ABS Catalogue

VIEWS: 203 PAGES: 68

									ISSUE UPDATED FEBRUARY 2005




 A.B.N. 51 000 770 650
                                                                  TABLE OF CONTENTS

                                                                                                                     PAGE

  INSTRUCTIONS FOR SAFE USE --------------------------------------------------------------------------- 4 - 5
  SUPER LIFT II INSERTS -------------------------------------------------------------------------------------- 6 - 7
  SUPER LIFT III INSERTS ------------------------------------------------------------------------------------- 8
  WALL BRACE INSERTS --------------------------------------------------------------------------------------- 9
  GROUND BRACE INSERTS ---------------------------------------------------------------------------------- 9
  INVERTED WALL BRACE INSERTS --------------------------------------------------------------------- 10
  COIL BOLTS -------------------------------------------------------------------------------------------------------- 10
  COIL LIFTING INSERTS - SINGLE ----------------------------------------------------------------------- 11
  COIL LIFTING INSERTS - DOUBLE ---------------------------------------------------------------------- 11
  FIXING FERRULES - HEXAGONAL CROSS-HOLE TYPE -------------------------------------- 12
  FIXING FERRULE ACCESSORIES - CHAIRS / CAPS / NAILING PLATE ----------------- 12
  THREADED REBAR --------------------------------------------------------------------------------------------- 13
  BURKE SLOT INSERT ------------------------------------------------------------------------------------------ 14 - 17
  PRECAST - BURKE RAPID-LIFT -------------------------------------------------------------------------- 18
  PRECAST - 1 TON ERECTION ANCHOR --------------------------------------------------------------- 19
  PRECAST - ANCHORS ----------------------------------------------------------------------------------------- 20
  PRECAST - SPREAD ANCHOR ----------------------------------------------------------------------------- 21
  PRECAST - TWO HOLE ANCHOR ------------------------------------------------------------------------- 22
  PRECAST - PLATE ANCHOR -------------------------------------------------------------------------------- 23
  PRECAST - FLAT FOOT ANCHOR ------------------------------------------------------------------------ 24
  PRECAST - SANDWICH PANEL ERECTION ANCHOR ------------------------------------------- 25
  PRECAST - ERECTION ANCHOR 2.5t, 5t, 10t W/SHEAR PLATE ---------------------------- 26 - 27
  ERECTION ANCHORS ----------------------------------------------------------------------------------------- 28 - 29
  PRECAST - 5t HAIR PIN EDGE LIFT ANCHOR ----------------------------------------------------- 30
  BRACES - MEADOW BURKE SUPR BI-POD ---------------------------------------------------------- 31 - 34
  BRACES - SUPER / SUPR 17 / MINI-SUPER / BABY ---------------------------------------------- 35 - 36
  BRACE GUIDE - TILT-UP WALL PANEL BRACING ----------------------------------------------- 37 - 38
  TILT-UP LIFTING PRODUCTS - STRONGBACKS -------------------------------------------------- 39 - 43
  SUPER BOLT ------------------------------------------------------------------------------------------------------- 44




ADVANCED BUILDING                                                  Unit 2/22 Violet Street, Revesby NSW 2212
                                                                   PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                                  Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                                   Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com
                                                                                                                            2
                                                                TABLE OF CONTENTS

                                                                                                                 PAGE


  SUPER LIFT II CLUTCH --------------------------------------------------------------------------------------- 45
  SUPER LIFT III CLUTCH ------------------------------------------------------------------------------------- 46
  FOR HIRE - SINGLE SWIVEL LIFT PLATE ------------------------------------------------------------ 47
  FOR HIRE - DOUBLE ANGLE LIFT PLATE ------------------------------------------------------------ 47
  FOR HIRE - TAPER BOLTS ----------------------------------------------------------------------------------- 48
  FOR HIRE - ABS/BURKE BAR & MINI BAR ----------------------------------------------------------- 49
  PLASTIC ACCESSORIES - SUPER SHIMS -------------------------------------------------------------- 50
  PLASTIC ACCESSORIES - MODFIX SHIMS ----------------------------------------------------------- 51
  PLASTIC ACCESSORIES - EASY-T CONCRETE CRACK INDUCER ------------------------ 52
  PLASTIC ACCESSORIES - PVC CHAMFER STRIP ------------------------------------------------- 53
  PLASTIC ACCESSORIES - CHAMFER CUTTERS &
                     SHEFFIELD CHAMFER CUTTERS ------------------------------------ 53
  PLASTIC ACCESSORIES - PLASTIC STICK-ON PATCH ----------------------------------------- 54
  CHECK LIST - EQUIPMENT CHECK LIST FOR LIFTING DAY ------------------------------- 55
  HAND SPRAYER + SPARE PARTS -------------------------------------------------------------------------- 56
  CHAPIN PROFESSIONAL SPRAYER - VITRON ------------------------------------------------------ 56
  DRUM RACK -------------------------------------------------------------------------------------------------------- 57
  SUPER TILT BOND BREAKER WB ------------------------------------------------------------------------ 58 - 59
  CLEAN LIFT 90 BOND BREAKER ------------------------------------------------------------------------- 60
  SPARTAN-COTE CURE-SEAL-HARDENER ------------------------------------------------------------ 61
  BURKE TITAN HARD -------------------------------------------------------------------------------------------- 62
  PROTECTIVE COATINGS - BURKE SHIELD 244 ---------------------------------------------------- 63
  SHARASOL TOOL CLEANER AND FORM RELEASE ---------------------------------------------- 64
  CONCRETE HANDLING EQUIPMENT - ALLEN RAZORBACK                                          TM   AIR DRIVEN -------- 65
  CONRETE HANDLING EQUIPMENT - ALLEN RAZORBACK                                      TM   ENGINE DRIVEN --- 65
  SCREED KING ------------------------------------------------------------------------------------------------------ 66
  ANNEXURE A - S.W.L. LIMITS - WALL BRACE INSERTS --------------------------------------- 67
  REVISED TRADING TERMS AND CONDITIONS -AS AT NOVEMBER 2004 -------------- 68




ADVANCED BUILDING                                                   Unit 2/22 Violet Street, Revesby NSW 2212
                                                                    PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                                   Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                                    Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                                          3
                 Falling Panels, Bracing or Hardware
          Can Cause Property Damage, Severe Injury or Death.
          All instructions and information should be clearly understood by all job site
          personnel involved in the construction and erection process prior to
          proceeding with construction. If anyone is unclear or has doubts about the
          proper use or installation of the products shown, contact Advanced
          Building Systems representative or your Design Engineer for clarification.
          Failure to do so my result in exposure of workers and other personnel in
          the area of the job site to unsafe conditions of hazards, resulting in the
          possibility of injury or death.

Warning   Do not weld or modify products.
          Welding or modifying products may reduce the products load carrying capacity causing unexpected
          failure of the product, resulting in possible property damage, injury or death.

Warning   Do not substitute products or interchange components from other
          manufacturers.
          Substituted products may not have the same load carrying capacity or functionality as those
          specified. Product components from different manufacturers may not be compatible, causing
          product malfunction and/or a reduction in the products load carrying capacity. Either case may result
          in an unexpected failure of the product, resulting in possible property damage, injury or death.

Warning   Do not use drill-in expansion anchors as lifting inserts or brace
          connections unless approved in writing by your Structural
          Engineer.
          Drill-in expansion anchors do not have the same load resistance characteristics or load carrying
          capacities as cast-in inserts. Their improper use may result in a serious accident causing
          possible property damage, injury or death.

Warning   Do not use damaged or worn products.
          Failure to check and replace damaged or worn products may result in product failure causing
          property damage, injury or death.

Warning   Do not climb on or ride panels during erection.
          Riding or climbing on panels can cause severe injury or death.

Warning   Do not alter rigging, reinforcing steel or strongbacks.
          Altering the rigging can change the applied lift insert loads, panel stresses and overall behaviour of
          the panel during erection. Altering or omitting reinforcing steel or strongbacks can cause cracking
          or complete panel collapse during erection. Both can lead to property damage,severe injury or death.

Warning   Do not deviate from the information shown on the drawings without
          notifying Advanced Building Systems Pty. Limited and obtaining
          approval from the Design Engineer for the project.



ADVANCED BUILDING                                        Unit 2/22 Violet Street, Revesby NSW 2212
                                                         PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                        Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                         Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                                   4
                                                                 WARNING



 The MEADOWS BURKE RAPID-LIFT SYSTEM and the MEADOWS
 BURKE SUPER-LIFT SYSTEM are concrete lifting systems comprised of
 four major components each: a lifting clutch, anchor, void former and
 supplementary hardware.
 Each of these components has been designed, engineered and manufactured by
 MEADOWS BURKE to work together in an integrated lifting system. Users
 must observe all instructions in the RAPID-LIFT Systems Manual and the
 MEADOWS BURKE on Tilt-Up Manual also AS 3850 is one of the applicable
 Australian Standards.




                !WARNING!
        MEADOWS BURKE LIFTING SYSTEM
         COMPONENTS MUST NOT BE USED
        WITH COMPONENTS FROM ANOTHER
               MANUFACTURER.




ADVANCED BUILDING                         Unit 2/22 Violet Street, Revesby NSW 2212
                                          PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                         Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                          Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                              5
                      MEADOW BURKE SUPER LIFT INSERTS

Inserts can also be supplied                             COMPLIES WITH AS3850
hot-dipped galvanised on request.

                                     4 antennae clearly
                                     signal insert’s location


   Easy to remove                                                       Indicator arrow for
   with screwdriver                                                     correct alignment



                                                                              Recess former creates
                                                                              a perfectly matched
                                                                              recess for the ring
                                                                              clutch and eliminates
                                                                              excessive bearing.


Pin section snaps
securely into the centre                                             Anchor is made of high strength
of the platform                                                      low alloy steel. The shape of the
                                                                     anchor is engineered for
                                                                     maximum strength.




        The four legs on the
        large base give stable
        support. Plastic feet will                                        Notches on the sides aid in
        not be visible on face of                                         wiring the anchor to rebar.
        finished wall and will
        not cause surface stains.                                         DO NOT WELD ANCHOR
                                                                               TO REBAR
AVAILABLE IN SIZES:
125MM                                NOTE: Galvanic action can occur. Designers
150MM                                should be aware that a galvanic cell can be
175MM                                created. If galvanised steel and black steel
200MM                                come in contact with each other.

ADVANCED BUILDING                                     Unit 2/22 Violet Street, Revesby NSW 2212
                                                      PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                     Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                      Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                          6
                        MEADOW BURKE SUPERLIFT INSERTS
                                          SUPER LIFT II
Working Loads in kN in 17 MPa Concrete, 2.5:1 Safety Factor
(This table shows loads based only on the dead load. The dead load should be increased at least 40%
to compensate for initial bond and impact). Additional increases due to unusual live loads or cable
angle magnification may be required for some job conditions. The minimum edge distance required
to obtain the rated loads for face applications is twice the insert depth. For lightweight concrete,
reduce loads by the ratio of the concrete densities.
                                        Nominal Slab Thickness (mm)
Type of Lift                125            140          150        175           200     225        250

Face Tension              32.88          32.88        51.46       54.27         54.27   54.27      54.27
Face Shear                46.09          46.09        54.27       54.27         54.27   54.27      54.27
Note: For Designers and Engineers.
Based on a 5:1 safety factor for reusable lifting devices under AS Code 3850 you should be aware
that our 5t Clutch, when used with inserts above 150mm, that the insert working load limit is
limited by the working load limit of the Clutch.

 SUPER LIFT BASE EXTENSION
                        Engages Super Lift base
                        very securely

  Base



  Extension                                                                                          62.5mm

 ‘Easy Clip-off
 12mm segments

INSTALLATION                              Arrow on insert cap MUST point
Insert shall be located as shown          towards top or bottom of the panel.
with the arrow on the yellow
void former pointing towards
the top of the panel. Be sure the
insert size is the same as the
panel thickness. Be certain the            Place two Y12 x 500mm bars
yellow void former is                      on insert. DO NOT WELD
completely pushed on to the
insert and the cap tightly closed.
Allow at least 300mm from
centre of insert to nearest ob-
struction above it.

Y12 bar is used solely for
location of the insert not to                     Vibrate concrete thoroughly
gain its Working Load Limit.                      around insert.


ADVANCED BUILDING                                              Unit 2/22 Violet Street, Revesby NSW 2212
                                                               PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                              Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                               Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                                   7
                      MEADOW BURKE SUPERLIFT INSERTS
                                        SUPER LIFT III

RATING 10t
The BURKE Super-Lift III Tilt-Up Insert
with a maximum lifting capacity of 10t (2:5:1)
factor of safety is capable of safely lifting more
than any other tilt-up insert in the marketplace.
The BURKE Super-Lift III Insert is sold
assembled and ready to use with void-former
and base attached. See Engineering Data Sheet
for working loads in various panel thicknesses.
An oval void requires minimum patching. The
BURKE Super-Lift III Insert also has notches
for rebar tying.




                                                     SUPERLIFT III INSERT
                                                          WLL          Tension
                                                                       Shear         99.64 kN

                                                          WLL          Clutch       100 kN




                                                      An easy to use BURKE Double Bar is
                                                      available for double insert requirements.




ADVANCED BUILDING                                    Unit 2/22 Violet Street, Revesby NSW 2212
                                                     PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                    Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                     Email: mjdavis@tiltbilt.com Web: www tiltbilt.com

                                                                                                         8
                                                                    BRACING INSERTS

 WALL BRACE INSERT                                                          COMPLIES WITH AS 3850

 Specifically designed for use with SUPER BRACES.                  125mm
 19MM DIAMETER COIL BOLT.                                          150mm
                                                                   175mm
 High strength, heat treated coil. PVC caps on chair.              200mm
 Can also be used as a fixing ferrule for strong backs
 and structural fixings/members with greater ease
 and flexibility. Rolled thread in insert and matching
                                                                                  Plastic Tip Feet
 coil bolt gives quick attachment.
                                                                                  to prevent corrosion
 For Working Load Limits on Inserts please refer to Annexure A
 at back of catalogue.
                                        PANEL THICKNESS

                150mm                            175mm                               200mm

      Initial         Safe             Initial           Safe              Initial          Safe
      Failure         Working          Failure           Working           Failure          Working
                       Loads                             Loads                              Loads

      16433             29.24           24467             43.53              18500             32.92
       (lbs)            (kN)            (lbs)             (kN)               (lbs)             (kN)
                • The loads shown above are tensile loads at 28 MPa concrete strength.

 GROUND BRACE INSERT                                                        COMPLIES WITH AS 3850

 Designed for maximum stability during concrete pour
 and maximum resistance to pull out during bracing.
 The insert is positioned by pushing down into sub
 strata as far as crank in wire.

 Ground brace inserts are the safest method of fixing
 braces to the floor slab. If one is accidentally                                         SLAB
 omitted, use a SUPERBOLT. (See SUPERBOLT                                                 THICKNESS
 page in this catalogue for further information).
 Where waterproof membrane is used under the slab,
 it is recommended that a wall brace insert be used.
 Working Load Limit 11.15 kN. Safety Factor (2.5:1)           125mm                       PUSH IN
                                                              150mm                       GROUND
 • The loads are based on 102mm slab, 13.8 MPa                175mm
   concrete strength.
 • The loads increase with the square root of the
   concrete strength and by the sheared concrete cone
   surface as the slab thickness.

                                Unit 2/22 Violet Street, Revesby 2212
Advanced Building Unit 2/22 Violet Street, Revesby NSW NSW 2212
  ADVANCED BUILDING             PO Box 113, North Revesby NSW 2212
                                 Bankstown NSW 2200
Systems Pty. Ltd. P.O. Box 546, Phone: (02) 9771 1011 Fax: (02) 9792 1414
  SYSTEMS PTY. LTD.
                                                         Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                             9
                                                                     BRACING INSERTS

INVERTED WALL                      ONE SIZE FITS ALL                         COMPLIES WITH AS 3850
BRACE INSERT                       PANEL THICKNESSES.

Designed for use when panels are to be braced externally, or
when panels to be braced internally are cast external face up.

Also used when fixing awnings to the outside (under face) of a
panel.
Working Load Limit (2.5:1) Tension 20.82 kN, Shear 43.23 kN
• Loads are based on 21 MPa concrete strength.
• The load increases with square root of the concrete strength.

COIL BOLTS                                                TIE-BACK APPLICATION
Coil bolts are made from high strength steel,             Continuous Threaded Coil Rod develops the full
maximum tensile strength = 689 MPa for all                strength of standard rod when embedded length is
sizes except 3/4” minimum 500 MPa. These                  30 times the rod diameter in 13.8 MPa.
have fast acting, self-cleaning coil threads which
fit into the helix coils of coil ties and coil inserts.

Coil Bolts require correspondingly small holes in         COIL NUT
forms, are fast to apply, do not bend in removal,         Heavy hex-shaped Coil Nuts are available for all
and may be backed out for reuse without                   sizes of coil rod. One nut will develop the full
removing waler.                                           strength of standard coil rod. TWO NUTS ARE
                                                          REQUIRED TO DEVELOP THE FULL
Coil bolts should penetrate two full thread               STRENGTH OF HIGH STRENGTH ROD.
lengths beyond the end of the coil in order to
develop full strength.                                    With the addition of a Plate Washer and Hex Nut
                                                          or a Coil Nut Washer, it becomes a Coil bolt of
                                                          flexible length that easily adjusts to different sizes
                                                          of form lumber.

  COIL BOLT
  Nominal              Working Loads          Working Loads            Min. Coil              Threads
  Dia.                 Safe factor = 2.5      Safe factor = 5          Penetration            Per cm
                       Tension                Tension
  19mm (3/4”)            40 kN                  20 kN                   38mm                   1.75
  25mm (1”)              64.1 kN                32 kN                   51mm                   1.38
  32mm (1-1/4”)          96.8 kN                48.4 kN                 51mm                   1.38
  COIL ROD                     STANDARD ROD                            HIGH STRENGTH ROD
 Nominal               Working Loads          Working Loads          Working Loads           Working Loads
 Dia.                  Safety Factor =        Safety Factor =        Safety Factor =         Safety Factor =
                       2.5 Tension            5 Tension              2.5 Tension             5 Tension
 12mm (1/2”)             21.3 kN                10.6 kN               32.2 kN                 16.1 kN
 19mm (3/4”)             32.2 kN                16.1 kN               64.0 kN                 32.0 kN
 25mm (1”)               64.0 kN                32.0 kN               133.4 kN                66.7 kN

ADVANCED BUILDING                                           Unit 2/22 Violet Street, Revesby NSW 2212
                                                            PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                           Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                            Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                                   10
                                                          COIL LIFTING INSERTS

Although generally replaced by the Super Lift Insert, the Meadow Burke Coil Insert system is
suitable for lifting panels with exposed aggregate or other specialised surface treatments. The
small hole created by this type of insert facilitates patching of the surface. Coil Lifting Inserts
use 32mm diameter coil bolts.
SINGLE LIFTING INSERT (For use with single swivel lift plate).
                                                     Dual lifting inserts connected by a spacing
                                                     rod. For use with Double Angle Lift Plate or
                                                     strongback. Comes complete with caps and
                                                     seepage plugs.

                                                     N.B. When using lifting inserts with exposed
                                                     aggregate panels, it is recommended that one
                                                     size smaller than indicated be used to prevent
                                                     corrosion problems and facilitate patching.

                                   AVAILABLE IN SIZES: 125mm
                                                             150mm
                                                             175mm
DOUBLE LIFTING INSERT (For use with double angle lift plate)
                                                     32mm coil insert is large enough to provide
                                                     a safe lift, yet small enough to facilitate
                                                     patching of the surface.

                                                     Although replaced by the Superlift anchor,
                                                     this insert is still used as a lifting anchor on
                                                     some exposed aggregate panels.

                                                     AVAILABLE IN SIZES: 125mm
                                                                         150mm
                                                                         175mm

Working Loads in kN in 17 MPa Concrete, 2.5:1 Safety Factor
(This table shows loads based only on the dead load. The dead load should be increased at least 40%
to compensate for initial bond and impact). Additional increases due to unusual live loads distance
required to obtain the rated loads for face applications is twice the insert depth. For lightweight
concrete, reduce loads by the ratio of the concrete densities.

    Type of Lift                                 Nominal Slab Thickness in mm.
                                             125          150         175                    200
    SINGLE LIFT INSERT
    Tension                                37.01           40.78           44.48            46.98
    Shear                                  49.32           56.94           56.94            56.94
    DOUBLE LIFT INSERT
    Tension                                64.77           79.00           88.97            90.03
    Shear                                  83.34           97.15          106.05           113.168


ADVANCED BUILDING                                        Unit 2/22 Violet Street, Revesby NSW 2212
                                                         PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                        Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                         Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                             11
                                                                 FIXING FERRULES

HEXAGONAL CROSS-HOLE TYPE
                                               Used as a fixing insert for the panel connection to roof
Test results available.                        framing, floor slab and other structural members.

Manufactured from S1214 free cutting steel
(460 MPa), and finished with hot dip
galvanising to AS1214-1983.
Cross bars are manufactured from round mild
steel (250 MPA), and supplied in 300mm
lengths.




Available with screw cap,
feeler cap or nailing plate.
                                                   Working load in kN in
                                                   32 MPa concrete for
        A      B     C     D       E     F         Pullout with crossbar
                                                      Safety Factor 2.33:1
       12.0 65      20     8.0     8.0   44                  17.1
       16.0 75      24    10.0    11.0   44                  22.2
       20.0 100     28    12.0    12.7   50                  40.4                 Stainless steel grades
       24.0 100     32    12.0    12.7   50                  41.7                 303 and 316 also
       30.0 100     42    16.0    16.0   60                  46.0                 available on request.

FERRULE ACCESSORIES

FERRULE CHAIR                                     CAPS                            NAILING PLATE




                                 Feeler Cap   Push Cap      Screw Cap


ADVANCED BUILDING                                    Unit 2/22 Violet Street, Revesby NSW 2212
                                                     PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                    Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                     Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                           12
                                                                 THREADED REBAR

THREADED REBAR                   (For use with fixing ferrule)

Manufactured from plain             1.5 dia
grade 250R and deformed
grade 400Y bars are
required. Can be supplied
without thread for use in
dowelled joints in slabs and
walls. Lengths, shapes and
sizes as requested.




Threaded rebar and dowel bars can also be supplied hot-dipped galvanised, on request.




ADVANCED BUILDING                                     Unit 2/22 Violet Street, Revesby NSW 2212
                                                      PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                     Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                      Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                          13
                        BURKE SLOT INSERT




ADVANCED BUILDING   Unit 2/22 Violet Street, Revesby NSW 2212
                    PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.   Phone: (02) 9771 1011 Fax: (02) 9792 1414
                    Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                        14
                                                                    BURKE SLOT INSERT

                                                                                                  Patent Pending




        STRAP MODEL                               19mm N.C. NUT                       19mm COIL NUT

    Insert   Depth    Finish Weight      Insert     Depth    Finish Weight       Insert   Depth   Finish Weight
    Model                                Model                                   Model

    2M-STR   51mm     MILL      .69 kg   2M-NC      51mm     MILL       .73 kg   2M-CL    51mm    MILL    .73kg
    2G-STR   51mm     GALV      .68 kg   2G-NC      51mm     GALV       .77 kg   2G-CL    51mm    GALV    .77 kg
    3M-STR   76mm     MILL      .95 kg   3M-NC      76mm     MILL 1.04 kg        3M-CL    76mm    MILL   1.04 kg
    3G-STR   76mm     GALV     1.0 kg    3G-NC      76mm     GALV 1.09 kg        3G-CL    76mm    GALV 1.09 kg
    4M-STR 102mm      MILL   1.27kg      4M-NC 102mm         MILL 1.41 kg        4M-CL 102mm      MILL   1.41 kg
    4G-STR 102mm      GALV 1.32 kg       4G-NC 102mm         GALV 1.45 kg        4G-GL    102mm   GALV 1.45 kg



                     T-STRAPS                                       THREADED STRAPS

    ITEM     LENGTH WIDTH THICKNESS WEIGHT                   ITEM        LENGTH WIDTH THICKNESS WEIGHT

79606 (G)    152 mm    51 mm       9.5 mm          .73 kg   79706 (G)     152 mm    51 mm     9.5 mm      .64 kg
79608 (G)    203 mm    51 mm       9.5 mm          .91 kg   79708 (G)     203 mm    51 mm     9.5 mm      .82 kg
79610 (G)    254 mm    51 mm       9.5 mm         1.04 kg   79710 (G)     254 mm    51 mm     9.5 mm     1.04 kg
79612 (G)    305 mm    51 mm       9.5 mm         1.27 kg   79712 (G)     305 mm    51 mm     9.5 mm     1.22 kg


•    Economical Solution                                            •    A Jam Nut is supplied to accommodate
                                                                         the “Push-Pull” movement of wind
•    Weldable grade of steel.                                            loads.

•    Notch in strap assures positive connection to insert.          •    A Threaded Strap can be rotated to any
                                                                         angle.
•    Tee Head allows adjustment for erection tolerances.
                                                                    •    Allow secure placement into insert prior
                                                                         to final placement of the panel.




ADVANCED BUILDING                                              Unit 2/22 Violet Street, Revesby NSW 2212
                                                               PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                              Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                               Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com
                                                                                                                    15
                                                          BURKE SLOT INSERT

                                                                                       Patent Pending




       ANCHOR           TYPE OF               ULTIMATE LOADS IN kN
       POSITION         FORCE           51MM DEPTH           76MM DEPTH           102MM DEPTH

        FIELD          TENSION              59.6 kN              69.2 kN              85.5 kN

        FIELD          SHEAR                80.8 kN              89.0 kN              89.0 kN

        SIDE           TENSION              37.5 kN              59.9 kN              67.9 kN

        SIDE           SHEAR                40.4 kN              46.7 kN              46.7 kN

        CORNER         TENSION              35.4 kN              61.3 kN              79.8 kN

        CORNER         SHEAR                40.0 kN              44.2 kN              50.4 kN

        END            TENSION              18.7 kN              45.9 kN              62.3 kN

        END            SHEAR                68.7 kN              73.2 kN              80.1 kN



 1. Loads are based on full embedment in
    concrete with a minimum compressive
    strength of 34A N/mm2.

 2. Reinforcement as shown is required to
    achieve the corner location only.
    Reinforcement is not required to achieve the
    other indicated loads.

 3. Insert design gives full load capacities over
    the length of the slot.



ADVANCED BUILDING                                     Unit 2/22 Violet Street, Revesby NSW 2212
                                                      PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                     Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                      Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                          16
                                                        BURKE SLOT INSERT

                                                                                     Patent Pending




Designed for the Precaster




                                                                      12.7mm




                  DIMENSIONS FOR BURKE SLOT INSERTS
       MODEL          A             B             C               D        E           F

       2X-XX        51mm         165mm         54mm        16mm         25mm        114mm
       3X-XX        76mm         165mm         54mm        16mm         25mm        114mm
       4X-XX       102mm         165mm         54mm        16mm         25mm        114mm
 n   Nut or strap type slot inserts provide erection tolerance.
 n   High pull-out capacity (up to 89 kN).
 n   Sealed nut box prevents leakage.
 n   Perforated top quickly exposes slot for connection.
 n   Available in hot dip galvanised (ASTM A123/A153) or mill finish.

ADVANCED BUILDING                                     Unit 2/22 Violet Street, Revesby NSW 2212
                                                      PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                     Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                      Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                          17
                                                                 STOP SPALLING around your lifting inserts

                                                                                             PRE-CAST
BURKE RAPID-LIFT                         Versatile, Economical
Repeated lifting and moving of pre-      • Lifting Units are free to rotate 360° under load, saving man hours and
cast units calls for versatility in a      crane time at the plant and on the site.
lifting system. Burke Rapid-Lift is      • Burke Rapid-Lift System eliminates all labour costs associated with
Burke’s ‘no hang-up’ system for all        the cutting, weaving and burning-off of protruding lifting strand.
types of structural and architectural    • Low cost anchors are suitable for a variety of lifts.
pre-cast members including thin          • Even oblique pulls are possible in any direction with no time wasted
slabs. Combining economy with              fitting up shims or repositioning shackles and slings.
fast, smooth and safe handling,
Burke Rapid-Lift is ideal for beams,
piles, tees, wall and hollow core
panels - virtually every type of
precast element.
The Systems’ Three Major
Components
Lifting Units have a built-in safety
feature that only allows coupling of
anchors of the same capacity. Note:
Lifting Units are identical to tilt-up
lifting clutches.
Recessing Members secure the
anchors in place and form a void for
the lifting unit. They are available
in oil resistant plastic, throw-away
plastic, 4-hole plastic for medium
re-use, iron for greater use.
Anchors fabricated from high
quality steel are available in four
load capacities - 1.25, 2.5, 5 & 8
tonnes - which come in several
configurations to accommodate            1.25t BURKE RAPID-LIFT SYSTEM
virtually every type of pre-cast unit.   Because the needs of architectural pre-casters differ from manufacturers
                                         of structural panels, Burke has developed a special 1.25 tonne Burke
Quick, Safe
                                         Rapid-Lift Package.
• Ring clutches connect and
  disconnect quickly but cannot be
                                         Incorporating all the features of the standard Burke Rapid-Lift line, the
  accidentally disengaged.
                                         1.25 tonne system is designed especially for thin walled panels. Lifting
• Anchors and lifting units of
                                         Unit, galvanised Anchor, Recess Member, Shear and Tension Bars are all
  different capacities are not
                                         reduced in size to fit architectural applications.
  interchangeable to prevent
 coupling of incompatible units.
                                         Of Course, none of the components in the 1.25 tonne System will mate
Burke Rapid-Lift System                  with those of higher rated capacities.
Pre-cast Manual
For more information on Burke’s pre-     The most significant feature of this product is the single ear at the center
cast product line and engineering        of the 1.25 tonne Erection Anchor. This ear keeps the ring clutch from
service, please ask your Advanced        spalling the concrete.
Building Systems representative for a
Burke Rapid-Lift System Pre-cast         Accessories include a Two-Hole Plastic Recess Member instead of the
Manual.                                  standard Four-Hole and galvanised Shear and Tension Bars.

 ADVANCED BUILDING                                              Unit 2/22 Violet Street, Revesby NSW 2212
                                                                PO Box 113, North Revesby NSW 2212
 SYSTEMS PTY. LTD.                                              Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                                Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com
                                                                                                                        18
                                                                                    PRE-CAST

1 TONNE ERECTION ANCHOR
1.   The 2.5:1 safety factor is used with tilt-up, the
     load shown is dead load. The dead load should be
     increased by 40% to compensate for initial bond
     and impact. Additional increases due to unusual
     live loads or cable magnification may be required
     for some applications. To obtain the shear values
     shown, it is necessary to use the Burke Shear Bar
     or equivalent.

2.   The 4:1 safety factor is used in precast work and
     normally requires no increases.

3.   Given full embedment, reinforcement, and
     minimum compressive strength of 17.2 MPa
     (2500 psi). Erection Anchors should achieve a
     pullout strength equal to their ultimate
     Mechanical Strength if reinforced with the shear
     and tension bar.



                     Rated Loads for Panel Rotation and Edge Lifts in Tension.

       Ring Clutch        Minimum          2.5:1 Safety 1     4:1 Safety 2       4:1 Safety 3
        Load              Panel            1 Factor            Factor            Factor
                          Thickness        Shear              Tension            Tension
                          (mm)
       1.25 tonne          76.2            4.35 (kN)           6.67 (kN)         8.90 (kN)

     This table shows loads based on the dead load only at 17.2 MPa (2500 psi) concrete strength.




ADVANCED BUILDING                                        Unit 2/22 Violet Street, Revesby NSW 2212
                                                         PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                        Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                         Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                             19
                                                                                  PRE-CAST

ANCHORS
The four standard Burke Rapid-Lift anchors together with the Hairpin Anchor are designed to handle
nearly every pre-cast panel currently in production. Regardless of use, each size anchor - 1.2 5, 2.5, 5
and 10 tonne - is matched to an equivalent size lifting device. The feature makes Burke Rapid-lift
anchors as safe to use as they are easy to install. Your Advanced Building Systems representative will
help select the best anchor for your particular application.
SPREAD ANCHOR
The most versatile anchor in the Burke Rapid-Lift
line, the Spread Anchor can be used for stripping and
erecting and in tension and in shear loads (except
edge shear in thin panels). Its spread feet design
produces high pull-out strength and allows for back
stripping of panels as well as rotation from horizontal
to vertical.
TWO-HOLE ANCHOR
The bottom hole in this anchor is located well
beneath the concrete line. Thread this hole with a          Spread Anchor
tension bar, as specified in the Pre-cast Manual, to
achieve a pull-out load equal to the ultimate
mechanical load. This allows lifting of very thin wall
panels that must be handled at low compressive
strengths, as well as panels made of lightweight                                      Erection Head
concrete. Often used for high tension loads which                                     Two-Hole Anchor
cannot be resisted with spread anchors.
PLATE ANCHOR
The low profile and wide, flat base of the Plate
Anchor make it ideal for face and brick lifts of thin-
walled units. The horizontal plate welded to the
bottom gives the anchor high pull-out strength in
stripping, handling and erection applications.
FLAT FOOT ANCHOR
The Flat Foot Anchor is perfect for back-stripping
and for lifting thin-walled units. Slightly less
expensive than the Plate Anchor, this unit permits
                                                           Two-Hole Anchor            Flat Foot Anchor
lifting of all but the thinnest panels.
ANCHORS FOR SPECIAL APPLICATIONS
By delivering even load distribution to both wythes of
a sandwich panel, the Sandwich Panel Erection
Anchor eliminates the need for special lifting devices.
This anchor absorbs shear load without
spalling the concrete.                                     Sandwich Panel
Combining the reinforcing capabilities of the Two-                                 Plate Anchor
Hole Anchor with the spall-free performance of the
Erection Anchor, The Erection Head Two-Hole
Anchor is ideal for lifting from an ‘A’ frame or tilt
table or whenever the lift is not straight up. Designed
solely for hollow core wall panels, the ingenious
Hollow Panel Anchor installs without bolts or
hardware for fast, safe lifts.                                       Hollow Panel Anchor

ADVANCED BUILDING                                       Unit 2/22 Violet Street, Revesby NSW 2212
                                                        PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                       Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                        Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com
                                                                                                            20
                                                                                     PRE-CAST

SPREAD ANCHOR
The minimum cover below the feet of the anchor
should be at least 20mm (3/4”).

In those situations where the anchor must be placed
near the edge (Anchor to Edge distance less than
Min. Anchor-Edge Distance), the load capacity of the
anchor will be reduced. Consult Advanced Building
Systems in those situations.

For installations, see Section Erection Anchor on
recessing member.

The 2.5:1 safety factor is used in tilt-up work. The
loads are based on the dead load. The dead load
should be increased at least 40% to compensate for
initial bond and impact. Additional increases due to
unusual live loads or cable angle magnification may
be required for some job conditions.

The 4:1 safety factor is used in precast work and
normally requires no increases except for cable
magnification.

NOTE: For Designers and Engineers
Based on a 5:1 safety factor for reusable lifting
devices under AS Code 3850 You should be aware
that our 2.5t and 10t Clutch when used with Spread
Anchors, that the insert working load limit is limited
by the working load limit of the Clutch.


               Ring Clutch      Min. Anchor - Edge       Working 1 Load      Working 2 load
               Load Range       Distance (mm)            (kN) 2.5:1          (kN) 4:1

               2.5 tonne              137                    14.24               8.90
                                      156                    28.46              17.79
                                      118                    28.46              17.79

               5 tonne                178                    54.27              35.58
                                      261                    54.27              35.58

               10 tonne               310                    113.87             71.17

            Working loads are based on concrete compressive strength = 17.2 MPa (2500 psi).



ADVANCED BUILDING                                        Unit 2/22 Violet Street, Revesby NSW 2212
                                                         PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                        Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                         Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                             21
                                                                                   PRE-CAST

TWO HOLE ANCHOR
1. 2.5:1 Safety factor is used for tilt-up work. The loads
   shown based only on dead load which should be
   increased by 40% to compensate for initial bond and
   impact. Additional increases due to unusual live loads on
   cable angle magnification may be required for some job
   conditions.

2. 4:1 Safety factor is used in precast work and normally
   requires no increases in dead load except for cable
   magnifications.

NOTE: For Designers and Engineers
Based on a 5:1 safety factor for reusable lifting devices under
AS Code 3850 you should be aware that our 2.5t and 10t
Clutch,when used with Two Hole Anchors, that the insert
working load limit is limited by the working load limit of the
Clutch.


                  RING CLUTCH                  Working Load 1              Working Load 2
                  LOAD RANGE                       2.5:1                        4:1

                      2.5 tonne                     28.47 kN                    17.79

                      5 tonne                       54.27 kN                    35.58

                      10 tonne                     113.87 kN                    71.17

*Note: Given full embedment, reinforcement, and a minimum compressive strength of
10.34 MPa (1500 psi), Two Hole Anchor should achieve above Working Loads.
Minimum Reinforcing Length (R)
Needed to Develop the Nominal strength of Anchor.


              Load Group Rebar            2.5 tonne            5 tonne           10 tonne
                    Size                     R10                 Y12               Y20
             10.34 MPa* (1500 psi)         0.91 m               1.22 m            1.83 m

             13.79 MPa* (2000 psi)          0.84 m             1.07 m             1.68 m

             20.69 MPa* (3000 psi)          0.76 m             0.91 m             1.37 m

            * Concrete strength at time of lift.


ADVANCED BUILDING                                       Unit 2/22 Violet Street, Revesby NSW 2212
                                                        PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                       Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                        Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                            22
                                                                                   PRE-CAST

PLATE ANCHOR
1.    2.5:1 safety factor is used for tilt-up work. (This table shows loads based only on the dead load.
     The dead load should be increased at least 40% to compensate for initial bond and impact).
     Additional increases due to unusual live loads or cable angle magnification may be required for
     some job conditions. The minimum edge distance required to obtain the rated loads for face
      applications is twice the insert depth. For lightweight concrete, reduce loads by the ratio of the
     concrete densities.

2.   4:1 safety factor is used in precast work and normally requires no increase except for cable
     magnification.
NOTE: For Designers and Engineers
Based on a 5:1 safety factor for reusable lifting devices under AS Code 3850, you should be aware
that our 2.5t Clutch, when used with Plate Anchors, that the insert working load limit is limited by
the working load limit of the Clutch.

        Ring Clutch      Allowable 1       Allowable 1       Allowable 2        Allowable 2
        Load Range       unreinforced       reinforced       unreinforced        reinforced
                         Tension Load      Tension Load      Tension Load       Tension Load
                         Safety Factor     Safety Factor     Safety Factor       Safety Factor
                            2.5:1*            2.5:1**             4:1*               4:1**

         2.5 tonne          5.69 kN          28.47 kN           3.56 kN           17.79 kN

         5 tonne           18.50 kN          54.27 kN          11.56 kN           35.58 kN

* Values are for tension in 17.2 MPa (2500 psi) standard weight concrete with minimum Edge
distance of 73mm for 2 tonne Plate Anchor, or minimum Edge distance of 130mm for 4 tonne Plate
Anchor.

** Values are for tension in 20.69 MPa (3000psi) standard weight concrete with a minimum edge
distance of 254mm (10”), using Y12(#4) rebar cut to length of 458mm (18”) as described.


                                                                    Reinforcement




ADVANCED BUILDING                                       Unit 2/22 Violet Street, Revesby NSW 2212
                                                        PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                       Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                        Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                            23
                                                                                 PRE-CAST

FLAT FOOT ANCHOR
2.5:1 safety factor is used with tilt-up work, the loads shown are based on dead load, which should
be increased by 40% to compensate for initial bond and impact. Additional increases due to unusual
live loads on cable angle magnification may be required for some job conditions.

4:1 safety factor is used with precast work and requires no increase except for cable magnification.

NOTE: For Designers and Engineers
Based on a 5:1 safety factor for reusable lifting devices under AS Code 3850, you should be aware
that our 2.5T Clutch, when used with Flat Foot Anchors, that the insert working load limit is limited
by the working load limit of the Clutch.

WITHOUT REINFORCEMENT
  Ring Clutch         Height          Allowable           Allowable         Min. Edge
  Load Range                         Tension Load        Tension Load       Distance
                                       S.F. 2.5:1          S.F. 4:1
    2.5 Ton           2-3/4”           7.97 kN             4.98 kN               86
    2.5 Ton           3-3/8”          11.39 kN             7.12 kN              102
      5 Ton           3-3/4”          14.23 kN             8.90 kN              115
    10 Ton            6-1/4”          39.30 kN            24.56 kN              190

1. NOTE: Values are for tension in 17.2 MPa (2500 psi), standard weight concrete, with
  minimum edge distanced shown above. Consult A.B.S. for other edge distance or
  concrete strength.
WITH REINFORCEMENT
  Ring Clutch Load          Height        Allowable Tension        Allowable Tension
      Range                               Load Safety Factor       Load Safety Factor
                                                2.5:1                     4:1
        2.5 Ton             2-3/4”             28.47 kN                 17.79 kN
        2.5 Ton             3-3/8”             28.47 kN                  7.79 kN
          5 Ton             3-3/4”             42.71 kN                 26.69 kN
        10 Ton              6-1/4”             33.37 kN                 53.39 kN

2. NOTE: Values are for tension in 20.68 MPa (3000 psi) standard weight concrete with
  a minimum edge distance of 254mm (10”) using Y12 rebar cut to length of 458mm (18”).

      Reinforcement




ADVANCED BUILDING                                    Unit 2/22 Violet Street, Revesby NSW 2212
                                                     PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                    Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                     Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                         24
                                                                                 PRE-CAST

SANDWICH PANEL ERECTION ANCHOR
1. The 2.5:1 safety factor is used with tilt-up work. The loads shown are dead load which
   should be increased by 40% to compensate for initial bond and impact. Additional increases
   due to unusual live loads or cable magnification may be required for some applications.

2. The 4:1 safety factory is used with precast work and normally requires no increases except for
   cable magnification.

3. Given full embedment, reinforcement, and a minimum compressive strength of 22.75 MPa
    (3300 psi), the 4 Ton Sandwich Panel Erection Anchors should achieve a pullout strength
    equal to their ultimate Mechanical strength if reinforced with (2 # 3Ø x 2’-6”) 2 R10 x
    762mm long bent as shown in section 2.6 of the Rapid-Lift Manual.

4. Given full embedment, reinforcement, and a minimum compressive strength 31.02 MPa (4500
    psi), the 8 Ton Sandwich Panel Erection Anchor should achieve a pullout strength equal to
    their ultimate Mechanical strength if reinforced with 2 R16 x 1067mm long bent as shown in
    section 2.6 of the Rapid-Lift Manual.
   3:2:3 (22.75 MPa Concrete)

                               Shear-Parallel            Tension 2          Shear-perpendicular 1
                              // to thickness 1                                to thickness 2
           5 Ton                  24.47 kN              35.58 kN 3                35.58 kN

          10 Ton                  21.28 kN              71.17 kN 4                41.81 kN



    4:2:2 (31 MPa Concrete)
                               Shear-Parallel            Tension 2         Shear-perpendicular 1
                              // to thickness 1                                to thickness 2
           5 Ton                  23.43 kN              35.58 kN 3                35.58 kN

          10 Ton                  24.61 kN              71.17 kN 4                46.70 kN




ADVANCED BUILDING                                    Unit 2/22 Violet Street, Revesby NSW 2212
                                                     PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                    Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                     Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                         25
                                                                                           PRECAST

ERECTION ANCHOR                       2.5t, 5t, 10t
w/SHEAR PLATE
The Erection Anchor with Shear
Plate is specifically designed for
horizontal to vertical edge pulls and the
shear rotation of thin-walled units. Two
steel protusions or “ears” on the head of
the anchor provide added protection against
spalling. These protrusions hug either side of
the ring clutch, restricting its rotation during
lateral pulls. As a result, lateral forces are transmitted directly to
the edges of the anchor instead of the concrete. The shear plate of
this Erection Anchor is positioned to resist shear loads for spall-
free rotation. No shear reinforcement is required.

Reinforcement

The stress caused by the shear lift of a thin panel is resisted by the shear plate.

While the panel is being rotated on its edge, the load can usually be factored by 0.5. During this phase
of the lift, the anchors are not bearing the full weight of the panel. The rated loads and minimum
panel thicknesses can be found in the accompanying table.

During rotation, it is recommended that the sling angle be perpendicular to the surface.

Once the panel has been rotated to vertical, the tension lift is initiated. During the tension phase of the
lift, the Erection Anchor with Shear Plate will work like the Spread Anchor or the Two Hole Anchor.
A glance at the accompanying table will show that there are two sets of data. If the higher loads are
desired, additional reinforcement should be placed through the lower hole of the anchor. Consult the
reinforcement charts for rebar length, diameter, and bend angle.

 Ring A** B** C** D** Weight Min.
 Clutch                Per   Panel                               n    Erection Anchors with Shear Plate
 System mm mm mm mm Piece Thickness                                   eliminate the need for shear bars,
                                                                      making them easier to install.
 2.5T      63.5    19 76.2 6.4         .96kg    88.9mm
                                                                 n    Erection Anchors with Shear Plate can
 5T        63.5 31.8 76.2 9.5 2.24kg 101.6mm                          be placed in thinner panels than the
                                                                      erection Anchors with Shear Bars.
 10T       76.2 41.3 88.9 9.5 3.76kg 178mm
                                                                 n    No special ring clutch or recessing
 10T       76.2 41.3 88.9 9.5 4.69kg 178mm                            members required.


** See standard Erection Anchor for all other dimensions.
NOTE: Erection Anchor with double shear plates available special order.

ADVANCED BUILDING                                             Unit 2/22 Violet Street, Revesby NSW 2212
                                                              PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                             Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                              Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                                  26
                                                                                                     PRECAST

    ERECTION ANCHOR
    w/SHEAR PLATE 2.5t, 5t, 10t
Ring          Panel           SHEAR            SHEAR                     TENSION                 TENSION
Clutch        Thickness        Safety Factor 1 Safety Factor 2           w/oTension Bar          w/Tension Bar
               in mm           2.66:1          4:1                       Safety Factor 2,3       Safety Factor 2,3
                                                                         4:1                     4:1

2.5t            89 min             9.6 kN               6.4 kN                 11.7 kN                 17.8 kN

2.5t              102             13.0 kN               8.7 kN                 14.2 kN                 17.8 kN
    2.5t          114             13.5 kN               9.0 kN                 15.8 kN                 17.8 kN

    2.5t          127             14.0 kN               9.3 kN                 17.3 kN                 17.8 kN

    5t         102 min            12.0 kN               8.0 kN                 15.1 kN                 35.6 kN

    5t            114             16.5 kN              11.0 kN                 17.2 kN                 35.6 kN

    5t            127             17.8 kN              11.8 kN                 21.0 kN                 35.6 kN

    5t            140             18.5 kN              12.3 kN                 22.1 kN                 35.6 kN

    5t            152             19.1 kN              12.7 kN                 23.0 kN                 35.6 kN

    10t        178 min            26.8 kN              17.8 kN                 31.6 kN                 53.4 kN

    10t           190             26.8 kN              17.8 kN                 32.1 kN                 53.4 kN

    10t           203             26.8 kN              17.8 kN                 34.2 kN                 53.4 kN
    10t       178min              26.8 kN             17.8 kN                  31.6 kN                 71.2 kN

    10t           190             26.8 kN             17.8 kN                  32.1 kN                 71.2 kN

    10t           203             26.8 kN             17.8 kN                  34.2 kN                 71.2 kN

(shear bar not required)                  USE THESE VALUES       USE THESE VALUES IF PANEL IS LIFTED FREE OF
                                          IF PANEL IS TILT-UP    GROUND AND ANCHORS ARE STILL IN SHEAR.

*This anchor uses the10 tonne recessing member and ring clutch (shear bar not required).
1
 2.66:1 safety factor which is commonly used when stripping, increased 33% to compensate for initial bond and impact.
Additional increases due to unusual live loads or cable magnification may be required for some applications. To obtain
the shear values shown, it is not necessary to use the Burke Shear Bar when using the Erection Anchor with Shear Plate.
2
    The 4:1 safety factor is used with precast work and normally requires no increases except for cable magnification.
3
  Given full embedment and reinforcement, and a minimum compressive strength of 3,500 psi, Erection Anchors should
achieve a pullout strength equal to their Ultimate Mechanical Strength if reinforced like Two-Hole Anchors. See the
standard Erection Anchor tension reinforcement chart.
                                                                  Unit 2/22 Violet Street, Revesby NSW 2212
ADVANCED BUILDING                                                 PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                                 Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                                  Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                                          27
                                                                  ERECTION ANCHORS

ERECTION ANCHOR                                                                  COMPLIES WITH AS 3850
The erection anchor is specially                           Anchor can also be supplied
designed for horizontal to vertical                        hot-dipped galvanised on request
edge pulls and the shear rotation of
thin-walled units. Two steel
protrusions on the head provide
added protection against spalling.
These protrusions hug the two
sides of the ring clutch to give
added support when pulled
laterally. Notches on the sides of
the anchor accept reinforcement for
                                               Available       Length       Superlift
spall-free panel rotation.
                                               in Sizes                     Clutch
Additional tension bar can be
placed through the centre holes to                 2.5t        208mm        2.5 tonne
achieve the nominated rated load in                 5t         267mm          5 tonne
tension.                                           10t         325mm        10 tonne
RECESSING MEMBER
                                                                     Nailing
The recessing member holds the anchor firmly in
                                                                     Plate       Reusable PVC recess former
place during casting and creates a void in the
concrete into which the ring clutch head will fit.
Available in REUSABLE or SINGLE USE grades.
DIMENSIONS
Reusable                 Length      Width         Depth
2.5t       Orange        104mm       43mm          45mm
 5t        Black         126mm       49mm          59mm
10t        Green         188mm       67mm          85mm              Not to scale
Disposable Yellow
REINFORCEMENT                                                        Additional A.B.S. Shear Bar where
Shear Bar                                                            panel may be lifted from opposite side.
The Shear Bar provides simple and
economical reinforcement for the erection
anchor during the rotation phase of edge lifts.
The loop of the shear bar fits over the erection
anchor and spreads the shear stress over a
wide area. It is stronger, less expensive and
easier to use than fabricated rebar.
Tension Bar
The tension bar is fitted through the hole in
the erection anchor when a Factor of Safety
exceeding 2.5:1 is required. The tension bar
will provide extra tension capacity for edge
tension lifts up to the full tension capacity of
the anchor
ADVANCED BUILDING                                            Unit 2/22 Violet Street, Revesby NSW 2212
                                                             PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                            Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                             Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                                 28
                                                                ERECTION ANCHORS

   Working Loads in kN, without tension bar, in 17 MPa Concrete 2.5:1 Safety Factor for Tilt-Up.
  (This table shows loads based only on the dead load. The dead load should be increased at least 40%
  to compensate for initial bond and impact). Additional increased due to unusual live loads or cable
  angle magnification may be required for some job conditions. The minimum edge distance required
  to obtain the rated loads for face applications is twice the insert depth. For lightweight concrete,
  reduce loads by the ratio of the concrete densities.
                      Type of Lift                       Nominal Slab Thickness in mm.
                                                        125 140 150 175 200                      225   250
                             2.5t Edge
                                  Tension              23.54 25.66 26.38 28.46 28.46 28.46 28.46
                             2.5t Edge
                                  Shear               12.67 13.88 15.16 17.26 19.07 20.57 21.95
                             5t Edge
                                  Tension                    29.89 29.89 35.58 35.58 35.58 35.58
                             5t Edge
                                  Shear                      16.18 17.79 19.07 20.58 21.95 23.20
                              10t Edge
                                    Tension                                       44.13 45.19 45.19
                              10t Edge
                                    Shear                                         24.13 24.72 25.8
  NOTE: For Designers and Engineers
  Based on a 5:1 safety factor for reusable lifting devices under AS Code 3850, you should be aware that
  our 2.5t and 10t Clutch ,when used with Erection Anchors, that the insert working load limit is limited
  by the working load limit of the Clutch.
                          Shear values are based on using Erection Anchor Shear Bars as shown.
  Working Loads with tension bar.




ANCHOR/        Minimum Slab    Minimum Edge        Working Loads With   Minimum Tension Bar Dimensions
TYPE OF         Thickness        Distance          Tension Bar in 17MPa Needed to Develop Full Tension
 LIFT             T                  A            Concrete              Capacity of Anchor.
                                                   2.5:1 Safety Factor
                                                  (Note 1)              DIAMETER            LENGHT
2.5T Tension    102mm           200mm                    28.46            R10mm              850mm
5T Tension       140mm          300mm                    54.27            Y12mm             1050mm
10T Tension     203mm           400mm                  113.86             Y20mm             1700mm

  Note 1: Safety factor for Tilt-up to comply with Tilt-Up Construction - AS 3850
  Note 2: Safety factor for precast to comply with AS 3850.3

  ADVANCED BUILDING                                        Unit 2/22 Violet Street, Revesby NSW 2212
                                                           PO Box 113, North Revesby NSW 2212
  SYSTEMS PTY. LTD.                                        Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                           Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                               29
                                                                                                 PRE-CAST

5T HAIR PIN EDGE LIFT ANCHOR                                                                               A
The Hairpin Anchor has gained wide popularity since it has been
designed to allow the use of centrally located steel mesh.

Advanced Building Systems P/L supplies with these anchors either:-

1.     A Disposable Plastic Void Former.
2.     A reusable Rubber Void Former with or without a Nailing Plate.

Shear Bars must be used when edge lifting from the horizontal.

It comes galvanised.
                                                                                             B
SHEAR LOADS
 5t Hairpin Anchor             Ultimate Load Ultimate Load
                                   (kN)          (Kg)
       25MPa                       17.9          1825                                                              C
       40MPa                         31.7                  3230
Safety Factor 2.5.1 tests by a Certified Testing Laboratory verify a
                                                                                                           D
Working Load Limit of 5 tonne.
                                                                                                           E
TENSION LOADS
Ensure heavy mesh reinforcement and perimeter bars are used
                                                                                                   A   =   65mm
to gain WLL of 5T for tension lift in 150mm thick panels.
                                                                                                   B   =   250mm
                                                                                                   C   =   16mm
                                                                                                   D   =   37mm
PLASTIC DISPOSABLE RECESSING MEMBER                                                                E   =   70mm

Made of high density polyethylene, the recessing
member holds the Rapid-Lift Anchor in place during
casting and creates a narrow, semicircular recess in
the concrete for the ring clutch. The disposable
recessing member is available in two and four ton sizes.

Installation:
1. Nail plastic holding plate to wood bulkhead.
2. Place recessing member on anchor.
3. Slide recessing member & anchor over holding plate.
4. Nail recessing member to bulkhead.

      Description       H           I            J           K             P        Q

        2-Ton        50.8mm      38.1mm       84.08mm       9.52mm       38.1mm    8mm

        5-Ton        63.5mm     57.15mm      109.5mm      15.88mm        50.8mm   127mm




 ADVANCED BUILDING                                                   Unit 2/22 Violet Street, Revesby NSW 2212
                                                                     PO Box 113, North Revesby NSW 2212
 SYSTEMS PTY. LTD.                                                   Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                                     Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                                         30
                                   BRACES
                  MEADOW BURKE SUPER BI-POD

      STOP PRESS
      New Unsupported Braces available June 05
      n       13.00 metres
      n       15.85 metres




     W.W.L. 32kN ON BI-POD USING 2 SUPER BRACES




ADVANCED BUILDING            Unit 2/22 Violet Street, Revesby NSW 2212
                             PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.            Phone: (02) 9771 1011 Fax: (02) 9792 1414
                             Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                 31
                                                      BRACES
                                     MEADOW BURKE SUPER BI-POD

n    ADD THE SUPER BI-POD KIT TO A BURKE SUPER BRACE - Create a
     Brace that will support tall panels up to 19.8 metres high with 4893kg ultimate
     capacity. A Burke Super 6.7 Brace may be combined with another Super 6.7
     Brace (fig. 1). Extension (fig. 2) to make a Bi-Pod Brace.

n    SUPER BI-POD SOLVES KNEE BRACE AND CROSS LACING
     PROBLEMS -

     n     Bi-Pod   adjusts to plumb panel.
     n     Bi-Pod   requires less labour.
     n     Bi-Pod   reduces floor clutter.
     n     Bi-Pod   does not require a ladder to attach bracing.

n    EASY TO HANDLE - Two part design breaks down to permit handling by only
     two people.

n    EASY TO INSTALL - All components can be raised with the wall panel and
     rotated into position.

n    EASY TO ADJUST - Doka Screw and Center Swivel combine to permit easy
     adjustment.




                                      Brace          Panel               Ultimate           Total
    Super Bi-Pod Assembly             Length      Height Range         Strength (kg)        Weight

    Super 6.7 + Super 6.7 w/Sleeve    13 metres   9.45m to 19.8m           4893kg            163kg




ADVANCED BUILDING                                  Unit 2/22 Violet Street, Revesby NSW 2212
                                                   PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                  Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                   Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                       32
                                                         BRACES
                                        MEADOW BURKE SUPER BI-POD

                                                                                                             (E)
4.   On the Floor End Brace (A) install the Centre Swivel (E) into                         (K)
     Brace (A). Do this by inserting the Swivel into the Pipe and
     installing the two Set Screws (K) with an Allen Wrench.
     Note: Set Screws must be screwed in as far as possible.



                                                                                                        (K)

                                                                                         (A)




                      Floor End



                                                                                                               Panel End


5.   First, slip the Sleeve (M) over the Centre Swivel onto Brace (A)
     that attaches to the Floor, align the Bi-Pod Leg Assembly (B)
     with the lower Sleeve hole and insert the Bolt and Nylock      Nut (N).
     Second, slip the Sleeve (M) onto Extension (C) that
                                                              (N)
     attaches to the Panel and insert the Bolt and
                                                                                                 (C)
     Nylock Nut (N).



                                                                           (M)                                 Panel End

Floor End
                                  (A)
                                                                     (B)




6.   The assembly is now complete and
     should look like this.




                                                                     Parts not needed for this application

Floor End




 ADVANCED BUILDING                                       Unit 2/22 Violet Street, Revesby NSW 2212
                                                         PO Box 113, North Revesby NSW 2212
 SYSTEMS PTY. LTD.                                       Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                         Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                                           33
                                                    BRACES
                                   MEADOW BURKE SUPER BI-POD


                         BI-POD BRACE INSTALLATION

1. Follow Bi-Pod Brace Assembly instructions for your style
   of Bi-Pod, leaving the Upper brace or Extension out of the
   center sleeve so the brace is in two pieces. To assist in
   handling, tie the Bi-Pod legs to the lower brace with tie
   wire (fig. 1).
2. Using two people, take the upper portion of the brace to the
   panel and connect the shoe with a 19mm Burke Coil Bolt to
   the Burke B-75 Coil Insert embedded in the panel (fig.2).
3. Using two people, take the lower portion of the brace to the
   panel and insert its upper end into the sleeve and attach
   with Bolts and Nuts.

4. Repeat this operation for the other braces on this panel.
5. Erect the panel being certain that the brace or Bi-Pod legs
   do not strike the floor during the erection.
6. After the panel base is set in its final position and while the
   crane is still balancing the panel, connect the shoe on the
   lower end of the brace to the floor slab using a Burke Super
   Bolt or 19mm coil bolt into an embedded Burke floor slab
   insert (fig. 3).
7. Install a temporary support under the centre of the brace
   length to maintain the brace straightness (fig. 4).
8. Disconnect the tie wire holding the Bi-Pod legs to the main
   brace.
9. Rotate a Bi-Pod leg over to the wall about 1.52m from the
   centreline of the brace and mark for an expansion anchor
   drill hole (fig. 5).

10. Drill the hole and install the expansion anchor which
    connects the Bi-Pod shoe to the wall.

11. Repeat steps 10 and 11 for the other Bi-Pod leg and then
    remove the temporary support.

12. Repeat for other braces on the panel until the panel is
    completely braced.

13. With all the bracing in place, the panel can now be plumbed
    by turning the lower main pipe (fig. 6).




ADVANCED BUILDING                                     Unit 2/22 Violet Street, Revesby NSW 2212
                                                      PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                     Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                      Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                          34
                                                                                   BRACES
                                                                                    13m
SUPER BRACE
Minimum 6.5m - Maximum 6.95m
0.75m, 1.1m,1.5m, 2.25m, 3.0m extension kits
available.
                                                                                               9m
Super Brace combines high strength with light
weight for easy handling and solid support of tilt-
up panels. The fixed length Super Brace handles
different panel heights by varying the angle of the
brace. The Super Brace is 6.5m long and can
support walls from 5m up to 9m above finished
floor level. Extensions are available for use with                                                  5m
higher panels, up to 13m. It has 450mm of easy
adjustment for final setting of brace and plumbing
corrections.
NOTE: Obtain Brace Design Data Sheet from ABS.
                                                                60 o
                                                      with extension              45 o
SUPER 17                                               without extension
                                                           without extension
Minimum 4.95m - Maximum 5.40m
0.75m, 1.1m, 1.5m, 2.25m, 3.0m extension kits                                        10m
available.

A shorter form of Super Brace. For panels from
4m to 11m above floor level.
                                                                                               6m
MINI-SUPER BRACE
Minimum 4.2m - Maximum 4.65m
0.75m, 1.1m, 1.5m, 2.25m, 3.0m extension kits
available.
                                                                                                    4m
The Mini-Super Brace is shorter, lighter, with all
the features of the Super Brace. The Mini-Super is
4.20m long with 450mm adjustment and can                               60 o
support walls 4m up to 6m above finished floor
level. Extensions are available for use with higher
                                                            with extension
                                                           without extension        45 o
                                                              without extension
panels up to 10m.
                                                                                               5m
BABY BRACE
Telescoping Brace - 2.3m to 3.95m
Normally used for panel heights up to 5m above
                                                                                                    2m
finished floor level. Steel pipe sections telescope
for continuous adjustment. A doka rod at the
bottom of the brace provides 450mm of
adjustment for final setting of brace and panel                                     o      o
plumbing correction.                                                 with extension 60 45
                                                                     without extension
ADVANCED BUILDING                                     Unit 2/22 Violet Street, Revesby NSW 2212
                                                      PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                     Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                      Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                          35
                        Note:- When designing bracing insert locations make
                        sure they fit within the brace dimensions below. For                   BRACES
                        your assistance see bracing guide following.

 WORKING LOADS
                        Extensions                Length (m)                        Safety Factor = 2
                     available (m)              Min.      Max.                        W.L.L. (kN)
  SUPER BI POD                --               12.70        13.15                       31.80
  SUPER                      --                 6.50         6.95                      31.80
                            0.75                7.25         7.70                      26.30
                            1.10                7.70         8.10                      25.70
                            1.50                8.00         8.45                      21.90
                            2.30                8.80         9.25                      18.30
                            3.05                9.55        10.00                      15.60
  SUPER 17                   --                 4.95         5.40                      31.80
                            0.75                5.70         6.15                      31.80
                            1.10                6.05         6.50                      31.80
                            1.50                6.45         6.90                      31.80
                            2.30                7.25         7.70                      26.30
                            3.05                8.00         8.45                      21.90
  MINI-SUPER                 --                 4.20         4.65                      31.80
                            0.75                4.95         5.40                      31.80
                            1.10                5.30         5.75                      31.80
                            1.50                5.70         6.15                      31.80
                            2.30                6.50         6.95                      31.80
                            3.05                7.25         7.70                      26.30
  BABY                       --                 2.30         3.95                      31.80
                                                                                       18.60 Fully extended
  SUPER 13                                     12.81        13.26                      17.88

  SUPER 16                                     15.87        16.32                      12.84
                          Safety factor as per AS 1250 SAA Steel Structures Code

 THE BEST TILTBILT BRACES IN THE WORLD!
 n      Brace Lengths 2.3m to 16.32m.

 n      Appropriate Working Load Limit
        in Accordance with AS 3850.

 n      Rugged construction.

 n      Easy to use.                                        Self lubricating
                                                            Doka rod - Clog free.
 n      Only available for hire.

TILTBILT braces are designed for use only in conjunction with
tilt-up precast concrete construction. Due to the problems inherent
in bracing masonry walls, Advanced Building Systems Pty Limited
assumes no responsibility if braces are used to support concrete
block, brick or other masonry walls.


 ADVANCED BUILDING                                          Unit 2/22 Violet Street, Revesby NSW 2212
                                                            PO Box 113, North Revesby NSW 2212
 SYSTEMS PTY. LTD.                                          Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                            Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                                36
                                                                              BRACE GUIDE

                                             GUIDE FOR

                             TILT-UP WALL PANEL BRACING

                                   KEEP THIS DATA ON FILE

The reason for producing this guide is to help Engineers, Architects and Contractors in selecting
suitable Tilt-Up temporary brace sizes when completing work shop drawings and panel layouts.

Advanced Building Systems has the largest stock of Tilt-Up braces. These braces are for hire and are
maintained by Advanced Building Systems in accordance with Australian Standard 3850.

Here are some bracing set out design recommendations.

1.   Do not locate the wall brace inserts above the lifting inserts or the structural steel inserts, as the
     braces will foul the rigging. Locate the wall brace inserts either under or to one side of the
     lifting inserts.

2.   Locate the wall brace inserts 900-1000mm from the sides of the wall panels.

3.   Offset braces 300mm away from each other in the corners.

4.   DO NOT BRACE one panel to another panel for structural support.

5.   Brace angles can vary from 45° to 60° the ideal brace angle is 60° to the horizontal.

6.   The vertical panel dimension for the wall brace calculation should be measured from the
     finished floor level.

7.   Check when setting out ground brace inserts, make sure the measurements are taken from the
     inside face of the panel.

8.   Whilst awaiting the installation of the roof steel make daily checks on the tightness of the coil
     bolts connected to the panels and floor.

The following brace sizes are available ex-factory.

Any variation to these brace sizes requires:-

1.   4 days notice for assembly.
2.    Assembly charge of $15.00 per brace plus the hire charge for the extension.



 ADVANCED BUILDING                                       Unit 2/22 Violet Street, Revesby NSW 2212
                                                         PO Box 113, North Revesby NSW 2212
 SYSTEMS PTY. LTD.                                       Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                         Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                              37
38
      Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com
      Phone: (02) 9771 1011 Fax: (02) 9792 1414                                                SYSTEMS PTY. LTD.
      PO Box 113, North Revesby NSW 2212
      Unit 2/22 Violet Street, Revesby NSW 2212
                                                                                               ADVANCED BUILDING
               * WWL = Working Load Limit.
                        insert.
                     = The horizontal distance from the inside face of the panel to the ground brace                                  * H
                     = The Vertical height for the finished floor level to the wall brace insert.                                     * V
           12.84 kN                  60°                 7940               13990                 16085                         Super 16
           17.88 kN                  60°                 6430               11340                 13035                         Super 13
            31.8 kN                  60°                6370                11245                 12925                   Bi Pod Brace
            15.6 kN                  60°                 4820               8504                  9775              + 3050 Extension
            18.3 kN                  60°                 4450               7852                  9025              + 2300 Extension
            21.9 kN                  60°                 4050               7156                  8225              + 1500 Extension
           30.30 kN                  60°                 3860               6808                  7825             + 1100 Extension
            31.8 kN                  60°                 3320               5850                  6725                     Super Brace
            31.8 kN                  60°                 3690               6503                  7475              + 2300 Extension
            31.8 kN                  60°                 2560               4500                  5175                 Super 17’ (5.4)
            31.8 kN                  60°                 2180               3854                  4425                      Mini Super
            31.8 kN                  60°                 1540               2719                  3125                               Baby
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
                                                                                                 (mm)
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
                                 ANGLE                 (mm)                (mm)           LENGTH
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
            *WWL                 BRACE                  *H                  *V           MEAN BRACE                  BRACE TYPE
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
       987654321 1098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
                2
       98765432121098765432109876543210987654321210987654321098765432109876543212109876543210987654321098765432121098765432109876543210987654321
                                                   WALL BRACING SET OUT
                                                                 See AS 3850
                                       TILT PANEL WALL BRACING
     BRACE GUIDE
                            TILT-UP LIFTING PRODUCTS

                           STRONGBACKS                (see AS 3850 - 2003 Clause 3.9)


                  A.   If a panel design appears to be unstable a strongback can act
 When will they         as a crutch to balance the weight. See diagram erected - Fig.1.
 be needed ?
                  B.   When panels have very wide openings. The strongback keeps
                       the panel from sagging under the opening.

                  C.   When panels have slender legs, less than 178mm thick, where
                        the height of the leg divided by the width of the leg is less
                        than 0.12. A strongback is needed because the leg
                        cannot support the weight of the panel bearing on it during
                        lift. For legs 178mm and thicker often ties can be added
                       around the reinforcing to avoid strongbacks.

                  D.   To avoid large amounts of added reinforcing. In certain
                       instances strongbacks are cheaper.

                  Using splice plates on 200mm channel allows a “hinge” to form
 How to attach    thereby reducing the capacity of the strongback, depending on
 Strongbacks      the location of the splice. So it’s important to know where to splice
 properly         a strongback.

                  1.   Strongback Legs - We do not want the hinge to occur
                       between H/2 + 910mm above the Double Lift Plate (DBL).

                       H - is the distance from bottom of panel to DBL coil.
                       H/2 - 1/2 of that distance. If you have a notch that is 3.66m,
                       it’s 1/2 of 3.66m of 1.83 + 910mm = 2.74m.

                  2.   Second condition is strongbacks spanning openings. We don’t
                       want the splice to occur within 910mm above to 910mm below
                       the first strongback insert around the opening.




                                                         Fig 1.


ADVANCED BUILDING                        Unit 2/22 Violet Street, Revesby NSW 2212
                                         PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                        Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                         Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                             39
                                TILT-UP LIFTING PRODUCTS

                                 STRONGBACKS
                 This section covers a few of the conditions that will normally require the
Special          use of wood or steel strongbacks. If your project has panel configurations
Requirements     that are similar to the conditions shown in this section, it is very likely
                 strongbacks will be required to lift the panels. Please remember that this is
                 a guideline of some of the more common cases and does not cover all of
                 the many possible requirements for strongbacks.

                 1.    The bottom of the panel must be relatively straight in order for it to
Panels with      rotate properly. When a portion of the bottom end of the panel does not
Stepped or       contact the ground, a strongback leg may be rebuilt to provide support for
Sloped Bottoms   the panel. The three step conditions shown represent cases where
                 strongbacks may be required to provide support.




                 2.    When the bottom of a panel slopes, strongback legs may be required
                 to ensure the panel lifts straight. As a general rule, if the slope of the
                 bottom end of the panel has a rise of 100mm or more per 3.0m of panel
                 width, strongback legs will be rquired. The following conditions are
                 common and will normally need strongback legs to lift.




ADVANCED BUILDING                             Unit 2/22 Violet Street, Revesby NSW 2212
                                              PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                             Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                              Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                  40
                                    TILT-UP LIFTING PRODUCTS

                                             STRONGBACKS
                1.    Panels with tall narrow
Panels          concrete legs may require
with            strongbacks for added strength.
Narrow          As a guideline, any leg less than
                610mm in width, whose width to
                height ratio is less than 0.12, will
                normally require a strongback
                over its entire height.

                2.    For panel legs 178mm or
                more thick, it may be possible to
                eliminate the need for added
                strongbacks by the addition of
                added reinforcing steel, and ties
                in a column pattern. In order for
                this method to work, the
                reinforcing steel must be detailed
                with minimum concrete cover.


                1.    A non-reinforceable section is one in which reinforcing steel cannot be
Panels          added to adequately resist the bending stresses created during the lifting
with non-       process. This may result from many different conditions. The following are a
                few typical cases.
reinforceable
sections
                a.    If the existing structural reinforcing steel is placed too deep in the panel to
                be used to resist the erection stresses, and the structural engineer will not move
                the steel closer to the surface, there may not be sufficient room to add additional
                erection reinforcing at the required clearances.

                b.     Deep reveals do not allow placement of the reinforcing steel close enough
                to the smooth surface of the panel between the reveals to prevent visible
                cracking. While it may be possible to place the reinforcing steel close enough to
                the reveals to prevent deep cracking within them, the depth of the reinforcing
                steel in the smooth areas between reveals, will result in cracks that go deep
                enough into the panel surface to still be visible after the panel is erected.

                c.     Sections of some panels can be subjected to such high bending stresses
                that it is impossible to fit enough reinforcing steel in the sections to prevent
                visible cracks from occuring.

                2.    If the insert spacings cannot be adjusted to reduce the concrete bending
                stresses and eliminate the need for the reinforcing steel, the only option may be
                to use external strongbacks to resist the erection stesses.




ADVANCED BUILDING                                      Unit 2/22 Violet Street, Revesby NSW 2212
                                                       PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                      Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                       Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                           41
                                 TILT-UP LIFTING PRODUCTS

                                          STRONGBACKS


               Certain panel configurations make it difficult to place lifting inserts in
Panels with
               the concrete areas that they must pick up. This normally occurs when
an Opening
               large openings are placed in the panels and the inserts can be located on
Seperating
Concrete       only one side of the opening. A strongback is used to span across the
Areas          opening like an arm to pick up the concrete on the opposite side. The
               following cases are examples of typical conditions that may require the
               use of strongbacks. The shaded areas represent the portion of the panel
               the strongback is trying to lift.




              1.    “L”-shaped panels will normally
Ell-Shaped    require a long strongback attached to
Panels        the upper portion of the panel
(One-         extending to the ground, to act as a
Legged        temporary leg for support during
Panels)       erection. A shore, attached to the
              underside of the strongback, extending
              from the bottom of the panel to the top
              of the opening, is to provide initial
              bearing for the strongback and vertical
              support of the panel once it is in the
              vertical position.

ADVANCED BUILDING                                Unit 2/22 Violet Street, Revesby NSW 2212
                                                 PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                 Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                     42
                                TILT-UP LIFTING PRODUCTS

                                   STRONGBACKS

              2.    It is sometimes necessary to add more than one strongback leg. This
Ell-Shaped
              is not usually preferred, but is sometimes necessary to limit the size of the
Panels
              strongbacks to a member that is readily available.
cont.


              1.    Strongbacks are normally made of double wood or steel members
General       placed back-to-back. The size of the strongbacks required is dependent upon
Information   the size and shape of each panel and, therefore, can only be determined by a
              full analysis of each panel.

              2.    Where common wood size members are not available, the required
              strongback length exceeds 6.10m or when wood members are not strong
              enough, the Super-Lift strongback can be used, however, check to determine
              the availability of these members in your area.

              3.    Strongbacks are attached to the concrete with B-75 Coil Inserts spaced
              50mm to 75mm maximum on centre. For strongback leg conditions, the first
              insert above the top of the door is normally a B-2-125 Double Coil Insert.




ADVANCED BUILDING                               Unit 2/22 Violet Street, Revesby NSW 2212
                                                PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                               Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                    43
                                                                           SUPER BOLT
                                                                  Reusable Ground Brace Insert

SUPER BOLT
Provides POSITIVE ENGAGEMENT to the slab and
does not depend on friction or expansion pressure
against the concrete.

SUPERBOLT fastens at the exact location of the brace
shoe. No need for embedded inserts.                             NOTE: For Designers and Engineers

As fast and simple as drilled expansion anchors yet             Super Bolt has been designed and
much, much safer.                                               tested to give an ultimate failure load
                                                                of 105 kN in tension. The bolt
SUPER BOLT is reusable. Nothing is left in the slab;            eccentric head will develop a full
no inserts or expansion bolts to cut off and cover later.       cone failure to the top of the slab.
The assembly can be used again and again.                       The working load limit in concrete
                                                                will be determined by the depth of the
SUPER BOLT combines strength, simplicity and                    slab and concrete strength.
economy in one dependable, easy-to-use system.

SUPERBOLT is available for hire on a monthly basis.

       Why risk the cost of a panel by using other inferior devices.

                                     SUPER
                                     BOLT
                                                                             BRACE SHOE
                                      WEDGE            HEX NUT
                                                      & WASHER




To use SUPERBOLT, drill a 32mm hole through the floor slab and extending 51mm into the
surface below. Position the bolt in the hole so the eccentric head will slide under the slab.
Insert the wedge next to the bolt on the side marked ‘wedge’. This forces the head under the
slab giving positive engagement and full load bearing on the concrete. The brace shoe fits
around the bolt to take a washer and hex nut.


ADVANCED BUILDING                                       Unit 2/22 Violet Street, Revesby NSW 2212
                                                        PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                       Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                        Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                            44
                                                                SUPER LIFT CLUTCH

SUPER LIFT CLUTCH                                                                 Only available for hire

Super Lift Clutch has only two moving        Clutches        Safety Factor
parts. A sturdy shackle that follows         Available          (5:1)
the flow of the lift, and a sliding clutch
bar which creates a secure union             1.25 tonne
between the lifting unit and the insert.     2.5 tonne        18.68 (kN)
The lifting unit is lowered into a           5 tonne          54.27 (kN)
preformed recess and does not contact        10 tonne         72.06 (kN)
or bear down on the panel’s exposed
surface. Then the clutch bar lever is        Tested and Proof Loaded in
pushed down towards the exposed              accordance with AS 3850.
surface. This motion passes the curved
section of the clutch bar through the
eye of the anchor and locks the unit in
place. Because the clutch bar lever is
readily visible, the crane crew will
know immediately that all lifting units
are securely engaged and ready to lift.
The ring clutch mechanism will not           SIZES 1.25T                            SAFE !! Crane driver
release the insert once the crane slings           2.5T                               can clearly see that
have been tightened to a minimum of                5.0T                              the clutch is engaged
1.8 kN.
                                                  10.0T
Also, the Super Lift Ring clutch is
compatible with Rapid Lift System.
This eliminates the need for utilising
additional conventional hardware, such
as Single or Double Lift Plates.

Easy Ground Release

A quick, even tug on the lifting unit’s
rope, after the crane operator has
lowered the rigging, will slide the bolt
out of the insert’s eye and release the
lifting unit from the panel.
n    No adjustments
n    No delicate pins or bolts
n    No springs
n    No ‘mouse traps’ to set
n    No pre-loading
n No shimming or bearing pads
  to place under unit.

ADVANCED BUILDING                                         Unit 2/22 Violet Street, Revesby NSW 2212
                                                          PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                         Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                          Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                              45
                                                      SUPER LIFT III CLUTCH



 The BURKE Super-Lift III Clutch (patented)
 has a safe lifting capacity of 10t. (5:1 factor of
 safety). The industry proven BURKE clutch
 assembly was developed with a high strength
 casting and a forged handle which has been
 lengthened, to make for safer lifts and easier
 ground releases. The oval cross section prevents
 clutch rotation during handling, lifting and
 release. The BURKE Super-Lift III Clutch is
 hired with chain and lanyard attached ready for
 jobsite use. There are no moving parts to bind
 against the concrete during engagement and
 release. The BURKE Super-Lift III Clutch and
 BURKE Super-Lift III Insert combine to
 provide the strongest, simplest and safest lifting
                                                                      W.L.L. load 100 kN
 system available in the market today.

 Product Description          Unit Weight

 Super-Lift III Ring Clutch        7.55 kg




ADVANCED BUILDING                                     Unit 2/22 Violet Street, Revesby NSW 2212
                                                      PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                     Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                      Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                          46
                                                                                     FOR HIRE



SINGLE SWIVEL LIFT PLATE

Single Swivel Lift Plate weighs 6.4 kg.
Use with 152mm coil bolts of 32mm or 19mm                                                          32mm or
diameter.                                                                                          19mm

Exposed aggregate face-up panels may require
longer bolts. Sleeves are available for 25mm
and 19mm diameters.

Working Load Limit: 32mm dia
                      19mm dia
is dependent on Tensile/Shear of Taper Bolts.




                                                                                EL
                                                                           AN                      27mm
                                                                         FP
                                                                    PO
                                                               TO                                         39.7mm
DOUBLE ANGLE LIFT PLATE                                    E
                                                    H   ER
Double-Angle Lift Plate is 102mm x 152mm x
19mm structural angle with welded centre lug
29mm plate. Wt. = 23.66 kgs. Use with taper
bolts. These bolts require a 25mm masonary                                                m
                                                                                        4m
drill bit. See Taper Bolts on opposite page for                                       25
                                                                                              mm
W.W.L. and installation. Washers required under                                          43
                                                                                           1.8
bolt head. Exposed aggregate face-up panels
may require longer bolts.




ADVANCED BUILDING                                 Unit 2/22 Violet Street, Revesby NSW 2212
                                                  PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                 Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                  Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                                   47
                                                                                                       FOR HIRE


   TAPER BOLTS


                                      21 MPa Concrete                                    35 MPa Concrete
         Dia                Embedment      Tensile                     Shear *         Tensile      Shear *

                              32mm               1.85 kN                              2.30 kN
     6.35mm                                                            2.70 kN                         3.89 kN
                            76.2mm               2.58 kN                              2.53 kN

     25.4mm                  118mm              31.43 kN              40.32 kN        34.27 kN        42.80 kN


   The above working loads are based on manufacturers recommended 4:1 safety factor.
   * Shear strength based on minimum embedment.

   Taper-Bolt is an engineered Fastening System
   which incorporates the capabilities of a high
   strength threaded fastener into a masonry
   anchor.


                                                                      ADVANTAGES OF TAPER BOLTS:

                                       Finished professional          STRENGTH The highest tensile and shear strength
                                       appearance. Can be set
                                       with an impact wrench          available. This anchor retains torque.
    No threads to
    be damaged
                                                                      APPEARANCE No unsightly studs here! Each
                                                                      installation has a neat, professional finished
                                                                      appearance.
                                                                      SPEED Bolt size is hole size. Taper-Bolts can be set
                                      S.A.E. Grade 5
                                      Heat treated steel              with “Pit Stop” speed utilising an impact wrench.
Greater clamping power                                                ADJUSTABLE No spinning - no slipping. Only
since it functions like a
standard nut and bolt                                                 Taper-Bolt can be adjusted for slightly over size or
                                                                      irregular holes.
                                                                      REMOVABLE Like a bolt in a tapped hole, Taper-
                                                                      bolt can be removed and replaced.
Nut may be pre-expanded              Nut expands parallel to the      REUSABLE Remove the bolt - add a new expander
to fit oversized holes               sides of the hole distributing
                                     compression along the entire     nut and use it again! Approximately 70% of the anchor
                                     length of the anchor
                                                                      cost is recoverable with the second use.
                                                                      VERSATILE Wherever? Whenever? Taper-Bolt
                                                                      solves your anchoring problem! adjusted.




ADVANCED BUILDING                                                         Unit 2/22 Violet Street, Revesby NSW 2212
                                                                          PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                                         Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                                          Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                                              48
                                                                         FORHIRE
ABS/ BTRKE BAR - Lc4&: 142llnm
                          dqnolitionmd
TheBute Br is anall-purpoac
          b0.
coDshnction Wcight 6.0Lg.
It is qrc€U€nt shipping
               for        fornwqt ard
pcticulady usefinduringercction  ofTll;lBtr.:f
ponels.Thewidespring    steelh€ad €Drbl€B
manoeuvering    ofpmels withou thesurfrce
demsge    oftencaused cmwbrs andsimilu
                     by
impl€mqts. Thehollowrrdaogulr stcel
bandle light aodsudy md givessperior
         is
 gip. Weluwtl osa gea pm.fud b! or-sitc
                        with
ror*a!. Alsoavailable a had and
                   -
knuclle prcteclor €rqufui€s w€lcome.

Certificd ty ETRSNATAL.borrtotT.
AppViDgr downwrd forceof 167kg.t .rd
of hrndle will Iift | l,ord4.7,1t50nm in from
tongueedge,
 "BcwareoJhrlofun cqb !! Copying a ts
  co''plt/ncnL-.,,brdno, a suffic tor
  thc origiml"

ABS/IIIINI BAR - LengttulZl0nm
TheoriginalAES/BtllKE BAR andthe
MII\ BAR bothba/ea cwvedblade        which
basbeen  eogine€rsd more
                    for               than
                              l€ri€rage
             The        is
competitors. blade bea trededfut                                      AES,MIMBAN
mExinun stcngth. Bothsizcs bevery
                                cm                                    L€ogth:l22ortrtt
us€frrlonjobsites,"therigtt toolfor the                               weight 3kg
rtghtjob". TheABS/BI'RKE BAR 8nd
                          for
MINI BAR aredesigncd tbctitt-up
contractor nakejobsquicker easier.
          to                    md
Weight 3.01g.

Ccrtificd by ETRSNATAlrborrtory.
Applyitrg I downwrd forceoftllg et
end of hmdle will llft . lood 13t 5|)mDin         ADS/MINI BrRPLI'S
frrm toDglc edgc-                                 IrDgth: l650nD
                                                  wciehf 4kg
ABS/MIM BAR PLUS- Lrngah:l650nm
Thigis a Mini Barwith I430m odcod€d hsndle.
     for
Great stipping overhead   formwortc
Wcight ,t.0kg.

                                                         VioLi Str€.t,Rlv€sty NSW 2212
                                                 Unit 2122
ADVANCEDBIIILDING                                POBd 113,  NodhRrv!$Y NSW 2212
SYSTEMSPTY. LTD.                                 Ph@c:(02)977rl01l Fax: (@)97921414
                                                       midsvir@rihbilLo@ Wcbr tw'.dltbl&q4
50
     Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com
     Phone: (02) 9771 1011 Fax: (02) 9792 1414                                       SYSTEMS PTY. LTD.
     PO Box 113, North Revesby NSW 2212
     Unit 2/22 Violet Street, Revesby NSW 2212
                                                                                     ADVANCED BUILDING
                                                                                               Also available individually.
      6.0mm                                                                       Also available in 10mm & 20mm sizes.
      6.0mm
      6.0mm
      3.0mm                                                          n 2 Blue (1.5mm) 4 Red (3.0mm) 6 White (6.0mm)
      3.0mm
      1.5mm                                                                         n 12 shims, each 150mm x 100mm.
                                                                      Each pack contains sufficient shims to level a panel.
                                                                                                        PANEL PACK
                                                                                  27.58 (MPa) safety factor 2.0
                                                                                  Laboratory to the working load limit
                                                                                  Super Shims have been tested by a Nata
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
                   is ours, to protect your client
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
                                                                                    n No elastomeric drift, no slipping.
              0987654321098765432121098765432109876543210987654321
                  Quality and Stability under load
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
                               BUT
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
                                                                                    oxidation from moisture.
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
                    Price may be your criteria
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
                                                                                   chemicals, micro-organisms, rot or
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
                                                                                    Unaffected by alkali, ground         n
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
                                WARNING:
              0987654321098765432121098765432109876543210987654321
              0987654321098765432121098765432109876543210987654321
                                                                                     not rust.
                                                                                     Waterproof, non-staining. Will      n
                                                                                     money on lifting day.
                                                                                     Simple to use, saving time and      n
                                                                                                         25.5mm
                                                                support.
                                                                compressive strength provides permanent
               150mm                                            not fracture under load. Their high             100mm
                                                                an excellent bearing material which will
                                                                serrated to eliminate slippage. They are
                                                                rigid, high impact plastic specially
                                                                panels. Super Shims are extruded from
                                                                Super Shims are used to level tilt-up
                                                                                                      SUPER SHIMS
     PLASTIC ACCESSORIES
                                     PLASTIC ACCESSORIES



MODFIX SHIMS

We now also stock Modfix Shims for
your convenience.

Shim Packets/Sizes
2 x Brown     1mm
4 x Blue      2mm
4 x Green     3mm
6 x Yellow    5mm
1 Packet      52mm


Available to 20t - loose

   1mm
   2mm
   3mm
   5mm




ADVANCED BUILDING                    Unit 2/22 Violet Street, Revesby NSW 2212
                                     PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                    Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                     Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                         51
                                                                  CRACK INDUCERS




      FASTER! EASIER! BETTER! CHEAPER!
The EASY-T plastic joint former and crack inducer consists
of two sections; an arrow shaped section which locks into the
concrete, forming the joint and a top section which facilitates
handling and placing - this is removed after firming of the
concrete surface.


FINISH:

n Joints can be formed right up to walls, columns and
  isolation joints, producing a clear, neat finish. Tooled
  joints and saw cuts are eliminated.

n No need for joint sealants.

n The EASY-T joint is ideal for heavy point loads such as
  fork lifts.


LENGTHS:

The EASY-T strip is supplied in 3 metre lengths and can be
adapted to any length joint, without wastage, by overlapping
the upper section.


DEPTHS:

The suggested proportion of strip to concrete depth is 1:4 to a
maximum of 1:5. EASY-T is available in depths of 25mm,
38mm, 50mm and 65mm.

USED BY: Municipal Councils and RTA.




ADVANCED BUILDING                                      Unit 2/22 Violet Street, Revesby NSW 2212
                                                       PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                      Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                       Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                           52
                                                           PLASTIC ACCESSORIES

PVC CHAMFER STRIP                                       Available in standard lengths of 3 metres. It is
                                                        recommended that a form release compound be
FEATURES:                                               used on the surface of the strip prior to attachment.

n      Flexible and reusable.                              A            B              C            D
n      Resists chips and cracks.                         25mm         16mm            5mm         12mm


                                                                                         Formwork




                                   Nail concrete
    Can be used for                                                                      Formwork angle
    decorative reveals




                                                Chamfer creates slurry seal
                                                and decorative arris.

CHAMFER CUTTERS
For quick, clean cuts in wood moldings, try these chrome
steel Chamfer Cutters. The hardened steel blade slices
through most soft woods with ease. But as sharp as the
blade is, the real secret behind the cutter’s prowess is its
ingenious anvil. The anvil acts like a chopping block,
supporting the chamfer as the blade passes through it. No
bypass shear works as effortlessly or cuts as true. A built-in
fence to either side of the blade assures perfect 45° miters
every time.

Cutters lock tight for safe carring and can be quickly
disassembled for sharpening. This precision crafted, pocket
sized wonder belongs in every contractor’s belt.

SHEFFIELD CHAMFER CUTTERS
Heavy duty universal shears
Replacement blade available
Replacement anvil available


ADVANCED BUILDING                                          Unit 2/22 Violet Street, Revesby NSW 2212
                                                           PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                          Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                           Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                                53
                                                   PLASTIC ACCESSORIES

PLASTIC STICK-ON PATCHS
Plastic Stick-On Patch permanently covers lifting insert and recess holes on tilt-up panels. The
Patch is precision moulded of high-impact, long lasting plastic which has concrete colour and
texture, and is highly resistant to chemical assault from a variety of manufacturing and
environmental chemicals. Super Patch easily locks into the insert or recess hole and blends into
the panel’s surface.

FEATURES:-

n    Neat.
n    Quick, easy to install - only one person needed.
n    No special trades or tools required.
n    Permanent seal - resistant to temperature changes, chemicals, and inpact.
n    Matt finish for easy painting.
n    No mixing, no wastage, no mortar.




          Super Patch for Super                                           Wall Patch for
          Lift recess holes.                                              wall brace holes.
          150 mm                                                          80 mm




 NOTE: If Super Patch is to be used on panel interiors or exteriors exposed to high moisture
 environment, spray metal insert with a rustproofing compound before inserting patch. Super
 Patch will not eliminate rusting.


ADVANCED BUILDING                                    Unit 2/22 Violet Street, Revesby NSW 2212
                                                     PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                    Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                     Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                         54
                                                       CHECK LIST



              EQUIPMENT CHECK LIST FOR
                    LIFTING DAY




  o   CLUTCHES

  o   BRACES, COIL BOLTS AND WASHERS

  o   WEDGES

  o   BURKE BARS

  o   SHIMS

  o   IMPACT WRENCH

  o   SMALL COMPRESSOR (TO CLEAN OUT INSERT VOIDS)

  o   LADDER

  o   HAMMER AND SCREWDRIVERS (FOR VOID FORMER REMOVAL)

  o   SUPERBOLTS

  o   32MM DRILL BIT

  o   PANEL BRACES




ADVANCED BUILDING               Unit 2/22 Violet Street, Revesby NSW 2212
                                PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.               Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                    55
                                                                       HAND SPRAYER

HAND SPRAYER
Standard 11.4 litre stainless steel tank.
Recommended for use with cure coats,
sealers and hardeners.

n     Wide mouth for easy filling.

n     Corrosion resistant brass pump.

n     Solvent resistant neoprene hose.

n     500mm curved brass spray wand.

n     Brass fan spray tip 2.8 litre/min.




          GASKET REPAIR KIT                                  STRAIGHT WANDS




                                                                   CURVED               PLUNGER ROD
    SPRAY TIP               TRIGGER                                WANDS                ASSEMBLY

ALSO AVAILABLE: Threaded collars, additional hoses and carry straps.


CHAPIN PROFESSIONAL SPRAYER                                  VITRON
n     Industrial heavy duty grade 11 litre poly tank for corrosive jobs.

n     Polyethylene pump and Viton seals.

n     Braided hose with 450mm lance and fan nozzle.

n     Pressure relief valve and padded strap.




ADVANCED BUILDING                                      Unit 2/22 Violet Street, Revesby NSW 2212
                                                       PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                      Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                       Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                           56
                                                                            DRUM RACK



DRUM RACK

Suits up to 200 litre drums. Load capacity: 317 kg.

Length: 762mm
Width: Base 595mm Top 394mm.
Height: Top rail - 508mm. Bung - 560mm.
Weight: 13.6 kg.




  ADVANCED BUILDING                                   Unit 2/22 Violet Street, Revesby NSW 2212
                                                      PO Box 113, North Revesby NSW 2212
  SYSTEMS PTY. LTD.                                   Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                      Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                          57
                                                       SUPER TILT WB (EXPORT)

PRODUCT DESCRIPTION:                                   HOT WEATHER PROCEDURES:
Super Tilt WB (Export) is a liquid VOC compliant,      It is important to verify the integrity of the
water-based, reactive and membrane forming             bondbreaker coat in all weather conditions.
bondbreaker for use in tilt wall construction. Super   Verification can be achieved by sprinkling water
Tilt WB (Export) is a special formula of polymers      on the casting bed. (Water should bead up as on a
and propriety ingredients designed to provide clean,   freshly waxed automobile). The applied, dried
easy lifting of tilt panels from properly designed     material should have a soap like feel, uniformly over
concrete casting beds. It contains a fugitive dye      the substrate. Failure to verify proper application
for ease of visual inspection during application.      can result in panel sticking.
ADVANTAGES:                                            In hot weather, it is recommended to fog spray the
· Water Based                                          slab with water prior to the first application of Super
· V O C Compliant                                      Tilt WB (Export). The fog spraying of the slab with
· Panels lift cleanly                                  water will help cool the concrete and reduce the
· Minimal panel residue                                high demand for bond breaker material.
· Resists construction foot traffic
                                                       DRY TIME:
APPLICATION INSTRUCTIONS:                              Approximately 2 hours at 21°C.
The concrete base casting slab, and tilt wall panels
must be properly designed, finished and cured in       COVERAGE RATES:
accordance with industry standards. Concrete           Cure Coat: 4.9 m2/L
casting slabs must be smooth and dense. Improper       Bond Breaker Coats:
or inadequate curing or finishing will increase slab   First Coat: 9.8 m2/L
permeability and decrease bondbreaker                  Second Coat: 13.5 – 17.2 m2/L
effectiveness.
                                                       V.O.C. CONTENT:
Thoroughly agitate the Super Tilt WB (Export)          Less than 100 grams per litre. Complies with the
prior to each use.                                     most stringent overseas health standards for Bond
                                                       Breakers.
The casting bed should be free of all foreign
material. The Super Tilt WB (Export) should be         PACKAGING:
protected while drying from all contaminants or        20 litre pails or 208 litre drums.
particulate matter (i.e. dust, dirt, etc).
                                                       CLEAN-UP:
Just prior to placing the reinforcing steel, and       For tools and equipment use warm, soapy water.
within two weeks of pouring the panels spray apply     After the product dries, solvents like mineral spirits
the first bond breaker application of Super Tilt       may be necessary to remove the product.
WB (Export) at a rate of 9.8m2/L. Spray at right
angles to curing compound spray pattern. Wait
until dry, approximately 2 hours at 21°C , and apply
a second coat at right angles to the previous coat.
Coverage will typically be 13.5 – 17.2 m2/L for the
second coat. If light or white spots appear within
10-40 minutes after spraying, those areas are extra
porous and should be fogged with water followed
by a reapplication of the Super Tilt WB (Export).
Do not over apply. Avoid puddles and excess
material. Do not walk on areas treated with Super
Tilt WB (Export) until it dries. Do not apply when
surface or air temperature is below 4°C or over
frost or standing water. Allow Super Tilt WB
(Export) to dry completely prior to pouring concrete
panels.
                                                                For Commercial/Industrial Use Only


 ADVANCED BUILDING                                       Unit 2/22 Violet Street, Revesby NSW 2212
                                                         PO Box 113, North Revesby NSW 2212
 SYSTEMS PTY. LTD.                                       Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                         Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com


                                                                                                                 58
                                            SUPER TILT WB (EXPORT)
                                                COMPARISON SHEET


 SUPER TILT WB (EXPORT)
 Apart from the cost benefit, it is environmentally accepted by the Unions and EPA as
 it is a water based product versus volatile organic compounds (VOC).

 Application

 1st Coat:                            9.8 m2 per litre
                                      VERSUS
 V.O.C. Bond Breaker at:              6m2 - 8.5m2 per litre (average 7.5m2/litre)



 2nd Coat:                            15.35 m2 per litre
                                       VERSUS
 V.O.C. Bond Breaker at:              6 m2 - 8.5 m2 per litre (average 7.5 m2/litre)

 Hence, average application
 of Super Tilt WB (Export) versus     You apply twice as much solvent
 V.O.C. Solvent Base                  based versus water based.


                           This is an actual saving to you!
             Check the prices, then check the usage, then check the result!


 If the Solvent bond breaker is $700 for 205 litres
 ABS Super Tilt WB (Export) is $899 for 205 litres

 Then Super Tilt WB (Export) only uses half the amount of the Solvent Based Bond
 Breaker.

 This means it costs only $449.50 versus $700.




ADVANCED BUILDING                            Unit 2/22 Violet Street, Revesby NSW 2212
                                             PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                            Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                             Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com


                                                                                                 59
                                 CLEAN LIFT 90 BOND BREAKER

CLEAN LIFT 90 Bond Breaker is                 Bond Breaking (Bond Breaker Coat):
composed of a chemically active non-
membrane forming material that functions      Apply this coat after the edge forms have
as both a curing compound and as a bond       been set and before reinforcing steel is
breaker for tilt-up construction.             placed. The surface must be clean and
                                              free of foreign material. Sweep or use
Concrete treated with Clean Lift 90           compressed air to clean surface before
retains the mixing water necessary for        application.
hydration and proper curing.
                                              Apply Clean Lift 90 at a rate of 6-8.5m2/
A second coat applied to the casting slab     l per coat for two light coats applied at a
prevents tilt-up panels from bonding to       90 degree angle to each other. Allow the
the slab. Panels lift easily without          first coat to dry approximately 15
sticking. Less force is required than is      minutes before applying the second coat.
typical with membrane type bond               Actual coverage rate is dependent on the
breakers.                                     finishing method and surface porosity.

Properly applied, Clean Lift 90 yields a      Before placing concrete it is advisable to
panel surface ready to receive paint or       check bond breaker coverage by
other treatments. Since no resin              sprinkling water on the surface. Water
membrane is present, there is no need to      drops should bead up. If they spread and
wait for membrane residues to oxidize         soak into the concrete, another
before applying coatings to the panel.        application is required. If in doubt, re-
Clean Lift 90 Bond Breaker remaining on       apply a light coating. When the panel is
the floor slab will not prevent the bonding   cast and finished, spray a coating of
of solvent-based adhesives used to apply      Clean Lift 90 Bond Breaker on the
tile, linoleum or other coverings.            surface as a curing compound at a rate of
                                              7m2 to 10 m2/l depending upon surface
APPLICATION                                   porosity.

First Coat (Curing Coat):
Clean Lift 90 can be applied with any
equipment that produces a fine spray and
even application. Clean Lift 90 must be
applied after the final trowel finish and
immediately after the water sheen has
disappeared. Do not delay application.
cover the surface with a uniform coat at a
rate of 5-6m2/l depending on the finishing
method and surface porosity. A porous
surface will require heavier coverage. A
hard steel trowelled surface assures best
results for bond breaking. A blue fugitive
dye is added to aid application.




ADVANCED BUILDING                             Unit 2/22 Violet Street, Revesby NSW 2212
                                              PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                             Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                              Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                  60
                                                           SPARTAN-COTE
                                                     CURE-SEAL-HARDENER
TO IMPRESS YOUR CUSTOMER OR LESSEE USE SPARTAN COTE TO OBTAIN A
GREAT FINISH ON YOUR FLOOR.


SPARTAN-COTE is a high             APPLICATION                         SPECIFICATIONS
quality styrene-acrylate
copolymer resin that cures,        Apply as a curing compound on       When applied at the specified
seals, hardens and dustproofs      newly poured concrete surfaces      rate, SPARTAN-COTE Cure-
freshly cast concrete. It          after final finish and              Seal-Hardener meets and
provides long lasting odour free   immediately after the water         exceeds:
floor protection.                  sheen has disappeared from the
                                   surface. Use a Burke hand           STANDARD
SPARTAN-COTE resists               sprayer or low pressure power
yellowing and deteriorating        sprayer for best application,       ASTM C-309, type 1, Class A &
effects of ultraviolet rays.       with these rates of coverage:       B AASHTO M-148, Type 1, Cl.
This quality makes SPARTAN-                                            A&B
COTE ideal where an exterior       Smooth finish - 7 sq.m/litre
architectural finish is desired.                                       Flash point 28° C.
                                   Rough finish - 5 sq.m/litre
A one step application provides                                        Keep away from sparks and open
a moisture barrier which           When used as a sealer or dust       flame.
minimises efflorescence,           proofer on existing concrete
dusting and destruction of         surfaces, the surface must be       Modified formulations meet IT-
carpet backing. It provides a      thoroughly cleaned and swept.       C-800A, Type 1, Class 1 and Air
good base for most mastic          Apply at a rate of 10 to 12 sq.m/   Pollution Control Regulations.
adhesives and coatings.            litre. For added protection to
                                   the concrete apply a second coat
                                   at 12 sq.m./litre. Also can be      Spartan-Cote is compatible
                                   applied by brushing or rolling.     with Burke Bond Breakers.
                                   Drying time is 1 to 2 hours.

                                   Clean application equipment
                                   after use with xylene.

                                   CAUTION:
                                   Contains xylene. Use
                                   respirator for application.




ADVANCED BUILDING                                       Unit 2/22 Violet Street, Revesby NSW 2212
                                                        PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                       Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                        Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                            61
                                                                  BURKE TITAN HARD

BURKE TITAN HARD
Burke Titan Hard is a penetrating      n     Protects concrete from          The exact coverage depends upon
water-based reactive siliconate        detrimental spalling effects of       the porosity of the slab. If the
solution specifically designed for     deicing salts.                        concrete is extremely porous,
protecting concrete floors against     n     No V.O.C., no harmful           more than one coat may be
abrasion, dusting and spillage.        fumes or odours.                      necessary.
Tital Hard penetrates deeply           n     Breathable sealer for
creating an integral matrix that       interior or exterior use.             Titan Hard will develop a low
won’t wear away. Titan Hard            n     Can be used to enhance          gloss satin finish with use. If
                                       hardened and dustproofed non-         desired, a floor buffer will bring
imparts a low gloss, satin sheen
                                       metallic, dry shake floors.           out the shine immediately.
with use without buffing.
                                       Architectural Specifications
Burke Titan Hard is specifically       Sealer/Dustproofer: A ready-to-
formulated for use on old or new       use clear siliconate sealer shall
concrete surfaces to improve           be applied to the concrete slab
hardness and abrasion resistance.      in accordance with the
Use Titan Hard to dustproof            manufacturers written
concrete surfaces imparting an easy    instructions. Sealer must be
to maintain low sheen surface.         guaranteed for 10 years against
Titan Hard can be used for interior    dusting. Approved product:
                                       Burke by Edoco Titan Hard or
and exterior applications since it
                                       approved equivalent.
allows the concrete to breath while    Important: When using Titan
still resisting penetration of oils    Hard in conjunction with a
and other contaminates.                curing compound, use only
                                       Burke by Edoco Res. X, Aqua
BENEFITS                               Resin Cure or Super
                                       Bondbreaker. Consult ABS for
                                       special procedures for use.
n Imparts an integral shine that
builds with use and won’t scratch,     Application
peel or discolour like modified
acrylic styrene butadiens, urethanes   Sealer & Hardener Application:
or epoxies.                            Coverage:
n Seals and densifies the
concrete surface resisting spills,     Hard Trowelled Finish     7.4 - 9.8
dirt and chemical attack.              Broom or Float Finish     4.9 - 7.4
n No surface coating to allow          Rough Slab Finish         3.7 - 6.2
                                       Old Concrete              3.7 - 6.2
black rubber tyre marks.
                                       Vertical Surface - lamb’s
n Hardens & dustproofs in one          wool roller recommended 7.4 - 9.8
easy step on most floors.
n Safe & easy to use; no mixing,
no etching, no expensive
equipment.


 ADVANCED BUILDING                                        Unit 2/22 Violet Street, Revesby NSW 2212
                                                          PO Box 113, North Revesby NSW 2212
 SYSTEMS PTY. LTD.                                        Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                          Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                                  62
                                          PROTECTIVE COATINGS

   BURKE SHIELD
       244
A penetrating, weatherproofing
sealer.

Burke Shield 244 protects new or
existing concrete, masonry, stone,
clay tile or brick surfaces from
damage due to intrusion of water, sea
water, water borne contaminates or
airborne pollutants. Typical
applications include parking stations,
bridges, retaining walls, stadiums,
natural stone building facades, airport
runways, wharves and piers. Burke
Shield produces a clear, water
repellant membrane which prevents
contaminants from penetrating the
concrete and attacking the steel
reinforcement.

This clear, siloxane-based product
has a history of good performance
and is supported by independent
testing laboratories.

n Can be applied over broad
  temperature range.

n Does not require an alkali as a
  host, so it can be applied to
  new or old concrete.




ADVANCED BUILDING                         Unit 2/22 Violet Street, Revesby NSW 2212
                                          PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                         Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                          Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                              63
                                                                         SHAROSOL


CONCRETE TOOL CLEANER

 Sharasol - Is a biodegradeable cleaner.

 A cleaner, so forms and tools used with concrete are kept in a clean condition free
 from cementatious paste.

 APPLICATION:

 For wood, metal and PVC forms. Sharosol is applied by spray or brush in a light and
 consistent coating on clean forms.

 Rough or new forms should first be saturated with release agent, as they will be
 highly absorbent.

 Non absorbing forms should be cleaned of excess agent with a wiper.

 CHARACTERISTICS:

 n   Bio-degradable, solvent free.

 n   Leaves no spots or pores on concrete surface.

 n Combined chemical and physical release action, ensures easy separation.

 n   Provides very good corrosion protection.

 n   Problem free application of plaster, tiles and wall paper over the concrete.

 n   Low consumption 1 litre for app. 65- 85 m2 depending on the type of form.

 n   Not water soluable




ADVANCED BUILDING                               Unit 2/22 Violet Street, Revesby NSW 2212
                                                PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                               Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                    64
                               CONCRETE HANDLING EQUIPMENT

ALLEN RAZORBACK TM                                                       FOR SALE OR FOR HIRE
AIR DRIVEN SCREED - Model 12HD                                        Write or phone for Testimonials
n All welds vibration proof.
                                      High strength winches
n Vibration adjustable to
  suite concrete slump.               control production rate
                                                                    Top pipe coupler
n Available in sections to                                          prevents sag
  suite any pour width
   up to 15.55 metres
n Normal 85-150 cfm air
  compressor powers
   screed.
n Modular 2.29m, 1.525m
  and 0.61m Sections.
n Manual winches or powered
  winches.
n Complete line of attaching
  accessories.
n Available with air driven motor
  winches. Only on order.
ALLEN RAZORBACK TM                                                       FOR SALE OR FOR HIRE
ENGINE DRIVEN SCREED - Model 12 ED                                    Write or phone for Testimonials

WHEN YOU DON’T WANT TO HIRE A COMPRESSOR
THE ENGINE DRIVEN RAZORBACK IS THE ANSWER
                           TM




                                Self-propelled or
                                standard winches




                                                         n End engine mount or centre mount kit.
                                                         n      9 HP Honda engine.
                                                         n Dual winch mounts available.
                                                         n Available in section to suite any pour
                                                           width up to 15.55m.
                                                         n Vibrators at 750mm centres on front
                                                           and back blades give uniform
                                                           vibration.

  ADVANCED BUILDING                                   Unit 2/22 Violet Street, Revesby NSW 2212
                                                      PO Box 113, North Revesby NSW 2212
  SYSTEMS PTY. LTD.                                   Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                      Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                          65
                                                                                             SCREED KING


                                              Our offset handle balances
                                              eccentric weight torque for better
 The Lifting Handle is located over the       control
 centre of mass allowing easy and                                                        The durable “Set & Forget” throttle
 balanced manoeuvring.                                                                   allows the operator to find the
                                                                                         optimum RPM and lock it in place
                                                                                         for consistent vibration
     Screed King’s power transfer system           Powerful 4 stroke 31cc
     has no flex shaft to lubricate. The           Honda engine
     rubber coupler is engineered to sheer,                                                          Screed King’s exclusive
     should the eccentric weight become                                                              bearing system is factory
     blocked protecting the bearings from                                                            sealed preventing the need
     overload damage                                                                                 for maintenance and is
                                                                                                     oversized for longer life.

Screed King’s adjustable handlebars can                                                 Screed King’s eccentric weight
accommodate any user height in any depth of                                             offers quick and easy in-field
concrete and with our exclusive quick release                                           adjustment for vibration amplitude
levers no tools are required for adjustment. Our                                        without taking the power head off
wide offset handles design provides better line                                         the board.
of vision and increased operator comfort when
compared to in-line style screeds.
                                                                              Screed King’s unique double dampening
                                                                              vibration system provided 8 rubber bushings to
                                                                              isolate the operator from vibration, minimizing
                                                                              fatigue while providing smoother operation.




  The Screed King is virtually maintenance free with no
  bearings to grease or shafts to lube and comes with an
  industry best, 2-year warranty on all parts and labour.




    MAGNESIUM EXTRUDED                                      Enclosed design virtually eliminates warping or torquing.
    SCREED BOARD
                                                            No brackets or adjustable torsion rods mean no crevices for concrete
                                                            to gather in, making clean up a breeze.

                                                            150mm base allows the Screed King to float in any clump of
                                                            concrete and our unique CURL EDGE helps to roll the excess
                                                            concrete back to the rakers and allows the board to float or ride on
                                                            forms.

                                                            The MAGnesium FLOat Boards provide the lightest material in the
                                                            industry and will not react with concrete like aluminium screed bars.

                                                            Threaded mounting studs stay with the board for quick coupling.

                                                            MAGFLO Boards are available in a variety of lengths:
                                                            1.21m, 1.52m, 1.83m, 2.44m, 3.05m, 3.66m, 4.25m




ADVANCED BUILDING                                                  Unit 2/22 Violet Street, Revesby NSW 2212
                                                                   PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                                                  Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                                                   Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                                                    66
                                                                    ANNEXURE A



  W.W.L. LIMITS - WALL BRACE INSERTS

    Item Number       Core Thickness       Face Tension        Face Shear
                          in mm
      B75050              127 mm              27.73 kN          29.25 kN
      B75060              150 mm              36.1 kN           36.1 kN
      B75070              178 mm              36.1 kN           36.1 kN
      B75080              200 mm              36.1 kN           36.1 kN
      B75120              300 mm              36.1 kN           36.1 kN

     The loads shown above are tensile loads at 17 mPa concrete strength.




ADVANCED BUILDING                              Unit 2/22 Violet Street, Revesby NSW 2212
                                               PO Box 113, North Revesby NSW 2212
SYSTEMS PTY. LTD.                              Phone: (02) 9771 1011 Fax: (02) 9792 1414
                                               Email: mjdavis@tiltbilt.com Web: www.tiltbilt.com

                                                                                                   67
                                                REVISED TRADING TERMS AND
                                                CONDITIONS as at NOVEMBER 2004

1. Should you request to open a credit account with Advanced then        ORDERING OF HIRE EQUIPMENT
it will be necessary for you to complete our credit application form
in detail. Until your application has been approved by Advanced,         11. Brace and lifting equipment orders are filled on a “first
goods cannot be released. Such application for credit will require       come, first served” basis and while we undertake to advise you as
the completion of a relevant guarantee in the case of a proprietary      soon as possible in the event that we may be unable to fill your
company.                                                                 order by your specified date, we accept no other responsibility
                                                                         and you shall not be entitled to make any claim for compensation
DISCOUNT STRUCTURE                                                       or otherwise against us in the event of non-delivery by that
                                                                         specified date.
2. A discount structure is available BUT OUR TERMS OF
PAYMENT MUST BE MET.                                                     12. All hire equipment including braces and clutches damaged
                                                                         will be charged for at replacement cost.
TERMS OF PAYMENT FOR APPROVED CREDIT
                                                                         RETURN OF BRACES FROM SITE
3. Thirty (30) days payment.
                                                                         13. The period of hire commenced from pick-up date and
4. All good supplied by ABS to its customers remain the property         continues until the hired items arrive back into our store.
of Advanced until payment is received for purchase or hire of the        Advanced will not accept goods as being returned on the basis of
said items                                                               a phone call. To facilitate the return of braces we advise that you
                                                                         should arrange transport and inform Advanced of the delivery
5. Accounts unpaid after thirty (30) days after statement date will      times. Store hours are between 8.00 am and 3.30 pm Monday to
incur interest from the date the statement is received by you until      Friday.
payment is made in full, at a rate being two per cent (2%) above the
rate charged from time to time by the Commonwealth Bank of               14. Braces are initially hired for a 30-day period.
Australia on a fully drawn overdraft in excess of one hundred
thousand dollars ($100,000) or 15% per cent per annum whichever          15. When arranging to have the braces collected from your site,
is the greater.                                                          please have all the braces bundled together or stacked in the
                                                                         racks provided by Advanced. TRANSPORT COMPANIES
6. Without prejudice to any other method of service, any notice or       CHARGE FOR TIME WASTED ON SITE while the braces are
other document shall be sufficiently served if sent by prepaid post      gathered together and THIS COST IS PAYABLE BY YOU.
to you at your last known place of business, registered office or
residence and if that letter is not returned through Australia Post      16. All braces are to be returned with the threaded doka rods
undelivered, it shall be deemed to be made at the time when the          wound in. All brace extensions are to be disassembled and
letter would be delivered in the ordinary course of business.            stacked ready for collection. Otherewise a labour charge of $45
                                                                         per hour based on the Storeman & Packers State Award, will be
7. It is agreed that the amount shown on each invoice forwarded by       charged to the customer for the time required to carry out these
Advanced is prime facie evidence of the amount owed for the goods        functions.
and or services to which that invoice relates.
                                                                         SAFETY WARNING
It is agreed that should any dispute arise as to the merchantable
quality of such goods and or services or if it is believed there is an   17. The brace racks will carry either 20 Super Braces or 30
error which has occurred in the invoice then you hereby agree to         Mini-Super Braces. Please ensure that not more than these
seek your remedies under the appropriate provisions of such section      numbers are stacked in the racks. It is important to have
of the common law and not withhold payment to Advanced nor to            braces arranged centrally in the rack so that the rack is
plead at law that you have a right to prevent Advanced from              unlikely to overbalance.
recovering such amounts shown on such invoices together with
such costs of collection therein.                                        COIL BOLTS
TRANSPORT COSTS                                                          18. All coil bolts and washers are to be returned to Advanced
                                                                         with the braces. Rental for coil bolts is incorporated in brace
8. You, the customer, may arrange transport to facilitate pick-up        hire charges, but if these items are not returned they must be paid
and delivery times on your site. However, if Advanced is requested       for at full retail price.
to make transport arrangements all costs associated with such
delivery are payable by the customer.                                    DISCLAIMER
9. Transport charges are the responsibility of the customer.             Advanced do not recommend the use of drilled-in expansion
Advanced undertakes to move freight as economically as possible          anchors as a substitute for fixing to the ground slab the
but due to demand or the lateness of ordering, multiple freight bills    temporary braces used to support wall panels. No responsibility
are occasionally incurred.                                               will be taken by Advanced for the failure of any of our equipment
                                                                         used in conjunction with such drilled-in expansion anchors.
RETURN OF PURCHASED GOODS                                                Advanced recommends the use of the Burke Super Bolt where
                                                                         Ground Brace Inserts are misplaced or not installed.
10. Advanced will accept the return of goods at their discretion but
a 20% re-stocking fee based on the invoice price of such goods will      TERMS OF PAYMENT FOR HIRE
be charged to the customer. Claims made for short deliveries or
incorrect deliveries must be made within 48 hours of delivery of         19. All payment for hire of goods shall be paid monthly in
such goods to the customer.                                              advance unless other provision for payment has been made.