Estimate for Electrical Wiring ESIC Hospital, Naini,

Document Sample
Estimate for Electrical Wiring ESIC Hospital, Naini, Powered By Docstoc
					                {ks=h; dk;kZy;
             deZpkjh jkT; chek fuxe
         iapnhi&Hkou] loksZn; uxj] dkuiqj m0iz0

                 fufonk vkea=.k lwpuk

       deZpkjh jkT; chek fpfdRlky;] uSuh bykgkckn] fiijh
¼jsuqdwV½] ik.Ms;iqj] okjk.klh ] ,oe~ fdnobZ uxj] dkuiqj esa
fo|qr ok;fjax dk;Z gsrq eqgjcUn fyQkQksa esa fufonk vkeaf=r
dh tkrh gS A izR;sd fpfdRlky; ds dk;Z dh vuqekfur ykxr dze’k%
:011-62 yk[k,:0 8-70 yk[k ] 9-99 yk[k ,oe~ :0 3.36 yk[k gS A
fufonknkrk fdlh ,d ;k lHkh fpfdRlky; Hkouksa esa fo|qr ok;fjax
dk;Z gsrq fufonk Mky ldrs gSa A fufonk izi= tek djus dh vfUre
frfFk 13-12-10 vijkUg 3-00 cts rd -gS A fufonk izi= fodz; dh
vof/k o ‘krsZa deZpkjh jkT; chek fuxe dh osclkbV
www.esicuttarpradesh.org ij ns[kh@MkmuyksM dh tk ldrh gS A


                                            jkT;      fpfdRlk
vk;qDr
                               REGIONAL OFFICE
           EMPLOYEES’ STATE INSURANCE CORPORATION
        PANCHDEEP BHAWAN; SARVODAYA NAGAR,KANPUR-5
                                Notice Inviting Tender
Work- electric wiring in E.S.I. Hospital Naini Allahabad, Pipri (Renukoot),
Pandeyapur, Varanasi and Hospital Kidwai Nagar, Kanpur.
        Sealed envelop tenders are invited from the contractors for electric wiring in entire
building of ESI Hospital at Naini Allahabad, Pipri (Renukoot), Pandeyapur, Varanasi
and Hospital Kidwai Nagar, Kanpur as per specifications given in the enclosed bill of
quantity. Estimated cost of the work & EMD to be deposited is given below.. The last date
of submission of the tender documents is 13.12.10 by 3.30 P.M. Tender documents and Terms
& Conditions may be seen / downloaded from website of ESI Corporation i.e.
www.esicuttarpradesh.org .
Sl.No. Name of E.S.I. Hospital            Estimated Cost Cost of tender Amount of EMD (
                                          of work ( in lac ) documents ( in in Rs. )
                                                             Rupees )
1.        Naini , Allahabad               11.62              500/-                23240/-
 2.       Pipri (Renukoot)                 8.70              500/-                17480/-
 3.       Pandeyapur, Varanasi            9.99               500/-                20,000/-
 4.       Kidwai Nagar,Kanpur             3.36               500/-                 6720/-
Date of sale/ calling tender 25.11.10 to 10.12.10 ( 11 AM to 4.30 PM )
Date of Submission of tender - 13.12.10 by 3.00 PM
Date of opening of tender 13.12.10 at 3.30 PM
Terms & Conditions:-
    1. Tender documents will be issued only to those contractors who have obtained the
         license/registration under labour laws for doing electrical works.
    2. Preference will be given to the contractors who show the proof of their works of
        similar nature for not less than Rs. 20/- Lakh through one tender or Rs. 10/- Lakh or
        more for two tenders.
    3. Interested contractors are advised to visit the site before giving offer.
    4. The contractors may apply for electric wiring work in one or all of the above hospital
        buildings.
    5. Rate quoted should be firm and fixed, valid for 60 days atleast and should be inclusive
        of cost of labour, material, tool & plant etc. whatsoever including all taxes.
    6. No escalation of any nature will be payable.
    7. The tenderer should also enclose their latest Income Tax clearance certificate and
        photocopy of his PAN Card..
    8. Tenderer must have TIN No. of Trade Tax department and having experience of 03
        years of same type of work.
    9. Conditional tenders are not acceptable.
    10. Successful tenderer will have to deposit secutiry money @ 5% of estimated cost of
        tender before start of work. The work has to be completed within 30 days from the
        date of award of work.
    11. EMD of unsuccessful tenderers shall be refunded within one month from the date of
        award of work to the successful tenders.
    12. Cost of tender, EMD and Security money will be payable through
       Demand Draft/Bankers’ Cheque in favour of RD, ESI Corporation, Kanpur.
    13. All the electrical material will be used I.S.I. marked only i.e. Havells, Nicco, Anchor,
        Legred, Skytone, Plaza and Standard make only.
    14      Points/Quantity mentioned in the Bill of Quantity is estimated only which may
    increase or decrease as per site requirement.
    15. Earnest Money deposited will be forefeited if the tender documents / bill of quantity
        is not complete in all respect.
    16. Awarded work should be completed in prescribed time otherwise damages @ 5% of
        quoted value may be imposed . The contractor will have to submit circuit / line
         diagram after completion of work.
      17. The tenderer who have submitted the complete tender documents for same work on
          27.09.10 , may obtain the fresh tender documents free of cost from this office.
      18.The competent authority of ESIC reservers the right to accept or reject any or all tender
         without assigning any reason thereof.

                                                    STATE MEDICAL COMMISSIONER
Estimate for Electrical Wiring ESIC Hospital, Naini,
                           Allahabad
                                                                       -1-

Estimate for electrical wiring in respect of Panchdeep Project IT works in Allahabad
                                                                              ( U.P.)


Sl.     CPWD         Item Description                           Qty.         Unit   Rate     Amt
No      Spec
.       Code
1.      As per       Supply & fixing & testing of          800 m             Mts
        MR           Aluminium Armoured cable
                     3 .5 core x16mm2
2.      -do-         3.5x70 mm2                            30m               Mts
3.      -do-         S/F installation & testing etc of 200 01Set             Set
                     Amps VTPN DB in suitable MS Panel
                     & painting etc as required to
                     complete
4.      1761         S/F installation & testing of 8 way
                     (8+24) TPN Vertical type MCB,DB
                     Double Door each 4 Pole MCCB
                     100 A 16 KAB each
                     6 A to 32 Amp. rating DP MCB ‘B’
                     Series 10KA breaking capacity 24
                     Nos
        1610
        1703                                                    06           Set


5.      1.32         Supply of fixing installation & testing    75           Each
        PPACC        power plug in Modular type
        MOD          accessories in suitable size PVC
                     Modular Box with Modular plate and
                     cover (in White Colour ) infront on
                     surface or in recourses including
                     power and fixing 6 pin 15/16 Amp &
                     5/6 Amp Modular Socket out Lets
                     and 15/16 Amp Modular socket-02
                     Sets comitun painting and Control by
                     one MCB with same Box
        1702
Sl. CPWD          Item Description                          Qty.     Unit     Rate     Amt
No Spec
.   Code
6 1.12            Poert Plug wiring in PVC candure          1500     Mtr
    WGPVC         (2x4)2mm2 wiring for power plug
    PP2           with 2x4 mm2 FRPVC insulated
                  Copper Conductor single core cable
                  in surface / resus PVC candut
                  alongwith 1 Number 4 mm2 PR PVC
                  insulated Cu Conductor Single Core
                  cable for loop earthing etc. complete
                  required.




                                                                   Continue on page…2…


7.    1.13 WG     Power plug wiring in PVC candut           900      Mtr
      PVC PP2     2x2 mm2 FRPVC insulated copper            mm
                  candutor single core cable in
                  surface/recived PVC candure
                  alongwith with 2 Nos. 4 mm2/ R PVC
                  insulated copper candut single core
                  copper cable for loop earthing as
                  required.
8.    1.14 WG     Circuit Sub Main Wiring in PVC            1000     Mtr
      PVC SB      candutre wiring for circuit/submain
                  wiring along with earth wire and ctc
                  2x6 mm2 + 1x6 mm2 Earth Wire
                  Copper Candutor Single cable in
                  surface/resist PVC candure as
                  required.
9.    As per      Supply & Fixing & texting Copper          01Set    SET
      Mkt         Bus Bar 50x6 mm Leminated with
                  standard colour code (RYB and G )
                  in a factory made DB and indication
                  lamp cable lugs etc. required.
10.   1730        20 Amp SPN Industrial Type Socket         Set      06
      As per      Outlet with plug Top and Metal clad
      MR
11.   As MR       S/F Change over switch 400 Amp in         01 Set   Set
                  MS Panel as required
12.   As MR       S/F of Testing Copper Plate Earthing      04       Sets
                  600x600x3mm thick plate and metal

       Note: All the electric material will be used I.S.I. marked only i.e. Havells,
Nicco,Anchor,Legred, Skytone , Plaza and Standard make only.




                                           Name & Address of the Contractor with
                                                                      Signature
             Bill of Quantity for Electric Wiring in ESI Hospital, Pipri/Renukoot
                                              -1-

Estimate for electrical wiring in respect of Panchdeep Project IT works in ESI
Hospital, Renukoot.

Sl.   CPWD          Item Description                          Qty.   Unit     Rate   Amt
No    Spec
.     Code
1.    As per        Supply & fixing & testing of          200 m      Mts
      MR            Aluminium Armoured cable in open
                    3 .5 core x16mm2 underground as
                    required
2.    -do-          3.5x70 mm2                            200        Mts
3.    -do-          S/F installation & testing etc of 200 01Set      Set
                    Amps VTPN DB in suitable MS Panel
                    & painting etc as required to
                    complete
4.    1761          S/F installation & testing of 8 way
                    (8+24) TPN Vertical type MCB,DB
                    Double Door each 4 Pole MCCB
                    100 A 16 KAB each
                    6 A to 32 Amp. rating DP MCB ‘B’
                    Series 10KA breaking capacity 24
                    Nos for given supply to power
      1610          Boards, as required
      1703                                                05         Set


5.    1.32          Supply of fixing installation & testing   75     Each
      PPACC         power plug in Modular type
      MOD           accessories in suitable size PVC
                    Modular Box with Modular plate and
                    cover (in White Colour ) infront on
                    surface or in recourses including
                    power and fixing 6 pin 15/16 Amp &
                    5/6 Amp Modular Socket out Lets
                    and 15/16 Amp Modular socket-02
                    Sets comitun painting and Control by
                    one MCB with same Box
      1702
Sl. CPWD          Item Description                          Qty.     Unit       Rate   Amt
No Spec
.   Code
6 1.12            Poert Plug wiring in PVC candure          600      Mtr
    WGPVC         (2x4)2mm2 wiring for power plug
    PP2           with 2x4 mm2 FRPVC insulated
                  Copper Conductor single core cable
                  in surface / resus PVC candut
                  alongwith 1 Number 4 mm2 PR PVC
                  insulated Cu Conductor Single Core
                  cable for loop earthing etc. complete
                  required.




                                                                   Continue on page…2…


7.    1.13 WG     Power plug wiring in PVC candut           1200     Mtr
      PVC PP4     4x4 mm2 FRPVC insulated copper            mm
                  candutor single core cable in
                  surface/recived PVC candure
                  alongwith with 2 Nos. 4 mm2/ R PVC
                  insulated copper candut single core
                  copper cable for loop earthing as
                  required.
8.    1.14 WG     Circuit Sub Main Wiring in PVC            800      Mtr
      PVC SB      candutre wiring for circuit/submain
                  wiring along with earth wire and ctc
                  2x6 mm2 + 1x6 mm2 Earth Wire
                  Copper Candutor Single cable in
                  surface/resist PVC candure as
                  required.
9.    As per      Supply & Fixing & texting Copper          01Set    SET
      Mkt         Bus Bar 50x6 mm Leminated with
                  standard colour code (RYB and G )
                  in a factory made DB and indication
                  lamp cable lugs etc. required.
10.   1730        20 Amp SPN Industrial Type Socket         Set      02
      As per      Outlet with plug Top and Metal clad
      MR
11.   As MR       S/F Change over switch 400 Amp in         01 Set   Set
                  MS Panel as required
12.   As per      S/F + Testing Copper plate earthing       04       Sets
      Mr          600x600x3 mm thick plate and
                  material its as required

Note: All the electric material will be used I.S.I. marked only i.e. Havells,
Nicco,Anchor,Legred, Skytone , Plaza and Standard make only.
                                                  Name & Address of the Contractor
                                                                   with Signature




       Estimate for SRO & Hospital , ESIC, Pandeyapur, Varanasi
                                          -1-

Estimate for electrical wiring in respect of Panchdeep Project IT works in SRO and
ESIC Hospital, Pandeyapur, Varnasi. ( U.P.)


Sl.   CPWD       Item Description                          Qty.   Unit   Rate    Amt
No    Spec
.     Code
1.    As per     Supply & fixing & testing of          350 m      Mts
      MR         Aluminium Armoured cable
                 3 .5 core x16mm2
2.    -do-       3.5x70 mm2                            30m        Mts
3.    -do-       S/F installation & testing etc of 200 01Set      Set
                 Amps VTPN DB in suitable MS Panel
                 & painting etc as required to
                 complete
4.    1761       S/F installation & testing of 8 way
                 (8+24) TPN Vertical type MCB,DB
                 Double Door each 4 Pole MCCB
                 100 A 16 KAB each
                 6 A to 32 Amp. rating DP MCB ‘B’
                 Series 10KA breaking capacity 24
                 Nos
      1610
      1703                                                 06     Set


5.    1.32       Supply of fixing installation & testing   80     Each
      PPACC      power plug in Modular type
      MOD        accessories in suitable size PVC
                 Modular Box with Modular plate and
                 cover (in White Colour ) infront on
                 surface or in recourses including
                 power and fixing 6 pin 15/16 Amp &
                 5/6 Amp Modular Socket out Lets
Sl. CPWD          Item Description                          Qty.     Unit     Rate     Amt
No Spec
.   Code
                  and 15/16 Amp Modular socket-02
                  Sets comitun painting and Control by
                  one MCB with same Box
      1702
6     1.12        Poert Plug wiring in PVC candure          800      Mtr
      WGPVC       (2x4)2mm2 wiring for power plug
      PP2         with 2x4 mm2 FRPVC insulated
                  Copper Conductor single core cable
                  in surface / resus PVC candut
                  alongwith 1 Number 4 mm2 PR PVC
                  insulated Cu Conductor Single Core
                  cable for loop earthing etc. complete
                  required.




                                                                   Continue on page…2…


7.    1.13 WG     Power plug wiring in PVC candut           1200     Mtr
      PVC PP4     4x4 mm2 FRPVC insulated copper            mm
                  candutor single core cable in
                  surface/recived PVC candure
                  alongwith with 2 Nos. 4 mm2/ R PVC
                  insulated copper candut single core
                  copper cable for loop earthing as
                  required.
8.    1.14 WG     Circuit Sub Main Wiring in PVC            800      Mtr
      PVC SB      candutre wiring for circuit/submain
                  wiring along with earth wire and ctc
                  2x6 mm2 + 1x6 mm2 Earth Wire
                  Copper Candutor Single cable in
                  surface/resist PVC candure as
                  required.
9.    As per      Supply & Fixing & texting Copper          01Set    SET
      Mkt         Bus Bar 50x6 mm Leminated with
                  standard colour code (RYB and G )
                  in a factory made DB and indication
                  lamp cable lugs etc. required.
10.   1730        20 Amp SPN Industrial Type Socket         Set      04
      As per      Outlet with plug Top and Metal clad
      MR
11.   As MR       S/F Change over switch 400 Amp in         01 Set   Set
                  MS Panel as required
12.   Earthing    600x600x3mm thick plate and metal         04       Sets
                  + Supply Fixing and testing copper
                  plate Earthing etc as required.

       Note: All the electric material will be used I.S.I. marked only i.e. Havells,
Nicco,Anchor,Legred, Skytone , Plaza and Standard make only.
                                           Name & Address of the Contractor with
                                                                      Signature




                                  BILL OF QUANTITY
 Electrical wiring in respect of Project Panchdeep IT Works in ESI Hospital, Kidwai
                                                              Nagar, Kanpur (U.P.)

Sl.No.   CPWD        Description of Item              Qty Unit     Rate         Amount
1.       1761        S/F Installation & testing of 8
         1610        way (8+24) TPN vertical type
         1703        MCBDB Double Door. 4
                                                       03  Sets
                     Pole MCCB 100A, 6 A to 32
                     rating DPCCB B Series 10
                     KA breaking capacity 24 Nos.
2.       1.32        Supply & Fixing installation
         PPACC       & testing Modular type power
         MOD         plug accessories in suitable
         1702        size. PVC Modular Box with
                     Modular plate and cover ( In
                     white colour) infront on
                     surface or in receisis including
                     power plug fixing 6 pin 15/16
                     Amp & 5/6 Amp Modular
                     socket out cut and 15/16 Amp 60      Sets
                     modular switch sets complete
                     and control by one MCB in
                     the same Box complete in all
                     respect as require.
3.       1.12        Power wiring 2 x 4 mm 2 by
         WGPVC       PVC Condure And Earthing
         PP2         etc. 1x 4 mm2 PVC insulated 800M       M
                     copper conductor single core
                     cable complete as required
4.       1.144 WG    Circuit sub main Wiring in
         PVC SG      PVC 2x 6 mm2 + 1 x 6 mm2 500m
                                                           Mtr
                     copper conductor wire in PVC      m
                     as required
5.       1730        20 Amp SPN Indl. Amp Type         04  Sets
                   Socket out Let plug top metal
                   clot complete as required
6.     1.14        Circuit / Submain wiring in     80   Mts
       WGPVC       PVC Conduit along with earth
       SB 1.7.5    size PVC insulated Copper
                   2x10mm2 Conductor Single
                   Core Cable in surface/recess
                   PVC Conduit + 1x 10mm2
                   earthing as required.
7.     As per MR   Earthinng with copper earth     03   Sets
                   plate Electrole to salt, coke
                   and charcoal.

                   Cost Index Escalation-30 %
                   on Item No. 1 to 6


Note: All the electric material will be used I.S.I. marked only
i.e.Havells,Nicco,Anchor,Legred,Skytone,Plaza &Standard make
only.


                                    Name & Address of the Contractor