					       Emerson Network Power
       Data Centre Cooling



Questnet May 07
Who Is Emerson? …Liebert Corp.
          Founded in 1890
          Record of consistent long-term
           performance
          Global product/market leadership
          Recognized outstanding
           management process
          Strong global presence
          Solid financial position
          FY2006 Sales of $20.1B
          Over 108,000 employees and 245
           worldwide plants
                    .

                                              2
Among The World‟s Most Admired…

               ELECTRONICS
               1 General Electric      7.80
               2 Emerson               7.69
               3 Siemens Corp.         6.81
               4 Maytag                6.45
               5 Royal Philips         6.09
               6 Eaton                 5.95
               7 Whirlpool             5.91
               8 Toshiba               5.76
               9 SPX                   5.44
               10 Tyco International   3.57




                .

                                              3
      Emerson Network Power Systems
      Global Service Capability
    NORTH AMERICA                          EUROPE
     15 District Offices                    12 District Offices
    122 Service Centers                     50 (10 Direct + 44 Dist) Service Centers
    292 Air Contractor / USA Partners      279 Service Field Engineers
     27 Approved-Certified EF&I Partners   150 Technical Support / Response                            ASIA-PACIFIC
    464 Service Field Engineers                                                                         11 District Offices
    224 Technical Support / Response                                                                   175 Service Field Engineers
                                                                                                        47 Technical Support / Response

                                                                                                       CHINA
                                                                                                       29 Customer Service Centers
                                                                                                        7 Regional MS Engineering Dept.
                                                                                                        7 Regional DP Technical Support
                                                                                                       210 Service Field Engineers
                                                                                                       122 Technical Support / Response
             Many Locations




SOUTH AMERICA
 12 District Offices / Support Centers
167 Pre-approved Service Subcontractors
329 Field Service Engineers/Technicians
 35 Technical Support / Response

                                                                                 Sales Offices
                                                                                 Distributors & Reps
                                                                .

                                                                                                                                          4
 Emerson Network Power
 Grid to chip in the Data Centre and beyond.
Inbound               DC Power Systems                      OEM Embedded
 Power
                                                                 Power      Connector
                                                                 Units      Assemblies
 Utility
  AC                                                            DC/DC
             AC                                                             C
                                                                Converter   o
            Surge    DC Power System   DC Power Interface
                                                                            n
                                                                            n
                      AC Power Systems                                      e
                                                                 AC/DC      c
                                                                 Power      t
                                                                 Supplies   I
                                                                            v
Transfer                                                        DC/DC       I   Tower
 Switch      AC                                                 Converter   t
                                                                            y
            Surge           UPS         AC Distribution

             Precision
              Climate                                         OSP
                                                            Solutions
Generator    Systems


            - Maintenance
 Services
            - Monitoring               .

                                                                                         5
Agenda
 Issues facing the Data Centre


 Developing the right cooling strategy for
  today… and into the future


 Efficiency costs and benefits


 Example of how the right cooling strategy
  can lower the Total Cost of Ownership

                     .

                                              6
  Managing High Density Servers
     Rack density trend when
      fully populated with the
     newest server technology




                                                                   How most sites are dealing
                                                                      with server density
    2000            2002            2006              2009
28 x 2U Servers 42 x 1U Servers 6 Blade Centers    Rabid Blades
2kW Heat Load 6kWw Heat Load 24kW Heat Load       40kW Heat Load


                              Heading Toward 50kW



                                                         .

                                                                                                7
      Progression to High Density
                                                              The average server replacement cycle is 3-4 years

                                                                                       Rack kW
                                                                                          1 kW
                                                                                          2 kW
                                                                                          5 kW
                                                                                         10 kW
                                                                                         15 kW
                                                                                         20 kW




Issues facing the IT Manager
   Getting hot air out of the Racks
   Hot air mixing with the inlet of other racks
   Diversity of loads in the Data Centre
   Flexibility of “On Demand Cooling”
   Inefficiencies in room design i.e. no raised floors


                                                          .

                                                                                                                  8
  DCUG Survey Results – What are the
  Biggest Issues facing the IT Manager
                                        0%                      10%   20%          30%   40%   50%

              Heat Density (Cooling)                                         22%
        Space Constraints/Grow th                                      19%
                     Pow er Density                                   18%
   Adequate Monitoring Capabilities                             8%
                Availability (Uptime)                       7%
     Technology Changes / Change                            7%
Energy Costs / Equipment Efficiency                    5%
                               Other               4%
       Security (Physical or Virtual)             3%
        Data Center Consolidations            2%
                       Data Storage           2%
                Hardw are Reliability        1%
             Regulatory Compliance           1%
        Staffing/Training Limitations    0%




                                                            .

                                                                                                 9
Cooling Presents an Opportunity
For Energy Savings
             Data Centre Power Draws
                              Electricity        Lighting, etc.
                             Transformer/             3%
                                 UPS
                         Air     10%
                      Movement
 Cooling                12%
                                                                                   IT Equipment
About 35%-                                                                              50%
   40%                          Cooling
                                 25%
                                               Source: EYP Mission Critical Facilities Inc., New York

                                Sources of Energy Waste
            Lack of air containment (cable openings, room leakage)
            Unit cycling
            Lack of humidification control
            Mixing of Hot and Cold air
            Excess Fan energy that turns into heat
            Inefficiencies in room design


                                       .

                                                                                                        10
Cooling Solutions to meet the
Higher Density Requirements
 Requires moving the cooling closer to the heat source to;
   – more precisely cool the specific load
   – not waste energy - “brute force” by cooling the whole room.

 Cooling coils may be in multiple locations;
   – External to the Rack – Overhead, Back, Side
   – In the Rack – Under, Side
   – Part of the Server

 Requires a fluid to be delivered to the cooling coils to transport
  the heat out of the Data Centre. Can be;
   – Chilled Water (ChW)
   – Refrigerant (pumped low pressure)


                                 .

                                                                       11
            Adaptive Cooling Architecture

    Reliability                             Flexibility
•Optimal Redundancy                        • XD Cooling on Demand
• Two refrigeration circuits                 • Retrofit any floor, any
• Design for Reliability                      space, any time
• Extended Compressor life                   • Designed for the Future
• Open architecture                        • Extensive configuration options
• Room balance
• Extended fail safe operation         Total Cost
•High Density cooling without    • Significant Energy savings
 introducing water in the room     • Operating Modulation for lowest energy consumption
 or rack                           • Cooling at the Source
                                 • Minimal to zero Floor Space consumed
                                 • Extends current infrastructure into the Future

                                       .

                                                                                      12
 Planning for High Density requires A
 Systems Approach to the Cooling System
 Traditional Floor-Mount - the first 1-1.5 kW/m2 (or 3 - 4 kW per rack)
               and then utilise Supplemental Cooling above that level


                               Provides high density sensible cooling at
Computer
                                              the source
 Room /
  Data
 centre
                           SUPPLEMENTAL COOLING


           TRADITIONAL                 Controls Humidity and Filtration
            Floor-Mount
                                   Creates the base airflow distribution



           0         5    10      15            20   25      30      35    40
                                       kW / Rack

                                            .

                                                                                13
High Efficiency CRAC units at what cost?



              EC fans
              Ensure the good distribution of the
              cooling capacity when the
              infrastructure grows


              Copeland Digital ScrollTM
              Rooms that drive quickly changing
              business give out peaks of heat load


                    .

                                                     14
Copeland Digital Scroll Compressor
only in Emerson CRAC units.

               10 to 100% capacity
                modulation
                 – Power input reduction at
                   partial load
               Adjusts quickly to the heat load
                 – less need for re heating
               Less number of start/stop
                cycling:
                 – longer life for the
                   compressor


                   .

                                                   15
Under Floor Space is an Air Plenum not a cable zone !!!




          Power Cabling           Communications Cabling
                          .

                                                           16
  Four Adaptable Solutions for High density cooling
  All Available from Emerson Network Power
                                             Fluid
                                             Refrigerant

                                                           Liebert XDV           Liebert XDH
                              Liebert XDC




                                                                  Liebert XDO
                Knurr          Liebert XDP
                CoolTherm R
Closed                                                                                   Open
Architecture                                                                             Architecture




                                                     Liebert XDWP

                                                                   Liebert XDR
               Knurr
               CoolTherm
                                                      Liebert XDWC

                                              .   Fluid
                                                  Water
                                                                                                   17
Liquid Cooling Configurations –
with Building Chilled Water
Building Chiller                                 XDWP
                                                            CW




             Valve
  Building
                       Heat
  Chilled
                     Exchanger
   Water
                            Tank



CDU                                       2nd               XDP
                     Pump          Pump   Loop

                                                                  Refrigerant




                                                        .

                                                                                18
Liquid Cooling Configurations –
without Building Chilled Water

                                           CW




                                                Refrigerant




  Heat Rejection   XDC/XDWC Chiller
                   (with secondary loop)
                                   .

                                                              19
XDV Nominal capacity >10 kW (2.8 Ton) @ 37°C EAT
–XD Coolant (R134A) changes from a liquid to a gas as heat is
absorbed in the cooling coil and returned to the XDP to
condense back to a liquid




                           .

                                                                20
XDO Nominal capacity >20 kW (5.7 ton) @ 33°C EAT
    •capacty is dependent on the entering air temperature.
    •Higher EAT will yield more capacity (up to 20%)




                             .

                                                             21
Plug and Play Capacity on Demand




                 .

                                   22
Liebert XDH – Horizontal „Inter-Rack‟ Cooler
  Cooling Capacity 22 or 30 kW (6.3 or 8.5 Ton)            Top View   Hot
  Fan Coil (Enclosure, Coils, 6 Fans, Controls) with                  Aisle
     Horizontal Air Flow Pattern, Placed in the
     Equipment Row
                                                                       Cold
    Connects to one or two Liebert XDP/XDC Pumped
     Refrigerant Circuits                                              Aisle
    Nominal Dual (A and B) Power Cords
    Connection to Liebert XD Pumped Refrigerant                       Hot
     Circuit with Hard Piping or with Flexible Piping                  Aisle
     with Quick Connect Couplings
    Condensate Detection
    Front Air Diffuser for Discharge to Both Sides or to
     One Side.
    Technical Specifications
      – 240V-1ph-50Hz
      – 1250, 2000 Lts /sec
      – 500, 1200 watt
      – W300 x L1066 x H1982mm)

                                          .

                                                                          23
              TM               TM
Liebert XD         CoolFrame
  Up to 14kw per rack




                        .

                                    24
Liebert XD Customer Base




           .

                           25
Liebert XD Customer Base




           .

                           26
                            Dell Computers
    Determines the Liebert XD system is the best means to solve the high density
     heat problems generated by the new generation of servers
    Builds a 100 sq/m simulated Data Center to test their new servers and to show
     their customers the recommended solutions for high density heat load


             The only equipment demonstrated is the
                            Liebert XD solution


     Engaging with Liebert to provide Environmental Assessments for their
      customers
     Opportunity to recommend and sell Liebert equipment




                                          .

                                                                                     27
Dell Lab Application Using XD solution




                  .

                                         28
Dell Lab Application Using XD solution




                  .

                                         29
Dell Lab Application Using XD solution




                  .

                                         30
H.S.B.C. Application New York




                  .

                                31
VA. Tech Application Using XD solution




                  .

                                         32
 Secondary Fluid Comparisons
  Pumped Refrigerant System Chilled Water Based System
  Advantages                        Advantages
   – No Water in the DC or            – Lowest Fluid Cost
     electrical hazards               – No limitation to room size
   – Micro-channel coil efficiency
     (+50%), lower air side pressure
     drop => lower operating costs
   – Smaller piping requirements  Disadvantages
   – Cooling Modules can be          – Electrical Hazard
     located anywhere
   – Scalable Capacity (2-3x to CW ) – Operating Efficiency
                                     – May require fluid treatment to
 Disadvantages                        prevent fouling
   – Small room scalability          – Limited overhead cooling
   – Higher Fluid Cost                 options



                                 .

                                                                        33
Liebert XD (eXtreme Density)
   Supplemental Cooling Products
        Dew Point Controlled                                  Pre-Piping
                                                              Assembly
      Pumped Refrigerant Cooling




                                                      XDO20                    XDCoolFrame20
                                                      Overhead
                                                                               Custom for Egenera
                                                      Cooling
                                                                               Cooling Module
                                        XDV10         Module      XDH20/32
   XDC                 XDP              Above                     Horizontal
   Chiller with   or   Pumping          Rack                      Cooling
   Pumping Unit        Unit             Module                    Module

Base Infrastructure (140 kW)                  Cooling Modules (mix and match)
• Not DX (Compressorised Direct Expansion) but refrigerant R134A at low pressure is used as
a fluid to transport the heat. Refrigerant is a HFC, non hazardous or flammable


                                          .

                                                                                               34
Pre-piping Assemblies

 Plug and Play cooling
  on DEMAND
 Add and remove cooling
  modules while the system is
  running
 Quick connect sizes are standard for all
  cooling modules
 Multiple configurations depending on the
  redundancy plan (50mm,100mm centres)
 Outfit the Data Centre at one time




                                       .

                                             35
   Additional System Opportunities for
   Improved Cooling Efficiencies
kW for cooling per kW of server heat load


                                            0.7    0.65                                                    Energy Savings driven by
                                                                                                        reduction in Fan Power (cooling
                                            0.6
                                                                                                         system and server) plus Heat
                                            0.5                        0.42                                    Transfer efficiency
                                                                                   0.36
                                            0.4    Data centre Best Practices
                                                                                                          0.31 30%




                                                                                    Enclosed Rack
                                            0.3                                                                                                                45%




                                                                                                           XD Modules
                                                                         Optimal                                                                   0.2




                                                                                                                                        Embedded
                                            0.2




                                                                                                                        Egenera




                                                                                                                                         Cooling


                                                                                                                                                   Component
                                                                                                                                                     Cooling
                                            0.1

                                             0
                                                    1990


                                                              2000


                                                                          2005




                                                                                                                                           2010
                                                                                    2006/2007


                                                                                                           2004/2006


                                                                                                                            2006/2007




                                                                                                                                                     Future
                                                  Traditional Cooling             Liebert XD Opportunities 
                                                                                                    .

                                                                                                                                                                     36
Improving The Total Cost Of Ownership
with the Liebert XD Cooling Systems
                     How                          Results in …
 Cooling closer to the source of the heat    Less Power (energy
  makes the heat exchangers more efficient     consumed)
  (higher entering air temperatures)
 Lower total Fan HP                          Less Power (energy
                                               consumed)
 Sensible cooling eliminates wasted          Less Power (energy
  energy dehumidify unnecessarily and          consumed)
  then having to re-humidify
 Less Chiller or DX infrastructure required  Less Power and
                                               Capital Equipment
 Overhead cooling modules require no         Less Floor Space
  additional floor space                       consumed
 Cooling solutions that meet the cooling     Less Floor Space
  requirements to fill racks of high density   consumed
  servers

                               .

                                                                    37
Summary
 Cooling solutions for higher density will need to move
  closer to the load and will require a reliable fluid delivery
  means
   – Cost effective cooling solutions exist that can be
     employed today that meet future needs
   – Allow racks to be fully populated

 Cooling at the source of the heat load will actually lower
  your incremental energy consumption
   – Less power for the cooling system provides more
     power for the IT equipment


Which leads to a significantly reduced TCO.


                                 .

                                                                  38
Extreme Heat Density                                     Xtreme
Solution                                                 Density soln
                                                         - XDO
                                          Hot Cold Hot
                                         Aisle Aisle Aisle
                    PRECISION ROOM AIR
                    CONDITIONER




                                                      REMOTE
                                                      DISTRIBUTION
                                                      CABINET



    Cold
    Aisle
Xtreme
Density soln- XDV
                       RACKCOOLER
Thank You