FacilityID       SchoolName                               InspectionDate
          3076   PPS ROSE CITY PARK ELEMENTARY SCHOOL              6/16/2009
          3076   PPS ROSE CITY PARK ELEMENTARY SCHOOL              6/16/2009
          3076   PPS ROSE CITY PARK ELEMENTARY SCHOOL             11/12/2009
          3076   PPS ROSE CITY PARK ELEMENTARY SCHOOL             11/12/2009
          3076   PPS ROSE CITY PARK ELEMENTARY SCHOOL             11/12/2009
          8756   PPS BINNSMEAD MIDDLE SCHOOL                       8/17/2009
         12463   PPS BOISE ELIOT ELEMENTARY SCHOOL                  6/5/2009
         12463   PPS BOISE ELIOT ELEMENTARY SCHOOL                  6/5/2009
         12463   PPS BOISE ELIOT ELEMENTARY SCHOOL                  6/5/2009
         12463   PPS BOISE ELIOT ELEMENTARY SCHOOL                  6/5/2009
         12463   PPS BOISE ELIOT ELEMENTARY SCHOOL                  6/5/2009
         12463   PPS BOISE ELIOT ELEMENTARY SCHOOL                  6/5/2009
         12463   PPS BOISE ELIOT ELEMENTARY SCHOOL                  6/5/2009
         12463   PPS BOISE ELIOT ELEMENTARY SCHOOL                  6/5/2009
         12463   PPS BOISE ELIOT ELEMENTARY SCHOOL                  6/5/2009
         12463   PPS BOISE ELIOT ELEMENTARY SCHOOL                  6/5/2009
         12463   PPS BOISE ELIOT ELEMENTARY SCHOOL                  6/5/2009
         12463   PPS BOISE ELIOT ELEMENTARY SCHOOL                  6/5/2009
         12463   PPS BOISE ELIOT ELEMENTARY SCHOOL                  6/5/2009
         12463   PPS BOISE ELIOT ELEMENTARY SCHOOL                  6/5/2009
         12463   PPS BOISE ELIOT ELEMENTARY SCHOOL                  6/5/2009
          1812   PPS GRANT HIGH SCHOOL                             10/2/2009
         19374   PPS GROUT SCHOOL                                  6/16/2009
         19374   PPS GROUT SCHOOL                                  6/16/2009
         19374   PPS GROUT SCHOOL                                  6/16/2009
         19374   PPS GROUT SCHOOL                                  6/16/2009
         19374   PPS GROUT SCHOOL                                  6/16/2009
         33252   PPS HUMBOLDT ELEMENTARY SCHOOL                     6/5/2009
         33252   PPS HUMBOLDT ELEMENTARY SCHOOL                     6/5/2009
         33252   PPS HUMBOLDT ELEMENTARY SCHOOL                     6/5/2009
         33252   PPS HUMBOLDT ELEMENTARY SCHOOL                     6/5/2009
         33252   PPS HUMBOLDT ELEMENTARY SCHOOL                     6/5/2009
         33252   PPS HUMBOLDT ELEMENTARY SCHOOL                     6/5/2009
         33252   PPS HUMBOLDT ELEMENTARY SCHOOL                     6/5/2009
         33252   PPS HUMBOLDT ELEMENTARY SCHOOL                     6/5/2009
         36002   PPS HUMBOLDT ELEMENTARY SCHOOL                     6/5/2009
         10453   PPS JAMES JOHN ELEMENTARY SCHOOL                 10/22/2009
          8939   PPS JASON LEE ELEMENTARY SCHOOL                   10/8/2009
          8939   PPS JASON LEE ELEMENTARY SCHOOL                   10/8/2009
          8939   PPS JASON LEE ELEMENTARY SCHOOL                   10/8/2009
          8939   PPS JASON LEE ELEMENTARY SCHOOL                   10/8/2009
          8939   PPS JASON LEE ELEMENTARY SCHOOL                   10/8/2009
          8939   PPS JASON LEE ELEMENTARY SCHOOL                   10/8/2009
          8939   PPS JASON LEE ELEMENTARY SCHOOL                   10/8/2009
          8939   PPS JASON LEE ELEMENTARY SCHOOL                   10/8/2009
          8939   PPS JASON LEE ELEMENTARY SCHOOL                   10/8/2009
          8939   PPS JASON LEE ELEMENTARY SCHOOL                   10/8/2009
          8939   PPS JASON LEE ELEMENTARY SCHOOL                   10/8/2009
         33268   PPS JEFFERSON HIGH GYM                            9/25/2009
         33268   PPS JEFFERSON HIGH GYM                            9/25/2009
         33266   PPS JEFFERSON HIGH SCHOOL                         9/25/2009


                                           Page 1
                              PPS___Violations


33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
33266   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
41644   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
41644   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
41644   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
41644   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
41645   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
41645   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
41645   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
41645   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
41645   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
41645   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
41645   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
41645   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
41645   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
41645   PPS JEFFERSON HIGH SCHOOL                   9/25/2009
 9062   PPS LENT ELEMENTARY SCHOOL                  10/8/2009
 9062   PPS LENT ELEMENTARY SCHOOL                  10/8/2009
 9062   PPS LENT ELEMENTARY SCHOOL                  10/8/2009
 9062   PPS LENT ELEMENTARY SCHOOL                  10/8/2009
 9062   PPS LENT ELEMENTARY SCHOOL                  10/8/2009
 9062   PPS LENT ELEMENTARY SCHOOL                  10/8/2009
 9062   PPS LENT ELEMENTARY SCHOOL                  10/8/2009
 9062   PPS LENT ELEMENTARY SCHOOL                  10/8/2009
 9062   PPS LENT ELEMENTARY SCHOOL                  10/8/2009
 9062   PPS LENT ELEMENTARY SCHOOL                  10/8/2009
 9062   PPS LENT ELEMENTARY SCHOOL                  10/8/2009
29665   PPS LINCOLN HIGH SCHOOL                    10/27/2009
29665   PPS LINCOLN HIGH SCHOOL                    10/27/2009
29665   PPS LINCOLN HIGH SCHOOL                    10/27/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/3/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009


                                  Page 2
                              PPS___Violations


 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009
 2732   PPS MARTIN LUTHER KING ELEMENTARY SCHOOL     6/5/2009
31483   PPS MARY RIEKE ELEMENTARY SCHOOL            10/2/2009
31483   PPS MARY RIEKE ELEMENTARY SCHOOL           10/22/2009
32346   PPS PORTSMOUTH MIDDLE SCHOOL                10/2/2009
32346   PPS PORTSMOUTH MIDDLE SCHOOL                10/2/2009
32346   PPS PORTSMOUTH MIDDLE SCHOOL                10/2/2009
32346   PPS PORTSMOUTH MIDDLE SCHOOL                10/2/2009
32346   PPS PORTSMOUTH MIDDLE SCHOOL                10/2/2009
32346   PPS PORTSMOUTH MIDDLE SCHOOL                10/2/2009
32346   PPS PORTSMOUTH MIDDLE SCHOOL                10/2/2009
32346   PPS PORTSMOUTH MIDDLE SCHOOL                10/2/2009
32346   PPS PORTSMOUTH MIDDLE SCHOOL                10/2/2009
32346   PPS PORTSMOUTH MIDDLE SCHOOL                10/2/2009
32346   PPS PORTSMOUTH MIDDLE SCHOOL                10/2/2009
32346   PPS PORTSMOUTH MIDDLE SCHOOL                10/2/2009
32346   PPS PORTSMOUTH MIDDLE SCHOOL                10/2/2009
32346   PPS PORTSMOUTH MIDDLE SCHOOL                10/2/2009
32346   PPS PORTSMOUTH MIDDLE SCHOOL                10/2/2009
32346   PPS PORTSMOUTH MIDDLE SCHOOL                10/2/2009
33339   PPS ROOSEVELT HIGH SCHOOL                   10/2/2009
20932   PPS ROSEWAY HEIGHTS MIDDLE SCHOOL           8/28/2009
  894   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009
  894   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009
  894   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009
  894   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009
  894   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009
  894   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009
  894   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009
  894   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009
  894   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009
  894   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009
  894   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009
  894   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009
  894   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009
  894   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009
  894   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009
  981   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009
  981   PPS SABIN ELEMENTARY SCHOOL                 10/7/2009


                                  Page 3
                              PPS___Violations


  981   PPS SABIN ELEMENTARY SCHOOL              10/7/2009
  981   PPS SABIN ELEMENTARY SCHOOL              10/7/2009
 1022   PPS SABIN ELEMENTARY SCHOOL              10/7/2009
31476   PPS WILSON HIGH SCHOOL                   10/2/2009




                                  Page 4
                                  PPS___Violations


InspectionType    ViolationCode
REGULAR           A17
REGULAR           S28
SPECIAL           A17
SPECIAL           S28
SPECIAL           X17
SPECIAL           A03
REGULAR           A17
REGULAR           E02
REGULAR           E12
REGULAR           F02
REGULAR           I01
REGULAR           I10
REGULAR           I14
REGULAR           I14
REGULAR           I99
REGULAR           K13
REGULAR           S16
REGULAR           S24
REGULAR           X01
REGULAR           X01
REGULAR           X99
SPECIAL           A03
REGULAR           A17
REGULAR           S28
REGULAR           S99
REGULAR           X17
REGULAR           X17
REGULAR           A17
REGULAR           E12
REGULAR           E13
REGULAR           E99
REGULAR           F02
REGULAR           I08
REGULAR           I14
REGULAR           X18
REGULAR           E12
SPECIAL           A99
                  A17
SPECIAL - OWNER REQUEST
                  E03
SPECIAL - OWNER REQUEST
                  E05
SPECIAL - OWNER REQUEST
                  E99
SPECIAL - OWNER REQUEST
                  F02
SPECIAL - OWNER REQUEST
                  I99
SPECIAL - OWNER REQUEST
                  K22
SPECIAL - OWNER REQUEST
                  K25
SPECIAL - OWNER REQUEST
                  S99
SPECIAL - OWNER REQUEST
                  X09
SPECIAL - OWNER REQUEST
                  X24
SPECIAL - OWNER REQUEST
REGULAR           K30
REGULAR           S01
REGULAR           A06


                                      Page 5
                          PPS___Violations


REGULAR           E02
REGULAR           E05
REGULAR           E05
REGULAR           E06
REGULAR           E13
REGULAR           E99
REGULAR           F02
REGULAR           F02
REGULAR           F02
REGULAR           F02
REGULAR           F02
REGULAR           F04
REGULAR           F04
REGULAR           F99
REGULAR           K30
REGULAR           S16
REGULAR           S22
REGULAR           S28
REGULAR           X17
REGULAR           X17
REGULAR           X18
REGULAR           E05
REGULAR           X18
REGULAR           X18
REGULAR           X18
REGULAR           E12
REGULAR           F02
REGULAR           F04
REGULAR           F99
REGULAR           I14
REGULAR           I14
REGULAR           K13
REGULAR           K30
REGULAR           X02
REGULAR           X18
                  A17
SPECIAL - OWNER REQUEST
                  E03
SPECIAL - OWNER REQUEST
                  E05
SPECIAL - OWNER REQUEST
                  E12
SPECIAL - OWNER REQUEST
                  I08
SPECIAL - OWNER REQUEST
                  K25
SPECIAL - OWNER REQUEST
                  S99
SPECIAL - OWNER REQUEST
                  X02
SPECIAL - OWNER REQUEST
                  X17
SPECIAL - OWNER REQUEST
                  X17
SPECIAL - OWNER REQUEST
                  X99
SPECIAL - OWNER REQUEST
SPECIAL           X01
SPECIAL           X02
SPECIAL           X04
SPECIAL           X17
REGULAR           A17
REGULAR           E12


                              Page 6
                          PPS___Violations


REGULAR           F04
REGULAR           I08
REGULAR           I14
REGULAR           I14
REGULAR           I14
REGULAR           K19
REGULAR           K19
REGULAR           K28
REGULAR           K30
REGULAR           K30
REGULAR           S28
REGULAR           T01
REGULAR           T01
REGULAR           X02
REGULAR           X09
SPECIAL           A03
SPECIAL           A99
REGULAR           A06
REGULAR           A13
REGULAR           A15
REGULAR           E03
REGULAR           E05
REGULAR           F02
REGULAR           F99
REGULAR           I08
REGULAR           I14
REGULAR           K30
REGULAR           K30
REGULAR           K99
REGULAR           T02
REGULAR           X02
REGULAR           X02
REGULAR           X09
SPECIAL           A09
SPECIAL           A99
                  A11
SPECIAL - OWNER REQUEST
                  A17
SPECIAL - OWNER REQUEST
                  E03
SPECIAL - OWNER REQUEST
                  E17
SPECIAL - OWNER REQUEST
                  F02
SPECIAL - OWNER REQUEST
                  I01
SPECIAL - OWNER REQUEST
                  K25
SPECIAL - OWNER REQUEST
                  K25
SPECIAL - OWNER REQUEST
                  K99
SPECIAL - OWNER REQUEST
                  S02
SPECIAL - OWNER REQUEST
                  S28
SPECIAL - OWNER REQUEST
                  T05
SPECIAL - OWNER REQUEST
                  T10
SPECIAL - OWNER REQUEST
                  X03
SPECIAL - OWNER REQUEST
                  X17
SPECIAL - OWNER REQUEST
                  E02
SPECIAL - OWNER REQUEST
                  E05
SPECIAL - OWNER REQUEST


                              Page 7
                          PPS___Violations


                  K13
SPECIAL - OWNER REQUEST
                  K25
SPECIAL - OWNER REQUEST
REGULAR           K25
SPECIAL           A03




                              Page 8
                                      PPS___Violations


ViolationDesc
PROVIDE REQUIRED MAINTENANCE AND/OR TESTING OF FIRE ALARM SYSTEM AS PER NFPA 72
PROVIDE PROOF OF NFPA 25 REQUIRED INSPECTION,TESTING AND/OR MAINTENANCE OF SPRINKLER, STANDPIP
PROVIDE REQUIRED MAINTENANCE AND/OR TESTING OF FIRE ALARM SYSTEM AS PER NFPA 72
PROVIDE PROOF OF NFPA 25 REQUIRED INSPECTION,TESTING AND/OR MAINTENANCE OF SPRINKLER, STANDPIP
REPAIR FIRE DOORS TO THEIR SELF-CLOSING AND LATCHING CONDITION AND/OR DISCONTINUE USE OF ANY BLO
PROVIDE REPAIR TO ALARM SYSTEM.
PROVIDE REQUIRED MAINTENANCE AND/OR TESTING OF FIRE ALARM SYSTEM AS PER NFPA 72
DISCONTINUE RUNNING EXTENSION CORDS THROUGH WALLS, CEILING, FLOORS, OR UNDER DOORS AND/OR PRO
PROVIDE COVER PLATES TO ALL OPEN ELECTRICAL BOXES AND SWITCHES.
MAINTAIN FIRE-RESISTANCE RATING OF FIRE-RESISTANCE-RATED CONSTRUCTION. OPENINGS SHALL BE PROTE
DISCONTINUE PRACTICE OF CLOTHESLINING WHERE WIRE CABLES ARE STRETCHED ACROSS CLASSROOMS BEL
DISCONTINUE USE OF NON COMMERICAL DECORATIVE LIGHTING
MAINTAIN OR REPAIR SWINGING FIRE DOORS SO THAT THE DOORS CLOSE AND LATCH AUTOMATICALLY. THE DO
MAINTAIN OR REPAIR SWINGING FIRE DOORS SO THAT THE DOORS CLOSE AND LATCH AUTOMATICALLY. THE DO
INSTITUTIONS "OTHER" CODE
MAINTAIN ORDERLY STORAGE OF COMBUSTIBLE MATERIALS IN BUILDINGS.
REPLACE MISSING ESCUTCHEONS AS NEEDED.
MAINTAIN MINIMUM 24" CLEARANCE BETWEEN STORAGE AND CEILING IN UNSPRINKLERED BUILDING AND 18" BEL
DISCONTINUE BLOCKING EXIT DOOR.
DISCONTINUE BLOCKING EXIT DOOR.
EXITS "OTHER" CODE
PROVIDE REPAIR TO ALARM SYSTEM.
PROVIDE REQUIRED MAINTENANCE AND/OR TESTING OF FIRE ALARM SYSTEM AS PER NFPA 72
PROVIDE PROOF OF NFPA 25 REQUIRED INSPECTION,TESTING AND/OR MAINTENANCE OF SPRINKLER, STANDPIP
SPRINKLER/STANDPIPE "OTHER' CODE
REPAIR FIRE DOORS TO THEIR SELF-CLOSING AND LATCHING CONDITION AND/OR DISCONTINUE USE OF ANY BLO
REPAIR FIRE DOORS TO THEIR SELF-CLOSING AND LATCHING CONDITION AND/OR DISCONTINUE USE OF ANY BLO
PROVIDE REQUIRED MAINTENANCE AND/OR TESTING OF FIRE ALARM SYSTEM AS PER NFPA 72
PROVIDE COVER PLATES TO ALL OPEN ELECTRICAL BOXES AND SWITCHES.
SWITCHES, OUTLET AND JUNCTION BOXES: (A.) COVERS MISSING AND WIRES EXPOSED, (B.) SWITCHES OR OUTL
ELECTRICAL "OTHER" CODE
MAINTAIN FIRE-RESISTANCE RATING OF FIRE-RESISTANCE-RATED CONSTRUCTION. OPENINGS SHALL BE PROTE
REPAIR/REPLACE SMOKE GASKETS ON FIRE DOOR FRAMES.
MAINTAIN OR REPAIR SWINGING FIRE DOORS SO THAT THE DOORS CLOSE AND LATCH AUTOMATICALLY. THE DO
RESTORE LIGHTED EXIT ILLUMINATION TO EXIT SIGNS. (INTERNAL)
PROVIDE COVER PLATES TO ALL OPEN ELECTRICAL BOXES AND SWITCHES.
FIRE ALARM SYSTEMS "OTHER" CODE
PROVIDE REQUIRED MAINTENANCE AND/OR TESTING OF FIRE ALARM SYSTEM AS PER NFPA 72
DISCONTINUE THE PRACTICE OF GANG PLUGGING POWER TAPS TOGETHER.
DISCONTINUE USE OF EXTENSION CORDS IN LIEU OF PERMANENT WIRING
ELECTRICAL "OTHER" CODE
MAINTAIN FIRE-RESISTANCE RATING OF FIRE-RESISTANCE-RATED CONSTRUCTION. OPENINGS SHALL BE PROTE
INSTITUTIONS "OTHER" CODE
PROVIDE PROPER CLEARANCE OF COMBUSTIBLE FROM HEATING APPLIANCES. (AS PER THE LISTING AND MANUF
PROVIDE FLAME RETARDANT TREATMENT AND MEET REQUIREMENTS OF PFC CHAPTER 805 & 806 NFPA 286 OR R
SPRINKLER/STANDPIPE "OTHER' CODE
MAINTAIN EMERGENCY EXIT LIGHTING IN OPERATIONAL CONDITION.
PROVIDE ANNUAL TEST ON EVERY REQUIRED BATTERY-POWERED EMERGENCY LIGHTING SYSTEM FOR NOT LES
REPAIR OR REPLACE (i.e.: ceiling tiles) REQUIRED FIRE RESISTIVE CONSTRUCTION TO REQUIRED LEVEL OF FIRE R
DISCONTINUE HANGING OBJECTS FROM SPRINKLER PIPES.
PROVIDE ANNUAL REPORTING OF SUPERVISED FIRE ALARM SYSTEM AS PER NFPA 72.


                                           Page 9
                                      PPS___Violations


DISCONTINUE RUNNING EXTENSION CORDS THROUGH WALLS, CEILING, FLOORS, OR UNDER DOORS AND/OR PRO
DISCONTINUE USE OF EXTENSION CORDS IN LIEU OF PERMANENT WIRING
DISCONTINUE USE OF EXTENSION CORDS IN LIEU OF PERMANENT WIRING
DISCONTINUE USE OF MULTI-PLUG ADAPTERS
SWITCHES, OUTLET AND JUNCTION BOXES: (A.) COVERS MISSING AND WIRES EXPOSED, (B.) SWITCHES OR OUTL
ELECTRICAL "OTHER" CODE
MAINTAIN FIRE-RESISTANCE RATING OF FIRE-RESISTANCE-RATED CONSTRUCTION. OPENINGS SHALL BE PROTE
MAINTAIN FIRE-RESISTANCE RATING OF FIRE-RESISTANCE-RATED CONSTRUCTION. OPENINGS SHALL BE PROTE
MAINTAIN FIRE-RESISTANCE RATING OF FIRE-RESISTANCE-RATED CONSTRUCTION. OPENINGS SHALL BE PROTE
MAINTAIN FIRE-RESISTANCE RATING OF FIRE-RESISTANCE-RATED CONSTRUCTION. OPENINGS SHALL BE PROTE
MAINTAIN FIRE-RESISTANCE RATING OF FIRE-RESISTANCE-RATED CONSTRUCTION. OPENINGS SHALL BE PROTE
PROVIDE APPROVED ANNUAL TEST FOR FIRE DOOR TO ENSURE PROPER OPERATION AND FULL CLOSURE.
PROVIDE APPROVED ANNUAL TEST FOR FIRE DOOR TO ENSURE PROPER OPERATION AND FULL CLOSURE.
FIRE PROTECTION SYSTEMS "OTHER" CODE
REPAIR OR REPLACE (i.e.: ceiling tiles) REQUIRED FIRE RESISTIVE CONSTRUCTION TO REQUIRED LEVEL OF FIRE R
REPLACE MISSING ESCUTCHEONS AS NEEDED.
REMOVE ANY OBSTRUCTIONS THAT PREVENT ADEQUATE SPRINKLER PATTERN DEVELOPMENT OR COVERAGE.
PROVIDE PROOF OF NFPA 25 REQUIRED INSPECTION,TESTING AND/OR MAINTENANCE OF SPRINKLER, STANDPIP
REPAIR FIRE DOORS TO THEIR SELF-CLOSING AND LATCHING CONDITION AND/OR DISCONTINUE USE OF ANY BLO
REPAIR FIRE DOORS TO THEIR SELF-CLOSING AND LATCHING CONDITION AND/OR DISCONTINUE USE OF ANY BLO
RESTORE LIGHTED EXIT ILLUMINATION TO EXIT SIGNS. (INTERNAL)
DISCONTINUE USE OF EXTENSION CORDS IN LIEU OF PERMANENT WIRING
RESTORE LIGHTED EXIT ILLUMINATION TO EXIT SIGNS. (INTERNAL)
RESTORE LIGHTED EXIT ILLUMINATION TO EXIT SIGNS. (INTERNAL)
RESTORE LIGHTED EXIT ILLUMINATION TO EXIT SIGNS. (INTERNAL)
PROVIDE COVER PLATES TO ALL OPEN ELECTRICAL BOXES AND SWITCHES.
MAINTAIN FIRE-RESISTANCE RATING OF FIRE-RESISTANCE-RATED CONSTRUCTION. OPENINGS SHALL BE PROTE
PROVIDE APPROVED ANNUAL TEST FOR FIRE DOOR TO ENSURE PROPER OPERATION AND FULL CLOSURE.
FIRE PROTECTION SYSTEMS "OTHER" CODE
MAINTAIN OR REPAIR SWINGING FIRE DOORS SO THAT THE DOORS CLOSE AND LATCH AUTOMATICALLY. THE DO
MAINTAIN OR REPAIR SWINGING FIRE DOORS SO THAT THE DOORS CLOSE AND LATCH AUTOMATICALLY. THE DO
MAINTAIN ORDERLY STORAGE OF COMBUSTIBLE MATERIALS IN BUILDINGS.
REPAIR OR REPLACE (i.e.: ceiling tiles) REQUIRED FIRE RESISTIVE CONSTRUCTION TO REQUIRED LEVEL OF FIRE R
DISCONTINUE BLOCKING EXIT PATHWAY.
RESTORE LIGHTED EXIT ILLUMINATION TO EXIT SIGNS. (INTERNAL)
PROVIDE REQUIRED MAINTENANCE AND/OR TESTING OF FIRE ALARM SYSTEM AS PER NFPA 72
DISCONTINUE THE PRACTICE OF GANG PLUGGING POWER TAPS TOGETHER.
DISCONTINUE USE OF EXTENSION CORDS IN LIEU OF PERMANENT WIRING
PROVIDE COVER PLATES TO ALL OPEN ELECTRICAL BOXES AND SWITCHES.
REPAIR/REPLACE SMOKE GASKETS ON FIRE DOOR FRAMES.
PROVIDE FLAME RETARDANT TREATMENT AND MEET REQUIREMENTS OF PFC CHAPTER 805 & 806 NFPA 286 OR R
SPRINKLER/STANDPIPE "OTHER' CODE
DISCONTINUE BLOCKING EXIT PATHWAY.
REPAIR FIRE DOORS TO THEIR SELF-CLOSING AND LATCHING CONDITION AND/OR DISCONTINUE USE OF ANY BLO
REPAIR FIRE DOORS TO THEIR SELF-CLOSING AND LATCHING CONDITION AND/OR DISCONTINUE USE OF ANY BLO
EXITS "OTHER" CODE
DISCONTINUE BLOCKING EXIT DOOR.
DISCONTINUE BLOCKING EXIT PATHWAY.
DISCONTINUE CONCEALMENT/OBSTRUCTION OF EXIT SIGN.
REPAIR FIRE DOORS TO THEIR SELF-CLOSING AND LATCHING CONDITION AND/OR DISCONTINUE USE OF ANY BLO
PROVIDE REQUIRED MAINTENANCE AND/OR TESTING OF FIRE ALARM SYSTEM AS PER NFPA 72
PROVIDE COVER PLATES TO ALL OPEN ELECTRICAL BOXES AND SWITCHES.


                                          Page 10
                                      PPS___Violations


PROVIDE APPROVED ANNUAL TEST FOR FIRE DOOR TO ENSURE PROPER OPERATION AND FULL CLOSURE.
REPAIR/REPLACE SMOKE GASKETS ON FIRE DOOR FRAMES.
MAINTAIN OR REPAIR SWINGING FIRE DOORS SO THAT THE DOORS CLOSE AND LATCH AUTOMATICALLY. THE DO
MAINTAIN OR REPAIR SWINGING FIRE DOORS SO THAT THE DOORS CLOSE AND LATCH AUTOMATICALLY. THE DO
MAINTAIN OR REPAIR SWINGING FIRE DOORS SO THAT THE DOORS CLOSE AND LATCH AUTOMATICALLY. THE DO
PROVIDE DOCUMENTATION THAT DRAPES AND OTHER DECORATIVE MATERIALS MEET THE FLAME SPREAD INDE
PROVIDE DOCUMENTATION THAT DRAPES AND OTHER DECORATIVE MATERIALS MEET THE FLAME SPREAD INDE
REMOVE COMBUSTIBLE STORAGE FROM BOILER, MECHANICAL AND ELECTRICAL ROOMS.
REPAIR OR REPLACE (i.e.: ceiling tiles) REQUIRED FIRE RESISTIVE CONSTRUCTION TO REQUIRED LEVEL OF FIRE R
REPAIR OR REPLACE (i.e.: ceiling tiles) REQUIRED FIRE RESISTIVE CONSTRUCTION TO REQUIRED LEVEL OF FIRE R
PROVIDE PROOF OF NFPA 25 REQUIRED INSPECTION,TESTING AND/OR MAINTENANCE OF SPRINKLER, STANDPIP
DISCONTINUE BLOCKING FIRE EXTINGUISHERS OR FIRE FIGHTING EQUIPMENT.
DISCONTINUE BLOCKING FIRE EXTINGUISHERS OR FIRE FIGHTING EQUIPMENT.
DISCONTINUE BLOCKING EXIT PATHWAY.
MAINTAIN EMERGENCY EXIT LIGHTING IN OPERATIONAL CONDITION.
PROVIDE REPAIR TO ALARM SYSTEM.
FIRE ALARM SYSTEMS "OTHER" CODE
PROVIDE ANNUAL REPORTING OF SUPERVISED FIRE ALARM SYSTEM AS PER NFPA 72.
REPAIR HEAT DETECTORS AS NEEDED
EXTEND ALARM SYSTEM COVERAGE UNDER BENEFIT OF PERMIT FROM FIRE MARSHAL OFFICE
DISCONTINUE THE PRACTICE OF GANG PLUGGING POWER TAPS TOGETHER.
DISCONTINUE USE OF EXTENSION CORDS IN LIEU OF PERMANENT WIRING
MAINTAIN FIRE-RESISTANCE RATING OF FIRE-RESISTANCE-RATED CONSTRUCTION. OPENINGS SHALL BE PROTE
FIRE PROTECTION SYSTEMS "OTHER" CODE
REPAIR/REPLACE SMOKE GASKETS ON FIRE DOOR FRAMES.
MAINTAIN OR REPAIR SWINGING FIRE DOORS SO THAT THE DOORS CLOSE AND LATCH AUTOMATICALLY. THE DO
REPAIR OR REPLACE (i.e.: ceiling tiles) REQUIRED FIRE RESISTIVE CONSTRUCTION TO REQUIRED LEVEL OF FIRE R
REPAIR OR REPLACE (i.e.: ceiling tiles) REQUIRED FIRE RESISTIVE CONSTRUCTION TO REQUIRED LEVEL OF FIRE R
HOUSEKEEPING "OTHER" CODE
MOUNT FIRE EXTINGUISHER WITH TOP NO HIGHER THAN 5’ FROM FLOOR AND BOTTOM AT LEAST 4” OFF FLOOR.
DISCONTINUE BLOCKING EXIT PATHWAY.
DISCONTINUE BLOCKING EXIT PATHWAY.
MAINTAIN EMERGENCY EXIT LIGHTING IN OPERATIONAL CONDITION.
REPAIR SMOKE DETECTORS (REQUIRED) AS NEEDED
FIRE ALARM SYSTEMS "OTHER" CODE
PROVIDE / MAINTAIN ACCESS TO FIRE ALARM PANELS / PULL STATIONS
PROVIDE REQUIRED MAINTENANCE AND/OR TESTING OF FIRE ALARM SYSTEM AS PER NFPA 72
DISCONTINUE THE PRACTICE OF GANG PLUGGING POWER TAPS TOGETHER.
A WORKING SPACE OF NOT LESS THAN 30 INCHES (762 MM) IN WIDTH, 36 INCHES (914 MM) IN DEPTH AND 78 INCH
MAINTAIN FIRE-RESISTANCE RATING OF FIRE-RESISTANCE-RATED CONSTRUCTION. OPENINGS SHALL BE PROTE
DISCONTINUE PRACTICE OF CLOTHESLINING WHERE WIRE CABLES ARE STRETCHED ACROSS CLASSROOMS BEL
PROVIDE FLAME RETARDANT TREATMENT AND MEET REQUIREMENTS OF PFC CHAPTER 805 & 806 NFPA 286 OR R
PROVIDE FLAME RETARDANT TREATMENT AND MEET REQUIREMENTS OF PFC CHAPTER 805 & 806 NFPA 286 OR R
HOUSEKEEPING "OTHER" CODE
DISCONTINUE STORAGE IN FRONT/AROUND SPRINKLER VALVE.
PROVIDE PROOF OF NFPA 25 REQUIRED INSPECTION,TESTING AND/OR MAINTENANCE OF SPRINKLER, STANDPIP
PROVIDE ANNUAL SERVICE TO FIRE EXTINGUISHER(S) BY CERTIFIED COMPANY.
REMOVE SUBSTANDARD PORTABLE FIRE EXTINGUISHER AND/OR SUPPLY APPROVED FIRE EXTINGUISHER AS PR
DISCONTINUE COMBUSTIBLE MATERIAL STORAGE IN EXIT OR EXIT ENCLOSURE
REPAIR FIRE DOORS TO THEIR SELF-CLOSING AND LATCHING CONDITION AND/OR DISCONTINUE USE OF ANY BLO
DISCONTINUE RUNNING EXTENSION CORDS THROUGH WALLS, CEILING, FLOORS, OR UNDER DOORS AND/OR PRO
DISCONTINUE USE OF EXTENSION CORDS IN LIEU OF PERMANENT WIRING


                                          Page 11
                                   PPS___Violations


MAINTAIN ORDERLY STORAGE OF COMBUSTIBLE MATERIALS IN BUILDINGS.
PROVIDE FLAME RETARDANT TREATMENT AND MEET REQUIREMENTS OF PFC CHAPTER 805 & 806 NFPA 286 OR R
PROVIDE FLAME RETARDANT TREATMENT AND MEET REQUIREMENTS OF PFC CHAPTER 805 & 806 NFPA 286 OR R
PROVIDE REPAIR TO ALARM SYSTEM.




                                       Page 12
                                      PPS___Violations


Comments

SPRINKLER


CORRIDOR DOORS ARE TO BE SELF CLOSING OR AUTOMATIC SELF CLOSING. PLEASE PROVIDE APPROVED DEVI
NAC #1 - 1 END OF LINE VOLTAGE IS TO LOW AND NEEDS TO BE CORRECTED BEFORE FINAL APPROVE OF ALARM

RM. #230 - DISCONTINUE RUNNING EXTENSION CORD THROUGH CEILING.
CAFETERIA STAGE - WHERE OLD CLOCK WAS MOUNTED.
RM. #215 - RESEAL CONDUIT.
REMOVE ART WIRES FROM COMMON AREA NEAR RM. #133
RM. #108-A
RM. #127D - REPAIR DOOR CLOSER.
RM. # 127
KILN DOES NOT APPEAR TO BE INSTALLED WITH PERMIT - EXHAUST IS NOT PROPERLY INSTALLED.
REDUCE AND ORGANIZE COMBUSTIBLE STORAGE IN: 1.) RM. #128 2.) RM. #137 3.) RM. #145
1ST FLOOR GIRLS RESTROOM
BOILER ROOM STORAGE AREA - MAINTAIN 18 INCHES BELOW SPRINKLER DEFLECTORS.
RM. #118 - REMOVE BOOK SHELF FROM BEHIND DOOR, UNABLE TO OPEN DOOR FULLY.
RM. #145 - KEEP EXIT DOORS CLEAR FO FURNITURE AND STORAGE.
RM. #128 - REMOVE ART HANGING IN DOOR WAY.
AS PER NFPA 72 REPORT DATED 07/07/09: 1. NEW GYM BEAM DETECTORS DO NOT REPORT TROUBLE. 2. THE 3


FIRE HOSE CABINETS NEED TO BE EITHER: UNLOCKED, PROVIDE A BREAKING TOOL OR GLASS REPLACED WITH F
REMOVE DOOR WEDGE DEVICES WHEN UNOCCUPIED- SPOKE WITH THE PRINCIPAL AND INFORMED THAT I WOUL
DOOR WEDGE IN FIRE DOOR TO CAFETERIA- ABATED

RM. # 30-D
RM. # 33 - REPAIR OUTLET.
PLUG POWER TAPS DIRECTLY INTO WALL OUTLET, NOT INTO EXTENSION CORDS. 1.) PRINCIPAL'S OFFICE 2.) R
RM. #26 - SEAL HOLES WHERE CONDUIT IS PENETRATING WALL.
MAIN OFFICE, #35, #30, #5, #12, #13, #23, #22, #21.
CROSS CORRIDOR NEAR RM. #16
LIBRARY
WHERE OLD CLOCK WAS MOUNTED.
FACP-2 NAC CIRCUIT END OF LINE VOLTAGE IS 15.06 AS PER TESTING DONE BY STONER ELECTRIC. THIS IS TO LO
E-MAIL OR FAX DOCUMENTATION OF ALARM TEST TO INSPECTOR ALICE JOHNSON Alice.Johnson@fire.ci.portland.or
MAIN OFFICE, ROOM 122,
ROOM 109
RM 108 - REMOVE LAMP WITH EXPOSED BULB.
SEAL OPENINGS WITH FIRE CAULKING: CUSTODIAL #1, #C2, .#C3
PROVIDE FIRE AND LIFE SAFETY BOOK ("RED BOOK").
DISCONTINUE STORING COMBUSTIBLES AGAINST WALL MOUNTED RADIANT HEATERS IN SMALL ROOMS 1,2, & 3 B
PER INTERNATIONAL FIRE CODE (807.1): IN "E" OCCUPANCIES, " CURTAINS, DRAPERIES, HANGINGS AND OTHER D
FIRE HOSE CABINETS SHALL BE EITHER: UNLOCKED; PROVIDED WITH A BREAKING TOOL; OR GLASS REPLACED W
RESTORE BATTERY BACKUP FOR EXIT LIGHT AT EXIT INTO COURTYARD.
EMERGENCY LIGHTING NEEDS TO BE TESTED. PROVIDE WRITTEN DOCUMENTATION THAT EACH EMERGENCY LIG
MISSING CEILING TILE - BOYS LOCKER ROOM.
REMOVE ROPES FROM SPRINKLER PIPES IN BASEBALL ROOM A-104.




                                          Page 13
                                      PPS___Violations


B-33
B-33
A-8
B-33
ABOVE ELEVATOR 2ND FLR. NEAR ROOM # D-35.
REPAIR WALL OUTLET IN B-32.
SEAL CONDUIT IN ELECTRICAL ROOM # D-35.
SEAL CONDUIT - C-FLOOR I.T. ROOM, NW STAIR.
SEAL CONDUIT IN CEILING OF STORAGE CLOSET NEAR RM. # C-39.
REPAIR GLASS IN FIRE DOOR - STAIRWELL B-LEVEL NEAT B-23.
SEAL CONDUIT - MDF 1.1 OFF LIBRARY.
HORIZONTAL FIRE DOORS (2) IN LIBRARY.
BOILER ROOM.
SMOKE CURTAIN FOR ELEVATOR DOOR ON 2ND FLR. NEAR RM. # D-35 IS NOT COMPLETELY IN PROPER RESET PO
CEILING TILES MISSING RMS. # D-25, D-1, C-28, C-32, B-33, 6, LOCKER ROOM OFFICE FOR GIRLS GYM, A-36
RMS. # D-33, WILBANKS OFFICE, 17, 18, 19, 20, 22
REMOVE TAPE FROM SPRINKLER HEAD - B5A BOOKKEEPER'S OFFICE.

DO NOT BLOCK OPEN FIRE DOOR - STAIRWELL B-LEVEL NEAR B-23.
DO NOT LOCK DOWN DOGS ON FIRE DOOR LATCHES, DOOR MUST LATCH - STAIRWELL B -LEVEL NEAR B-23.
C-23, STAIRS BETWEEN TV STUDIO & C- CORRIDOR, A-8, A-12.
REMOVE EXTENSION CORD RUNNING ON TOP OF CUBICLE WALLS IN DANCE OFFICES.
TV STUDIOS
OUTSIDE MENS LOCKER ROOM NEAR DANCE OFFICES.
ENTRANCE TO DANCE STUDIO - WEST STAIRWELL.
3RD FLR. CORRIDOR.
MISSING DOOR BETWEEN BALCONY AND FOYER.
BACK OF STAGE
KEEP FIRE DOOR CLEAR OF ALL OBJECTS TO ALLOW DOOR TO FULLY CLOSE- BACK OF STAGE.
BALCONY EXIT FROM C-4.
2ND FLR. STAIRWELL - WEST BEHIND STAGE.
DRESSING ROOM B-79.
CEILING TILE MISSING IN FOYER OF BALCONY.
REMOVE STORAGE FROM STAIRWELLS, CORRIDORS & EXITS BEHIND STAGE.
1.) BACK OF STAGE - PROP STORAGE. 2.) CORRIDOR BEHIND STAGE. 3.) STAIRWELL - EAST BEHIND STAGE 1ST &
 E-MAIL OR FAX DOCUMENTATION OF ALARM TEST TO INSPECTOR ALICE JOHNSON Alice.Johnson@fire.ci.portland.o
-SUN OFFICE -RM 125 -COMPUTER LAB#146 -RM 113 AT ROLLING DESK
-CUSTODIAL OFFICE OFF BOILER ROOM -GYM OFFICE - EXTENSION CORD STAPLED TO WALL OVER DOORWAY
GYM - EXPOSED ELECTRICAL WIRES AT WALL CLOCK LOCATION
DOUBLE DOORS TO CAFETERIA
-PINK CURTAINS ON BOOK CASES RM 157 -PALM TREE IN SPANISH ROOM (#?) -PAPER TREE RM 109 CURTAINS P
FIRE HOSE CABINETS SHALL BE EITHER: UNLOCKED; PROVIDED WITH A BREAKING TOOL; OR GLASS REPLACED W
LOCKER ROOM 127 NEAR GYM - SHELVES ARE BLOCKING EXIT DOOR
DOUBLE DOORS B/W SOUTH WING AND CENTER HALLWAY DO NOT SELF LATCH
DISCONTINUE PROPPING FIRE DOORS OF ROOMS WHEN THEY ARE NOT OCCUPIED (RESTROOMS).
RM 152 - DISCONTINUE BLOCKING FIRE MARSHAL SIGN WITH POSTER ON DOOR
REMOVE FURNITURE, PIANO AND OTHER ITEMS THAT ARE BLOCKING DOUBLE EXIT DOORS TO RIGHT OF STAGE.
REMOVE NEWLY CONTRUCTED RAMP THAT IS BLOCKING EGRESS PATHWAY IN AUDITORIUM.
REMOVE COVER FROM EGRESS LIGHT THAT IS OVER DOUBLE EXIT DOORS TO THE SIDE OF THE STAGE.
IMMEDIATELY DISCONTINUE WEDGING RESTROOM DOORS OPEN. RESTROOMS HAVE HEAT DETECTION AND OPE

RM. #208


                                          Page 14
                                              PPS___Violations


BOILER ROOM - 4 SLIDING FIRE DOORS.
#132, FACULTY DINING, 103, 102, 104, 140-C, 201, CROSS CORRIDOR BETWEEN #204 & 205, 208, 213, 212.
WEST CAFETERIA ENTRANCE -- NOT LATCHING
RM. #200 - NOT LATCHING.
1.) RM. #216 - NOT CLOSING COMPLETELY. 2.) RM. #215 - NOT LATCHING.
RM. # 123
RM. #140A - BETWEEN CLASSROOM AND LUNCH ROOM.
RM. #157 - REMOVE COMBUSTIBLE STORAGE.
GIRLS RESTROOM ACROSS FROM #105 - REPAIR CEILILING TILE.
FACULTY LOUNGE - REPAIR CEILING TILE.
ANNUAL SPRINKLER TEST
RM. #120
1.) STAGE IN LIBRARY 2.) HALLWAY BETWEEN FACULTY LOUNGE & MAIN OFFICE.
REMOVE STORAGE FROM STAIRS NEAR RM. #140-D.
STAIRS NEAR RM. #140-D & RM. #140-D.
AS PER NFPA 72 TEST REPORT DEFICIENCIES: 1. RELOCATE SMOKE DETECTOR IN NURSE'S OFFICE A MINIMUM
PROVIDE SMOKE DETECTION COVERAGE FOR FIRE ALARM CONTROL PANEL.

ELECTRICAL ROOM OFF BOILER ROOM.
ADD FIRE DETECTION TO RESTROOMS # 216, 217, 239, & 240 AS REQUIRED FOR STANDARD Q - OPTION 1 CORRID
GYM TEACHERS OFFICE
GYM TEACHERS OFFICE
SEAL CONDUIT IN I.T. CLOSET ACROSS FROM RM. # 224
DISCONTINUE BLOCKING RESTROOM FIRE DOORS OPEN WHERE DOORS OPEN TO CORRIDORS.
RMS # 130, 115, 101, 206A, 203, 201, 200, 214, 215, 216, 218, 221, 227, 236, 237, 239, 240, 238, 242, 248, 254, 251, 023, 01
RM # 186 - NOT LATCHING.
CEILING TILE - RM # 215, NEAR EXIT D.
REPLACE OR REPAIR CEILING TILE IN CORRIDOR NEAR ROOM #183A.
PROVIDE METAL COVER FOR TRASH CANS IN RESTROOMS # 015 & 016.
LIBRARY STAFF BREAK ROOM.
REMOVE LARGE TABLE FROM CORRIDOR NEAR ROOM #248.
REMOVE STORAGE FROM EXIT PATH - DOOR # 150 IN LIBRARY.
BULB MISSING IN GYM NEAR BOYS LOCKER ROOM.
SMOKE DETECTORS - 2.41, 2.42, 2.43 ARE NOT SHOWING TROUBLE OR ALARM AT FIRE PANEL AS PER NFPA 72 TE
SMOKE DETECTORS IN GYM ARE SO CLOSE TO THE HVAC DIFFUSERS THAT IT IS DIFFICULT TO GET THEM INTO A
TWO PULL STATIONS ARE BLOCKED BY DOUBLE DOORS ON 3RD FLOOR. THEY ARE THE DOUBLE FIRE DOORS OF
E-MAIL OR FAX DOCUMENTATION OF ALARM TEST TO INSPECTOR ALICE JOHNSON Alice.Johnson@fire.ci.portland.or
BASEMENT ART ROOM - POWER TAPS ARE GANG PLUGGED AND POWER TAP IS PLUGGED INTO EXTENSION COR
CLEAR ACCESS TO ELECTRICAL EQUIPMENT RM 312
SEAL PIPE OPENINSG WITH FIRE CAULKING: STOREROOM 111, 211, ROOM 309, BASEMENT CUSTODIAN ROOM, AB
TEACHERS LOUNGE RM 214. VERIFY THAT WIRE IS AT LEAST 84".
TEACHER'S LOUNGE RM 214, CEILING DECORATIONS.
RM 313 CEILING DECORATIONS
ROOM 203, COVER OPENING IN DUCT WORK FOR DRYER THAT HAS BEEN DECOMMISSIONED.
DISCONTINUE STORAGE THAT IMPEDES ACCESS TO SPRINKLER.
 E-MAIL OR FAX DOCUMENTATION OF SPRINKLER TEST TO INSPECTOR ALICE JOHNSON Alice.Johnson@fire.ci.portla
ROOM 203, BOILER ROOM 102A, STAGE
CLASSROOM 100A. PROVIDE EXTINGUISHER WITH MINIMUM RATING OF 2A:10BC. EXTINGUISHER SHALL BE MOUN
DEAD END CORRIDOR ON BASEMENT NEAR BOILER ROOM.
REPLACE DOORS WHICH HAVE BEEN REMOVED FROM 3RD FLOOR BOYS RESTROOM (RM 311) AN D GIRLS RESTR
THROUGH WALL OF BATHROOM.
DISCONTINUE USE OF HANGING LIGHT FIXTURE IN BATHROOM WHICH IS SERVED BY AN EXTENSION CORD IN LIE


                                                   Page 15
                                    PPS___Violations


DO NOT STORE COMBUSTIBLES AGAINST WALL MOUNTED RADIANT HEATER IN BATHROOM.
CURTAIN IN BATHROOM, WINDOW "VALENCE" IN CLASSROOM.
CURTAIN IN WOMEN'S BATHROOM
AS PER NFPA 72 REPORT DATED 08/26/09 : 1. DETECTORS ON 2ND FLR. ARE MISLABLED WITH INCORRECT MODU




                                        Page 16
                                                PPS___Violations




ROVIDE APPROVED DEVISES ON THESE DOORS I.E. KINDERGARTEN CLASSROOM
NAL APPROVE OF ALARM SYSTEM.




ORT TROUBLE. 2. THE 3 BEAM DETECTORS IN THE NEW GYM HAVE BEEN DISCONNECTED AND DO NOT FUNCTIION.   We repa


GLASS REPLACED WITH FRANGIBLE MATERIAL- THROUGHOUT
 INFORMED THAT I WOULD LOOK INTO THE SAFETY ISSUE OF DOORS BEING OPEN- THESE BATHROOMS ARE SPRINKLERED A




RINCIPAL'S OFFICE 2.) RM. #30-C




 ELECTRIC. THIS IS TO LOW OF VOLTAGE FOR MOST LISTED DEVICES, PLEASE CONFIRM AND CORRECT.
Johnson@fire.ci.portland.or.us FAX# (503) 823-3969 ATTN: ALICE JOHNSON PHONE # (503) 823-3799




 SMALL ROOMS 1,2, & 3 BEHIND AUDITORIUM. ALTERNATIVE IS TO DECOMISSION HEATERS.
HANGINGS AND OTHER DECORATIVE MATERIALS SUSPENDED FROM WALLS OR CEILINGS SHALL MEET THE FLAME PROPAGA
; OR GLASS REPLACED WITH FRANGIBLE MATERIAL THAT IS EASILY BROKEN. THROUGHOUT SCHOOL

AT EACH EMERGENCY LIGHT IS WORKING PROPERLY (NOTE EACH LOCATION). BACK-UP POWER SHALL BE TESTED FOR 30 SE




                                                    Page 17
                                                     PPS___Violations




 LY IN PROPER RESET POSITION.
 GIRLS GYM, A-36




 -LEVEL NEAR B-23.




AST BEHIND STAGE 1ST & 2ND FLRS. 4.) 3RD FLR. CORRIDOR.
 .Johnson@fire.ci.portland.or.us FAX# (503) 823-3969 ATTN: ALICE JOHNSON PHONE # (503) 823-3799

WALL OVER DOORWAY


REE RM 109 CURTAINS PRINCIPAL'S OFFICE
; OR GLASS REPLACED WITH FRANGIBLE MATERIAL THAT IS EASILY BROKEN.




RS TO RIGHT OF STAGE.

 OF THE STAGE.
 AT DETECTION AND OPEN TO THE EGRESS CORRIDOR, THEY ARE NOT ALLOWED TO BE BLOCKED OPEN.




                                                         Page 18
                                                          PPS___Violations



, 208, 213, 212.




SE'S OFFICE A MINIMUM OF 3 FEET FROM AIR DIFFUSER.            2. PROVIDE SMOKE DETECTION FOR FACP.



RD Q - OPTION 1 CORRIDOR UPGRADE.




 242, 248, 254, 251, 023, 019, 015, 165, 162, 157, 151, 147, 146, GYM DOORS.




ANEL AS PER NFPA 72 TEST REPORT DATED 08/13/2009.
ULT TO GET THEM INTO ALARM (AS WITNESSED BY HANEY AT ALARM RE-ACCEPTANCE TEST) PLEASE MOVE DETECTORS AW
 DOUBLE FIRE DOORS OFF EACH END OF THE MAIN CORRIDOR. WHEN HELD BY MAGNETIC HOLD-OPENS, THEY OBSCURE AN
Johnson@fire.ci.portland.or.us FAX# (503) 823-3969 ATTN: ALICE JOHNSON PHONE # (503) 823-3799
 D INTO EXTENSION CORD. POWER TAPS SHALL BE PLUGED DIRECTLY INTO WALL OUTLETS.

T CUSTODIAN ROOM, ABOVE BOILER ROOM DOOR.




Alice.Johnson@fire.ci.portland.or.us   FAX# 503-823-3969 ATTN: ALICE JOHNSON

UISHER SHALL BE MOUNTED SO THAT TOP IS NOT MORE THAN 5 FT ABOVE THE FLOOR AND CLEARANCE BETWEEN THE FLO

M 311) AN D GIRLS RESTROOM (RM 308).

 EXTENSION CORD IN LIEU OF PERMANENT WIRING.


                                                              Page 19
                                            PPS___Violations




WITH INCORRECT MODULE NUMBER. 2. PROGRAM DESCRIPTOR LABLES ARE INACCURATE. 3. DOOR HOLDERS IN THE BUILD




                                                Page 20
                                                      PPS___Violations




ND DO NOT FUNCTIION.   We repaired that during the summer. All is okay   Denny Clawson Facilities



 ATHROOMS ARE SPRINKLERED AND HAVE A SMOKE/HEAT DETECTOR.




 CORRECT.




 ALL MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701… OR BE NONCUMBUSTIBLE". PLEASE PROV


WER SHALL BE TESTED FOR 30 SECONDS EACH MONTH AND FOR 90 MINUTES ANNUALLY. E-MAIL OR FAX DOCUMENTATION TO




                                                           Page 21
              PPS___Violations




OCKED OPEN.




                  Page 22
                                            PPS___Violations




 PLEASE MOVE DETECTORS AWAY FROM DIFFUSERS OR PROVIDE A BLOCKING DEVICE TO REDIRECT AIR AWAY FROM SMO
HOLD-OPENS, THEY OBSCURE AND BLOCK ACCESS TO PULL STATIONS.




CLEARANCE BETWEEN THE FLOOR AND THE BOTTOM OF EXTINGUISHER IS NOT LESS THAN 4 INCHES.




                                                Page 23
                                            PPS___Violations




3. DOOR HOLDERS IN THE BUILDING ARE POWERED FROM THE MAIN FIRE ALARM PANEL.