							Building Inspection - Campus Center - October 2007                                                                                                            4/13/2011

                                                                                                                                 Responsible
74    Pic      Level          Location               Discrepancy               Action Required                        Type         Agency               Follow Up
                                                                             Keep electrical panels
6      6       Lower      Kitchen                Electrical panel blocked    unobstructed                    Safety             Aramark              Noted/corrected
                                                 Handwashing sinks do not                                                                            Complete (Bruce
7      7       Lower      Kitchen Storage        have towels              Install towels                     Food Safety        Aramark              Gonsalves 10/30/07)
                                                 MSDS database            Include MSDS of all                                                        noted / will comply by
11     11      Lower      Kitchen                incomplete               chemicals                          Chemical Hygiene   Aramark              1-01-2008

                                                                                                                                                     Student Activities
                                                                           Forward Campus Center                                                     does allow candles to
                                                                           candle policy to RM/EHS, if                                               be used for events.
                                                 Evidence of candles being different from Safety &                              Aramark redirected   Candles must be
10     10      Lower      Kitchen Storage        used                      Loss Control Manual         Fire safety              by Campus Center     enclosed in a volative.
                                                 Furniture in exit access
1      1       Lower      Service Hallway        corridor                  Remove furniture            Fire safety              Campus Center        Furniture removed

28     28      Lower      Gallery                Tree obstructing exit sign Move tree                        Fire safety        Campus Center        Complete
                                                                              Move equipment away
                                                 Equipment obstructing        from exit to allow 5 feet of
51     51      Middle     Aerobics 222           egress                       unobstructed clear width       Fire safety        Campus Center        Complete
                                                 Materials obstructing        Keep stairs and exits clear
63     63      Middle     Varsity Gym            egress                       at all times                   Fire safety        Campus Center        Complete
                                                                              Contact Facilities and
                                                                              determine if they will need
                          Intramurals Gym        Materials stored in front of immediate access to this
40     40      Middle     Storage                equipment                    equipment/panel                Safety             Campus Center        Moved equipment
                                                                                                                                                     Will be moving and
                                                 Materials present trip      Store materials properly,                                               restoring in better
58     58      Middle     Storage 218B           hazard                      especially cords                Safety             Campus Center        shape
                                                                                                                                                     Contacted Public
                                                                             Keep guard rails closed                                                 Safety and Athletics
                                                                             when bleachers aren't                                                   to be sure to follow up
61     61      Upper      Varsity Gym            Guard rail left open        extended                        Safety             Campus Center        with this
                          Storage areas,
                          maintenance rooms,                                 Conduct periodic checks to                                              Will double check to
                          other areas with low                               turn off lights, or effect                                              be sure they are
73      -        All      usage                  Lights left on              other administrative control    Energy Conservation Campus Center       always turned off
                          Game Room Storage      Chemicals not on            Put chemicals on chemical
34     34      Lower      101B                   inventory                   inventory                       Chemical Hygiene   Campus Center        Complete
                                                 Chemicals not on            Put chemicals on chemical
35     35      Lower      Game Room 101          inventory                   inventory                       Chemical Hygiene   Campus Center        Complete
                                                 Chemicals not on            Put chemicals on chemical
37     37      Middle     Kitchen 213            inventory                   inventory                       Chemical Hygiene   Campus Center        Complete

Page 1 of 18                                                                                                                                             UWG RM/EHS
Building Inspection - Campus Center - October 2007                                                                                                   4/13/2011

                                                                                                                             Responsible
74    Pic      Level          Location               Discrepancy              Action Required                   Type           Agency           Follow Up
                                                                         Add chemical to chemical
52     52      Middle     Aerobics 221 Storage Chemical not on inventory list                           Chemical Hygiene    Campus Center    Complete
                                                                         Verify chemicals are on
                                               Chemicals may not be on inventory; if not, add them
56     56      Middle     Exercise Room        inventory                 to inventory                   Chemical Hygiene    Campus Center    Complete
57     57      Middle     Exercise Room        Unlabeled containers      Label all containers           Chemical Hygiene    Campus Center    Complete
                                               Chemicals not stored      Store chemicals properly
                                               properly and not on       and add chemical to
65     65      Middle     Equipment Room 235 inventory                   inventory                      Chemical Hygiene    Campus Center    Complete
                                               Materials (easels)
29     29      Lower      Storage 100B         improperly stored         Store easels properly          Building Improvement Campus Center   Complete
                                                                         Have shuffleboard table                                             Reported this to
36     36      Lower      Game Room 101        Shuffleboard table broken fixed                          Building Improvement Campus Center   facilities
                                               Plaster, paint coming off Submit work order to have
38     38      Middle     Intramurals Gym      column                    column repaired                Building Improvement Campus Center   Work order done
                          Hallway between
                          elevator foyer and
53     53      Middle     Aerobics 221         Debris accumulating       Clean up debris                Building Improvement Campus Center   Complete
                          Hallway between                                Submit work order to have
                          elevator foyer and                             wall cleaned and/or
55     55      Middle     Aerobics 221         Stained wall              painted                        Building Improvement Campus Center   Work order done
                                                                                                                                             Facilities Out-Plant
                                                                                                                                             Const. has evaluated
                                                                                                                                             sprayer and
                                                                                                                                             determined that it is
                                                                            Return sprayer to owner,                                         worthless and will
                                              Concrete sprayer left on      add to Facilities inventory,                                     dispose of
66     66      Middle     Equipment Room 235 site                           or discard                   Building Improvement CP&D           accordingly.
                                              Combustible material
2      2       Lower      Electrical Room 117 (pallet) in electrical room   Remove pallet             Fire safety           Facilities       Complete
                                                                            Remove materials from fan
3      3       Lower      Electrical Room 117    Material (paper) in fan    blades and clean          Fire safety           Facilities       Complete
                                                 Chemical stored on hot
30     30      Lower      Custodial Closet 106   water heater               Store chemical properly     Fire safety         Facilities       Complete

                                                                           Reinstall fire putty, if you
                                                 Fire putty removed from   cannot confirm that there is
54     54      Middle     Electrical Room 220    conduit                   a fire break along this pipe Fire safety         Facilities       Complete
                                                                           Contact owner of
                                                 Materials blocking access equipment and instruct to
50     50      Middle     Electrical Room 223    to electrical panels      remove equipment             Electrical Safety   Facilities       Complete


Page 2 of 18                                                                                                                                    UWG RM/EHS
Building Inspection - Campus Center - October 2007                                                                                                 4/13/2011

                                                                                                                            Responsible
74    Pic      Level          Location               Discrepancy              Action Required                    Type         Agency          Follow Up
                                                                         Schedule inspection or
13     13      Lower      Boiler Room         Boiler permits out-of-date install new permits            Safety             Facilities     Work in Progress
                                                                         Remove light bulbs or
                          Old Mechanical Room                            install new compact                                              lights demoed in
21     21      Lower      119                 Lights out                 fluorescents                   Safety             Facilities     place R. Watts
                          Mechanical Room     Chemical improperly
16     16      Lower      116                 stored                     Store chemical properly        Chemical Hygiene   Facilities     Complete
                                                                         Store chemical properly,
                                              Chemical (cove base        add to chemical inventory                                        This is attice for
                          Old Mechanical Room adhesive) improperly       or contact RM/EHS for                                            building. Should
20     20      Lower      100J                stored                     disposal                       Chemical Hygiene   Facilities     remain. R.Watts
                                                                         Remove chemicals that are
                                                                         no longer used, contact
                                                                         RM/EHS for disposal; store
                                                                         other chemicals properly
                          Old Mechanical Room Chemicals improperly       and add to chemical
23     23      Lower      120                 stored                     inventory                      Chemical Hygiene   Facilities     Complete

                          Old Mechanical Room Chemical (Dumpster          Add chemical to chemical
26     26      Lower      100J                Daisy) not on chemical list list                          Chemical Hygiene   Facilities     Work in Progress
                                                                          Store chemical properly,
                                                                          out of air handling room,
                          Air Handling Room   Chemical (sheetrock         contact RM/EHS for
59     59      Upper      (off walking track) primer) improperly stored disposal if needed              Chemical Hygiene   Facilities     Complete

                                                                             Remove HID light; store
4      4       Lower      Storage 115           HID light on scissors lift   properly or discard properly Environmental    Facilities     Complete
                                                                             Store lamps properly, or
                                                Compact fluorescent          remove to accumulation
12     12      Lower      Storage 113           lamps accumulating           area                         Environmental    Facilities     Complete

                          Old Mechanical Room Spent fluorescent light        Remove spent fluorescent
25     25      Lower      120                    accumulating                lights to accumulation area Environmental     Facilities     Complete
48     48      Middle     Bathroom 234           Sink will not shut off      Fix sink                    Environmental     Facilities     Complete
                                                 Tennis balls accumulating
68     68       Roof      Close to tennis courts near drain                  Remove tennis balls        Environmental      Facilities     Complete
18     18      Lower      Service Elevator       Floor dirty                 Clean elevator floor       Housekeeping       Facilities     Complete
                                                 Floor/door has spilled
19     19      Lower      Service Hallway 100E liquid                        Clean door and floor       Housekeeping       Facilities     Complete




Page 3 of 18                                                                                                                                  UWG RM/EHS
Building Inspection - Campus Center - October 2007                                                                                                     4/13/2011

                                                                                                                                Responsible
74    Pic      Level          Location               Discrepancy               Action Required                  Type              Agency         Follow Up

                                                                             Store mop properly in
                          Old Mechanical Room                                custodial closet or dispose
27     27      Lower      100J                Mop improperly stored          of if no longer needed      Housekeeping          Facilities     Work in Progress
                                              Dust accumulating on
31     31      Lower      Electrical Room 103 door frame                     Clean dust off door frame   Housekeeping          Facilities     Complete
                          Mechanical Room
15     15      Lower      116                 Drain pipe broken              Fix pipe                    Building Improvement Facilities      Work in Progress
                          Mechanical Room     Loose hardware next to         Store hardware in central
17     17      Lower      116                 pumps                          location                    Building Improvement Facilities      Complete
                          Old Mechanical Room                                Remove unused items                                              Attic stock-should
24     24      Lower      120                 Abandoned materials            from room                   Building Improvement Facilities      remain. R.Watts

32     32      Lower      Café 102              Ceiling tile off grid        Reposition ceiling tile     Building Improvement Facilities      Complete

33     33      Lower      Lounge 100A           Ceiling tile off grid    Reposition ceiling tile         Building Improvement Facilities      Complete
                                                Recessed sprinkler heads Install new sprinkler head
39     39      Middle     Intramurals Gym       missing cap              caps                            Building Improvement Facilities      Work in Progress
                          Data Closet (near
46     46      Middle     Varsity Gym)          Ceiling tile missing         Install ceiling tile        Building Improvement Facilities      Complete
                                                Drinking fountain does not
49     49      Middle     Hallway outside 232   work                         Fix drinking fountain       Building Improvement Facilities      Material Waiting
                                                Soap dispenser does not      Fix or replace soap
67     67      Middle     Locker Room 238       work                         dispenser                   Building Improvement Facilities      Complete
                          Between Campus                                                                                      Public Safety
                          Center and tennis                                                                                   redirected by
70     70      Outside    courts                Abandoned traffic cones      Remove traffic cones        Building Improvement Facilities      Complete

                          Data Closet (near     Abandoned material (pipe Remove insulation, plug
45     45      Middle     Varsity Gym)          insulation); hole in wall pipe hole with firestop        Fire safety           ITS            Complete

                                                                                                                                              Permissible in
                                                                                                                                              accordance with
                                                                                                                                              NFPA 25, para
                                                                                                                                              5.2.1.2. Contact with
                                                                                                                                              pipe is not in the
                                                                                                                                              horizontal plane of the
                                                                                                                                              water discharge.
                                                                                                                                              Sent to University
                          Old Mechanical Room Sprinkler head in contact                                                                       Architect for her
22     22      Lower      119                 with overhead pipe             Review code                 Fire safety           RM/EHS         response, as well.


Page 4 of 18                                                                                                                                      UWG RM/EHS
Building Inspection - Campus Center - October 2007                                                                                                            4/13/2011

                                                                                                                                 Responsible
74    Pic      Level          Location               Discrepancy                 Action Required                    Type           Agency               Follow Up
                                                                                                                                                     Permissible, since
                                                                                                                                                     this is not an
                                                                                                                                                     enclosed stairwell,
                                                                                                                                                     and is out of the path
                                                                                                                                                     of egress. Sent to
                                                                                                                                                     University Architect
                                                 Materials stored under                                                                              for her response, as
64     64      Middle     Varsity Gym            stairs                         Review code                Fire safety          RM/EHS               well.

                                                                                                                                                     In accordance with
                                                                                                                                                     Georgia Rule 290-5-
                                                                                                                                                     14.05 (10) Protection
                                                                                                                                                     of Clean Items, any
                                                                                                                                                     food-contact
                                                                                                                                                     equipment should be
                                                                                                                                                     protected from
                                                                                                                                                     contaminants, such
                                                                                                                                                     as dust. Storage in
                                                                                                                                                     such a manner is
                                                                                                                                                     permissible, provided
                                                 Food covers stored food-                                                                            the items are cleaned
9      9       Lower      Kitchen Storage        side up                        Review code                Food Safety          RM/EHS               prior to service.
                          Student Activities &   Location of Workers'
                          Campus Center          Compensation posters not       Verify proper installation of
72      -        All      Offices                evident                        WC posters                    Risk Management   RM/EHS               Complete.
                                                 Gap between floor and                                                                               Pending architect
62     62      Upper      Varsity Gym            wall at stairwell landing      Review code                Safety               RM/EHS               review.
                                                                                Remove extinguisher to
41     41      Middle     Old Electrical Room    Abandoned extinguisher         spares                     Building Improvement RM/EHS               Complete
                          Student Activities     Cracked glass/plastic on
60     60      Upper      Conference Room        poster                         Replace glass/plastic      Safety               Student Activities   Complete
                                                 Freezer needs to be
69     69      Upper      Room 316               defrosted                      Defrost freezer            Environmental        Student Activities   Complete

                                                 Examination table surface      Replace or recover table,
                                                 is cracked hard to sterilize   consider using disposable                                            No Response in Time
42     42      Middle     Training Room 233      allowing bacteria to reside    paper sheets              Occupational Health   Sports Medicine      for Final Report
                                                 Hand washing sink does         Submit work order to have                                            No Response in Time
43     43      Middle     Training Room 233      not have soap                  soap dispenser installed  Occupational Health   Sports Medicine      for Final Report




Page 5 of 18                                                                                                                                             UWG RM/EHS
Building Inspection - Campus Center - October 2007                                                                                                        4/13/2011

                                                                                                                           Responsible
74    Pic      Level          Location               Discrepancy          Action Required                  Type              Agency                  Follow Up
                                                                                                                                                 Signage is placed
                                                                                                                                                 inside the door
                                                                                                                                                 intentionally to
                                                                                                                                                 designate the room
                                                                                                                                                 but not to bring it to
                                                                                                                                                 anybody’s attention
                                                                                                                                                 since it is a wall closet
                                                                                                                                                 to store the folding
                                                                                                                                                 partitions. It was felt
                                                                                                                                                 that placing the sign
                                                                                                                                                 outside the door
                                                                                                                                                 would only clutter the
                                                Room numbers on inside Verify that this was                                                      gallery and would not
71     71      Lower      Gallery               of door                intentional                  Building Improvement University Architect    serve any purpose.
                                                                                                                                                 Does not meet code.
                          Intramurals storage   Glass doors used to                                                                              Will need to be
74     74      Middle     235                   replace fire doors       Verify adherence to code   Fire safety           University Architect   corrected.




Page 6 of 18                                                                                                                                         UWG RM/EHS
Building Inspection - Campus Center - October 2007      4/13/2011




Page 7 of 18                                         UWG RM/EHS
Building Inspection - Campus Center - October 2007      4/13/2011




Page 8 of 18                                         UWG RM/EHS
Building Inspection - Campus Center - October 2007      4/13/2011




Page 9 of 18                                         UWG RM/EHS
Building Inspection - Campus Center - October 2007      4/13/2011




Page 10 of 18                                        UWG RM/EHS
Building Inspection - Campus Center - October 2007      4/13/2011




Page 11 of 18                                        UWG RM/EHS
Building Inspection - Campus Center - October 2007      4/13/2011




Page 12 of 18                                        UWG RM/EHS
      Building Inspection - Campus Center - October 2006                                                                                                     4/13/2011

Item                                                                                                                        Responsible
  #  Pic        Level           Location             Discrepancy             Action Required                     Type         Agency                Follow Up
                                                  Ice machine does not      Install scoop for ice
 27     27       Lower      Kitchen 114           have a scoop              machine                     Food Safety        ARAMARK               Complete
                                                  Discarded materials in
                                                  room present slip/trip
 25     25       Lower      Kitchen 114           hazard                     Clean room                 Safety             ARAMARK               Complete
                                                                             Move equipment to allow
                                                  Equipment blocking         unobstructed access to
 26     26       Lower      Kitchen 114           access to electrical panel electrical panel           Safety             ARAMARK               Complete
                                                                                                                                                 Organization
                                                                                                                                                 contacted by
                                                                                                                                                 DeLandra M. Hunter
 16     16       Upper      Room 318              Refrigerator moldy       Clean refrigerator           Environmental      BSA                   via email on 12/13/06
                                                                           Clear materials to ensure
                                                 Materials blocking fire   unobstructed access to
 23     23       Lower      Storage Room 113     extinguisher              extinguisher                 Fire Safety        Campus Center         Complete
                                                                           Clear materials; keep path
 56     56       Middle     Hallway 220          Egress obstructed         of egress clean              Fire Safety        Campus Center         Complete
                            Workout room (near                             Clear materials; keep path
 58     58       Middle     elevator)            Egress obstructed         of egress clean              Fire Safety        Campus Center         Complete
  2      2       Upper      Room 303             Chairs broken             Repair or surplus chairs     Safety             Campus Center         Complete
  3      3       Upper      Room 302             Broken chair              Repair or surplus chair      Safety             Campus Center         Complete
                                                                           Store ladders properly
                                                                           (submit a work order if
                                                                           hardware needs to be
 22     22       Lower      Storage Room 113     Ladders improperly stored installed)                   Safety             Campus Center         Complete
                                                 Materials stored in       Store materials in a less
 70     70       Middle     Campus Center Office hallway                   traveled space               Safety             Campus Center         Complete

                                                                                                                                                 Those doors are not
                                                                                                                                                 entrance doors and
                                                                                                                                                 therefore no one can
                                                                                                                                                 enetr there. They may
                                                                                                                                                 exit and they work for
                                                                                                                                                 that. They are
                                                                                                                                                 activiated for home
                                                                            Activate (turn on) ADA                         Campus Center         basketball games or
                            Student Activities                              doors at the beginning of                      redirected by Student for any event that may
 9       9       Upper      foyer                 ADA doors not activated   each day                    ADA                Activities            be in the large gym.
                                                                            Label container with
 62     62       Middle     Workout room          Unlabeled container       identity of contents        Chemical Hygiene   Campus Center         Complete



      Page 13 of 18                                                                                                                                     UWG RM/EHS
      Building Inspection - Campus Center - October 2006                                                                                                  4/13/2011

Item                                                                                                                            Responsible
  #  Pic        Level           Location              Discrepancy               Action Required                    Type           Agency          Follow Up
                                                                                                                                               They are closed
                                                                                                                                               unless someone
                                                                                                                                               proprs them open for
                                                                                                                                               a class but we check
 64     64       Middle     Main gymnasium        Door open                    Keep doors closed          Environmental       Campus Center    periodically.
                                                  Discarded materials in
 21     21       Lower      Storage Room 113      room                         Clean room                 Building Improvement Campus Center   Complete
                                                  Discarded materials in
 24     24       Lower      Storage Room 115      room                         Clean room                 Building Improvement Campus Center   Complete

 39     39       Lower      A/V Room 107-A        Debris in room               Clean room                 Building Improvement Campus Center   Complete
                                                                               Determine what this
                                                                               diffuser is used for;
                                                                               reinstall or discard, as
 43     43       Lower      Conference 105        Building material on floor   necessary                  Building Improvement Campus Center   Complete

 54     54       Middle     Room 219              Debris in room            Clean room                    Building Improvement Campus Center   Complete
                                                                            Determine if wires are                                             Should be a punchlist
 59     59       Middle     Rooms 218 A & B       Wire protruding from wall necessary                     Electrical safety   Facilities       item

                                                  Floor equipment stored by Store equipment in suitable
 38     37       Lower      Storage 100-J         door; presents trip hazard location                   Safety                Facilities       Complete
                            Ballroom Storage                                                                                                   Should be a punchlist
 40     40       Lower      108M                  Exposed wiring               Install plate or outlet    Safety              Facilities       item
                                                                               Remove ladder from
 45     45       Lower      Elevator Room 101A    Unsafe ladder in room        service                    Safety              Facilities       Complete
 48     48       Middle     Officials 234         Mirror not installed         Install mirror             Safety              Facilities       Complete
                                                                                                                                               Torn out by
                                                  Bathroom has step                                                                            contractors punch
 49     49       Middle     Officials 234         hazard                      Consider installing mat     Safety              Facilities       item
                                                  Location of switches
                                                  present opportunity to pull
                                                  fire alarm or shut down
 69     69       Middle     Mechanical 216A       HVAC                        Install night light         Safety              Facilities       Complete
                                                  Cable presents trip                                                                          Should be a punchlist
 73     73      Outside     Outside               hazard                      Secure cable to ground      Safety              Facilities       item
                                                                              Remove chemicals from
                            Mechanical Room                                   mechanical room; discard
 8       8       Upper      301C                  Unused chemicals            or store properly           Chemical Hygiene    Facilities       Complete
                                                                              Label container with
 28     28       Lower      Custodial 112         Unlabeled container         identity of contents        Chemical Hygiene    Facilities       Complete

      Page 14 of 18                                                                                                                                  UWG RM/EHS
      Building Inspection - Campus Center - October 2006                                                                                                   4/13/2011

Item                                                                                                                              Responsible
  #  Pic        Level           Location              Discrepancy              Action Required                  Type                Agency         Follow Up
                                                                             Remove chemical from air
                            Air Handling Room                                handling room; discard or
 29     29       Lower      111                   Abandoned chemical         store properly            Chemical Hygiene         Facilities      Complete

                                                                          Remove chemical from
                            Mechanical Room       Unused chemical in room mechanical room; store
 32     32       Lower      116                   (adhesive)              properly or discard properly Chemical Hygiene         Facilities      Complete

                            Abandoned                                        Remove chemical from
                            Mechanical Room                                  mechanical room; store
 35     35       Lower      120                   Abandoned chemical         properly or discard properly Chemical Hygiene      Facilities      Complete

                                                                             Remove chemical from
                                                                             mechanical room; store
 37     37       Lower      Storage 100-J         Abandoned chemical         properly or discard properly Chemical Hygiene      Facilities      Complete
                                                                             Label container with
 41     41       Lower      Custodial 106         Unlabeled container        identity of contents         Chemical Hygiene      Facilities      Complete

                                                                                                                                                Should be a punchlist
                                                                                                                                                item Should have
                                                                                                                                                been removed by
 71     71                  Roof                  Debris on roof             Clean debris off roof       Environmental          Facilities      contractor
                            Gymnasium
                            bleachers,
 1       1       Upper      scoreboard side       Unused material on floor   Clean materials off of floor Building Improvement Facilities       Complete
                            Hallway, outside room
 4       4       Upper      301-F                 Ceiling tile missing       Install ceiling tile        Building Improvement Facilities        Complete

 12     12       Upper      Room 312              Ceiling tile stained       Replace ceiling tile        Building Improvement Facilities        Complete
                                                  Sprinkler escutcheon
                                                  (ring) detached from       Reattach sprinkler                                                 Should be warranty
 15     15       Upper      Room 320              ceiling                    escutcheon                  Building Improvement Facilities        item

 18     18       Lower      Room 100M (Dock)      Debris in room             Clean room                  Building Improvement Facilities        Complete

 20     20       Lower      Room 100N             Debris in room           Clean room                    Building Improvement Facilities        Complete
                            Mechanical Room                                Remove materials (rebar,
 31     31       Lower      116                   Unused materials in room pipe) if no longer needed     Building Improvement Facilities        Complete
                            Mechanical Room
 33     33       Lower      116                   Debris in room             Clean out trash from room Building Improvement Facilities          Complete


      Page 15 of 18                                                                                                                                   UWG RM/EHS
      Building Inspection - Campus Center - October 2006                                                                                                      4/13/2011

Item                                                                                                                               Responsible
  #  Pic        Level           Location              Discrepancy               Action Required                     Type             Agency          Follow Up
                            Abandoned                                       Develop storage plan;
                            Mechanical Room       Materials accumulating on install shelves as                                                   This is Attic stock left
 36     36       Lower      120                   floor                     necessary                      Building Improvement Facilities       by contractor

 44     44       Lower      Electrical 103        Debris in room              Clean room                   Building Improvement Facilities       Complete

 46     46       Middle     Laundry 236           Dryer vent detached         Reattach dryer vent          Building Improvement Facilities       Warranty item

 47     47       Middle     Officials 234         Ceiling tile missing        Install ceiling tile         Building Improvement Facilities       Complete

 50     50       Middle     Officials 234         Towel rack broken           Repair/replace towel rack    Building Improvement Facilities       Complete
                                                                              Remove drain hardware;
                                                  Drain hardware on soap      install in drain, as
 51     51       Middle     Officials 234         holder                      necessary                    Building Improvement Facilities       Complete

 52     52       Middle     Elevator Room 101A    Unused materials in room Clean room                      Building Improvement Facilities       Complete

 53     53       Middle     Room 225              Ceiling tile missing        Install ceiling tile         Building Improvement Facilities       Complete

 55     55       Middle     Room 221              Ceiling tile has hole       Replace ceiling tile         Building Improvement Facilities       Punch list item

 57     57       Middle     Electrical 220        Debris in room              Clean room                   Building Improvement Facilities       Complete
                            Intramural basketball
 63     63       Middle     courts                Paint missing from post     Paint post                   Building Improvement Facilities       Complete
                                                  Fireproofing debris on
 67     67       Middle     Room 235              floor                       Clean up debris              Building Improvement Facilities       Complete

 68     68       Middle     Electrical 216        Trash in room               Remove trash                 Building Improvement Facilities       Complete
                                                  Location of emergency       Include emergency phone
                                                  phones do not register at   locations in Caller-ID for
 7       6         All      Entire building       dispatch                    dispatch                     Safety                ITS             Complete
                                                  Emergency phones do not     Install signage for
 6       6         All      Entire building       have signage.               emergency phones             Safety                Public Safety   Work in Progress
                                                                                                                                                 Permitted as long as
                                                                                                                                                 no more than 10
                                                                              Determine if this is                                               gallons are stored
 66     66       Middle     Room 235              Flammable stored            permissible                  Fire Safety           RM/EHS          outside
                                                                              Assess risk; determine
                                                  Improvements made to        who made these
 10     10       Upper      Gym bleachers         bleachers                   improvements                 Safety                RM/EHS          Complete


      Page 16 of 18                                                                                                                                      UWG RM/EHS
      Building Inspection - Campus Center - October 2006                                                                                               4/13/2011

Item                                                                                                                         Responsible
  #  Pic        Level           Location             Discrepancy              Action Required                     Type         Agency         Follow Up
                                                                             Determine where alarm is
                                                                             sounded; notify building
 17     17       Upper      Hallways              AEDs in alarmed boxes      manager                    Safety              RM/EHS         Complete
                                                  Fall hazard may be                                                                       Will be reviewed Jan
 19     19       Lower      Dock                  present                    Audit area                 Safety              RM/EHS         07

                                                                                                                                           Was unable to get
                                                                                                                                           reading. Equipment
                                                                                                                                           generating noise must
                                                                                                                                           be on intermittently.
                                                                                                                                           Will continue to try to
                                                                                                                                           get a reading however
                                                                                                                                           it is anticipated that
                                                                                                                                           the noise level
                                                                             Test to see if noise hazard                                   coupled with the
                            Mechanical Room       Noise hazard may be        exists; install signage as                                    duration, the area is
 30     30       Lower      116                   present                    necessary                   Safety             RM/EHS         not noise hazardous
                                                                                                                                           Measurements are
                                                                                                                                           between 84-85 dBA.
                                                  Custodian uses leaf                                                                      Hearing protection
                                                  blower with no hearing     Test to see if noise hazard                                   has been
 42     42       Lower      Custodial 106         protection                 exists                      Safety             RM/EHS         recommended.
                                                                             Determine if this is in                                       Inquiry sent to Tom
                                                                             compliance with weapons                                       Mackel. Reply
 61     61       Middle     Room 218 A (IRS)      Flare gun stored           policy                      Safety             RM/EHS         pending.
                                                                                                                                           IRS does not have a
                                                                                                                                           chemical inventory list
                                                                                                                                           on record with
                                                                             Determine if chemicals are                                    RM/EHS. Email was
                                                                             on inventory; prompt IRS to                                   sent to IRS
 60     60       Middle     Room 218 A (IRS)      Miscellaneous chemicals    provided MSDS               Chemical Hygiene   RM/EHS         accordingly.
                                                                                                                                           Organization will
                                                                                                                                           acquire non-toxic
                                                                                                                                           substitutes for
                                                                                                                                           toxic/flammable
                                                                                                                                           chemicals that are
                                                                                                                                           currently ion
                                                                                                                                           inventory. In the
                                                  Xylol-based paints being   Determine if hazard exists,                                   interim the door will
                                                  used; possible chemical    based on chemical and                                         remain open when in
 14     14       Upper      Room 321              exposure                   room ventilation            Environmental      RM/EHS         use.


      Page 17 of 18                                                                                                                               UWG RM/EHS
      Building Inspection - Campus Center - October 2006                                                                                                 4/13/2011

Item                                                                                                                        Responsible
  #  Pic        Level           Location              Discrepancy          Action Required                 Type               Agency             Follow Up
                            Abandoned
                            Mechanical Room       Moisture barrier may                                                                        Sampled, results
 34     34       Lower      120                   contain ACM             Sample; update database    Environmental        RM/EHS              pending
                                                                                                                                              Extinguisher log
                                                                                                                                              updated. Contractor
                                                                          Remove extinguisher;                                                will remove
                                                                          place into inventory (KA                                            extinguisher and
 65     65       Middle     Room 235              Extinguisher off wall   080 758)                   Building Improvement RM/EHS              place into spares.
                                                  Unused hardware on
 72     72                  Roof                  room                    Remove hardware           Building Improvement RM/EHS               Complete
                            Student Activities                            Submit work order to have
 13     13       Upper      bathroom              Mirror not installed    mirror installed          Safety               Student Activities   Complete
                                                                          Label container with
 11     11       Upper      Room 305              Unlabeled container     identity of contents      Chemical Hygiene     Student Activities   Complete




      Page 18 of 18                                                                                                                                 UWG RM/EHS

						
Related docs
Other docs by rws61529
Mployee Provident Fund Form
Views: 14  |  Downloads: 0
Mpls Service Contract
Views: 9  |  Downloads: 0
Mpp Network Project Plan
Views: 63  |  Downloads: 0
Mou for Business Acquisition Proposal
Views: 406  |  Downloads: 0
Ms Company Annual Report Word Template - PDF
Views: 32  |  Downloads: 0
Mpd Management
Views: 17  |  Downloads: 0
Mpfi Technology - DOC
Views: 29  |  Downloads: 0
Moving Agreement
Views: 31  |  Downloads: 0