					Manual for Software DALI Professional
Description of Application Program

Introduction
The OSRAM DALI PROFESSIONAL System is a lighting control based on standartized DALI Bus
according to IEC 62386 -> see : http://www.dali-ag.org/

With this a flexible addressable digital lighting control can be built-up. The central component is the
DALI PROFESSIONAL CONTROLLER with 4 DALI lines. These DALI lines can be equipped with
DALI suitable ECG for lamp operation and DALI operation units / sensors.




Detailed product descriptions are available for :
   • DALI Controller
   • DALI Sensorcoupler + sensors LS/PD
   • DALI Pushbutton Coupler


ZPE 2542228 000 00                      Page 1 of 13
Use with PC, first steps

Software Installation

Insert CD

If not already present, install 'Adobe Reader' - for reading the manuals

If not already present, install '.NET2.0 framework'

Install DALI Professional system software by starting
'Setup OSRAM DALI Professional vx.x.x.x.exe'
Default directory for the software : C:\Programme\OSRAM\DALI Professional\

Establish USB connection Controller - PC

Start program with desktop icon             or by
Start / Programs / OSRAM / DALI Professional / OSRAM DALI Professional

Supported Windows Versions : successfully tested with Windows XP, Windows Vista, Windows 7


Operation, Commissioning

Read out devices and addressing

Define groups and functions

Define scenes

Store settings

Store down settings to Controller


--------------------------------------------------------------------------------------
Caption for Screenshots


Menue line

Message line



click for action



pull for drawing connection                
(use numerical order)




ZPE 2542228 000 00                                 Page 2 of 13
Exampleapplication      Single Office
Components              Controller, Luminaires (ECG), Pushbutton / Sensorcoupler

Startscreen, connection with Controller, start search devices




              connect       search
                            devices




Search devices, search process




                                                     if all found and readout ->
                                                     automatic jump into naming
                                                     process




ZPE 2542228 000 00                    Page 3 of 13
Find devices and assign names to them
 start blinkchain
 assign ECG name (if skipped automatic name definition = devicetype port# (device#)




                                                       

               




                                          
 if all ECG identified -> continue with 'Next'

then analog for coupler :
 due to the fix mechanical connection between PIR- and Lightsensor
these devices will get assigned names in same workstep




                                                       




                                                       




                                          
 continue and complete

In the 'Blinking Chain' different parameters can be changed in 'Options' :
e.g. chain velocity, blinkfrequency, lightlevel before, after ....

ZPE 2542228 000 00                      Page 4 of 13
Representation Result Identification of Devices




analog 'Merge'
means merging a existing configuration with new components




Additional feature in mergeprocess : name proposals
Already used names without assigned device are shown in pull down menue
-> important for ECG exchange




ZPE 2542228 000 00                  Page 5 of 13
Define Functions and Parameters - Graph view




                                                                            

                     


                                                                                


                     
                                      




                                a




 pull Ballast with into Graph window
into empty area -> new group will be opened
into group -> added to group

 pull Sensor into Graph window
into empty area -> new group will be opened
into group -> added to group

a observe ressource status

 click into function field and draw line to belonging group -> connected

 define parameters of function (optional if presets shall be changed)

 define actions, finish sequence with Action = <none>




ZPE 2542228 000 00                    Page 6 of 13
Lightsensor - include and setvalue
pull lightsensor into a funktion
add activation possibility (pushbutton and/or PIR sensor)
define suitable reference-ECG (directly influencing the lightsensor)




press button for 'regulation setting'

adjustment window shows up




set requested illumination level (morning or evening to avoid too much natural light)
save value - according group flashes -> value saved




ZPE 2542228 000 00                      Page 7 of 13
(Optional) Arrange Devices and Create Scenes - Picture view


               




                                                                                            

                                                       




                                                           




 tie in room picture as .jpg

 pull ballast symbols (yellow rectangle) to luminaire
analog pull sensors, pushbuttons to requested position

 check connection lines
in example all devices which are functional connected with the luminaire

 create scenes (with slider) and store by 'Add'. Multiple selection of luminaires is possible.
check screen luminaire against real luminaire with 'Live view'

! no configuration changes possible in this view, only in Graph view
---------------

Finish Setup
 store configuration

 load down configuration to controller

close program and disconnect USB

-> installation ready for use




ZPE 2542228 000 00                      Page 8 of 13
Simultaneous View of Picture and Graph - Design of View Window




                                       




 click marker tab and pull to requested position
in this case above Picture view

 result :




ZPE 2542228 000 00                    Page 9 of 13
Firmwareupgrade Controller
With every new GUI-Softwareupgrade e.g. from OSRAM Internet www.osram.com/evg-software)
the latest firmware for the controller is automatically included. The upgrade is done by USB
connection to controller

open OSRAM DALI Professional software, click        in menue line
click marker tab ''firmware update' -> search, choose, update




default path for firmware (stored there with software instalaltion)
C:\Programms\OSRAM\DALI Professional\Firmware

screen during installation




when update finished - close window, reset controller by mains voltage interruption
wait minimum 10 seconds, switch on controller mains voltage again
now the installation is available with new firmware
with click to   in menue line the new loaded version number shows up




ZPE 2542228 000 00                      Page 10 of 13
FAQ
Wires
We recommend to carry the 2-pole DALI line with the usual electrical installation e.g. NYM 5-wire. The DALI bus is no
safety low voltage and has to be handeled like mains voltage.

Mains Interruption
After mains voltage interruption the last project status will be reestablished

Mains Voltage Sensitivity of the DALI Connections
During switch-on the Controller is protected against mains voltage on DALI terminals, but there is no protection during
operation. The couplers are not protected against wrong wiring with mains voltage and can be detroyed.

DALI Supply
OSRAM DALI PRO CONT-4 supplies max. 200mA to each DALI line

DALI Linefailure
In case of a shortcut in a DALI line the according LED of the Controller will show this by flashing.
The remaining DALI lines still have full functionality.

Reset
To bring the controller into the delivery status (plug & play functionality) an empty configuration has to be upload to it.
After this the connected devices can be reset to delivery status by longpress on button ON/OFF/DIM. With this the
function of the system is the same as in a new installation without configuration, means all connected pushbuttons /
PIR sensors act parallel in the according DALI line.

Setup with Plug&Play
see Controller manual

Select Language
Click 'Configuration' in left tree, select language in properties on the right side of the screen
Close software, open it again

Addressing
ECG und Coupler are addressable acc. current status of IEC 62386-103 (OSRAM / Siemens proposal)

Groups, Functions
are created visually in Graph view

Scenes
Creation of scenes and storage in Picture view

Eventcontrol - Stairway Function, Corridor Function
Use PIR Sensor with function Movement and configure Actions

Sequences see Eventcontrol
Time dependent control see Eventcontrol

Central OFF
Create additional group containing all ECG and connect pushbutton

Energysaving by Daylight Harvesting
Select lightcontrol in Properties and sensor + reference ECG

ECG Exchange
replace a defect ECG by merging with exisiting configuration (Merge function)

Lampdefect
If ERROR-LED is flashing at the Controller there is a lampfailure (missing or defect lamp).
Related DALI Port and ECG name is reported in message line.

Remote Connection of PC to Controller - USB to LAN / WLAN
successfully tested with BELKIN Network USB hub (USB to LAN) and D-Link DAP 1160 (LAN to WLAN)

Firmwareupdate
checked with each Softwareupdate


ZPE 2542228 000 00                              Page 11 of 13
Competitor Products
Non-OSRAM devices e.g. ECG can be used if DALI-Standards are fulfilled.
For DALI couplers the standartisation is ongoing and not finished (IEC 62386-103 (OSRAM / Siemens proposal),
therefore only OSRAM and Siemens products are well defined in these system. Full functionality with other suppliers
devices cannot be guaranteed.

Supported Windows Versions
Successfully tested with Windows XP, Windows Vista, Windows 7.

ECG Parameter Setting
Standard DALI ECG parameters e.g. System Failure Level can be set directly within the software




Use of already adressed ECG
If during setup there are found used ECG which carry e.g. already a dali short adress so this will be unchanged.
Should there be 2 identical addresses the conflict will be solved by automatical address increase.

Only One Sensor per Sensorcoupler
In case of MULTI3 up to 4 sensors can be connected because the device is directly conneted to mains voltage. In the
DALI Professional systeem the power of the coupler and sensor is supplied from DALI line. To maximize the total
number of possible sensors per DALI line and to avoid additional circuit complication only one Sensor per
Sensorcoupler is possible.

Wire Length Sensor
The maximum wire length of LS/PD Sensor to Sensorcoupler is 5 meter. An extension up to 50m like with MULTI3 is
not possible because the power of the coupler and sensor is supplied from DALI line and with this there is a lower EMI
tolerance.

Use of MULTIeco Funktionality in DALI Professional System
PIR can be inactivated by not using an action in ‚Movement’
PIR only for shut-off can be achieved by setting ‚time to action’ e.g. 300s und Action = OFF. With this the timer starts
with each movement and after 5 minutes without presence the light will switch off.
In both cases a pushbutton should be configurated with 'Shortpress' for manual operation.

Energysaver Function by Integrated Controller Relay
Already implemented into the circuit but not realized in current GUI - to be solved by later update.
Planned setup procedure : all relay off, query for ECG answers, relay K1 on, query ...
New : OSRAM DALI EVG with 200mW standby power losses, with this the energysaver function is less critical.

Pushbutton Coupler Connector - how shown in GUI Pushbutton A 01...04
Counting of the pushbutton couplers starts with 01 and is count up per DALI Linie (A..D).
The automatic predefined names show the inputs of the housing label + colour of cable.
During a perfect setup a selfexplaining name will be given e.g. ' room 2 pushbutton right'.




Project Documentation
as projekt im DALI Professional dataformat - .osrdpc
als projekt on screen - print Graph und Picture + addresstable from setup

Sensorcoupler Setup
SELECT mode - uses DALI command 'Physical Selection' for reliable identification of the device
IDENTIFY mode - identifies a single device by DALI command 'Identify Device' and LED on sensorhead




ZPE 2542228 000 00                             Page 12 of 13
Corridorfunction
with OSRAM DALI Sensorcoupler - independent configuration with flexible steps, delays, ramps
with other devices e.g. OSRAM HighBay Sensor - integration by pushbutton coupler (configuration as 'switch')




DALI Logo
The official DALI Logo             is not allowed on the product because the standartisation of Input Devices IEC
62386-103 (coupler) is not finally signed by the committee. Conformity with the requirements to control DALI EVG IEC
62386-102 is effectively given.

Emergency Lighting
not implemented

Partitition Function
The use of a switch together with logic functions is not possible up to now. Updates are planned.

Firmwareupgrade Controller
Together with each upgrade of the software (e.g. via OSRAM Internetseite www.osram.com/ecg-software)
there is transported automatically the latest firmware of the controller. Installation via USB cable to controller (no mains
supply required for this upgrade)

Procedure : open OSRAM DALI Pro Software, click       in menue line
-> submenue 'update firmware' -> search, select -> Update




ZPE 2542228 000 00                             Page 13 of 13

				