					GAS RELEASE PANEL                                                                                    SPencer    FIRE SYSTEMS


                                                                                   S.NO.69,LAXMI ARCADE,OFFICE NO.4,FIRST FLOOR,
                                                                                   B.T.KAWADE ROAD,GHORPADI GAON,PUNE-411001
                                                                                   Tele Fax : 020-26810404 Mobile : 9860706067
                                                                                   E-mail : spencerfiresystems@yahoo.co.in



INTRODUCTION
The SP-GRM is a Micro controller Based Single Gas Release Panel
With Timer & Built In LCD Display,Real Time Clock,Event Logging & On Site
                                                                                 MODEL - SP-GRM
System Configuration.
An Addressable System can be used For Gas Release Application by
connecting a combination of Addressable Control & Monitor Modules
along with the SP-GRM Panel.
Also SP-GRM accepts Inputs from Cross Zoned Relay Output of any
Conventional Fire Alarm Panel or any Devices/Equipment having Output
as Normally Open Contact
The Gas Release Input section has Dual inputs with Cross Zone
detection to avoid accidental gas release.
This Microprocessor Based Gas Release Module Is Implemented With
Wide Range Of Application Required In Gas Release Automation.
It’s Default/On Site Settings Are Suitable To Use CO2,Inergen &
FM-200 Applications.


FEATURES
- Rugged CRCA sheet with powder coating.
- Microcontroller based 16 X 2 Alpha Numeric LCD display with back light.
- Error free Power/Alarm/Gas Release status in unambiguous coloured
  LED indication.
- Real Time Clock & Event Logging for Input Alarm,Power Fault &
  Gas Release Events.
- Poly-Carbonate LCD display membrane keyboard with Tactile switches.
- ON site system configuration/setting for Gas Release operations Via
  programmable LCD display keyboard.
- Cross Zonning Facility.
- Monitored Power Supply-Operates On 230V, AC Supply.
- Battery Back Up with built in charging.
- Relay out puts for Cross Zonning /Input Alarm & Actuators.
- Solenoid circuit monitoring for Open & Short Circuit.
- Two modes operating facility (Auto/Manual)
- Built in Instant Gas Release switch in Auto mode.
- Built in Gas Inhibit switch in Auto/Manual mode.
- Manual Release & Manual Abort Facility from field.
- Manual Gas Release Operation with or without Timer.
- Programable Time delay for Solenoid ON:0 - 999 sec.
- Programable Time delay for Solenoid cut off:15 - 999 sec.
- Actuator Pressure Low status monitoring.
- Gas Release confirmation via Pressure Switch status monitoring.




TECHNICAL SPECIFICATIONS                                                    GAS RELEASE OUTPUTS
- Mains Supply              : 230V AC,50 Hz.                                - Cross Zone Hooter/Strobe Output    : 0.5 Amp. @ 24 VDC
- Standby Supply            : 24V DC Battery                                - Solenoid Output                    : 0.75 Amp. @ 24 VDC
- Charger Capacity          : 7 Amp. Hour Battery Max.
- Operating Voltage         : 24V DC
                                                                            REMOTE OUTPUTS
CIRCUIT PROTECTION                                                          - Cross Zone Alarm Contact (C,NO,NC) : 120 VAC/24 VDC @ 2 Amp
- Mains Supply              : 1 Amp. Fast Blow Fuse.
- Battery                   : 2 Amp. Fast Blow Fuse.                        PANEL DIMENSION
- System                    : 2 Amp. Fast Blow Fuse.                        - 350 mm (L) X 275 mm (H) X 100 mm (D)

CURRENT CONSUMPTION
- Panel Standby Current : 80 mA
                                                                            PANEL COLOUR
- Input Alarm Current   : 12 mA Threshold                                   - Broken White
- Input Loop Resistance : 50 Ohms Max.
 GAS RELEASE PANEL                                                                                                                            SPencer         FIRE SYSTEMS



                                       INDICATIONS AND CONTROLS

                                         GAS RELEASE PANEL

                                                          SP-GRM
                    SYSTEM ON                                                                                                               AUTO MODE
                                                        LCD DISPLAY
                    A C ON                                                                                                                  MANUAL MODE

                    BATTERY ON                                                                                                              TIMER ON
                                                                             ALARM
                    CHARGER ON                                                                                                              MANUAL RELEASE

                    SOLENOID FAULT                                                                                                          GAS INHIBIT
                                        MENU                                                                               ENTER
                    ACT.PRESSURE LOW                                                                                                        GAS RELEASED
                                                                                           GAS                         INSTANT
                                        SILENCE               RESET                       INHIBIT                      RELEASE

                     SPENCER                                                                                                                 SP-GRM



POWER INDICATIONS                                       PROGRAMMING                                                                                             GAS RELEASE MODULE
FAULT INDICATIONS                                     AND CONTROL KEYS                                                                                              INDICATIONS




                                               ACT-PL-SW MAN.ABRT MAN.REL.   PRS.SW   ALARM IN   CRZ - HTR   CRZ - RELAY   SOV-O/P

     LCD DISPLAY KEYPAD
                                                                                                             CO
                                                                                                             NO
                                                                                                             NC




                                                                                                                           0V        0V
                                                                                                                            AC        AC
                                                                                                                           BAT       BAT
                                                                                                                           24 V      24 V
                                                                                                                           0V        0V
                                                                                                                                                       26 V




    Survey No.69,Office No.4,First Floor,Laxmi Arcade, B.T.Kawade Road, Ghorpadi Gaon, Pune-411001.
    Tel & Req. Fax: 020-26810404. E - mail : spencerfiresystems@yahoo.co.in / spenterprises@eth.net

				