SECTION 10 22 19 – DEMOUNTABLE PARTITIONS



PART 1 - GENERAL

1.01   RELATED DOCUMENTS

       A. Drawings and general provisions of the Contract, including General and Supplementary
          Conditions and Division 01 Specification Sections, apply to this Section.

       B. Specifications throughout all Divisions of the Project Manual are directly applicable to this
          Section, and this Section is directly applicable to them.

1.02   REFERENCE STANDARDS

       A. The latest published edition of a reference shall be applicable to this Project unless identified
          by a specific edition date.

       B. All reference amendments adopted prior to the effective date of this Contract shall be
          applicable to this Project.

       C. All materials, installation and workmanship shall comply with all applicable requirements and
          standards.

1.03   DEFINITIONS

       A. Demountable full height modular office partitions: A system of walls suitable for interior
          general office use. The basic components of the system are produced by a single
          manufacturer and are designed to permit relocation, reconfiguration and reuse of the
          components.

       B. Demountable full height high performance partitions: A system of walls suitable for interior
          special use applications which demand acoustical, air quality, thermal, and durability
          performance levels greater than that required for general office use. The basic components
          of the system are produced by a single manufacturer and are designed to permit relocation,
          reconfiguration and reuse of the components.

       C. Structural Panel System: A demountable partition system comprised of self supporting
          sandwich panel units which interlock by means of intermediate panel posts or other similar
          methods.

       D. Non Structural Panel System: A demountable partition system comprised of panels which are
          not self supporting and require a metal stud framework to be installed prior to panel
          application.

1.04   QUALITY ASSURANCE

[DELETE OR REVISE 2 OPTIONS BELOW IF NOT REQUIRED BY SIZE OF JOB.]

[ARCHITECT/ENGINEER MUST DELETE EVERYTHING IN BLUE AND IN BRACKETS BEFORE PUBLISHING.]




 The University of Texas                                                  DEMOUNTABLE PARTITIONS
 MD Anderson Cancer Center                                                               10 22 19
 MS072210                                                                                 1 OF 10
MD ANDERSON Project No. XX-XXXX                                       MD ANDERSON PROJECT NAME
AE Name                                                                           Issue Description
AE Project No.                                                                     Month, 00, 0000

      A. Installer Qualifications: Engage an experienced Installer who has successfully completed
         demountable partition installations similar in material, design, and extent to that indicated for
         Project.

      B. Single Source Responsibility: Obtain materials from one source from a single manufacturer.

[REVISE OR DELETE CHARACTERISTIC BELOW IF NOT APPLICABLE. FIRE HAZARD RATINGS VARY WITH
EACH MFR. AND TYPE OF MATERIAL.]

[USE CAUTION, AND AVOID REFERENCE TO STANDARDS UNLESS YOU ARE VERY FAMILIAR WITH EACH
ONE AND ARE AWARE OF ALL THEIR EMBEDDED OPTIONS. USE THIS ARTICLE TO INDICATE THE FULL
DESIGNATION AND TITLE TO ELIMINATE HAVING TO REPEAT THEM IN PARTS 2 AND 3.]
      C. Fire Performance Characteristics: Provide a system of demountable partitions that is identical
         to that tested for the following fire performance requirements, according to test method
         indicated, by UL or other testing and inspecting agency acceptable to authorities having
         jurisdiction. Identify products with appropriate markings of applicable testing and inspecting
         organization.

[REVISE FLAME SPREAD AS REQUIRED.]
          1. Surface Burning Characteristics: As follows:

[CHOOSE FROM 2 OPTIONS BELOW.]
              a. Flame Spread: Not more than 25

              b. Smoke Developed: Not more than 50

              c.   Flame Spread: Not more than 75

              d. Smoke Developed: Not more than 100

[GENERALLY RETAIN TEST METHOD BELOW WHICH IS REFERENCED BY AUTHORITIES HAVING
JURISDICTION. ALL REFER TO WHAT IS ESSENTIALLY THE SAME METHOD.]
              e. Test Method: ASTM E 84

              f.   Test Method: UL 723

              g. Test Method: NFPA 255

[REVISE FIRE RATINGS BELOW AS REQUIRED.]
          2. One hour fire rated partition assembly: ASTM E 119

          3. Twenty minute fire rated door assembly: ASTM E 152

      D. Physical Properties: Provide demountable partitions that are identical to that tested for the
         following physical properties, according to the test method indicated.

[REVISE ACOUSTICAL RATINGS AS REQUIRED.]




 The University of Texas                                                 DEMOUNTABLE PARTITIONS
 MD Anderson Cancer Center                                                              10 22 19
 MS072210                                                                                2 OF 10
MD ANDERSON Project No. XX-XXXX                                        MD ANDERSON PROJECT NAME
AE Name                                                                            Issue Description
AE Project No.                                                                      Month, 00, 0000

       E. Acoustical Characteristics: Provide system of demountable partitions that is identical to that
          tested in accordance with ASTM E 90 for an STC rating of 40.

       F. Load Bearing Characteristics: Provide a system of demountable partitions that is identical to
          that tested for the following load bearing properties, according to the test method indicated.

[SELECT FROM 2 OPTIONS BELOW OR REVISE LOAD BEARING CHARACTERISTICS AS REQUIRED.]
           1. Test Method: BIFMA Proof Load Standard for Static Loads.

           2. Rating: 4.5 pounds per lineal inch.

           3. Test Method: BIFMA Proof Load Standard for Static Loads.

           4. Rating: 7 pounds per lineal inch.

       G. Certification: Submit manufacturer's certificate stating that materials furnished comply with
          specified requirements. Include supporting certified laboratory testing data indicating that
          material meets specified test requirements.

       H. Mock up for Verification Purposes: In a location designated by the Architect, install a full scale
          installation incorporating at least one of each type of panel, and accessory required,
          illustrating each installation condition. Retain mock up installation until completion of total
          installation or dismantle earlier at the direction of the Architect. Materials used for the mock
          up installation will not be considered part of either the base contract materials or the attic
          stock materials.

[REQUEST ONLY THAT DATA NECESSARY FOR CONTROL OF SPECIFIC PROJECT.]
1.05   SUBMITTALS

       A. Product Data:

           1. Product data on physical characteristics, durability, resistance to fading, and flame spread
              characteristics for each type of partition and accessory.

[RETAIN BELOW IF PROCEDURES FOR PRODUCT CERTIFICATIONS RETAINED UNDER "QUALITY
ASSURANCE" ARTICLE.]
           2. Product certificates signed by manufacturers of partitions certifying that their products
              comply with specified requirements.

           3. Acoustical Certification from an independent testing agency stating that product and
              materials furnished comply with specified requirements. Include certified laboratory
              testing data indicating that panels and materials meet specified test requirements.
              Include STC and NRC ratings and square foot weight of panel.

       B. Samples:

           1. Samples for initial selection purposes in form of manufacturer's standard color charts
              showing full range of colors, textures, and patterns available for each type of material
              exposed to view.



 The University of Texas                                                   DEMOUNTABLE PARTITIONS
 MD Anderson Cancer Center                                                                10 22 19
 MS072210                                                                                  3 OF 10
MD ANDERSON Project No. XX-XXXX                                       MD ANDERSON PROJECT NAME
AE Name                                                                           Issue Description
AE Project No.                                                                     Month, 00, 0000

[DELETE ABOVE IF FINISHES PRESELECTED AND SPECIFIED OR SCHEDULED. RETAIN BELOW WITH OR
WITHOUT ABOVE.]
           2. Samples for verification purposes of each type of finish indicated, in sets for each color,
              texture, and pattern specified, showing a full range of variations expected in these
              characteristics.

               a. Panel Finish Face: Manufacturer's standard size unit, not less than 3 inches square.

               b. Door Finish Face: Manufacturer's standard size unit, not less than 3 inches square.

               c.   Panel Glazing: Manufacturer's standard size unit, not less than 3 inches square.

               d. Base Trim: 12 inch long sample.

               e. Between Panel Trim: 12 inch long sample.

       C. Shop Drawings:

[CLARIFY SPECIAL CONDITIONS THAT DEVIATE FROM STANDARD INSTALLATION. REQUEST
INSTALLATION DETAILS FOR SPECIFIC CONDITIONS IN LIEU OF MAKING A GENERAL STATEMENT
REGARDING SPECIAL INSTALLATION DETAILS.]
           1. Shop drawings showing location and extent of partitions. Include plans, elevations, large
              scale details of anchorages, and accessory items. Indicate unit conditions at openings,
              typical and special details, and location and installation requirements for hardware.

           2. Template drawings prepared by manufacturer showing location of items supported or
              anchored by permanent construction.

       D. Record Documents:

           1. Provide record approved product data, samples, warranties, and shop drawings.

1.06   DELIVERY, STORAGE AND HANDLING

       A. Deliver materials to Project Site in original factory wrappings and containers, clearly labeled
          with identification of manufacturer, brand name, quality or grade, fire hazard classification,
          and lot number. Store materials in original undamaged packages and containers, inside well
          ventilated area protected from weather, moisture, soiling, extreme temperatures, and
          humidity; laid flat, blocked off ground to prevent sagging and warping.

       B. Comply with instructions and recommendations of manufacturer for special delivery, storage,
          and handling requirements.

1.07   EXTRA MATERIALS

[REVISE PERCENTAGE TO SUIT PROJECT REQUIREMENTS. THE NEED FOR REPLACEMENT MATERIALS
MAY VARY GREATLY DEPENDING ON SYSTEM DESIGN AND ANTICIPATED USE.]




 The University of Texas                                                 DEMOUNTABLE PARTITIONS
 MD Anderson Cancer Center                                                              10 22 19
 MS072210                                                                                4 OF 10
MD ANDERSON Project No. XX-XXXX                                       MD ANDERSON PROJECT NAME
AE Name                                                                           Issue Description
AE Project No.                                                                     Month, 00, 0000

       A. Deliver to the Owner, not less than three percent of the Project total for each component,
          panel and accessory of each type, color, and finish of demountable partition system exclusive
          of material required to properly complete installation. Furnish accessory components and
          installation tools as indicated on schedule. Furnish extra materials from same production run
          as materials installed. Package extra materials with protective covering, identified with
          appropriate labels.

1.08   SEQUENCING AND SCHEDULING

       A. Sequence demountable partition installation with other Work to minimize possibility of damage
          and soiling during remainder of construction period.

[IF ANY ALTERNATES, ALLOWANCES OR UNIT PRICES APPLY, ADD HERE.]
1.09   WARRANTY

       A. Special Product Warranty: Submit a written warranty, executed by Manufacturer, agreeing to
          repair or replace demountable partition units which fail in materials or workmanship within the
          specified warranty period. Failures include, but are not limited to structural failures, faulty
          operation, and deterioration of materials beyond normal wear. This warranty shall be in
          addition to, and not a limitation of, other rights the Owner may have against the Contractor
          under the Contract Documents.

[BELOW IS AN EXAMPLE ONLY; REVISE WARRANTY PERIOD AS REQUIRED AFTER VERIFYING
AVAILABLE FROM WARRANTORS.]
           1. Warranty period is three years after the date of Substantial Completion.


PART 2 - PRODUCTS

2.01   GENERAL

       A. All materials shall meet or exceed all applicable referenced standards, federal, state and local
          requirements, and conform to codes and ordinances of authorities having jurisdiction.

2.02   MANUFACTURERS

       A. Subject to compliance with requirements, manufacturers offering products which may be
          incorporated into the Work include, but are not limited to, the following:

[REVISE MANUFACTURERS LISTING TO SUIT AVAILABLE PRODUCTS.]
           1. Donn Corporation

           2. Gold Bond Building Products

           3. Knoll International

           4. KI

           5. Haworth

           6. Steelcase


 The University of Texas                                                 DEMOUNTABLE PARTITIONS
 MD Anderson Cancer Center                                                              10 22 19
 MS072210                                                                                5 OF 10
MD ANDERSON Project No. XX-XXXX                                        MD ANDERSON PROJECT NAME
AE Name                                                                            Issue Description
AE Project No.                                                                      Month, 00, 0000

            7. DIRTT Environmental Solutions

            8. Teknion Corp.

[REVISE TO SUIT PROJECT REQUIREMENTS OR PROPRIETARY SYSTEMS.]

[SELECT ONE OR MORE OF THE FOLLOWING TO SUIT PARTITION TYPE REQUIRED. IF MORE THAN ONE
TYPE, IDENTIFY EACH SEPARATE TYPE WITH CONSISTENT DESIGNATION IN TEXT AND ON DRAWINGS.]
2.03   STRUCTURAL PANEL SYSTEMS

       A. Ceiling Trim: Minimum 18 gage steel interchangeable trim, adjustable to variations in ceiling
          level and able to be installed independently from each side of the partition to permit
          continuous wiring.

       B. Base Trim: Minimum 18 gage steel interchangeable trim, adjustable to variations in floor level
          and able to be installed independently from each side of the partition to permit continuous
          wiring.

       C. Interchangeable Partition Panel: Minimum 20 gage stretcher leveled quality steel with internal
          horizontal reinforcements welded to back of face panel, factory assembled into complete
          panel units. Internal insulation and gasketed joint conditions as required to achieve specified
          acoustical ratings.

[SELECT ONE OR REVISE.]
            1. Panel Thickness: 2-1/4 inches.

            2. Panel Thickness: 3 inches.

[SELECT ONE OF THREE OPTIONS BELOW, OR REVISE TO SUIT PROJECT REQUIREMENTS.]
       D. Panel Surface: Painted finish with base coat etched phosphate rust resistant coating, second
          coat rust inhibiting primer, final coat alkyd urea enamel. Three step finish oven baked.

       E. Panel Surface: Woven Class A fire rated fabric, factory applied over standard painted panel.

       F. Panel Surface: Owner's Class A fire rated fabric, factory applied over standard painted panel.

       G. Door Frames: Minimum 18 gage cold rolled welded steel non handed and interchangeable
          frames, mortised to receive two pair 4-1/2 inch by 4-1/2 inch butt hinges and ANSI Standard A
          115.1 strike. Provide thickness of door frames compatible with specified panel thickness.

[SELECT ONE OF THREE OPTIONS BELOW OR REVISE TO SUIT PROJECT REQUIREMENTS.]
       H. Doors: Flush 20 gage steel door, 1-3/4 inch thick, height as specified and shown on drawings;
          3/32 inch clearance at jambs and head.

       I.   Doors: Flush 20 gage steel door with glass vision panel, 1-3/4 inch thick, height as indicated;
            3/32 inch clearance at head and jambs. Thickness and size of glass vision panel to be as
            indicated.

       J.   Doors: 1-3/4 inch solid core wood door, dimensions, veneer, and finish as indicated.


 The University of Texas                                                  DEMOUNTABLE PARTITIONS
 MD Anderson Cancer Center                                                               10 22 19
 MS072210                                                                                 6 OF 10
MD ANDERSON Project No. XX-XXXX                                        MD ANDERSON PROJECT NAME
AE Name                                                                            Issue Description
AE Project No.                                                                      Month, 00, 0000

       K. Horizontal Top and Bottom Seal: Continuous PVC.

       L. Vertical Partition Post Seal: Continuous extruded vinyl.

[DELETE IF NO GLASS PANELS OR PARTIAL PANELS. SELECT FROM 4 OPTIONS BELOW, OR REVISE TO
SUIT PROJECT REQUIREMENTS. COORDINATE GLASS TYPE WITH CODE REQUIRED LOCATIONS FOR
SAFETY GLAZING.]
       M. Glass: Provide 1/8 inch double strength glass units where indicated.

       N. Glass: Provide 1/4 inch clear float glass units where indicated.

       O. Glass: Provide 1/4 inch tinted float glass units where indicated.

       P. Glass: Provide 1/4 inch laminated glass units where indicated.

2.04   NON STRUCTURAL PANEL SYSTEMS

[SELECT ONE OF 3 OPTIONS BELOW. OR REVISE TO SUIT PROJECT REQUIREMENTS.]
       A. Studs: 2-1/2 inch minimum 25 gage steel prepunched studs.

       B. Studs: 2-1/2 inch minimum 20 gage steel prepunched studs.

       C. Studs: 5 inch minimum 20 gage steel prepunched studs.

[INCLUDE WITH ABOVE IF REQUIRED.]
       D. Provide stud extenders of like material to allow for floor or ceiling height variation of up to 2
          inches.

       E. Ceiling Runner: Steel channel, gage and thickness to match stud.

       F. Floor Track: Steel channel, gage and thickness to match stud.

       G. Reinforcing Channel: Minimum 25 gage steel channel.

[SELECT ONE OF EIGHT OPTIONS BELOW OR REVISE TO SUIT PROJECT REQUIREMENTS.]
       H. Panel Board: 1/2 inch gypsum board.

       I.   Panel Board: 5/8 inch gypsum board.

       J.   Panel Board: 1/2 inch vinyl covered gypsum board.

       K. Panel Board: 5/8 inch vinyl covered gypsum board.

       L. Panel Board: 1/2 inch fabric covered gypsum board.

       M. Panel Board: 5/8 inch fabric covered gypsum board.

       N. Panel Board: 1/2 inch gypsum board with .020 inch steel cladding, with the following finish:

       O. Panel Board: 5/8 inch gypsum board with 0.020 inches steel cladding, with the following finish:



 The University of Texas                                                     DEMOUNTABLE PARTITIONS
 MD Anderson Cancer Center                                                                  10 22 19
 MS072210                                                                                    7 OF 10
MD ANDERSON Project No. XX-XXXX                                        MD ANDERSON PROJECT NAME
AE Name                                                                            Issue Description
AE Project No.                                                                      Month, 00, 0000

[INCLUDE WITH STEEL CLAD PANELS, ONE OF THE 6 FOLLOWING FINISHES OR REVISE TO SUIT
PROJECT REQUIREMENTS.]
           1. Baked on polyester enamel paint

           2. Vinyl

           3. Porcelain

           4. Porcelain chalkboard

           5. Powder paint

           6. Stainless steel

[SELECT ONE OF 2 OPTIONS BELOW. REVISE AS REQUIRED TO SUIT PROJECT REQUIREMENTS.]
       P. Door Frames: Flush aluminum frame, height as indicated, width to match panel system
          dimension, mortised for two pair of 4-1/2 inch X 4-1/2 inch butt hinges and ANSI standard A
          115.1 strike. Provide non handed and interchangeable frame.

       Q. Door Frames: Throated 19 gage steel frames, height as indicated, width to match panel
          system dimension. Provide frame mortised for two pair of 4-1/2 inch X 4-1/2 inch butt hinges
          and ANSI standard A 115.1 strike. Provide non handed and interchangeable frames.

[BELOW IS MOST COMMON DOOR TYPE. INSERT OTHER TYPES AS REQUIRED. OMIT IF WOOD DOOR IS A
PART OF THE DOORS SPECIFIED IN DIVISION 08.]
       R. Doors: 1-3/4 inch solid core wood door; dimensions, veneer, and finish as indicated.

       S. Light and Acoustical Seals: Continuous PVC.

       T. Glass: Provide glass units where indicated.

[A FEW POSSIBILITIES ARE LISTED BELOW. SELECT ONE OR REVISE TO SUIT PROJECT REQUIREMENTS.
COORDINATE GLASS TYPE WITH CODE REQUIRED LOCATIONS FOR SAFETY GLAZING.]
       U. Glass: Provide 1/8 inch double strength glass units where indicated.

       V. Glass: Provide 1/4 inch clear float glass units where indicated.

       W. Glass: Provide 1/4 inch tinted float glass units where indicated.

       X. Glass: Provide 1/4 inch laminated glass units where indicated.

       Y. Glazing Frame: Materials, details and dimensions to match door frames, snap on exterior trim
          to allow for re-glazing.

       Z. Base: Snap on PVC base, color to match wall trim components.

       AA. Trim: Snap on aluminum.

2.05   FINISHES

[SELECT FROM 6 FINISH OPTIONS BELOW, OR REVISE TO SUIT PROJECT REQUIREMENTS.]


 The University of Texas                                                     DEMOUNTABLE PARTITIONS
 MD Anderson Cancer Center                                                                  10 22 19
 MS072210                                                                                    8 OF 10
MD ANDERSON Project No. XX-XXXX                                          MD ANDERSON PROJECT NAME
AE Name                                                                              Issue Description
AE Project No.                                                                        Month, 00, 0000

       A. Primed to receive field finish.

       B. Painted: standard color selected by the Architect.

       C. Painted: custom color selected by the Architect.

       D. Vinyl covered: standard color selected by the Architect.

       E. Vinyl covered: custom color selected by the Architect.

       F. Fabric covered: custom color selected by the Architect.


PART 3 - EXECUTION

[COORDINATE REQUIREMENTS SPECIFIED IN OTHER SECTIONS FOR CONSTRUCTION AND TOLERANCES
TO ENSURE THAT THEY ARE APPROPRIATE FOR MATERIALS SELECTED.]
3.01   PREPARATION

       A. Prior to installation of demountable partition system, clean floor to remove dust, debris, and
          loose particles.

[DELETE IF PROJECT IS NOT RENOVATION.]
       B. Illuminate areas of installation to provide an ambient light level of at least 100 foot candles
          measured in the area where partitions are to be installed.

       C. Acclimatize materials by removing from sealed protective wrappings for a period of not less
          than 48 hours prior to installation. Provide protection from damage during this period.

       D. Verify that materials are those specified before installing.

       E. Maintain temperature in the area of installation at a constant minimum of 65 degrees F with
          relative humidity less than 70 percent for a period of 48 hours prior to installation and during
          installation process.

3.02   INSTALLATION

       A. Installation shall meet or exceed all applicable federal, state and local requirements,
          referenced standards and conform to codes and ordinances of authorities having jurisdiction.

       B. All installation shall be in accordance with manufacturer’s published recommendations.

       C. Install demountable partitions and accessories after other finishing operations, including
          painting, have been completed.

       D. Do not use materials with defects which are visible in the finished Work.

       E. Install demountable partitions to comply with Drawings and final shop drawings in strict
          compliance with manufacturer's printed instructions.

       F. Install panel surfaces flat and with straight tight vertical and horizontal joints, with components
          assembled into a rigid structure, fitted to building conditions, straight and plumb with
          horizontal lines level.

 The University of Texas                                                   DEMOUNTABLE PARTITIONS
 MD Anderson Cancer Center                                                                10 22 19
 MS072210                                                                                  9 OF 10
MD ANDERSON Project No. XX-XXXX                                             MD ANDERSON PROJECT NAME
AE Name                                                                                 Issue Description
AE Project No.                                                                           Month, 00, 0000

       G. Conceal screws, nuts, and rivets. Replace damaged items with new materials.

       H. Install partitions on top of finished flooring. Where on carpeting, furnish snap on carpet
          adaptors which permit installation of partition system without damage to carpeting or other
          finished flooring.

       I.   Install partitions after finished ceiling has been installed.

[BELOW APPLIES TO STRUCTURAL PANEL SYSTEM ONLY.]
       J.   Lock panel and door frame units together by alignment clips precision fit to panel posts.
            Conceal alignment clips and posts by continuous light and sound seal. Brace each post
            condition to ceiling with a rigid post extension which permits continuous wiring distribution
            within partition.

[BELOW APPLIES TO NON STRUCTURAL PANEL SYSTEM ONLY.]
       K. Install partitions using concealed fastening devices which will not mar floor and ceiling
          surfaces. Provide through posts to ceiling or structure as shown on approved shop drawings
          and as required to assure lateral stability.

[INSERT ADDITIONAL SIMILAR PARAGRAPHS FOR OTHER SPECIAL APPLICATIONS AS REQUIRED FOR
PROJECT.]

[REVISE QUANTITIES BELOW OR DELETE REQUIREMENT IF SIZE OF PROJECT DOES NOT WARRANT THIS
ADDITIONAL WORK]
3.03   FIELD QUALITY CONTROL

       A. Testing:

            1. Upon completion of installation, test partitions to demonstrate capability and compliance
               with requirements by removing and reinstalling three wall panels and three door and
               frame units selected by the Architect.



                                         END OF SECTION 10 22 19