					REHAU PROFILA BENCH TRUNKING
INSTALLATION GUIDELINES




www.rehau.co.uk                Building Solutions
                                       Automotive
                                          Industry
PROFILA BENCH TRUNKING
CONTENTS PAGE




                1. Generalities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 03
                2. Fixing the Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 03
                       2.1 Adjacent lengths of PROFILA Bench Trunking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 03
                3. Protective Foil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 04
                4. Dividers..... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 04
                5. Main Lid .... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 04
                6. Accessory Boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 04
                7. Endcaps (Single & Twin) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 04
                8. Internal and External Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 05
                9. Flat Angles & Tee Pieces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 05
                10. Security Rivets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 05
                11. Typical Installation Layouts........................................................................................................ 06
                       11.1 Installation on Worktops and against Walls ......................................................................... 06
                       11.2 Instalation on Island Location ............................................................................................ 06
                       11.3 PODS .............................................................................................................................. 06
                       11.4 Post Columns .................................................................................................................. 06
                12. Classification ............................................................................................................................. 07
                13. Cable Capacity ........................................................................................................................... 07
REHAU BENCH TRUNKING
INSTALLATION GUIDELINES



Cabling inside this trunking must only be installed and maintained      2. Fixing the Base
by a competent person in accordance with BS7671 (UK Wiring
Regulations)                                                            Base must be fixed to worktop and back wall (if available) 25mm from
                                                                        the ends as shown below.
PROFILA Bench Trunking is a cable management system intended
for distribution of low voltage power and communication circuits on
worktops.

1. Generalities

PROFILA Bench Trunking is a cable management system based on
an asymmetric triangular shaped profile for protecting low voltage
electrical and data installations.

Due to its asymmetric design the system can be installed in two
different configurations:




                                                                        Fig 3: Fixing distances


                                                                        Fixing pints between end cuts can be done alternating along the
                                                                        grooved channels as shown below. We recommend using No. 8 round
                                                                        head screws and washers.
Fig 1: High configuration            Fig 2: Low configuration



High configuration - Default configuration for all fabricated
                     accessories, recommended in most applications

Low configuration - It requires special internal and external corners



        PROFILA Bench Trunking can be used in continuous extrusion
lengths or as individually assembled POD units.

        Internal and external corners come in high configuration as
standard. Low configuration corners must be ordered specifiying this    Fig 4: Interval distances

requirement.
                                                                                If worktop and wall are not perpendicular (90° angle), fix base
                                                                        only to worktop.
2.1. Fixing Adjacent Lengths of PROFILA Bench Trunking                      3 Protective Foil

Adjacent lengths of base must be aligned and joined together by using       PROFILA Bench Trunking profiles come with a protective tape to
3 off metallic dowel pins (Art.265921). Some pins are supplied with         prevent damage during transport and installation. This protective layer
the main profile; additional pins are available separately.                 must not be removed before completion of installation.

Insert 3 off dowel pins in one section of trunking as shown:                4 Dividers

                                                                            Dividers provide circuit segregation.
                                                                            PROFILA Bench Trunking can be further subdivided in two or three
                                                                            compartments by attaching additional PVC dividers onto the built-in
                                                                            DIN 35 rail as follows:




Fig 5: Joining adjacent lengths of bench trunking

                                                                            Fig 9: Divider options
Bring the two profiles together without leaving any gaps:
                                                                            5 Main Lid

                                                                            The main lid provides access and protection to circuits inside trunking.
                                                                            PROFILA Bench Trunking uses a common lid with the REHAU
                                                                            perimeter trunking systems COMPACT Data (140 X 50) and PROFILA
                                                                            Data (180x65). To fit, align clip features on lid and base and apply
                                                                            pressure. To remove, peel the cover away from the base.

                                                                            6 Accessory Boxes

                                                                            The accessory box allows installation of standard BS1363 electrical
Fig 6: Adjacent profile lengths                                             accessories and data outlets. It comes in single and double gang
                                                                            configuration.
To install lids, leave a 13mm (+/-2) gap ensuring that the joint line
on the base is right in the middle of the gap. Finally, place joint cover   Adjustable single socket box: Art. 202415
ensuring it overlaps lids on both sides.
                                                                            Adjustable double socket box: Art. 202425

                                                                            Adjustable socket boxes are common to all REHAU data trunking
                                                                            ranges and the internal depth can be set between 38 and 48mm
                                                                            within the PROFILA Bench Trunking range.
                                                                            Socket boxes clip directly onto the base and should be fitted prior to
                                                                            main lid as the later will overlap built-in lugs on the boxes.


Fig 7: Main lid gap                          Fig 8. Joint cover installed




                                                                            Fig 10: Bench trunking with adjustable accessory boxes
                                                                         Minimum column size using fabricated corners:
7 Endcaps (Single and Twin)

Provide side protection to circuits and accessories.




                                                                         Fig 14: Minimum column dimensions


                                                                                  Standard internal and external corners come in high configu-
Fig 11: Fixing endcaps                                                   ration as default; if low configuration is required this must be informed
                                                                         at the time of ordering.

To fit, align pegs on endcaps with receptacle features on base and       9 Flat Angle and Tee Pieces
push fit until the internal face of the endcap makes contact with the
end side of the base.                                                    These accessories are non-standard and the following information
                                                                         must be provided when ordering
                                                                         - Type of configuration: (High or low)
                                                                         - Up or down accessory
                                                                         - Left or right handed accessory

                                                                         10 Security Rivets

                                                                         Nylon push-rivets (Art. 289585) provide additional security for fixing
                                                                         endcaps and joint covers.

Fig 12: Correct fitting of single endcaps

If possible, inspect the back of the trunking making sure there are no
gaps between the endcap and the base.

8 Internal and External Corners

Corners provide change of direction horizontally at 90° angles.

                                                                         Fig 15: Security rivets
Internal and external corners are fabricated using sections of PROFILA
Bench Trunking profile cut at 45° angle and welded. The installation     To fix, drill a 3.0mm hole through the accessories and base or main
of these articles must be done in a similar way to adjacent lengths      lid to accommodate the rivet shaft. Finally, push plunger until head is
using dowel pins and joint covers as explained in section 1.2.           flush against the accessory surface.




                                                                         Fig 16: Security rivets installed
Fig 13: Fabricated corners
                                                                         For endcaps, drill holes towards the inside of the accessory (not in the
                                                                         middle) ensuring base and/or lids are engaged by rivet shaft.
                                                                                                                                                   3
                                                                            11.3 PODS

                                                                                                                    Stand alone units in 4 different
                                                                                                                    configurations:

                                                                                                                    - Single POD with 1 gang box
                                                                                                                    - Single POD with 2 gang box
                                                                                                                    - Twin POD with 2 off 1 gang
                                                                                                                      box
                                                                                                                    - Twin POD with 2 off 2 gang
                                                                            Fig 20: POD unit
                                                                                                                      box
Fig 17: Joint cover with security rivets
                                                                            POD units do not include frontplates.
For join covers, drill holes offset towards either side of the accessory
(not in the middle) ensuring base and/or lids are engaged by rivet          PODS come with one endcap loose to allow wiring and installation of
shaft                                                                       electrical accessories and also to allow drilling of the manin base to
                                                                            pass cables through.
11 Typical Installation Layouts                                             After wiring is completed and the POD is secured to the worksop, the
                                                                            endcap must be securely fitted.
PROFILA Bench Trunking base has internal grooves that can be used
as guides for drilling fixing holes.                                        11.4 Posts Columns

11.1 Installation on Worktops and Against Wall                                                                      Vertical cable management
                                                                                                                    solutions and in areas with high
In order to maximise the useful working area it is recommended                                                      density of sockets (Power and
to use PROFILA Bench Trunking on high configuration. Standard                                                       data).
internal and external corners are set for this configuration and are not
suitable if the trunking is installed in low configuration (with the lon-                                           Two default options are available:
gest side horizontally). Special corners must be ordered to suit the low
configuration.                                                                                                      - 8 sockets
                                                                                                                      (For use on top of working
                                                                                                                      surfaces)

                                                                                                                    - 24 sockets
                                                                                                                      (For use in combination with
                                                                                                                      raised access floor systems)



                                                                            Fig 21: Vertical solutions




                                                                                  Specific advice for fixing these units must be requested in
Fig 18: Recommended orientation over worktops
                                                                            advance to REHAU
11.2 Installation on Island Location

Single or Twin (back to back with twin endcap)




Fig 19: Twin configuration


4
12 Classification

According to BSEN 50085-1 (2005):

-    Non-flame propagating
-    With electrical insulating characteristics
-    With high protection outside and inside
-    Cable Trunking System (CTS) for impact 5J
-    Minimum installation and application temperature: -5°C
-    Maximum application temperature: 60°C

Other classification

- Protection against the ingress of solid objects according to
  BS EN 60592:1992 IP4X

- Total maximum current capacity of circuits inside Profila Bench
  Trunking 120A @ 230V

13 Cable Capacity

- Cross section area




Fig 22: Cross section areas



- Number of Cables

                                       POWER                                                     DATA
      Conductor                           Compartment                  Cable outside   Compartment
         CSA                Full           With socket     Bottom        diameter          Full         With socket       Top
        (mm2)           compartment            Box       compartment       (mm)        compartment          box       compartment
                            (1)                (2)           (4)                           (1)              (2)           (3)
    1.5                266                113            28            6               81            34               15
    2.5                181                77             20            7               59            25               12
    4.0                138                58             16            8               45            19               9
    6.0                108                46             12            9               36            15               6
Tab 1: Cable capacity bench trunking


This product is Design Registered.




                                                                                                                                    5
  UK & IRELAND SALES OFFICES

 London, REHAU Ltd, The Building Centre, 25 Store Street, London WC1E 7BT Slough, Units 5 J & K, Langley Business Centre, Station Road, Langley, Slough SL3 8DS Phone:
 01753 588500 Fax: 01753 588501 Manchester, Brinell Drive, Irlam, Manchester M44 5BL Phone: 0161 777 7400 Fax: 0161 777 7401 Glasgow, Phoenix House, Phoenix
 Crescent, Strathclyde Business Park, Bellshill, North Lanarkshire ML4 3NJ Phone: 01698 503700 Fax: 01698 503701 Dublin, 9 St. Johns Court, Business Park, Swords Road,
 Santry, Dublin 9 Phone: 00353 (0)1 8165020 Fax: 00353 (0)1 8165021




www.rehau.co.uk                                                                                                                                    E39.680EN/JOP/08.10

				
DOCUMENT INFO
Shared By:
Categories:
Stats:
views:115
posted:3/9/2011
language:English
pages:8