					                       MICHIGAN DEPARTMENT OF TRANSPORTATION
                   BUREAU OF AERONAUTICS - STANDARD SPECIFICATION
                                                L-109
                   Installation of Airport Transformer Vault and Vault Equipment


                DESCRIPTION                           when requested by the engineer.

1.1      This item shall consist of an airport         VAULT AND PREFABRICATED METAL
transformer vault or a prefabricated metal                        HOUSING
housing constructed and installed in accordance
with this specification at the location and in        2.2      Concrete. The concrete for the vault
accordance with the design and dimensions             shall be proportioned, placed, and cured in
shown in the plans. This work shall also include      accordance with Item P-610, Structural Portland
the installation of conduits in floor and             Cement Concrete, using 3/4 inch maximum size
foundation, painting and lighting of the vault or     coarse aggregate.
metal housing, and the furnishing of all
incidentals necessary to produce a completed          2.3      Reinforcing Steel. Reinforcing steel bars
unit. Included as a separate part under this item     shall be intermediate or structural grade
or as a separate item where an existing vault is      deformed-type bars and shall meet the
to be utilized shall be the furnishing of all vault   requirements of AASHO M 31.
equipment, wiring, electrical buses, cable,
conduit, potheads, and grounding systems. This        2.4     Brick. Brick shall conform to ASTM C-
work shall also include the painting of               62, Grade SW.
equipment and conduit; the marking and
labeling of equipment and the labeling or             2.5    Asbestos Cement Duct. Asbestos
tagging of wires; the testing of the installation;    cement duct and fittings shall be in accordance
and the furnishing of all incidentals necessary to    with Fed. Spec. W-C-571.
place it in operating condition as a completed
unit to the satisfaction of the engineer.             2.6      Fiber Conduit. Fiber conduit and
                                                      fittings shall be in accordance with Fed. Spec.
      EQUIPMENT AND MATERIALS                         W-C-581.

2.1     General.                                      2.7     Rigid Steel Conduit. Rigid steel
                                                      conduit and fittings shall be in accordance with
        (a)     Airport lighting equipment and        Fed. Spec. WW-C-581.
materials covered by FAA specifications shall
have the prior approval of the Federal Aviation       2.8      Lighting. Vault or metal-housing light
Administration, Airports Service, Washington,         fixtures shall be of a vapor-proof type.
D.C. 20591, and shall be listed in the most
recent Advisory Circular 150/5345-1, Approved         2.9      Outlets. Convenience outlets shall be
Airport Lighting Equipment.                           heavy-duty duplex units designed for industrial
                                                      service.
        (b)      All other equipment and
materials covered by other referenced                 2.10   Switches. Vault or metal-housing light
specifications shall be subject to acceptance         switches shall be single-pole switches.
through manufacturer’s certification of
compliance with the applicable specification

FAA Approved: October 24, 1974
L-10 9, Installation of Airpo rt Tra nsform er Vault and Vault Equipment.                             Page 2 of 10

2.11     Floor Drains. The floor drains shall be               2.14     Bus Connectors. Connectors shall be
similar to type Z-798-A (or equal), as                         similar to Burndy Type NT (or equal) for copper
manufactured by the Z. A. Zurn Manufacturing                   tubing. Connectors for insulated bus cable shall
Company.                                                       be of the proper size and type for the service
                                                               intended.
2.12     Paint.
                                                               2.15      Bus Supports. Bus supports shall be
         (a)     Red lead priming paint for                    similar to Westinghouse No. 527892 (or equal),
ungalvanized metal surfaces and the mixing                     insulated for 7,500 volts, single clamp type for 2-
thereof shall conform to the 97% grade in Fed.                 bolt flat mounting.
Spec. TT-R-191. The red lead shall be
furnished in paste form and delivered to the job               2.16   Ground Bus. Ground bus shall be 1/8
in the original unbroken packages bearing the                  inch X 3/4 inch copper bus bar.
maker’s name and brand. The raw linseed oil,
turpentine, and drier shall be in accordance with              2.17     Square Duct. Duct shall be square
the Federal specifications listed below:                       similar to that manufactured by the Square D
                                                               Company (or equal), or the Trumbull Electric
                                                               Manufacturing Company (or equal). The entire
 Raw Linseed Oil                          TT-L-215             front of the duct on each section shall consist of
                                                               hinged or removable cover for ready access to the
 Turpentine                               TT-T-801             interior. The cross section of the duct shall be
                                                               not be less than 4 by 4 inches except where
 Drier; Paint, Liquid, Type I             TT-D-651             otherwise shown in the plans.

        (b)     White paint for body and finish                2.18    Ground Rods. Ground rods shall be
coats on metal and wood surfaces shall be                      copper or copper-clad of the length and diameter
ready-mixed paint conforming to Fed. Spec. TT-                 specified in the plans.
P-102.
                                                               2.19    Potheads. Potheads shall be similar to
         (c)     Priming paint for wood surfaces               G&W Type N, Shape C (or equal), unless
shall be mixed on the job by thinning the above                otherwise specified. Potheads shall be furnished
specified white paint by adding ½ pint of raw                  with plain insulator bushings and conduit
linseed oil to each gallon.                                    couplings. Potheads shall have a rating not less
                                                               than the circuit voltage.
         (d)     Paint for the floor, ceiling, and
inside walls shall be in accordance with Fed.                  2.20    Prefabricated Metal Housing. The
Spec. TT-E-487. Walls and ceiling shall be                     prefabricated metal housing shall be in
light gray and the floor shall be medium gray.                 accordance with Advisory Circular 150/5340-9.

        (e)     The roof coating shall be hot                  2.21    FAA-Approved Equipment. Certain
asphalt material in accordance with Fed. Spec.                 items of airport lighting equipment installed in
SS-R-451.                                                      vaults are covered by individual FAA equipment
                                                               specifications. The specifications are listed
2.13     High-Voltage Bus. High-voltage bus                    below:
shall be standard weight 3/8 inch IPS copper
tubing or it may be insulated copper cable of the
size and voltage rating specified.
L-10 9, Installation of Airpo rt Tra nsform er Vault and Vault Equipment.                              Page 3 of 10


 AC 150/5345-3          Specification for L-821                  AC 150/5345-21        Specification for L-813
                        Airport Lighting Panel                                         Static Indoor Type
                        for Remote Control of                                          Constant Current
                        Airport Lighting                                               Regulator Assembly; 4
                                                                                       KW and 7.5 KW; for
 AC 150/5345-5          Specification for L-847                                        Remote Operation of
                        Circuit Selector Switch,                                       Taxiway Lights
                        5000 Volt, 20 Ampere
                                                                 AC 150/5345-35        Specification for L-816
 AC 150/5345-7          Specification for L-824                                        Circuit Selector Cabinet
                        Underground Electrical                                         Assembly for 600 Volt
                        Cables for Airport                                             Series Circuits
                        Lighting Circuits
 AC 150/5345-10         Specification for L-828                2.22     Other Electrical Equipment. Constant-
                        Constant Current                       current regulators, distribution transformers, oil
                        Regulator With Stepless                switches, cutouts, relays, terminal blocks,
                        Brightness Control                     transfer relays, circuit breakers, and all other
                                                               regularly used commercial items of electrical
 AC 150/5345-11         Specification for L-812                equipment not covered by FAA equipment
                        Static Indoor Type                     specifications shall conform to the applicable
                        Constant Current                       rulings and standards of the Institute of Electrical
                        Regulator Assembly; 4                  and Electronic Engineers or the National
                        KW and 7.5 KW; with                    Electrical Manufacturers Association. When
                        Brightness Control for                 specified, test reports from a testing laboratory
                        Remote Operation                       indicating that the equipment meets the
                                                               specifications shall be supplied. In all cases,
 AC 150/5345-13         Specification for L-841
                                                               equipment shall be new and a first-grade product.
                        Auxiliary Relay Cabinet
                                                               This equipment shall be supplied in the quantities
                        Assembly for Pilot
                                                               required for the specific project and shall
                        Control of Airport
                                                               incorporate the electrical and mechanical
                        Lighting Circuits
                                                               characteristics specified in the proposal and
 AC 150/5345-18         Specification for L-811                plans.
                        Static Indoor Type
                        Constant Current                       2.23     Wire. Wire in conduit rated up to 5,000
                        Regulator Assembly, 4                  volts shall conform to Advisory Circular
                        KW; with Brightness                    150/5345-7, Specification for L-824
                        Control and Runway                     Underground Electrical Cables for Airport
                        Selection for Direct                   Lighting Circuits, for rubber insulated neoprene-
                        Operation                              covered wire, or Fed. Spec. J-C-30, Type RHW,
                                                               for rubber insulated fibrous-covered wire. For
                                                               ratings up to 600 volts, thermoplastic wire
                                                               conforming to Fed. Spec. J-C-30, Types TW,
                                                               THW, and THWN, shall be used. The wires
                                                               shall be of the type, size, number of conductors,
                                                               and voltage shown in the plans or in the proposal.

                                                                            (a)   Control Circuits. Wire shall be
L-10 9, Installation of Airpo rt Tra nsform er Vault and Vault Equipment.                             Page 4 of 10

not less than No. 12 AWG and shall be insulated                mechanical type so that when the forms are
for 600 volts. If telephone control cable is                   removed the ends of the ties shall be at least 1
specified, No. 19 AWG telephone cable                          inch beneath the concrete surface; the holes shall
conforming to the United States Department of                  be plugged and finished to prevent discoloration.
Agriculture, Rural Electrification                             Reinforcing steel shall be placed, as shown in the
Administration (REA) Bulletin 345-14 shall be                  drawings, and secured in position to prevent
used.                                                          displacement during the concrete placement.

                                                               The external surfaces of the concrete shall be
(b)      Power Circuits.                                       thoroughly worked during the placing operation
         1.     600 volts maximum-Wire shall                   to force all coarse aggregate from the surface.
                be No. 6 AWG or larger and                     Thoroughly work the mortar against the forms to
                insulated for at least 600 volts.              produce a smooth finish free from air pockets and
         2.     3,000 volts maximum-Wire                       honeycomb.
                shall be No. 6 AWG or larger
                and insulated for at least 3,000               The surface film of all pointed surfaces shall be
                volts.                                         removed before setting occurs. As soon as the
         3.     Over 3,000 volts-Wire shall be                 pointing has set sufficiently, the entire surface
                No. 6 AWG or larger and                        inside and outside of the vault shall be
                insulated for at least the circuit             thoroughly wet with water and rubbed with a No.
                voltage.                                       16 carborundum stone, or equal quality abrasive,
                                                               bringing the surface to a paste. All form marks
        CONSTRUCTION METHODS                                   and projections shall be removed. The surface
                                                               produced shall be smooth and dense without pits
3.1      General. The contractor shall construct               or irregularities. The materials which have been
the transformer vault or prefabricated metal                   ground into a paste during the rubbing process
housing at the location indicated in the plans.                shall be spread or brushed uniformly over the
Vault construction shall be reinforced concrete,               entire surface (except the interior surfaces that
concrete masonry, or brick wall as specified.                  are to be painted shall have all paste removed by
The metal housing shall be prefabricated                       washing before painting) and permitted to reset.
equipment enclosure to be supplied in the size                 Final exterior finish shall be obtained by rubbing
specified. The mounting pad or floor details,                  with No. 30 carborundum stone, or an equal
installation methods, and equipment placement                  quality abrasive. The surface shall be rubbed
are shown in the plans.                                        until the entire surface is smooth and uniform in
                                                               color.
The contractor shall clear, grade, and seed the
area around the vault or metal housing for a                            (b)      Brick and concrete construction.
minimum distance of 10 feet on all sides. The                  When this type of construction is specified, the
slope shall be not less than ½ inch per foot away              foundation shall be concrete conforming to the
from the vault or metal housing in all directions.             details shown in the plans. The outer edge of the
                                                               foundation at the floor level shall be beveled 1-
3.2      Foundation and Walls.                                 1/2 inches at 45°. Brick walls shall be 8 inches
                                                               thick, laid in running bond with every sixth
         (a)     Reinforced concrete                           course a header course. Brick shall be laid in
construction. The contractor shall construct the               cement mortar (1 part masonry cement and 3
foundation and walls in accordance with the                    parts sand) with full mortar bed and shoved
details shown in the plans. Unless otherwise                   joints. All joints shall be completely filled with
specified, internal ties shall be of the                       mortar, and facing brick shall be back-parged
L-10 9, Installation of Airpo rt Tra nsform er Vault and Vault Equipment.                              Page 5 of 10

with mortar as work progresses. All joints shall               and secured in position to prevent displacement
be 3/8 inch thick, exterior joints tooled concave,             during the pouring of the concrete. The concrete
and interior joints struck flush. Both interior                shall be poured monolithically and shall be free
and exterior brick surfaces shall be cleaned and               of honeycombs and voids. The surface shall
nail holes, cracks, and other defects filled with              have a steel-trowled finish and shall be sloped as
mortar. When specified, a nonfading mineral                    shown in the drawing. The underside of the roof
pigment mortar coloring shall be added to the                  slab shall be finished in the same manner as
mortar. Steel reinforcing bars, 3/8 inch in                    specified for walls.
diameter and 12 inches long, shall be set
vertically in the center of the brick wall on not              One brush or mop coat of hot asphalt roof
more than 2 foot centers to project 2½ inches                  coating shall be applied to the top surface of the
into the concrete roof slab. Lintels for                       roof slab. The asphalt material shall be heated to
supporting the brickwork over doors, windows,                  within the range specified by the manufacturer
and louvers shall consist of two 4- X 3- X 3/8-                and immediately applied to the roof. The
inch steel angles. Lintels shall be painted with               finished coat shall be continuous over the roof
one coat of red lead before installation, and all              surface and free from holidays and blisters.
exposed parts shall be painted similar to doors                Smears and dribbles of asphalt on the roof edges
and window sash after installation.                            and building walls shall be removed.

Window sills may be concrete poured in place                   3.4      Floor. The floor shall be reinforced
or precast concrete as indicated in the plans. All             concrete as shown in the drawings. When
exposed surfaces shall have a rubbed finish as                 present, all sod, roots, refuse, and other
specified under reinforced concrete                            perishable material shall be removed from the
construction. After completion, all interior and               area under the floor to a depth of 8 inches, unless
exterior faces of walls shall be scrubbed with a               a greater depth is specified in the invitation for
solution of muriatic acid and water in the                     bids. This area shall be backfilled with materials
proportions of not less than 1 part acid to 10                 consisting of sand, cinders, gravel, or stone. Fill
parts of water. All traces of efflorescence, loose             shall be placed in layers not to exceed 4 inches
mortar, and mortar stain shall be removed, and                 and shall be thoroughly compacted by tamping or
the walls washed down with clear water.                        rolling. A layer of building paper shall be placed
                                                               over the fill prior to placing concrete. The floor
         (c)      Concrete masonry construction.               surfaces shall have a steel-trowled finish. The
When this type of construction is specified, the               floor shall be level unless a drain is specified, in
foundation shall be concrete conforming to the                 which case the floor shall be pitched 1/4-inch per
details shown in the plans. The concrete                       foot downward toward the drain. A 1/4- inch
masonry units shall be standard sizes and shapes               asphalt felt expansion joint shall be placed
and shall conform to ASTM C-90 and shall                       between floor and foundation walls. The floor
include the closures, jambs, and other shapes                  shall be poured monolithically and shall be free
required by the construction as shown in the                   of honeycombs and voids.
plans. Standard construction practice shall be
followed for this type of work including mortar,               3.5       Floor Drain. If shown in the plans, a
joints, reinforcing steel for extensions into roof             floor drain and dry well shall be installed in the
slab, etc. Plaster for interior walls, if specified,           center of the floor of the equipment room. The
shall be portland cement plaster.                              dry well shall be excavated 4 X 4 feet square and
                                                               to a depth of 4 feet below the finished floor
3.3      Roof. The roof shall be reinforced                    elevation and shall be backfilled to the elevation
concrete as shown in the plans. Reinforcing                    of the underside of the floor with gravel-which
steel shall be placed as shown in the drawing                  shall all pass a 2-inch mesh sieve and shall all be
L-10 9, Installation of Airpo rt Tra nsform er Vault and Vault Equipment.                             Page 6 of 10

retained on a 1/4-inch mesh sieve. The gravel                  adding 2/3-quart of spar varnish and 1/3-quart of
backfill shall be placed in 6-inch maximum                     turpentine to each gallon of paint. The second
layers, and the entire surface of each layer shall             coat shall be applied without thinning. All doors,
be tamped either with a mechanical tamper or                   lintels, and windows shall be cleaned to remove
with a hand tamper weighing not less than 25                   any rust or foreign material and shall be given
pounds and having a face area of not more than                 one body and one finish coat of white paint.
36 square inches nor less than 16 square inches.               Bare metal surfaces shall be given a prime coat
The drain inlet shall be set flush in the concrete             of red lead prior to the body and finish coats.
floor. The drain shall have a clear opening of
not less than 8 inches in diameter.                            3.9      Lights and Switches. The contractor
                                                               shall furnish and install a minimum of two
3.6      Conduits in Floor and Foundation.                     duplex convenience outlets in the vault room.
Conduits shall be installed in the floor and                   Where a control room is specified, at least two
through the foundation walls in accordance with                duplex outlets shall be installed.
the details shown in the plans. All underground
conduit shall be painted with a bituminous                         INSTALLATION OF EQUIPMENT IN
compound. Conduit shall be installed with a                       VAULT OR PREFABRICATED METAL
coupling or metal conduit adapter flush with the                             HOUSING
top of the floor. All incoming conduit shall be
closed with a pipe plug to prevent the entrance                3.10      General. The contractor shall furnish,
of foreign material during construction. Space                 install, and connect all equipment, equipment
conduit entrances shall be left closed.                        accessories, conduit, cables, wires, buses,
                                                               grounds, and support necessary to insure a
3.7      Doors. Doors shall be metal-clad                      complete and operable electrical distribution
fireproof Class A doors conforming to                          center for the airport lighting system as specified
requirements of the National Electric Code and                 herein and shown in the plans. When specified,
local electrical codes.                                        an emergency power supply and transfer switch
                                                               shall be provided and installed.
3.8      Painting. The floor, ceiling, and inside
walls of concrete construction shall first be                  The equipment installation and mounting shall
given a hardening treatment, after which the                   comply with the requirements of the National
contractor shall apply two coats of paint as                   Electrical Code and local code agency having
specified below, except that interior face brick               jurisdiction.
walls need not be painted. The hardening
treatment shall consist of applying two coats of               3.11     Power Supply Equipment.
either a commercial floor hardener or a solution               Transformers, regulators, booster transformers,
made by dissolving 2 pounds of magnesium                       and other power supply equipment items shall be
fluosilicate or zinc sulphate crystals in 1 gallon             furnished and installed at the location shown in
of water. Each coat shall be allowed to dry at                 the plans or as directed by the engineer. The
least 48 hours before the next application. After              power supply equipment shall be set on steel “H”
the second treating coat has dried, the surfaces               sections, “I” beams, channels, or concrete blocks
shall be brushed clean of all crystals and                     to provide a minimum space of 1½ inches
thoroughly washed with clear water. Paint for                  between the equipment and the floor. The
walls and ceiling shall be a light gray color                  equipment shall be placed so as not to obstruct
approved by the engineer. The floor paint shall                the oil-sampling plugs of the oil-filled units; and
be a medium gray color approved by the                         nameplates shall, so far as possible, not be
engineer. Before painting, the surfaces shall be               obscured.
dry and clean. The first coat shall be thinned by
L-10 9, Installation of Airpo rt Tra nsform er Vault and Vault Equipment.                              Page 7 of 10

If specified in the plans and specifications,                  installing the vault equipment shall bring the
equipment for an alternate power source or an                  cables from the trench or duct through the
emergency power generator shall be furnished                   entrance conduits into the vault and make the
and installed. The alternate power supply                      necessary electrical connections. For the
installation shall include all equipment,                      incoming and outgoing high-voltage load circuits,
accessories, an automatic changeover switch,                   the contractor shall furnish and install rigid
and all necessary wiring and connections. The                  metallic conduit risers, surmounted by potheads,
emergency power generator set shall be the size                from floor level to the level as shown in the
and type specified.                                            plans.

3.12    Switchgear and Panels. Oil switches,                   The incoming high-voltage power supply service
fused cutouts, relays, transfer switches, panels,              to the vault shall enter below the floor of the
panel boards, and other similar items shall be                 vault and shall rise from the floor level in a rigid
furnished and installed at the location shown in               metallic conduit riser, surmounted by a pothead,
the plans or as directed by the engineer. Wall or              as described above. Using insulated high-voltage
ceiling-mounted items shall be attached to the                 cable, the incoming power service shall be
wall or ceiling with galvanized bolts of not less              connected from the pothead to the oil-fused
than 3/8-inch diameter engaging metal                          cutouts or to the specified disconnecting switch
expansion shields or anchors in masonry or                     or equipment. From the oil-fused cutouts or
concrete vaults.                                               disconnecting device, the insulated service
                                                               conductors shall be connected to the overhead
3.13     Duct and Conduit. The contractor                      voltage bus system of the vault. The high-
shall furnish and install square-type exposed                  voltage bus system shall utilize the materials
metallic ducts with hinged covers for the control              specified and shall be mounted and installed in
circuits in the vault. These shall be mounted                  accordance with the requirements of the National
along the walls behind all floor-mounted                       Electrical Code or the local code agency having
equipment and immediately below all wall-                      jurisdiction.
mounted equipment. The hinged covers shall be
placed to open from the front side with the                    3.15    Wiring and Connections. The
hinges at the front bottom.                                    contractor shall make all necessary electrical
                                                               connections in the vault in accordance with the
Wall brackets for square ducts shall be installed              wiring diagrams furnished and as directed by the
at all joints 2 feet or more apart with                        engineer. In wiring to the terminal blocks, the
intermediate brackets as specified. Conduit                    contractor shall leave sufficient extra length on
shall be used between square ducts and                         each control lead to make future changes in
equipment or between different items of                        connections at the terminal block. This shall be
equipment when the equipment is designed for                   accomplished by running each control lead the
conduit connection. When the equipment is not                  longest way around the box to the proper
designed for conduit connection, conductors                    terminal. Leads shall be neatly laced in place.
shall enter the square-type control duct through
insulating bushings in the duct or on the conduit              3.16    Marking and Labeling. All equipment,
risers.                                                        control wires, terminal blocks, etc., shall be
                                                               tagged, marked, or labeled as specified below:
3.14     Cable Entrance and High-Voltage
Bus System. Incoming underground cable from                            (a)      Wire identification. The
field circuits and supply circuits will be installed           contractor shall furnish and install self-sticking
outside the walls of the transformer vault as a                wire labels or identifying tags on all control
separate item under Item L-108. The contractor                 wires at the point where they connect to control
L-10 9, Installation of Airpo rt Tra nsform er Vault and Vault Equipment.                                Page 8 of 10

equipment or to the terminal blocks. Wire                      installation. This price shall be full
labels, if used, shall be of the self-sticking                 compensation for furnishing all materials and for
preprinted type and of the manufacturer’s                      all preparation, assembly, and installation of
recommended size for the wire involved.                        these materials, and for all labor, equipment,
Identification markings designated in the plans                tools, and incidentals necessary to complete the
shall be followed. Tags, if used, shall be of                  item.
fiber not less than 3/4-inch in diameter and not
less than 1/32-inch thick. Identification                      The first three digits of any item for work
markings designated in the plans shall be                      included under this specification shall be 109, i.e.
stamped on tags by means of small tools dies.                  109XXXX.
Each tag shall be securely tied to the proper
wire by a nonmetallic cord.
                                                               Payment will be made under:
         (b)     Labels. The contractor shall
                                                                 Item L-109-5.1    Construction of Airport
stencil identifying labels on the cases of                                         Transformer Vault in Place-
regulators, breakers, and distribution and control                                 per unit.
relay cases with white oil paint as designated by
the engineer. The letters and numerals shall be                  Item L-109-5.1    Installation of Airport
not less than 1 inch in height and shall be of                                     Transformer Vault
proportionate width. The contractor shall also                                     Equipment in Place-per unit.
mark the correct circuit designations in
accordance with the wiring diagram on the                        Item L-109-5.1    Construction of
terminal marking strips which are a part of each                                   Prefabricated Metal
terminal block.                                                                    Housing and Foundation in
                                                                                   Place-per unit.
       METHOD OF MEASUREMENT
                                                                 Item L-109-5.1    Installation of Prefabricated
                                                                                   Metal Housing Equipment
4.1     The quantity of vaults to be paid for
                                                                                   in Place-per unit.
under this item shall consist of the number of
vaults constructed in place and accepted as a
complete unit.                                                          FEDERAL SPECIFICATIONS
                                                                        REFERENCED IN ITEM L-109
4.2     The quantity of prefabricated metal
housings to be paid for under this item shall                    Number                          Title
consist of the number of housings constructed in
place and accepted as a complete unit.                           J-C-30               Cable and Wire,
                                                                                      Electrical (Power, Fixed
4.3      The quantity of vault or prefabricated                                       Installation)
metal housing equipment to be paid for under
                                                                 W-C-581              Conduit and Fittings;
this item shall consist of all equipment installed,
                                                                                      Nonmetallic, Rigid,
connected, and accepted as a complete unit
                                                                                      (Bituminized
ready for operation.
                                                                                      Homogeneous Fiber).
             BASIS OF PAYMENT                                    SS-R-451             Roof-Coating; Asphalt,
                                                                                      Brushing-Consistency
5.1      Payment will be made at the contract
unit price for each completed and accepted vault                 TT-D-651             Drier, Paint, Liquid
or prefabricated metal housing equipment
L-10 9, Installation of Airpo rt Tra nsform er Vault and Vault Equipment.                          Page 9 of 10


 TT-E-487                Enamel; Floor and Deck                  AC 150/5345-7    Specification for L-824
                                                                                  Underground Electrical
 TT-L-215                Linseed Oil, Raw (For                                    Cables for Airport Lighting
                         Use in Organic                                           Circuits
                         Coatings)
                                                                 AC 150/5345-10   Specification for L-828
 TT-P-102                Paint, Oil: Titanium-                                    Constant Current Regulator
                         Lead- Zinc and Oil,                                      With Stepless Brightness
                         Exterior, Ready-Mixed,                                   Control
                         White and Light Tints
                                                                 AC 150/5345-11   Specification for L-812
 TT-R-191                Red Lead, Dry and                                        Static Indoor Type Constant
                         Paste in Oil                                             Current Regulator
 TT-T-801                Turpentine; Gum                                          Assembly; 4 KW and 7.5
                         Spirits, Steam Distilled,                                KW; With Brightness
                         Sulfate Wood, and                                        Control for Remote
                         Destructively Distilled                                  Operation

 W-C-571                 Conduit and Fittings,                   AC 150/5345-13   Specification for L-841
                         Nonmetal, Rigid;                                         Auxiliary Relay Cabinet
                         (Asbestos-Cement or                                      Assembly for Pilot Control
                         Fire-Clay Cement), (for                                  of Airport Lighting Circuits
                         Electrical Purposes)                    AC 150/5345-18   Specification for L-811
 WW-C-581                Conduit, Metal, Rigid;                                   Static Indoor Type Constant
                         and Coupling, Elbow,                                     Current Regulator
                         and Nipple, Electrical                                   Assembly, 4 KW; With
                         Conduit: Zinc-Coated                                     Brightness Control and
                                                                                  Runway Selection for Direct
                                                                                  Operation.
FAA SPECIFICATIONS REFERENCED IN
            ITEM L-109                                           AC 150/5345-21   Specification for L-813
                                                                                  Static Indoor Type Constant
 Number                                Title                                      Current Regulator
                                                                                  Assembly, 4 KW and 7.5
 AC 150/5340-9           Prefabricated Metal                                      KW for Remote Operation
                         Housing for Electrical                                   of Taxiway Lights
                         Equipment
                                                                 AC 150/5345-35   Specification for L-816
 AC 150/5345-3           Specification for L-821                                  Circuit Selector Cabinet
                         Airport Lighting Panel for                               Assembly for 600 Volt
                         Remote Control of Airport                                Series Circuit
                         Lighting
                                                                 ASTM SPECIFICATIONS REFERENCED
 AC 150/ 5345-5          Specification for L-847
                                                                           IN ITEM L-109
                         Circuit Selector Switch,
                         5,000 Volt 20 Ampere
                                                                 Number                    Title
L-10 9, Installation of Airpo rt Tra nsform er Vault and Vault Equipment.   Page 10 of 10


 ASTM C-62           Specification for Building
                     Brick (Solid Masonry Units
                     Made from Clay or Shale)

        RURAL ELECTRIFICATION
       ADMINISTRATION BULLETIN
       REFERENCED IN ITEM L-109

 Number                        Title
 REA Bulletin 345-14           REA Specification for
                               Fully Color-Coded,
                               Polyethylene-Insulated,
                               Double Polyethylene-
                               Jacketed Telephone
                               Cables for Direct Burial
                      MICHIGAN DEPARTMENT OF TRANSPORTATION
                  BUREAU OF AERONAUTICS - STANDARD SPECIFICATION
                  Installation of Airport Transformer Vault and Vault Equipment
                           Standard Supplemental Specification No. L-109

This supplemental specification augments and amends the specification of like number published in
Federal Aviation Administration Advisory Circular 150/5370-1A, Standard Specifications for
Construction of Airports, published May, 1968, and such subsequent changes as may be published to
date.

Additional information pertinent to this specification may be shown on the plan sheets.

SPECIFICATION ITEM NO. L-109, AIRPORT TRANSFORMER VAULT AND VAULT
EQUIPMENT, is amended as follows:

CONSTRUCTION METHODS

Installation of Equipment in Vault or Prefabricated Metal Housing

109-3.16 Marking and Labeling. ADD the following:

(c) Cards. Where equipment is furnished with cardholders, the contractor shall furnish cards, if
necessary, and shall print or type the correct circuit designations on the cards. Each card shall be
protected with a transparent plastic cover furnished, if necessary, by the contractor.

(d) Wiring Diagram. The contractor shall install a wiring diagram furnished by the engineer showing
final connections and identification markings. The diagram shall be installed on a wall of the vault room
under glass in a 1½ inch wide by 3/4 inch thick wood frame. The diagram shall be mounted where
directed by the engineer.

(e) Signs. The contractor shall furnish and install a sign on the outside face of the vault fireproof door, at
approximately 5 feet above the floor level. The sign shall be enameled metal containing words
“DANGER” and “HIGH VOLTAGE” on it (red-on-white, or white-on-red) in letters at least 2 inches
high.

109-3.17 Grounding. ADD this new section:

The contractor shall furnish and install a permanent and effective grounding system in the vault for all
transformer and switch cases, panelboard and relay cabinets, outlet boxes, pull boxes, conduit, etc., and
for all neutral conductors. At least 2 ground rods shall be furnished and installed outside the building by
the contractor and the vault grounding system shall be electrically connected to the ground rods.

(a) Grounding Conductors. The ground bus inside the vault shall be mounted 1/4 inch out from the wall
and 6 inches above the floor. Connections to the ground bus bar from equipment and to ground rods or
plates shall be No. 6 bare copper wire or larger. Grounding conductors shall be attached to neutral
circuits, equipment cases, conduits, cabinets, relay boxes and to ground rods or plates by means of
suitable lugs, pressure connectors, or clamps. Connections which depend upon solder shall not be used.


FAA Approved: February 1, 1971
(b) Rods. Ground rods installed outside the vault shall be spaced at least 6 feet apart and at least 3 feet
from the vault foundation. The rods shall be driven into the ground so that the top is at least 6 inches
below grade.

(c) Plates. Where rock conditions prevent the driving of ground rods, as specified above, grounding
plates may be used if authorized by the engineer. A minimum of 3 plates spaced at least 6 feet apart and
at least 3 feet from the vault foundation shall be used for each separate ground. Each plate shall be of
copper not less than 18 inches square and not less than 0.06 inch thick. Plates shall be embedded in an
area of permanent moisture, unless otherwise specified. The plates shall be set in a horizontal plane, as
deep as possible in rock fissures or depressions to obtain the best available ground. There shall be a
minimum of 3 inches of earth under the plate, and a minimum of 1 foot of earth backfilled above the
plate with the backfill approximately flush with the surrounding surface.

(d) Resistance. The resistance to ground of any part of the grounding system shall not exceed 10 ohms.

109-3.18 Testing. ADD this new section:

The entire vault equipment installation shall be tested in operation as a completed unit prior to
acceptance. Tests shall include resistance, voltage, and current readings, as required by the engineer.
Testing equipment shall be furnished by the contractor. Tests shall be conducted as directed by the
engineer and shall be to his satisfaction. The contractor shall be responsible for all equipment and
materials furnished, and any equipment or materials found to be defective or damaged shall be replaced
by the contractor at his own expense.

				