					TABLE OF CONTENTS
EXECUTIVE SUMMARY...................................................................................... 1

1.     BACKGROUND.......................................................................................... 4

2.     ASSESSMENT PROCEDURES ................................................................. 5

3.     FINDINGS AND RESULTS......................................................................... 6

4.     ABBREVIATIONS AND HAZARD ASSESSMENT KEY.......................... 18

5.     CONCLUSIONS AND RECOMMENDATIONS......................................... 19




APPENDICES

APPENDIX I                DIAGRAM OF BULK SAMPLE LOCATIONS AND
                          CONFIRMED ASBESTOS CONTAINING MATERIALS
APPENDIX II               PHOTOGRAPHS
APPENDIX III              COPY OF SCDHEC INSPECTOR AND/OR MANAGEMENT
                          PLANNER LICENSES
APPENDIX IV               ASBESTOS BULK SAMPLE ANALYSIS SHEETS AND
                          CHAIN OF CUSTODY RECORDS
APPENDIX V                1990 DAVIS & FLOYD ASBESTOS SURVEY REPORT
Asbestos Survey Report                                                    S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                            March 31, 2009



EXECUTIVE SUMMARY

An asbestos survey was conducted on October 9 & 13, 2008 of the Williams building
located on the South Carolina Department of Mental Health (SCDMH) Bull Street
Campus in Columbia, South Carolina. The purpose of the assessment was to verify the
presence of asbestos-containing materials (ACMs) in the building as determined in a
previous asbestos survey report by Davis & Floyd (1990), and to perform supplemental
bulk sampling and analysis to conform with the South Carolina Department of Health and
Environmental Control (SCDHEC) Regulation 61-86.1 Standards of Performance for
Asbestos Projects effective June 27, 2008.

The building is a two-story masonry block structure on a pillar foundation with a finished
basement and crawlspace. The building was reportedly constructed in 1938 and contains
approximately 79,366 square feet of interior space. This structure was formerly used as a
patient ward and hospital with various offices and storage rooms and a kitchen. The
Williams building is currently vacant.

Bulk samples were collected from suspect ACMs that were observed and the samples
were subsequently analyzed for asbestos content by an accredited laboratory. These
materials included: various acoustic ceiling tiles with mastic, sheetrock, joint compound,
various floor tiles with mastic, vinyl baseboards and mastic, vinyl stair treads and mastic,
window glazing, thermal systems insulation (TSI) and mastic, fire door insulation, mastic
on HVAC ducts, roofing materials, roof flashing and roof sealant. The Environmental
Protection Agency (EPA) and South Carolina Department of Health & Environmental
Control (SCDHEC) define materials as asbestos-containing if an asbestos content of
greater than one percent (>1%) is detected in a representative sample. Asbestos, in
concentrations >1%, was identified as a result of the assessment. The following table
summarizes the ACMs identified:

                                             Asbestos Type                Potential for   *Approx.
     Material              Location                           Condition
                                               & Percent                  Disturbance     Quantity

                       On sheetrock in         Chrysotile –
 Joint compound                                                Good           PSD         1,500 ft2
                         basement                  2%
  12” ceiling tile   Lobbies, dayrooms,        Chrysotile -
                                                               Good           PSD         10,000 ft2
      mastic         meeting rooms, etc           6%
Dark brown ceiling      Above dropped          Chrysotile -
                                                               Good           PSD         6,000 ft2
    tile mastic       ceilings in hallways        6%
                                             Chrysotile -6%
     Hard joint        Basement pipes
                                                Amosite -      Good           PSD         300 joints
 Black pipe mastic      with fiberglass
                                                  2%
                                               Chrysotile –                                 278
 Window glazing      Exterior of windows                       Good           PSD
                                                   2%                                     windows




                                                    1
Asbestos Survey Report                                                      S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                              March 31, 2009


                                              Asbestos Type                  Potential for   *Approx.
      Material               Location                           Condition
                                                & Percent                    Disturbance     Quantity


 9” Cream floor tile
                                               Chrysotile –
        &               Throughout building                       Good          PSD          9,000 ft2
                                                   2%
 9” Green floor tile

Bottom layer floor       1st floor Elevator    Chrysotile –
       tile              lobby, Stair well         2%             Good          PSD           196 ft2
  Black mastic                 landing             6%
                                               Chrysotile -
Fire door insulation       Second floor           25%             Good          PSD          20 doors
                                               Amosite -2%
                                               Chrysotile –
   Roof sealant              Main roof                            Good          PSD          1,240 ft2
                                                   5%
                                               Chrysotile –
   Roof sealant            Walkway roof                           Good          PSD          1,200 ft2
                                                   8%
                          Elevator control     Chrysotile –
Bakelite arc shields                                              Good          PSD          2 panels
                               panel               5%
                                                                                             2 motors
    Brake pads            Elevator motor        Presumed          Good          PSD           (2 pads
                                                                                               each)
                         Basement steam         Chrysotile -
 Black TSI mastic                                                 Good          PSD           200 ln ft
                             pipes                 7%
**9” White floor tile                          Chrysotile –
                        Rooms 042 and 043                         Good          PSD           808 ft2
   Black mastic                                 7%, 6%
 **Black mastic on      Above suspended        Chrysotile –
                                                                  Good          PSD          2,500 ln ft
    HVAC ducts              ceilings               6%
 **Black mastic on      Above suspended
                                                 Unknown          Good          PSD          2,000 ln ft
      pipe TSI              ceilings
   **Equipment
                         Basement boiler
insulation and TSI                               Unknown        Unknown         PSD          Unknown
                             room
  (not observed)
                        Crawlspace under                                                               2
     TSI debris                                 Presumed           SD           PSD           450 ft
                           front porch

ft2 = square feet           ln ft = linear feet
PSD = Potential for Significant Disturbance            SD = Significantly Damaged
*Note: The quantities are estimated and should be field verified for bidding purposes.
** Note: ACM identified by Davis & Floyd in report dated January 1990. Quantities, conditions, asbestos
type and % are from Davis & Floyd or based on current observations and samples.



The identified asbestos-containing roofing materials/sealants, floor tiles and floor tile
mastic are classified as Category I non-friable materials, in good condition. The
identified window glazing, ceiling tile mastics, arc shields, elevator brake pads, TSI
mastics and duct mastic are classified as Category II non-friable materials, in good
condition. The identified, thermal system insulation (debris, wraps, and hard joints), fire
door insulation and joint compound are classified as friable materials in good condition.
All of the identified ACM are considered to have a significant potential for disturbance


                                                     2
Asbestos Survey Report                                            S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                    March 31, 2009


should the structure be subject to demolition or renovation. No asbestos in
concentrations >1% was detected in the remaining samples of suspect materials collected
from the building.

The EPA and SCDHEC require proper removal and disposal of ACMs that will be
destructively affected by renovation and/or demolition activities, therefore we
recommend the identified ACMs be properly removed and disposed by a qualified
abatement contractor licensed by SCDHEC prior to any renovation or demolition
activities. A copy of this report should also be provided to the contractor(s) to assist with
compliance with the applicable State and Federal regulations. If additional suspect
materials are discovered during future renovation or demolition activities, bulk samples
must be collected and analyzed for asbestos content.

A copy of this assessment report must be submitted to SCDHEC, along with a demolition
license application, 10 weekdays prior to demolition activities.




                                               3
Asbestos Survey Report                                             S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                     March 31, 2009



1.      BACKGROUND

S&ME was contracted to perform an asbestos survey of the Williams building located on
the SCDMH Bull Street Campus in Columbia, South Carolina. The purpose of the
assessment was to identify asbestos-containing materials (ACMs) in the building.

The Williams building is a two-story masonry block structure on a pillar foundation with
a finished basement and crawlspace. The building was reportedly constructed in 1938
and contains approximately 79,366 square feet of interior space. The building has a flat,
built-up bituminous roof. Interior finishes include concrete floors that are mostly
covered with terracotta tiles or ceramic tiles. Other areas are finished with nine-inch or
2-inch vinyl floor tiles. Walls are generally plaster, with some renovated areas having
painted sheetrock walls. Ceilings are finished with a mixture of adhered 12-inch acoustic
tiles, 12-inch acoustic tiles adhered to a dropped ceiling in the hallways and suspended 2’
x 4’ or 2’ x 2’ acoustic tiles. Thermal system insulation (TSI) is present throughout the
building on the pipes associated with the heating and cooling system. This structure was
formerly used as a hospital and a patient ward and is currently vacant.

S&ME reviewed an asbestos survey report of this building prepared by Davis & Floyd,
Inc. dated January 1990. A copy of this report is presented in Appendix V. The January
1990 report discusses the June 1988 and December 1989 asbestos surveys of the subject
building that included the collection of approximately 50 bulk samples from various
materials throughout the building. Of the samples of suspect ACM collected by Davis &
Floyd in 1988 and 1989, asbestos was determined to be present in the following
materials:

        •   White and green floor tile in Rooms 101 and 102 (currently Rooms 042 and
            043)
        •   Black bituminous duct insulation sealant and pipe sealant throughout the
            building
        •   12-inch ceiling tiles on the first and second floors
        •   General debris in the crawlspace on the western end of the building and below
            the front entrance
        •   Pipe insulation and hard joint insulation in the boiler room and Room 100
        •   Insulation on the surge tank and condensate tank in the boiler room
        •   Roof flashing on the roof

The purpose of the assessment was to verify the presence of asbestos-containing
materials (ACMs) in the building as reported by Davis & Floyd (1990), and to perform
supplemental bulk sampling and analysis to conform with the South Carolina Department

                                               4
Asbestos Survey Report                                          S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                  March 31, 2009


of Health and Environmental Control (SCDHEC) Regulation 61-86.1 Standards of
Performance for Asbestos Projects effective June 27, 2008. The identification of ACMs
will aid in the prevention of occupational exposures and/or environmental releases of
airborne asbestos. Identification of ACMs also complies with Title 40 Code of the
Federal Regulations, part 61, and State regulation 61-86.1 enforced by the SCDHEC,
along with Title 29 Code of Federal Regulations, part 1926 enforced by OSHA. The
following sections describe the investigative procedures used, results of the suspect
ACMs sampled and analyzed, and conclusions and recommendations regarding the
structure as related to ACMs.

2.      ASSESSMENT PROCEDURES

The assessment was performed by observing and collecting statistically random samples
of suspect asbestos-containing materials associated with the interior and exterior of the
structure. The possibility exists that suspect materials were not detected in inaccessible
areas such as flooring overlays, pipe chases or wall voids. If additional suspect materials
are discovered during future renovation or demolition activities, bulk samples should be
collected and analyzed for asbestos content.

A sampling strategy was developed to provide representative samples in accordance with
OSHA, SCDHEC and EPA. Bulk samples were then extracted from suspect ACMs and
recorded on a chain of custody record and submitted to our in house Polarized Light
Microscopy (PLM) laboratory. Non-friable organically bound materials requiring
confirmation by Transmission Electron Microscopy (TEM) were submitted to EMSL
Analytical for analysis. The laboratories are accredited by the National Voluntary
Laboratory Accreditation Program (NVLAP), which is administered by the National
Institute of Standards and Technology.

Polarized Light Microscopy (PLM)
The suspect materials were analyzed by trained microscopists using PLM techniques
coupled with dispersion staining in accordance with EPA Test Method Title 40 Code of
Federal Regulations, Chapter I (1-1-87 edition), Part 763, Subpart F-APPENDIX A. This
method identifies asbestos mineral fibers based on six optical characteristics:
morphology, birefringence, refractive index, extinction angle, sign of elongation and
dispersion staining colors. The laboratory analysis reports the specific type of asbestos
identified (there are six asbestos minerals) and the percentage of asbestos present.

Transmission Electron Microscopy (TEM)
Suspect non-friable organically bound materials, exhibiting negative results by PLM
analysis, were analyzed by trained microscopists by TEM using EPA 600 Method in
accordance with ASTM E2356.



                                               5
Asbestos Survey Report                                                      S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                              March 31, 2009


3.         FINDINGS AND RESULTS

The asbestos assessment conducted on October 9 & 13, 2008, included the quantification
and statically random bulk sampling of various suspect asbestos-containing materials
located on the interior and exterior of the structure. These materials include: various
acoustic ceiling tiles, plaster and skim coat, thermal system insulation (TSI), hard joint
material, window glazing compounds, sheetrock, joint compound, various vinyl floor
tiles and mastics, electrical arc shields, bituminous sealants on ductwork and TSI, various
vinyl baseboards and mastics, fire door insulation and roofing materials. Of the
representative materials sampled and analyzed, asbestos in concentrations >1% was
identified in the following materials summarized below:

                                               Asbestos Type                Potential for   *Approx.
        Material             Location                           Condition
                                                 & Percent                  Disturbance     Quantity

                         On sheetrock in        Chrysotile –
 Joint compound                                                  Good           PSD         1,500 ft2
                           basement                 2%
     12” ceiling tile   Lobbies, dayrooms,      Chrysotile -
                                                                 Good           PSD         10,000 ft2
         mastic         meeting rooms, etc         6%
Dark brown ceiling        Above dropped         Chrysotile -
                                                                 Good           PSD         6,000 ft2
    tile mastic         ceilings in hallways       6%
                                               Chrysotile -6%
     Hard joint          Basement pipes
                                                  Amosite -      Good           PSD         300 joints
 Black pipe mastic        with fiberglass
                                                    2%
                                                Chrysotile –                                  278
 Window glazing         Exterior of windows                      Good           PSD
                                                    2%                                      windows

9” Cream floor tile
                                                Chrysotile –
       &                Throughout building                      Good           PSD         9,000 ft2
                                                    2%
9” Green floor tile

Bottom layer floor       1st floor Elevator     Chrysotile –
       tile              lobby, Stair well          2%           Good           PSD          196 ft2
  Black mastic                 landing              6%
                                               Chrysotile -
Fire door insulation       Second floor           25%            Good           PSD         20 doors
                                               Amosite -2%
                                                Chrysotile –                                           2
     Roof sealant            Main roof                           Good           PSD         1,240 ft
                                                    5%
                                                Chrysotile –
     Roof sealant          Walkway roof                          Good           PSD         1,200 ft2
                                                    8%
                          Elevator control      Chrysotile –
Bakelite arc shields                                             Good           PSD         2 panels
                               panel                5%
                                                                                            2 motors
      Brake pads          Elevator motor         Presumed        Good           PSD          (2 pads
                                                                                              each)
                         Basement steam         Chrysotile -
 Black TSI mastic                                                Good           PSD         200 ln ft
                             pipes                 7%




                                                     6
Asbestos Survey Report                                                      S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                              March 31, 2009


                                              Asbestos Type                  Potential for   *Approx.
        Material            Location                            Condition
                                                & Percent                    Disturbance     Quantity

**9” White floor tile                          Chrysotile –
                        Rooms 042 and 043                         Good          PSD           808 ft2
   Black mastic                                 7%, 6%
 **Black mastic on      Above suspended        Chrysotile –
                                                                  Good          PSD          2,500 ln ft
    HVAC ducts              ceilings               6%
 **Black mastic on      Above suspended
                                                 Unknown          Good          PSD          2,000 ln ft
      pipe TSI              ceilings
   **Equipment
                         Basement boiler
insulation and TSI                               Unknown        Unknown         PSD          Unknown
                             room
  (not observed)
                        Crawlspace under
    TSI debris                                  Presumed           SD           PSD           450 ft2
                           front porch

ft2 = square feet           ln ft = linear feet
PSD = Potential for Significant Disturbance            SD = Significantly Damaged
*Note: The quantities are estimated and should be field verified for bidding purposes.
** Note: ACM identified by Davis & Floyd in report dated January 1990. Quantities, conditions, asbestos
type and % are from Davis & Floyd or based on current observations and samples.

The EPA classifies ACMs into two categories: friable and non-friable. A friable material
creates a greater health hazard due to the fact that it may be "crumbled, pulverized or
reduced to powder by the forces expected to act upon it in the course of demolition or
renovation operations." The identified asbestos-containing roofing materials/sealants,
floor tiles and floor tile mastic are classified as Category I non-friable materials, in good
condition. The identified window glazing, ceiling tile mastics, arc shields, elevator brake
pads, TSI mastics and duct mastic are classified as Category II non-friable materials, in
good condition. The identified, thermal system insulation (debris, wraps, and hard
joints), fire door insulation and joint compound are classified as friable materials in good
condition. All of the identified asbestos-containing materials are considered to have a
significant potential for disturbance during future renovation/demolition activities. No
asbestos in concentrations >1% was detected in the remaining suspect materials sampled
and analyzed from the structure.

TEM analysis was performed on eight samples of non-friable, organically-bound
materials that tested negative for asbestos via PLM analysis. These materials are:

    •      Brown mastic associated with 12-inch textured ceiling tiles
    •      Brown vinyl baseboard and mastic
    •      Dark brown vinyl baseboard and mastic
    •      Black six-inch vinyl baseboard and mastic
    •      Dark brown vinyl stairtread and mastic
    •      Green 12-inch vinyl floor tile and mastic from the elevators
    •      Beige vinyl baseboard and mastic


                                                     7
Asbestos Survey Report                                           S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                   March 31, 2009


    •   Roofing paper

The TEM analysis confirmed that no asbestos is present in the samples that were
analyzed. No additional TEM analysis was warranted in this assessment for the other
negative PLM results obtained for organically bound materials because they were
reported in materials associated with materials that tested positive for the presence of
asbestos. These materials (e.g. mastics associated with positive floor tiles or multiple
layers of flooring in the elevator lobby) should be considered to be asbestos-containing
due to their association with confirmed ACM.

Rooms 042 and 043 (formerly rooms 101 and 102) were inspected for the presence of the
asbestos-containing floor tiles identified by Davis & Floyd in 1990. Nine-inch white
floor tiles with green streaks are present in both the rooms. Three bulk samples of the
floor tiles and mastic were collected as part of this assessment. The floor tiles and mastic
were reported to contain 7% and 6% chrysotile, respectively.

The crawlspaces and areas above the suspended or dropped ceilings throughout the
building were inspected for the presence of the asbestos-containing bituminous pipe
insulation sealant and duct insulation sealant identified by Davis & Floyd in 1990. The
bituminous sealant was observed on ductwork and pipe insulation above the suspended
ceiling in the basement. The bituminous sealant on ductwork was also noted above the
suspended ceilings near the nurses’ stations. The duct sealant was sampled and reported
to contain 6% chrysotile.

The building was inspected for the presence of the asbestos-containing 12-inch ceiling
tiles reported by Davis & Floyd in 1990 to be present on the first and second floors. At
least three varieties of 12-inch ceiling tiles were identified and sampled in the building
and none of the tiles were reported to contain asbestos. However, the brown mastic
associated with the smooth and stippled 12-inch ceiling tiles that are present in the
dayrooms, meeting rooms and front lobby was reported to contain 6% chrysotile.
Additionally, brown mastic is present on the original ceilings in the hallways above the
current dropped ceiling. This mastic was also reported to contain 6% chrysotile.

The boiler room was inspected for the presence of the asbestos-containing equipment
insulation (on a surge tank and condensate tank) as well as asbestos-containing pipe
insulation and hard joint material. No suspect equipment insulation or TSI was observed
in the boiler room. The boiler room appears to have been abated and the insulation that
was observed appeared to be non-suspect fiberglass.

The roof was inspected for the presence of the asbestos-containing roof flashing
identified by Davis & Floyd in 1990. Four bulk samples of the roofing paper were
collected and none of the samples were reported to contain asbestos. Four samples of


                                               8
Asbestos Survey Report                                         S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                 March 31, 2009


roofing sealant were collected from the edges of the roof of the Williams building. One
of the samples was reported to contain 5% chrysotile.

The crawlspaces of the building were inspected for the presence of the asbestos-
containing TSI debris reported by Davis & Floyd in 1990. No evidence of pipe TSI, hard
joint material or debris was observed in the western crawlspace. Apparent Aircell pipe
insulation debris was observed in the crawlspace under the front steps.

The following summary table exhibits the sample number, location, type of material
tested, approximate quantity of the material sampled, condition of the material, and
corresponding result for each sample. A diagram exhibiting the bulk sample locations
and locations of the confirmed asbestos containing materials is provided in Appendix I.
Photographs of building conditions and select ACM are included in Appendix II. A copy
of the inspector’s SCDHEC license is provided in Appendix III, and the laboratory
analyses and chain-of-custody records are provided in Appendix IV.




                                               9
Asbestos Survey Report                                                                                                     S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                                                                             March 31, 2009

     TABLE I: SUMMARY OF ASBESTOS BULK SAMPLE ANALYSIS
                                                                POLARIZED LIGHT MICROSCOPY
Sample                                                                              Approx.        Asbestos
                          Location                           Material                                           Percent2   Condition   P.F.D.3   H.A.4
  No.                                                                               Quantity1        Type
            st
           1 Floor, western hall ceiling (Room              Sheetrock                                 ND          NA          NA         NA       NA
 SRC-1
                          119)                           Joint compound                               ND          NA          NA         NA       NA

            st
           1 Floor, eastern hall ceiling (Room              Sheetrock               3,920 ft2         ND          NA          NA         NA       NA
 SRC-2
                          190)                           Joint compound                               ND          NA          NA         NA       NA

            nd
           2     Floor, eastern hall ceiling (Room          Sheetrock                                 ND          NA          NA         NA       NA
 SRC-3
                             258)                        Joint compound                               ND          NA          NA         NA       NA

 SRP-1                    Room 101                     Sheetrock partition                            ND          NA          NA         NA       NA

 SRP-2                   Room 184A                     Sheetrock partition          3,360 ft2         ND          NA          NA         NA       NA

 SRP-3                    Room 207                     Sheetrock partition                            ND          NA          NA         NA       NA

           Basement, Room 006, post office                 Sheetrock                                  ND          NA
 SRB-1                                                                                                                     Good, F      PSD        3
                       wall                             Joint compound                             Chrysotile     2%

               Basement, Room 006 dictation                Sheetrock                                  ND          NA
 SRB-2                                                                                                                     Good, F      PSD        3
                       office wall                      Joint compound                         2   Chrysotile     2%
                                                                                    1,500 ft
 SRB-3              Basement, Room 015                      Sheetrock                                 ND          NA          NA         NA       NA

                                                           Sheetrock                                  ND          NA
 SRB-4           Basement room 074 (salon)                                                                                 Good, F      PSD        3
                                                        Joint compound                             Chrysotile     2%

                                                            Sheetrock                                 ND          NA          NA         NA       NA
 SR2-1            2nd floor offices, room 252
                                                         Joint compound                               ND          NA          NA         NA       NA

                                                            Sheetrock                          2      ND          NA          NA         NA       NA
 SR2-2            2nd floor offices, room 262                                       1,680 ft
                                                         Joint compound                               ND          NA          NA         NA       NA

                                                            Sheetrock                                 ND          NA          NA         NA       NA
 SR2-3            2nd floor offices, room 249
                                                         Joint compound                               ND          NA          NA         NA       NA

 CT-1            Basement, dining room 049           2’ x 4’ Ceiling tile (grey)    1,600 ft2         ND          ND          NA         NA       NA



                                                                               10
Asbestos Survey Report                                                                                               S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                                                                       March 31, 2009

     TABLE I: SUMMARY OF ASBESTOS BULK SAMPLE ANALYSIS
                                                            POLARIZED LIGHT MICROSCOPY
Sample                                                                           Approx.     Asbestos
                         Location                         Material                                        Percent2   Condition   P.F.D.3   H.A.4
  No.                                                                            Quantity1     Type

 CT-2          Basement, dining room 052         2’ x 4’ Ceiling tile (grey)                    ND          ND          NA         NA       NA
                                                                                 1,600 ft2
 CT-3            Basement by room 060            2’ x 4’ Ceiling tile (grey)                    ND          ND          NA         NA       NA

 CT-4            Basement by room 058            2’ x 4’ Ceiling tile (white)                   ND          ND          NA         NA       NA

 CT-5        Hall by nurse’s station, room 110   2’ x 4’ Ceiling tile (white)    2,200 ft2      ND          ND          NA         NA       NA

 CT-6            Hall, by office, room 170       2’ x 4’ Ceiling tile (white)                   ND          ND          NA         NA       NA

 CT-7          Basement, dining room 049         2’ x 4’ Ceiling tile (pink)                    ND          ND          NA         NA       NA

 CT-8            Ward 118, by room 129           2’ x 4’ Ceiling tile (pink)     1,400 ft2      ND          ND          NA         NA       NA

 CT-9            Ward 118, by room 126           2’ x 4’ Ceiling tile (pink)                    ND          ND          NA         NA       NA

 CT-10                                               2’ x 2’ Ceiling tile                       ND          ND          NA         NA       NA

 CT-11           2nd floor office, room 251          2’ x 2’ Ceiling tile         200 ft2       ND          ND          NA         NA       NA

 CT-12                                               2’ x 2’ Ceiling tile                       ND          ND          NA         NA       NA

                                                 12” Textured ceiling tile                      ND          NA          NA         NA       NA
 CT-13          1st Floor hall by room 188
                                                      Brown mastic                              ND          NA          NA         NA       NA

                                                 12” Textured ceiling tile                      ND          NA          NA         NA       NA
 CT-14          Ward 118, near room 128
                                                      Brown mastic                              ND          NA          NA         NA       NA
                                                                                 3,920 ft2
                                                 12” Textured ceiling tile                      ND          NA          NA         NA       NA
 CT-15         2nd Floor hall near room 225
                                                       Tan mastic                               ND          NA          NA         NA       NA

 CT-15
               2nd Floor hall near room 225             Tan mastic                              ND          NA          NA         NA       NA
 (TEM)

                                                  12” Smooth ceiling tile                       ND          NA
 CT-16              Group Room 125                                               2,000 ft2                           Good, F      PSD        3
                                                      Brown mastic                           Chrysotile     6%



                                                                            11
Asbestos Survey Report                                                                                                   S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                                                                           March 31, 2009

     TABLE I: SUMMARY OF ASBESTOS BULK SAMPLE ANALYSIS
                                                             POLARIZED LIGHT MICROSCOPY
Sample                                                                            Approx.        Asbestos
                        Location                          Material                                            Percent2   Condition   P.F.D.3   H.A.4
  No.                                                                             Quantity1        Type

                                                   12” Smooth ceiling tile                          ND          NA
 CT-17            Lounge, Room 107                                                                                       Good, F      PSD        3
                                                       Brown mastic                              Chrysotile     6%
                                                                                             2
                                                                                  2,000 ft
                                                   12” Smooth ceiling tile                          ND          NA          NA         NA       NA
 CT-18            Dayroom, Room 276
                                                        Tan mastic                                  ND          NA          NA         NA       NA

                                                   12” Stippled ceiling tile                        ND          NA
 CT-19             Group Room 125                                                                                        Good, F      PSD        3
                                                       Brown mastic                              Chrysotile     6%

                                                   12” Stippled ceiling tile                        ND          NA
 CT-20            Lounge, Room 107                                                8,000 ft2                              Good, F      PSD        3
                                                       Brown mastic                              Chrysotile     6%

                                                   12” Stippled ceiling tile                        ND          NA          NA         NA       NA
 CT-21            Dayroom, Room 276
                                                         Tan mastic                                 ND          NA          NA         NA       NA

 CM-1        1st Floor hallway by Room 168       Brown ceiling tile mastic                       Chrysotile     6%       Good, F      PSD        3

 CM-2        1st Floor hallway by Room 126       Brown ceiling tile mastic        6,000 ft2      Chrysotile     6%       Good, F      PSD        3

 CM-3       2nd Floor hallway by room 237A       Brown ceiling tile mastic                       Chrysotile     6%       Good, F      PSD        3

 WF-1        Covered walkway by driveway                                                         Chrysotile     8%       Good, F      PSD        3

 WF-2        Covered walkway by driveway                                                     2   Chrysotile     8%       Good, F      PSD        3
                                                Bituminous sealant/flashing       1,200 ft

           Upper level of covered walkway in
 WF-3                                                                                            Chrysotile     8%       Good, F      PSD        3
                    building corner

              Steam pipe, above ceiling in     Bituminous sealant over sulfur
 PM-1                                                                             200 ln ft      Chrysotile     7%       Good, F      PSD        3
                basement and east hall                   rock TSI

                                               Bituminous sealant on HVAC
 MAC-1          Basement above ceiling                                                           Chrysotile     6%       Good, F      PSD        3
                                                         ducts
                                                                                  2,500 ln ft
                                               Bituminous sealant on HVAC
 MAC-2     Hall by nurse’s station, room 110                                                     Chrysotile     6%       Good, F      PSD        3
                                                         ducts



                                                                             12
Asbestos Survey Report                                                                                                      S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                                                                              March 31, 2009

     TABLE I: SUMMARY OF ASBESTOS BULK SAMPLE ANALYSIS
                                                             POLARIZED LIGHT MICROSCOPY
Sample                                                                                Approx.       Asbestos
                              Location                     Material                                              Percent2   Condition   P.F.D.3   H.A.4
  No.                                                                                 Quantity1       Type

                                                 Bituminous sealant on HVAC
 MAC-3            Hall, by office, room 170                                           2,500 ln ft   Chrysotile     6%       Good, F      PSD        3
                                                           ducts

           Basement above ceiling on water            Black sealant/wrap                            Chrysotile     6%
  HJ-1                                                                                                                      Good, F      PSD        3
                       pipes                          Hard joint material                            Amosite       2%
                                                                                      300 joints
           Basement above ceiling on water            Black sealant/wrap                            Chrysotile     6%
  HJ-2                                                                                                                      Good, F      PSD        3
                       pipes                          Hard joint material                            Amosite       2%

 FD-1             Basement boiler room door           Fire door insulation                             ND          NA          NA         NA       NA
                                                                                      20 doors
               nd                                                                                   Chrysotile    25%
 FD-2         2     floor elevator lobby door        Fire door insulation                                                   Good, F      PSD        3
                                                                                                     Amosite       2%

  P-1                         Basement                      Plaster                                    ND          NA          NA         NA       NA

  P-2                         Basement                      Plaster                                    ND          NA          NA         NA       NA

  P-3                         Basement                      Plaster                                    ND          NA          NA         NA       NA

                                                           Plaster                                     ND          NA          NA         NA       NA
  P-4                       1st Floor Lobby
                                                          Skim coat                   110,000 ft2      ND          NA          NA         NA       NA

                                                           Plaster                                     ND          NA          NA         NA       NA
  P-5                          1st Floor
                                                          Skim coat                                    ND          NA          NA         NA       NA

  P-6                 2nd Floor dayroom                     Plaster                                    ND          NA          NA         NA       NA

  P-7               2nd Floor elevator lobby                Plaster                                    ND          NA          NA         NA       NA

                                                Brown vinyl baseboard        Mastic                    ND          NA          NA         NA       NA
 BB-1                1st Floor, Room 167
                                                                                                       ND          NA          NA         NA       NA
                                                                                       110 ln ft
                       st                       Brown vinyl baseboard        Mastic                    ND          NA          NA         NA       NA
 BB-2                1 Floor, Room 168
                                                                                                       ND          NA          NA         NA       NA




                                                                             13
Asbestos Survey Report                                                                                              S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                                                                      March 31, 2009

     TABLE I: SUMMARY OF ASBESTOS BULK SAMPLE ANALYSIS
                                                             POLARIZED LIGHT MICROSCOPY
Sample                                                                            Approx.     Asbestos
                             Location                     Material                                       Percent2   Condition   P.F.D.3   H.A.4
  No.                                                                             Quantity1     Type

                                               Brown vinyl baseboard     Mastic                 ND         NA          NA         NA       NA
 BB-3              1st Floor, Room 168
                                                                                                ND         NA          NA         NA       NA
                                                                                  110 ln ft
  BB-3                  st                     Brown vinyl baseboard     Mastic                 ND         NA          NA         NA       NA
                   1 Floor, Room 168
 (TEM)                                                                                          ND         NA          NA         NA       NA

                                                 Dark brown vinyl baseboard                     ND         NA          NA         NA       NA
 BB-4            1st Floor elevator lobby
                                                        Yellow mastic                           ND         NA          NA         NA       NA

                                                 Dark brown vinyl baseboard                     ND         NA          NA         NA       NA
 BB-5            1st Floor elevator lobby
                                                        Yellow mastic                           ND         NA          NA         NA       NA
                                                                                   40 ln ft
                   st                            Dark brown vinyl baseboard                     ND         NA          NA         NA       NA
 BB-6            1 Floor elevator lobby
                                                        Yellow mastic                           ND         NA          NA         NA       NA

  BB-6                                           Dark brown vinyl baseboard                     ND         NA          NA         NA       NA
                 1st Floor elevator lobby
 (TEM)                                                  Yellow mastic                           ND         NA          NA         NA       NA

                                                   6” black vinyl baseboard                     ND         NA          NA         NA       NA
 BB-7            1st Floor office, hallway
                                                         Yellow mastic                          ND         NA          NA         NA       NA

                                                   6” black vinyl baseboard                     ND         NA          NA         NA       NA
 BB-8            1st Floor offices, hallway
                                                         Yellow mastic                          ND         NA          NA         NA       NA
                                                                                  300 ln ft
                                                   6” black vinyl baseboard                     ND         NA          NA         NA       NA
 BB-9              1st Floor front lobby
                                                         Yellow mastic                          ND         NA          NA         NA       NA

  BB-9                                             6” black vinyl baseboard                     ND         NA          NA         NA       NA
                   1st Floor front lobby
 (TEM)                                                   Yellow mastic                          ND         NA          NA         NA       NA

                                                 Dark brown vinyl stair tread                   ND         NA          NA         NA       NA
  ST-1                  Elevator stairwell                                         180 ft2
                                                        Black mastic                            ND         NA          NA         NA       NA

  ST-1                                           Dark brown vinyl stair tread                   ND         NA          NA         NA       NA
                        Elevator stairwell
 (TEM)                                                  Black mastic                            ND         NA          NA         NA       NA




                                                                          14
Asbestos Survey Report                                                                                                   S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                                                                           March 31, 2009

     TABLE I: SUMMARY OF ASBESTOS BULK SAMPLE ANALYSIS
                                                              POLARIZED LIGHT MICROSCOPY
Sample                                                                               Approx.     Asbestos
                        Location                            Material                                          Percent2   Condition   P.F.D.3   H.A.4
  No.                                                                                Quantity1     Type

                                                  Dark brown vinyl stair tread                      ND          NA          NA         NA       NA
  ST-2              Elevator stairwell
                                                         Black mastic                               ND          NA          NA         NA       NA

                                                  Dark brown vinyl stair tread                      ND          NA          NA         NA       NA
  ST-3              Elevator stairwell                                                180 ft2
                                                         Black mastic                               ND          NA          NA         NA       NA

                                               12” Green floor tile          Black                  ND          NA          NA         NA       NA
 FT-13               South Elevator
                                                           mastic/felt                              ND          NA          NA         NA       NA

                                               12” Green floor tile          Black                  ND          NA          NA         NA       NA
 FT-14               South Elevator
                                                           mastic/felt                              ND          NA          NA         NA       NA
                                                                                       50 ft2
 FT-14                                         12” Green floor tile          Black                  ND          NA          NA         NA       NA
                     South Elevator
 (TEM)                                                     mastic/felt                              ND          NA          NA         NA       NA

                                               12” Green floor tile          Black                  ND          NA          NA         NA       NA
 FT-15               North Elevator
                                                           mastic/felt                              ND          NA          NA         NA       NA

                                                     Beige vinyl baseboard                          ND          NA          NA         NA       NA
 BB-10          1st Floor office, Room 155
                                                         Yellow mastic                              ND          NA          NA         NA       NA

                                                     Beige vinyl baseboard                          ND          NA          NA         NA       NA
 BB-11          1st Floor office, Room 155
                                                         Yellow mastic                              ND          NA          NA         NA       NA
                                                                                      60 ln ft
                                                     Beige vinyl baseboard                          ND          NA          NA         NA       NA
 BB-12          1st Floor office, Room 158
                                                         Yellow mastic                              ND          NA          NA         NA       NA

 BB-12                                               Beige vinyl baseboard                          ND          NA          NA         NA       NA
                1st Floor office, Room 158
 (TEM)                                                   Yellow mastic                              ND          NA          NA         NA       NA

  G-1         Exterior window, room 068          Window glazing compound                         Chrysotile     2%       Good, NF     PSD        3

                                                                                       278
  G-2         Exterior window, room 039          Window glazing compound                         Chrysotile     2%       Good, NF     PSD        3
                                                                                     windows

  G-3         Exterior window, post office       Window glazing compound                         Chrysotile     2%       Good, NF     PSD        3




                                                                           15
Asbestos Survey Report                                                                                                    S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                                                                            March 31, 2009

     TABLE I: SUMMARY OF ASBESTOS BULK SAMPLE ANALYSIS
                                                               POLARIZED LIGHT MICROSCOPY
Sample                                                                             Approx.        Asbestos
                        Location                            Material                                           Percent2   Condition   P.F.D.3   H.A.4
  No.                                                                              Quantity1        Type

  R-1      Roof, sides of stands, parapets, etc           Roofing paper                              ND          NA          NA         NA       NA
                                                                                   25,000 ft2
  R-2      Roof, sides of stands, parapets, etc           Roofing paper                              ND          NA          NA         NA       NA

  R-3      Roof, sides of stands, parapets, etc           Roofing paper                              ND          NA          NA         NA       NA

  R-4      Roof, sides of stands, parapets, etc           Roofing paper                              ND          NA          NA         NA       NA
                                                                                   25,000 ft2

  R-4
           Roof, sides of stands, parapets, etc           Roofing paper                              ND          NA          NA         NA       NA
 (TEM)

 RS-1             Roof, edges, joints             Roofing sealant (with silver)                   Chrysotile     5%       Good, NF     PSD        3

 RS-2               Roof, edges joint                    Roofing sealant                             ND          NA          NA         NA       NA
                                                                                   1,240 ft2
 RS-3               Roof, edges joint                    Roofing sealant                             ND          NA          NA         NA       NA

 RS-4               Roof, edges joint                    Roofing sealant                             ND          NA          NA         NA       NA

                                                  9” White floor tile with green                  Chrysotile     7%
  FT-1            Basement, room 043                                                                                      Good, NF     PSD        3
                                                          Black mastic                            Chrysotile     6%

                                                  9” White floor tile with green          2       Chrysotile     7%
  FT-2            Basement, room 043                                                808 ft                                Good, NF     PSD        3
                                                          Black mastic                            Chrysotile     6%

                                                  9” White floor tile with green                  Chrysotile     7%
  FT-3            Basement, room 042                                                                                      Good, NF     PSD        3
                                                          Black mastic                            Chrysotile     6%

                                                    9” Cream vinyl floor tile                     Chrysotile     2%
  FT-4         Basement, west stairwell                                                                                   Good, NF     PSD        3
                                                          Black mastic                               ND          NA

                                                    9” Cream vinyl floor tile                 2   Chrysotile     2%
  FT-5          Basement, records room                                             4,500 ft                               Good, NF     PSD        3
                                                          Black mastic                               ND          NA

                                                    9” Cream vinyl floor tile                     Chrysotile     2%
  FT-6          1st floor office, room 140                                                                                Good, NF     PSD        3
                                                          Black mastic                               ND          NA



                                                                           16
Asbestos Survey Report                                                                                                             S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                                                                                     March 31, 2009

     TABLE I: SUMMARY OF ASBESTOS BULK SAMPLE ANALYSIS
                                                                      POLARIZED LIGHT MICROSCOPY
Sample                                                                                     Approx.        Asbestos
                             Location                               Material                                           Percent2    Condition   P.F.D.3   H.A.4
  No.                                                                                      Quantity1        Type

                                                          9” Green vinyl floor tile                       Chrysotile     2%
  FT-7             Basement, west stairwell                                                4,500 ft2                               Good, NF     PSD        3
                                                               Black mastic                                  ND          NA

                                                          9” Green vinyl floor tile                       Chrysotile     2%
  FT-8             Basement, records room                                                                                          Good, NF     PSD        3
                                                               Black mastic                                  ND          NA
                                                                                                      2
                                                                                           4,500 ft
                       st                                 9” Green vinyl floor tile                       Chrysotile     2%
  FT-9                1 floor office, room 140                                                                                     Good, NF     PSD        3
                                                               Black mastic                                  ND          NA

                                                          12” Off-white vinyl floor tile                     ND          NA
                 st                                               Tan mastic                                 ND          NA
 FT-10          1 floor office, elevator lobby                                                                                     Good, NF     PSD        3
                                                          2nd layer brown floor tile                      Chrysotile     2%
                                                                Black mastic                              Chrysotile     6%

                                                          12” Off-white vinyl floor tile                     ND          NA
                                                                  Tan mastic                      2          ND          NA
 FT-11        Elevator lobby, stairwell landing                                             196 ft                                 Good, NF     PSD        3
                                                          2nd layer brown floor tile                      Chrysotile     2%
                                                                Black mastic                              Chrysotile     6%

                                                          12” Off-white vinyl floor tile                     ND          NA
                                                                  Tan mastic                                 ND          NA
 FT-12        Elevator lobby, stairwell landing                                                                                    Good, NF     PSD        3
                                                          2nd layer brown floor tile                      Chrysotile     2%
                                                                Black mastic                              Chrysotile     6%

  AS             Elevator control panel, roof         Brown Bakelite arc shield            2 Panels       Chrysotile     5%        Good, NF     PSD        3


       ft2 = square feet      ND = No Asbestos Detected           F = Friable              PSD = Potential for Significant Disturbance
       ln ft = linear feet    NA = Not Applicable                 NF = Non-friable

       Note 1: The quantities are estimated, and should not be used for bidding purposes, as field conditions should be verified.
       Note 2: The EPA, SCDHEC and OSHA define a material as asbestos-containing if an asbestos content greater than one percent (>1%) is detected in a
             representative sample.
       Note 3: Potential for Disturbance
       Note 4: Hazard Assessment
       Room numbers are assigned on the building diagrams included in Appendix I




                                                                                     17
Asbestos Survey Report                                               S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                       March 31, 2009



4.      ABBREVIATIONS AND HAZARD ASSESSMENT KEY

In accordance with the EPA and SCDHEC, a confirmed ACM is assigned a hazard
assessment based on its present condition and potential for disturbance. The hazard
assessment is used as a tool for prioritization in remedial actions regarding the identified
ACM(s). The following key exhibits the criteria that compose the hazard assessment.

Present Condition

F = Friable              G = Good (Very localized limited damage)
NF = Non-friable         D = Damaged (Damage of less than 10% distributed and less than
                              25% localized)
                         SD = Significantly Damaged (Damage equal to or greater than 10%
                              distributed, 25% localized)

Potential for Future Disturbance

LPD = Low Potential for Disturbance (Contact, Vibration, and Air Erosion all of Low Concern)
PD = Potential for Disturbance (Contact, Vibration, or Air Erosion of Moderate Concern)
PSD = Potential for Significant Disturbance (Contact, Vibration, or Air Erosion of High Concern)


                                       Hazard Assessment




     Significantly
                                           Damaged                                   Good
      Damaged
                                             (D)                                      (G)
        (SD)




                               PSD             PD          LPD             PSD         PD           LPD




           7                       6           5            4               3           2            1




                                                    18
Asbestos Survey Report                                             S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                     March 31, 2009



5.       CONCLUSIONS AND RECOMMENDATIONS

The asbestos survey conducted on the Williams building located on the SCDMH Bull
Street campus in Columbia, South Carolina, identified the presence of asbestos-
containing building materials as follows:

     •   Joint compound (2% chrysotile) associated with non-asbestos containing
         sheetrock walls in the basement. The samples were collected from the office area,
         records room and post office located in the eastern wing and from the salon
         located in the north wing – approximately 1,500 square feet.
     •   Dark brown mastic (6% chrysotile) associated with the non-asbestos containing
         12-inch smooth and stippled ceiling tiles located in the lobby, dayrooms and
         meeting rooms on the first and second floor – approximately 10,000 square feet of
         ceiling tile.
     •   Dark brown mastic (6% chrysotile) from former ceiling tiles located on the
         original ceiling above the dropped ceiling in the hallways on the first and second
         floor – approximately 6,000 square feet.
     •   Hard joint material (2% amosite) and black mastic/wrap (6% chrysotile) on
         elbows of water pipes with fiberglass insulation located above the suspended
         ceiling in the basement – approximately 300 joints.
     •   Window glazing compound (2% chrysotile) located between the metal frame and
         the glass on the exterior of the windows throughout the building – approximately
         278 windows.
     •   Nine-inch cream-colored vinyl floor tiles and nine-inch green vinyl floor tiles
         (2% chrysotile) located in offices, stairwells and under carpets throughout the
         building – approximately 9,000 square feet.
     •   Brown vinyl floor tiles (2% chrysotile) and black mastic (6% chrysotile) located
         under non-asbestos containing off-white 12-inch vinyl floor tiles in the first floor
         elevator lobby and adjoining stairwell landings – approximately 196 square feet.
     •   Fire door insulation (25% chrysotile, 2% amosite). Fire doors are located
         throughout the building on the stairwells and elevator lobbies – approximately 20
         doors.
     •   Black bituminous roofing sealant (5% chrysotile) on the joints and edges of the
         building’s roof – approximately 1,240 square feet.
     •   Black bituminous sealant (8% chrysotile) on the joints and edges of the covered
         walkway roof on the north side of the building – approximately 1,200 square feet.
     •   Brown Bakelite arc shields (5% chrysotile) located on the elevator control panels
         in the elevator equipment room on the roof – approximately 2 control panels.


                                               19
Asbestos Survey Report                                           S&ME Project No. 1614-08-285
Williams Building - SCDMH Bull Street Campus                                   March 31, 2009

    •   Two white brake pads were observed on each of the two elevator motors in the
        elevator equipment room on the roof of the building. The pads were not sampled
        because the elevators were active at the time of the assessment. The pads are
        presumed to be asbestos-containing – 4 brake pads.
    •   Black insulation sealant/mastic (7% chrysotile) located on the non-asbestos
        containing sulfur rock insulation covering the steam pipe above the ceiling in the
        basement – approximately 200 linear feet.
    •   Nine-inch white vinyl floor tiles with green streaks (7% chrysotile) and associated
        black mastic (6% chrysotile) located in rooms 101 and 102 in the basement –
        approximately 808 square feet.
    •   Black mastic/sealant (6% chrysotile) on HVAC duct insulation above the
        suspended ceilings throughout the building – approximately 2,500 linear feet.
    •   Previously identified black mastic/sealant on fiberglass pipe insulation located
        above the suspended ceilings throughout the building – approximately 2,000
        linear feet.
    •   Apparent Aircell pipe TSI debris was observed in the crawlspace under the front
        porch. The surficial soil located in this crawlspace is considered to be
        contaminated with ACM – approximately 450 square feet.

The EPA and SCDHEC require proper removal and disposal of ACMs that will be
destructively affected by renovation and/or demolition activities, therefore we
recommend the identified ACMs be properly removed, transported, and disposed of by a
qualified abatement contractor licensed by SCDHEC, Asbestos Section, prior to any
renovation/demolition activities. If additional suspect materials are discovered during
future renovation/demolition activities, bulk samples must be collected and analyzed for
asbestos content. Access to areas with significantly damaged ACM should be limited to
asbestos trained personnel with proper personal protective equipment (PPE).

A copy of this assessment report must be submitted to SCDHEC, along with a demolition
license application 10 weekdays prior to demolition activities.




                                               20
                 APPENDIX I

DIAGRAM OF BULK SAMPLE LOCATIONS AND CONFIRMED
        ASBESTOS CONTAINING MATERIALS
APPENDIX II

PHOTOGRAPHS
DMH Bull St. Campus – Williams Building
S&ME Project No. 1614-08-285
Taken: October 9 & 13, 2008




Photo #1    The front of the Williams Building.        Photo #2 The rear of the Williams building. The
                                                          elevator control room is visible on the roof.




Photo #3 A small amount of window glazing is           Photo #4    9-inch white floor tiles with green streaks
    present on the windows. The glazing tested            are present in Rooms 101 & 102. The tiles and
    positive for asbestos (2% chrysotile).                mastic tested positive for asbestos (7% & 6%).




Photo #5 9-inch Cream and Green floor tiles are        Photo #6 Hard joint material (2% amosite) and
    present thru-out much of the building. The tiles      black sealant (6% chrysotile) are present on
    tested positive for asbestos (2% chrysotile).         pipes above the ceiling in the basement.
DMH Bull St. Campus – Williams Building
S&ME Project No. 1614-08-285
Taken: October 9 & 13, 2008




Photo #7 Aircell pipe insulation debris observed in    Photo #8 Brown ceiling tile mastic and black HVAC
    the crawlspace under the front porch. The debris      duct sealant (both 6% chrysotile) are present
    is presumed to contain asbestos.                      above the dropped ceilings in the hallways.




Photo #9 Brown ceiling tile mastic (6% chrysotile)     Photo #10 The interior of a fire door on the 2nd floor
    was also observed on the ceiling of some pipe          was sampled (25% chrysotile, 2% amosite).
    chases.




Photo #11 The brown Bakelite arc shields on the        Photo #12 The white brake pads located on the
    elevator control panels tested positive for            elevator motors are presumed to be asbestos-
    asbestos (5% chrysotile).                              containing.
DMH Bull St. Campus – Williams Building
S&ME Project No. 1614-08-285
Taken: October 9 & 13, 2008




Photo #13 The brown mastic associated with the 12-    Photo #14 Two layers of floor tiles are present in the
                                                            st                           nd
    inch ceiling tiles (smooth and stippled) tested       1 floor elevator lobby. The 2 layer and mastic
    positive for asbestos (6% chrysotile).                tested positive for asbestos (2%, 6% chrysotile).
               APPENDIX III

COPY OF SCDHEC INSPECTOR AND/OR MANAGEMENT
             PLANNER LICENSES
  South Carolina Department
               of
Health and Environmental Control
        Asbestos License


        Owen R. Astwood




      Air Sampler AS-00226
    Building Inspector BI-00475
    Project Designer PD-00085
   Asbestos Supervisor SA-01241
                  APPENDIX IV

ASBESTOS BULK SAMPLE ANALYSIS SHEETS AND CHAIN OF
                CUSTODY RECORDS
            APPENDIX V

DAVIS & FLOYD ASBESTOS SURVEY REPORT

				