151 HVAC QA ISSUES LOG DATE: 12/24/0
Owner's DDC System Installation Project
ITEM ID Notification ISSUES ACTION REQUIRED CHECKED
PARTY DATE
NO. DATE DATE LOG Responsible REQ. BY
General
5 1/12/04 1/14/04 Owner's Point naming convention has not been followed
QA reviewed Cont.'s handout - more still needs to be done to follow point naming
5 1/21/04 convention - offered to mark it up
QA to review point names on graphics and provide comment to Cont. once Cont.
5 3/10/04 provides document
5 4/14/04 QA documented point name corrections on Cont.'s spreadsheet.
5 6/17/04 QA edited Cont.'s point name spreadsheet, adding soft points for Main Building
QA to provide the remainder of corrected hard and soft point names. Update
5 6/22/04 provided 7/2/7/04 based on feedback from Cont..
Point name corrections are still to be completed. QA provided access to program
and has began making revisions to point names and trend names in program per
5 8/13/04 7/27/04 spreadsheet.
Met terminal box point names are still to be revised and zone controller
5 9/1/04 Co/HeReset% trend wires added in FBs. See 9/2/04 spreadsheet Cont. 9/19/04 QA
6 2/19/04 Override stat location vs. isolation area needs to be worked out
6 3/17/04 QA provided marked up prints and description of zone blocks and requirements
6 6/2/04 QA provided update to Cont.'s programmer
Cont. indicated programming has been completed but it is noted that warm-up and
6 6/22/04 overrides are not interfaced properly
What is the status of schedule override blocks for MnCVRH1-3, MnVAVRH1-8,
6 8/5/04 8/13/04 MnVAVRH2-31: are they included and where?
MnCVRH1-3 is by itself but should not have override capability. QA zeroed out
6 8/28/04 override on time. MnVAVRH1-8 override is included as specified.
MnAC2 terminal boxes do yet have their override blocks, which includes 2-31a/b,
6 8/28/04 8/30/04 programmed as specified in QA's 8/28/04 Schedule Override Blocks.doc. Cont. 9/19/04 QA
7 2/24/04 2/25/04 Cable tied to conduit needs to secure and free of sags (2)
IT recommends that historical data be installed on the D:/ drive; its much larger than
8 3/12/04 4/23/04 C:/. Completed with the installation of V2.5 QA
18 4/27/04 Need to define location of CO2 Sensors: conference rooms and cafeteria
5 conference rooms in Main and 1 in Met. Cafeteria is not included because it does
18 5/5/03 not have an operable outside air damper.
Cont. to work with QA to draft a memo training staff on the use of the zone
24 4/28/04 thermostats Team 5/24/04 QA
Zone thermostats should only indicate zone temperature and not blink outside air
25 5/3/04 temperature Cont. QA
Similar point names should use % for a PID output and V for volts/analog output.
29 6/2/04 QA 8/6/04: QA to complete revision QA QA
82 8/28/04 8/30/04 Why do we not have archived data? Data removed from database for use in SOAP. (2)
Label all wiring per spec sections 3.07.A.8. and 3.11.A. Include point name and
64 8/12/04 address.
Inspected w/ Cont. & Operator: Unfinished items in Main chiller room and on Met
64 10/26/04 roof remain. Cont. 11/1/04 QA
Label all panels per spec section 3.11.C. This also applies to abandoned-in-place
65 8/12/04 panels used as wiring junction cans. Cont. 8/31/04
65 10/26/04 Inspected w/ Cont. & Operator: Unfinished items on Met roof remain. Cont. 11/1/04 QA
Identify all control components per spec sections 3.11.D. and 3.11.E. Provide
66 8/12/04 terminal box label at the entrance location on Tbar, if box is located above the ceiling. Cont. 9/19/04
66 10/5/04 10/19/04 QA: Not all complete; example VAVRH1-19 in room Mn127 QA
If the old static pressure Pitot tube sensors are no longer used, remove the
68 8/12/04 pneumatic tubing and the Pitot tubes. Plug the duct opening. Cont. 8/31/04 QA
69 8/12/04 MGTF Building: Correct the panel label that reads MTEng.. Cont. 8/31/04 QA
MGTF Building: Relocate the temperature room sensor to the office which is the
70 8/12/04 conditioned space. Cont. 8/31/04 QA
72 8/12/04 Insulate all piping where sensors are installed. Cont. 8/31/04 QA
Schedule implementation of optimal start and stop programs. Cont. to contact
73 8/13/04 Operator2 to set up a date by 10/1/04. Team 8/31/04 QA
MnL16CommRoom logic does not require a setpoint controller or outgoing requests.
99 10/6/04 It is just a sensor as in MGTF. Cont. 11/1/04 QA
Submittal #4: O&M manual - QA provided comments on Asbuilt Drawings10/23/04.
Eng. provided comments 10/25/04 QA needs to update spec. and return to Eng..
11/9/04: QA provided comment to Eng.. 11/22/04: Eng. provided as-buit spec to
Cont. QA 11/22/04: Spec needs to include the update for Met DDVAV and Met
Electric Reheat Only. 12/13/04: Cont. e-mailed updated as-built spec to QA & Eng..
12/14/04 QA: Provided comments to Cont.; Eng. to update and reissue. 12/15/04:
Cont. provided complete update of as-built docs. 12/16/04: Cont. submitted Project
Close Out documentation on CD, and FedExed a copy to Eng.. Cont. requests all to
provide comments/feedback as soon as possible so that this documentation can be
106 10/20/04 finalized, and the specified three hard copies of this information can be provided. Eng 12/20/04
107 10/20/04 Submittal #4: Training Plan 11/9/04: Comments provided by Eng. and QA Cont. 11/16/04 QA
Formal Training by Contractor: Owner needs to schedule date and determine who
will attend. Cafetria 11/17 &11/19 9:00 AM to1:00 PM Operator, Operator2,
108 10/20/04 HVAC.Maint.Cont., Operator3., Operator4 Cont. 11/17/04 QA
109 10/25/04 Systems Manual QA 12/23/04 QA
Server needs to automatically come back up after a power outage. I've asked IT to
110 10/25/04 investigate.
Cont.'s service techs needs Cistrix. He has yet to fill out new forms. 10/29/04 Forms IT ? QA
sent to Owner. Cont. to provided contact info 11/2/04. Waiting on IT. 11/8/04: IT
issued e-mails. IT will contact Cont.'s programmers and techs. QA 12/2/04: Cont.'s
service techs have their log-ins completed; Cont.'s service tech1 has the software
and key; Cont.'s service tech2 is waiting to receive the software and key. Cont.
12/15/04: Cont.'s service tech1 has left Cont.; Cont.'s service tech2 has his and its
working; Hiring someone to replace Cont.'s service tech1. IT 12/15/05: Cont.'s
111 10/20/04 service tech1 needs to turn his key into IT; address provided. Cont. 12/23/04 QA
Staff needs training for recovering Standards Lab after a Chilled Water or Hot Water
Valve sequence has enabled the "out of range breaker". Sequence will need to be
119 10/30/04 11/9/04 manually reset. Cont. (8) 11/19/04 QA
As-builts: Where is the explanation of how to back up the data base to save the
trends? Is this automated? If not the procedure must be described. QA: #37 of
124 11/9/04 11/17/04 Training document. Cont. 11/19/04 QA
127 11/9/04 11/17/04 Cont. needs to provide comments on project specification. Cont. 12/17/04 open
MnAC1 & 2 terminal units were not scheduled for Nov. 11 holiday; building is
128 11/11/04 11/17/04 running; need training on use of schedules Cont. 11/19/04 QA
130 11/17/04 11/17/04 Trend sample times need to be adjusted per spec. To be completed 12/10/04 Cont. 12/8/04 QA
Team needs to complete Functional Witness Testing such that failed items are
resolved. 11/22/04 Conducted tests; not all items are resolved. 12/3-4/04
Conducted additional tests. 12/10/04: Tests completed subject to memo from Cont.
131 11/17/04 11/17/04 regarding heating valves for VAV2-6 and 7 being correct. See #103 below. Cont. 12/10/04 QA
Cont. and IT need to move server to basement comm room at completion of project.
132 11/17/04 11/17/04 Cont. to schedule a date w/ IT. Cont. 12/15/04: Server moved and functional. Cont./IT QA
After the server is moved to the basement comm room, what physical access does
the contractor need to the comm room to fullfil the warranty requirements of the
142 12/10/04 contract? IT 12/14/04: Cont. to work with Owner if access is needed. QA 12/15/04 QA
Cont. is requested to submit a letter of successful completion of the project with a
warranty start date of 12/15/04, and two spaces (for Owner's project manager and
QA) for approval sign off. Upon receipt of this letter, Owner's project manager will
process the final invoice. Cont. has submitted this to the Cont. process. Owner's
144 12/15/04 project manager will be receiving this letter via email in the next day or so. Cont. 12/23/04 open
Cont. is requested to turn in all access cards and keys. Cont. and programmers
have provided these to Owner. Cont. is still collecting the others and will submit to
145 12/15/04 Operator2 as soon as possible. Cont. 12/23/04 Operator2
Cont. is requested to submit unconditional waiver upon final payment from Owner.
146 12/15/04 12/16/04: Cont. concurs. Cont. 12/23/04 open
Graphics
QA reviewed owner's other site graphics w/ Cont.; they are aware of the level of
9.1 3/24/04 quality we are looking for.
9.1 3/31/04 QA provided Cont.'s programmer a thorough review of graphics issues
9.1 4/12/04 4/13/04 QA documented graphics issues; e-mailed to Cont. & Cont.'s tech
9.1 6/24/04 Detailed comments on graphics pages provided to Cont. by QA
See 4/13/04 and 6/24/04 reviews by QA. QA completed markup of graphic pages
provided by Cont.. As of 8/13/04 not all requested changes have been made. We
46 7/30/04 need to look at this together. Cont., QA 8/31/04
46 10/19/04 QA: some minor stuff remains, but will not push it. QA
MnAC7 and MnAC8: where is the return duct? Needs both OA and RA, OA is fixed.
9.2 3/26/04 3/31/04 6/23/04: QA noted that this is true also for MetAC1,4,5
9.2 8/5/04 8/13/04 MnAC7 and 8 have RA, MtAC1, 4, and 5 have OA. Make all RA Cont. 8/31/04 QA
9.3 3/26/04 MnAC3 - why 2 discharge ducts? (2)
9.4 3/26/04 3/31/04 MnAC4 - No outside air on this unit Cont. QA
9.5 3/24/04 VFD's need correct point naming labels. Revised by QA 8/13/04 Cont. QA
VFD graphic needs to include a status point indicating whether or not the VFD is in
11 4/14/04 "hand" mode Cont. 8/31/04
11 10/4/04 VFD "Hand" graphic put on air handler graphic page - OK
MnAC4 HoW S R Temp sensors are located at the air handler. MnAC4 HoW Xovr QA
valves are mounted in the Mn Boiler supply and return piping to the MnAC4. MnAC4
HoW Xovr valves need to be added to AC4 boiler graphics and sensors located
14.1 4/23/04 4/26/04 appropriately. Cont. QA
14.4 8/13/04 HoWS Local and HoWR Local should be located on the local boiler side of the tees Cont. 8/31/04 QA
14.2 4/23/04 4/26/04 MnAC4 ChW S R Temp sensors are backwards.
MnAC4 ChW S & R Temp sensors are still backwards. Supply should be the lower
14.2 8/4/04 one.
MnAC4 ChW S&R Temp sensors are located at the air handler. MnAC4 ChW Xovr Cont. 8/31/04 QA
valves are mounted in the Mn Chiller supply and return piping to the MnAC4.
MnAC4 ChW Xovr valves need to be added to AC4 chiller graphics and sensors
14.3 4/23/04 4/26/04 located appropriately. Cont. QA
14.5 8/13/04 ChWS Local and ChWR Local should be located on the local chiller side of the tees Cont. 8/31/04 QA
QA/Operator2: Main space color graphics needs improvements. QA to document
32 5/25/04 6/23/04 and forward to Team QA 6/24/04
34 6/23/04 7/15/04 Need RH only graphic for units in Main Building Cont. QA
Location (building-room number) of thermostats needs to be provided above stat
35 6/24/04 graphic Cont.
36 7/7/04 7/15/04 Need second floor main building graphic Cont. QA
Main Building Basement graphic is incorrect. L16 and electric meeter in wrong place.
37 7/7/04 7/15/04 See graphic dwgs provided by Owner QA
37 7/30/04 Graphic is OK except meter needs moved. See 7/30 marked up pages. Cont. QA
MnAC1 and MnAC2 Zone Condition Monitor tables: add Airflow Setpoint and Htg
Valve Position;data below "Status in Room" should indicate the room number
47 8/2/04 8/13/04 (Mn101). Provided marked up printout 7/30/04 and 8/28/04.
47 10/1/04 10/4/04 Mode is not functioning Cont. ? QA
MtAC3 dual duct VAV box graphics need Hot and Cold deck supply air
48 8/4/04 8/13/04 temperatures. See 7/15/04 memo and 7/30/04 marked up pages.
48 9/23/04 Delete "From Ahu XX.X" Cont. ? QA
MtAC3 Zone Condition Monitor tables: label Damper Pos with appropriate duct; add
hot and cold duct supply air temps; data below "Status in Room" should indicate the
room number (Mt201). Note data in terminal box graphic is not same as in table. See
49 8/4/04 8/13/04 MtDD-1.
49 10/1/04 Mode is not functioning for CO boxes Cont. ? QA
MnAC5 Zone Condition Monitor tables: add Airflow Setpoint and Htg Valve Position;
50 8/4/04 8/13/04 data below "Status in Room" should indicate the room number (Mn151).
50 10/1/04 Mode is not functioning Cont. ? QA
51 8/4/04 8/13/04 Provide graphic for MnCVRh3-1. Cont. 8/31/04 QA
71 8/13/04 Include CV and Rh only boxes in the AC1 zone table
71 10/1/04 10/4/04 1-3 still needs to be added Cont. 11/1/04 QA
CO2 sensor level and setpoint in ppm need to be added to their respective terminal
77 8/20/04 8/20/04 box graphic Cont. 8/31/04 QA
79 8/20/04 MtAC1 stat is in Mt109, not Mt108. This needs to changed on the Met graphic. Cont. 8/31/04 QA
Heat Source link on MnAC1, 2, 3 & 5 terminal box graphics needs to jump to MnBlr
85 8/30/04 8/30/04 not the air handler. Appropriate links have yet to be installed on Met terminal boxes. Cont. 9/30/04 QA
MnBlr is showing 3 ConRP; need to confirm that there is actually two and revise
93 9/23/04 Cont.rdingly Cont. ? QA
MGTF graphic only provides color; it needs to provide the actual temperature like
104 10/23/04 ML16 CommRoom. Cont. 11/1/04 QA
135 11/22/04 MnCCVRH1-3: upper right hot links are not visable; coolsource link does not function Cont. 12/3/04 QA
138 12/2/04 MtAC3 mixed air damper graphic should read "% open" Cont. 12/3/04 QA
149 12/16/04 Warranty support: MtRH101 and MtRH108 graphics pages are not accessible. Cont. ?
OAT (6)
ACs
MnAC1&2 needs SAF HiStcPres Alarm paged. Reviewed program with Eng. and
17.1 4/27/04 Cont.'s programmer. Not to spec. Cont.'s programmer will revise and resubmit.
Cont. discussed with Eng.. To implement a hard reset at the panel in the Loft but will
use a soft relay. Tried to locate the button. Where is the button? In cabinet near
17.1 6/23/04 AC1ChWVlv.
Install each duct static pressure resets per spec section 3.03.D.1.d and shall include
17.1 8/12/04 a reset button and a pilot light indicator on the face of the associated panels. Cont. 9/19/04
17.1 MnAC1&2: Pilot lights and reset buttons are installed QA
Need HiPresStatic Alarm reset procedure for each airhandler which uses it. This
17.2 8/4/04 8/13/04 would be for training and use in the systems manual Cont., (5, 8) 8/31/04 QA
40 7/7/04 Shouldn't return fan be locked out when the return damper is at 0%?
40 9/1/04 Revise MnAC1&2 graphic to show barometric relief Cont. 9/1/04 QA
MnAC2: zero flow to the following boxes do not read zero: VAVRh2-22, 2-24, 2-25, 2-
41 7/7/04 8/13/04 A number of Main Bldg boxes are
27, VAV2-6, 2-9. See QA data. not reading zero when air handlers are off. Mn1-
16 = -33%; Mn2-25 = -40%; Mn2-33a = +33%; Mn2-33 b= +15%; Mn5-3 = 10%
41 10/23/04 QA QA
59 8/5/04 8/13/04 Why are we getting a HighStcPres Alarm on MnAC1 on start-up? Cont. 8/31/04
59 10/1/04 QA increase delay from 10 minutes to 20 minutes QA
MnAC1 and MnAC2 fans operated Saturday morning (10/30/04) for a few minutes.
No zone appeared overridden. Why? Check if zone is in setback. Setback Mode is
not trended. The lowest zone temps on MnAC1 & 2 were down to ~55 Deg.F from
7:00-8:30AM. This is above Setback Mode starting setpoint of 50 to 52 Deg.F.
117 10/3/0/04 11/2/04 Cont.: Needs to be verified by team. (7)
MnAC3 does not need to be scheduled on. The HVCR is used infrequently and staff
is used to using an on timer. Can local override provide an total of 8hrs on time per
16 4/27/04 4/28/04 use and users trained? Yes.
MnAC3: once VAVs are operational and stat is installed, stat can be programmed for
2hr increments; max time for this equipment is only 224 minutes. Program my be
16 4/28/04 forthcoming in November to change this to 8 hours. Cont., (4, 5) QA
MnAC3 chilled water valve is at 100%, while zone is calling for heating. Why? No
129 11/11/04 11/17/04 longer occuring. Cont. 11/19/04 QA
1 12/17/03 12/17/03 AC-4 valving to alternate chillers and boilers need to be automated
1 1/14/04 Owner received quote from Cont.
At a minimum, we need some form of DDC indication as to the status of the position
1 1/15/04 1/16/04 of the manual valves if they are kept.
1 1/21/04 Cont. sequence is incorrect; house steam boiler is normal operation for MnAC4
Discuss valving requirements in meeting; Cont. proposed valving modification and
1 2/4/04 will develop sequence
1 2/27/04 Cont. sequence as submitted is incorrect. House boiler is primary supply for MnAC4.
1 3/10/04 Cont. submitted new sequence; QA to review and define point names
1 3/16/04 QA provided comments to Cont. and Taylor Engineering
1 3/24/04 Eng. asked if all information agreed upon.
MnAC4Chlr ChWP Run and MnAC4Blr HoWP Run should be interlocked with Xover
1 8/6/04 8/13/04 Valves. Eng. to provide specification revision.
Spec revision revised again and approved by QA and Eng.. Program is yet to be
1 10/19/04 installed. 10/21/04 - Program installed. Cont., (6) 10/19/04 QA
Does the MnAC4 Nortec Humidifier setpoint adjustment need to be automated? Eng.
2.1 1/15/04 1/15/04 to review; we at least need the setpoint monitored and a paged alarm Eng
2.1 3/24/04 Cont. to propose sequence for using the Nortec and dew point control. Cont.
2.1 8/4/04 No reset was implemented but Nortec status is monitored and alarms provided. QA
QA: Rotronics dew point sensor will not be used. Cont. to provide acceptable
2.2 4/7/04 alternate. Cont. QA
MnAC4: Need sequence for Standards lab if Chiller 1 is required to run. Mn Chiller
4 2/24/04 4/7/04 sequence modified 6/21/04 to maintain 42 deg.F if MnAC4 is on Team, (6) QA
19 4/27/04 MnAC4: Can TempSpAdj be eliminated? Yes QA
If MnAC4 Boiler Xovr Alarm is too be used it should only indicate if valves are
26 5/21/04 5/28/04 opposite Cont.
26 Alarm has been removed.
QA discussed with Cont.'s programmer the need to add a +/-4 deg F. hysterisis to QA
the MnAC4 ChWVlv and HoWVlv zone temp breakers. 4 and 2 are used
30 6/2/04 respectively. Cont. QA
MnAC4 ChWS and R sensors are grossly inaccurate. Calibrate & reinstall or replace
60 8/4/04 with better sensors.
Cont. indicates that theses have been recailibrated. ChWS Temp is ~ 9 deg. F
60 10/19/04 greater that chiller leaving temperature measured with a Pete's plug gauge.
MnAC4 ChWS and R sensors appear to be impacted by room temp. At cool bldg
temps (<65) the ChWST is close to the measured chiller leaving temp (37.5 ~ 38.8),
but as the building warms, the CHWST & RT rise, but the chiller leaving temp
doesn't. They need to be replaced with ones in thermal wells, preferably at the
60 10/20/04 chiller. Cont. 11/1/04
60 10/28/04 New sensors were installed in thermall wells at the coil. QA
Standards Lab panic button needs to be documented and functional tested.
123 11/9/04 11/17/04 Functional test to place 11/19/04. Cont. 11/19/04 QA
MnAC5 1) economizer control logic is not the same as MnAC1(spec). 2) "or"
12 4/19/04 4/21/04 statement in econ lockout logic is miss wired. 3) RADmpr% trend wire is mislabeled Cont., (6) QA
MnAC5 4) DAT >> RAT and ChWVlv open, Fan Not Running! Why? Contractor had
been working around original pneumatic system downstairs, may have disturbed the
13 4/19/04 4/19/04 tubing. Unit is now cut over, but the old equipment still needs to be removed. Cont. QA
MnAC5: Air flow is inadequate at zone boxes, SF is manual and VFD is at 15% and
39 7/7/04 8/13/04 HiPresStatic Alarm is on.
39 8/4/04 8/13/04 Need HiPresStatic Alarm reset procedure for training and systems manual. See 17.2 above.
MnAC5SF is shutting down on Low Static Pressure during warm-up. Raul checked it
out. He thinks that the switch is defective. Will replace if it happens again. 11/21/04
126 11/9/04 MnAC1, 2 and 5 sensors are to be replaced. Cont. 12/3/04 QA
133 11/17/04 MnAC1 and MnAC2 need low pressure cutout per spec. Cont. 12/8/04 QA
MnAC5 RADmpr is being closed during warm-up. This impacts the fans ability to
136 11/22/04 heat the space. It appears this may also be true with MnAC1 and MnAC2. Cont. 12/3/04 QA
10 3/26/04 MnAC7: Temperature is rising across DX coil
MnAC7: This is because the system is recirculating air through the return duct, which
10 4/13/04 has been omitted from the graphic. (2)
MnAC7 and 8: Spec calls AC7 the unit that serves the cafeteria; the program says
that it is the unit that serves the kitchen. AC7 serves the kitchen. The spec needs
20 4/27/04 changed QA QA
MnAC7& 8: Is compressor cycling lockout part of equipment or does it need to be
21.1 4/27/04 4/28/04 installed in program? A five minute timer is in the program. Cont. 8/31/04 QA
MnAC7& 8: 2nd Stg Cooling PID range is not correct. 2nd stage cooling PID OK per
21.2 4/27/04 4/28/04 Eng. Cont. QA
MnAC7: why does stat display 2 numbers? Second number is for outside
22 4/27/04 5/19/04 temperature. It is now removed QA
Small AC units (MnAC7&8, Count Room AC, MetAC1,4,5 and WhAC1&2 all require
84 8/28/04 8/30/04 TempSpAdj trend wires to be added to FB Cont. 9/19/04 QA
Sensors currently installed in the Environmental Chambers will need to be replaced
28 5/28/04 with appropriate sensors.
QA reviewed spec and Vaisala products with Cont.. Vaisala 61W is not satisfactory.
A Vaisala 247 or similar product is specified. On 6/23/04 it was agreed to use the
28 6/22/04 Testo 650HPW.
Testo sensors installed, but transmitter cover is missing from the transmiter in the
28 8/12/04 8/13/04 West chamber.
28 8/19/04 8/20/04 Environmental chamber humidity and temperature sensors are still not operational. Cont. 8/31/04 QA
MtAC2 OADamper does not close during unoccupied periods. See 3.03D.2 and
TE44 (damper is trended; but its not programmed properly) 11/21/04: Cont.'s
118 10/30/04 11/1/04 programmer says he fixed it; QA to check Cont., (6) 11/19/04 QA
MtAC3: RA Temp is not on original points list but is noted in the logic. Is this RAT of
63 8/6/04 8/13/04 another MAT in the heating duct? If real add to graphics in appropriate place. Cont. 8/31/04 QA
MtAC3 oscillates between Cool1 and Cool2. Increasing the delay timer to 15 minutes
on 9/1/04 did not reduce the oscillation. Increase cycle time if possible.
90 9/2/04 Eng.10/25/2004: 15 minute cycle is OK. Cont. 9/19/04 QA
MtAC3 warm-up and cool-down sequences currently allow the fans to run anytime
after 3:00AM when the building is unoccupied and other conditions permit. This
allows it to run on weeQAds. It should be using a schedule as MnAC1. Also, the
heating PID loop is not programmed as specified. 11/21/04 QA to check results of
updated program. QA 11/22/04: Cooling fan does not run during warm-up but
spaces do not come up to temp fast enough as hot air flow falls off. Cooling air-flow
comes on at occupancy even without a request for cooling. Cool air from bypass
damper cools hot air supply. Cont.'s programmer is in the process of fixing. QA
12/3/04: Looks correct. Final approved sequence needs to be put into the as-built
113 10/29/04 11/1/04 spec., see #106 above. Cont./Eng 12/3/04 QA
Even with the cool morning, MtAC5 needed cooling but it was locked out due to low
OAT. An OAT based cooling or heating lockout is not in the spec. (3.03.O.3).
Remember, these units do not have economizers. Remove lockout logic from
102 It appears we have similar units.MtAC2 still to be done.
10/20/04 programming for all confusion over which unit is MtAC1 and MtAC5. When the Cont. 11/1/04 QA
Current Facilities Requirements doc was being developed Joe indicated to me that
MtAC5 provided conditioned air 24/7 to Mt109, where the SEM is located and Mt
108, the small room next door. MtAC1 provided conditioned air 6-6 M-F to the Met
lab in Room Mt106 and the darkroom adjacent to it in room Mt107. This later went
into the spec. Once the installation of DDC hardware was completed, Cont. techs
noted that this was backwards and programming and documentation was changed
accordingly, which includes my recent mark-up of the spec. Unfortunately, I believe
this may now be incorrect. Saturday, the Met color graphic indicated that the unit
supporting Mt106 was on not Mt109. A test of the zone overrides seemed to verify
this to be the case. This needs to be cleared up once and for all. Appropriate
changes, if necessary, will need to be made on graphic pages, point names,
schedules, equipment labels if need be, and in the CFR and Spec. 11/2/04:
Program complete but not spec. 11/9/04 QA provided comment on spec revision to
116 10/30/04 11/2/04 Eng.; Eng provided update to Cont.: See #116 above
Terminal Units
Many boxes have 78 deg.F unoccuppied setpoints, thus requesting the chiller to
43 7/19/04 7/21/04 come on over the weekend. Spec indicates this should be 90. Cont. QA
Met dual duct vav boxes: check for proper installation. Both hot and cold ducts are
53 8/4/04 8/12/04 reading airflow. See all boxes MtDD-1 to MtDD-8.
53 10/1/04 10/19/04 QA: OK except MtDD-8 hot deck air flow is not reading - damper is at 100%
QA & DM investigated MtDD-8. Determined that spec requires Heating Supply Fan
to turn off if not required. The program currently switches between cooling airflow
and heating airflow depending on zone controller ouput, staying in heating until
cooling > 0. It provides no flow if still in heating (0%) when the heating fan turns off.
53 10/22/04 See 3.03U.4b Damper Control. 10/29/04: Eng. to work with Cont.
Cont. to change program so that Cool fan is not running on Warm-up mode. Start
heating fan for warm-up or heating when scheduled. 11/21/04 Cooling fan still
53 11/2/04 running during warm-up. Cont. 11/19/04 QA
MtDD-8: Hot damper is wide open, flow is 0; cold damper is closed, flow sp is 80,
97 10/5/04 10/19/04 flow is 30. See #53 above.
55 8/5/04 8/13/04 Delete CO2 sensors in the GEO tree of MnRh107, 108A and 109 Cont. 8/31/04 QA
If a Zone controller is used in the logic program, add trends for Clg% and Htg%. For
57 8/5/04 8/13/04 example: MnVAVRh1-10 Cont. 8/31/04 QA
MnVAV2-8 and 2-9 thermosstats are connected to opposite boxes. This has caused
78 8/20/04 8/20/04 some confusion upstairs. Cont. 8/31/04 QA
Mt108 and Mt101 have additional original stats that control electric reheat. Need to
address this in an FB and graphics. Cont. has submited Change Order request.
Owner's project manager wants to CO reissued based finalized cost info. Cont.:
80 8/23/04 Official CO pending. Will proceed with installation. Cont. 12/8/03 QA
MnVAVRH31a/b: both ducts are cooling; why is one shown as heating? Why is CO2
83 8/28/04 8/30/04 included?
Cont. to revise MnVAVRH31a/b FB such that the 2nd duct and its variables are
83 9/1/04 noted as a cooling duct 2 and CO2 sequence is removed. Cont. 9/19/04 QA
88 9/2/04 Change termianl box setpoint controller color hysterisis to 0.3. Cont. 9/19/04 QA
Many main building VAVRH terminal boxes heating valves oscillate. This particularly
89 9/2/04 impacts the spaces served by reheat only boxes. Cont. 9/19/04 QA
92 9/23/04 Noise coming from VAV box 2-8 in 2nd floor Main building Cont. 11/1/04 QA
MnAC1 and MnAC2 VAV boxes are not providing more than minimum air flow when
heating is required due to that fact that airflow controller Heat Mode is not enabled
when zone controller HTG % output is greater than 50%. 10/21/04: Numerous
zones are very cold; Heat Mode was enabled manually. This is a factory program; it
100 10/19/04 needs fixed ASAP. Cont.
Fb's have been replaced, but logic blocks on screen are not as programmed.
100 10/22/04 10/25/04Ok after server was rebooted. Cont. 11/1/04 QA
MnVAVRH2-7 hot water re-heat valve is not providing heat. Cont.'s tech thinks it is
plugged. Note, Tstat is behind construction screen. 10/28/04: Cont. found strainer
plugged. This may be true elsewhere including 2-6, 2-30, 2-31a/b and 1-16.
11/2/04: MnVAVRH1-16 balance and shut-off valve were closed - Cont. opened
them. MnVAV2-30 Tstat is located behind construction partition, raised supply air
setpoint 5oF. MnVAV2-31a/b looks like 3-way is piped backwards - Contractor
adjusted the bypass, he feels that it's piped correctly. MnVAVRH2-6 may not have
enough capacity -- Cont. to check. 11/21/04: MnVAVRH1-9, 2-6, 2-7, 2-30 and 2-
31a/b boxes are not providing sufficeint heat. We need to checked the airside on all
of these. See witness test requirements. Cont. 11/30/04: Tuned 2-31a/b. Cont.
12/2/04: Confirmed airflow is within 5%. SA Temp adjusted up 5oF. Added foam
backing placed behind stats. Check tomorrow. QA 12/3/04: All HoWValves are
controlling except for 2-6 and 2-7. Cont. needs to confirm correct valves sizes were
103 8/23/04 installed. QA 12/15/04: Cont. provided doc. Cont. 12/8/04 QA
Reheat only terminal box MnRh1-109 in Mn109 seems starved for air. It takes a very
long time to warm up. 10/04: Raised SAT setpoint to 105oF. QA 12/3/04: Raised
105 10/23/04 10/25/04 SAT setpoint to 110oF. (1) QA
Operator Indicates that he's talked to Cont.'s programmer about the overrides not
working in the Met Building. 10/30/04: Tested MtDD8 on Saturday. Only it goes
112 10/29/04 10/30/04 active instead of the entire floor. Also, on time is 30 minutes instead of 1 hour. Cont. ? QA
120 11/2/04 MnVAVRH2-9 heating PID is oscillating. Cont. 11/19/04 QA
Rooms Mn110 and 110A are cold. Stat does not appear to be communicating
125 11/9/04 properly with MnVAV2-20. Raul replace wiring and controller. Its working now. Cont. 11/19/04 QA
MnAC1, 2 and 5 OADamper is opening to the "OADmpr Min" position druing setback
and warm-up. MnAC5 OADmpr is also open during the unoccupied period. They
should be closed at these times. 12/10/04: MnAC5 OADmpr is still open during the
137 12/2/04 unoccupied period. Cont.: Fixed. QA to check. Cont. 12/8/04 QA
QA: When a zone goes into setback, which zones go live: only the unit that is below
setpoint, the block of zones used for override, or all zones served by the air handler?
[Eng.] The related isolation zone which is the block of zones used for override. QA
12/4/04: Tested setback, only zone in setback goes live. Change per Eng.'s
comment. Program update arriving 12/10/04, QA to test 12/11/04. 12/11/04: Unable
to perform test. Cont.'s programmer revision to the override programming has
locked the system on 24/7 in both Main and 2nd floor Met, but not in 2nd Floor Main.
140 12/3/04 12/4/04 Called Cont. to correct. 12/13/04: Corrected 12/14/04: Checked OK Cont. 12/10/04 QA
148 12/6/04 Cont.: CO2 sensor in contractor's room (Mn134) will be replaced Cont. 12/23/04
Warranty support:MnVAVRH1-7 is operating outside of standard schedule. Local
150 12/16/04 override is not enabled. MnAC1 is being energized to early. Cont. 12/23/04
If a local zone goes into setback, its group of zones are also suppose to come on in
151 12/18/04 setback with unoccupied setpoints. They are currently coming on with occuppied Cont. 12/23/04
ChW Pumping
Chilled Water Plant
Is sequence M5 adequate to meet Standards Lab needs if AC-4 Chiller is down? Mn
4 1/15/04 4/7/04 Chiller sequence modified 6/21/04 to maintain 42 deg.F if MnAC4 is on Team QA
Main cooling tower: Why is Lo Status on when Lo Cmd is off and High Cmd is on
37 7/7/04 8/13/04 and Hi Status is on? Cont. 8/31/04 QA
There are three sets of temperature sensors for the entering and leaving chilled
water temperature. The strap-on sensors are not acceptable and do not comply with
specification section 2.12.A.4 and should be removed from the chiller piping. One of
the other two sets of sensors may be used our new well sensors may be installed.
The immersion well sets of sensors are for the Onicon meter and for the York control
panel. If either of these can be communicated with they should be used. The
preference is to use the Onicon meter and avoid primary control of the chiller though
45 7/28/04 a gateway. Cont. 8/31/04 QA
52 8/4/04 8/13/04 Why are there two MnChlr1 Run points? QA to fix. Cont. 8/31/04 QA
What is the status of getting data from the York Chiller via the gateway? It does not
54 8/5/04 8/13/04 appear fully operational. New template installed. OK Cont. 9/19/04 QA
MnChlr1 cooling tower is having trouble meeting setpoint. High fan on even though
94 9/24/04 10/19/04 delta T across the chiller is only 2-3 deg.F. Programm is OK Team 11/1/04 QA
HoW Pumping
Boilers
MnAC4 Boiler - Why is HoWRT is higher than HoWST? Sensors swapped at
15 4/26/04 controller. QA
33 5/21/04 5/28/04 MnBlr: Need status point for Condensate Return Pump (MnBlr ConRP Status) Cont. 8/31/04 QA
New MnAC4Blr and pump is running, yet MnAC4 Xovr valves are in House. My
understanding was that the changeover valves would lock out the pump. See 1
86 8/30/04 above. (7)
134 11/21/04 New MnAC4Blr needs to run w/o 2 DO's Cont. 12/8/04 QA
VFD's
VFD data via Mod Bus is missing from this points list. This data needs to be unique
23.1 4/14/04 for each VFD.
23.1 8/13/04 QA enter point names in program. QA
MnAC1, 2 & 5 and VFD graphics do not provide data for whe VFD in local "hand"
mode. This is an essential point for each VFD per spec. Put "VFD in Hand" alarm
from sequence on air handler graphic. QA: Graphic added to MnAC1,2&5; no
23.2 8/13/04 graphic added to VFD - OK Cont., (6) 8/31/04 QA
Is fan status as it is currently implemented from the VFD adequate (VFD says fan is
on but it isn't), can it be modified to look at current level or is a current switch on the
56 7/7/04 motor needed? See 7/7/04 e-mail to Eng..
We continue to have occurrences when MnAC2SF VFD says that it is on and the
motor is not spinning. ABB says they cannot find a problem. 9/1/04: Cont. to
56 8/4/04 8/13/04 request that ABB to replace unit. 10/19/04: Was MnAC2SF VFD unit replaced? Yes Cont. 9/19/04 QA
The procedure for resetting the drive after a failure is identified (as in 56 above)
62 8/5/04 8/13/04 needs to be documented. It was decided to request that the unit be replaced instead. (7)
81 8/23/04 8/30/04 Why are we seeing ~20% to 25% difference between VFD CmdHZ and VFD Freq?
VFD's are programmed by the Mfg rep with 15 Hz @ 0 input volts. This requires
minimum PID output to be 25%. Programming for MnAC1, MnAC2 and MnAC5 has
81 10/23/04 been corrected so that Spd Cmd, Volts out and VFD Hz are the same.
81 10/25/04 Eng.: Spec requires 10Hz minimum. Cont. to reprogram VFD and sequences. Cont. 11/1/04 QA
MnAC1, 2 & 5 VFD's: Mod Bus communication is intermittent. Data quality is poor.
95 9/30/04 10/4/04 Units reset by turn off and on - data look Ok. Cont. ? QA
MnAC1SFVFD and MnAC2SFVFD: Drive Status Bit and Fault Status Bit are not
consistent with themselves or with the other VFD's. Fault in on, Drive is off and the
96 9/30/04 10/4/04 fan is running? Units reset by turn off and on - data look Ok. Cont. ? QA
122 11/9/04 VFD Mod Bus data appears to be 3 minutes earlier than ALC command data. Why? Cont. 11/19/04 QA
Electric Demand Monitoring
Pulse output on electric meter in basement has been installed. Connect wires too
terminal block in conduit box. K factor is on meter. Unfortunately, this meter is not
74 8/12/04 the primary building meter. Cont. 8/31/04 QA
Load Calcs & History
Btu meter is reading high 300 tons. Chiller is rated 195 tons. Chiller flowmeter is
38.1 7/28/04 reading 750 gpm. Historically this flow has been around 500 gpm.
38.1 8/17/04 Pipe is 6 inch not 8 inch. Correct at BTU meter. Cont. 8/31/04 QA
38.2 7/28/04 Chiller kW appears to low. Data should be somewhere between 60 and 80kW.
38.2 8/17/04 DDC output compares well with chiller panel meter. (2) QA
Plant performance should read zero when chiller is off. Use flow >100 gpm as a
87 8/30/04 threshhold. Cont. QA
Events/Alarms
Need means for locking out an alarm that has been acknowledged, but for which
58 8/5/04 8/13/04 maintenance is pending Cont. 8/31/04 QA
61 7/26/04 QA provided comment on Alarm matrix.
Paged and e-mail critical alarms should be identical as possible conveying enough
information for the individual receiving them to understand what is going on. See QA
10/6/04 mark-up of Cont.'s spreadsheet. 11/2/04: Cont. to review; remove
61 8/12/04 standardslab template making each meassage unique as defined. Cont. 8/31/04 QA
64 8/13/04 Provide training in setting up alarm messaging Cont., (8) 8/31/04 QA
Verify the system will alarm when fan is commanded on but the fan does not operate
67 8/12/04 such as when a HOA is off, a VFD does not work or a fan belt is off. Cont., (6) 8/31/04 QA
Environmental Chamber & Cooling Tower: Add condenser water pump on to
76 8/19/04 8/20/04 CondWS and R Temp overrange events. QA revised limits. Cont. 9/19/04 QA
91 9/23/04 Non critical alarms need to be delayed - suggest 1 hour - Training provided Cont., (8) 11/1/04 QA
Event outputs blocks have not been attached to MnAC1 and MnAC2 runtime blocks.
Thresholds should be set for appropriate maintenance periods for fan motors, belts
98 10/6/04 and filters. Cont., (8) 11/1/04 QA
MnBlr went down @ 18:00 on Friday. The Std Lab zone temp then later went into
alarm. No paged alarms were sent to Facilities staff. Why? Cont.:"from" email was
114 10/30/04 11/1/04 missing in progrqm. Cont., (6) ? QA
All alarms under the category of HVAC General are classified in alarms
programming as "Critical". Why? (2) Has the critical alarm matrix been
115 10/30/04 11/1/04 implemented? Cont.: Yes QA
There are now no critical alarms. This category have been removed. Why?
141 12/8/04 12/10/04 Cont.: We don't know; will fix. Cont. 12/15/04 QA
REMARKS:
(1) EXISTING CONDITION DETERMINED TO BE ACCEPTABLE
(2) DETERMINED NOT TO BE A QA PROBLEM
(3) May be a problem, but out off scope
(4) Discuss once initial installation complete
(5) Document in Systems Manual
(6) FT
(7) Addressed in another item
(8) Requires training
# Trends & Events
Cont. Contractor and techs
QA Owner's QA Rep
Eng Engineer
IT Information Tech services staff
Operator Owner's building mechanics
nt is neither approved
DATE: 12/24/04
Cont. 10/25/04 and 11/16/04 Phone Call 2004-10-25 (GAF
DATE Comments Notes)
10/5/04
10/23/04
6/22/04
6/1/04
5/5/04
8/31/04
Let's schedule a walk to
confirm the completion of this Done, needs a walkthrough
item with QA.
11/21/04 Still need MetAC-2 labeling.
Let's schedule a walk to
confirm the completion of this Done, needs a walkthrough
item with QA.
MET Roof, the final panels to
11/17/04 be labeled, are complete.
10/23/04
Let's schedule a walk to
confirm the completion of this Done, needs a walkthrough
10/26/04 item with QA.
8/30/04
8/26/04
Let's schedule a walk to
confirm the completion of this Done, needs a walkthrough
10/26/04 item with QA.
9/1/04
This is just a room sensor.
QA wants the logic changed
11/2/04 so it is just that simple.
Cont. revising O&M per
commentsfor review and Eng..
Submitted from QA 11/5/04.
Revised plan submitted for
11/16/04 review 11/15/04. 7 hard
Schedued 11/17 and 11/19,
11/21/04 9AM - 1PM. 6 Trainees.
12/24/04
10/16/04 Complete and proven 11/2/04.
12/24/04
Cont. to provide this training
11/21/04 during our training sessions.
11/9/04
11/17/04
12/10/04
12/15/04
12/15/04
12/15/04
12/24/04
10/19/04
10/1/04
8/13/04
8/13/04
10/19/04
8/13/04
10/1/04
8/30/04
8/13/04
10/1/04
8/5/04
8/2/04
8/13/04
8/13/04
10/19/04
10/5/04
10/19/04
10/19/04
8/28/04
Cont. will do tomorrow with
11/21/04 Will add 10/26/04 Cont.'s programmer.
10/19/04
10/1/04
10/1/04
10/19/04
10/26/04 Complete.
12/2/04
12/3/04
8/30/04
11/17/04 Training Manual Will merge into submittals.
10/1/04
11/21/04 Complete 11/4/04. Cont. will look at this.
10/1/04
Needs to be verified by team.
6/23/04
11/21/04
10/22/04 Done. Need to witness test.
8/4/04
6/23/04
8/4/04
6/23/04
8/5/04
8/5/04
Sensor is affected by
ambient and needs to be
fixed. STILL OPEN. Cont.
Well Sensors installed by will review tomorrow and
Cont.. Complete. comment.
10/28/04
11/21/04
6/23/04
8/4/04
12/4/04
12/10/04
12/2/04
8/5/04
8/19/04
6/23/04
6/2/04
10/1/04
Both sensors in Cont.'s hands
12/4/04 now. Cont. will install ASAP.
Complete. Needs to be
11/22/04 verified by team.
10/19/04
10/25/04 Done.
Re-programming complete
and downloaded. Needs to be
12/3/04 verified by team.
10/26/04 Complete.
Complete.
8/4/04
During startup has zero
setpoint. Needs to start in
heat or cooling. Heating fan
is shutting down. Needs to
DM/DJ to review QA 10/22 use cooling on startup.
email of discoveries. Heating fan needs to run
Reprogamming complete
11/17/04. Needs check by
11/21/04 team.
8/14/04
8/28/04
8/30/04
Cont. awaiting CO18 to
12/10/04 proceed.
10/1/04
10/1/04
May be a balance issue. See
Cont./DM provided additional Eng.'s trend log review
11/21/04 PID tuning. comments.
This is air noise in the hot
water loop. This may be after
boiler was replaced and air
go in the system. Air may
need to be vented. Not an
Per the team, this is no longer Cont. issue unless it is a
11/2/04 an issue. valve problem.
Completed. Now works and
air flow goes up when heat is
required. Heat mode
graphics not showing on
graphics screen. Screens
need to update and they do
10/25/04 not.
12/15/04
12/3/04
11/2/04 Complete.
11/21/04
11/9/04
12/14/04
12/14/04
8/4/04
9/1/04
8/19/04
8/19/04
10/5/04
10/15/04 Operating per sequence.
4/27/04
8/19/04
12/9/04
8/13/04
10/19/04
VFD has been replaced.
10/25/04 Resolved.
Programming issues by VFD
factory to have 15 Hz
minimum so 0 volts equals
15 Hz. ALC ranged 0 to 60 ,
not 15 to 60. Now 25%=0
volts and everything agrees
and this is true for all five
drives. Minimum should be
10 Hz. Per section 3.03D.1.c.
10/26/04 Resolved.
10/5/04
10/5/04
11/21/04
8/19/04
8/18/04
8/17/04
9/2/04
11/21/04 Training Manual. Cont. will get this to us.
QA provided this so it is up
to Cont.. Nothing will be
coming from Operator and
Operator2. Cont. will find this
11/21/04 Cont. to finalize. or ask QA for it.
11/17/04 Cont. to provide training Training will be provided.
11/2/04 Needs to be verified by team. Witness test item.
10/19/04
This is training item so
Operator and Operator2 can
11/17/04 Cont. to provide training set this up.
This is a training item and
the outputs need to be
generated. Cont. needs to
generate the run time output
11/21/04 for maintenance alarm.
11/2/04 Complete.
11/21/04 Cont. to verify and prove.
12/13/04
ITEM ID Notification ISSUES
LOG
NO. DATE DATE Trended Device Date of Trend Time of Day
MnVAVRH1-
TE-1. 10/20/2004 10/20/2004 19/General 9/19/2004/General Afternoon/General
MnVAVRH1-
TE-2. 10/20/2004 10/20/2004 19/General 9/21/2004/General Morning/General
TE-3. 10/20/2004 10/20/2004 MnVAVRH1-18 9/19/2004 Afternoon
TE-4. 10/20/2004 10/20/2004 MnVAVRH1-18 9/20/2004 Morning
TE-5. 10/20/2004 10/20/2004 MnVAVRH1-17 9/19/2004 Afternoon
TE-8/10. 10/20/2004 10/20/2004 MnRH1-109 9/20/2004 Morning
TE-9. 10/20/2004 10/20/2004 MnVAVRH1-16 9/20/2004/General Morning
TE-16. 10/20/2004 10/20/2004 MnRH1-107 9/21/2004 Afternoon
TE-18. 10/20/2004 10/20/2004 MnRH1-3 9/21/2004 Morning
TE-20. 10/20/2004 10/20/2004 MnAC1SATemp 9/19/2004 2:00 PM
TE-24. 10/20/2004 10/20/2004 MnAC2SATemp 9/21/2004 10:00 AM
Resets from zones
TE-27. 10/20/2004 10/20/2004 and rogue zones General General
TE-29. 10/20/2004 10/20/2004 MnAC1OADamper 9/21/2004 14:00
TE-30. 10/20/2004 10/20/2004 MnAC2OADamper 9/21/2004 14:00
TE-31. 10/20/2004 10/20/2004 MnAC3 9/22/2004 General
MnVAV1-19
Heating SA Flow
TE-35. 10/20/2004 10/20/2004 Reset/General 9/29/2004 General
9/21/2004/ 4:00 PM/
TE-38. 10/24/2004 10/24/2004 MnAC4Boiler General General
AC5 SAStatic
TE-39. 10/24/2004 10/24/2004 Pressure General General
Environmental
TE-40. 10/24/2004 10/24/2004 Chambers General General
TE-43. 10/24/2004 10/24/2004 Chilled water plant General General
TE-44. 10/24/2004 10/24/2004 MtAC2 OA Damper General General
TE-46. 10/24/2004 10/24/2004 MtAC3 General General
TE-47. 10/24/2004 10/24/2004 MtAC3 General General
TE-48. 10/25/2004 10/25/2004 DD-1 9/21/2004 4:00 AM
TE-49. 10/25/2004 10/25/2004 DD General General
TE-50. 10/25/2004 10/25/2004 Page 14 of 65 As Built Drawings
TE-51. 10/25/2004 10/25/2004 Page 17 of 65 As Built Drawings
TE-52. 10/25/2004 10/25/2004 Page 20 of 45 As Built Drawings
TE-53. 10/25/2004 10/25/2004 Page 29 of 45 As Built Drawings
TE-54. 10/25/2004 10/25/2004 Page 31 & 32 of 45 As Built Drawings
TE-55. 10/25/2004 10/25/2004 Page 35 & 42 of 45 As Built Drawings
Items noted with "General" means this happens in many other trends and is referenced to one trend for information.
Items noted with "General" shall be addressed on all similar points.
Were the term “General” is used it means that the same observation was found on other similar systems and all systems shoul
ISSUES ACTION REQUIRED CHECKED
LOG PARTY
Comment Responsible DATE REQ. BY DATE
Unit could not achieve airflow setpoint. Raised max
duct static for MnAC1, MnAC2 and MnAC5 to 2
inches. Cont 10/29/2004 QA 11/22/2004
SA temperature is not maintained at 95oF setpoint.
SA temperature setpoint and hot water valve position
are not trended. Cont 10/29/2004 QA 11/22/2004
Unit could not achieve airflow setpoint. Cont 10/29/2004 QA 11/22/2004
HW valve cycles from 0 to 50% during warm up. The
heating SP is not trended so this cannot be
evaluated. The cycling appears to be during warm-up
when warm-up cycles unit on and off before the
occupied period. QA 11/22/04: Setpoint is achieved
at 6:00 AM with limit hot water valve cycling. Cont 10/29/2004 QA 11/22/2004
Unit could not achieve airflow setpoint. Cont 10/29/2004 QA 11/22/2004
SA Temperature does not maintain 95oF setpoint
and hunts 30 to 40oF every 15 minutes. QA
11/22/04: PID response is impacted by SA Flow from
VAVRH1-14. When the master zone is satisfied, air
flows drop, which excites the PID (+/- 20%). Things
stablize at higher flows. Cont 10/29/2004 QA 11/22/2004
HW valve opens 100% and SA temperature does not
get above 72oF. 11/2/04: Valve closed Cont 10/29/2004 QA 11/22/2004
SA Temperature does not maintain 95oF setpoint
and hunts from 55 to 95oF every 10 minutes. QA
11/22/04: This continues ot happen. QA 12/2/04:
PID sample increased from 10 to 60 secs; now 65oF
to 95oF every 45 min. Cont 12/3/2004 QA 12/3/2004
Not heating up and HW is cycling every 6 minutes.
HW Valve is not trended. SA does not maintain 95oF
setpoint. QA 12/4/04: Cont. increased PID from 10
to 60 secs. Cont 10/29/2004 QA 12/2/2004
The supply air temperature fluctuates by up to 5oF
every 6 minutes. QA 11/22/04: It cycles 15oF every
35 minutes in the afternoon. QA 12/2/04: winter
operation looks OK. Cont 10/29/2004 QA 12/2/2004
The supply air temperature fluctuates by up to 5oF
every 6 minutes. QA 11/22/04: It cycles 15oF every
35 minutes in the afternoon. QA 12/2/04: winter
operation looks OK. Cont 10/29/2004 QA 12/2/2004
Check for rogue zones, see Specification Section
2.04B.5.c.3. Eng.: Reports now exist and work.
Dmpr Pos (%) notation is misleading. Change to
Percent of Setpoint Flow. QA: Delete Rogue Zone
graphic - data found in VAV Zone Condition Monitor
graphic; change notation in it. Cont 12/3/2004 QA 12/3/2004
OA gets over 80oF and the OA damper is still open.
Explain. Cont 10/29/2004 QA 11/22/2004
OA gets over 80oF and the OA damper is still open.
Explain. Cont 10/29/2004 QA 11/22/2004
What initiates this unit? Does it normally not run?
QA: Override only. Cont 10/29/2004 QA 11/22/2004
Airflow does not change with ZAT in heating. Why
not? Cont 10/29/2004 QA 12/2/2004
HSWR & HRWT go down when the OA goes up.
Why? Is it influence of ambient or is it because the
reheat load is the highest at high OA conditions? Is
the boiler too small? No, No; new boiler reaches
temp quicker than HoWVlv can react, so temps cycle
but are stable. There is no corrolation with OAT.
Unit is to be reconfigured so that ther is no direct
control of Lo/Hi fire. See 11/22/04 witness test log. Cont 10/29/2004 QA 11/22/2004
Supply air static pressure does not track the setpoint.
Why? Cont 10/29/2004 QA 12/2/2004
When
Run trend log with new sensors and new chambers Cont possible QA 12/2/2004
Are the power units and tons correct? Cont 10/29/2004 QA 11/22/2004
Is the damper control working, it is not trended? Cont 10/29/2004 QA 11/22/2004
He and Co requests don't seem correct since they
change without a pattern or not at all. Explain. Cont 10/29/2004 QA 12/2/2004
Why do the fans operate over the weekends? Cont 10/29/2004 QA 12/2/2004
Why is the total flow higher than the hot or cold flow
when only one is supposed to be on? Cont 10/29/2004 QA 12/2/2004
DD Boxes are not working per spec. Correct. QA
12/3/04: Program corrected. Eng. needs to verify. Eng. 12/8/2004 open
TE: Dewpoint sensor, not humidity sensor. QA:
There is no dewpoint sensor. The inputs are
ambient temperature and humidity. Dewpoint
temperature is calculated by the controller. Cont 12/8/2004 Eng. 12/18/2004
Boiler has high and low fire Cont 12/8/2004 Eng. 12/18/2004
Are these space sensors accurate for what is
installed? Are these sensors included in the O&M
information? Cont 12/8/2004 Eng. 12/18/2004
Remove damper is the box is a CAV without a
damper. Cont 12/8/2004 Eng. 12/18/2004
How is slave controller wired? Cont 12/8/2004 Eng. 12/18/2004
Are these units single stage cooling? Cont 12/8/2004 Eng. 12/18/2004
o one trend for information.
similar systems and all systems should be corrected for this situation.
Cont Action
Raised max DS Sp to
2.0 from 1.5
Modified Zone PID
Raised max DS Sp
Modified, downloaded
and verified FB.
Raised max DS Sp
Modified Zone PID
Found that circuit setter
was closed
Modified Zone PID
Modified Zone PID
Sped up PID
Sped up PID
Rogue zone graphic is
completed.
Re-verify with team.
Re-verify with team.
Re-verify with team.
Modified FB
downloaded.
We shall run trend for a
few more days and
review as a team.
Sped up PID.
We plan to install
sensors this week; we
first need to ask Becky
if we can shut down
units; connecting
sensors under moist
conditions is a hazard.
Yes.
No. We have modified
the programming and
want to verify with the
team. Verified 11/22/04
Reprogrammed, need
to verify with team.
Reprogrammed, need
to verify with team.
Re-programmed, need
to verify with team.
151
PROJECT: Owner's DDC System Installation Project
ITEM ID Notification
NO. DATE DATE
31 6/17/04
16 4/28/04
3 1/15/04 4/13/04
27 5/21/04
75 8/19/04 9/23/04
TE-42 10/24/2004 10/24/2004
101 10/11/04
44 9/1/04
121 11/2/04
TE-45. 10/24/2004 10/24/2004
139 12/3/04
143 12/9/2004
REMARKS:
(1) EXISTING CONDITION DETERMINED TO BE ACCEPTABLE
(2) DETERMINED NOT TO BE A QA PROBLEM
(3) May be a problem, but out off scope
(4) Discuss once initial installation complete
(5) Document in Systems Manual
(6) FT
(7) Addressed in another item
(8) Still open
HVAC QA ISSUES LOG - Out of Scope DATE: 12/24/04
DDC System Installation Project
ISSUES: Out of Scope ACTION REQUIRED Resolved
LOG By
We had been loosing data in the trends from time to time. Controls Mfg. said
that it could be a network configuration issue. Cont. to meet with IT to resolve.
We need to verify this condition does not return once the server is move to the
basement comm room. (4, 5) QA
MnAC3: once VAVs are operational and stat is installed, stat can be
programmed for 2hr override increments; note max time for this equipment is
224 minutes. Program update my be forthcoming from Controls Mfg. in
November to change this to 8 hours. Cont. Service Tech2 to notify us when it
is available. We may get this under warranty. QA 12/15/04: Installed ; need to
test. (4, 5)
MnAC4: Are we going to reset the Nortec based on outside %RH? Is reset
necessary? Eng.: Not unless dry winter conditions indicate that it is necessary.
QA 11/21/04: It appear we are over dehumidifying in winter. Consider resetting
coil leaving air temp based on hot water and humidifier PID > 25%. QA
11/29/04: Tried this wihtout much success as chiller operation impacts zone
temp stability. Need chiller with greater turndown. (3, 4, 5)
MnAC4 Chiller Setpoint is 45 deg.F. How is this physically set? It does not
always provide low enough chilled water to meet %RH setpoint; see 5/21/04
data. The chiller setpint is internal to the chiller. It is set at 38 deg.F leaving
water temp. Air handler may not have enough capacity. (3, 4, 5)
MnAC4 Chiller Comp 1 & 2 Alarms do not appear functional. Are these analog
or digital points? Per Cont. tech MnAC4Chiller Alarm outputs do not work (3, 4, 5)
MnAC7: Why does the SA temperature on cooling run so high? Does not get
below 58oF. This appears to be a mechanical issue. (3, 4 ,5)
Wining noise coming from VAV box 1-19 in Room 134 Main building. After 4
hours the noise went away and has not come back sense. 10/25/04: This may
be a warranty issue, but Owner's staff needs to help diagnose problem if it
happens again. Noise comes from a loose duct access cover. Operator2
installed a piece of cardboard to quiet it. (5) QA
York Gateway to be used to reset chiller leaving water temperature instead of
hard wire. 10/1/04 - Chilled water reset is being sent to and being received by
the York chiller but it does not appear to be functioning. Understand from York
that the control board in the chiller needs updating. (3, 4, 5)
House chiller chilled water pump currently cycles on/off under low load
conditions (currently after ~3 hours). Consider disabling the house chiller
based on cooling request and all ChWVlvs at 0%. QA 12/15/04: Control
program enables the chiller start sequence to run, which then turns on the
chilled water pump. The chilled water pump should stay on as long as the start
sequence is enabled. It is disabled once the all ChWValves are at 0%. Why
the pump has been staying on for an extended period of time beyond this
needs to be investigated. It also needs to be tested when MnAC4 on the house
chiller. (3, 4, 5)
MtAC3: CoSAT gets down to 38oF. This is too cold. Airflow may be difficient. (3, 4, 5)
MtAC2: 1st stage of heating does not appear to be functioning properly. SA
Temp is not warm up until 2nd stage operates. (3, 4, 5)
Main building heating hot water loop may need balancing. This could the
source of MnVAV2-6 and 2-7 capacity problems. Cont. has confirmed that the
newly installed valves were correct. HVAC.Maint.Cont. is scheduled to check
all strainers. (3, 4, 5)
EXISTING CONDITION DETERMINED TO BE ACCEPTABLE
DETERMINED NOT TO BE A QA PROBLEM
May be a problem, but out off scope
Discuss once initial installation complete
Document in Systems Manual
Addressed in another item
DATE: 12/24/04
Resolved
Date
12/17/04
11/22/04
Heating, Ventilating, and Air Conditioning Systems Witness Testing
Test Expected response Observed response Pass/Fail
Morning system All rooms satisfied Not all rooms were satisfied. Fail
review, check out Not all rooms work properly
rooms not satisfied and achieve comfort.
and find out why
MnAC-4 Hot COV: Graphic should Graphic changed. Alarm Pass
Change the hot water change, check for received.
change over valves alarm
MnAC-4 Cold COV: Graphic should Graphic changed. Alarm Pass
Change the chilled change, check for received.
water change over alarm
valves
CO2 control: Increase Zone minimum flow VAV box flow increases. Pass
MnVAV1-12 CO2 PID of zone goes to
to 50% increased flow
CO2 control: Increase AH-1 minimum OA damper minimum reset. Pass
MnVAV1-12 CO2 PID outside airflow goes
to 100% to increased flow
Confirm main chiller Supply water Chiller supply water setpoint Pass
supply water reset by temperature reset.
closing all valves to changes based on
no more than zone
Check rogue 50% mostzones valve
Find open that No report. Fail
reports for rogue cause chilled water
zones reset and AH static
pressure reset
pressure reset
Check for rogue zones Find zones that Checked manually and MnAC- Pass
cause chilled water 1, AC-2 & AC-5 all reset
reset and AH static supply air static pressure.
pressure reset Chiller reset supply water
setpoint.
Put MnAC-1 return Graphic change and VFD indicates “HAND” on Fail
fan VFD out of out of range alarm graphic. No alarm. Alarm
desired range by when power is turned off at
putting in “HAND” motor control center. Correct
for all fans with VFD’s.
MnAC-5 create high AH should lock out, Failed low and high. Correct Fail
supply air pressure alarm and can be and test for all VAV systems.
reset “are reset by
the reset DO point
or a push-button on
the panel face. A
pilot light on the
panel face indicates
static pressure
safety lockout is in
effect”
Afternoon system All rooms satisfied Not all rooms were satisfied. Fail
review, check out Not all rooms work properly
rooms not satisfied and achieve comfort.
and find out why
Check trends for Data is in history Recent data history exists. Pass
recent history data
Simulate server Server comes back Rebooted. Pass
power outage on line, controls
function normally,
date and time is
correct
Close large MnVAV Flow reads near zero Cont. to do this in the evening Not Done
box completely and confirm success.
Close small MnVAV Flow reads near zero Cont. to do this in the evening Not Done
box completely and confirm success.
Check MnAC-4 chiller Graphic reads near Readings are more accurate Pass
SWT & RWT same temperatures since sensors were changed
to wells.
Cycle Mt DD-8 box to Box sequence Not Done
cooling and heating responds per
specifications
Mt DD-8 verify airflow Readings are Not Done
readings on hot and accurate
cold ducts
Mt DD-6 verify airflow Not Done
readings on hot and
cold ducts
Set all Met DD boxes Last box stays in Not Done
but one to cooling and heating for minimum
put last box in airflow and hot fan
heating, then last box stays on
in deadband
Set all Met DD boxes Hot fan turns off Not Done
to cooling
MnAC-5 change OA Cooling does not Cooling does not lock-out. Pass
temperature to 30oF lock-out
MnAH-1 set to 10Hz VFD runs at 10Hz Worked. Pass
SA command speed
Place MnAC-1 VFD in Alarm generated Alarmed. Pass
off
MnVAVRH 2-31 a/b Both dampers open Only one damper opens in Fail
full heating to heating max and 100% heating.
supply air
temperature
maintained at
setpoint
MnVAVRH 2-31 a/b Both dampers open Does not work. Fail
full cooling to cooling max
MnVAVRH1-17 full Damper open to full Goes to max setpoint, flow Pass
cooling cooling max achieved.
Building pressure Return fan and EA Responded. Pass
0.15” damper respond
Turn chiller on, Chiller power QA has confirmed this. Pass
measure power graphic is accurate
MnAC-5 measure Graphic is accurate Magnehelic reading 1.4” to Pass
static pressure 1.5”, graphic reading 1.46 to
1.50.
MnAC-7 on cooling, Graphic is accurate Fluke reading 58oF, graphic Pass
measure SA reading 59oF.
temperature
MnAC-8 on cooling, Graphic is accurate Fluke reading 59oF, graphic Pass
measure SA reading 59oF.
temperature
Mt AC-3 on cooling, Graphic is accurate Not Done
measure SA
temperature
Verify Met heating Requests are Not Done
and cooling request accurate
Mt DD-1 verify airflow Graphic flow is Not Done
accurate
MtAC-1 remove fan Unit status changes Unit status changed. Pass
current switch
MtAC-5 verify supply Check with Fluke Fluke reading 56.7oF, graphic Pass
air sensor calibration meter reading 56.8oF.
MtAC-1 remove fan Unit turns off No response. Correct all DX Fail
current switch heating and cooling systems’ function blocks.
and alarms
MtAC-1 cycle cooling Should time out 5 Timed out 5 minutes. Pass
minutes before
starting cooling
MtAC-2 OA damper Damper should close Does not close Fail
during unoccupied
MtAC-2 Cooling Follow spec No interlock with cooling and Fail
sequence condenser water pump. No
interlock with fan.
Electric heat should Stages cycle. Removed 5 Pass
cycle on. minute off timer.
WhAC-1 No cooling cycle time delay. Fail
Change electric heat section
of function block to gas heat.
Additional Cont. to address 2-9 needs to be tuned Fail
Observations items
2-6 check to see flow
and valve is correct.
Observations items
2-31a/b is valve in
backwards, why isn't it
working?
Change MtAC-3
cooling fan only operates
during occupied, setup or
cool down modes
Change MtAC-3
heating fan only operates
during occupied, setback
or warm-up modes and not
when all zones are in
cooling
Remove low limit on
economizers
DD-5, 6 & 7 when hot
is closed graphic displays
open.
Main Chiller cycles
chilled water pump when it
reaches setpoint. This is
bad for Standards Lab.
Cont. shall provide
proposal for interlock relay
to run chilled water pump
when AC-4 is running on
house chilled water.
Eliminate reset on
chilled water setpoint when
AC-4 is on building chiller.
Can the York chiller
leave the ChWP on when
the system is enabled and
not cycle the ChWP with
the chiller? Met with York
technician.
Spec Section 15900 3.16C.3.c. reads, “c. Any tests that fail to demonstrate the operation of the system shall be repeated at a l
Any tests that fail shall be remedied and all similar system types shall be similarly corrected and retested by the contractor prior
11/22/2004 Pass/Fail 12/2-3/2004 Pas/Fail
AC-1 all okay. Fail Fail
AC-2 zones are operating properly AC-2 zones are operating properly
except 2-6 and 2-7 are not working on except 2-6 and 2-7 are not achieving
heating. They are not achieving supply supply air temperature of 95oF. Cont.,
air temperature of 95oF. please confirm that these valves are
sized properly.
Hot water controls is not working on Yet to be corrected
local boiler. Sensors are bad and in
wrong location. The local boiler is only
enabled by Controls, not controlled. The
control is local on the boiler for 180oF.
The Controls program only enables the
pump and boiler per spec.
MET DD zones are cold. The MtAC3 is Much better
bringing on cooling when no zones are
calling for cooling.
Reports now exist and work. Fail QA: Delete Rogue Zone reports; data Pass
found in existing VAV Zone Conditon
Monitor - changed notation in it.
Dmpr Pos (%) notation is misleading.
Change to Percent of Setpoint Flow.
MnAC5 SAT is not resetting properly. At OK
55oF OA we are seeing a setpoint of
54.5oF when no zones are calling for
cooling. Check all the VAV AHU supply
air FB’s. Same DATSP on AC-2 so this
is wrong, too.
This already passed. Glenn had it noted Pass
wrong.
Not ready to test yet. They will test. Fail Pass
Not done. All rooms satisfied except MnVAV-6 with Fail
the reheat valve at 100%.
Cont. Tech did this in the evening. 2-22 Pass
reading plus or minus 1.5%.
Cont. Tech did this in the evening. 2-20 Pass
reading plus or minus 5%.
Responded properly. Checked max Pass
heat, max cooling, min heat, min cool
and changeover latch. All work.
Controls reading 80 CFM in heating with Fail Readings were corrected and checked Pass
110 CFM SP; hood reading 230 CFM.
Magnehelic reading is 0.3” which is 245
CFM.
Controls reading 280 in cooling with 280
CFM SP, hood reading 152 CFM.
Magnehelic reading is 0.025” which is
143 CFM.
Controls reading 380 CFM in heating Fail All zones airflows were within 5% of Pass
with 100% open; Magnehelic reading is Need to magnehelic measurements
0.75” which is 390 CFM. confirm
Controls reading 210 CFM in heating this for
with 225 CFM SP; Magnehelic reading all
is 0.175” which is 195 CFM. boxes.
Controls reading 230 in cooling with 240 Check
CFM SP, hood reading 120 CFM. Mn 2-6,
Heat fan stays on. Pass
Heat fans turns off. Turned one zone on Pass
and the heat fan comes on.
Maintaining 95oF DAT on heating. Pass
Both dampers open in both heat and Pass
cool.
Return 67.5oF measured and 68.2 oF in Pass
Controls.
57.5 measured and 55.8 in Controls.
Run when I run is still in place so there Fail Pass
are extra requests.
Measured DD-6 & 8 and both failed; so Fail Five in Main building were correct. All Pass
skip this and leave it to the contractor to zones in Met were corrected - see Cont.
verify all boxes in this building and Tech's spreadsheet. 3 were check w/
check (5) in the main building. If there QA per above.
are three failures there, then correct
them all.
Unit is heating. Removed current Pass
sensor. Heat cycled off.
Timed out on cycle. Pass
Trend shows it does close when Pass
unoccupied.
Works except it does not shut cooling Pass
off when the fan is not on. Tag ties to
“RUN” not “F.”
Change FB from “RUN” to “F”.
Done. Pass
2-9 is tuned (pass) Fail Pass
2-6 is not working. (fail) Eng.: HoWValve is at 100%, but not
What is flow balance at design and meeting setpoint-may lack capacity.
are we getting it? Out of scope (pass)
2-31a/b is working. (pass)
MtAC-3 cooling fan only Test not feasible during winter-future
operates during cool down and (pass)
setup. Needs to be verified. (fail)
MtAC-3 During setback and (Pass)
warmup eliminate requirement for
cooling fan to be on in order to run
heating fan. Needs to be verified.
(fail)
Economizer low limit has been
removed. (pass)
DD-5, 6 & 7 graphics display
correctly. (pass)
Mn Chiller pump is staying on Out of scope (pass)
even though the chiller is cycling off
when AC-4 is in local chiller. We do
not know why. (fail)
Completed (Pass)
Mn Chiller pump is staying on even Control's program enables the chiller
though the chiller is cycling off when AC- control, which turns on the chilled water
4 is in local chiller. We do not know why. pump. The fact the pump stays on for
(fail) an extended period of time even when
the chiller is cycled off is out of scope.
Issue added to the out of scope list.
(pass)
the operation of the system shall be repeated at a later date. The EMCS Contractor shall be responsible for any
milarly corrected and retested by the contractor prior to additional witness testing by the engineer.
12/15/2004 Pass/Fail
Pass
Cont. has confirmed
that these valves were
sized properly.
Working
Out of scope Pass
Get documents about "