Digital Room Controller DNT-T305

Document Sample
Digital Room Controller DNT-T305 Powered By Docstoc
					                                                                             NETWORK THERMOSTAT
                                        Digital Room Controller                                     DNT-T305
                                        with LCD and Keypad
Description                                                                                         SPECIFICATIONS

The Delta™ Room Controller is a Native BACnet™ Application Controller that communicates             LCD
on an RS-485 LAN using the BACnet™ MS/TP protocol.
                                                                                                    Large font 4-digit alpha numeric
The controller is housed within a stylized wall mounted housing and includes programmable           display (for time or objects values)
LCD and keypad functions, and supports the Delta BACstat™.                                          Small font 4-digit alpha numeric
                                                                                                     display (for time or units display)
Strategies are written in GCL, rather than reside in fixed algorithms.
                                                                                                    12-digit alpha numeric display
Both firmware and controller databases are                                                          (for object names or menu
loadable over the network.                                                                          commands and options)
                                                                                                    10 display icons representing
                                                                                                    different functions
         Application
                                                                                                    Optional backlighting
         With the 3 external inputs , one fixed
         internal temperature input and 5 binary                                                    Keypad
         outputs, the Room Controller is suitable                                                   4 or 8 or 16 buttons
         for various room applications with small                                                   (suitable for different applications)
         I/O requirements such as Fan Coil Units,                                                   Security Door
         Unit Ventilators and Heat Pumps.                                                           Temperature Sensor
         The Room Controller is completely                                                          Thermistor Input - 10K Ω at 77°F
         programmable; GCL programs and                                                             (25° C)
         BACnet™ objects can be created and                                                         Accuracy +/-0.4° F from 32-158° F
         modified for the specific application.               DNT-T305 Room Controller              (+/- 0.2° C from 0-70° C)
                                                                                                    Display resolution of 0.1°
                                                         Features
                                                                                                    Stability 0.24° F over 5 years
                                                         > Native BACnet™ firmware                  (0.13° C)                      >>
                                                         > BACnet™ MS/TP communications
                                                         > Stylized wall-mount housing
                                                         > 4/8/16 button keypad
                                                         > Completely programmable in GCL
                                                         > Programmable LCD with optional
                                                           backlight
                                                         > Application database loadable over
                                                           the network
                                                         > Controller firmware flash loadable
                                                           over the network
                                                         > Derived Network Addressing (DNA)
                                                           for simple integration into a standard
                                                           network architecture



         Integrated Facilities Management Solutions. Simplified!
         Delta Controls Inc.                                                                        Technical specifications are subject to
         17850 56th Avenue      Tel: (604) 574-9444                                                 revision without notice.
         Surrey                 Fax: (604) 574-7793
         British Columbia       www.deltacontrols.com
         Canada V3S 1C7                                                                             Rev. 10_02
                                                                        NETWORK THERMOSTAT
                                                                        Digital Room Controller                                                                        DNT-T305
                                                                                                                                                                       SPECIFICATIONS (cont.)
                      Output 4         Output 3                                            Output 5                               Output 1    Output 2
   Power: 24VAC Class 2 at 5VA or 10 to 35VDC at 5VA excluding output loading.
   Outputs: 24 VAC / VDC at 12 VA / 0.5 Amps maximum for each output.                                                                                                  External Inputs
   For use in a Class 2 circuit.
   Use copper conductors only.
   Caution: To Reduce the Risk of Fire and Electric Shock, Do Not Interconnect the Outputs of 2 different Class 2 Circuits.
                                                                                                                                                                       3 Universal Inputs - 10 bit
                                                                                                                                                                       (supporting 0-5v, 0-10v, 10K)
     Ouputs: Jumper Configuration                                                              Inputs: Jumper Configuration                                    Clear
                     Jumper         External          Internal                              Input Jumper 10 KThermistor 0 - 5VDC 0 - 10VDC
                                                                                                                                                               Run
      Output            s           Source             source                                                                                                          External Outputs
        1&2            JP01                                                                 IP2       JP2
                       JP02

                       JP03                                                                 IP3       JP3
                                                                                                                                                                       5 Binary FET outputs (AC or DC
        3&4            JP04                                                                                                                                            switching or PWM)
                       JP05
                                                                                            IP4       JP4
          5
                       JP06                                                                                                                                            Jumper Selection for Internal or
   Note: Outputs can only be configured in pairs, and                                                                                                                  External Power on Binary Outputs
         both jumpers must be set the same.

                                                                                                                                                                       Technology
                                                                  CPU Status                                                                                           32-bit processor
                                                                                                                                                                       512 KB (4 MB) Flash Memory
                                                                                                                                                                       64 KB SRAM memory for database
                                                                                                                                                                       CPU Status LED
                                                                                                                                                                       Device Addressing
                                                                                                                                                                       Set via Keypad Configuration Setup
                                                                                 GND




                                                                                                      GND




                                                                                                                       GND
                                                OP5


                                                              COM 5


                                                                        IP4




                                                                                               IP3




                                                                                                                 IP2




                             JP05/06
                                                                                                                                                                       or software setup
                                                                                                                                       JP01/02 JP4 JP3 JP2             Communications Ports
                                                                                                                                                             10K
                                                                                                                                                             5V
                                                                                                                                                             10V       MAIN LAN (NET1)
                                                                                 COM 3/4




                                                                                                       COM 1/2


                                                                                                                 OP1
                                                OP4




                                                                        OP3




                                                                                                OP2
                                                              COM 3/4




                                                                                                                        COM 1/2




                         JP03/04

                               Rx      Tx
                                                                                                                                                                       BACnet™ MS/TP @ 9,600 or 19,200
                                                        Power/NET1                                                                                                     or 38,400 or 76,800 bps (default)
   Use same color wire for
                              NET1
                                                                                                                                                                       (maximum of 99 devices per MS/TP
   COMS and GNDS
                                                                                                                                                                       segment)
                                                               -
                                                                              +
                                          GND


                                                        ~24




       NET1 120 Ohm
       RC termination
       circuit jumper
                                                                         NET1
                                                                                                                                                   indicates LED
                                                                                                                                                                       SubLAN (NET2)
                                                      NET1
                                                      TERM
                                                                                                                                             Network Configure
                                                                                                                                                                       None with this model            >>
                                                                              10KOhm Thermistor                                          No Termination
                                                                                  location                                                Termination




                                                       Board Layout DNT-T305




Integrated Facilities Management Solutions. Simplified!
                                NETWORK THERMOSTAT
                                Digital Room Controller                                 DNT-T305
                                                                                        SPECIFICATIONS (cont.)
Ordering
                                                                                        Connectors
Order the Delta™ Room Controller with the desired options according to the              AMP plug-in terminal connectors
following product numbers.
                                                                                        Wiring
Features                       DNT-T305      DAC-T305     DSC-T305        DSM-T0        Class II
Internal Thermistor Input         ●              ●               ●           ●          Power
Additional I/O (3 IP & 5 OP)      ●              ●               ●                      10 VA (not including output loading)
                                                                                        24 VAC c/w visual LED status
Internal Audio Beeper                            ●               ●           ●          indication
RTC & Battery Backed SRAM                                        ●           ●          Ambient
RS-485 Main Port                  ●              ●               ●           ●          32° to 131° F (0° to 55°C)
RS-485 Subnet/LinkNet Port                       ●               ●           ●          10 - 90% RH (non-condensing)
RS-232 Port                                                      ●           ●          Dimensions
Backlighting                   Option B      Option B     Option B       Option B       43/16 x 511/16 x 11/8 ins
                                                                                        (10.7cm x 14.4cm x 3.0cm)
Keypad &                 G1A, G2A, H2A       Any Listed   Any Listed    Any Listed
Security Door                                  Below        Below         Below         Approvals/Standards
                                                                                        UL916; CE; FCC

An appended keypad and door code must be included to specify the desired model as
follows:
Code     Description                                 Extra          Exposed
                                                   Program          Through
                                                    Buttons           Door
G1A        General - 4 Buttons                            None         Top 4 Buttons
G1B        General - 16 Buttons                           Yes          Top 4 Buttons
G2A        General c/w Fan Speed - 8 Buttons              None         Top 8 Buttons
G2B        General c/w Fan Speed - 16 Buttons             Yes          Top 8 Buttons
G3A        General c/w Time & Date - 8 Buttons            None         Top 4 Buttons
H2A        Hotel c/w Fan Speed - 8 Buttons                None         Top 8 Buttons
K1A        Keypad Applications - 16 Numbered Buttons       All         All 16 Buttons

Accessories
RPT-768            Delta™ Network Repeater for MS/TP
TRM-768            Delta™ Network Terminator for MS/TP

				