AC DC POWER SUPPLY PRIMARY SWITCHED MODE SINGLE OUTPUT PH
Document Sample


AC / DC POWER SUPPLY
PRIMARY SWITCHED MODE
SINGLE OUTPUT
PH 1003 SERIES
– 3 x 340 - 550 V wide range input
– Optional power factor correction (PFC)
– IT-Net suitable
– Mains input protected by fuse
– Mains buffering 15 - 27 ms
– Output adjustable
– Parallel connection with load sharing
– Power boost with high start-up current
– Output SELV according to EN 60950
– Diverse control and load signals
– Primary/secondary overvoltage protection
– Overtemperature protection
– Operational in every installation position by
integrated fan
– EMC standards EN 50081-1 and EN 50082-2
b e a n st a
w er lt
ge
Ba
es
L and
yer
n
✱ ✱
ht
bau
ac
420
ar
rw
ge e
t
prü b
ft und ü
R
3
Years
Guarantee!
230 230
136.5
127
125
125
200
190
180
160
Din-rail mounting Wall mounting
ORDER DATA Order numbers in italics Please ensure a distance of approx. 50 mm of the air
Vo Io Type-No. Type-No. inlet openings at the front of the housing and of the air
V A DIN-rail Wall mounting outlet openings at the top and at the bottom of the
device from surrounding components or surfaces.
24 0 - 40 PH1003-2440 PH1003-2440 Also make sure during installation that outgoing air
15.8041.200 15.8041.205
will not be once more sucked into the device.
24 0 - 40 PH1003-2440PFC PH1003-2440PFC
15.8041.600 15.8041.605
Further output voltages (e.g. 48 V, 60 V) and additional features
upon request
MGV Stromversorgungen GmbH · Bayerwaldstraße 27 · 81737 München · Germany
Tel. +49 / 89 / 67 80 90-0 · Fax +49 / 89 / 67 80 90 80 · Email: info@mgv.de · Internet: www.mgv.de
AC / DC POWER SUPPLY
PRIMARY SWITCHED MODE
SINGLE OUTPUT
PH 1003 SERIES
INPUT EMC
Input voltage range AC 3 x 340 - 550 V, 50/60 Hz Mains feedback (PFC) EN 61000-3-2: 1995 Class A
Efficiency 90% applicable for PFC model only!
Input current limitation < 50 Apeak typ. – in cold state Interference suppression/ EN 50082-2: 1995
< 100 Apeak typ. – in hot state interference immunity EN 61000-4-2 Intensity 4
EN 61000-4-3 Noise level 10 V/m
Fuse Internal fuse with 3 x 5 AT
EN 61000-4-4 Intensity 4
External fuse sufficient up to max. 32 A
EN 61000-4-5 Intensity 4
OUTPUT EN 61000-4-6 Noise level 10 V
Adjustment range 22 - 29 V factory preset at 24 V / ±0.1 V EN 61000-4-11
Max. output 960 W Interference emission EN 50081-1, EN 55011 / EN 55022 Class B
Operation indicator Green LED for Vo, red LED for errors interference transmission depends on
assembly
Ripple typ. 80 mVpp
OPERATING DATA
Noise voltage typ. 100 mVpp typ. (band width 20 MHz)
Temperature coefficient ≤ 0.025% / K Temperature range 0...+70°C, internal, temperature-controlled
ventilator, air intake at the front
Switch on/switch off No overshooting of Vo (soft-start)
performance Derating 3% / K at +60°C (see diagram)
Rise-delay time ≤ 0.1 s Weight Without PFC approx. 2.4 kg
With PFC approx. 2.8 kg
Run-up time typ. 5 ms / 60 ms at 100.000 µF load
REGULATION In general, kindly refer to the MGV user instructions before use.
Fire protection has to be ensured by the surrounding housing system.
Line regulation < 0.2% for Vo at Vimin - Vimax
MECHANICS
Load regulation < 0.5% for Vo at Io 0 - 100%
for single operation Connection Mains input: 4-poles
0.75 - 10/16 mm2 strand/wire
< 3% for Vo at Io 0 - 100%
for parallel operation Load output: 4-poles
2.5 - 10/16 mm2 strand/wire
Response time < 0.3 ms at Io 20 - 80%
Control signals: 5-poles
PROTECTION AND CONTROLLING
0.15 - 2.5 mm2
Overvoltage protection 29 - 34 V automatically repeating Assembly All systems can be snapped onto a sym-
Current limitation 105 - 140% Inominal (see diagram), metrical 35 x 7.5 mm DIN-rail according to
output permanent short-circuit proof DIN 50022 or mounted onto a sidewall with
Overtemperature Switches off if inside temperature becomes mounting plates.
protection too high, reconnection with hysteresis EXPLANATION
Mains buffering see diagram PE Do not use supply without PE-connection!
Monitoring signal Relay contact (< 60 V / 0.2 A), L1 / L2 / L3 Mains phases
change-over at operation /error
+ /- Load connection
Control signal OFF External switching off with > 2 - 24 V or
Relay / OK / Fail Monitoring connections
with switch from Vo
Off / Ua Control connections
SAFETY
Switching from Single- By switch at the bottom of housing
EN 60950 / VDE 0805 / VDE 113 to parallel operation
Safety Class I, VDE 0100, IP 20 mode
Sparking distance in air and leakage distance
according to VDE 0160/pr / EN 50178
UL 508 Listed / UL 1950 / CSA 22.2-950
▼
Po/%
100
70
Ta/°C ▼
Vo/%
▼
0
0 60 70 100
Derating 80
▼
t/ms
50
30 Periodical restart,
at AC 3 x 500V "Ticker operation"
20
Io/%
▼
at AC 3 x 400V 0
10 0 100 160
at AC 3 x 340V Current limiting characteristic
Vo/V
The start-up takes place with short-circuit current
0
▼
between 140% and 180% of the nominal current for a
22 24 29 period of approx. 0.4 s. Start-up frequency is approx. 0.3
Mains buffering for nominal current Hz. The average short-circuit current is about 25% Inominal
04/01
Get documents about "