IXP110 Controller

Document Sample
IXP110 Controller Powered By Docstoc
					                                                                                       www.powelltronics.com


                                         IXP110 Controller
                                    ImproX IXP110 Controller




Overview
Introduction

         The ImproX IXP110 Controller is a fully featured Controller that forms part of the IXP110 Software
         System. The IXP110 Controllers applications include access control (access of up to 900 users
         through a single door) and alarm control. The IXP110 Controller is available in three models:


                                 IXP904-1-0-GB-XX: IXP110, Aluminium Cabinet, RS232 connection to the
                                 Host PC.
                                 IXP905-1-0-GB-XX: IXP110, Aluminium Cabinet, USB connection to the Host
                                 PC (USB cable included).
                                 IXP906-1-0-GB-XX: IXP110, Aluminium Cabinet, Ethernet connection to the
                                 Host PC.

         The following Antenna Readers are compatible with the IXP110 Controller and are suitable for most
         installations:


                                 ImproX (MMA) Mullion Antenna Reader.
                                 ImproX (MA) Micro Antenna Reader.
                                 ImproX (MHA) Metal Antenna Reader.
                                 ImproX (KHA) Metal Keypad Antenna Reader.
                                 ImproX (KMA) Mullion Keypad Antenna Reader.
                                 ImproX (RA) Rod Antenna Reader.
                                 ImproX (KA) Keypad Antenna Reader.
                                 ImproX (DPA) Door Entry Panel Antenna Reader.
                                 ImproX (CA) Conduit Antenna Reader.

         Instead of using a mechanical key, the door is opened when a valid Tag is presented to the Antenna
         Reader. Advanced security features prevent the door latch being opened even if the wiring is
         tampered with, or if the Antenna Reader is substituted with another Antenna Reader.

         For added security, the System can be programmed so that, in addition to presenting a Tag, a 4-digit
         Personal Identification Number (PIN-code) is also required to be entered via a Keypad Antenna
         Reader before access is allowed. As a cost effective option, provided the System is programmed to
         accept it, a 5-digit Personal Access Code (PAC-code) can be used in place of a Tag.

                                                                                                                1
                                                                         Part Number:        IXP904-1-0-GB-XX
                                                                                             IXP905-1-0-GB-XX
                                                                                             IXP906-1-0-GB-XX




        Three Tagholder levels are provided for in the System: User (entry during specified time periods only),
        Supervisor (entry at all times) and Administrator (entry at all times, and may program the System).

        The IXP110 System provides a variety of features, while keeping the system easy to use. Basic
        features are available using the Keypad Antenna Reader; advanced features are available by means
        of the PC Software program.

        The Controller is enclosed in an Aluminium Cabinet; however, as the Cabinet is NOT waterproof, the
        Controller is intended for indoor use only.

        The Controller offers a single Status LED for the installer.


Key Features

        Hardware Specific

                                 Installation friendly using a robust aluminium extrusion.
                                 Pluggable terminal blocks.
                                 Utilizes Quick Click Glands.
                                 Two Anti-tamper switches.
                                 Connection to up to two Antenna Readers per Controller.
                                 Supports all ImproX Antenna Readers (XTT901 – XTT909).
                                 In-field Firmware upgrades.
                                 Read/Write capability using the following Impro Tags: Slim Tags and Omega
                                 Tags (Read Only). WriTag 128 and WriTag 2048 (Read/Write).
                                 Reads selected Third-party Tags.
                                 Authorized Tagholders (“Administrator or Supervisor”) are able to arm and
                                 disarm a separate alarm panel by means of the Antenna Readers Keypad.
                                 Runs off AC power (16 V AC), charges a 12 V Sealed Lead Acid Battery,
                                 therefore no need for an external battery backed-up Power Supply.
                                 Supports 9 V DC to 24 V DC.




                                                                                                                  2
                                                                       Part Number:      IXP904-1-0-GB-XX
                                                                                         IXP905-1-0-GB-XX
                                                                                         IXP906-1-0-GB-XX




        System Specific

                                 Self contained system.
                                 Supports Anti-passback (APB) Mode.
                                 Three user-tag levels comprising of: “User, Supervisor and Administrator”.
                                 A unique 4-digit PIN-code per Tagholder.
                                 Operates as a simple intrusion alarm, whereby a siren activates when a door
                                 open sensor is triggered.
                                 A maximum of 900 Tagholders with a maximum of 950 transactions stored in
                                 the Transaction Buffer.
                                 Lost Tags can be voided from the System without having to change locks, or
                                 having any impact on other Tagholders.
                                 Supports Time Management Reporting.


Tag Read/Write Ranges

        The range that the Antenna Readers can read from or write to a Tag is dependent on the type of Tag,
        type of Antenna Reader and material on which the Antenna Reader is installed.

        Typical ranges are shown in Table 1.


                                                                 Typical Range (Minimum)
                        Tag Type                       (Antenna Reader installed on non-metallic surface)
                                                              (mm)                             (in)
            ISO Credit Card (Slim)                             60                              2.36
            ISO Credit Card (Omega)                            60                              2.36
            Key Ring Tag                                       40                              1.58
            Pico Tag                                           20                              0.78
            ISO Credit Card WriTag 2048                        60                              2.36
            ISO Credit Card WriTag 128                         60                              2.36
            Third-party Credit Card Tags                      30-50                         1.18-1.96
            NOTE:     Installing the Antenna Reader on a metallic surface will reduce the Tag reading range
                      slightly.
                                           Table 1: Typical Read/Write Ranges


Approvals


                                 CE Approved.
                                 FCC Approval Pending.




                                                                                                               3
                                                                Part Number:        IXP904-1-0-GB-XX
                                                                                    IXP905-1-0-GB-XX
                                                                                    IXP906-1-0-GB-XX




Specifications
Physical


           Dimensions
               Length                     :   104 mm (4 in).
               Width                      :   150 mm (6 in).
               Height                     :   54 mm (2 in).
           Approximate Weight
               IXP904-1-0-GB-XX           :   505 g (18 oz).
               IXP905-1-0-GB-XX           :   503 g (18 oz).
               IXP906-1-0-GB-XX           :   510 g (18 oz).
           Cabinet Material               :   Aluminium.
               Colour                     :   Black.


Environmental


           Temperature
                                                 o         o     o          o
               Operating                  :   -25 C to +60 C (-13 F to +140 F).
                                                 o         o     o          o
               Storage                    :   -40 C to +80 C (-40 F to +176 F).
                                                                                o       o
           Humidity Range                 :   0 to 95% relative humidity at +40 C (+104 F) non-
                                              condensing.
           Approvals (Test Information)   :   EN 300 330-1.
                                              EN 301 489-3.
           Dust and Splash Resistance     :   Designed to work in an indoor (dry) environment similar
                                              to IP40. The Controllers are not sealed against water.
           Drop Endurance                 :   2 m (7 ft) drop (in packaging).




                                                                                                        4
                                                                             Part Number:    IXP904-1-0-GB-XX
                                                                                             IXP905-1-0-GB-XX
                                                                                             IXP906-1-0-GB-XX




Electrical


              Power Requirements
                  Input Voltage using a Sealed     :    14 V AC to 18 V AC.
                  Lead Acid Backup Battery,             18 V DC to 24 V DC.
                  Connected to the Battery
                  Input and or Strike Lock
                  Connected to the Power
                  Output
                  Input Voltage NOT using a        :    9 V AC to 18 V AC.
                  Sealed Lead Acid Backup               9 V DC to 24 V DC.
                  Battery and or Strike Lock

             NOTE:     Battery Charging Voltage and Power Output Voltage are set at between 13.6 V DC and
                       13.8 V DC.

             NOTE:     This current is measured using 18 V DC Input Voltage.
                  IXP110 with two Antenna          :    135 mA (2.43 W).
                  Readers Connected

             NOTE:     Each Relay draws an extra 120 mA.

             NOTE:     The IXP110 current limits the charging current into the Sealed Lead Acid Battery to a
                       maximum of 350 mA.

             NOTE:     The maximum size Sealed Lead Acid Battery that can connect to the Battery Input is 12 V,
                       7 Ahr.

             NOTE:     The maximum current that can be drawn from the Power Output is 250 mA. (If using a
                       Maglock or high current Strike Lock, connect the Lock to a separate power supply).
                  Permissible Input Supply         :    1 V PP at 50 Hz.
                  Ripple Voltage (Max)
                  Power Input Protection           :    Reverse polarity, over-voltage and over-current
                                                        protection are provided on the Controller.
              Ethernet Port
                  Connection                       :    Standard Ethernet RJ45 connector.
                                                        10/100 Mbps, half or full duplex.
              RS232 Port
                  Connection                       :    9-Way, D-type, male connector at 115 200 Baud.
              USB Port
                  Connection                       :    USB, Type-B, female connector, USB 2.0 compliant
                                                        12 Mbps.
              Relays
                  Relay Output                     :    2 Relays, each with NO, COM and NC contacts.
                  Contact Ratings                  :    5 A at 28 V DC,
                                                        1.5 A at 220 V AC,
                                                        5 A at 120 V AC.




                                                                                                                  5
                                                                        Part Number:      IXP904-1-0-GB-XX
                                                                                          IXP905-1-0-GB-XX
                                                                                          IXP906-1-0-GB-XX




           Digital Inputs
               DOS Input                         :   Dry contact, non-potential sensing or 4 V to 30 V
                                                     potential sensing. Input protection to 50 V DC
                                                     (continuous).
               RTE Input                         :   Dry contact, non-potential sensing. Input protection to
                                                     50 V DC (continuous).
           Anti-tamper Protection                :   2 Anti-tamper switches provided.


Factory Default Settings


           Beep Codes
               Fails Power-on Self-test          :   Continuous beep for 2 seconds.
               Passes Power-on Self-test         :   Two short beeps of 200 ms duration, separated by a
                                                     200 ms inter-beep pause.


Operator or Installer Interfaces


           Controller
               Status LED                        :   Green LED (externally visible).
           Antenna Readers (x2)
               Status Indicator
                    Status LED                   :   Bi-colour, Red or Green LED.
               Buzzer
                    Volume and Tone              :   4-Step adjustable volume, single tone.

         Interface Details
         Relays
         The IXP110 Controller has two independent single-pole, double-throw (SPDT) Relay Outputs. The
         Latch Relay lets you interface to door strikes and magnetic locks. The Alarm Relay can be configured
         for Alarm Control.
         Dry Contact Digital Inputs
         The IXP110 Controller has two Dry Contact Digital Inputs. When used with the IXP110 Software these
         Digital Inputs can perform specific tasks such as:


                                  Door Open Sensing (DOS).
                                  Request to Enter or Exit (RTE).

         The Door Open Sensing (DOS) input is Software configurable in Normal Sensing Mode and in End of
         Line (EOL) Sensing Mode.




                                                                                                                6
                                                                Part Number:      IXP904-1-0-GB-XX
                                                                                  IXP905-1-0-GB-XX
                                                                                  IXP906-1-0-GB-XX




End of Line (EOL) Sensing




                   Figure 1: End of Line (EOL) Sensing Circuit

These Inputs can be individually configured to have End of Line (EOL) Sensing in the Software via the
Communications Protocol. With End of Line Sensing active, the Input detects when the input line has
gone open or closed circuit. Connect a 1 kOhm Resistor either in series with, or in parallel to, the Dry
Contact, mounted as close as possible to the Dry Contact for effective End of Line Sensing.

The recommended connection of the Resistor for Normally Closed (NC) and Normally Open (NO)
contacts is shown in Figure 1. For Normally Closed Dry Contacts, connect the 1 kOhm Resistor in
series with the contact; while for Normally Open contacts connect the Resistor in parallel with the
contact, see Figure 1.




                                                                                                           7
                                                                        Part Number:      IXP904-1-0-GB-XX
                                                                                          IXP905-1-0-GB-XX
                                                                                          IXP906-1-0-GB-XX




Installation Information
Accessories

          Find the following when unpacking the ImproX IXP110 Controller:


                                 An IXP110 Controller housed in a Black, Aluminium extruded Cabinet. The
                                 Cabinet consists of a Top Cover, a Base and two End Plates. Each End Plate
                                 is attached with four Thread Cutter Screws (2.2 x 5 mm).
                                 One copy of IXP110 Software on CD.
                                 A 3 V Lithium Battery (CR2032).
                  CAUTION:       DO NOT use the Metal-oxide Varistors (25 Vrms, 500 A, 77 V max
                                 clamping) with mains power applications.
                                 Two Metal-Oxide Varistors, 25 Vrms, 500 A, 77 V max clamping.
                                 Four Wood Screws (3.5 mm x 25 mm).
                                 Four Wall Plugs (7 mm).
                                 IXP905-1-0-GB-XX includes a standard 2 m (7 ft) USB Printer Cable. The
                                 USB Cable will have a Type „A‟ plug fitted at one end and a Type „B‟ plug fitted
                                 at the other end.
                                 IXP906-1-0-GB-XX includes a MAC Address Label.
                                 An extra Fixed Address Label.


General

          Remember the following when installing your IXP110 Controller:

          Communications Distance

                                 The Ethernet version of the Controller plugs into an Ethernet Switch or Hub (or
                                 other network device), cable runs for this must conform to ethernet cabling
                                 specifications.
                                 The RS232 communications distance between the IXP110 Controller and
                                 either the connected Host PC or Modem MUST NOT exceed 25 m (82 ft).
                                 Achieve this by using good quality screened 4-core cable.
                                 The USB communications distance between the Host PC and the IXP110
                                 Controller MUST NOT exceed 5 m (16 ft). Please note, however, that the
                                 supplied cable cannot be extended.




                                                                                                                    8
                                                                Part Number:      IXP904-1-0-GB-XX
                                                                                  IXP905-1-0-GB-XX
                                                                                  IXP906-1-0-GB-XX




EARTH Connection
Connect the IXP110 Controller to a good EARTH point. Using the Power Input Port, connect the
EARTH Lead to the „ETH‟ Terminal. Mains EARTH can be used, but electrical noise may exist.

Antenna Reader
Antenna Reader Distance
The ideal cable distance between the IXP110 Controller and its Antenna Reader ranges between 2 m
to 16 m (7 ft to 53 ft). Achieve this using a good quality shielded multi-strand **3-pair twisted cable.
                                                                      2            2
The cross-sectional area of the cable must not be less than 0.2 mm (0.0003 in ).

NOTE:      **When installing an ImproX RA, use 1-pair twisted cable.

Cable Specifications

The cable specifications should be similar to the following:


                         Conductor Resistance:          < 2 ohms.
                         Capacitance, Core to Earth: < 160 pF/m.
                         Capacitance, Core to Core:     < 100 pF/m.

Distance between Antenna Readers from the SAME Controller
To avoid mutual interference Install the Antenna Readers no closer than 150 mm (6 in) apart.
Distance between Antenna Readers from DIFFERENT Controllers
To avoid mutual interference Install the Antenna Readers no closer than 500 mm (20 in) apart.

Arc Suppression
Snubber devices are recommended for EMF Flyback and Arc Suppression when driving an inductive
load with the Relay, see Figure 2.




                               Figure 2: EMF Flyback




                                                                                                           9
                                                                         Part Number:      IXP904-1-0-GB-XX
                                                                                           IXP905-1-0-GB-XX
                                                                                           IXP906-1-0-GB-XX




Mounting the Controller

         CAUTION:         Make certain that you mount the Controller on a vibration-free surface.

         Select the mounting position of the IXP110 Controller, considering accessibility, routing of wires and
         visibility of the LED. Secure the Base to the mounting surface, using four suitable screws and wall
         plugs (supplied), nuts and bolts or rivets.

         Top Cover Release Mechanism

                            1.   Remove the top two Thread Cutter Screws (2.2 x 5 mm) from each of the End
                                 Plates.
                            2.   Insert a flat head screwdriver (maximum 7 mm) into the cut out in either of the
                                 two End Plates. Swivel the screwdriver until the Top Cover makes a click
                                 sound.
                            3.   Insert the screwdriver in the gap (on the side of the IXP110 Controller)
                                 between the Top Cover and the Base. Swivel the screwdriver again, to
                                 release the Top Cover from the Base.




                                      Figure 3: Front End Plate




                                      Figure 4: Back End Plate




                                                                                                                   10
                                                                          Part Number:     IXP904-1-0-GB-XX
                                                                                           IXP905-1-0-GB-XX
                                                                                           IXP906-1-0-GB-XX




Installing the Real Time Clock (RTC)/RAM Backup Battery

         CAUTION:         When handling the Real Time Clock (RTC)/RAM Backup Battery, be careful NOT
                          to touch the Positive and Negative Poles simultaneously. Doing so will
                          discharge the Battery.

         The Battery Holder is located on the left-hand side of the Controller‟s Printed Circuit Board (PCB),
         alongside the RTE Input Terminal Block (see Figure 6).

         First Time Use

                             1.   Remove the Controller‟s Top Cover.
                             2.   Slide the supplied 3 V, CR2032, Lithium cell Battery under the metal clip of the
                                  Battery Holder, with the "+" Terminal facing UP.
                             3.   Press the Battery firmly into the Battery Holder.
                             4.   Attach the Controller‟s Top Cover.


         Replacement

                             1.   Remove the Controller‟s Top Cover.
                             2.   Remove the old 3 V, CR2032, Lithium cell Battery from the Battery Holder by
                                  pulling the plastic retaining clip horizontally AWAY from the Battery Holder.
                                  The Battery Holder is spring-loaded, and will raise the Battery out of the
                                  Holder.
                             3.   Slide the new 3 V, CR2032, Lithium cell Battery under the metal clip of the
                                  Battery Holder, with the "+" Terminal facing UP.
                             4.   Press the new Battery firmly into the Battery Holder.
                             5.   Attach the Controller‟s Top Cover.




                                                                                                                     11
                                                                       Part Number:     IXP904-1-0-GB-XX
                                                                                        IXP905-1-0-GB-XX
                                                                                        IXP906-1-0-GB-XX




Electrical Connections
System Layout

        The block diagram (Figure 5) details the parts of the IXP110 System, and their interconnections.




                               Figure 5: IXP110 System Overview

        NOTE:     Items a, b and c are Impro-supplied, the remaining items are user-supplied.




                                                                                                           12
                                                        Part Number:   IXP904-1-0-GB-XX
                                                                       IXP905-1-0-GB-XX
                                                                       IXP906-1-0-GB-XX




Controller Layout




                    Figure 6: Key Component Positions




                                                                                          13
                                    Part Number:   IXP904-1-0-GB-XX
                                                   IXP905-1-0-GB-XX
                                                   IXP906-1-0-GB-XX




Figure 7: Input and Power Connections


                                                                      14
                                        Part Number:   IXP904-1-0-GB-XX
                                                       IXP905-1-0-GB-XX
                                                       IXP906-1-0-GB-XX




Figure 8: Antenna Reader and Relay Connections


                                                                          15
                                                                         Part Number:      IXP904-1-0-GB-XX
                                                                                           IXP905-1-0-GB-XX
                                                                                           IXP906-1-0-GB-XX




IXP110 System Maintenance

        Deleting the Database
        If it becomes necessary to clear all Tagholders, including all Tagholder settings, follow these steps:




                                  Figure 9: Deleting the Database


        Restore Factory Defaults
        If it becomes necessary to return the IXP110 System to its factory default settings, follow these steps:




                              Figure 10: Restoring Factory Defaults




                                                                                                                   16
                                                                        Part Number:      IXP904-1-0-GB-XX
                                                                                          IXP905-1-0-GB-XX
                                                                                          IXP906-1-0-GB-XX




Fixed Address Label

        Once the IXP110 is installed, sketch a rough site plan. Attach the loose, extra Fixed Address Label
        packaged with the Controller, in the position of the Controller on the sketched site plan. When the
        system installation is complete and all the units are represented on the site plan by their Fixed Address
        Labels, file the site plan for future reference.

        The Fixed Address is also used for system maintenance functions, including: deleting the database,
        and restoring factory defaults.

        MAC Address
        The MAC Address identifies the Lantronix® XPort™ component placed in each Ethernet version of the
        IXP110 Controller (IXP906-1-0-GB-XX).

        The MAC Address and description of the Controller‟s location are required by the Software Installer to
        enable an IP Address to be assigned to the Controller.

        We recommend that you attach the MAC Address Label to the site plan in the Controller‟s installed
        location.




Guarantee or Warranty
        CAUTION:         We reserve the right to nullify the products guarantee or warranty where you
                         have not properly installed the Metal-oxide Varistors.

        This product conforms to our Guarantee or Warranty details placed on our Web Site, to read further
        please go to www.impro.net.




Ordering Information
        Order the ImproX IXP110 Controller using the following Impro part numbers:


                      IXP904-1-0-GB-XX:       IXP110, RS232 connection to the Host PC.
                      IXP905-1-0-GB-XX:       IXP110, USB connection to the Host PC (USB cable included).
                      IXP906-1-0-GB-XX:       IXP110, Ethernet connection to the Host PC.




                                                                                                                    17
                                                                               Part Number:          IXP904-1-0-GB-XX
                                                                                                     IXP905-1-0-GB-XX
                                                                                                     IXP906-1-0-GB-XX




        This manual is applicable to the ImproX IXP110 Controller, IXP904-1-0-GB-02, IXP905-1-0-GB-02 and
       IXP906-1-0-GB-03. (The last two digits of the Impro stock code indicate the issue status of the product).
                                                                               IXP110\Controller\Product Specification Catalogue\
IXP354-0-0-GB-06        Issue 07           September 2007
                                                                                       LATEST ISSUE\IXP110C-psc-en-07.docx




                                                                                                                                    18

				