             364,622     04/15/2004
             FixPropDlgRes.dll NLS:English              69,632      04/15/2004
             NLSAPI.DLL                                 41,014      04/12/2004
             LDBA.dll                                   299,061     04/12/2004
             ExpertGlobal.fxg                           2,700,800   04/12/2004
             Fix2DShapeDll.dll                          434,307     04/12/2004
             FixShapeDll.dll                            110,707     04/12/2004
             Fix2DShape.tlb                             30,128      04/12/2004
             FixDataLinkDll.dll                         213,152     04/12/2004
             ElectronicSignature.dll                    184,427     04/12/2004
             Fix2DPenDll.dll                            430,239     04/08/2004
             FixBackgroundServer.exe                    45,138      04/02/2004
             FixEventDll.dll                            155,780     04/02/2004
             OpcDataSystem.dll                          450,690     04/02/2004
             Fix2DChartDll.dll                          360,611     04/02/2004
             IHHDA.dll                                  86,080      04/01/2004
             ALMLIB.DLL                                 86,070      03/31/2004
             SUMQLIB.DLL                                81,975      03/31/2004
             CrossReference.exe                         610,385     03/31/2004
             PictureConverterDll.dll                    491,616     03/31/2004
             SecuritySynchronizerDLL.dll                356,423     03/31/2004
             SECMGR.dll                                 61,494      03/31/2004
             SECCFG.exe                                 401,462     03/31/2004
             ExpressionEditor.ocx                       258,138     03/31/2004
             NAM.exe                                    61,491      03/24/2004
             SKT.DLL                                    188,473     03/22/2004
             TCPTASK.EXE                                167,997     03/22/2004
             FixDB32_DA.dll                             73,814      03/12/2004
             Fix2DTextDll.dll                           290,959     03/12/2004
             FixUserPreferencesResDll.dll NLS:English   49,288      03/12/2004
             FIXERROR.DLL                               139,264     03/03/2004
             PlugandSolve.fxg                           840,192     03/02/2004
             DataBaseManager.exe                        663,635     03/01/2004
             Fix2DGroupDll.dll                          282,769     02/23/2004
             SEC_AF.DLL                                 16,384      02/19/2004
             SecuritySynchronizerRes.dll                32,768      02/19/2004
             AlarmSummaryOCX.ocx                        385,112     02/19/2004
             FixSchedulerDll.dll                        520,326     02/19/2004
             FixKeyMacroDll.dll                         65,641      02/19/2004
             FixKeyMacroHandlerDll.dll                  77,943      02/19/2004
             XDBA.dll                                   53,301      02/13/2004
             AlmODBCConfig.exe                          159,836     02/04/2004
             ALMODBC.exe                                118,847     02/04/2004
             ExpertGlobals2.fxg                         1,610,752   02/04/2004
             FixVariableDll.dll                         131,193     01/30/2004
             Fix2DLegendDll.dll                         262,309     01/28/2004
             Fix2DAxisDll.dll                           213,153     01/28/2004
FixAnimationDll.dll                           139,388             01/21/2004
FixAppDll.dll                                 209,007             01/19/2004
FixPictureDll.dll                             438,402             01/19/2004
VisiconXData.ocx                              413,787             01/16/2004
FixDynamoSetServer.dll                        159,875             01/16/2004
FixGlobalsServer.dll                          159,871             01/16/2004
FixPictureServer.dll                          159,871             01/16/2004
FixSchedulerServer.dll                        159,875             01/16/2004
FixToolbarServer.dll                          159,871             01/16/2004
FixToolbarDll.dll                             348,290             01/16/2004
SIMUninstall.dll                              217,159             12/31/2003
SumqUpdate.exe                                24,645              12/10/2003
LOGIN.EXE                                     143,410             11/21/2003
Scripting.dll                                 225,356             11/20/2003
QUE2LIB.DLL                                   61,494              11/17/2003
Fix2DBitmapDll.dll                            192,659             11/10/2003
FixComponentDll.dll                           589,931             11/10/2003
Fix2DBitmap.tlb NLS:English                   30,196              11/10/2003
FixControlContainerDll.dll                    327,843             09/26/2003
launch.exe                                    102,465             09/24/2003
ExpertGlobalRES.dll NLS:English               86,016              09/23/2003
FD_BDW.dll NLS:English                        28,672              09/17/2003
AppValidator.exe                              241,741             09/17/2003
AppValidatorRes.dll NLS:English               77,824              09/17/2003
launchres.dll NLS:English                     49,152              09/15/2003
StartupProfileMgrRes.dll NLS:English          40,960              09/12/2003
StartupProfileMgr.exe                         94,295              09/12/2003
BackupRestoreRes.dll NLS:English              86,016              09/11/2003
BackupRestoreDll.dll                          270,426             09/11/2003
BackupRestore.exe                             32,847              09/11/2003
TimerManager.dll                              57,426              09/08/2003
FixDB32_DARes.dll NLS:English                 16,384              07/14/2003

* Can not switch to run between iFIX and Sample System (NLS) (279886)

* NLS Translation issues (279280)

* New command line options for backup/restore.

* The DA block's alarm mode switch's to NEVER from ACK, if no option is selected.
(283296)

* Database Manager only shows first 50 tags upon initial startup. (286760)

* DatabaseManager crash while opening on a machine with Windows Server 2003,
iFix 3.5, and iHistorian 2.0 installed. (283446)

* Database Manager could not modify values in certain fields (Init Alarm, etc.)
(286209)

* Database Manager could not load queries if the extension was capitalized (i.e.
*.QRY) (283131)

* E-Sig writes values with improper precision.(285358)
* Added a configuration setting to the .ini file to allow the user to specify the method
iFIX uses to open picture (290712)

* Cannot translate main window title, Detail Report window (Row Count) , Auto Report
Naming (Browse dir window - "Select a directory")

* Double bytes strings are not displayed correctly in Application Validator main dialog,
Comparison Detail Report dialog, and Print Preview dialog. (278413)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* Increased range of Help context ID values to support values between -
2,147,483,648 and -2,147,483,647 (290334)

* Some EGU values entered as scientific notation would trigger an "out of range" error
(283944B)

* Reentering the Color Expert dialog and then moving the focus off the Data Source
field causes the Color Threshold Table to be reset to the default if the data source
contains multiple tags.(286911)

* Object becomes invisible in run mode when animation is deleted from iFix Browser
Tree (283047)

* Inserting a datalink and setting a historical datasource, then get an error, and setting
a realtime datasource results in a WorkSpace crash. (286063)

* Workspace crash in PTimeDll when pictures containing charts were repeatedly
opened and closed and modified the time range of the charts. (287787)

* CrossReference tool doesn't use regional settings when saving a file as CSV.
(284883)

* FixBackgroundServer can't monitor running schedules, when run as a service.
(287836)

* Key License error "The license xxxxxxx was removed, please restore the license", is
randomly seen using Terminal Server. (282359)

* RAMP block does not ramp down when low EGU is greater then hi EGU (288563)

* Unable to log into iFix when connection to primary domain controller is lost (267542)

* Security Configuration Modifications to support Classic Desktop. (287808)

* SAC would not start up for 20 seconds, when using a large database. (257584)

* sq_remove() error thrown when trying to modify an AIS block thru the
DatabaseManager. (257625)

* SAC slows down after changing 200 AO blocks current mode from AUTO to MANL.
(269990)

* Added "iBatch - Start iWorkInstruction Editor" to iFIX application security areas
(280371)
* Added command line parameter to suppress ORNG (OverRange) Alarm.(273507)

* SecuritySynchronizer /R removes RECIPE User Account from iFix Security
(281002)

* SecurityArea in Picture Properties will not allow you to assign a area name of 22B, if
you have already assigned a security area 22A to a previous picture (264728)

* iFIX - Windows security it was not possible to use a "." or "'" in the NT user name
(275124)

* Incorrect License Error: iFix has detected a serious problem please shutdown iFix.
(278711)

* OnTrue/OnFalse scheduled events fire on startup even when "Fire DataChange
Event on Startup" is deselected. (285575)

* While trending with T_DATA pens on Terminal Server, a random crash occurs.
(279198)

* Charts created using iFix automation interface get abnormal Width and Height
properties.(285999)

* ETR data doesn't show up correctly when changing the pen's Duration in Run
mode.(285687)

* Picture Conversion causing datalink font size to increase drastically. (288371)

* Object animations and data links not updating because of faulty hardware HAL or
BIOS. (269172)

* Foreground color animation doesn't work until the data source changes its value if
the picture is opened in Run mode. (282461)

* Leading and Trailing spaces for Text objects are being deleted. (283218)

* Setting a pen's fixed start time with only time in a chart group file causes a type
mismatch error when you apply the chart group file.(284209)

* Deleting animations with the Basic Animations dialog will result in the animation
being deleted from the object, but it remains in the system tree. (280962)

* Incorrect datalink format when migrating from fix 32 with a symbol from a tag group
(277426)

* Converting pictures from Fix32 and then trying to rotate objects in iFix would not
work correctly. (272793)

* Picture Converter was not converting a text object's visibility animation exact match
tolerance correctly. (273899)

* Picture converter does not convert expressions for visibility correctly when regional
setting is something other than English (272789)
* Picture converter does not make first line of command script a comment when that
first line is a comment. (262514)

* Picture converter doesn't convert chart's, when the pen's datasource doesn't exist.
(263527)

* If an object is nested in two groups, the size or position animations of that object do
not initialize correctly.(278574)

* If a grouped object has been highlighted and selected and then its group or itself
becomes invisible, the highlight of the object remains on the screen despite the object
being invisible.(277979)

* "invalid argument was encountered..." error while adding pen using WIN2003, iFIX
3.5 and iHistorian. (287196)

* Converted Fix32 datalink with taggroup symbol displays drop down combo box as
alpha-numberic instead of numeric in iFix Datalink Custom Dialog (287172)

* AlarmSummaryOCX not sorting correctly when sort order is set using VB
automation properties (285530)

* Error in setting timer interval, when using Italy regional settings & time separator of
':' (286249)

* Using Key Macros causes memory leak.(283043)

* A global variable's value, when animated to a database tag, is set to zero when
communication is lost to that tag. (284423)

* iFIX Workspace crash showing a memory access violation in PTimedll.dll. when
using a schedule and also picture initialization code to modify Pens in a chart on the
picture. (284593)

* In Build Dynamo Wizard, partial substitution for a dynamo property value does not
work properly if multiple occurences needed. (283379)

* AlarmODBC unable to handle schema name when defined in tablename when
writing to ORACLE (286150)

* Widened fields to support NLS strings (286795)

* Cannot edit a Chart Group File in run mode, using Chart Group Wizard. (285935)

* Opening or replacing a picture containing charts displaying ETR data or other real
time data is slow at iClient nodes. (281963)

* A historical trend chart shows a wrong value for the average over range if only part
of the chart is filled with data. (265305)

* 'High over range' value in charts is 0 if high is a negative number. (275225)

* Pen in Average Hist mode displays line after last known Good value in Chart
(273503)
* Corrected field truncations in Create Picture Wizard and Print Crystal report wizard
forms (285441)

* PictureConverter crash when using DDE links as source of Dynamic Coloring
Property (285824)

* Event firing was inconsistent when using picture caching. (278187)

* Opc datasources used in TagGroup datalinks do not re-connect when the OPC
Server is shutdown and re-started. (282205)

* ETR data doesn't display in charts when opening or replacing the containing
picture.(283572)

* VisiconX Data object would reset back to first record after a query. (284551)

* Workspace temporarily freezes when pictures directly access OPC data points
(285074)

* AlarmODBC.cfg become corrupt if tablename is changed to a shorter name
(284313)

* Security Issue (283386)

* Data Source gets changed from F_# to F_CV if tag does not exist prior to using
color expert (282956)

* Login.exe dialog closes when pressing ESC if opened by iFixScreenSaver (281132)

* When using the iFIX Screensaver, users are unable to change password if expired
(274065)

* F10 Key Macro does not work correctly (263027)

* Tolerance is not being saved using datalinks. (282037)

* Create Picture expert inserts incorrect sizes, using predefined configuration.
(282124)

* MouseUp events do not fire if the mouse button is released off the object. (281070)

* Picture Converter doesn't set MaxCharactersPerLine property to 80 for text objects
less than 80, also AutoSize is set to false. (279003)

* Picture converter corrupts Kanji characters, when converting small Push Buttons.
(278656)

* Table animation entries are not saved when using tag groups as the datasource on
a datalink caption animation. (279936)

* Fix.exe will hang on the shutdown waiting for third-party application which was
registered with iFix using FixRegisterConsole() helper function (277058)

* Cannot set Column widths to stay persistent for alarm summary in configure mode
(279311)
* Cannot translate Build Dynamo Wizard dialog (279274)

* Cannot translate "Use Pixel Coordinates" and "Use Percentage Coordinates"
checkboxes in "In Enter New Configuration Name" dialog (279273)

* Create Picture Wizard NLS: String ID in Tag property were missing in
btnDeleteConfig, pgStyles, pgSizes, btnSave control (278561)

* Continuous iFix Timers would occasionally fire 1 second early. (277455)

* Toolbar buttons are missing from the toolbar, during a mode switch. (276640)

* Double bytes strings are not displayed correctly in Server selection ComboBox and
Item browsing spread control. (NLS) (280803)

* AlmSum.exe was hogging 100% CPU for an indefinite period of time. (252294)

* Alarm Summary Sorting Problem when using LIN driver and there is no PDB and
WSACTASK being used (276687)

* Unable to remove user created alarm queue when started by background schedule
(276672)

* Alarm ODBC service did not log double bytes operator message correctly with
calling SendSignedOperatorMessage function when the message is over 82 bytes.
(282253 NLS)

* Double bytes strings are not displayed correctly in Startup Profile Mgr main dialog.
(278412)

* NAM is only dispersing about 10+ alarms per second to attached NAC's (289755)

* Enables iHistorian API timeout to be configurable (277122)

* Allows throttling of the frequency of alarm cycles for the thread that moves alarms
from the SAC queue to the Summary queue. (268948)

* An iClient cannot connect thru the RAS client connection if iFIX was already running
on the RAS server (SCADA) when the RAS connection was made. (269268)

				
DOCUMENT INFO
Shared By:
Categories:
Tags:
Stats:
views:136
posted:8/11/2011
language:English
pages:151