QuickGuide DoorFan
Document Sample


QuickGuide-DoorFan
2 Install the system
2.1 Set up the door panel.
See: QuickGuide-DoorPanel-Cloth or -DoorPanel-Modular
2.2 Connect the yellow tube between yellow ports
marked "Ref B" on fan and gauge. If the fan has a
green port ("B"), connect the green tube.
2.3 Connect the Ethernet cable between fan and
gauge.
2.4 Pass long red tube through the panel. Toss the
end away from the fan’s airstream.
Note : Water in the tube will result in erroneous readings.
1 Prepare the building
2.5 Install the fan.
2.6 Connect the fan power plug to a wall outlet.
Model 1000
1.1 Close outside doors and windows.
1.2 Open all interior doors leading to conditioned
spaces.
1.3 Turn gas, hot water, to pilot.
1.4 Fireplaces and stoves must be cold with doors Model Q46, Q56 uses 2000 fan
closed. Cover ashes.
1.5 Shut off HVAC, combustion appliances, exhaust
fans, dryers, A/C and furnaces.
See: Manual - Door Fan Operation.pdf for additional
information.
Model Q4E, Q5E & QMG uses 3000SR fan
Remove or Gas valve to Pilot Close all
cover ashes windows
Place gauge case near fan or, on door panel.
Page 1 of 4
M:\PDF\Source\QuickGuide-DoorFan\QuickGuide-DoorFan.docx rev-2011-03-15
3 Conduct depressurization test, CFM@50 Gauge set up
See: QuickGuide-DM2 Mark II Digital Gauge Turn Auto Zero "On" to
3.1 Press [On] twice. zero gauge (every 8
Note See "Gauge set up" on first use. Gauge seconds).
will recall previous set up.
3.2 Press [Baseline]. Press [Enter], to save, when Press [Device] until "Retrotec 1000" is
fluctuation is 1 Pa or less. displayed for 1000 systems,
3.3 Install fan-ring B. "Retrotec 2000" for Q46 & Q56 systems or
3.4 Press [Range Config] to
get "B" on display. "Retrotec 3000SR" for QMG, Q4E & Q5E
systems.
Remove other devices using Setup Menu.
Using Range "B" is good for most houses,
try “C8” for tighter new houses, or “A” for
looser older houses, if required.
3.5 Adjust speed until pressure is about 50 Pa.
3.6 Read results.
Press [Mode] to cycle through results.
Check the Door Fan Operation Manual to
discover the correct results required for
your region.
4 No results displayed? Follow the QuickGuide-DM-2 mark II to
If the target pressure has been reached, but “TOO LOW” eliminate unused Devices, Ranges and
appears, the fan is running too slowly to measure flow. Modes.
4.1 Add the next smaller fan-ring and readjust speed.
4.2 Repeat until a flow is displayed.
4.3 Change [RangeConfig] to match. Press [@ Pressure] to display results
See: QuickGuide-Fan-RangeConfig-2000&3000 exactly at (@) a test pressure. Use Set
If the fan reaches 100% speed, but does NOT reach the Pressure or the menu in Setup to change
target pressure, check to see if a door or window is the value displayed.
open. If not, more flow is needed.
4.4 Remove a fan-ring and readjust speed.
4.5 Repeat until pressure is reached.
4.6 Change [RangeConfig] to match.
If the fan reaches 100% speed with all flow-rings Set Time Avg to 10 seconds. Increase if
removed: the test pressure fluctuates over 1 Pa.
4.7 Press [@ Pressure] to calculate the flow required Wait for twice the Time Average length
to establish the target pressure. before taking a reading.
Note: 2520 cfm is the flow rate that would occur at 50Pa, even though Ex Set [Time Avg] to "10s" then wait for 20
only 36.5 Pa was achieved. seconds before taking a reading.
Tip Use longer time averaging in windy conditions.
Page 2 of 4
Results in cfm Pressurization test
Press [Mode] to access the avaiable results or use Flip the fan to blow air into the house.
[Setup] to access even more results. Some of the
popular options are shown below.
Note: Tubing configuration is the same for both directions.
Adjust fan speed with the gauge
Connect Ethernet style control cable to fan. Solid green
Status light indicates DM-2 is connected.
Press [Set Pressure] [25] [Enter] to test at 25 Pa.
Or establish any test pressure. High test pressures are
more likely to disturb building contents and cause
damage. It is best not to exceed 90 Pa.
Press [Set Speed] [50] [Enter] to set speed to 50%.
Area and volume are input using the The fan will accept any Set Speed from 1 to 100%.
[Enter] key. Tip Click once to change by 1%, hold to increase by 5%.
When speed or pressure is set, press [Jog/Hold] until
"Jog" appears, then [] [] to adjust up or down.
Results in leakage area
Press [Mode] until “EqLA” appears.
The DM-2 displays the pressure and the selected
leakage area.
Press [Exit] to turn the fan off, and clear a saved
baseline value. To stop the fan without clearing the
baseline, press [Set Speed] [0] [Enter] to set the fan
speed to zero.
Adjust fan speed remotely
Note Equivalent Leakage Area (EqLA) describes the leakage Use optional remote up to 300 feet
area in terms of one large hole in a flat surface. Unlike
flow, EqLA is fairly consistent at different test pressures, from fan.
but is usually referenced to 10Pa.
Note Effective Leakage Area (EfLA) is a different measure of
leakage area, and is never used for ducts. It is usually
calculated at 4Pa.
Page 3 of 4
Fan speed control with software Field system check recommended
Speed control is handled automatically with FanTestic Perform a door fan test on the building and record
software, for complete automation. the EqLA.
Install cardboard in upper part of doorway with a 20
x 20 inch hole cut in it.
Perform a second door fan test on the building and
record the EqLA.
Subtract the first from the second result and this
should be 400 sq. in. +/-10%.
Field check gauge (recommended weekly)
Connect the red and
yellow ports.
Both channels
should have same
reading within 1%.
Alternatively, use the a calibration plate in the optional
second fan panel OR use the optional Flexduct with a
400 sq. in. hole in the plate on the end.
Page 4 of 4
Get documents about "