					                    Manual     201712A02
“COMPACT” AIRBLUE   Issue           02.99
MICROPROCESSOR      Replaces          --.--




Use manual




                                       1370
MICROCHILLER Compact                                                               Page: 1


                                        CONTENTS

 Section                                Topic                               Page

      1. General description                                                  2

      2. Preliminary guidelines                                               2
    2.1. User interface                                                       2

      3. Keypad                                                               4
    3.1. Access to set point and to main machine operating parameters         5
         (DIRECT parameters)
    3.2. Access to user parameters (USER parameters)                          5
    3.3. Access to manufacturer parameters (FACTORY parameters)               6
    3.4. Switching off BUZZERS                                                6
    3.5. Clearing ALARMS                                                      7
    3.6. Activating the forced defrosting CYCLE
    3.7. Enabling/disabling COOLING ON/OFF unit (summer mode)                 7
    3.8. Enabling/disabling COOLING ON/OFF unit (winter mode)                 7
    3.9. Switching off the machine (stand by mode)                            8
   3.10. Resetting counters                                                   8
   3.11. Summary of key functions                                             8

      4. List of parameters                                                   9

      5. Description of parameters                                           17
    5.0.   Password                                                          17
    5.1.   Probe settings (“/” parameters)                                   17
    5.2.   Regulator settings (“r” parameters)                               18
    5.3.   Compressor activity (“c” parameters)                              19
    5.4.   Fan activity (“F” parameters)                                     21
    5.5.   Defrosting (“d” parameters)                                       23
    5.6.   Antifreeze (“A” parameters)                                       25
    5.7.   Alarms (“P” parameters)                                           26
    5.8.   General parameters (“H” parameters)                               27

      6. Alarms and indicators                                               29
    6.1. Alarms                                                              29
    6.2. Indicators                                                          31

      7. Extra microchiller circuit boards                                   32
    7.1. Fan ON/OFF card                                                     32
    7.2. Fan speed card                                                      32
    7.3. Serial converter                                                    33




       Air Blue                Manual              Issue                Replaces
                                E 04               02.99                  --.--
MICROCHILLER Compact                                                                     Page: 2




1.    General description

The “COMPACT” AIRBLUE MICROPROCESSOR is a compact electronic control unit with
reduced dimensions created for running single-compressor heat pumps and chillers.
The “COMPACT” AIRBLUE MICROPROCESSOR can be connected by means of an optional
electronic circuit board to a computer for complete remote management, monitoring and
maintenance of the systems, through the unit’s supervision and teleservice functions.
The “COMPACT” AIRBLUE MICROPROCESSOR is equipped with memory for the SUMMER-
WINTER ON-OFF functions as well as all memorised parameters, which continues to operate
even without mains power. When the machine is switched on, this memory unit ensures that
conditions prior to switch-off are available.
The “COMPACT” AIRBLUE MICROPROCESSOR can be used in the following units:
  FREEZY           Air-condenser heat pumps and water chillers with scroll compressors
  FREEZY HP
  MU            Water-condenser heat pumps and water chillers with scroll compressors
  MU HP
  MU ST         Water-condenser heat pumps and water chillers with storage tank, pump
  MU ST HP      and scroll compressors
  MU PF         Water-condenser heat pumps and water chillers with circulation pump
  MU PF HP      and scroll compressors
  MU LC         Evaporator units and heat pumps with remote air heat exchanger option
  MU LC HP      and scroll compressors
  MU ST LC      Evaporator units and heat pumps with remote air heat exchanger option,
  MU ST LC HP   with storage tank, pump and scroll compressors
  MU PF LC      Evaporator units and heat pumps with remote air heat exchange option,
  MU PF LC HP   with circulation pump and scroll compressors

2.    Preliminary guidelines

All of the functions in the “COMPACT” AIRBLUE MICROPROCESSOR are contained in a single
unit having the dimensions of a normal thermostat.

      2.1.          User interface

The interface gives user access to machine data. The three-figure display normally shows the
temperature measured by regulation probe B1 (that is, the water temperature at evaporator
inlet). Information regarding machine status is provided by the four LEDs on the display:

         Led              Flashing light                        Fixed light
      Compr.               Compressor on            Compressor activated
      Summer                     /                  Cooling mode
      Winter                     /                  Heat pump mode
      x 100                      /                  Value x 100

An optional remote control unit can be used for rapid programming of the conditioning unit.
An internal buzzer (which can be disabled using a microswitch or parameter setting) signals
any machine operating malfunctions.



         Air Blue               Manual                Issue                   Replaces
                                 E 04                 02.99                     --.--
                                                                                                                                                                                                                                              CONDENSATE PROBE


                                                                                                                                                                                                                                                   OUTLET SENSOR                                                                                      FUN
                                                                                                                                           OUTLET SENSOR




                                                                                                                                                                                                                                                                        CHILLERS
                                                                                                                                                                                                                                                   INLET SENSOR
                                                                                                                                                                                                                                                                                                                                                      POMP
                                                                                                                                           INLET SENSOR
                                                                                                                                                                                                                                                                                                                                   RES.
                                                                                                                                                                                                                                                                                                                                                          RES.


                                                                                                                                                                                                                                                                                                                                          COMP.                    COMP.




                                                                                                                                                                         POWER SUPPLY




    Air Blue
                                                                        POWER SUPPLY
                                                                                                                                                                                                                              LOW PRESSURE

                                                                                                                                                                                                                              FLOWSWITCH


                                                                                                                                                                                                                              MULTIFUNCTION
                                                                                                                           LOW PRESSURE
                                                                                                                                                                                                                                                                                                                                                                                                  MICROCHILLER Compact




                                                                                                                           FLOWSWITCH
                                                                                                                                                                                                                              HIGH PRESSURE

                                                                                                                           MULTIFUNCTION
                                                                                                                                                                                                                              REMOTE ON/OFF




                                                                                                                                                                                                                   FAN RPM
                                                                                                                                                                                                                                                                                                                                          ALARM                          ALARM




                                                                                                                                                                                                                  REGULATOR
                                                                                                                           HIGH PRESSURE


                                                                                                                           REMOTE ON/OFF
                                                                                                                                                                                                                                                                                                                                                                                 CHILLERS
                                                                                                                                                                                                                                                                                                                                                                                  CHILLERS




 E 04
                                                                                                                                                                                                                                              CONDENSATE PROBE




Manual
                                                                                                                                                                                                                                                 OUTLET SENSOR                                                                                     POMP


                                                                                                                                                                                                                                                 INLET SENSOR                                                                                      RES.



                                                                                                                                                                                                                                                                                                                                                                 COMP.




                                                                                                                                                                                                                                                                                      TO REMOTE TERMINAL




               NOTE: All ------ (broken line) components are OPTIONAL
                                                                                                                                                                                    POWER SUPPLY
                                                                                                                                                                                                                              LOW PRESSURE

                                                                                                                                                                                                                              FLOWSWITCH


                                                                                                                                                                                                                              DEFROST END
                                                                                                                                                                                                                              PRESSURE SWITCH

                                                                                                                                                                                                                              HIGH PRESSURE
                                                                                                                                                                                                                                                                                                                                                                 ALARM
                                                                                                                                                                                                                              REMOTE ON/OFF




                                                                                                                                                                                                                    FAN
                                                                                                                                                                                                                   ON/OFF
                                                                                                                                                                                                                                                                                    TO SERIAL LINE
                                                                                                                                                                                                                                                                                                                 KEY




Issue
02.99
                                                                                                                                                                                                                                   FAN RPM
                                                                                                                                                                                                                                  REGULATOR
                                                                                                                                                                                                                                                                                                           TO PROGRAMMING
                                                                                                                                                    ANTI-FREEZE SENSOR




                                                                                                                                                                                                                                                                        HEAT PUMP
                                                                                                                                                    OUTLET SENSOR




                                                                                                                                                    INLET SENSOR                                                                                   ANTI-FREEZE SENSOR                                                                                 4-WAY VALVE

                                                                                                                                                                                                                                                   OUTLET SENSOR                                                                                     POMP
                                                                                                                                                                                                                                                                                                                            4-WAY VALVE

                                                                                                                                                                                                                                                   INLET SENSOR                                                                                       RES.
                                                                                                                                                                                                                                                                                                                            RES.




                                                                                        POWER SUPPLY
                                                                                                                                                                                                                                                                                                                                                                   COMP.
                                                                                                                                                                                                                                                                                                                                          COMP.
                                                                                                                                                                                                                                                                                                                                                                                  HEAT PUMPS




                                                                                                                                    LOW PRESSURE




                                                                                                                                                                                                   POWER SUPPLY
                                                                                                                                    FLOWSWITCH


                                                                                                                                    MULTIFUNCTION
                                                                                                                                                                                                                                                                                                                                                                                     HEAT PUMPS




                                                                                                                                    HIGH PRESSURE                                                                                  LOW PRESSURE




  --.--
                                                                                                                                                                                                                                   FLOWSWITCH
                                                                                                                                    REMOTE ON/OFF
                                                                                                                                                                                                                                   DEFROST END




Replaces
                                                                                                                                                                                                                                   PRESSURE
                                                                                                                                                                                                                                                                                                                                                                   ALARM
                                                                                                                                                                                                                                   SWITCH                                                                                                  ALARM
                                                                                                                                                                                                                                   HIGH PRESSURE




                                                                                       REMOTE EVAP./CONDENSER FAN ON/OFF
                                                                                                                                                                                                                                                                                                                                                                                                  Page: 3
MICROCHILLER Compact                                                                                              Page: 4


The following is a list of inputs and outputs with relative connectors.

           Connector                                      Description                                    Unit


     Analog inputs
     B1 - GND                  Evaporator inlet water probe (chiller mode)                                All
     B2 - GND                  Evaporator outlet water probe (antifreeze)                                 All
     B3 - GND                  Condensation probe (for regulating fan speed in chiller mode, an        FREEZY HP
                               optional feature, or for controlling the defrost cycle in the heat      MU LC HP
                               pump mode, supplied as standard equipment)
     B3 - GND                  Source heat exchanger outlet water probe                                 MU HP

     Digital inputs
     ID1   -   GND             End-defrost pressure switch                                              HP Unit
     ID2   -   GND             Flow switch                                                                All
     ID3   -   GND             High-pressure switch                                                       All
     ID4   -   GND             Low pressure switch                                                        All
     ID5   -   GND             On/off from external contact                                               All

     Analog outputs
     Y - GND                   PWM analog output (For regulating fan speed in chiller mode, an            All
                               optional feature, or switching fans on/off in heat pump mode, a
                               standard feature)

     Digital outputs
     NO    -   C   /   COMP    Compressor                                                                 All
     NO    -   C   /   RES     Antifreeze heating element                                                 All
     NO    -   C   /   PUMP    Service water pump                                                   ST and PF Units
     NO    -   C   /   VALVE   Fans ON-OFF (chiller mode)                                               FREEZY
     NO    -   C   /   VALVE   Reverse cycle valve (heat pump mode)                                     HP Unit
     NO    -   C   /   ALARM   Remote general alarm signal                                                All

     The following are found at the rear of the enclosure:
     G - G0                    Power-supply connection (24Vac)                                            All
     SERIAL                    Connection for optional serial card for interfacing with a                 All
                               centralised supervision and/or teleservice system
     KEY                       Connection of an optional card (removable hardware key) for                All
                               immediate programming of all data




3.         Keypad

The keypad is used to set machine operating parameters.




                   Air Blue                  Manual                      Issue                      Replaces
                                              E 04                       02.99                        --.--
MICROCHILLER Compact                                                                       Page: 5


The following section explains the functions of each key.

         3.1.          Procedures for access to set point and to main machine operating
                       parameters (DIRECT parameters) .




Pressing SEL for more than 5 seconds permits display of the summer and winter set point, as
well as the main machine control parameters called DIRECT parameters; the display will show
the code of the first available DIRECT parameter, that is the summer set point.
Press   or    to scroll all DIRECT parameters.
Press SEL once again to display the setting of the selected DIRECT parameter, which can be
modified using the       and    keys.
Press PRG to save the changed parameter setting and exit from the procedure. Press SEL to
return to the DIRECT parameter selection menu.
During the parameter setting phase, if no keypad operation is attempted for several seconds,
the display will start flashing. If no key is pressed for 60 seconds, the procedure will return to
the normal operating mode without saving any of the parameters that may have been
changed.

       3.2.            Procedures for access to user parameters (USER parameters).




Pressing PRG for more than 5 seconds gives access to the menu of USER parameter settings,
that is the machine’s “working” parameters. This level is protected by a code (password) to
prevent access by non-authorised persons.
Entering the password: Display shows “0”; use keys      and      to enter the password, then
press SEL for access to the USER level.
During the password entry phase, if no key is pressed on the keypad for several seconds, the
display starts flashing.
Selecting USER parameters: The display shows the first available USER parameter. Press keys
   and        to scroll all the USER parameters. Press SEL to display the setting of the selected
USER parameter, which can be modified if desired using keys         and

          Air Blue                 Manual                 Issue                 Replaces
                                    E 04                  02.99                   --.--
MICROCHILLER Compact                                                                  Page: 6


Press PRG to save changes and exit from the procedure. Press SEL to return to the USER
parameter selection menu.
During the parameter setting phase, the display will start flashing if no key is pressed for
several seconds. If no key is pressed within 60 seconds of procedure activation, the normal
operating mode is restored without saving any of the parameter settings which may have
been changed.

      3.3.          Procedure for access to manufacturer parameters (FACTORY parameters)




Pressing PRG and SEL for more than 5 seconds gives access to the FACTORY parameter
setting menu; these are the machine set-up parameters. This level is protected by a code
(password) which is different than the USER password, to allow assigned personnel only to
have access to this data.
Entering the password: The display shows “0”; use keys     and     to enter the password,
then press SEL for access to the FACTORY level.
During the password entry phase, the display will begin flashing if no key is pressed for
several seconds.
Selecting FACTORY parameters: The code of the first parameter appears on display. Press
or    to scroll all parameters.
Press SEL to display the setting of the selected FACTORY parameter, which can be changed if
desired using keys     and .
Press PRG to save changes and exit from the procedure. Press SEL to return to the FACTORY
parameter selection menu.
During the parameter setting phase, the display will start flashing if no key is pressed for
several seconds.
If no key is pressed within 60 seconds of procedure activation, the normal operating mode is
restored without saving any of the changes made to parameters.

      3.4.          Switching off the BUZZER




         Air Blue              Manual                 Issue                Replaces
                                E 04                  02.99                  --.--
MICROCHILLER Compact                                                                    Page: 7


Press the MUTE key to disable the buzzer, if previously activated.

       3.5.          Clearing ALARMS




Pressing both  and     keys simultaneously for five seconds will delete all existing alarms
from memory (manual reset), disactivating the alarm message on display as well as the alarm
relay.

       3.6.          Activating the forced defrost CYCLE




Pressing SEL and     for more than 5 seconds activates a forced defrost cycle (if temperature
values of the external heat exchanger are such to permit defrosting; that is, below the end-of-
defrosting threshold).

       3.7.          Enabling/disabling COOLING / ON-OFF unit (Summer mode)

Pressing     for more than five seconds enables or disables the Summer operation mode. It is
not possible to go directly from the Winter mode to the Summer mode. If the machine is on
the Winter mode, pressing this key will have no effect.




         Air Blue                Manual                  Issue               Replaces
                                  E 04                   02.99                 --.--
MICROCHILLER Compact                                                                               Page: 8




      3.8.           Enabling/disabling COOLING / ON-OFF unit (Winter mode)




Pressing    for more than five seconds will enable or disable the winter operation mode. It is
not possible to go directly from the Summer mode to the Winter mode. If the machine is on
the Summer mode, pressing this key will have no effect; the Summer mode must be disabled
first.

      3.9            Switching off the machine (stand by mode)

The machine is switched off when both the Summer and the Winter modes have been
disabled.

      3.10.          Resetting counters

When the compressor function hour-counter (parameter c9) is displayed, pressing                    and
allows immediate resetting. The compressor maintenance count is thus interrupted.

      3.11.          Summary of key functions

The following chart summarises the meaning of each key in the various modes.

         Key                  Machine status                     Effect of pressing key
         SEL     1. Normal (that is, when display shows   After 5” DIRECT parameters
                 water temperature at evaporator inlet)
                 2. List codes                            Display setting
                 3. Display settings                      Display code list
         PRG     1. Normal                                After 5” password for USER parameters
                 2. Code list                             Saves parameters in Eeprom and returns
                                                          to display of water temperature at
                                                          evaporator inlet
                 3. Display settings                      Saves parameters in Eeprom and returns
                                                          to display of water temperature at
                                                          evaporator inlet
                 4. Buzzer activated                      Switches off buzzer
                 1. Normal                                After 5” enables/disables Summer mode
                 2. List codes                            Scrolls parameter codes
                 3. Display settings                      Increase setting




         Air Blue                      Manual               Issue                   Replaces
                                        E 04                02.99                     --.--
MICROCHILLER Compact                                                                             Page: 9


                 1. Normal                          After 5” enables/disables Winter mode
                 2. List codes                      Scrolls parameter codes
                 3. Display settings                Decrease setting
        PRG +    1. Normal                          After 5” password FACTORY parameters
         SEL
                 1. Normal                          After 5” forces a manual defrost cycle (if
                                                    temperature conditions allow it)
      SEL +
                 1. Normal                          After 5” manual alarm reset
          +
                 2.Display hour counter             Immediate resetting of counter


4.    List of parameters

The “COMPACT AIRBLUE MICROPROCESSOR parameters have been classified into three
groups:

DIRECT (D):
directly accessible without a password
USER (U):
accessible using password
FACTORY (F):
accessible using factory-level password

WARNING: to modify the USER and FACTORY parameters, the password must be requested
from AIRBLUE. Only qualified personnel can make such modifications without risking
malfunctioning or breakage.
The warranty is immediately invalidated if these parameters are modified arbitrarily without
manufacturer authorisation.

The following list reports the parameter settings of the machine as it is supplied by the
factory, divided into its various units.
These parameters are memorised by means of a personalised hardware key, and are checked
during the machine testing phases.




         Air Blue                      Manual          Issue                      Replaces
                                        E 04           02.99                        --.--
MICROCHILLER Compact                                                                                            Page: 10


                                                  UNIT : FREEZY
          DESCRIPTION                            Type Set.             DESCRIPTION                             Type Set.


PROBE                                                        DEFROSTING
/1                                                           d1   Defrost check                                 U    1
/2                                                           d2   Time or temperature defrost                   U    1
/3   Type of condensation probe                   F     0    d3   Defrost start temperature                     U    0
/4   Min. current input setting                   F     0    d4   Defrost end temperature                       U   20
/5   Max. current input setting                   F    30    d5   Min. start defrost interval                   U   150
/6   Water probe at inlet B1                      U    0     d6   Min. defrost time                             U    0
/7   Water probe at outlet B2                     U    0     d7   Max. defrost time                             U    4
/8   Condenser probe B3                           U     0    d8   Interval between two defrost start-ups        U   30
/9                                                           d9
/A                                                           dA
/b   Digital filter                               U    4     db   Defrost antifreeze resistances                U    0
/C   Input limit                                  U    8     dc   Time lag before defrosting                    F    0
/d   Unit of meaement                             U    0     dd   Time lag after defrosting                     F    0
                                                             de

REGULATOR                                                    ANTIFREEZE/BACK-UP RESISTANCES
r1   Summer set                                   D    12    A1   Antifreeze alarm set point                    U    4
r2   Summer                                       D     2    A2   Antifreeze alarm differential                 U    4
r3   Winter set point                             D    45    A3   Antifreeze alarm by-pass time                 U    0
r4   Winter differential                          D     2    A4   Antifreeze resistance activationpoint         U    4
r5                                                           A5   Antifreeze resistance                         U    4
r6   Water temperature at B2 evaporator           D     -    A6   Back-up resistance probe                      F    4
r7                                                      -    A7   Antifreeze alarm setting limit                F    4
r8   B3 Condensation temperature                  D     -    A8   Back-up resistance heat setting               U    4
r9                                                      -    A9   Back-up resistance heat differential          U    4
rA   Min. summer set point                        U     7
rb   Max. summer set point                        U    20
rC   Min. winter set point                        U    25
rd   Max. winter set point                        U    45

COMPRESSOR                                                   ALARM
c1   Min. ON time                                 U    0     P1   Flowswitch alarm delay at pump start-up       U    20
c2   Min. OFF time                                U    6     P2   Flow switch setting alarm lag                 U     5
c3   Interval between two compressor start-ups    U    36    P3   Low pressure alarm lag                        U    60
c4                                                           P4   Buzzer activation                             U    1
c5                                                           P5   Alarm reset                                   F     0
c6   Switch-on delay                              U     0    P6
c7   Pump start-up delay                          U    10    P7   Probe low pressure alarm                      F    0
c8   Pump shut-down delay                         U     2    P8   Digital input 1 setting                       F     0
c9   Compressor hour counter                      D     -    P9   Digital input 2 setting                       F     5
cA                                                           PA   Low pressure alarm selection                  F    0
cb   Maintenance call threshold                   U    0     Pb   High temperature alarm set point              U    90
cc   Pump hour counter                            D    -     PC   High temperature at start-up alarm            U    30

FANS                                                         GENERAL
F1   Fan output                                   F     0    H1   Machine model                                 F    2
F2   Fan operating mode                           U     3    H2
F3   Min. triac voltage                           F     ?    H3
F4   Max. triac voltage threshold                 F     ?    H4
F5   Summer min. speed temperature                U    30    H5   Pump mode                                     F    1
F6   Summer max. speed temperature                U    40    H6
F7   Winter min. speed temperature                U    30    H7   Digital input ON/OFF                          U    0
F8   Winter m. speed temperature                  U    20    H8   Number of                                     U    0
F9   Summer fan switch-off temperature            U    25    H9   Keypad lock                                   U    1
FA   Winter fan switch-off temperature            U    35    HA   Serial address                                U    1
Fb   Fan acceleration time                        U    25    Hb   Remote control password                       U    0
FC   Triac pulse length                           F     2    HC   Second set of parameters                      F    0
                                                             Hd   Invert winter/summer logic                    F    0
                                                             HE   Chiller-mode inversion valve status/summer    F    2
                                                             HF   Alarm relay status in absence of alarm        F    1
                                                             HG   Software version                              F   1.2
           Air Blue                       Manual                       Issue                        Replaces
                                           E 04                        02.99                          --.--
MICROCHILLER Compact                                                                                                    Page: 11



                         UNIT : FREEZY WITH RPM REGULATOR (OPTIONAL)
             DESCRIPTION                           Type Set.              DESCRIPTION                                 Type



 PROBE                                                         DEFROSTING
  /1                                                           d1   Defrost check                                      U      0
  /2                                                           d2   Time or temperature defrost                        U      1
  /3   Type of condensation probe                     F    1   d3   Defrost start temperature                          U      0
  /4   Min. current input setting                     F    0   d4   Defrost end temperature                            U     20
  /5   Max. current input setting                     F   30   d5   Min. start defrost interval                        U     150
  /6   Water probe at inlet B1                        U    0   d6   Min. defrost time                                  U      0
  /7   Water probe at outlet B2                       U    0   d7   Max. defrost time                                  U      4
  /8   Condenser probe B3                             U    0   d8   Interval between two defrost start-                U     30
  /9                                                           d9
  /A                                                           dA
  /b   Digital filter                                 U   4    db   Defrost sntifreeze resistances                     U     0
  /C   Input limit                                    U   8    dc   Time lag before defrosting                         F     0
  /d   Unit of measurement                            U   0    dd   Time lag after defrosting                          F     0
                                                               de

REGULATOR                                                       ANTIFREEZE/BACK-UP RESISTANCES
 r1    Summer set                                     D   12   A1   Antifreeze alarm                                   U      4
 r2    Summer                                         D    2   A2   Antifreeze alarm differential                      U      4
 r3    Winter set point                               D   45   A3   Antifreeze alarm by-pass time                      U      0
 r4    Winter differential                            D    2   A4   Antifreeze resistance activation                   U      4
 r5                                                            A5   Antifreeze resistance                              U      4
 r6    Water temperature at B2 evaporator             D    -   A6   Back-up resistance probe                           F      0
 r7                                                        -   A7   Antifreeze alarm setting                           F      4
 r8    B3 condensation temperature                    D    -   A8   Back-up resistance heat setting                    U     25
 r9                                                        -   A9   Back-up resistance heat differential               U      4
 rA    Min. summer set point                          U    7
 rb    Max. summer set point                          U   20
 rC    Min. winter set                                U   25
 rd    Max. winter set                                U   45

 COMPRESSOR                                                    ALARM
 c1    Min. ON time                                   U    0   P1   Flowswitch alarm delay at pump start-up            U     20
 c2    Min. OFF time                                  U    6   P2   Flowswitch setting alarm lag                       U      5
 c3    Interval between two compressor start-ups      U   36   P3   Low pressure alarm lag                             U     60
 c4                                                            P4   Buzzer activation                                  U      1
 c5                                                            P5   Alarm reset                                        F      0
 c6    Switch-on delay                                U    0   P6
 c7    Pump start-up delay                            U   10   P7   Probe low pressure alarm                           F      0
 c8    Pump shut-down delay                           U    2   P8   Digital input 1 setting                            F      0
 c9    Compressor hour counter                        D    -   P9   Digital input 2 setting                            F      5
 cA                                                            PA   Low pressure alarm selection                       F      0
 cb    Maintenance call threshold                     U   0    Pb   High temperature alarm                             U     90
 cc    Pump hour counter                              D   -    PC   High temperature at start-up alarm                 U     30

 FANS                                                          GENERAL
 F1    Fan output                                     F    1   H1   Machine model                                      F     2
 F2    Fan operating mode                             U    3   H2
 F3    Min. triac voltage threshold                   F   35   H3
 F4    Max. triac voltage threshold                   F   93   H4
 F5    Summer min. speed temperature                  U   30   H5   Pump mode                                          F     1
 F6    Summer max. speed temperature                  U   40   H6
 F7    Winter min. speed temperature                  U   30   H7   Digital input ON/OFF                               U      0
 F8    Winter max. speed temperature                  U   20   H8   Number of                                          U      0
 F9    Summer fan switch-off temperature              U   25   H9   Keypad lock                                        U      1
 FA    Winter fan switch-off temperature              U   35   HA   Serial address                                     U      1
 Fb    Fan acceleration time                          U   25   Hb   Remote control password                            U      0
 FC    Triac pulse length                             F    2   HC   Second set of parameters                           F      0
                                                               Hd   Invert winter/summer logic                         F      0
                                                               HE   Chiller-mode inversion valve status/summer         F      2
                                                               HF   Alarm relay status in absence of alarm             F      1
                                                               HG   Software version                                   F     1.2

            Air Blue                         Manual                      Issue                             Replaces
                                              E 04                       02.99                               --.--
MICROCHILLER Compact                                                                                             Page: 12


                                              UNIT : FREEZY HP
            DESCRIPTION                            Type Set.             DESCRIPTION                             Type Set.


 PROBE                                                         DEFROSTING
  /1                                                           d1   Defrost check                                 U    1
  /2                                                           d2   Time or temperature defrost                   U    1
  /3   Type of condensation probe                   F     1    d3   Defrost start temperature                     U    0
  /4   Min. current input setting                   F     0    d4   Defrost end temperature                       U   20
  /5   Max. current input setting                   F    30    d5   Min. start defrost interval                   U   150
  /6   Water probe at inlet B1                      U     0    d6   Min. defrost time                             U    0
  /7   Water probe at outlet B2                     U    0     d7   Max. defrost time                             U    4
  /8   Condenser probe B3                           U     0    d8   Interval between two defrost start-ups        U   30
  /9                                                           d9
  /A                                                           dA
  /b   Digital filter                               U    4     db   Defrost antifreeze resistances                U    0
  /C   Input limit                                  U    8     dc   Time lag before defrosting                    F    0
  /d   Unit of measurement                          U    0     dd   Time lag after defrosting                     F    0
                                                               de

 REGULATOR                                                     ANTIFREEZE/BACK-UP RESISTANCES
 r1    Summer set                                   D    12    A1   Antifreeze alarm                              U    4
 r2    Summer differential                          D     2    A2   Antifreeze alarm differential                 U    4
 r3    Winter set point                             D    45    A3   Antifreeze alarm by-pass time                 U    0
 r4    Winter differential                          D     2    A4   Antifreeze resistance activation              U    4
 r5                                                            A5   Antifreeze resistance                         U    4
 r6    Water temperature at B2 evaporator           D     -    A6   Back-up resistance probe                      F    4
 r7                                                       -    A7   Antifreeze alarm setting limit                F    4
 r8    B3 condensation temperature                  D     -    A8   Back-up resistance heat setting               U    4
 r9                                                       -    A9   Back-up resistance heat differential          U    4
 rA    Min. summer set point                        U     7
 rb    Max. summer set point                        U    20
 rC    Min. winter set point                        U    25
 rd    Max. winter set point                        U    45

 COMPRESSOR                                                    ALARM
 c1    Min. ON time                                 U     0    P1   Flowswitch alarm delay at pump start-up       U    20
 c2    Min. OFF time                                U     6    P2   Flowswitch setting alarm lag                  U     5
 c3    Interval between two compressor start-ups    U    36    P3   Low pressure alarm lag                        U    90
 c4                                                            P4   Buzzer activation                             U     1
 c5                                                            P5   Alarm reset                                   F     0
 c6    Switch-on delay                              U    0     P6
 c7    Pump start-up delay                          U    10    P7   Probe low pressure alarm                      F     0
 c8    Pump shut-down delay                         U    2     P8   Digital input 1 setting                       F     4
 c9    Compressor hour counter                      D     -    P9   Digital input 2 setting                       F     5
 cA                                                            PA   Low pressure alarm selection                  F     0
 cb    Maintenance call threshold                   U    0     Pb   High temperature alarm                        U    90
 cc    Pump hour counter                            D    -     PC   High temperature at start-up alarm            U    30

 FANS                                                          GENERAL
 F1    Fan output                                   F     1    H1   Machine model                                 F    3
 F2    Fan operating mode                           U     2    H2
 F3    Min. triac voltage                           F     ?    H3
 F4    Max. triac voltage threshold                 F     ?    H4
 F5    Summer min. speed temperature                U    30    H5   Pump mode                                     F    1
 F6    Summer max. speed temperature                U    40    H6
 F7    Winter min. speed temperature                U    30    H7   Digital input ON/OFF                          U    0
 F8    Winter max. speed temperature                U    20    H8   Number of terminals                           U    0
 F9    Summer fan switch-off temperature            U    25    H9   Keypad lock                                   U    1
 FA    Winter fan switch-off temperature            U    35    HA   Serial address                                U    1
 Fb    Fan acceleration time                        U    25    Hb   Remote control password                       U    0
 FC    Triac pulse length                           F     0    HC   Second set of parameters                      F    0
                                                               Hd   Invert winter/summer logic                    F    0
                                                               HE   Chiller-mode inversion valve status/summer    F    0
                                                               HF   Alarm relay status in absence of alarm        F    1
                                                               HG   Software version                              F   1.2
           Air Blue                      Manual                        Issue                         Replaces
                                          E 04                         02.99                           --.--
MICROCHILLER Compact                                                                                                  Page: 13



                    UNIT : FREEZY HP WITH RPM REGULATOR (OPTIONAL)
              DESCRIPTION                             Type Set.              DESCRIPTION                              Type Set.



   PROBE                                                          DEFROSTING
   /1                                                             d1   Defrost check                                   U    1
   /2                                                             d2   Time or temperature defrost                     U    1
   /3   Type of condensation probe                     F     1    d3   Defrost start temperature                       U    0
   /4   Min. current input setting                     F     0    d4   Defrost end temperature                         U   20
   /5   Max. current input setting                     F    30    d5   Min. start defrost interval                     U   150
   /6   Water probe at inlet B1                        U     0    d6   Min. defrost time                               U    0
   /7   Water probe at outlet B2                       U     0    d7   Max. defrost time                               U    4
   /8   Condenser probe B3                             U     0    d8   Interval between two defrost start-ups          U   30
   /9                                                             d9
   /A                                                             dA
   /b   Digital filter                                 U     4    db   Defrost antifreeze resistances                  U     0
   /C   Input limit                                    U     8    dc   Time lag before defrosting                      F     0
   /d   Unit of measurement                            U     0    dd   Time lag after defrosting                       F     0
                                                                  de

   REGULATOR                                                      ANTFREEZE/BACK-UP
   r1   Summer set point                               D    12    A1   Antifreeze alarm set point                      U     4
   r2   Summer                                         D     2    A2   Antifreeze alarm differential                   U     4
   r3   Winter set point                               D    45    A3   Antifreeze alarm by-pass time                   U     0
   r4   Winter differential                            D     2    A4   Antifreeze resistance activation                U     4
   r5                                                             A5   Antifreeze resistance differential              U     4
   r6   Water temperature at B2 evaporator             D     -    A6   Back-up resistance probe                        F     4
   r7                                                        -    A7   Antifreeze alarm setting limit                  F     4
   r8   B3 condensation temperature                    D     -    A8   Back-up resistance heat setting                 U     4
   r9                                                        -    A9   Back-up resistance heat differential            U     4
   rA   Min. summer set point                          U     7
   rb   Max. summer set point                          U    20
   rC   Min winter set                                 U    25
   rd   Max. winter set                                U    45

   COMPRESSOR                                                     ALARM
   c1   Min. ON time                                   U     0    P1   Flowswitch alarm delay at pump start-up         U    20
   c2   Min. OFF time                                  U     6    P2   Flow switch setting alarm lag                   U     5
   c3   Interval between two compressor start-ups      U    36    P3   Low pressure alarm lag                          U    90
   c4                                                             P4   Buzzer activation                               U     1
   c5                                                             P5   Alarm reset                                     F     0
   c6   Switch-on delay                                U     0    P6
   c7   Pump start-up delay                            U    10    P7   Probe low pressure alarm                        F     0
   c8   Pump shut-down delay                           U     2    P8   Digital input 1 setting                         F     4
   c9   Compressor hour counter                        D     -    P9   Digital input 2 setting                         F     5
   cA                                                             PA   Low pressure alarm selection                    F     0
   cb   Maintenance call threshold                     U     0    Pb   High temperature alarm                          U    90
   cc   Pump hour counter                              D     -    PC   High pressure at start-up alarm delay           U    30

   FANS                                                           GENERAL
   F1   Fan output                                     F     1    H1   Machine model                                   F     3
   F2   Fan operating mode                             U     3    H2
   F3   Min. triac voltage threshold                   F    35    H3
   F4   Max. triac voltage threshold                   F    93    H4
   F5   Summer min. speed temperature                  U    30    H5   Pump mode                                       F     1
   F6   Summer max. speed temperature                  U    40    H6
   F7   Winter min. speed temperature                  U    30    H7   Digital input ON/OFF                            U     0
   F8   Winter max. speed temperature                  U    20    H8   Number of                                       U     0
   F9   Summer fan switch-off temperature              U    25    H9   Keypad lock                                     U     1
   FA   Winter fan switch-off temperature              U    35    HA   Serial address                                  U     1
   Fb   Fan acceleration time                          U    25    Hb   Remote control password                         U     0
   FC   Triac pulse length                             F     2    HC   Second set of parameters                        F     0
                                                                  Hd   Invert winter/summer logic                      F     0
                                                                  HE   Chiller-mode inversion valve status / summer    F     0
                                                                  HF   Alarm relay status in absence of alarm          F     1
                                                                  HG   Software version                                F    1.2
          Air Blue                           Manual                     Issue                            Replaces
                                              E 04                      02.99                              --.--
MICROCHILLER Compact                                                                                                       Page: 14


                 UNIT : MU / MU ST / MU PF / MU LC / MU ST LC / MU PF LC
           DESCRIPTION                            Type Set.               DESCRIPTION                                 Type Set.



 PROBE                                                         DEFROSTING
 /1                                                            d1   Defrost check                                      U      1
 /2                                                            d2   Time or temperature defrost                        U      1
 /3   Type of condensation probe                      F    0   d3   Defrost start temperature                          U      0
 /4   Min. current input setting                      F    0   d4   Defrost end temperature                            U     20
 /5   Max. current input setting                      F   30   d5   Min. start defrost interval                        U     150
 /6   Water probe at inlet B1                         U    0   d6   Min. defrost time                                  U      0
 /7   Water probe at outlet B2                        U    0   d7   Max. defrost time                                  U      4
 /8   Condenser probe B3                              U    0   d8   Interval between two defrost start-ups             U     30
 /9                                                            d9
 /A                                                            dA
 /b   Digital filter                                  U   4    db   Defrost antifreeze resistances                     U      0
 /C   Input limit                                     U   8    dc   Time lag before defrosting                         F      0
 /d   Unit of measurement                             U   0    dd   Time lag after defrosting                          F      0
                                                               de

 REGULATOR                                                     ANTIFREEZE/BACK-UP RESISTANCES
 r1   Summer set point                                D   12   A1   Antifreeze alarm set point                         U      4
 r2   Summer differential                             D    2   A2   Antifreeze alarm differential                      U      4
 r3   Winter set point                                D   45   A3   Antifreeze alarm by-pass time                      U      0
 r4   Winter differential                             D    2   A4   Antifreeze resistance activation                   U      4
 r5                                                            A5   Antifreeze resistance differential                 U      4
 r6   Water temperature at B2 evaporator              D    -   A6   Back-up resistance probe                           F      4
 r7                                                        -   A7   Antifreeze alarm setting limit                     F      4
 r8   B3 condensation temperature                     D    -   A8   Back-up resistance heat setting                    U      4
 r9                                                        -   A9   Back-up resistance heat differential               U      4
 rA   Min. summer set point                           U    7
 rb   Max. summer set point                           U   20
 rC   Min. winter set point                           U   25
 rd   Max. winter set point                           U   45

 COMPRESSOR                                                    ALARM
 c1   Min. ON time                                    U    0   P1   Flowswitch alarm delay at pump start-up            U      20
 c2   Min. OFF time                                   U    6   P2   Flowswitch setting alarm lag                       U       5
 c3   Interval between two compressor start-ups       U   36   P3   Low pressure alarm lag                             U      60
 c4                                                            P4   Buzzer activation                                  U       1
 c5                                                            P5   Alarm reset                                        F       0
 c6   Switch-on delay                                 U    0   P6
 c7   Pump start-up delay                             U   10   P7   Probe low pressure alarm                           F       0
 c8   Pump shut-down delay                            U    2   P8   Digital input 1 setting                            F       0
 c9   Compressor hour counter                         D    -   P9   Digital input 2 setting                            F       5
 cA                                                            PA   Low pressure alarm selection                       F       0
 cb   Maintenance call threshold                      U   0    Pb   High temperature alarm setting                     U      90
 cc   Pump hour counter                               D   -    PC   High temperature at start-up alarm delay           U      30

 FANS                                                          GENERAL
 F1   Fan output                                      F    0   H1   Machine model                                      F      4
 F2   Fan operating mode                              U    3   H2
 F3   Min. triac voltage threshold                    F    ?   H3
 F4   Max. triac voltage threshold                    F    ?   H4
 F5   Summer min. speed temperature                   U   30   H5   Pump mode                                          F      1
 F6   Summer max. speed temperature                   U   40   H6
 F7   Winter min. speed temperature                   U   30   H7   Digital input ON/OFF                               U      0
 F8   Winter max. speed temperature                   U   20   H8   Number of terminals                                U      0
 F9   Summer fan switch-off temperature               U   25   H9   Keypad lock                                        U      1
 FA   Winter fan switch-off temperature               U   35   HA   Serial address                                     U      1
 Fb   Fan acceleration time                           U   25   Hb   Remote control password                            U      0
 FC   Triac pulse length                              F    2   HC   Second set of parameters                           F      0
                                                               Hd   Invert summer/winter logic                         F      0
                                                               HE   Chiller-mode inversion valve status / summer       F      2
                                                               HF   Alarm relay status in absence of alarm             F      1
                                                               HG   Software version                                   F     1.2


           Air Blue                          Manual                      Issue                             Replaces
                                              E 04                       02.99                               --.--
MICROCHILLER Compact                                                                                            Page: 15


                                UNIT : MU HP / MU ST HP / MU PF HP
            DESCRIPTION                           Type Set.             DESCRIPTION                             Type Set.


 PROBE                                                        DEFROSTING
  /1                                                          d1   Defrost check                                 U    1
  /2                                                          d2   Time or temperature defrost                   U    1
  /3   Type of condensation probe                  F    1     d3   Defrost start temperature                     U    0
  /4   Min. current input setting                  F     0    d4   Defrost end temperature                       U   20
  /5   Max. current input setting                  F    30    d5   Min. start defrost interval                   U   150
  /6   Water probe at B1 inlet                     U    0     d6   Min. defrost time                             U    0
  /7   Water probe at B2 outlet                    U    0     d7   Max. defrost time                             U    4
  /8   Condenser probe B3                          U     0    d8   Interval between two defrost start-ups        U   30
  /9                                                          d9
  /A                                                          dA
  /b   Digital filter                              U    4     db   Defrost antifreeze resistances                U    0
  /C   Input limit                                 U    8     dc   Time lag before defrosting                    F    0
  /d   Unit of measurement                         U    0     dd   Time lag after defrosting                     F    0
                                                              de

 REGULATOR                                                    ANTIFREEZE/BACK-UP RESISTANCES
  r1   Summer set point                            D    12    A1   Antifreeze alarm set point                    U    4
  r2   Summer differential                         D     2    A2   Antifreeze alarm differential                 U    4
  r3   Winter set point                            D    45    A3   Antifreeze alarm by-pass time                 U    0
  r4   Winter differential                         D     2    A4   Antifreeze resistance activation              U    4
  r5                                                          A5   Antifreeze resistance differential            U    4
  r6   Water temperature at B2 evaporator          D     -    A6   Back-up resistance probe                      F    4
  r7                                                     -    A7   Antifreeze alarm setting limit                F    4
  r8   B3 condensation temperature                 D     -    A8   Back-up resistance heat setting               U    4
  r9                                                     -    A9   Back-up resistance heat differential          U    4
  rA   Min. summer set point                       U     7
  rb   Max. summer set point                       U    20
  rC   Min. winter set point                       U    25
  rd   Max. winter set point                       U    45

 COMPRESSOR                                                   ALARM
  c1   Min. ON time                                U     0    P1   Flowswitch alarm delay at pump start-up       U    20
  c2   Min. OFF time                               U     6    P2   Flow switch setting alarm lag                 U     5
  c3   Interval between two compressor             U    36    P3   Low pressure alarm lag                        U    90
  c4                                                          P4   Buzzer activation                             U     1
  c5                                                          P5   Alarmn reset                                  F     0
  c6   Switch-on delay                             U     0    P6
  c7   Pump start-up delay                         U    10    P7   Probe low pressure alarm                      F     0
  c8   Pump shut-down delay                        U     2    P8   Digital input 1 setting                       F     4
  c9   Compressor hour                             D     -    P9   Digital input 2 setting                       F     5
  cA                                                          PA   Low pressure alarm setting                    F     0
  cb   Maintenance call threshold                  U    0     Pb   High temperature alarm                        U    90
  cc   Pump hour                                   D    -     PC   High temperature at start up alarm            U    30

 FANS                                                         GENERAL
  F1   Fan output                                  F     1    H1   Machine model                                 F    5
  F2   Fan operating mode                          U     2    H2
  F3   Min. triac voltage                          F     ?    H3
  F4   Max. triac voltage threshold                F     ?    H4
  F5   Summer min. speed temperature               U    30    H5   Pump mode                                     F    1
  F6   Summer max. speed temperature               U    40    H6
  F7   Winter min. speed temperature               U    30    H7   Digital input ON/OFF                          U    0
  F8   Winter max. speed temperature               U    20    H8   Number of terminals                           U    0
  F9   Summer fan switch-off temperature           U    25    H9   Keypad lock                                   U    1
  FA   Winter fan switch-off temperature           U    35    HA   Serial address                                U    1
  Fb   Fan acceleration time                       U    25    Hb   Remote control password                       U    0
  FC   Triac pulse length                          F     0    HC   Second set of parameters                      F    0
                                                              Hd   Invert winter/summer logic                    F    0
                                                              HE   Chiller-mode inversion valve status/summer    F    0
                                                              HF   Alarm relay status in absence of alarm        F    1
                                                              HG   Software version                              F   1.2

           Air Blue                      Manual                      Issue                          Replaces
                                          E 04                       02.99                            --.--
MICROCHILLER Compact                                                                                                Page: 16




                           UNIT : MU LC HP / MU ST LC HP / MU PF LC HP
          DESCRIPTION                            Type Set.             DESCRIPTION                             Type Set.


PROBE                                                        DEFROSTING
/1                                                           d1   Defrost check                                 U       1
/2                                                           d2   Time or temperature defrost                   U       1
/3   Type of condensation probe                   F     1    d3   Defrost start temperature                     U       0
/4   Min. current input setting                   F    0     d4   Defrost end temperature                       U      20
/5   Max. current input setting                   F    30    d5   Min. start defrost interval                   U      150
/6   Water probe at B1 inlet                      U    0     d6   Min. defrost time                             U       0
/7   Water probe at B2 outlet                     U     0    d7   Max. defrost time                             U       4
/8   Condenser probe B3                           U     0    d8   Interval between two defrost start-ups        U      30
/9                                                           d9
/A                                                           dA
/b   Digital filter                               U    4     db   Defrost antifreeze resistances                U       0
/C   Input limit                                  U    8     dc   Time lag before defrosting                    F       0
/d   Unit of measurement                          U    0     dd   Time lag after defrosting                     F       0
                                                             de

REGULATOR                                                    ANTIFREEZE/BACK-UP RESISTANCES
r1   Summer set point                             D    12    A1   Antifreeze alarm set point                    U       4
r2   Summer differential                          D     2    A2   Antifreeze alarm differential                 U       4
r3   Winter set point                             D    45    A3   Antifreeze alarm by-pass time                 U       0
r4   Winter differential                          D     2    A4   Antifreeze resistance activation              U       4
r5                                                           A5   Antifreeze resistance differential            U       4
r6   Water temperature at B2 evaporator outlet    D     -    A6   Back-up ressitance probe                      F       4
r7                                                      -    A7   Antifreeze alarm setting limit                F       4
r8   B3 condensation temperature                  D     -    A8   Back-up resistance heat setting               U       4
r9                                                      -    A9   Back-up resistance heat differential          U       4
rA   Min. summer set point                        U     7
rb   Max. summer set point                        U    20
rC   Min. winter set point                        U    25
rd   Max. winter set point                        U    45

COMPRESSOR                                                   ALARM
c1   Min. ON time                                 U    0     P1   Flowswitch alarm delay at pump start-up       U      20
c2   Min. OFF time                                U    6     P2   Flowswitch setting alarm lag                  U       5
c3   Interval between two compressor start-ups    U    36    P3   Low pressure alarm lag                        U      60
c4                                                           P4   Buzzer activation                             U      1
c5                                                           P5   Alarm reset                                   F       0
c6   Switch-on delay                              U    0     P6
c7   Pump start-up delay                          U    10    P7   Probe low pressure alarm                      F       0
c8   Pump shut-down delay                         U     2    P8   Digital input 1 setting                       F       0
c9   Compressor hour counter                      D     -    P9   Digital input 2 setting                       F       5
cA                                                           PA   Low pressure alarm setting                    F      0
cb   Maintenance call threshold                   U    0     Pb   High temperature alarm setting                U      90
cc   Pump hour counter                            D    -     PC   High temperature at start-up alarm lag        U      30

FANS                                                         GENERAL
F1   Fan output                                   F     0    H1   Machine model                                 F       5
F2   Fan operating mode                           U     3    H2
F3   Min. triac voltage threshold                 F     ?    H3
F4   Max. triac voltage threshold                 F     ?    H4
F5   Summer min. speed temperature                U    30    H5   Pump mode                                     F       1
F6   Summer max. speed temperature                U    40    H6
F7   Winter min. speed temperature                U    30    H7   Digital input ON/OFF                          U       0
F8   Winter max. speed temperature                U    20    H8   Numero di                                     U       0
F9   Summer fan switch-off temperature            U    25    H9   Keypad lock                                   U       1
FA   Winter fan switch-off temperature            U    35    HA   Serial address                                U       1
Fb   Fan acceleration time                        U    25    Hb   Remote control password                       U       0
FC   Triac pulse length                           F     2    HC   Second set of parameters                      F       0
                                                             Hd   Invert winter/summer logic                    F       0
                                                             HE   Chiller-mode inversion valve status/summer    F       0
                                                             HF   Alarm relay status in absence of alarm        F       1
                                                             HG   Software version                              F      1.2
            Air Blue                     Manual                        Issue                        Replaces
                                          E 04                         02.99                          --.--
MICROCHILLER Compact                                                                       Page: 17




5.      Description of parameters

        5.0.         Passwords

USER:
For access to the USER type parameters, press the PRG key for 5 seconds, enter the password
USER and press the SEL key.
FACTORY:
For access to the Factory type parameters, press the PRG and SEL keys together for 5 seconds,
enter the password FACTORY and press the SEL key.

        5.1.         Probe presetting (“/” parameters)

/3:    Type of condensation probe B3
Indicates the operating mode of the analog input relative to the condenser probe which
controls defrosting and the fans. These probes may not be included at all, or they may be
NTC type probes. The software setting must correspond to adequate hardware. If the
condensation probe is absent, defrosting and the use of the condensation fans are disabled.
If NTC probes have been selected and the optional speed regulation module is present as
well, when the compressor starts up, the fans are activated for Fb time, regardless of the
temperature measured; this allows the system to ready itself for compressor activity and
improves condensation regulation.

/4:

/5:

/6:   Correction of water probe at evaporator inlet B1
Allows correction of measured B1 value.

/7:   Correction of water probe at evaporator outlet B2
Allows correction of measured B2 value.

/8:   Correction of condensation probe B3
Allows correction of measured B3 value.

/b:    Digital filter
Allows setting of the coefficient used in digital filtering of the measured value. A high value at
this parameter allows elimination of any continuous interference at the analog inputs (but
decreases quick measurement). The recommended value is 4.

/C:     Input restrictions.
Allows setting of the maximum variation which can be measured by the probes in a machine
program cycle; in practice, the maximum variation measuring tolerance is from 0.1 to 1.5
units (°C or F) every second, approximately. A low value of this parameter limits the effects of
impulse-type interference. Recommended value 8.



          Air Blue                Manual                  Issue                 Replaces
                                   E 04                   02.99                   --.--
MICROCHILLER Compact                                                                                              Page: 18


/d:     Unit of measurement
Sets the operating mode to Centigrade or Fahrenheit degrees. When this parameter is varied,
the microprocessor automatically converts all values into the new unit ofmeasurement, while
all the other parameter settings (set-point, differential, etc.) are not changed.

       5.2.   Regulator presetting ("r” parameters)

r1:   Summer set point
Allows setting of Summer - Cooling set point (direct action).

r2:   Summer differential
Allows setting of differential for Summer regulation.

                             Summer mode (direct) 1 compressor


                                 Summer set point




                                                                     Summer set point + differential




r3:   Winter set point
Allows setting of Winter - Heating set point (reverse action).

r4:   Winter differential
Allows setting of differential for Winter regulation.
                                Winter mode (reverse) 1 compressor


                                                                           Winter set point




                                  Winter set point + differential



r6:    Water temperature at B2 evaporator outlet
Displays temperature at B2 evaporator outlet.

r8:    B3 Condensation temperature
Displays temperature of condenser B3.

rA: Minimum summer set point
Establishes the lower limit for setting the Summer Set Point.
         Air Blue                  Manual                                        Issue                 Replaces
                                    E 04                                         02.99                   --.--
MICROCHILLER Compact                                                               Page: 19




rb:     Maximum summer set point
Establishes the upper limit for setting the Summer Set Point.

rC:     Minimum winter set point
Establishes the lower limit for setting the Winter Set Point.

rd:     Maximum winter set point
Establishes the upper limit for setting the Winter Set Point.

       5.3.          Compressor activity (“c” parameters)

c1:    Minimum switch-on time
Sets the minimum length of time the compressor must remain active after it has been
switched on, even if no longer required.

                       Controls




                       Compressor




                                       Minimum ON time



c2:    Minimum switch-off time
Sets the minimum amount of time the compressor must remain off after it has been switched
off, even if service is required again. During this phase, the compressor LED flashes.

                       Controls




                       Compressor




                                        Minimum OFF time



c3:     Interval between two compressor start-ups
Establishes the minimum amount of time between two consecutive compressor start-ups
(determines the maximum number of times the compressor may be switched on per hour).
The compressor LED flashes during this phase.




         Air Blue                   Manual                 Issue        Replaces
                                     E 04                  02.99          --.--
MICROCHILLER Compact                                                                              Page: 20




                    Controls




                    Compressor




                                        Minimum time between two ON’s




c6:    Switch-on delay
At switch-on (understood as control unit power supply, 24 Vac), activation of all outputs is
delayed in order to distribute mains power absorption and to protect the compressor from
repeated start-ups in the case of multiple power failures.

c7:   Compressor lag after pump start-up


                      Pump


                      Outlet fan


                      Compressor



                                        Delay between outlet fan pump and compressor



In both the summer and winter operating modes, with the pump on call (parameter H5=2), if
compressor start-up is requested, the regulator activates the water circulation pump before
activating the compressor pump. If the pump is always on (H5=1), it is only activated when
the machine is switched on (or when the summer or winter mode is selected).

c8:   Pump lag after compressor shutdown

                       Compressor




                      Pump


                      Outlet fan


                                        Delay between outlet fan pump and compressor



In both the summer and winter operating modes, with the pump on call (parameter H5=2), if
compressor shut-down is requested, the regulator disactivates the compressor before
disactivating the pump.
If the pump is always on (H5=1), it is disactivated in the stand-by mode only.




         Air Blue                   Manual                               Issue         Replaces
                                     E 04                                02.99           --.--
MICROCHILLER Compact                                                                    Page: 21


c9:    Compressor hour counter
Indicates the number of hours the compressor has been running. Pressing             and
simultaneously when the counter value is on display will reset the counter and consequently
cancel the relative maintenance request.

cb: Maintenance call threshold
Establishes after how many hours of compressor running the maintenance request is to be
signalled. The 0 setting disables this function.

cC: Pump hour counter
Displays the number of hours the service water circulation pump has been running. Pressing
keys    and     simultaneously when the counter value is on display will reset the counter.

       5.4.            Fan activity (“F” parameters)

F1: Fan output
Sets fan operating mode :
• = 0 fans absent
• = 1 fans present
This selection requires installation of the optional fan control boards (On/Off or speed
variation).

F2: Fan operating mode
Sets fan operating mode:
• = 0 always activated, regardless of compressor status (unless the machine is on stand-by)
• = 1 on when the compressor is active (parallel operation)
• = 2 on when the compressor is active, with On/Off regulation dependent on the minimum
   and maximum speed temperatures (parameters F5, F6, F7 e F8). When the compressor
   shuts down, the relative fans are disactivated regardless of condensation temperature.
• = 3 on when the compressor is active, with speed regulation. When the compressor shuts
   down, the relative fans are disactivated regardless of condensation temperature.

Example 1:    F2 = 1


                           Compressor




                           Fan




Example 2:    F2 = 2




         Air Blue                       Manual          Issue                Replaces
                                         E 04           02.99                  --.--
MICROCHILLER Compact                                                                                                                                                                                                   Page: 22


Fan ON/OFF regulation in summer mode                                 Compressor ON                                 Fan ON/OFF regulation in winter mode                                    Compressor ON




                                                                                  Condensation temperature
                                                                                                                                                                                                   Condensation temperature
                                                                                                                   Fan activity

Fan activity

                 Minimum speed temperature                          Maximum speed temperature                                       Maximum speed temperature in                    Minimum speed temperature in
                 in summer mode                                     in summer mode                                                  winter mode                                     winter mode
Example 3:                             F2 = 3
       Fan regulation in summer mode                                        Compressor ON                       Fan regulation in winter mode                                          Compressor ON


                                       Minimum speed temperature in summer mode                                                                 Minimum speed temperature in winter mode




                                                                                                                    Max. speed

Max. speed                                                                           Condensation temperature                                                                                             Condensation temperature

                                                                                                                    Min. speed
Min. speed



                                                                                                                                  Maximum speed temperature in winter mode             Cutoff temperature in winter mode
             Cutoff temperature in summer mode                       Maximum speed temperature in summer mode




In this situation, at compressor switch-on, the fans start up at maximum speed for the Fb time
span, regardless of the temperature measured.

F3: Minimum voltage threshold for Triac
In order to regulate fan speed, an optional phase-cutting board (equipped with triac) must be
installed. In this case, it is necessary to specify the voltage delivered by the triac to the electric
fan motor corresponding to minimum speed. The set value does not correspond to the
effective applied voltage in Volts, but to a unit of calculation internal to the microprocessor.
See the paragraph on “fan speed regulation” for calculation of F3. If using an ON/OFF circuit
board, it is best to set this parameter to zero (FC = 0).

F4: Maximum voltage threshold for Triac
In order to regulate fan speed, an optional phase-cutting board (equipped with triac) must be
installed. In this case, it is necessary to specify the voltage delivered by the triac to the electric
fan motor corresponding to maximum speed. The set value does not correspond to the
effective applied voltage in Volts, but to a unit of calculation internal to the microprocessor.
See the paragraph on “fan speed regulation” for calculation of F3. If using an ON/OFF circuit
board, it is best to set this parameter to zero (FC = 0).

F5: Summer-mode minimum speed temperature (chilling)
Sets the temperature below which the fans continue running at minimum speed. In the case
of On/off regulation, this setting represents the temperature below which the fans are shut
down during the summer.

F6: Summer-mode maximum speed temperature (chilling)
Sets the temperature above which the fans continue running at maximum speed. In the case
of On/off regulation, this setting represents the temperature above which the fans remain on.

F7: Winter-mode minimum speed temperature (heating)
Sets the temperature above which the fans continue running at minimum speed. In the case
of On/off regulation, this setting represents the temperature below which the fans remain
off.

                        Air Blue                                                     Manual                                          Issue                                                  Replaces
                                                                                      E 04                                           02.99                                                    --.--
MICROCHILLER Compact                                                                       Page: 23


F8: Winter-mode maximum speed temperature (heating)
Sets the temperature below which the fans must continue running at maximum speed. In the
case of On/off regulation, this setting represents the temperature below which the fans
remain on.

F9: Summer-mode fan switch-off temperature (chilling)
If a speed regulator is being used, this setting represents the temperature below which the
fans remain off.
The fans are switched on 1°C above the switch-off setting, if NTC temperature probes for
condensation control (B3) are being used.

FA: Winter-mode fan switch-off temperature (heating)
If a fan speed regulator is being used, this setting represents the temperature above which
the fans remain off.
The fans are switched on 1°C below the switch-off setting, if NTC temperature probes for
condensation control (B3) are being used.

Fb: Fan acceleration time
Sets the length of time at which the fans must be kept running at maximum speed in order to
overcome the mechanical inertia of the motor. If set at 0, this function is disabled, that is, the
fans are activated at minimum speed and then regulated on the basis of condensation
temperature. The same timing is applied when the compressor is switched on as well (regardless
of condenser temperature), if NTC condensation-control probes have been selected and if speed
regulation has been enabled (F2=3). This serves to safeguard against the effects of a sudden
increase in pressure (which may not necessarily correspond to an equal rise in temperature in the
area where the probe is located) as well as to improve regulation.

Fc:    Triac pulse length
Sets the duration in milliseconds of the pulse applied to the triac. For inductive motors, set
the parameter to 2 (default), for capacitive motors, set the parameter to 0.

       5.5.          Defrosting (“d” parameters)

d1: Defrost check
For units FREEZY HP / MU LC HP / MU ST LC HP / MU PF LC HP establishes whether a
defrosting check should be done on the external heat exchanger (evaporator in winter mode).
For units MU HP / MU ST HP / MU PF HP enables defrost checking of the chilling water in the
external heat exchanger (evaporator in winter mode).

d2: Time or temperature defrost
Establishes whether defrosting should be done on the basis of time (fixed defrosting interval)
or of temperature (defrosting ends as soon as the condensation probe reaches the end
threshold, or if it detects the end-defrost contact open if P8 or P9 are set to 4).




         Air Blue                Manual                   Issue                 Replaces
                                  E 04                    02.99                   --.--
MICROCHILLER Compact                                                                                   Page: 24


d3: Defrost start temperature
For units FREEZY HP / MU LC HP / MU ST LC HP / MU PF LC HP, sets the temperature below
which a defrosting cycle will be begun. To start up the defrost cycle, the condition must
persist for d5 time. For units MU HP / MU ST HP / MU PF HP this setting defines the point of
intervention for the antifreeze alarm for the external heat exchanger chilling water
(evaporator in winter mode, on probe B3).
d4: Defrost end temperature
Sets the temperature above which the defrost cycle will end.
In units FREEZY HP / MU LC HP / MU ST LC HP / MU PF LC HP this parameter is not used.

d5: Minimum start-defrost interval
Sets the amount of time that temperature can remain below the d3 start-defrost cycle
threshold, as long as the compressor is switched on as well, before a defrost cycle is
activated.
                    Temperature defrost (d2=1)
                    Defrost a temperatura (d2=1)

                                                                                    Fine defrost
                                                                                    Stop defrost
              T   fine defrost (d4)
                    stop defrost                               Start defrost
                                                               Inizio defrost




       defrost start temperature (d3)
           inizio defrost (d3)
                                              Minimum start-defrost interval (d5)
                                              Tempo minimo inizio defrost (d5)
                                        Counter reset
                                        Reset conteggio          Minimum defrost time (d6)
                                                                 Tempo minimo defrost (d6)


d6: Minimum defrosting time
This setting represents the minimum length of the defrost cycle (defrosting will continue even
if the condensation probe exceeds the end-cycle temperature). If set to 0, the minimum
defrost time parameter is disabled.

d7: Maximum defrosting time
If a timed defrost cycle is enabled (d2=0), this parameter sets the length of this timed cycle. If
the defrosting cycle is set to end on a temperature basis or on the basis of an external
contact, this setting represents the maximum length of a defrosting cycle (alarm indicator
“r1” will be activated if this protection is tripped off).

d8: Interval between two defrost start-ups
This setting represents the minimum lag between two consecutive defrosting cycles.

db: Antifreeze resistances in defrost cycle
This parameter establishes whether, during defrosting, the antifreeze/back-up resistances
must be activated to limit the flow of cold water in the environment. The significance of the
parameter is as follows:



         Air Blue                       Manual                   Issue                      Replaces
                                         E 04                    02.99                        --.--
MICROCHILLER Compact                                                                       Page: 25



          db                                       Selection
           0      antifreeze/back up resistances NOT active during defrosting
           1      antifreeze/back-up resistances activated during defrosting

dc: Time lag before defrosting
When conditions are such that defrosting is enabled, before the cycle is actually activated, the
machine stops the compressor for a given amount of time: dc (set from 0 to 3 minutes).
Shutdown of the compressor enables rotation of the 4-way valves, after an amount of time
defined as dc/2; this lag permits the pressure to be equalised before the defrosting cycle
begins. Using this procedure, the protective compressor timing sequence is not applied,
leading to immediate shut-down of the compressor, as well as relative restarting. If dc=0, the
compressor is not shut down and the cycle inversion valve is rotated immediately.

dd: Time lag after defrosting
At the end of the defrosting cycle, the machine stops the compressor for a given amount of
time: dd (set from 0 to 3 minutes). Shut down of the compressor enables rotation of the 4-
way valves, after an amount of time defined as dd/2; this lag permits pressure to be equalised
and allows any water to drip off the external coil. Using this procedure, the protective
compressor timing sequence is not applied, leading to immediate shut-down of the
compressor, as well as relative restarting. If dd = 0, the compressor is not shut down and the
cycle inversion valve is rotated immediately.

       5.6.           Antifreeze (“A” parameters)

A1: Antifreeze alarm set point
This setting represents the water temperature at evaporator outlet below which the
machine’s antifreeze alarm is set off. The alarm condition shuts down the compressor while
the pump remains active. Resetting is manual, and can only take place when the water
temperature rises within the operating limits (that is, when it exceeds value A1+A2).

A2: Antifreeze alarm differential
Sets the antifreeze alarm differential; the alarm condition cannot be cancelled until the
temperature rises above the set point value + differential (A1+A2).

A3: Antifreeze alarm by-pass time for machine switch-on in winter mode
If the machine is in an antifreeze alarm condition, this setting allows the machine to be
switched on again for the set time (only when running on the winter mode, since the
machine will heat the water). If the alarm persists after this time has expired, the machine
shuts down again.

A4: Antifreeze resistance activation set point
Sets the threshold below which the antifreeze resistances are switched on. The antifreeze
resistance switch-on function is active even when the machine is on stand-by.

A5: Antifreeze resistance differential
Differential for activating and disactivating the antifreeze resistances.




         Air Blue                 Manual                   Issue                Replaces
                                   E 04                    02.99                  --.--
MICROCHILLER Compact                                                                                                                                            Page: 26


                                     Antifreeze alarm differential (A2)                 Antifreeze resistance differential (A2)




                                                                                                                                  Resistances




                                                                                                                                  Antifreeze alarm




                      Antifreeze alarm setting (A1)                       Antifreeze resistance setting (A1)




A6: Back-up resistance probe
Determines which probe is to be used (B1 or B2) to check the back-up resistances. If A6=0,
the selected probe is B1, while of A6=1, the selected probe is B2.

A7: Antifreeze alarm setting limit
Determines the minimum limit which can be used for setting the antifreeze alarm (A1).

A8: Back-up resistance heating setting
Sets the threshold below which the back-up resistances are switched on. This function is
active for the HP versions only.

A9: Back-up resistance heating differential
Differential for activating and disactivating the back-up resistances (see A8).

       5.7.          Alarms (“P” parameters)

P1: Flowswitch alarm delay at pump start-up
Sets delay in tripping flow switch alarm when the pump is started up (this allows flow rate to
rise to correct level; P9 must be = 5).

P2: Flowswitch setting alarm lag
Sets delay in tripping flowswitch alarm while running, in order to filter any variations in flow
rate or air bubbles in the water circuit.

P3: Low-pressure alarm lag at compressor start-up
Sets delay in tripping a low-pressure alarm when the compressor starts up, to allow the
compressor to reach a steady state of operation. This delay is also applied when the 4-way
valve is inverted in the gas circuit.

P4: Buzzer activation
Indicates the length of buzzer sounding in case of an alarm:
• if set to 0, the buzzer is always disabled;
• with a setting from 1 to 14, the buzzer is automatically switched off after this amount of
   time, in minutes
• if set to 15, the buzzer continues to sound for as long as the alarm which generated it
   persists.

P5: Alarm reset
Enables automatic reset of all alarms which are normally reset manually (high pressure, low
pressure, flowswitch and antifreeze) according to the following chart:
         Air Blue                                       Manual                           Issue                                                       Replaces
                                                         E 04                            02.99                                                         --.--
MICROCHILLER Compact                                                                                       Page: 27


      P5 setting              manual reset alarms                           automatic reset alarms
      0 (default)   High pressure, low pressure, flowswitch and                           /
                    antifreeze
          1                               /                       All alarms
          2         High pressure, antifreeze                     Low pressure
          3         High pressure                                 Low pressure, antifreeze
          4         High, low pressure                            Antifreeze

P7:      /
P8:      ID1 digital input setting
P9:      ID2 digital input setting

Assigns the device connected to digital input ID1

       Setting              Function of connected device                       Air Blue selection
       P8 / P9
                                                                             ID 1               ID 2
          0         No device connected                                X (disable P8=4)       Not usable
          1         Flowswitch with manual reset                          Not usable          Not usable
          2         Thermal switch with manual reset                      Not usable          Not usable
          3         Remote summer/winter selection (*)                    Not usable          Not usable
          4         End defrost with pressure switch                   X (disable P8=0)       Not usable
          5         Flowswitch with automatic reset                       Not usable              X
          6         Thermal switch with manual reset                      Not usable          Not usable

         (*) =      With contact open, the machine is on summer mode, while with contact closed it is on
                    winter mode (this is Hd =0, otherwise the logic is inverted).



ATTENTION: Do not assign the same value to P8 and P9.

PA: Low pressure alarm selection
Enables selection of whether a low pressure condition should be detected even when the
compressor is off (PA=1) or only when the compressor is active (PA=0 default).
In any case, when the compressor starts up, the alarm remains disactivated for time P3.

Pb:      High temperature alarm setting
This setting represents the high temperature alarm threshold (detected by probe B1); the differential is
fixed at 2°, and resetting is automatic (the indicator-only alarm relay is activated and “Ht” appears on
display). When the regulator is switched on, this alarm is inhibited for time “PC”.
PC:      High temperature at start-up alarm delay
This sets the lag in the high temperature alarm both when the power is switched on as well as when a
remote ON/OFF keypad command is given.

         5.8.             General parameters (“H” parameters)

H1: Machine model
Permits selection of the type of machine to be monitored:
      H1 setting                                         Type of machine
          2         FREEZY
          3         FREEZY HP / MU LC HP / MU ST LC HP / MU PF LC HP
          4         MU / MU ST / MU PF / MU LC / MU ST LC / MU PF LC
          5         MU HP / MU ST HP / MU PF HP

              Air Blue                  Manual                      Issue                     Replaces
                                         E 04                       02.99                       --.--
MICROCHILLER Compact                                                                       Page: 28




H5: Pump mode
Sets the operating mode of the water circulation pump. The pump may be disabled (H5=0),
always on (H5=1) or switched on at regulator command (H5=2) when heating or cooling is
required; the pump starts up first, followed by the compressor.
When the pump is disabled, the flowswitch alarm is disabled as well.
H7: Digital input ON/OFF
Enables or disables On/off selection from a digital input. If the setting is enabled (H7=1)
“open” status forces the machine to switch off, while with “closed” status the machine can
be switched on or off from the keypad.

H8: Number of terminals
Establishes the number of terminals connected to the machine. If H8=0, there is no remote
terminal, while if H8=1, the remote terminal is connected.

H9: Direct parameter modification lock
Allows modification of DIRECT and USER parameters from the keypad or remote control unit
to be disabled. The parameter settings can be called up on display in any case. The
enable/disable summer mode, enable/disable winter mode, forced defrosting and counter
reset functions are all disabled as well.
The enabled/disabled status setting option is as follows:

          Setting             Remote control                        Keypad
              0                  enabled                            disabled
         1 (default)             enabled                            enabled
              2                  disabled                           disabled
              3                  disabled                           enabled

HA: Serial address
Establishes the address for serial connection, by means of an optional circuit board, to a
computer for supervision and/or teleservice.

Hb: Remote control password
Establishes the address for transmission of remote control data. If several instruments are
positioned within the radius of action of the remote control unit, it is possible to send the
parameter modifications simultaneously to all the instruments or to only one in particular. If
the password setting is 00, connection is immediate; any number other than zero means that
the customer must type in this number after the START key on the remote control keypad as
an access code whenever he is using the remote control unit.

HC: Second set of parameters
If Hc=1, this enables activation of a second set of DIRECT, USER and FACTORY parameters; in this
situation, the following parameters shift from level U (as indicated in the parameter chart in the
following manual) to level F; in other words, the level accessible with the manufacturer password:




         Air Blue                Manual                   Issue                 Replaces
                                  E 04                    02.99                   --.--
MICROCHILLER Compact                                                                          Page: 29


         Parameter
           types                  FROM                                  TO
            “/”                      /6                            /C (included)
            “r”                      RA                            rd (included)
            “c”                      c1                            c3 (included)
            “F”                      All                                  /
            “d”                      All                                  /
            “A”                      All                                  /
            “P”                All except P4                              /
            “H”                       /                                   /

Hd: Invert summer/winter logic
When this parameter is set to 1, the summer/winter selection operating logic is inverted.
HE: Chiller-mode inversion valve status (summer)
Defines the status of the cycle inversion valve output in the heat pumps. For cold-only
machines, this output can be set for use as an ON/OFF control for the condenser fans:
• = 0 relay de-energised in chiller mode (in HP units);
• = 1 relay energised in chiller mode (in HP units);
• = 2 fan On/off output (cold-only unit).

HF: Alarm relay status in absence of alarm
Defines relay status in the absence of alarm conditions:
• = 0 relay de-energised in absence of alarm
• = 1 relay energised in absence of alarm.

HG: Software version
Indicates software release

6.     Alarms and indicators

        6.1.         Alarms

The following procedure results from an alarm tripping off:
• the buzzer sounds (if enabled, see parameter P4, and if the machine is not on stand-by);
• the alarm relay is activated;
• the temperature display starts flashing;
• the alarm code is shown on display, alternated with the temperature reading.

When the alarm is acknowledged by means of a manual reset or by simultaneously pressing
keys     and    for 5 seconds to clear (for manual-reset alarms), the following occurs:
• the buzzer turns off;
• the alarm relay is disactivated;
• the temperature display stops flashing;
• the alarm code is no longer shown on display.
If alarm conditions persist, the alarm procedure described above will repeat itself.




         Air Blue                Manual                    Issue                   Replaces
                                  E 04                     02.99                     --.--
MICROCHILLER Compact                                                                    Page: 30


   Display                     Type                   State of   Delay          Reset
    Code                                               alarm
     H1         High pressure or compressor thermal   ID3 open      /          Manual
                   switch and/or pump and/or fan
      L1                    Low pressure              ID4 open     P3         Automatic
      FL                     Flowswitch               ID2 open   P1 / P2      Automatic
     A1                       Antifreeze                 B2         /          Manual
    E1/2/3                   Probe 1/2/3                  /         /         Automatic
    EE/EP                   Eeprom error                  /         /         Automatic
      EL                  Line interference               /         /         Automatic
     EU              High voltage power supply            /         /         Automatic
     EO              Low voltage power supply             /         /         Automatic
      n1             Compressor maintenance               /         /          Manual
      d1                     Defrosting                   /         /         Automatic
      r1                  Defrosting error                /         /      Automatic/Manual
     Cn                 Communication error               /         /         Automatic

H1: High pressure (and/or compressor thermal cutout, pump, fan)
Immediately shuts down the compressor (without following the protection timing procedure).

L1: Low pressure
The alarm may be detected with the compressor on or off (depending on PA), regardless of
pump status. Results in immediate shutdown (without following the protection timing
procedure) of the compressor, or failure to start up the compressor if not already on.

t1:    Compressor thermal switch
Not system controlled.

FL:    Flowswitch
The alarm state is detected only if the pump is on, regardless of the compressor status. All
outlets are disabled: pump, compressor (without following the protection timing procedure),
condensation fan.
The water chiller control (H1≠0, 1) and the service water pump (H5≠0) must be enabled.

A1
LO: Antifreeze
The alarm state is detected in the water chillers only (H1=2, 3, 4, 5 or 6) by means of the
evaporator outlet water-temperature probe (B2). The compressor and the condensation fan
are immediately shut down.
If the microprocessor is on standby, the alarm condition is not detected; the system only
controls the resistances.

Other alarms

E1
E2
E3: Probe alarm
Detected even when the machine is on standby.
A probe alarm leads to disactivation of the compressor, the condensation fan and the pump.



          Air Blue                 Manual                Issue              Replaces
                                    E 04                 02.99                --.--
MICROCHILLER Compact                                                                         Page: 31


EE
EP: Eeprom error alarm
Indicates a problem in parameter memorisation by the machine’s non volatile memory
(EEPROM); the microprocessor continues to make adjustments with the data present in the
volatile memory (RAM) which contains a physical copy of all data. As soon as there is a
power failure of any sort, the system set up will be lost. The buzzer and alarm relay are not
activated.

EU
EO: High or low voltage power supply error
If power supply voltage is too low, the message “EU” appears on display; if voltage is too
high “EO” will appear. In these cases, correct microprocessor operation is no longer
guaranteed.

EL: Line “interference” error
This alarm is tripped if there is strong interference (loud noise) on the line. In this case, if the
fans are running on a regulator module, they will operate on an ON/OFF basis as long as the
interference continues.

Ht: High ambient temperature
This alarm is activated if the threshold reported in parameter “Pb” (detected by B1) is
exceeded. It is delayed at switch-on by parameter “PC” and leads to activation of the alarm
relay without disabling outlets. Resetting is automatic as soon as the situation which
provoked the alarm is normalised.

        6.2.          Indicators

n1: Compressor maintenance.
When the number of compressor running hours exceeds the maintenance call threshold
(factory set at zero; this alarm is normally disabled), the maintenance indicator is activated.
The buzzer and alarm relay are not activated.

d1: Defrosting status
During defrosting, the machine displays message d1 alternating with the temperature
reading; since this is merely an operating message, the standard alarm procedure is not
tripped off (buzzer, alarm relay).

r1:    Defrosting error.
If the defrosting procedure continues to its maximum time limit, while temperature or
external-contact defrost-end control had been selected, the message r1 will appear on
display. The message can be cleared using the alarm cancellation procedure or by running
another correct defrosting cycle.
The buzzer and alarm relay are not activated.

Cn: Communication error with remote terminal
If there should be a communication error between the “Compact” microchiller and the
remote terminal, message Cn appears on display; check the cable and parameter H8.
The buzzer and alarm relay are not activated. The display continues to show Cn.


         Air Blue                  Manual                  Issue                  Replaces
                                    E 04                   02.99                    --.--
MICROCHILLER Compact                                                                       Page: 32


NOTE:
If the microprocessor is set to standby while at least one alarm is present, all indicators remain
activated except for the buzzer, which switches off. Keep in mind, in any case, that when the
machine is already on standby no non-system alarms are detected (that is, only the eeprom
and probe alarms continue to be monitored, while none of the digital input alarms are
monitored).

7.     Extra microchiller circuit boards

       7.1.          Fan ON/OFF control board

This module enabled conversion of a PWM regulation signal in an ON/OFF outlet by means of
a relay, to allow control of the condensation fans. The control relay can be switched from 10
A to 250 Vac in AC1 (1/3 inductive HP).
This board is included as standard equipment in units FREEZY HP / MU LC HP / MU ST LC HP /
MU LC PF HP.

       7.2.          Fan speed control board

The phase-cutting circuit board allows control of the axial condensation fan rotation speed.

IMPORTANT: Power supply to the microchiller (G and GO) and the speed control board
must be in phase.

Calculating minimum and maximum fan speed
Given the range of motors available on the market, it has become necessary to foresee the
possibility of setting the voltage provided by the electronic circuit board corresponding to the
temperature of minimum and maximum speed.
If factory set parameters are not applicable, proceed as follows:
• set parameter F2=0 (fans always on) and reset F3 and F4.
• increase F4 until the fan is running at sufficient speed (remember to check, after having
     stopped the fan, that it will start up again if left alone).
• "copy” this setting onto parameter F3; the minimum speed voltage is set.
• connect a voltmeter (positioned in ac, 250V) between terminals “L” (in other words, the
     two external contacts).




         Air Blue                 Manual                  Issue                 Replaces
                                   E 04                   02.99                   --.--
MICROCHILLER Compact                                                                     Page: 33




•  increase F4 until the voltage stabilises at approximately 2 Vac (inductive motors) or 1.6-1.7
   Vac (capacitive motors). Once the setting has been identified, you will note that even by
   increasing F4, the voltage will not drop any further. Avoid increasing F4 past this point to
   prevent damage to the motor (which could occur at 30/40 units over the identified limit).
• Set F2=3

The procedure is completed.
The fan speed control circuit board is supplied as optional equipment in units FREEZY and
FREEZY HP, MU LC HP, MU ST LC HP, MU PF LC HP.

       7.3.          Serial converter

The serial converter is an electronic device that allows interfacing of the Compact Air Blue
microchiller to a standard RS485 (asynchronous) supervision network and/or to a remote
terminal.
For correct operation of the remote terminal and supervisor, remember to set parameters H8
(H8=1) and HA (HA=serial address of supervisor RS485 network). The supervisor serial line
must terminate with the 120 Ohm 1/4W converter resistance found at the end of the
network.
Take care to comply with the following instructions:
1. Do not simultaneously earth the transformer secondary which powers the board and the
remote terminal cable braid; this would damage the board irreparably.
2. If using the supervisor, do not power up the converter before having connected it to the
microprocessor, or keep the microprocessor switched off while doing so: otherwise the
communication between the supervisor and any other peripherals connected to the RS485
bus could be disturbed.




         Air Blue                Manual                 Issue                 Replaces
                                  E 04                  02.99                   --.--
MICROCHILLER Compact                                                           Page: 34




                                        TO uCH COMPACT




                                            SERIAL CONVERTER FOR
                                                uCH COMPACT




                                                        TO REMOTE
                                                         TERMINAL

                                    TO SERIAL
                                      LINE




       Air Blue        Manual   Issue                               Replaces
                        E 04    02.99                                 --.--
BLUE BOX Condizionamento
AIR BLUE Air Conditioning
BLUE FROST Refrigeration

are trademarks of the

BLUE BOX GROUP




BLUE BOX GROUP s.r.l.
Via E. Mattei, 20
35028 Piove di Sacco PD Italy
Tel. +39.049.9716300
Fax. +39.049.9704105




Technical data may change without notice
201712A02 – Issue 02.99 / Supersedes --.--   ISO 9001– Cert. N.0201

				