Diagnostic and Combustion Safety Form Directions Pre weatherization information should be documented in the shaded boxes Post weatherization information should be documented in t

Description

Estimate for Work Preformed document sample

Shared by: jwi45103
Categories
Tags
-
Stats
views:
92
posted:
1/31/2011
language:
English
pages:
9
Document Sample
scope of work template
							                   Diagnostic and Combustion Safety Form Directions
Pre-weatherization information should be documented in the shaded boxes. Post-weatherization information should
be documented in the non-shaded boxes.
                                    Page 2: Combustion Safety Testing
Make sure the information section at the top of page one, is completed. Include agency name, testers, and dates
tested.
               Building DTL and CAZ Pressure Differentials (top left side of the page).
Pre-WX Delta P. These tests document the existing condition of the building, prior to weatherization
work. They help to determine the measures needed for the safe operation of combustion appliances in
the building.
1) Baseline Depressurization. Measure and record                              Building DTL and CAZ Pressure Differentials
                                                                   Pre-WX                                                                                  Post-WX
the pressure difference (Delta P) between the                      Delta P                                                                                  Delta P
Combustion Appliance Zone (CAZ) and the outside.                                              Baseline Depressurization
2) Turn on Exhaust Appliances. Turn on all of the                                       (Interior doors open, CAZ door closed,
exhaust appliances in the building, measure, and                                        exhaust appliances off, record pressure)


record pressure. A negative reading larger than Step 1)                                Turn on All Exhaust Appliances in the
Baseline usually means the exhaust fans depressurize                                                 Building
the CAZ.                                                                                                    (Record Pressure)
                                                                                 Forced Air Distribution Impact on Delta P
3) Turn on the Air Handler. Measure and record
pressure difference (Delta P). A negative reading larger                                   Turn On Furnace Air
                                                                                                        (Record Pressure)
than Step 2) exhaust fans, usually means the return
ducts depressurize the CAZ. A positive reading usually                                            Position Interior
                                                                                  (Smoke door; if smoke drawn into room open door, if smoke pushed
means there are supply ducts pressurizing the CAZ.                                          out or neutral, close door. Record Pressure)

Determine distribution sealing needs based on this
reading and other diagnostic tests (when needed).
                                                                                                     Open Door to CAZ
                                                                                                          (Record Pressure)
4) Position Interior Doors. Use a smoke product
device and smoke each of the interior doors to
                                                                                            Worst Case Depressurization
determine whether to open or close the doors. If smoke                             Adjusted for Baseline:DG3-subtract baseline; DG700-use the baseline
is drawn into the room, open the door. If smoke is                                                          feature to adjust
                                                                                                                                           (Use Post for 'As Is' Worst
                                                              (Use Pre for 'As Is' Worst
pushed out of the room or is neutral, close door.             Case                                                                         Case



Measure, and record pressure difference (Delta P). A negative reading, larger than Step 3) air handler, usually
means there are not enough return ducts in the living area. Determine distribution modifications based on this
reading nd other diagnostic tests (when needed).
5) Open the door to the CAZ. Measure and record pressure difference (Delta P). A negative reading larger than
Step 4) Position Interior Doors, usually means the exhaust fans depressurize the CAZ.
6) Worst Case Depressurization. Subtract the Baseline reading from the largest negative reading obtained to get
the adjusted Worst Case Depressurization. Use this figure on page 1, Depressurization Limits Section, when
comparing the guidelines to the actual readings.
                    Post Weatherization Building DTL and CAZ Pressure Differentials
Post-WX Delta P. These tests document the final condition of the building when weatherization work is completed.
They help determine that the combustion appliances in the building are operating safely.
• Repeat Step 1) through Step 6) above, after all planned work is completed.
                        Pre Weatherization Draft, Spillage, and CO Measurements
These tests document the existing condition of the appliances. They are conducted under the Pre-Worst Case
Depressurization conditions (above). Take the draft test in the flue(s). Take the carbon monoxide test before the
appliance draft divertor or barometric damper. See the Set-up and Guideline worksheet for additional setup
information. Always cycle the atmospheric combustion appliance with the lowest BTU output first.
• Cycle Water Heater. Take draft reading at 3 minutes. Test for spillage using a smoke device. Measure the CO
PPM in the flue. The unit passes if the draft reading is acceptable for the fuel type and outside temperature (see the
Set-up and Guideline worksheet), there is no spillage, and CO level in flue are less 100 PPM.
• Cycle Furnace. Take draft reading at 3 minutes for gas, 10 minutes for oil. Test for spillage using a smoke
device. Measure the CO PPM in the flue. The unit passes if the draft reading is acceptable for the fuel type and
outside temperature (see the Set-up and Guideline worksheet), there is no spillage, and CO level in flue are less
• Repeat these steps for other appliances.
• Document any important circumstances.
• Failed appliances must have problem resolved prior to the completion of the weatherization work.

                                                                                                                                           WI Division of Energy-EAB
                                                          Page 1                                                                                              12/8/04
                               Page 2: Combustion Safety Testing Continued
                         Post Weatherization Draft, Spillage, and CO Measurements
These tests document the post-weatherization condition of the appliances. They are conducted under the Post-
Worst Case Depressurization conditions.
• Repeat the steps outlined above when all other weatherization work has been completed.

                                         Gas Range CO Testing Results
These tests document the existing condition of the gas range prior to any weatherization work and the operation of
the range when the weatherizaton work is completed. See the Set-up and Guideline worksheet for guideline and
action level information. Follow Recommended Best Practices for Carbon Monoxide Testing of Gas Ranges
(Weatherization Manual).
• Measure ambient CO level outside of building or unit. Measure ambient CO level inside of building or unit.
Subtract outside reading from inside reading to determine the magnitude of any CO problem found within unit.
• Visually inspect the appliance. If unit has broken parts, pilot burning wrong, warped deflectors and is not
repairable unit should be to be replaced. Range top burners and oven MUST NOT BE DIRTY to the extent that it
will cause false CO readings. Customer should be informed to clean the unit before any testing can be done.
                                                 Testing Range Top Burners (as measured in ambient air without
       Pre-WX Gas Range CO Testing               adjustment for oxygen content).

                            Right                  1. Remove all pots and foil from the burner area.
  Left Rear
                  PPM        Rear       PPM        2. Turn all range top burners on high and allow to warm.
   Burner
                                                   3. Test 6” above the flame without pots or test fixtures.
 Left Front                 Right
  Burner          PPM                   PPM        4. Record reading (3 minutes).
                            Front

    Oven                                           Testing Range Ovens ( must be tested air free with
                         PPM air free              adjustment for oxygen content)
                                                   1. Test ranges and ovens after all other vented appliances
       Post-WX Gas Range CO Testing
                                                   have been tested
  Left Rear                 Right                  2. Remove any items stored in the oven and any foil coverings
                   PPM                  PPM        before proceeding.
   Burner                    Rear
 Left Front                 Right                  3. Assure that self cleaning features are not activated.
                  PPM                   PPM
   Burner                   Front                  4. Insert the instrument probe into the vent sleeve before
                                                   dilution air mixes with combustion by-products
     Oven
                         PPM air free              5. Measure oven during warm-up and record peak (10 minutes)


Note: When testing ranges, continually monitor ambient space around oven during testing to protect
inspector and customer. Retest ambient air to ensure no change in CO from initial tests.




                                                                                                   WI Division of Energy-EAB
                                                       Page 2                                                         12/8/04
                           Diagnostic and Combustion Safety Form Directions
Pre-weatherization information should be documented in the shaded boxes. Post-weatherization information
should be documented in the non-shaded boxes.

                                                    Page 1: Diagnostic Testing and Modeling
Fill in the information section at the top of page one, include agency name, testers, and dates tested.

                           Building Tight Limits Section (BTLa) (middle left side of the page).
              Building Tightness Limits (BTLa)
                           As Is Test                   Final Test
                                                                               • As Is Test. Document the As Is blower door test in the top
  House CaaFM50
                                                                               shaded box.
                                                                               • Use the ZipTestPro (BTLa) to determine building tightness limits.
                                   Building Height (ft)
  Flow Exponent                                                                Follow the directions in the ZipTestPro manual (pages 8-10). Enter
  (Default .65)
                                                                               the building information and the modeling results in the shaded
                                        Story Height (ft)
  Weather Factor                                                               boxed.
                                                                               Note that the ventilation BTLa calls for does not include the
                                         # People
  House Volume (cu ft)
                                        # Bedrooms                             existing ventilation in the building. The existing ventilation should
  House Floor (sq ft)
                                        Occupant Count                         be assessed for capacity (CFM Exhaust Appliances) and utilized,
                                  (larger of # of people or # of bedrooms+1)
                                                                               where feasible, for all or part of the ventilation requirement.
  Building Tightness Limit (BTLa:CFM50)                                        • Final Test. Document the Final blower test in the top non-
                                              As Is Est           Final
                                                                               shaded box.
  Continuous Ventilation Needed
  (BTLa cfm)                                                                   • Rerun BTLa with the final blower door test to determine if
                                                                               additional ventilation is needed.

                                  Depressurization Limits (DTL) (middle right side of the page).
Pre Modeling for Minimum Allowable CFM50                                                        Pre Modeling for Maximum Allowable
• Enter the total pre                            Depressurizaton Limits (DTL)                               CFM Exhaust
cfm of the exhaust                                  Pre                 Final                          • Enter the total pre cfm50 test
                          Total Exhaust cfm
appliances (as            (As Measured or Estimate)                                                    of the building in the top shaded
measured or             Maximum Delta P                                                                • Enter the maximum Delta P for
                        (Bldg Dep Guideline
estimate) in the top    Chart)                                                                         the building, based the existing
shaded box.             Flow Exponent                                                                  combustion appliances, from the
• Enter the maximum     (Default .65)
                                                                                                       Depressurization Guideline
                        Solve for DTL (cfm50 )
Delta P for the                                                                                        Chart (see Setup & Guidelines
                                                      Pre                Final
building, based the                                                                                    for Testing worksheet) in the
existing combustion       House CFM50                                                                  second shaded box.
appliances, from the    Maximum Delta P
                        (Bldg Dep Guideline                                                            • Enter the Flow Exponent. Use
Depressurization        Chart)
                                                                                                       either the default (.65) or the
                        Solve for Total Exhaust
Guideline Chart (see    (cfm)                                                                          actual exponent from a five-
Setup & Guidelines                                                                                     point blower door test.
for Testing               Worst Case Delta P*                                                          • Solve for maximum allowable
                      *record the max. ?P from Pre-WCD          *record the max. ?P from Post-WCD
worksheet) in the     adjusted for baseline ( page 2)           adjusted for baseline ( page 2)        CFM of the exhaust appliances.
second shaded box.                                                                                     Use the ZipTestPro
• Enter the Flow Exponent. Use either default (.65) or actual                                                     Software(DTL) to determine
exponent from a five-point blower door test.                                                                      building depressurized
• Solve for minimum allowable cfm50 blower door test.                                                             requirements. Follow the
Use the ZipTestPro Software (DTL) to determine depressurized building                                             directions in the ZipTestPro
requirements. Follow the directions in the ZipTestPro manual (pages 8-10).                                        manual (pages 8-10)
                                                                                                                  • Enter the pre Worst Case
                                                                                                                  Depressurization of the building
  Post Modeling for Minimum Allowable CFM50 and CFM Exhaust                                                       (page two).*
• Repeat the steps listed above for pre-modeling, with the final test results.
• Enter the post Worst Case Depressurization of the building (from page two).
*If the Worst Case Depressurization is greater than the maximum Delta P for the building, based on the
Depressurization Guideline Chart, the problem must be solved prior to completing the weatherization work. The
building may require additional returns, distribution sealing, a change of venting or combustion appliances, or
added make-up air.
                                                                                                                                WI Division of Energy-EAB
                                                                                       Page 3                                                      12/8/04
                          Page 1: Diagnostic Testing and Modeling Continued
             Results: Blower Door Tests and Sealing Work Section (bottom left corner of the page).
• As Is Test. Document the As Is blower door test in the top shaded box. Complete this blower door test prior to
any work on dwelling. This test documents existing conditions and allows for the modeling of building tightness.
It also helps determine if non-guideline sealing is needed in order to run an accurate blower door test. Examples
of non-guideline sealing include installing window where missing, sealing gross holes in the building envelope,
and sealing key junctures.
• Pre-Test. Document the Pre blower door test in the second box. Complete this test after any non-guideline
sealing work is completed. If no non-guideline sealing is needed the “as is” and “pre” may be the same test.
Document any cfm reductions and work
                                                               Results: Blower Door Tests and Sealing Work
hours for non-guideline sealing.                                                     cfm@ 50                        Work Hours
                                                                                             Non-Guideline
• Final Test. Document the Final blower                         CFM 50 of Building
                                                                (As Is Test)
                                                                                              Reduction
                                                                                             (As Is Test- Pre Test)
 door test in the third box. Document any                        CFM 50 of Building          Guideline Reduction
cfm reductions and work hrs. for guideline                      (Pre Test)                   (Pre Test-Final Test
sealing. Guideline sealing is sealing work                        CFM 50 of Building         Comfort Sealing
                                                                 (Final Test)                 (No Blower Door Test)
completed using the WI Cost Effective
Sealing Guidelines
(WCEG).WCEG                  • Comfort Sealing. Document the time spent on comfort sealing in the work hours
must be used with all        column. Comfort sealing is preformed when blower door testing cannot be preformed.
blower door guided           Sealing work is limited to attic bypass and key junctures and other sealing that will
sealing.                     effect the occupants comfort. It is limited to 1 labor hour.


                                  CFM of Exhaust Appliances (bottom middle of the page).
                                                   • Document pre cfm of the existing individual exhaust appliances.
      CFM of Exhaust Appliances
                                                   Measure or estimate cfm of existing exhaust. If ventilation is
                       Pre     Final               needed actual measurement should be completed.
            Dryer                                  • Total the cfm of the existing individual exhaust appliances at the
            Bath 1                                 bottom of the column.
            Bath 2                                 Note if the amount of existing ventilation is less than the required
                                                   ventilation (BTLa). The BTLa program does not calculate existing
            Kitchen                                ventilation, only the ventilation required for the building. The
            Other                                  existing ventilation should be assessed for capacity and, where
Total CFM Exhaust:                                 feasible, utilized for all or part of the ventilation requirement.

Note if the amount of existing ventilation exceeds the maximum exhaust allowed (DTL). This problem must be
solved as a part of the planned weatherization work. The building may require a change to venting or
combustion appliances, or added make-up air.
 • Repeat the steps listed above to document the final test results. If ventilation has been installed an actual
measurement is recommended.
• Total the cfm of the existing individual exhaust appliances at the bottom on the column.
Note the post Worst Case Depressurization of the building (from page two). If the post Worst Case
Depressurization is greater than the maximum Delta P for the building, based on the Depressurization Guideline
Chart, the problem must be solved prior to completing the weatherization work. The building may require
additional returns, distribution sealing, a change to venting or combustion appliances, or added make-up air. If
make-up air is to be added the existing exhaust appliances must be measured.

                                       Make-up Air Calculations (bottom right of page)
To verify that make-up air is necessary see the Make-Up Air Check                                Make-up Air Calculation
Worksheet. WI Uniform Dwelling codes required make-up air when the CAZ
is excessively depressurized or pressurized. Add make-up air that is 40% of                    Total cfm Exhaust
exhaust ventilation. Use Building Depressurization Guidelines to determine if                       Times 40%      X   .40
depressurization exceeds guidelines.
                                                                                            CFM of Make-up Air
• Enter total exhaust air (both continuous and intermittent) in top box.
• Multiple the total exhaust by 40% (.40).
• Total exhaust X.40 equals the amount of make-up air required (cfms).

                                                                                                         WI Division of Energy-EAB
                                                            Page 4                                                          12/8/04
                                                                  Make-up Air Check
                                  (Follow these steps to determine if make-up air is required to assure balanced ventilation.)
      Step #1
                Is the final ∆P less                   Yes        If yes, no further action is required.
                than or equal to the                                                                                        Yes       Go to Step #2.
                Building                                No        Is the problems caused by exhaust?
                Depressurization                                                                                            No        Go to Step #3.
                Guidelines? (Chart)


                 Step #2
                            Verify cfm exhaust estimates with actual measurement.
                                                                     cfm
                                                          Dryer
                                                         Bath 1                         Is final exhaust                    Yes       Go to Step #3
                                                         Bath 2                         cfm less than or
                                                        Kitchen                         equal to DTL                        No        Add Make-up air
                                                         Other                          maximum?                                               and/or
                                                                                                                                      Modify exhaust
                                         Step 2a.      Total                                                                          for safe operation

                             Step #3
                                         Modify and/or seal distribution system.                               RETEST

                                         Is the final ∆P                       Yes      If yes, no further action is required.
                                         less than or
                                         equal to the                           No      Add Make-up air
                                                                                                               Per Wisconsin Uniform Dwelling code when
                                         Building                                               and/or
                                                                                                               CAZ is excessiv ely depressurized or
                                         Depressurization                               Modify exhaust         pressurized, add make-up air that is 40% of
                                         Guidelines?                                    for safe operation     exhaust ventilation.
                                         (Chart)
                                                                                                                                 Make-up Air
                                                                                                   Use total from Step 2a   Total cfm Exhaust

                                                                                                                                    Times 40%      X .40
WI Division of Energy-EAB                                                                                           CFM of Make-up Air
Revision: 12/8/04
                                                                                 Diagnostic Testing and Modeling

    Agency                                                                                         Pre-WX                                             Pre-WX
                                                                                                   Tester                                             Test Date

    Building                                                                                       Post-                                              Post-WX
    ID #                                                                                           Tester                                             Test Date

                    Building Tightness Limits (BTLa)                                                                                      Depressurization Limits (DTL)
                                                                                                                                                         Pre                  Final
                                           As Is Test                      Final Test                                    Total Exhaust cfm
                                                                                                                         (As Measured or Estimate)
    House CFM50
                                                                                                                         Maximum ∆P
    Flow Exponent                                                                                                        (Bldg Dep Guideline Chart)
    (Default .65)
                                                   Building Height (ft)                                                  Flow Exponent
                                                                                                                         (Default .65)
    Weather Factor
                                                                                                                         Solve for DTL (cfm50)
    House Volume (cu ft)                           Story Height (ft)
                                                # People                                                                                                 Pre                  Final
    House Floor (sq ft)
                                                # Bedrooms
                                                                                                                         House CFM50
                                                   Occupant Count                                                        Maximum ∆P
                                                    (larger of # of people or # of bedrooms+1)                           (Bldg Dep Guideline Chart)
                                                                                                                         Flow Exponent
    Building Tightness Limit (BTLa:CFM50)                                                                                (Default .65)
                                                                                                                         Solve for Total
                                                                                                                         Exhaust (cfm)
                                                As Is Est            Final
    Continuous Ventilation Needed (BTLa                                                                                  Worst Case Delta P
    cfm50)                                                                                                               (∆P)*
                                                                                                                         *record the max. ∆P from Pre-WCD         *record the max. ∆P from Post-
                                                                                                                         adjusted for baseline (page 2)           WCD adjusted for baseline (page
                                                                                                                                                                  2)
                            Results: Blower Door Tests and Sealing Work                                                    CFM of Exhaust Appliances              Make-up Air Calculation
                                                                                                                                              Pre        Final    To verify that make-up air is
                                                                cfm@ 50                                     Work Hours                                            necessary see Make-Up Air Check
                                                                                  Non-Guideline                                  Dryer                            Worksheet. Wisconsin Uniform
                               CFM 50 of Building
                                                                                  Reduction (As Is Test-                                                          Dwelling code when CAZ is
                              (As Is Test)
                                                                                  Pre Test)                                     Bath 1                            excessively depressurized or
                                                                                                                                                                  pressurized, add make-up air that
                               CFM 50 of Building                                 Guideline Reduction                                                             is 40% of exhaust ventilation.
                                                                                                                                Bath 2
                              (Pre Test)                                          (Pre Test-Final Test)
                                                                                                                                                                     Total cfm Exhaust
                                                                                                                              Kitchen
                               CFM 50 of Building                                 Comfort Sealing
                                                                                  (No Blower Door Test)
                                                                                                                                                                          Times 40%      X     .40
                              (Final Test)
                                                                                                                                 Other
                                                                                                                                                                   CFM of Make-up Air
WI Division of Energy-EAB                                                                                       Total CFM Exhaust:
Revision 12/8/04
                                                   Combustion Safety Testing


        Building DTL and CAZ Pressure Differentials                                                     Gas Range CO Testing Results
 Pre-WX                                                                Post-WX
 Delta P                                                                Delta P                          Pre-WX Gas Range CO Testing
                      Baseline Depressurization                                                     Left Rear           Right
                (Interior doors open, CAZ door closed,                                               Burner       PPM   Rear                    PPM
               exhaust appliances off, record pressure)                                                Left             Right
                                                                                                      Front       PPM   Front                   ppm
               Turn on All Exhaust Appliances in the
                              Building                                                                 Oven
                         (Record Pressure)                                                                                       ppm air free


           Forced Air Distribution Impact on Delta P                                                     Post-WX Gas Range CO Testing
                                                                                                    Left Rear           Right
                     Turn On Furnace Air Handler                                                     Burner        ppm  Rear                    ppm
                          (Record Pressure.)                                                           Left             Right
                                                                                                      Front        ppm  Front                   ppm
                          Position Interior Doors
              (Smoke door; if smoke drawn into room open door, if
                smoke pushed out or neutral, close door. Record                                        Oven
                                                                                                                                 ppm air free
                                  Pressure.)

                                                                                                             Other Post-WX CO Testing
                             Open Door to CAZ
                              (Record Pressure)

                     Worst Case Depressurization
              Adjusted for Baseline:DG3-subtract baseline; DG700-
                        use the baseline feature to adjust
(Use Pre for 'As Is' Worst Case Delta                  (Use Post for 'Results' Worst Case
P (∆P) on page 1.                                      Delta P (∆P) on page 1)


                                         Draft, Spillage, and CO Measurements
          [Under Worst Case Draft conditions. Draft test in flue(s). CO test before appliance draft diverter or barometric damper.]
                     Pre-WX                                                                                 Post-WX
                                           Pass/        Recreate w/ WCD (greatest                                                 Pass/
  Draft       Spillage CO PPM               Fail               negative ∆P)              Draft       Spillage CO PPM               Fail
                                                         Cycle Water Heater
                                                         (Reading in flue@ 3 min)



                                                          Cycle Furnace
                                                         (Gas: measure @3 min.)
                                                         (Oil: measure @ 10 min. )


                                                           Other Appliance
                                                          Specify:



COMMENTS:




                                                                                                                     WI Division of Energy-EAB
                                                                                                                             Revision: 12/08/04
                                                                                                             Set-up for Combustion Safety Tests

These tests are required when atmospheric combustion appliances are present. CAZ depressurization should be measured for any appliance type.

DTL Test: Use TI-86 w/ ZipPro Software to solve for minimum blower door cfm50 and maximum exhaust cfm. Document 'As Is' and final conditions for testing variables, air sealing,
worst case delta P and ventilation results. Follow set-up procedure below.

Worst Case Draft Test: Completed on all dwellings with atmospheric combustion appliances that are designed to be vented to the outside of the building. Document results.
Recreate greatest negative pressure for testing draft and spillage tests. Test pre and post weatherization work. Follow set-up below.


                                                            Worst Case Draft Test and Depressurization Test Limit Initial Set-up
                                                                  Top tap to CAZ or
  1. Close house.                                                   Open in CAZ

  2. Install hose from input or top
  tap to the CAZ
                                                                                   -2


                                         Bottom reference
  3. Install hose from reference or      tap to Outside
  bottom tap to the exterior                                  INPUT
                                                                                             INPUT


                                                                                                                                                                   -2

  4. Reading is the pressure                                      A                           B


  difference between CAZ &                                     Reference                A




  Outside (Baseline)
  5. For use with Building
  Depressurization Guidelines
  adjust Worst Case
  Depressurization by baseline
                                                                                                                                                                                             Top tap to CAZ or
  reading (from step 4).                                                                                                                                                                       Open in CAZ
                                                            Top tap to CAZ or
                                                              Open in CAZ                                                                            To Flue for Draft
                                                                                                                To Flue for Draft



                                                                                                                                                                                                                 -2


                                                                                        -2
                                                                                                                                                                    Bottom reference
                                                                                                                                                                    tap to Outside
                                                                                                                                                                                              A                       B


                                                                                                                                                                                             INPUT                INPUT

                                                                                                                                                                                                     REFERENCE


                                                                           INPUT
                                                                               A
                                                                                                         B
                                                                                                     INPUT
                                                                                                                                                                         To Overfire Draft        REFERENCE




                                  Bottom reference                    REFERENCE


                                  tap to Outside                                              REFERENCE

                                                                                                                                                              For Oil Furnace draft and CO test:
For Gas Water Heaters: draft and CO test:                                                                                                                        1. Drill hole in flue before the barometric damper. Install
  1. Install hose from input, or top tap, to center of flue, half                                                                                                hose from input, or top tap, to metal sleeve and take draft
  way between the divertor and the chimney.                                                                                                                      test in each location. A second draft test should be taken
  2. Measure Draft after 3 minutes,                                                                                                                              at the overfire.
  3. Measure CO after draft.                                                                                                                                     2. Measure Draft after 10 minutes,
  4. Measure Spillage use smoke generator at divertor.                                         CO Test before diverter for gas and oil appliances.               3. Measure CO after draft.
                                                                                                                                                                 4. Measure Spillage use smoke generator at barometric
                                                                                                                                                                 damper.
                                   When testing for CO continually monitor CO of ambient air.
                                                                                                                                                                                                                          WI Division of Energy-EAB
                                                                                                                                                                                                                                  Revision: 12/08/04
                                                                 Guidelines and Action Levels for Combustion Safety Testing

                                                                                Building Depressurization Guidelines

                           Building Depressurization Guideline
                 Maximum Depressurization for Combustion Appliance Zones
                                    By Appliance Type
                                                                                                         Adjust readings for baseline by subtracting the baseline reading(CAZ wrt
                                                                                                         Outside) from measured WCD pressure. Example: Baseline is -2, WCD is -
             ND Water ND Heating ND Water ND Water                               PV Water                5, Adjusted reading is -3. If using DG700, use the baseline feature to
 Appliance      Heater      System or     Hter & Htg   Hter & ID    ID Heating Heater &                  automatically adjust the reading.
   Type:      (Orphaned)       Stove        System    Htg System      System    SC Furnace
Pascals:           -2            -5            -3           -5          -15         -25
Key:ND=natural draft; PV=power vented (water heater or condensing furnaces with one pipe, typically sidewall PVC vent, draws combustion air from CAZ); ID=Induced draft
(open flame with an induction fan venting to chimney);SC=sealed combustion (a condensing furnace that draws combustion air from and vents to the outside, typically
sidewall PVC pipe(s)). The Depressurization Guideline is based on the guidelines used by the Minneapolis Center for Energy and the Environment and the Energy
Conservatory. If basement depressurization is below -15, fire power vented water heater too assure there is no flame rollout.


                                                   Acceptable Draft Readings for Atmospheric Combustion Appliances

                      Acceptable Draft Test Readings for Gas Appliances                                                             Acceptable Draft Test Readings
                            with Respect to Outdoor Temperature                                                                         for Oil Fired Furnaces
           °F       <20         21-40        41-60       61-80        >80                 °F                                                              Acceptable Draft
          pa.        -5           -4           -3          -2          -1                 pa.                                Location                   w.c.i.             pascals
        w.c.i.      -.02        -.016        -.012       -.008       -.004                w.c.i.                    Overfire Draft                      -0.02                 -5
                                                                                                                    Flue Drafts                     -0.04 to 0.06      10 to 15
                                                                                                                          Guidelines based North Dakota WX Assistance Program guidelines.


                                Acceptable Carbon Monoxide Readings in Heating System & Action Levels for Gas Ranges

                Carbon Monoxide Action Level:                                                                   Action Levels for Range Top Burners
                   Gas & Oil Heating Systems                                                CO PPM    Measuring
                                                                                                                                      Action
                                    As                                                         As       Time
        Appliance                Measured                         Air Free                   < 25 PPM   3 min.  Advise customer to clean.
Gas/Furnace Boiler               100 PPM                          200 PPM                    25-50 PPM 3 min.   Have appliance serviced
Gas /Oil Water Heater            100 PPM                          200 PPM                    > 50 PPM   3 min.  Do not use appliance until repaired or replaced.
Oil Furnace/Boiler               100 PPM                          200 PPM
  Guidelines based North Dakota Weatherization Assistance Program guidelines.   Note: When testing ranges, continually monitor ambient space around oven during testing to protect inspector and
                                                                                customer . Retest ambient air to ensure no change in CO from initial tests.

                                                                             Action Levels for Gas Ovens
                                                                 Measuring
                                     Air Free CO PPM                                                          Action
                                                                   Time
                               < 800 PPM                          >10 min. Should be cleaned by client to prevent possible CO problems.
                               > 800 PPM, <1000 PPM               >10 min. Have appliance serviced
                               >1000 PPM                          >10 min. Oven should not be used. Replace appliance.



                                                                                                                                                                                            WI Division of Energy-EAB
                                                                                                                                                                                                    Revision: 12/08/04

						
Related docs