					           Unit                          1                              2                               3                              4
Power (MWe /MWth)                   460/1380                        784/2381                        784/2381                       784/2381
Type of Reactor                        BWR-3                         BWR-4                          BWR-4                           BWR-4

Status at time of EQ      In service – auto shutdown      In service – auto shutdown      In service – auto shutdown      Outage

Core and fuel integrity   Damaged                         Severe damage                   Damaged                         No fuel in the Reactor

                          RPV temperature high but
RPV & RCS integrity                                       RPV temperature stable          RPV temperature stable
                          stable                                                                                          Not applicable due to
                                                                                                                          outage plant status
Containment integrity     No information                  Damage suspected                Damage suspected

                          AC power available - power to   AC power available – power to   AC power available – power to   AC power available – power
AC Power                  instrumentation – Lighting to   instrumentation – Lighting to   instrumentation – Lighting to   to instrumentation – Lighting
                          Central Control Room            Central Control Room            Central Control Room            to Central Control Room

Building                  Severe damage                   Slight damage                   Severe damage                   Severe damage

                          Around half of Fuel is          Around half of Fuel is          Around half of Fuel is
Water level of RPV
                          shown uncovered (Stable)        uncovered (Stable)              uncovered (Stable)

Pressure of RPV           Increasing                      Stable                          Stable
                                                                                                                          Not applicable due to
CV Pressure Drywell       Decreasing trend                Stable                          Stable                          outage plant status
                          Injection of freshwater – via   Injection of freshwater – via   Injection of freshwater – via
Water injection to RPV    mobile electric pump with       mobile electric pump with       mobile electric pump with
                          off-site power                  off-site power                  off-site power

Water injection to CV     No information                  No information                  No information

                          Fresh water spraying                                            Freshwater injection via        Fresh water spraying
                                                          Freshwater injection to the
Spent Fuel Pool Status    completed by concrete                                           Fuel Pool Cooling Line and      completed by concrete
                                                          Fuel Pool Cooling Line
                          pump truck                                                      Periodic spraying               pump truck
04/06/2011 07:00 UTC
            Unit                         5                             6
Power                                 784/2381                     1100/3293

Type of Reactor                       BWR-4                         BWR-5

Status at the EQ occurred   Outage                        Outage

Core and Fuel                                                                           Severe condition
RPV & RCS integrity

Containment int.                                                                        Concern
AC Power
                                                                                        No immediate
                                                                                        concern
Building
                            Cold Shutdown                 Cold Shutdown
                            Being maintained using off-   Being maintained using off-
Water level of RPV
                            site electrical power and     site electrical power and
                            existing plant equipment.     existing plant equipment.
Pressure of RPV

Containment Pressure

Water injection to RPV

Water injection to CV

Spent Fuel Pool Status


04/06/2011 07:00 UTC

				