Docstoc

Bill of Quantities - Electrical

Document Sample
Bill of Quantities - Electrical Powered By Docstoc
					                                                                               BILL OF QUANTITIES

PJ.         SIRT CITY EMERGENCY PUMP STATION                                                                                       9 December, 2010


SI. No                                  Item description                                        Unit    Quantity   Rate   Amount         Remark


  1.0       ELECTRICAL WORKS - LIGHTING SYSTEM
          Supply and Installation of Vaportight Fluorescent Lighting Fixture, 2x36W T8,
      1.1 230V, 50Hz complete with HPF electronic ballast. Type "A". Includes                   set/s      51
          testing/commisioning and all accessories to complete the work according to
          drawings and specifications.
          Supply and Installation of Perimeter Lighting Fixture, with 70W high pressure
      1.2 sodium lamp, 230V, 50Hz. Type "B". Includes testing/commisioning and all              set/s      11
          accessories to complete the work according to drawings and specifications.
            Supply and Installation of Emergency Lighting Fixture, with 2x36W PAR lamp,
            230V, 50Hz complete with rechargeable battery and charger. Includes
      1.3                                                                                       set/s      12
            testing/commisioning and all accessories to complete the work according to
            drawings and specifications.
          Supply and Installation of Exit Lighting Fixture with LED, 230V, 50Hz. Includes
      1.4 testing/commisioning and all accessories to complete the work according to            set/s      5
          drawings and specifications.
            Supply and Installation of Louvered Type Fluorescent Lighting Fixture, 2x36W
            T8, 230V, 50Hz complete with HPF electronic ballast. Type "E". Includes
      1.5                                                                                       set/s      3
            testing/commisioning and all accessories to complete the work according to
            drawings and specifications.
          Supply and Installation of Downlight Fixture with 1x26W Compact Fluorescent
      1.6 Lamp, 230V, 50Hz. Includes testing/commisioning and all accessories to                set/s      1
          complete the work according to drawings and specifications.

            Supply and Installation of Light Switches. Includes testing/commisioning and all
      1.7
            accessories to complete the work according to drawings and specifications.

            Light Switch, 1-Gang, 230V, 50Hz                                                    set/s      5
            Light Switch, 3-Gang, 230V, 50Hz                                                    set/s      2
            Light Switch, 3-Way, 2-Gang, 230V, 50Hz                                             set/s      4
            Light Switch, 3-Way, 3-Gang, 230V, 50Hz                                             set/s      2

          Supply and Installation of wires and cables as specified on lighting plan. Includes
          testing/commisioning and all accessories to complete the work according to
      1.8
          drawings and specifications. Quantity and type of wires and cables are specified
          below.

            4mm² CU/PVC/LSF                                                                      lm       1392
          Supply and Installation of raceways as specified on lighting plan. Includes
      1.9 testing/commisioning and all accessories to complete the work according to
          drawings and specifications. Quantity and type of raceways are specified below.
            15mmØ RSC                                                                            lm       423

  2.0       ELECTRICAL WORKS - POWER SYSTEM

            Supply and Installation of Motor Control Center, MCCPH. Includes
            testing/commisioning and all accessories to complete the work according to
      2.1                                                                                       set/s      1
            drawings and specifications. Motor Control Center shall include the following
            equipment listed below.

            Main: 2000AT / 2000AF, 3P, 400V, 50Hz, IP52 Enclosure, 35KAIC (min)
            Branches:    4 - 1600AT / 1600AF, 3P, 400V, 50Hz
                          2 - 20AT / 100AF, 1P, 230V, 50Hz
                          1 - 80AT / 100AF, 3P, 400V, 50Hz
                          1 - 50AT / 100AF, 3P, 400V, 50Hz
                          1 - 400AT / 400AF, 3P, 400V, 50Hz, Spare
                          1 - 700AT / 800AF, 3P, 400V, 50Hz
                          1 - 30AT / 100AF, 3P, 400V, 50Hz
            Others, pls. Specify
                          4 - Soft Starter, 190kW, 3-phase, 400V, 50Hz
                          1 - Panel PPPH, 3-phase, 400V, 50Hz (Integral to MCCPH)
                          2 - UPS, 1kVA, 1-phase, 230V, 50Hz
                          1 - Programmable Logic Controller, PLC (By Others)
                          1 - Electronic Power Meter (EPM)
                          3 - Current Transformer, 2000:5A
                          3 - Current Limiting Fuse, 10A
                          1 - Capacitor Bank, 300kVAR, 3-phase, 400V, 50Hz
                          1 - TVSS, 100kA/phase, 400V, 50Hz

          Supply and Installation of Distribution Panelboard, PPPH integral to MCCPH.
          Includes testing/commisioning and all accessories to complete the work
      2.2                                                                                       set/s      1
          according to drawings and specifications. Distribution Panelboard shall include
          the following equipment listed below.

            Main: 80AT / 100AF, 3P, 400V, 50Hz, IP52 Enclosure, 10KAIC (min)
            Branches:    14 - 20AT / 100AF, 1P, 230V, 50Hz
                                                                                BILL OF QUANTITIES

PJ.          SIRT CITY EMERGENCY PUMP STATION                                                                                      9 December, 2010


SI. No                                   Item description                                       Unit    Quantity   Rate   Amount         Remark


                           3 - 30AT / 100AF, 1P, 230V, 50Hz
                           1 - 70AT / 100AF, 1P, 230V, 50Hz
           Supply and Installation of Main Circuit Breaker, 2000AT, 2000AF, 3P, 400V,
       2.3 50Hz in IP52 Enclosure. Includes testing/commisioning and all accessories to         set/s      1
           complete the work according to drawings and specifications.
           Supply and Installation of Automatic Transfer Switch, 2000A, 3P, 400V, 50Hz in
       2.4 IP52 Enclosure. Includes testing/commisioning and all accessories to complete        set/s      1
           the work according to drawings and specifications.

           Supply and Installation of Padmounted Transformer, 1000kVA, 3-phase, 11,000V
       2.5 - 400/230V, 50Hz. Includes testing/commisioning and all accessories to               set/s      1
           complete the work according to drawings and specifications.

           Supply and Installation of Diesel Stand-by Generator, 1000kVA, 3-phase,
       2.6 400/230V, 50Hz. Includes testing/commisioning and all accessories to complete        set/s      1
           the work according to drawings and specifications.
           Supply and Installation of Molded Case Switch, 1600A, 3P, 400V, 50Hz in IP52
       2.7 Enclosure. Includes testing/commisioning and all accessories to complete the         set/s      4
           work according to drawings and specifications.
           Supply and Installation of Enclosed Circuit Breaker, 50AT, 100AF, 3P, 400V,
       2.8 50Hz in IP52 Enclosure. Includes testing/commisioning and all accessories to         set/s      1
           complete the work according to drawings and specifications.
           Supply and Installation of Enclosed Circuit Breaker, 30AT, 100AF, 1P, 230V,
       2.9 50Hz in IP56 Enclosure. Includes testing/commisioning and all accessories to         set/s      1
           complete the work according to drawings and specifications.
           Supply and Installation of Enclosed Circuit Breaker, 20AT, 100AF, 1P, 230V,
      2.10 50Hz in IP56 Enclosure. Includes testing/commisioning and all accessories to         set/s      1
           complete the work according to drawings and specifications.
           Supply and Installation of Enclosed Circuit Breaker, 20AT, 100AF, 1P, 230V,
      2.11 50Hz in IP10 Enclosure. Includes testing/commisioning and all accessories to         set/s      1
           complete the work according to drawings and specifications.
           Supply and Installation of Magnetic Motor Starter, 5HP, 1-phase, 230V, 50Hz in
      2.12 IP52 Enclosure. Includes testing/commisioning and all accessories to complete        set/s      1
           the work according to drawings and specifications.
           Supply and Installation of Magnetic Motor Starter, 1.5HP, 1-phase, 230V, 50Hz in
      2.13 IP52 Enclosure. Includes testing/commisioning and all accessories to complete        set/s      1
           the work according to drawings and specifications.
           Supply and Installation of Magnetic Motor Starter, 1.5HP, 1-phase, 230V, 50Hz in
      2.14 IP10 Enclosure. Includes testing/commisioning and all accessories to complete        set/s      1
           the work according to drawings and specifications.
           Supply and Installation of Manual Motor Starter, Fractional Horsepower, 1-phase,
      2.15 230V, 50Hz. Includes testing/commisioning and all accessories to complete the        set/s      1
           work according to drawings and specifications.
           Supply and Installation of Convenience Outlet, Duplex, 16A, 2P, 220V,
      2.16 Grounding Type. Includes testing/commisioning and all accessories to complete        set/s      4
           the work according to drawings and specifications.
           Supply and Installation of Convenience Outlet, Duplex, 16A, 2P, 220V,
      2.17 Grounding Type with weatherproof enclosure. Includes testing/commisioning and        set/s      11
           all accessories to complete the work according to drawings and specifications.

             Supply and Installation of wires and cables as specified on power plan. Includes
             testing/commisioning and all accessories to complete the work according to
      2.18
             drawings and specifications. Quantity and type of wires and cables are specified
             below.

             4mm² CU/PVC/LSF                                                                     lm       783
             6mm² CU/PVC/LSF                                                                     lm        56
             25mm² CU/PVC/LSF                                                                    lm        11
             95mm² CU/PVC/LSF                                                                    lm       213
             120mm² CU/PVC/LSF                                                                   lm       116
             4mm² CU/XLPE/LSF                                                                    lm        21
             6mm² CU/XLPE/LSF                                                                    lm       137
             25mm² CU/XLPE/LSF                                                                   lm        42
             150mm² CU/XLPE/LSF                                                                  lm        45
             185mm² CU/XLPE/LSF                                                                  lm       593
             240mm² CU/XLPE/LSF                                                                  lm       347
           Supply and Installation of raceways as specified on power plan. Includes
      2.18 testing/commisioning and all accessories to complete the work according to
           drawings and specifications. Quantity and type of raceways are specified below.
             15mmØ RSC                                                                           lm       268
             20mmØ RSC                                                                           lm        56
             32mmØ RSC                                                                           lm        11
                                             BILL OF QUANTITIES

PJ.      SIRT CITY EMERGENCY PUMP STATION                                                    9 December, 2010


SI. No                    Item description             Unit       Quantity   Rate   Amount         Remark


         80mmØ RSC                                      lm          213
         100mmØ RSC                                     lm          116
                                                                              BILL OF QUANTITIES

PJ.         SIRT CITY EMERGENCY PUMP STATION                                                                                     9 December, 2010


SI. No                                  Item description                                      Unit    Quantity   Rate   Amount         Remark


  3.0       ELECTRICAL WORKS - GROUNDING SYSTEM

            Supply and Installation of Grounding Busbar. Includes testing/commisioning and
      3.1                                                                                     set/s      3
            all accessories to complete the work according to drawings and specifications.


            Supply and Installation of Ground Test Well. Includes testing/commisioning and
      3.2                                                                                     set/s      4
            all accessories to complete the work according to drawings and specifications.

          Supply and Installation of Ground Rod, 20mmØ x 3000mm L. Includes
      3.3 testing/commisioning and all accessories to complete the work according to          set/s      10
          drawings and specifications.

            Supply and Installation of grounding conductor as specified on grouding plan.
            Includes testing/commisioning and all accessories to complete the work
      3.4
            according to drawings and specifications. Quantity and type of wires and cables
            are specified below.

            100mm² Soft Drawn Bare Copper (SDBCW)                                              lm        82
            80mm² Soft Drawn Bare Copper (SDBCW)                                               lm        46


                                    TOTAL ELECTRICAL WORKS

				