									                     Snag & Inspect
                  Property Inspection Report
Cover Page




                 Green Community West, Dubai , U.A.E
                        Inspection prepared for:
               Inspection Date: 12/5/2010 Time: 10:00 hrs

                       Inspector: Douglas Ralph
                    P.O.Box. 282254, Dubai, U.A.E,
             Phone: +971 4 441 3679 Fax: +971 4 432 6016

                 Email: douglas@snagandinspect.com
                      www.snagandinspect.com
Snag & Inspect                                             Green Community West, Dubai , U.A.E

Report Summary
                                             Report Summary

 The summary below consists of potentially significant findings. These findings can be a safety
 hazard, a deficiency requiring a major expenses to correct or items I would like to draw extra
 attention to. The summary is not a complete listing of all the findings in the report, and reflects the
 opinion of the inspector. Please review all of the pages of the report as the summary alone does not
 explain all the issues. All repairs must be done by a licensed &bonded trade or profession. I
 recommend obtaining a copy of all receipts, warranties and permits for the work done.
 Inspection Details
 Page 6 Item: 5      Water Table          • Snag & Inspect Inspectors noted a big amount of standing
                                          water on the street in front of the villa and the entire area
                                          around the villa ( Pic 01,1A and 1B ).
                                           White crystals noted on the walkway in front of the house (
                                          Pic 02 and Pic 2A ) indicating presents of water and moisture
                                          in the ground under the tiles.
                                          Hole was digged in the garden in front of the main entrance
                                          of the villa. The present of the water in the ground was
                                          confirmed on ( Pic 03 and Pic 3A ).
                                          The Green Community Engineer met the Snag & Inspect
                                          Inspectors at the time of the inspections.
                                          His explanation was that the present water in the ground and
                                          the ponds of water around the villa and few different areas in
                                          the Green community is a Water Table ( standing under
                                          ground water ) as no pipe leakage was determined in the
                                          areas.
                                          According to the Engineer the water supply for the irrigation
                                          pipe lines was closed for five days and the main water supply
                                          for three days.
                                          Installation of pumps to remove the standing water from the
                                          area is the action taken by the Green Community
                                          Engineering team in order the Water Table issue to be
                                          rectified .
                                          Snag & Inspect Inspectors performed a moisture and visual
                                          inspections on the exterior walls of the house. The findings of
                                          this inspection are to be found in the section - Exterior Walls -
                                          Moisture Investigation on the exterior walls - of the report.

 A/C
 Page 8 Item: 1     General              • The chilled water supply was not SW/ON in the villa at the
                                         time of the inspection . The A/C unit is working ( only the fan
                                         blower was tested and working correctly ).The cooling to be
                                         checked once the chilled water supply is SW/ON.
 Water Heater / Water Tank
 Page 10 Item: 1 Water Heater            • The water heaters and hot water supply lines located in the
                  Condition              Kitchen , Guest Bathroom , Master Bathroom , Bedroom #03
                                         Bathroom ceilings are wrapped with plastic sheet ( if any
                                         other water heaters present in the villa to be checked as well
                                         ). The plastic sheet needs to be removed due the safety
                                         reasons .




                                                                                                Page 1 of 63
Snag & Inspect                                           Green Community West, Dubai , U.A.E

 Page 11 Item: 2   Water Tank           • The water tank pump/motor is not installed properly ( Pic 01
                   Condition            ).
                                        The pump/motor to be installed on a concrete base and
                                        bolted properly on two galvanized channels to the base.
                                        • The motor power supply wires are expose on the ground as
                                        the PVC wire conduit is broken or not fixed properly ( Pic 1A ).
                                        This a safety concern and action to be taken ASAP.
                                        • The water tank pipeline is not supported properly . Only one
                                        brick used at the moment as support ( Pic 02).
                                        The complete pipe line to be supported with clamps with the
                                        wall and the ground ( Pic 2A).
 Exterior Areas
 Page 13 Item: 1   Wall Condition       • The cracks noted on ( Pic 01 , 1A and 1B ) of the wall and
                                        outside window sill of the Guest Bathroom window to be
                                        repaired and wall re - painted.
 Page 15 Item: 2   Moisture             • The moisture level on the walls was measured and noted on
                   Investigation on     . The moisture level increases on the wall areas closer to the
                   the Extirior Walls   ground that indicates that the moisture has been sucked from
                                        underneath the ground up to the wall.
 Garage
 Page 17 Item: 2   Garage Door          • The garage door opener mechanism is not connected with
                   Condition            the garage door as the mounting bracket is missing or broken
                                        ( Pic 01 and Pic 1A ).
 Guest Bathroom - Ground Floor
 Page 24 Item: 16 Window Condition • The bathroom window broken hinge to be replaced.
 Study Room - Ground Floor
 Page 26 Item: 5 Wall Condition    • Paint blistering and peeling off from the walls next to the
                                   room windows ( Pic 01 , 1A and Pic 1B ). High level of
                                   moisture measured on the walls only on the areas close to the
                                   window edge .
                                   Possible reason for the wall damages is the window outside
                                   sill sloped towards the window not away from it. This allowed
                                   water ponding and penetrating thru the gaps on the wall noted
                                   on ( Pic 02 , 2A and Pic 2B ) . Recommended proper window
                                   sill slope to be made ( sloping away from the window ) and the
                                   gaps on the wall to be sealed.

 Master Bedroom - First Floor
 Page 37 Item: 2 Doors                  • The bedroom door is difficult to close as the top of the door
                                        rubs on the door frame ( Pic 01 ) and as a result of that
                                        damage on the door noted on ( Pic 1A ) .
                                        Door to be adjusted and damaged areas repaired and door re-
                                        painted.
 Page 39 Item: 5   Wall Condition       • Paint blistering and high level of moisture measured on the
                                        bedroom walls next to the patio doors ( Pic 01 , 1A ,1C , 02
                                        and Pic 2A ). High level of moisture measured on the left side
                                        wall of the room as well.
                                        Possible reason for the wall damages is the balcony floor
                                        sloped towards villa walls ( Master Bedroom Balcony Pictures
                                        ( Pic 01 and Pic 1A ). This allowed water ponding and
                                        moisture penetrating thru the walls .
                                        The right side wall of the room has no moisture present as the
                                        balcony floor drain is located on that side.
                                                                                             Page 2 of 63
Snag & Inspect                                         Green Community West, Dubai , U.A.E

 Master Bedroom Bathroom - First Floor
 Page 43 Item: 12 Bath Tubs          • The bath tub is not sealed properly .Caulking required
                                     around perimeter to prevent water seepage.
 Page 44 Item: 13 Enclosure          • The shower door can not be closed completely or open
                                     entirely ( the bottom of the door is rubbing on the threshold
                                     when closed and the door is getting stuck when being( half
                                     open ) ( Pic 01 and Pic 1A ) . The door and shower enclosure
                                     frame needs to be adjusted ( Pic 1B ) and if not possible
                                     removed and re - installed properly.
 Master Bedroom Balcony
 Page 45 Item: 1 Observations        • The master bedroom balcony floor slopes towards the walls
                                     of the villa allowing water ponding and moisture penetrating
                                     thru the walls ( Pic 01 and Pic 1A ).
                                     Floor tiles grout is damaged on different locations . Regrouting
                                     required.
 Bedroom #03 - First Floor
 Page 57 Item: 9 Patio Doors         • The outside glass pane of the patio sliding door is broken (
                                     Pic 01 and Pic 1A ). Needs to be replaced .




                                                                                          Page 3 of 63
Snag & Inspect                                                      Green Community West, Dubai , U.A.E

                                              Inspection Details
 1. Attendance
                                   In Attendance: Owner present
 2. Home Type
                                   Home Type: 5 B/R Villa
 3. Occupancy
                                   Occupancy: Vacant
 4. General Recommendations

                                   • We recommend fire/smoke detectors to be added to all bedrooms and the
                                   kitchen area to help protect the residents of the villa.
                                   • Recommend adding a water treatment system to the water tank to help
                                   protect the family.
 5. Water Table
 Good   Fair   Poor   N/A   None
                                   Observations:
               X                   • Snag & Inspect Inspectors noted a big amount of standing water on the
                                   street in front of the villa and the entire area around the villa ( Pic 01,1A and
                                   1B ).
                                    White crystals noted on the walkway in front of the house ( Pic 02 and Pic
                                   2A ) indicating presents of water and moisture in the ground under the tiles.
                                   Hole was digged in the garden in front of the main entrance of the villa. The
                                   present of the water in the ground was confirmed on ( Pic 03 and Pic 3A ).
                                   The Green Community Engineer met the Snag & Inspect Inspectors at the
                                   time of the inspections.
                                   His explanation was that the present water in the ground and the ponds of
                                   water around the villa and few different areas in the Green community is a
                                   Water Table ( standing under ground water ) as no pipe leakage was
                                   determined in the areas.
                                   According to the Engineer the water supply for the irrigation pipe lines was
                                   closed for five days and the main water supply for three days.
                                   Installation of pumps to remove the standing water from the area is the action
                                   taken by the Green Community Engineering team in order the Water Table
                                   issue to be rectified .
                                   Snag & Inspect Inspectors performed a moisture and visual inspections on
                                   the exterior walls of the house. The findings of this inspection are to be found
                                   in the section - Exterior Walls - Moisture Investigation on the exterior walls -
                                   of the report.




                                                                                                         Page 4 of 63
Snag & Inspect                                        Green Community West, Dubai , U.A.E




           Area in front of the house .




                                                    White crystals indicating presents of standing
                                                           water - road in front of the villa.




  White crystals indicating present of standing     Hole dug in the garden area - front side of the
  water- walkway in front of the main villa door.                       villa.


                                                                                          Page 5 of 63
Snag & Inspect   Green Community West, Dubai , U.A.E




                                          Page 6 of 63
Snag & Inspect                                                     Green Community West, Dubai , U.A.E

                                                      Electrical
 1. Electrical Panel
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • No major system safety or function concerns noted at time of inspection at
                                   main panel box.




                                                                                                      Page 7 of 63
Snag & Inspect                                           Green Community West, Dubai , U.A.E

                                                 A/C
 The heating, ventilation, and air conditioning and cooling system (often referred to as HVAC) is the
 climate control system for the structure. The goal of these systems is to keep the occupants at a
 comfortable level while maintaining indoor air quality, ventilation while keeping maintenance costs at
 a minimum. The HVAC system is usually powered by electricity and natural gas, but can also be
 powered by other sources such as butane, oil, propane, solar panels, or wood.

 The inspector will usually test the heating and air conditioner using the thermostat or other controls.
 For a more thorough investigation of the system please contact a licensed HVAC service person.
 1. General
  Good Fair Poor N/A None
                          Observations:
                 X        • The chilled water supply was not SW/ON in the villa at the time of the
                          inspection . The A/C unit is working ( only the fan blower was tested and
                          working correctly ).The cooling to be checked once the chilled water supply is
                          SW/ON.




                                                                                             Page 8 of 63
Snag & Inspect                                           Green Community West, Dubai , U.A.E

                            Water Heater / Water Tank
 1. Water Heater Condition
 Good Fair Poor N/A None
                         Observations:
            X            • The water heaters and hot water supply lines located in the Kitchen , Guest
                         Bathroom , Master Bathroom , Bedroom #03 Bathroom ceilings are
                         wrapped with plastic sheet ( if any other water heaters present in the villa to
                         be checked as well ). The plastic sheet needs to be removed due the safety
                         reasons .




                  Kitchen ceiling                                 Guest Bathroom Ceiling




              Guest Bathroom Ceiling




                                                                                              Page 9 of 63
Snag & Inspect                                           Green Community West, Dubai , U.A.E




 2. Water Tank Condition
 Good Fair Poor N/A None
                         Observations:
            X            • The water tank pump/motor is not installed properly ( Pic 01 ).
                         The pump/motor to be installed on a concrete base and bolted properly on
                         two galvanized channels to the base.
                         • The motor power supply wires are expose on the ground as the PVC wire
                         conduit is broken or not fixed properly ( Pic 1A ).
                         This a safety concern and action to be taken ASAP.
                         • The water tank pipeline is not supported properly . Only one brick used at
                         the moment as support ( Pic 02).
                         The complete pipe line to be supported with clamps with the wall and the
                         ground ( Pic 2A).




                                                                                            Page 10 of 63
Snag & Inspect   Green Community West, Dubai , U.A.E




                                         Page 11 of 63
Snag & Inspect                                                 Green Community West, Dubai , U.A.E

                                                   Grounds
 1. Driveway and Walkway Condition
 Good   Fair   Poor   N/A   None


  X

 2. Vegetation Observations
 Good   Fair   Poor   N/A   None


  X

 3. Gate Condition
 Good   Fair   Poor   N/A   None


  X

 4. Exterior Water Pipe Fittings
 Good   Fair   Poor   N/A   None


        X




                              Rusted clamp noted . To be replaced with galvanized clamp.
 5. Fence Condition
 Good   Fair   Poor   N/A   None


  X




                                                                                           Page 12 of 63
Snag & Inspect                                                     Green Community West, Dubai , U.A.E

                                                 Exterior Areas
 1. Wall Condition
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • The cracks noted on ( Pic 01 , 1A and 1B ) of the wall and outside window
                                   sill of the Guest Bathroom window to be repaired and wall re - painted.




  Rusting metal piece noted on the exterior wall -
                left side of the villa




 2. Moisture Investigation on the Extirior Walls
 Good Fair Poor N/A None
                         Observations:
      X                  • The moisture level on the walls was measured and noted on . The moisture
                         level increases on the wall areas closer to the ground that indicates that the
                         moisture has been sucked from underneath the ground up to the wall.




                                                                                                    Page 13 of 63
Snag & Inspect                       Green Community West, Dubai , U.A.E




          Front side of the house.




          Right side of the house.




                                                             Page 14 of 63
Snag & Inspect                      Green Community West, Dubai , U.A.E




           Left side of the house




                                                            Page 15 of 63
Snag & Inspect                                            Green Community West, Dubai , U.A.E

                  Windows and doors sealing condition
 1. Windows sealing condition
 Good Fair Poor N/A None
                         Observations:
  X                      • All the windows in the villa were sprayed with water from outside in order to
                         determine if they are sealed properly and determine the gaps that will allow
                         water and dirt to enter the house .The gaps on the windows were marked
                         with tape and it is recommended this gaps to be sealed .
 2. Doors sealing condition
 Good Fair Poor N/A None
                         Observations:
      X                  • All the doors in the villa were sprayed with water from outside in order to
                         determine if they are sealed properly and determine the gaps that will allow
                         water and dirt to enter the house .The gaps on the patio doors were marked
                         with tape and it is recommended this gaps to be sealed .
 3. Patio doors sealing condition
 Good Fair Poor N/A None
                         Observations:
      X                  • All the patio doors in the villa were sprayed with water from outside in order
                         to determine if they are sealed properly and determine the gaps that will
                         allow water and dirt to enter the house .The gaps on the patio doors were
                         marked with tape and it is recommended this gaps to be sealed .




                                                                                              Page 16 of 63
Snag & Inspect                                                     Green Community West, Dubai , U.A.E

                                                        Garage
 1. Floor Condition
 Good   Fair   Poor   N/A   None
                                   Observations:
               X                   • The complete garage floor is covered with cut grass, construction debris
                                   and garbage . Area to be cleaned.
 2. Garage Door Condition
 Good Fair Poor N/A None
                         Observations:
            X            • Garage vehicle door auto-reverse system not tested during the inspection
                         due the not functioning garage door opener.
                         • Eye beam system present but not tested during the inspection due the not
                         functioning garage door opener.
                         • The garage door opener mechanism is not connected with the garage door
                         as the mounting bracket is missing or broken ( Pic 01 and Pic 1A ).




                                                                                                     Page 17 of 63
Snag & Inspect                                                     Green Community West, Dubai , U.A.E

               Interior Areas + Living Room - Ground Floor
 1. Cabinets
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • No deficiencies observed.

 2. Door Bell
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • Operated normally when tested.

 3. Doors
 Good   Fair   Poor   N/A   None
                                   Observations:
               X                   • The entrance door to be sealed at the areas marked with tape ( Pic 01 , 1A
                                   and 1B ).. Refer to the general comment made for the villa doors.




                                                                                                     Page 18 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E




                 Tape marks to be cleaned.                       Area between the threshold and door frame to be
                                                                                     sealed.
 4. Electrical
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • All the electrical outlets and light switches tested and working correctly at
                                   the time of the inspection.
 5. Stairs & Handrail
 Good   Fair   Poor   N/A   None


  X

 6. A/C
 Good   Fair   Poor   N/A   None
                                   Observations:
                      X            • The chilled water supply was not SW/ON in the villa at the time of the
                                   inspection . The A/C unit is working ( only the fan blower was tested and
                                   working correctly ).The cooling to be checked once the chilled water supply is
                                   SW/ON.
 7. Window Condition
 Good   Fair   Poor   N/A   None


  X

 8. Ceiling Condition
 Good   Fair   Poor   N/A   None


  X

 9. Patio Doors
 Good   Fair   Poor   N/A   None


  X

 10. Screen Doors
 Good   Fair   Poor   N/A   None


  X



                                                                                                         Page 19 of 63
Snag & Inspect                                                      Green Community West, Dubai , U.A.E

 11. Wall Condition
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • Stain marks noted on the walls on ( Pic 01 , 1A and Pic 1B ).




 12. Floor Condition
 Good   Fair   Poor   N/A   None


  X




                                                                                                     Page 20 of 63
Snag & Inspect                                                     Green Community West, Dubai , U.A.E

                                   Guest Bathroom - Ground Floor
 1. Cabinets
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • The gap between the cabinet and the wall to be sealed to prevent water
                                   seepage.




 2. Ceiling Condition
 Good   Fair   Poor   N/A   None


  X

 3. Counters
 Good   Fair   Poor   N/A   None


  X

 4. Doors
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • The gap between the door threshold and door frame to be sealed ( Pic 01 ).




                                                                  Damage on the door wooden frame noted.


                                                                                                    Page 21 of 63
Snag & Inspect                                                         Green Community West, Dubai , U.A.E

 5. Electrical
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • All the electrical outlets and light switches tested and working correctly at
                                   the time of the inspection.
 6. GFCI
 Good   Fair   Poor   N/A   None


                      X

 7. Floor Condition
 Good   Fair   Poor   N/A   None
                                   Materials: Ceramic tile is noted.
  X

 8. Mirrors
 Good   Fair   Poor   N/A   None


  X

 9. Plumbing
 Good   Fair   Poor   N/A   None


  X

 10. Showers
 Good   Fair   Poor   N/A   None


  X




                                         The shower holder bracket cap is missing.
 11. Shower Walls
 Good   Fair   Poor   N/A   None


        X




                                                                                                         Page 22 of 63
Snag & Inspect                                                   Green Community West, Dubai , U.A.E




                                                   Grout piece missing.
 12. Bath Tubs
 Good   Fair   Poor   N/A   None


                      X

 13. Enclosure
 Good   Fair   Poor   N/A   None


  X

 14. Sinks
 Good   Fair   Poor   N/A   None


  X

 15. Toilets
 Good   Fair   Poor   N/A   None


  X

 16. Window Condition
 Good   Fair   Poor   N/A   None
                                   Observations:
               X                   • The bathroom window broken hinge to be replaced.




                                                                                         Page 23 of 63
Snag & Inspect                     Green Community West, Dubai , U.A.E




 17. Wall Condition
 Good   Fair   Poor   N/A   None


  X




                                                           Page 24 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E

                                     Study Room - Ground Floor
 1. Cabinets
 Good   Fair   Poor   N/A   None


  X

 2. Doors
 Good   Fair   Poor   N/A   None


  X




                                                  Paint drops to be cleaned.
 3. Electrical
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • All the electrical outlets and light switches tested and working correctly at
                                   the time of the inspection.
 4. Floor Condition
 Good   Fair   Poor   N/A   None
                                   Flooring Types: Ceramic tile is noted.
  X

 5. Wall Condition
 Good   Fair   Poor   N/A   None
                                   Observations:
               X                   • Paint blistering and peeling off from the walls next to the room windows (
                                   Pic 01 , 1A and Pic 1B ). High level of moisture measured on the walls only
                                   on the areas close to the window edge .
                                   Possible reason for the wall damages is the window outside sill sloped
                                   towards the window not away from it. This allowed water ponding and
                                   penetrating thru the gaps on the wall noted on ( Pic 02 , 2A and Pic 2B ) .
                                   Recommended proper window sill slope to be made ( sloping away from the
                                   window ) and the gaps on the wall to be sealed.




                                                                                                         Page 25 of 63
Snag & Inspect   Green Community West, Dubai , U.A.E




                                         Page 26 of 63
Snag & Inspect                                                     Green Community West, Dubai , U.A.E

 6. A/C
 Good   Fair   Poor   N/A   None
                                   Observations:
                      X            • The chilled water supply was not SW/ON in the villa at the time of the
                                   inspection . The A/C unit is working ( only the fan blower was tested and
                                   working correctly ).The cooling to be checked once the chilled water supply is
                                   SW/ON.
 7. Window Condition
 Good   Fair   Poor   N/A   None


        X

 8. Ceiling Condition
 Good   Fair   Poor   N/A   None


  X

 9. Patio Doors
 Good   Fair   Poor   N/A   None


                      X

 10. Screen Doors
 Good   Fair   Poor   N/A   None


                      X




                                                                                                     Page 27 of 63
Snag & Inspect                                                    Green Community West, Dubai , U.A.E

                        Kitchen + Dinning Area - Ground Floor
 The kitchen is used for food preparation and often for entertainment. Kitchens typically include a
 stove, dishwasher, sink and other appliances.
 1. Cabinets
  Good Fair Poor N/A None
                          Observations:
       X                  • The sink cabinet doors are rubbing each other with their top sections. Doors
                          needs to be aligned properly.( Pic 01 ).
                          • The cabinet doors on ( Pic 02 and Pic 2A ) are rubbing each other with
                          their top sections. Doors needs to be aligned properly.( Pic 01 ).
                          • Stain marks noted and marked with tape on the inside of the cabinet
                          doors.( Pic 03 ) to be cleaned.




 2. Counters
 Good   Fair   Poor   N/A   None


  X

 3. Doors
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • Damage seal on the kitchen door leading to the small bathroom noted on (
                                   Pic 01 ) .Caulking required around perimeter.

                                                                                                   Page 28 of 63
Snag & Inspect                                                     Green Community West, Dubai , U.A.E




                                                                Excess paint to be cleaned from the door frame.
 4. Cook top condition
 Good   Fair   Poor   N/A   None


                      X

 5. Oven & Range
 Good   Fair   Poor   N/A   None


                      X

 6. Sinks
 Good   Fair   Poor   N/A   None


  X

 7. Window Condition
 Good   Fair   Poor   N/A   None


  X

 8. Floor Condition
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • Grout pieces missing and marked with tape on the dining area floor tiles
                                   .Recommended regrouting .




                                                                                                     Page 29 of 63
Snag & Inspect                                                     Green Community West, Dubai , U.A.E




 9. Plumbing
 Good   Fair   Poor   N/A   None


  X

 10. A/C
 Good   Fair   Poor   N/A   None
                                   Observations:
                      X            • The chilled water supply was not SW/ON in the villa at the time of the
                                   inspection . The A/C unit is working ( only the fan blower was tested and
                                   working correctly ).The cooling to be checked once the chilled water supply is
                                   SW/ON.
 11. Ceiling Condition
 Good   Fair   Poor   N/A   None


  X

 12. Patio Doors
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • Scratches noted on the patio door ( Pic 01 ).
                                   • The patio door to be sealed at the areas marked with tape. Refer to the
                                   general comment made for the villa patio doors ( Pic 02).




                                                                                                     Page 30 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E

 13. Screen Doors
 Good   Fair   Poor   N/A   None


  X

 14. Electrical
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • All the electrical outlets and light switches tested and working correctly at
                                   the time of the inspection.
 15. GFCI
 Good   Fair   Poor   N/A   None


                      X

 16. Wall Condition
 Good   Fair   Poor   N/A   None


  X

 17. Refrigerator
 Good   Fair   Poor   N/A   None


                      X




                                                                                                         Page 31 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E

                                   Small Bathroom - Ground Floor
 1. Cabinets
 Good   Fair   Poor   N/A   None


  X

 2. Ceiling Condition
 Good   Fair   Poor   N/A   None


  X

 3. Counters
 Good   Fair   Poor   N/A   None


  X

 4. Doors
 Good   Fair   Poor   N/A   None


  X

 5. Electrical
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • All the electrical outlets and light switches tested and working correctly at
                                   the time of the inspection.
 6. GFCI
 Good   Fair   Poor   N/A   None


                      X

 7. Floor Condition
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • Grout pieces missing and marked with tape on the bathroom floor tiles ( Pic
                                   01 ).Recommended regrouting .
                                   • White crystals noted on the floor tiles next to the bathroom threshold
                                   indicating moisture trapped under the tiles. The type of the floor tiles did not
                                   allowed proper moisture measurements to be taken at the time of the
                                   inspection.




                                                                                                         Page 32 of 63
Snag & Inspect                     Green Community West, Dubai , U.A.E

 8. Mirrors
 Good   Fair   Poor   N/A   None


  X

 9. Plumbing
 Good   Fair   Poor   N/A   None


  X

 10. Showers
 Good   Fair   Poor   N/A   None


                      X

 11. Shower Walls
 Good   Fair   Poor   N/A   None


                      X

 12. Bath Tubs
 Good   Fair   Poor   N/A   None


                      X

 13. Enclosure
 Good   Fair   Poor   N/A   None


                      X

 14. Sinks
 Good   Fair   Poor   N/A   None


  X

 15. Toilets
 Good   Fair   Poor   N/A   None


  X

 16. Window Condition
 Good   Fair   Poor   N/A   None


  X

 17. Wall Condition
 Good   Fair   Poor   N/A   None


  X




                                                           Page 33 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E

                                      Store Room - Ground Floor
 1. Doors
 Good   Fair   Poor   N/A   None


  X

 2. Electrical
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • All the electrical outlets and light switches tested and working correctly at
                                   the time of the inspection.
 3. Floor Condition
 Good   Fair   Poor   N/A   None


  X

 4. Wall Condition
 Good   Fair   Poor   N/A   None
                                   Observations:
               X                   • Stain marks noted on the wall . Walls to be re- painted.




 5. Window Condition
 Good   Fair   Poor   N/A   None


                      X

 6. Ceiling Condition
 Good   Fair   Poor   N/A   None


  X




                                                                                                         Page 34 of 63
Snag & Inspect                                                      Green Community West, Dubai , U.A.E

                                       Interior Areas - First Floor
 1. Cabinets
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • No deficiencies observed.

 2. Electrical
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • All the electrical outlets and light switches tested and working correctly at
                                   the time of the inspection.
                                   • The Tel. Pulling Box cover is old , have screws missing and giving very low
                                   grade look of the First Floor Interior area ( Pic 01 and Pic 1A ) .




 3. Stairs & Handrail
 Good   Fair   Poor   N/A   None


  X

 4. A/C
 Good   Fair   Poor   N/A   None
                                   Observations:
                      X            • The chilled water supply was not SW/ON in the villa at the time of the
                                   inspection . The A/C unit is working ( only the fan blower was tested and
                                   working correctly ).The cooling to be checked once the chilled water supply is
                                   SW/ON.
 5. Window Condition
 Good   Fair   Poor   N/A   None


  X

 6. Ceiling Condition
 Good   Fair   Poor   N/A   None


  X

 7. Patio Doors
 Good   Fair   Poor   N/A   None


                      X


                                                                                                       Page 35 of 63
Snag & Inspect                     Green Community West, Dubai , U.A.E

 8. Screen Doors
 Good   Fair   Poor   N/A   None


                      X

 9. Wall Condition
 Good   Fair   Poor   N/A   None


  X

 10. Floor Condition
 Good   Fair   Poor   N/A   None


  X




                                                           Page 36 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E

                                    Master Bedroom - First Floor
 1. Cabinets
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • No deficiencies observed.

 2. Doors
 Good   Fair   Poor   N/A   None
                                   Observations:
               X                   • The bedroom door is difficult to close as the top of the door rubs on the
                                   door frame ( Pic 01 ) and as a result of that damage on the door noted on (
                                   Pic 1A ) .
                                   Door to be adjusted and damaged areas repaired and door re-painted.




        Poor repair noted on the door frame .
 3. Electrical
 Good  Fair Poor N/A None
                          Observations:
  X                       • All the electrical outlets and light switches tested and working correctly at
                          the time of the inspection.
 4. Floor Condition
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • White crystals noted on the floor tiles next to the patio doors indicating
                                   moisture trapped under the tiles. ( Pic 01 and Pic 1A )




                                                                                                        Page 37 of 63
Snag & Inspect                                                     Green Community West, Dubai , U.A.E




 5. Wall Condition
 Good   Fair   Poor   N/A   None
                                   Observations:
               X                   • Paint blistering and high level of moisture measured on the bedroom walls
                                   next to the patio doors ( Pic 01 , 1A ,1C , 02 and Pic 2A ). High level of
                                   moisture measured on the left side wall of the room as well.
                                   Possible reason for the wall damages is the balcony floor sloped towards
                                   villa walls ( Master Bedroom Balcony Pictures ( Pic 01 and Pic 1A ). This
                                   allowed water ponding and moisture penetrating thru the walls .
                                   The right side wall of the room has no moisture present as the balcony floor
                                   drain is located on that side.




                                                                                                     Page 38 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E




 6. A/C
 Good   Fair   Poor   N/A   None
                                   Observations:
                      X            • The chilled water supply was not SW/ON in the villa at the time of the
                                   inspection . The A/C unit is working ( only the fan blower was tested and
                                   working correctly ).The cooling to be checked once the chilled water supply is
                                   SW/ON.
 7. Window Condition
 Good   Fair   Poor   N/A   None


                      X

 8. Ceiling Condition
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • Small cracking in the ceiling is noted.




                                                                                                     Page 39 of 63
Snag & Inspect                                                      Green Community West, Dubai , U.A.E




 9. Patio Doors
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • The sliding patio door was functional during the inspection.

 10. Screen Doors
 Good   Fair   Poor   N/A   None


  X




                                                                                                    Page 40 of 63
Snag & Inspect                                                   Green Community West, Dubai , U.A.E

                       Master Bedroom Bathroom - First Floor
 1. Cabinets
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • The cabinet drawers handles loose and the handle screws rusted .
                                   Recommended new screws to be installed and handles tighten up ( Pic 01 ,
                                   1A and 1B ) .




 2. Ceiling Condition
 Good   Fair   Poor   N/A   None


  X

 3. Counters
 Good   Fair   Poor   N/A   None


  X

 4. Doors
 Good   Fair   Poor   N/A   None


  X


                                                                                                  Page 41 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E

 5. Electrical
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • All the electrical outlets and light switches tested and working correctly at
                                   the time of the inspection.
 6. GFCI
 Good   Fair   Poor   N/A   None


                      X

 7. Floor Condition
 Good   Fair   Poor   N/A   None
                                   Materials: Ceramic tile is noted.
        X                          Observations:
                                   • White crystals noted on the floor tiles next to the toilet bowl indicating
                                   moisture trapped under the tiles. The type of the floor tiles did not allowed
                                   proper moisture measurements to be taken at the time of the inspection.
 8. Mirrors
 Good   Fair   Poor   N/A   None


  X

 9. Plumbing
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • The toilet spay hose and gun missing.




 10. Showers
 Good   Fair   Poor   N/A   None


  X

 11. Shower Walls
 Good   Fair   Poor   N/A   None


  X




                                                                                                         Page 42 of 63
Snag & Inspect                                                     Green Community West, Dubai , U.A.E

 12. Bath Tubs
 Good   Fair   Poor   N/A   None
                                   Observations:
               X                   • The bath tub is not sealed properly .Caulking required around perimeter to
                                   prevent water seepage.




 13. Enclosure
 Good   Fair   Poor   N/A   None
                                   Observations:
               X                   • The shower door can not be closed completely or open entirely ( the
                                   bottom of the door is rubbing on the threshold when closed and the door is
                                   getting stuck when being( half open ) ( Pic 01 and Pic 1A ) . The door and
                                   shower enclosure frame needs to be adjusted ( Pic 1B ) and if not possible
                                   removed and re - installed properly.




                                                                                                     Page 43 of 63
Snag & Inspect                     Green Community West, Dubai , U.A.E




 14. Sinks
 Good   Fair   Poor   N/A   None


  X

 15. Toilets
 Good   Fair   Poor   N/A   None


  X

 16. Window Condition
 Good   Fair   Poor   N/A   None


  X

 17. Wall Condition
 Good   Fair   Poor   N/A   None


  X




                                                           Page 44 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E

                                         Master Bedroom Balcony
 1. Observations
 Good   Fair   Poor     N/A   None
                                     Observations:
               X                     • The master bedroom balcony floor slopes towards the walls of the villa
                                     allowing water ponding and moisture penetrating thru the walls ( Pic 01 and
                                     Pic 1A ).
                                     Floor tiles grout is damaged on different locations . Regrouting required.




                      Floor slopes to the walls.                             Floor slopes to the walls.




                                                                                                          Page 45 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E

                                       Bedroom #01 - First Floor
 1. Cabinets
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • No deficiencies observed.

 2. Doors
 Good   Fair   Poor   N/A   None


  X




                                       Paint drops to be cleaned from the door frame.
 3. Electrical
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • All the electrical outlets and light switches tested and working correctly at
                                   the time of the inspection.
                                   • Paint drops and stain marks from the electrical outlets to be cleaned and
                                   poor finish on the wall around the outlets noted.




 4. Floor Condition
 Good   Fair   Poor   N/A   None
                                   Flooring Types: Ceramic tile is noted.
  X
                                                                                                         Page 46 of 63
Snag & Inspect                                                     Green Community West, Dubai , U.A.E

 5. Wall Condition
 Good   Fair   Poor   N/A   None


        X

 6. A/C
 Good   Fair   Poor   N/A   None
                                   Observations:
                      X            • The chilled water supply was not SW/ON in the villa at the time of the
                                   inspection . The A/C unit is working ( only the fan blower was tested and
                                   working correctly ).The cooling to be checked once the chilled water supply is
                                   SW/ON.
 7. Window Condition
 Good   Fair   Poor   N/A   None


                      X

 8. Ceiling Condition
 Good   Fair   Poor   N/A   None


  X




                            Small crack on the joint between the ceiling and the wall noted.
 9. Patio Doors
 Good   Fair   Poor   N/A   None


  X

 10. Screen Doors
 Good   Fair   Poor   N/A   None


  X




                                                                                                     Page 47 of 63
Snag & Inspect                                                     Green Community West, Dubai , U.A.E

                            Bedroom #01 Bathroom - First Floor
 1. Cabinets
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • Cabinets to be sealed on the bottom to prevent water penetrating under
                                   them .




 2. Ceiling Condition
 Good   Fair   Poor   N/A   None


  X

 3. Counters
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • Damaged grout noted between the counter and the walls on ( Pic 01 , 1A
                                   and Pic 1B ). Recommended silicon to be used instead grout to seal the
                                   area.




 4. Doors
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • The door lock in hard to operate . Lock needs to be checked.


                                                                                                    Page 48 of 63
Snag & Inspect                                                         Green Community West, Dubai , U.A.E




                                                                 Cement noted on the door frame. To be cleaned
 5. Electrical
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • All the electrical outlets and light switches tested and working correctly at
                                   the time of the inspection.
 6. GFCI
 Good   Fair   Poor   N/A   None


                      X

 7. Floor Condition
 Good   Fair   Poor   N/A   None
                                   Materials: Ceramic tile is noted.
  X

 8. Mirrors
 Good   Fair   Poor   N/A   None


  X

 9. Plumbing
 Good   Fair   Poor   N/A   None


  X




                                                                                                         Page 49 of 63
Snag & Inspect                                      Green Community West, Dubai , U.A.E




                                   Spay hose and gun missing.
 10. Showers
 Good   Fair   Poor   N/A   None


                      X

 11. Shower Walls
 Good   Fair   Poor   N/A   None


                      X

 12. Bath Tubs
 Good   Fair   Poor   N/A   None


  X

 13. Enclosure
 Good   Fair   Poor   N/A   None


                      X

 14. Sinks
 Good   Fair   Poor   N/A   None


  X

 15. Toilets
 Good   Fair   Poor   N/A   None


  X

 16. Window Condition
 Good   Fair   Poor   N/A   None


  X

 17. Wall Condition
 Good   Fair   Poor   N/A   None


  X



                                                                            Page 50 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E

                                       Bedroom #02 - First Floor
 1. Cabinets
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • No deficiencies observed.

 2. Doors
 Good   Fair   Poor   N/A   None


  X




                                         Damaged grout noted. Regrouting required.
 3. Electrical
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • All the electrical outlets and light switches tested and working correctly at
                                   the time of the inspection.
 4. Floor Condition
 Good   Fair   Poor   N/A   None


  X

 5. Wall Condition
 Good   Fair   Poor   N/A   None


  X

 6. A/C
 Good   Fair   Poor   N/A   None
                                   Observations:
                      X            • The chilled water supply was not SW/ON in the villa at the time of the
                                   inspection . The A/C unit is working ( only the fan blower was tested and
                                   working correctly ).The cooling to be checked once the chilled water supply is
                                   SW/ON.
 7. Window Condition
 Good   Fair   Poor   N/A   None


                      X



                                                                                                         Page 51 of 63
Snag & Inspect                     Green Community West, Dubai , U.A.E

 8. Ceiling Condition
 Good   Fair   Poor   N/A   None


  X

 9. Patio Doors
 Good   Fair   Poor   N/A   None


  X

 10. Screen Doors
 Good   Fair   Poor   N/A   None


  X




                                                           Page 52 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E

                            Bedroom #02 Bathroom - First Floor
 1. Cabinets
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • No deficiencies observed.

 2. Ceiling Condition
 Good   Fair   Poor   N/A   None


  X

 3. Counters
 Good   Fair   Poor   N/A   None


  X

 4. Doors
 Good   Fair   Poor   N/A   None


  X

 5. Electrical
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • All the electrical outlets and light switches tested and working correctly at
                                   the time of the inspection.
 6. GFCI
 Good   Fair   Poor   N/A   None


                      X

 7. Floor Condition
 Good   Fair   Poor   N/A   None


  X

 8. Mirrors
 Good   Fair   Poor   N/A   None


  X

 9. Plumbing
 Good   Fair   Poor   N/A   None


  X

 10. Showers
 Good   Fair   Poor   N/A   None


  X

 11. Shower Walls
 Good   Fair   Poor   N/A   None


  X




                                                                                                         Page 53 of 63
Snag & Inspect                     Green Community West, Dubai , U.A.E

 12. Bath Tubs
 Good   Fair   Poor   N/A   None


                      X

 13. Enclosure
 Good   Fair   Poor   N/A   None


  X

 14. Sinks
 Good   Fair   Poor   N/A   None


  X

 15. Toilets
 Good   Fair   Poor   N/A   None


  X

 16. Window Condition
 Good   Fair   Poor   N/A   None


  X

 17. Wall Condition
 Good   Fair   Poor   N/A   None


  X




                                                           Page 54 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E

                                       Bedroom #03 - First Floor
 1. Cabinets
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • Cabinet door handle is detached .




 2. Doors
 Good   Fair   Poor   N/A   None
                                   Observations:
               X                   • Scratches and damages noted on the door and door wooden frame ( Pic
                                   01 and Pic 1A ). Areas to be sanded and door re - varnished.




 3. Electrical
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • All the electrical outlets and light switches tested and working correctly at
                                   the time of the inspection.
 4. Floor Condition
 Good   Fair   Poor   N/A   None


  X



                                                                                                         Page 55 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E

 5. Wall Condition
 Good    Fair   Poor   N/A   None


  X

 6. A/C
 Good    Fair   Poor   N/A   None
                                    Observations:
                       X            • The chilled water supply was not SW/ON in the villa at the time of the
                                    inspection . The A/C unit is working ( only the fan blower was tested and
                                    working correctly ).The cooling to be checked once the chilled water supply is
                                    SW/ON.
 7. Window Condition
 Good    Fair   Poor   N/A   None


                       X

 8. Ceiling Condition
 Good    Fair   Poor   N/A   None


  X

 9. Patio Doors
 Good    Fair   Poor   N/A   None
                                    Observations:
                X                   • The outside glass pane of the patio sliding door is broken ( Pic 01 and Pic
                                    1A ). Needs to be replaced .




        Seal damaged . Caulking required to seal
                  properly the joint.




                                                                                                       Page 56 of 63
Snag & Inspect                     Green Community West, Dubai , U.A.E




 10. Screen Doors
 Good   Fair   Poor   N/A   None


  X




                                                           Page 57 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E

                            Bedroom #03 Bathroom - First Floor
 1. Cabinets
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • The cabinet drawers handles loose and the handle screws rusted .
                                   Recommended new screws to be installed and handles tighten up ( Pic 01
                                   and Pic 1A) .




 2. Ceiling Condition
 Good   Fair   Poor   N/A   None


  X

 3. Counters
 Good   Fair   Poor   N/A   None


  X

 4. Doors
 Good   Fair   Poor   N/A   None


  X

 5. Electrical
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • All the electrical outlets and light switches tested and working correctly at
                                   the time of the inspection.
 6. GFCI
 Good   Fair   Poor   N/A   None


                      X

 7. Floor Condition
 Good   Fair   Poor   N/A   None


  X




                                                                                                         Page 58 of 63
Snag & Inspect                                                      Green Community West, Dubai , U.A.E

 8. Mirrors
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • Tape marks to be cleaned from the bathroom mirror.




 9. Plumbing
 Good   Fair   Poor   N/A   None


  X

 10. Showers
 Good   Fair   Poor   N/A   None


  X

 11. Shower Walls
 Good   Fair   Poor   N/A   None
                                   Observations:
        X                          • Grout pieces missing from the wall tiles .




 12. Bath Tubs
 Good   Fair   Poor   N/A   None
                                   Observations:
               X                   • The bath tub is not sealed properly ( Pic 01 , 1A and Pic 1B ).Caulking
                                   required around perimeter to prevent water seepage.
                                                                                                      Page 59 of 63
Snag & Inspect                     Green Community West, Dubai , U.A.E




 13. Enclosure
 Good   Fair   Poor   N/A   None


  X

 14. Sinks
 Good   Fair   Poor   N/A   None


  X

 15. Toilets
 Good   Fair   Poor   N/A   None


  X

 16. Window Condition
 Good   Fair   Poor   N/A   None


  X

 17. Wall Condition
 Good   Fair   Poor   N/A   None


  X

                                                           Page 60 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E

                                          Maid's Room - Outside
 1. Doors
 Good   Fair   Poor   N/A   None


  X




 2. Electrical
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • All the electrical outlets and light switches tested and working correctly at
                                   the time of the inspection.
 3. Floor Condition
 Good   Fair   Poor   N/A   None


  X

 4. Wall Condition
 Good   Fair   Poor   N/A   None


  X

 5. Window Condition
 Good   Fair   Poor   N/A   None


  X

 6. Ceiling Condition
 Good   Fair   Poor   N/A   None


  X




                                                                                                         Page 61 of 63
Snag & Inspect                                                       Green Community West, Dubai , U.A.E

                                      Maid's Bathroom - Outside
 1. Ceiling Condition
 Good   Fair   Poor   N/A   None


  X

 2. Doors
 Good   Fair   Poor   N/A   None


  X

 3. Electrical
 Good   Fair   Poor   N/A   None
                                   Observations:
  X                                • All the electrical outlets and light switches tested and working correctly at
                                   the time of the inspection.
 4. GFCI
 Good   Fair   Poor   N/A   None


                      X

 5. Floor Condition
 Good   Fair   Poor   N/A   None


  X

 6. Mirrors
 Good   Fair   Poor   N/A   None


  X

 7. Plumbing
 Good   Fair   Poor   N/A   None


  X

 8. Showers
 Good   Fair   Poor   N/A   None


  X

 9. Shower Walls
 Good   Fair   Poor   N/A   None


  X

 10. Sinks
 Good   Fair   Poor   N/A   None


  X

 11. Toilets
 Good   Fair   Poor   N/A   None


  X




                                                                                                         Page 62 of 63
Snag & Inspect                     Green Community West, Dubai , U.A.E

 12. Window Condition
 Good   Fair   Poor   N/A   None


  X

 13. Wall Condition
 Good   Fair   Poor   N/A   None


  X




                                                           Page 63 of 63

								