Occupancy Sensors

Document Sample
Occupancy Sensors Powered By Docstoc
					Occupancy Sensors




             meets energy codes • supports sustainable designs
                                                • saves energy
 The NEW generation of
 occupancy sensors:
 Watt Stopper/Legrand’s new generation of
 occupancy sensors are packed with features
 and options that streamline sensor installation
 and strengthen performance - yet fit in a small,
 clean package.




            Low profile
                 design Attractive new enclosures offer a flat,
                        extremely low profile appearance that
                        leaves the ceiling clean and
                        uncluttered.




360°
  coverage With a full 360° of coverage, these
           sensors are able to control a wide
           range of applications, either
           individually, or for large areas, in
           zones that overlap.




  SmartSet™
    technology
      Watt Stopper SmartSet technology means no
      adjustments are needed at installation.
      SmartSet monitors the space to identify usage
      patterns. With this information, it automatically



                                                          Walk-
      adjusts the time delay and sensitivity settings
      for both optimal performance and maximum


                                                           through mode
      energy efficiency.

                                                              The lights don’t need to stay on for the entire
                                                              length of the time delay if someone is just
                                                              dropping off mail or other items. With our
                                                              smart Walk Through Mode, lights turn off 3
                                                              minutes after an area is initially occupied if
                                                              no movement is detected within 30 seconds.
Quick
  terminal wiring
     Terminal wiring and depluggable terminal
     wiring are featured throughout our new
     generation of occupancy sensors. Quick and
     easy installations are now the new standard.




                       Low & line voltages       Low voltage sensors are well suited in most
                                                 applications. The simplicity of low voltage wiring
                                                 allows for optimal placement. However, some
                                                 applications, because of installer preference, are
                                                 better suited to line voltage ceiling mount sensors.
                                                 Our new generation of sensors are available in both
                                                 line and low voltage models to match each and
                                                 every application and installation style.




                                                     Diffusers
                                                             Both the ultrasonic and dual technology
                                                             sensors benefit from the new Ultrasonic
                                                             Diffusers. The diffusers are able to evenly
                                                             distribute the ultrasound in order to achieve
                                                             a more comprehensive coverage of the
                                                             controlled area.




                                              One touch
                                                light level
                                                      Many occupancy sensors contain a built-in
                                                      light level sensor. Our new generation
                                                      sensors incorporate this feature PLUS a
                                                      unique one-touch set up.




 Manual
   operation
  When the application calls for manual on/off control
  in addition to the occupancy based control, the new
  generation sensors do the job. They offer the
  convenience of a low voltage switch input (on the low
  voltage sensor models) so that wiring to a
  momentary wall switch is quick and easy.
              Occupancy sensor technologies




        Passive infrared
        ceiling mount sensors
        Many Watt Stopper PIR sensors
        are enhanced with advanced                Passive infrared technology (PIR)
        technologies to ensure higher
        sensitivity to minor motion               PIR technology senses occupancy by detecting the
        without the potential for false
                                                  difference between heat emitted from the human body in
        activations. These include
        Detection Signature Analysis              motion and the background space.
        and Pulse Count Processing.
                                                  Relying on a clear line-of-sight view, passive infrared
        WPIR
                                                  sensors make 100% coverage cut off possible. These
        CX series
                                                  sensors utilize a unique Fresnel lens which divides the
        CI-200 series
                                                  coverage area into zones, enhancing detection of small
        CI-300 series
                                                  movement.
        CB-100




                                          Wall switch technologies
                                          Watt Stopper automatic wall
                                          switches incorporate features, such
                                          as Zero Crossing, that increase the switch’s life and enhances
                                          reliability. They also offer features such as terminal style wiring,
                                          which simplifies installation, and SmartSet technology, which
                                          automatically adjusts time delays and sensitivity based on usage
                                          patterns.

                                          WS-200                    WN-100-120/277
                                          WA-200, WA-300            WD series
3   800.879.8585 • www.wattstopper.com    WI-200, WI-300
                                            Ultrasonic technology

                                             Using the Doppler principle, ultrasonic sensors work
                                             by bouncing ultrasonic sound waves off objects in an
                                             area and measuring the time it takes for the waves to
                                             return. Movement by a person in the area causes the
                                             sound waves to return at a changed frequency,
                                             resulting in a Doppler shift and occupancy detection.



         Ultrasonic technology
         These sensors utilize our Advanced Signal Processing Circuitry to
         automatically adjust the signal detection threshold in
         compensation for changing levels of activity and airflow. This
         helps eliminate false ON activations common in other ultrasonic
         sensors.

         W series
         WT series
         UT-300 series




Dual technology

While PIR and ultrasonic sensors provide
optimal control for a variety of spaces,                                 Dual technology
some applications pose difficulty for single
technology sensors.                                                      Dual Technology sensors
                                                                         ensure the greatest sensitivity
                                                                         and coverage for tough
We created and patented Dual Technology – a                              applications, without the threat
combination that takes advantage of the best                             of false triggers. This leads to
features of both PIR and ultrasonic technologies.                        the greatest energy savings.
Using the Dual Sensing Verification Principle, both
                                                                         DT-200 series
technologies must detect occupancy to turn
                                                                         DT-300 series
lighting on, while continued detection by only one
technology will hold lighting on.
                                                                                800.879.8585 • www.wattstopper.com   4
              Applying occupancy sensors



                                             In offices where the wall
                                             switch has a view of the work
                                             space, replace the switch with
                                             a passive infrared wall switch
                                             sensor. Take advantage of the
                                             built-in light level feature to
                                             keep lights off when ample
                                             sunlight is present.




                               Control lighting in restrooms with
                               ultrasonic sensors and eliminate
                               hours of unneeded on-time.
                               Ceiling-mounted ultrasonics can
                               sense motion around restroom
                               stalls for reliable coverage.




                                                  In open or partitioned offices,
                                                  use ultrasonic or dual
                                                  technology sensors. Placed on
                                                  the ceiling, these sensors
                                                  cover the area in zones that
                                                  overlap.




                                    PIR                                                     PIR Wall Switch
                                    Best Applications                                       Best Applications
                            • Warehouses                                            • Offices
                            • High ceiling mount locations                          • Copy rooms and other common
                            • Library bookstack or other aisles                       building areas
                            • Common building areas                                 • Storage closets
                            • Lobbies                                               • Small conference rooms
                            • Computer rooms




5   800.879.8585 • www.wattstopper.com
                          Common building spaces, such as
                          copy rooms, are ideal for
                          occupancy based control. With a
                          passive infrared sensor placed in
                          the corner of the ceiling or as a
                          wall switch replacement, users
                          can save hours of wasted lighting
                          each day.




                                 In large conference
                                 rooms, occupants may be
                                 still for long periods of time.
                                 Dual technology sensors will
                                 be able to detect the small motion
                                 and keep lights on as long as the
                                 space is occupied.




                                                           Use occupancy sensors
                                                           together with other control
                                                           methods such as lighting
                                                           control panels or daylighting
                                                           controls. Integrating control
                                                           options can help you meet
                                                           energy codes and sustainability
                                                           guidelines as well as maximize
                                                           energy savings.




                       In warehouses, a passive
                       infrared sensor mounted to
                       a ceiling or fixture will
                       control the lighting
                       between shelves – so that
                       lighting in unoccupied areas
                       will turn off or turn to a lower
                       level. Users can achieve this
                       control with fluorescent as well
                       as HID lighting.




         Ultrasonic                                                    Dual Technology
         Best Applications                                             Best Applications
• Restrooms                                               • Classrooms
• Open office spaces                                      • Large conference rooms
• Offices                                                 • Large offices
• Enclosed hallways                                       • Lunch rooms
• Stairways




                                                                            800.879.8585 • www.wattstopper.com   6
                WS-200 Automatic Wall Switch


                      Attractive, low-profile appearance                                                           Adjustable sensitivity

                                 Built-in light level sensor                                                       Zero Crossing Circuitry increases longevity

           Terminal style wiring for easy installation                                                             ASIC technology




       Specifications                                                                                                                           Applications
      • Dual 120/277 voltage                        • Compatible with all electronic                                                            • Small offices
      • 30 sec to 30 min time delay                   ballasts and PL lamp ballasts                                                             • Small conference rooms
      • Built-in light level sensor 2 to 200        • 2.6” x 1.7” x 2” L x W x D                                                                • Break rooms
        fc (107 to 1,614 lux)                         (66.0mm x 44.2mm x 50.8mm)                                                                • Utility rooms
      • No minimum load requirement                 • UL and CUL listed, 5 year warranty                                                        • Storage closets




       Wiring Diagram                                                                                Coverage Pattern


       The WS-200 can be                                  Neutral                                                                               Coverage shown is
       wired for single-level                                                                                                                   for half-step, walking
       lighting (shown), or                                                                                                                     motion, maximum of
       for manual bi-level      Load
                                                                                                                                                900 sq ft. For typical,
       control.                         Load                Line
                                                                                                                                                desktop activity,
                                                                                                                                        35'
                                                                                                                                      (10.7m)
                                                                                                                                                when mounted at 4 ft
                                                                                                                                                (1.2m), coverage is
                                       Ground                                                                                                   300 ft2 (27.9 m2).



                                                                                                                               15'
                                                                                                                             (4.6m)




          Order Information
             CATALOG #          VOLTAGE*                 LOAD REQUIREMENTS                   COVERAGE*
             WS-200             120 VAC; 60 Hz or         0-800 Watt Ballast or              up to 900 ft2 (83.6 m2), 180°
                                277 VAC; 60 Hz            0-1200 Watt Ballast
            Add –I to Cat. # for Ivory, -W for White, -A for Light Almond, -G for Grey, -B for Black; Single-gang cover plate
            ASP-211 included. Order ASP-422 for blank 2-gang cover plate, ASP-432 for 2-gang cover plate with switch
            option, specify color. *Models for 220-240 VAC (WS-230) and 347 VAC (WS-347) are available.




7   800.879.8585 • www.wattstopper.com
         WA Automatic Wall Switches


   SmartSet™ automatically selects optimal                                                                  Terminal style wiring simplifies installation
                  settings for each space
                                                                                                            Two relays and dual switch buttons control two
 Choice of Auto-ON or Manual-ON operation                                                                   separate lighting loads or circuits (WA-300)

                         Built-in light level sensor                                                        Audible and/or visual alerts of impending
                                                                                                            shut-off
            Selectable walk-through mode for
                            increased savings                                                               Vandal resistant hard lens

Specifications                                                                                                                    Applications
• Universal 100-300 VAC; 50/60 Hz                 • Built-in light level sensor 8 to 180                                          • Public area offices
  operation                                         fc (86 to 1,937 lux)                                                          • Small offices
• 1.0mm hard poly IR2 lens                        • No minimum load requirement                                                   • Small conference rooms
• SmartSet (automatic) time delay or              • Compatible with all electronic                                                • Storage closets
  fixed (5-30 minute)                               ballasts and PL lamp ballasts
• SmartSet (automatic) or reduced                 • 2.6” x 1.7” x 1.9” (66.0mm x
  sensitivity                                       43.2mm x 48.3mm)
• Zero Crossing Circuitry                         • UL and CUL listed, 5 year warranty




WA-200 Wiring                             WA-300 Wiring                                                     Coverage Pattern

                           Neutral        Neutral                     White


                                                                                                                                           Coverage shown is for half-
         Red              Hot BLK                                                                                                          step, walking motion,
  Load                                    Line      Black              Red      Primary
                                                                                 Load                                               25'
                                                                                                                                           maximum of 300 ft2. Typical
                                                                                                                                  (7.6m)   coverage at the desktop
     Ground                                         Blue              Brown Secondary
                                                                              Load                                                         level when mounted at 4 ft
         GRN                                      Ground                                                                                   is 150 ft2.


                                                                                                                          10'
  The WA-200 can be wired for                    The WA-300 can be wired for                                            (3.1m)

  single-level lighting (shown), or for          bi-level (shown) or dual circuit
  manual bi-level control.                       control.




   Order Information
    CATALOG #     DESCRIPTION                    VOLTAGE                        LOAD REQUIREMENTS       COVERAGE
   WA-200         Automatic wall switch          100/120 VAC; 50/60 Hz or       0-800 Watt Ballast or   up to 300 ft2
                                                 230/277 VAC; 50/60 Hz          0-1200 Watt Ballast     (28 m2)
   WA-300         Automatic wall switch,         100/120 VAC; 50/60 Hz or       0-800 Watt Ballast or   up to 300 ft2
                  dual relays                    230/277 VAC; 50/60 Hz          0-1200 Watt Ballast     (28 m2

    Add –I to Cat. # for Ivory, -W for White, -A for Light Almond, -G for Grey, -B for Black; Single-gang
    cover plate ASP-211 included. Order ASP-422 for blank 2-gang cover plate, ASP-432 for 2-gang
    cover plate with switch option, specify color.




                                                                                                                                 800.879.8585 • www.wattstopper.com      8
                    WI Automatic Wall Switches


         Choice of auto-ON or manual-ON operation                                                                           Two relays for control of two separate lighting
                                                                                                                            loads or circuits (WI-300)
          4 level lens for superior desktop detection
                                                                                                                            DIP switch adjustable sensitivity and time delay
                                             Built-in light level sensor




       Specifications                                                                                                                                       Applications
      • Dual 120/277 VAC                                      • No minimum load requirement                                                                 • Offices
      • Time delay of 15 sec to 30 min (WI-                   • Compatible with all electronic                                                              • Conference rooms
        200); 30 sec to 30 min (WI-300)                         ballasts and PL lamp ballasts
      • Built-in light level sensor 10 to 150                 • 2.8” x 4.8” x 1.5” (72.1mm x
        fc (107 - 1,614 lux) (on secondary                      121.9mm x 38.1mm)
        relay of WI-300)                                      • UL and CUL listed, 5 year warranty
      • LED indicator




       WI-200 Wiring                                         WI-300 Wiring                                       Coverage Pattern


        Neutral                                               Neutral
        277V Ground (GRN/YEL)                                                                                                                                0°
        120V Ground (GRN)                     Load
                                                             Hot              Black
        Hot (BLK)               Load (RED)
                                                                                                                                                             5°    4-level Fresnel lens
                                                                                      Blue    Primary                                                              detects horizontal and
                                                                                               Load
                                                                                                                                                             12°   vertical motion.
                                                                                             Secondary
                                                                                                                                                                   Maximum coverage
                                                                        Red           Red
                                                                                               Load


                                                                                                                                                  40'
                                                                                                                                                             30°   under ideal conditions
                                                               Ground (GRN)                                                                       (12.2m)          and for half-step walking
                                                                                                                                                                   motion is 1000 ft2.


     The WI-200 can be wired for                           The WI-300 can be wired for                                              15'
     single-level lighting (shown), or                     bi-level (shown) or dual circuit                                       (4.6m)

     for manual bi-level control.                          control.




         Order Information
            CATALOG #             DESCRIPTION                 VOLTAGE                   LOAD REQUIREMENTS          COVERAGE

            WI-200                Automatic wall switch       120 VAC; 60 Hz or          0-800 Watt Ballast or     up to 1000 ft2 (92.9m2) 180°
                                                              277 VAC; 60 Hz             0-1200 Watt Ballast
            WI-300                Automatic wall switch,      120 VAC; 60 Hz or          0-800 Watt Ballast or     up to 1000 ft2 (92.9m2) 180°
                                  dual relays                 277 VAC; 60 HZ             0-1200 Watt Ballast

           Add -W to cat # for White, -A for Light Almond; Order ASP-121 for blank switch 2-gang box
           plate; Order ASP-122 for 2-gang box plate with switch option (WI-200 only)




9   800.879.8585 • www.wattstopper.com
       WN Motion Sensor Nightlight Switch


       Manual-on or automatic-on operation                                                                         Adjustable time delay from 15 minutes to 2 hours

              Energy efficient, super bright LED                                                                   Impact resistant hard lens

     Built in nightlight illuminates whenever                                                                      Terminal wiring for quick and easy installation
                        overhead lights are off
                                                                                                                   Zero Crossing Circuitry increases product
                                                                                                                   longevity


Specifications                                                                                                                           Applications
• 120 or 277 VAC, 60 Hz                              • 2.63” x 1.69” x 1.88” (66.8mm x                                                   • Hotel guest bathrooms
• Time delay of 15 min, 30 min, 1                      42.9mm x 47.8mm)                                                                  • Military housing
  hour or 2 hours                                    • UL and CUL listed, 5 year warranty                                                • Healthcare facilities
• 1.0mm hard poly IR2 lens




Wiring Diagram                                                                                      Coverage Pattern


                                                    The WN-100 can be                                                                      The WN-100 has a
                                       Neutral
       Load                                         wired for single-                                                                      coverage range of 180°
                                       White
                                                    level lighting                                                                         and a maximum
                      TOP                           (shown), or for                                                                        coverage area of 300
    Load                               Hot
                                                    manual bi-level                                                              25'
                                                                                                                                           ft2. To maintain its
    Red                           ON

                                       Black        control.                                                                               coverage capacity and
                                  1                                                                                            (7.6m)
                                                                                                                                           optimally detect
                                                                                                                                           motion, the WN-100
    Ground                             Neutral                                                                                             must have a clear and
    Green       INDOOR USE ONLY
                                       White                                                                                               unobstructed view of
                                                                                                                        10'                occupants.
                                                                                                                      (3.1m)




   Order Information
    CATALOG #         VOLTAGE                    LOAD REQUIREMENTS                   COVERAGE
    WN-100-120 120 VAC; 60 Hz                    0-500W incandescent, fluorescent    up to 300 ft2 (28 m2), 180°
                                                 and compact fluorescent
    WN-100-277 277 VAC; 60 Hz                    0-1200W incandescent, fluorescent   up to 300 ft2 (28 m2), 180°
                                                 and compact fluorescent

    Add –I to Cat. # for Ivory, -W for White, -A for Light Almond; Single-gang cover plate ASP-211
    included. Order ASP-422 for blank 2-gang cover plate, ASP-432 for 2-gang cover plate with switch
    option, specify color.




                                                                                                                                        800.879.8585 • www.wattstopper.com   10
                      WD Dimmable Automatic Switch


              Occupancy sensing dimmable wall switch                                                                          Works with dimming ballasts

                                  Slide dimmer adjusts light level                                                            Vandal resistant, hard lens

                            Low profile, flat decorator design                                                                ASIC enhances reliability and helps to
                                                                                                                              eliminate false triggers
                      Zero voltage turn on/off increases life
                                                   of sensor


        Specifications                                                                                                                              Applications
       • WD-170, WD-270 operate at 120                              • 1.0 mm hard poly IR 2 lens                                                    • Small offices
         VAC; WD-180, WD-280 operate at                             • LED indicator                                                                 • Public area offices
         277 VAC                                                    • Adjustable sensitivity                                                        • Small conference rooms
       • WD-170/180 time delay of 30 sec to                         • 2.7”x1.8”x2.2” (68.9mm x 45.7mm x
         30 min                                                       55.9mm)
       • WD-270/280 fixed initial 15 min                            • UL and CUL listed, 5 year warranty
         delay for dim; secondary adjustable
         delay (5 min to 30 min) for off




        Wiring Diagram                                                                                            Coverage Pattern

         Neutral
                                   Load




         Ground GRN
         Hot BLK
                                                                                                                                                 Coverage shown is for half-
                       Load RED



                                                                                                                                                 step, walking motion,
                                                                                                                                                 maximum of 300 ft2. Typical
                                                                                                                                          25'
                                                                                                                                        (7.6m)
                                                                                                                                                 coverage at the desktop
                                          The WD can be wired for                                                                                level when mounted at 4 ft
                                          single-level lighting                                                                                  is 150 ft2.
                                          (shown) or for manual
                                          bi-level control.
                                                                                                                                 10'
                                                                                                                               (3.1m)




         Order Information
           CATALOG #              VOLTAGE                LOAD REQUIREMENTS       COVERAGE                OFF MODE
          WD-170                  120 VAC; 60 Hz         10-500 W Ballast        up to 300 ft2 (28 m2)   Automatic-OFF
          WD-180                  277 VAC; 60 Hz         10-500 W Ballast        up to 300 ft2 (28 m2)   Automatic-OFF
          WD-270                  120 VAC; 60 Hz         10-500 W Ballast        up to 300 ft2 (28 m2)   Dim-bef-disconnect

          WD-280                  277 VAC; 60 Hz         10-500 W Ballast        up to 300 ft2 (28 m2)   Dim-bef-disconnect

          Add –I to Cat. # for Ivory, -W for White, -A for Light Almond; Single-gang cover plate ASP-211
          included. Order ASP-422 for blank 2-gang cover plate, ASP-432 for 2-gang plate with switch option,
          specify color.           WD-170/180.wiring.single level




11   800.879.8585 • www.wattstopper.com
       CN, CW Vacancy Sensors for
       Residential Use
  Manual-on/automatic-off operation; lights                                                            Adjustable time delay from 1 to 30 minutes
                  cannot be overriden ON
                                                                                                       Impact resistant hard lens
      CN contains energy efficient nightlight
        that illuminates whenever overhead                                                             CEC 2005 Title 24 compliant
                                lights are off

              Simple pushbutton programming



Specifications                                                                                             Applications
• 120 VAC, 60 Hz                                • No minimum load requirement                              CW                            CN
• Time delay of 1 min to 30 min                 • 2.63” x 1.69” x 1.88” (66.8mm x                          • Hallways                    • Bathroom
• 1.0mm hard poly IR2 lens                        42.9mm x 47.8mm)                                         • Laundry rooms               • Bedrooms
• Compatible with 0-500W                        • UL and CUL listed, 5 year warranty                       • Garages
  incandescent, fluorescent, compact
  fluorescent, MLV, and ELV loads




Wiring Diagram                                                                              Coverage Pattern


                                      Neutral                                                                                 The sensors have a
       Load
                                      White                                                                                   coverage range of 180°
                                                                                                                              and a maximum
                                                                                                                              coverage area of 300
                     TOP
    Load                              Hot
    Red                          ON

                                      Black                                                                            25'    ft2. To maintain its
                                                                                                                     (7.6m)
                                                                                                                              coverage capacity and
                                 1




                                                                                                                              optimally detect
    Ground                            Neutral                                                                                 motion, the sensor
    Green      INDOOR USE ONLY
                                      White                                                                                   must have a clear and
                                                                                                                              unobstructed view of
                                                                                                             10'
                                                                                                           (3.1m)             occupants.




   Order Information
    CATALOG #          DESCRIPTION                VOLTAGE         LOAD REQUIREMENTS                        COVERAGE
   CN-100             Residential vacancy        120 VAC; 60 Hz   0-500W incandescent, fluorescent         up to 300 ft2 (28 m2), 180°
                      sensor with nightlight                      and compact fluorescent
   CW-100             Residential vacancy        120 VAC; 60 Hz   0-500W incandescent, fluorescent         up to 300 ft2 (28 m2), 180°
                      sensor                                      and compact fluorescent


    Add –I to Cat. # for Ivory, -W for White, -A for Light Almond. Single-gang cover plate ASP-211 included. Order ASP-422 for blank
    2-gang cover plate, ASP-432 for 2-gang cover plate with switch option, specify color.




                                                                                                                               800.879.8585 • www.wattstopper.com   12
                    WPIR Passive Infrared Sensor


        PIR occupancy sensor turns lights on and off                                                                                      ASIC technology reduces components and
                               based on occupancy                                                                                         provides greater reliability

                                         User-adjustable sensitivity                                                                      LED indicator

      User-adjustable time delay of 30 sec to 30 min                                                                                      30 segment multi-element Fresnel lens




        Specifications                                                                                                                   Applications
       • Adjustable time delay of 30 sec to                                 • 2.5” x 2.5” x 1.14”                                        • Small offices              • Computer rooms
         30 min                                                               (63.5mm x 63.5mm x 29.0mm)                                 • Copy rooms                 • Racquetball courts
       • Units per power pack: up to 8 (B);                                 • UL and CUL listed, 5 year warranty                         • Break rooms                • Library book stacks
         up to 10 (BZ)




        Product Controls                                                     Wiring Diagram                                  Coverage Pattern
                                Sensitivity                                   Neutral
                                Adjustment                                                                            Load
                                                                                                                      Load
        LED Indicator                         Override
                                                                                        White                   Red
                                                         Mounting                                    Power
                                                         Holes                Hot       Black        Pack       Red
              Time Delay
                                  SE




              Adjustment
                                 SE  N
                           TI
                           M




                                                                                                  Black
                           E




                                                                                                  Blue
                                                                                                  Red




                                                                                                                                                             Zone 1
                                                                                                                Switch                                       Zone 2
                                                     Sensor
                                                     Window                                                                   Horizontal                     Zone 3

                                                                                                                              coverage
                                                                                                                                                             Zone 4
                                                                                                                                                             Zone 5

                                                                                                  WPIR Sensor                 pattern


                                                                                                                                                   Vertical coverage pattern




                                                                                                                               5     4      3      2             1




          Order Information
            CATALOG #            VOLTAGE                        CURRENT                         COVERAGE
            WPIR                   24 VDC                           14 mA                       up to 300 ft2 (28 m2)

          All units are white and use Watt Stopper power packs




13   800.879.8585 • www.wattstopper.com
            CX Pa s s i ve I n f ra re d S e n s o r


                       Choice of four coverage patterns                                                                                                                     Swivel mounting bracket for convenient corner
                                                                                                                                                                            mounting to wall or ceiling
  User-adjustable time delay and sensitivity
                                                                                                                                                                            Built-in light level sensor (CX-100)
   ASIC technology reduces components and
                 provides greater reliability                                                                                                                               Isolated relay for use with HVAC or other
                                                                                                                                                                            control systems (CX-100)




Specifications                                                                                                                                                           Applications
• Time delay of 15 sec to 30 min                                           • 3.3” x 3.3” x 2.1” (83.8mm x                                                                • Large offices                                           • Open office spaces
• Built-in light level sensor 3 to 200                                       83.8mm x 53.3mm)                                                                            • Warehouses                                              • Classrooms
  fc (32 - 2,152 lux) (CX-100)                                             • UL and CUL listed, 5 year warranty                                                          • Computer rooms                                          • High bays
• Units per power pack: CX-100 up to
  6 (B), up to 8 (BZ); CX-105 up to 14
  (B), up to 18 (BZ)




Wiring & Controls                                                                                                                          Coverage Patterns
                                                                                                                                                                                                                            16ft

                                                                                                                                                                                                                             8ft
                                                              White (Neutral)                                                                                     t.
                                                                                                                                                              50f                                                             0

                                       Red (Line)                                                                                                                                                                            8ft

                                                                                                                                                                                                                            16ft
  N                  White         Power Pack
                                                                                             Lighting
                                                                                                                                                                                                   55ft.
                                                                                              Load                                                                                                                          10ft
  Hot                Black                                       Red (Load)        Switch                                                  TOP

                                                                                                                                                                                                 Standard                          0   10 15ft                          55ft                 85 90ft
                                        Black




                                                                                                                                                                                                 CX-100,                        Range Lens:
                                                                                                                                                                                                                           Long Long Range Lens (-1) CX-100-1, CX-105-1
                                                Blue




                                                                                   Wires
                                 Red




                                                       Isolated Relay Outputs
                                                         Normally Closed Contact   BRN
                                                         Common                    RED                                                                                                           CX-105
                                                         Normally Open Contact     ORN                                                           10 ft                                                                                      3 ft
        Auxiliary                                                                                                                                                                                                                             0
         Pack                                             Control Output 24VDC     YEL                                                     SIDE
                                                                      Common       GRN                                                                   0 7 ft 15 ft 25 ft               55ft                                                                         33° using MB-1 with
                                                                                                                                           5ft                                                                                             30ft                            maximum rotation
                     Blue                              Light Level Output 24VDC    BLU
                                                                                                                                            0
                                                                        +24VDC     VIO
                     Black                                                                                                                                                                                                                 15ft
                                                                        Common     GRA
                                                                                                                                          30ft            Dense Wide Angle Lens (Standard)                          15ft

                                                                                                                                                                   33.5ft                           33.5ft                                       0
  Hot               OFF switch      Light                                                                             Light               15ft                                                                      0
                                                                                                                                                                                                                                                     10 ft     0   10 ft 20 ft 30 ft 40 ft   50 ft
                                   Level                                                    on
                                                                                                                      Level
                    Red (load)    Lighting
                                                                                                        Sensitivity
                                                                                                                                            0
                                                                                                                                                 67ft             38ft   21ft 10ft   0 10ft 21ft      38ft   67ft                                    One Sided Aisleway:
                                   Load                                                     1 2 3 4 5
  N                                                                                                                                                                                                                                                  CX-100-4, CX-105-4
                                                                                      Time Delay DIP
                                                                                                                                         Two Sided Aisleway: CX-100-3, CX-105-3                                                                        Narrow Aisle Lens (-4)
                                                                                                                                                                                                                                                             using MB-1 bracket
                                                                                                                                                                                                                                                             with maximum rotation
                                                                                                                                                 Coverages shown are maximum. Under ideal conditions, coverage for half-step walking motion
                                                                                                                                                                Aisleway Lens (-3)
                                                                                                                                                                pointed straight down
                                                                                                                                                 (standard lens) can reach up to 2000 ft2 (185.8 m2), for desktop activity up to 1000 ft2 (92.9 m2).




      Order Information
        CATALOG #                VOLTAGE                     CURRENT               COVERAGE                                   FEATURES
      CX-100                     24 VDC                      19 mA                 up to 2000 ft2 (185.8 m2)                  light level, isolated relay
      CX-100-1                   24 VDC                      19 mA                 up to 90 linear ft (27.4 m)                light level, isolated relay
      CX-100-3                   24 VDC                      19 mA                 up to 120 linear ft (36.6 m)               light level, isolated relay
      CX-100-4                   24 VDC                      19 mA                 up to 50 linear ft (15.2 m)                light level, isolated relay
      CX-105                     24 VDC                        8 mA                up to 2000 ft2 (185.8 m2)
      CX-105-1                   24 VDC                        8 mA                up to 90 linear ft (27.4 m)
      CX-105-3                   24 VDC                        8 mA                up to 120 linear ft (36.6 m)
      CX-105-4                   24 VDC                        8 mA                up to 50 linear ft (15.2 m)

        All units are white and use Watt Stopper power packs. Order the MB-1 Industrial Mounting Bracket
        for installing the CX in industrial settings such as warehouses.


                                                                                                                                                                                                                     800.879.8585 • www.wattstopper.com                                                14
                      CI-200 Passive Infrared Sensor


                                                                                            360° coverage                                                        Isolated relay for use with HVAC or other
                                                                                                                                                                 control systems (CI-200)
               User adjustable time delay and sensitivity
                                                                                                                                                                 Built-in light level sensor (CI-200)
                             ASIC enhances reliability and helps
                                       eliminate false triggers




        Specifications                                                                                                                                                                                   Applications
       • Time delay 15 sec to 30 min                                                                 • 3.3” diameter x 2.2” total depth                                                                  • Open or partitioned
       • Built-in light level sensor 4 to 190                                                          (83.8mm x 55.9mm) Extends                                                                           office spaces
         fc (43 to 2,045 lux) (CI-200)                                                                 approx .36” from ceiling                                                                          • Conference rooms
       • SPDT isolated relay (CI-200)                                                                • UL and CUL listed, 5 year warranty                                                                • Computer rooms
       • Units per power pack: CI-200 up to                                                                                                                                                              • Classrooms
         5 (B), up to 7 (BZ); CI-205 up to 10
         (B), up to 13 (BZ)




        Wiring & Controls                                                                                                                                Coverage Patterns
                                                                                                                                                                                 Extended Range Lens : CI-200, CI-205
                                                                                White / Neutral

                                                     Red (Line)
         N                         White         Power Pack                                                Lighting     DIP Switch                                                 8 ft
                                                                                                           Load         for Time Delay
                                                                                                  Switch                and Sensitivity                                            Typical
         Hot                       Black                                          Red (Load)                                                                                      desk-top
                                                                                                                                                                                     level
                                                                                                                                                                        44 ft
                                                                         Isolated Relay Outputs   Cable
                                                       Black

                                                               Blue
                                               Red




                                                                         Closure upon Occupancy   Wires
                                                                         Normally Closed Contact 1-Brn
                                                                                                                                                                                                 22 ft         13 ft    7 ft 3 ft 0 3 ft 7 ft       13 ft        22 ft
                                                                         Common                  2-Red
                 Auxiliary                                               Normally Open Contact 3-Orn
                  Pack                                                                                         MAX
                                                                         Control Output 24VDC     4-Yel
                                                                                 Control Return   5-Grn        MIN
                                Blue                                  Light Level Output 24VDC    6-Blu

                                                                                                                                                                                   High Density Lens: CI-200-1, CI-205-1
                                                                                       +24VDC     7-Vio
                                Black                                                  Common     8-Gra


         Hot                 OFF switch     Light                                                                                                                                             8 ft
                                            Level                                                                     LED
                                            Lighting                                                                        Light Level
                             Red (load)                                                                                                                                                       Typical
                                            Load                                                                            Adjustment
                                                                                                                                                                                             desk-top
         N                                                                                                                                                                                      level
                                                                                                                                                                         24 ft
                                                                                                                                                                                                         12 ft 9 ft 7 ft 5 ft 3 ft     0        3 ft 5 ft 7 ft 9 ft 12 ft


                                                                                                                                                                                 Coverage shown represents half-step, walking motion.
                                                                                                                                                                                 Typical coverage at the desktop is 500 ft2 (46.5 m2) with
                                                                                                                                                                                 the Extended Range lens and 300 ft2 (111.5 m2) with the
                                                                                                                                                                                 High Density lens.




          Order Information
             CATALOG #                    VOLTAGE                                      CURRENT                                COVERAGE
          CI-200                           24 VDC                                       20 mA                                up to 1200 ft2 (111.5 m2)
          CI-200-1                         24 VDC                                       20 mA                                up to 500 ft2 (46.5 m2)
          CI-205                           24 VDC                                       11 mA                                up to 1200 ft2 (111.5 m2)
          CI-205-1                         24 VDC                                       11 mA                                up to 500 ft2 (46.5 m2)

             All units are white and use Watt Stopper power packs.




15   800.879.8585 • www.wattstopper.com
               CI-300, CI-355 360° PIR Sensor


                     Architecturally appealing low profile                                                                                                                      Accepts low voltage switch input for manual-on
                                              appearance                                                                                                                        operation (CI-300, CI-305)

           SmartSet automatically selects optimal                                                                                                                               Line and low voltage models available
                        time delay and sensitivity
                                                                                                                                                                                Walk-through mode increases
     Depluggable terminal wiring for quick and                                                                                                                                  savings potential
                             easy installation



Specifications                                                                                                                                                                                             Applications
• CI-300, CI-305: 24 VDC/VAC                                                                           • Isolated relay with N/O and N/C                     • Units per power pack: CI-300 up             • Open offices
• CI-355: 120/230/277/347 VAC,                                                                           outputs rated for 1 Amp at 30                         to 5 (B), up to 7 (BZ); CI-305 up to        • Conference rooms
  50/60 Hz                                                                                               VDC/VAC (CI-300)                                      12 (B), up to 16 (BZ)                       • Classrooms
• Time delays: SmartSet (automatic),                                                                   • Mounting options: ceiling tile; 4                   • 4.5” diameter x 1.02” (144.3mm x            • Offices
  fixed (5, 10, 15, 20, or 30 minutes),                                                                  square junction box with double                       25.9mm); (83.8mm x 55.9mm)
                                                                                                                                                                                                           • Storage rooms
  walk-through, test-mode                                                                                gang mudring (CI-300, CI-305)                         extends approx .36” from ceiling
                                                                                                                                                                                                           • Computer rooms
• Sensitivity adjustment: SmartSet                                                                     • Mounting options: 4 square                          • UL and CUL listed, 5 year
  (automatic) or reduced sensitivity                                                                     junction box with double gang                         warranty
• Built-in light level sensor; 10 to                                                                     mudring; 4 inch octagonal
  300 fc (107 to 3,229 lux) (CI-300,                                                                     junction box (CI-355)
  CI-355)

Wiring Diagrams                                                                                                                                                     Coverage Patterns
                                                                   White (Neutral)

                                  Red (Line)
 N          White             Power Pack
                                                                                                        Lighting                                                                                                      Extended Range Lens (Standard)
 Hot         Black                                                   Red (Load)           Switch
                                                                                                          load
                                                                                                                                                                                                                      CI-300, CI-305, CI-355
                                     Black

                                              Blue




                                                          Isolated Relay Outputs                                                                                                                  44 ft
                            Red




                                                            Common                        Relay Common                                                                                            13.4m      8 ft
                                                            Normally Open Contact                 N.O.
                                                            Normally Closed Contact              N.C.
       Auxiliary                                                                                                                                                                                            Typical
                     Blue                                                                                                                                                                                  desk-top
        Relay                                                                 Light Level (24VDC Out)                                                                                                         level
        Pack                                                                     Control (24VDC) Out
                                              Optional Momentary Switch   *              Man. Switch
                                                                                                                                                                                                                        22 ft        13 ft    7 ft 3 ft 0 3 ft 7 ft   13 ft       22 ft
                                                                                            +24V (In)
                      Black                                                                   Common
                                                                                        CI-300 Terminals
 Hot                 OFF switch
                                               Light
                                               level
                                                                  * Connect wire only when                                                              Neutral
                     Red (load)              lighting                                                                Load
                                                                                                                                                                                                                      High Density/Reduced Range Lens
 N
                                               load              momentary switch is installed

                                                                                                                                                                                                                      CI-300-1, CI-305-1, CI-355-1
                                         CI-300 Wiring                                                                Load                             Hot
                                                                                                                                                                                                  24 ft
                                                                                                                                                                                                  7.3m      8 ft
                                                                                                                       Ground                           Neutral                                             Typical
                                                                                                                                                                                                           desk-top
                                                                                                                      (Optional)                                                                              level


                                                                                                                                                                                                                       12 ft 9 ft 7 ft 5 ft 3 ft     0     3 ft 5 ft 7 ft 9 ft 12 ft
                                                                                                                                   CI-355 Wiring



       Order Information
       CATALOG #                                        VOLTAGE                                                    CURRENT/LOAD REQ                COVERAGE
       CI-300                                           24 VDC                                                     20 mA                           up to 1200 ft2 (111.5 m2)
       CI-300-1                                         24 VDC                                                     20 mA                           up to 500 ft2 (46.5 m2)
       CI-305                                           24 VDC                                                     9 mA                            up to 1200 ft2 (111.5 m2)
       CI-305-1                                         24 VDC                                                     9 mA                            up to 500 ft2 (46.5 m2)
       CI-355                                           120 VAC, 50/60 Hz                                          0-800 W Ballast/Tungsten        up to 1200 ft2 (111.5 m2)
                                                        230/277 VAC, 50/60 Hz                                      0-1200 W Ballast
                                                        347 VAC, 50/60 Hz                                          0-1500 W Ballast
       CI-355-1                                         120 VAC, 50/60 Hz                                          0-800 W Ballast/Tungsten        up to 500 ft2 (46.5 m2)
                                                        230/277 VAC, 50/60 Hz                                      0-1200 W Ballast
                                                        347 VAC, 50/60 Hz                                          0-1500 W Ballast

       All units are white and low voltage models use Watt Stopper power packs.
       For line voltage installations requiring an adapter plate, order cat # CA-1.
                                                                                                                                                                                                          800.879.8585 • www.wattstopper.com                                              16
                  CI-12,CI-24 Sensor for HVAC, BAS


                              Ceiling mount 360° sensor                                                         Four-level Fresnel lens offers superior desktop
                                                                                                                detection
        Interfaces directly with EMS or HVAC system
                      through internal isolated relay                                                           Advanced PIR technology

       User adjustable time delay and sensitivity via                                                           ASIC technology reduces components and
                                         DIP switch                                                             enhances reliability




        Specifications                                                                                         Applications
       • Time delay 30 seconds to 30                • 3.3” diam x 2.2” depth (83.8mm x                         • Open or partitioned                                            • Computer rooms
         minutes                                      55.9mm) extends approx .36” from                           office spaces                                                  • Classrooms
       • Isolated relay rated for 1 Amp at 24         ceiling                                                  • Conference rooms
         VAC/VDC                                    • UL and CUL listed, 5 year warranty




                  CB Low Temp Sensor


         PIR occupancy sensor for areas of extreme                                                              Choice of three coverage patterns
                                  low temperature
                                                                                                                Convenient DIP switch adjustments for time
        Watertight enclosure prevents moisture and                                                              delay and sensitivity
                       dust from affecting detection
                                                                                                                Isolated relay contact for use with HVAC or
                                                                                                                other control systems


        Specifications                                                                                         Applications
       • Time delay 15 sec to 10 min                • 3.94”x3.74”x2.36” (100.1mm x                             • Cold storage and                                               • Unconditioned
       • Temperature range -40°F to +95°F             95.0mm x 60.0mm)                                           freezers                                                         spaces
       • Units per power pack: up to 5 (B);         • UL and CUL listed, 5 year warranty
         up to 7 (BZ)                                                                                          Wiring Diagram
                                                                                                                                                                White / Neutral

                                                                                                                                         Red (Line)                                         Lighting
                                                                                                                N      White        Power Pack                                              Load


                                                                                                                Hot    Black                                      Red (Load)       Switch




         CI-12/CI-24 Order Information
                                                                                                                                 Black



                                                                                                                                                Blue
                                                                                                                                          Red




                                                                                                                                                       Isolated Relay Outputs      Cable
                                                                                                                                                       Closure upon Occupancy      Wires
                                                                                                                                                       Normally Closed Contact    1-Brn
                                                                                                                                                       Common                     2-Red
                                                                                                                                                       Normally Open Contact      3-Orn

          CATALOG #     VOLTAGE             LOAD REQUIREMENTS           COVERAGE                                                                         Control Output 24VDC     4-Yel
                                                                                                                                                                                  5-n/a

                         12 VDC             28 mA                       See coverage
                                                                                                                                                                                                              LED
          CI-12
                                                                                                                                                                                  6-n/a
                                                                                                                                                                       +24VDC     7-Vio
                                                                                                                                                                 Control Return   8-Gra
                                                                                                                                                                                                       on
                                                                                                                                                                                                             DIP
          CI-24          24 VAC, VDC        37 mA                       patterns CI-200
                                                                                                                                                                                                       off


                                                                                                                                                                                                             Switch




          Units are white; Extended Range lens is standard; Add -1 to
          Cat# for High Density/Reduced coverage lens.
                                                                              CB-100 Order Information
                                                                               CATALOG #     VOLTAGE      CURRENT              COVERAGE
                                                                              CB-100         24 VDC        20 mA               See coverage patterns CX-100

                                                                              Units are beige; Dense Wide Angle lens is standard; Add-1 to Cat# for Long
                                                                              Range, -3 for Two Sided Aisle way



17   800.879.8585 • www.wattstopper.com
           W Ultrasonic Occupancy Sensor


                      Advanced, omni-directional,                                                              Ideal for open office areas, conference rooms
                             Doppler technology                                                                and restrooms

        Adjustable time delay from 15 seconds                                                                  Advanced Signal Processing Circuitry
                                 to 15 minutes                                                                 automatically adjusts detection threshold
              500, 1000, 2000 sq ft, and hallway
                            coverages available



Specifications                                                                                                Applications
• Ultrasonic technology with 25KHz                  • Adjustable sensitivity                                  • Open and partitioned             • Storage areas
  frequency                                         • Units per power pack: up to 7 (B);                        spaces                           • Conference rooms
• Temperature and humidity resistant                  up to 9 (BZ)                                            • Restrooms                        • Hallways
  receivers                                         • 4.5” x 4.5” x 1.25” (114.3mm x
• Logic key/ON bypass                                 114.3mm x 31.8mm)
• LED indicator                                     • UL and CUL listed, 5 year warranty




Wiring Diagram                                                                                   Coverage Patterns

 Neutral                                     Load                                                                                   W-2000A
                                             Load                                                                           20'
                                                                                                                                    W-1000A
                                                                                                        29'
            White                      Red                                                                                  12'
                                                                                                                                    W-500A
                         Power                                                                                24'                                      **W-2000H
                                                                                                                            10'
 Hot        Black        Pack          Red
                                                                                                                            5'
                                                                                                                                                             Coverage shown
                                                                                                                                                             represents half-step,
                                                                                                  45'   25'   20'     5'    5'        15' 20'   25'   45'
                                                                                                                                                             walking motion.
                      Black
                      Blue




                                                                                                                                                             **W-2000H coverage is
                      Red




                                                                                                                            10'

                                       Switch
                                                                                                                            12'                              not drawn to scale
                                                                                                                            20'
                                                                                                                           sensor
                    Occupancy Sensor




   Order Information
       CATALOG #      VOLTAGE                 CURRENT              COVERAGE
    W-500A             24 VDC                 16 mA                360°, 500 ft2 (46.5 m2)
    W-1000A            24 VDC                 16 mA                360°, 1000 ft2 (92.9 m2)
    W-2000A            24 VDC                 16 mA                360°, 2000 ft2 (185.8 m2)
    W-2000H            24 VDC                 16 mA                360°, 90 linear ft (27.4 m)
    All units are white and use Watt Stopper power packs.




                                                                                                                                         800.879.8585 • www.wattstopper.com          18
                        WT Ultrasonic Occupancy Sensor


        Ultrasonic technology with 32 KHz frequency                                                                                                                   User-adjustable DIP switch time delay and
                                                                                                                                                                      sensitivity settings
                                 Utilizes advanced, omni-directional,
                                                 Doppler technology                                                                                                   600, 1100, 2200 sq ft and hallway
                                                                                                                                                                      coverages available
              Advanced Signal Processing automatically
                                                                                                                                                                      Isolated relay allows sensor to interface with
                           adjusts detection threshold
                                                                                                                                                                      building control systems


        Specifications                                                                                                                                                                            Applications
       • Ultrasonic technology with 32 KHz                                                          • Units per power pack:                                                                       • Open and partitioned spaces
         frequency                                                                                    WT-605 up to 4 (B), 5 (BZ); WT-600                                                          • Restrooms
       • Time delay 15 sec to 30 min                                                                  up to 3 (B), 4 (BZ); WT-1105, WT-                                                           • Storage areas
       • Isolated relay with N/O and N/C                                                              2205, WT-2255 up to 3 (B), 5 (BZ);
                                                                                                                                                                                                  • Conference rooms
         outputs; rated for 1 amp @ 30                                                                WT-1100, WT-2200, WT-2250 up to
         VDC/VAC                                                                                      2 (B), 3 (BZ)                                                                               • Hallways
       • 4.8” diam x 1.5” depth (121.9mm x                                                          • UL and CUL listed, 5 year warranty
         38.1mm)




        Wiring & Controls                                                                                                                               Coverage Patterns

                                                     White (Neutral)
                                                                                                                                                                45'     26' 22'                  0'                22' 26'                  45'
                        Red (Line)

               White
                                                                                                                                                          21'
        N                                                                         Lighting   Transducers                                                                                              WT-2200/2205
                             Power Pack                                            Load
               Black                                   Red (Load)       Switch
        Hot                                                                                                                                               14'
                                                                                                                                                                                  WT-1100/1105        WT-600/605
                                              Isolated Relay Outputs     Cable
                                                                                                                 DIP switch
                               Black

                                       Blue
                       Red




                                              Closure upon Occupancy Wires
                                                                                                                                                           5'
                                                 Normally Closed Contact 1 Brn
                                                 Common                  2 Red                                      LED                                                                                                      WT-2250/2255
                                                 Normally Open Contact 3 Orn                  ON                                                           0'
                                                                                              1 2 3 4 5 6

                                                Control Output 24VDC      4 Yel                                                                            5'
                                                       Control Return     5 Grn
                                                       No Connection      6 Blu                                      Sensitivity
                                                            +24VDC        7 Vio                             S

                                                                                                                                                          14'
                                                            Common        8 Gra
                                                                                                                                                                                                                              Coverage shown
                                                                                                                                                          21'                                                                 represents half-step,
                                                                                                                                                                                                                              walking motion




              Order Information
              CATALOG #                           VOLTAGE                         CURRENT                   COVERAGE                                FEATURE
              WT-605                             24 VDC                          27 mA                      360° one-sided, 600 ft2 (55.7 m2)
              WT-600                             24 VDC                          37 mA                      360° one-sided, 600 ft2 (55.7 m2)       isolated relay
              WT-1105                            24 VDC                          30 mA                      360° two-sided, 1100 ft2 (102.2 m2)
              WT-1100                            24 VDC                          40 mA                      360° two-sided, 1100 ft2 (102.2 m2)     isolated relay
              WT-2205                            24 VDC                          30 mA                      360° two-sided, 2200 ft2 (204.4 m2)
              WT-2200                            24 VDC                          40 mA                      360° two-sided, 2200 ft2 (204.4 m2)     isolated relay
              WT-2255                            24 VDC                          30 mA                      360° two-sided, 90 linear ft (27.4 m)
              WT-2250                            24 VDC                          40 mA                      360° two-sided, 90 linear ft (27.7 m)   isolated relay

              All units are white and use Watt Stopper power packs.



19   800.879.8585 • www.wattstopper.com
           UT-300, UT-355 360° Ultrasonic Sensor


                                         Architecturally appealing low                                                                                        Accepts low voltage switch input for manual-on
                                                   profile appearance                                                                                         operation (UT-300, UT-305)

SmartSet automatically selects optimal time                                                                                                                   Ultrasonic diffusers give more
                       delay and sensitivity                                                                                                                  comprehensive coverage

  Depluggable terminal wiring for quick and                                                                                                                   Walk-through mode increases
                          easy installation                                                                                                                   savings potential


Specifications                                                                                                                                                                               Applications
• UT-300, UT-305: 24 VDC/VAC                                                • Isolated relay with N/O and N/C                           mudring; 4 inch octagonal                            • Restrooms
• UT-355: 120/230/277/347 VAC,                                                outputs rated for 1 Amp at 30                             junction box (UT-355)                                • Large Offices
  50/60 Hz                                                                    VDC/VAC (UT-300)                                        • Units per power pack: UT-300                         • Open Offices
• Time delays: SmartSet                                                     • Built-in light level sensor; 10 to                        up to 2 (B), up to 3 (BZ); UT-305
  (automatic), fixed (5, 10, 15, 20,                                          300 fc (107 to 3,229 lux) (UT-                            up to 3 (B), up to 4 (BZ)
  or 30 minutes), walk-through,                                               300, UT-355)                                            • 4.5” diameter x 1.02” (144.3mm
  test-mode                                                                 • Mounting options: ceiling tile; 4                         x 25.9mm) (83.8mm x 55.9mm)
• Sensitivity adjustment:                                                     square junction box with double                           Extends approx .36” from ceiling
  SmartSet (automatic) or                                                     gang mudring (UT-300, UT-305)                           • UL and CUL listed, 5 year
  reduced sensitivity                                                       • Mounting options: 4 square                                warranty
• Ultrasonic frequency of 40 kHz                                              junction box with double gang

UT-300 Wiring                                                                                                      UT-355 Wiring                                   Coverage Patterns
                                                         White (Neutral)                                                                                Neutral     25'       20'    15'   10'    5'     0'      5'      10'   15'   20'   25'
                                                                                                                        Load
                       Red (Line)
 N      White      Power Pack                                                                                                                                       20'                                               UT-300-3
                                                                                          Lighting

 Hot     Black                                             Red (Load)        Switch
                                                                                            load                        Load                           Hot          15'
                                                                                                                                                                                                                UT-300-2
                          Black




                                                                                                                                                                    10'                                       UT-300-1
                                  Blue
                 Red




                                                 Isolated Relay Outputs
                                                  Common                     Relay Common                                Ground                         Neutral
                                                  Normally Open Contact              N.O.                                                                            5'
                                                  Normally Closed Contact           N.C.                                (Optional)
                                                                                                                                                                     0'
                                                                    Control (24VDC) Out
                                    OPTIONAL Momentary Switch*              Man. Switch                                                                              5'
                                                                               +24V (In)
                                                                                 Common                                                                             10'
                                                                            UT-300 Terminals
                         * Connect wire only when                                                                                                                   15'
                        momentary switch is installed

                                                                                                                                                                    20'

                                                                                                                                                                    25'

                                                                                                                                                                          UT-300-1   up to 500 sq ft for walking motion (22.3' x 22.3')
                                                                                                                                                                   Coverages represent half-step (31.6' x 31.6')
                                                                                                                                                                      UT-300-2 up to 1000 sq ft for walking motion
                                                                                                                                                                                                                   walking
                                                                                                                                                                      UT-300-3 up to 2000 sq ft for walking motion (44.7' for each
                                                                                                                                                                   motion. Actual coverages can vary x 44.7')
                                                                                                                                                                   application based on room shape, use and
                                                                                                                                                                     (walking motion coverage shown)

                                                                                                                                                                   obstacles.



       Order Information
       CATALOG #                          VOLTAGE                                                CURRENT/LOAD REQ                    COVERAGE
       UT-300-X                           24 VDC                                                     43 mA                           see diagram
       UT-305-X                           24 VDC                                                     37 mA
       UT-355-X                           120 VAC, 50/60 Hz                                          0-800 W
                                          230/277 VAC, 50/60 Hz                                      Ballast/Tungsten
                                          347 VAC, 50/60 Hz                                          0-1200 W Ballast
                                                                                                     0-1500 W Ballast

       X = 1 for 500 ft2 of coverage; -2 for 1000 ft2; -3 for 2000 ft2.
       All units are white and low voltage models use Watt Stopper power packs.
       For line voltage installations requiring an adapter plate, order cat # CA-1.



                                                                                                                                                                                           800.879.8585 • www.wattstopper.com                    20
                     DT-200 Dual Technology Sensor


                                      Combines passive infrared and                                                                                                 SmartSet automatically selects optimal settings
                                            ultrasonic technologies                                                                                                 for each space

         Trouble-free lighting control in applications                                                                                                              Accepts low voltage switch input for
              difficult for single technology sensors                                                                                                               manual-on operation

                                                         Built-in light level sensor                                                                                Walk-through mode increases savings
                                                                                                                                                                    potential


        Specifications                                                                                                                                                                     Applications
       • 24 VDC/VAC                                                                 • SPDT isolated relay (DT-200)                   • 4.4" x 3.4" x 2" (111.8mm x                         • Classrooms
       • Ultrasonic frequency of 40 kHz                                             • Isolated relay with N/O and N/C                  86.4mm x 50.8mm)                                    • Conference and training
       • Time delays: SmartSet                                                        outputs rated for 1 Amp at 24                  • UL and CUL listed, 5 year                             rooms
         (automatic), fixed (5, 10, 15, 20,                                           VDC/VAC (DT-200)                                 warranty                                            • Large offices
         or 30 minutes), walk-through,                                              • Built-in light level sensor; 2 to
         test-mode                                                                    200 fc (21 to 2,152) lux) (DT-200)
       • Sensitivity adjustment:                                                    • Units per power pack: DT-200
         SmartSet (automatic) or                                                      up to 3 (B), up to 4 (BZ); DT-205
         reduced sensitivity                                                          up to 4 (B), up to 5 (BZ)




        Wiring Diagram                                                                                                                             Coverage Pattern
                                                                           White (Neutral)

                                              Red (Line)
         N                 White          Power Pack
                                                                                                          Lighting
                                                                                                            load
         Hot                Black                                            Red (Load)          Switch


                                                                                                                                                                                                   Coverages shown are
                                                 Black




                                                                                                                                                                                      PIR
                                                          Blue
                                        Red




                                                                   Isolated Relay Outputs
                                                                     Common                  RED
                                                                                                                                                                                      coverage     maximum. Under ideal
                                                                     Normally Open Contact   ORG                                                                                      55ft.        conditions, coverage for
                                                                     Normally Closed Contact BRN
               Auxiliary                                                                                                                                                              Ultrasonic   half-step walking
                Relay         Blue                                   Light Level (24VDC Out)    BLU
                Pack                                                 Control (24VDC) Out        YEL
                                                                                                                                                                                      coverage     motion (standard lens)
                                                                                                                                                                                      38ft.
                                                                 Momentary Switch               GRN                                                                                                can reach up to 2000 ft2,
                                                                    +24V (In)                   VIO
                              Black                                 Common                      GRA
                                                                                                                                                                                                   for desktop activity up
                                                                                               DT-200                                                                                              to 1000 ft2.
                                                                                                wires
         Hot               OFF switch
                                            Light                                                                                          10 ft
                                            level
                           Red (load)     lighting
         N
                                            load

                                                                                                                                                   0   7 ft 15 ft   25 ft      55ft




                                                                                                                                                   Dense Wide Angle Lens (Standard)
             Order Information
             CATALOG #                VOLTAGE                          CURRENT               COVERAGE                FEATURES
             DT-200                   24 VDC                           43 mA                 2000 ft2 (185.8 m2)     light level, isolated relay
             DT-205                   24 VDC                           35 mA                 2000 ft2 (185.8 m2)

             All units are white and use Watt Stopper power packs.




21   800.879.8585 • www.wattstopper.com
               DT-300 360° Dual Technology Sensors


                     Architecturally appealing low profile                                                                                                                   Accepts low voltage switch input for manual-on
                                              appearance                                                                                                                     operation (DT-300, DT-305)

      SmartSet™ automatically selects optimal                                                                                                                                Depluggable terminal wiring for quick and easy
                     settings for each space                                                                                                                                 installation

                                                                                                                                                                             Walk-through mode increases savings potential
                                        Ultrasonic diffusers give more
                                             comprehensive coverage
                                                                                                                                                                             line and low voltage models available


Specifications                                                                                                                                                                                   Applications
• DT-300, DT-305: 24 VDC/VAC                                                                      • Isolated relay with N/O and N/C                  mudring; 4 inch octagonal                   • Classrooms
• DT-355: 120/230/277/347 VAC,                                                                      outputs rated for 1 Amp at 30                    junction box (DT-355)                       • Open office spaces
  50/60 Hz                                                                                          VDC/VAC (DT-300)                               • Units per power pack: DT-300                • Computer rooms
• Time delays: SmartSet                                                                           • Built-in light level sensor; 10 to               up to 2 (B), up to 3 (BZ); DT-305
  (automatic), fixed (5, 10, 15, 20,                                                                300 fc (107 to 3,229 lux) (DT-300,               up to 3 (B), up to 4 (BZ)
  or 30 minutes), walk-through,                                                                     DT-355)                                        • 4.5” diameter x 1.02” (144.3mm
  test-mode                                                                                       • Mounting options: ceiling tile; 4                x 25.9mm) Extends approx .36”
• Sensitivity adjustment: SmartSet                                                                  square junction box with double                  from ceiling
  (automatic) or reduced                                                                            gang mudring (DT-300, DT-305)                  • UL and CUL listed, 5 year
  sensitivity                                                                                     • Mounting options: 4 square                       warranty
• Ultrasonic frequency of 40 kHz                                                                    junction box with double gang

Wiring Diagrams                                                                                                                                                                             Coverage Pattern
                                                                    White (Neutral)

                                        Red (Line)
  N                  White          Power Pack
                                                                                                       Lighting
                                                                                                         load
  Hot                 Black                                           Red (Load)         Switch
                                           Black

                                                   Blue
                                  Red




                                                            Isolated Relay Outputs
                                                              Common                     Relay Common                                                                  Neutral
                                                              Normally Open Contact              N.O.                             Load
         Auxiliary
                                                              Normally Closed Contact           N.C.
                                                                                                                                                                                                                                   44 ft
          Relay         Blue                                                 Light Level (24VDC Out)                                                                                                                             (13.4m)
          Pack                                                                  Control (24VDC) Out
                                                          Momentary Switch              Man. Switch
                                                                                                                                  Load                             Hot
                                                                                           +24V (In)
                        Black                                                                Common
                                                                                        DT-300 Terminals
  Hot                OFF switch
                                                                                                                                   Ground                              Neutral
                                          Light
                                          level                                                                                   (Optional)
                     Red (load)         lighting
  N
                                          load                                                                                                                                           40 ft x 40 ft
                                                                                                                                                                                       (12.2m x 12.2m)
                                  DT-300 Wiring                                                                                                DT-355 Wiring
                                                                                                                                                                                         Coverage shown is maximum and represents
   Wiring diagram includes bi-level control and                                                                                                                                          half-step walking motion. Under ideal conditions,
   manual-on option with momentary switch.                                                                                                                                               coverage for half-step walking motion can reach
                                                                                                                                                                                         up to 1000 ft2 (92.9 m2).




        Order Information
        CATALOG #                                  VOLTAGE                                             CURRENT/LOAD REQ                   COVERAGE
        DT-300                                 24 VDC                                                  43 mA                                up to 1000 ft2 (92.9 m2)
        DT-305                                 24 VDC                                                  35 mA                                up to 1000 ft2 (92.9 m2)
        DT-355                                 120 VAC, 50/60 Hz                                       0-800 W Ballast/Tungsten             up to 1000 ft2 (92.9 m2)
                                               230/277 VAC, 50/60 Hz 0-1200 W Ballast                                                       up to 1000 ft2 (92.9 m2)
                                               347 VAC, 50/60 Hz                                       0-1500 W Ballast                     up to 1000 ft2 (92.9 m2)

        All units are white and low voltage models use Watt Stopper power packs.
        For line voltage installations requiring an adapter plate, order cat # CA-1.




                                                                                                                                                                                               800.879.8585 • www.wattstopper.com            22
                Power Packs


        Fully self-continued transformer and relay                                                              Two-relay output power pack that accepts signals
                                                                                                                from multiple control devices (LC-100)
          Many models of power pack products for
                      wide range of applications                                                                Daylighting control with photosensor (LC-100)

                                              Plenum rated                                                      2 channel dimming with 0-10V ballasts (LC-100)

                                                                                                                Load shed dimming or ON/OFF switching
                                                                                                                capability (LC-100)

        B Power Pack Specifications                               BZ Specifications                                     LC-100 Specifications
       • Secondary voltage of 24VDC                               • 120/277 VAC voltage input, 60 Hz                   • 120/277 VAC voltage input, 50/60 Hz
       • Secondary output of 150 mA, 114 mA with                  • Secondary voltage of 24VDC                         • 2 relay outputs rated 20 Amp 120V
         relay connected                                          • Secondary output of 150 mA, 150 mA with              tungsten and ballast, 20 Amp 277V ballast
       • Low voltage leads rated for 300 volts                      relay connected                                    • Secondary output of 150 mA, 150 mA with
       • UL rated 94V-0 plastic enclosure, units                  • Low voltage leads rated for 300 volts                relay connected
         are white                                                • UL rated 94V-0 plastic enclosure, units            • Dual switch inputs for on/off or dimming
       • ABS UL 2043 plenum rated plastic and                       are grey                                           • 2 isolated NO/NC relays rated 1 Amp @ 24
         wiring                                                   • ABS UL 2043 plenum rated plastic and                 VDC
       • 1.6" x 2.75" x 1.6" (41mm x 70mm x                         wiring                                             • NEMA 1 enclosure, acceptable for use in
         41mm) with a 1/2’ snap-in nipple                         • Relay is Zero Crossing                               plenum spaces
       • UL and CUL listed, 5 year warranty                       • Hold-ON/hold-OFF inputs                            • Output power 150mA @ 24 VDC with
                                                                  • LED status and overcurrent indicator                 automatic overload protection
                                                                  • 1.6" x 2.75" x 1.6" (41mm x 70mm x                 • Dual voltage input 120 or 277 VAC @ 14
                                                                    41mm) with a 1/2’ snap-in nipple                     watts maximum
                                                                  • UL and CUL listed, 5 year warranty                 • Switch wiring distances up to 1000 feet
                                                                                                                         with 18 gauge wire
                                                                                                                       • 6.6" x 6.1" x 2.1" (168mm x 156mm x
                                                                                                                         54mm) with a 1/2’ nipple
                                                                                                                       • UL and CUL listed, 5 year warranty
         Order Information
                                                                   LOAD RATINGS
          CATALOG #              INPUT VOLTAGE            BALLAST(A) INCAN(A) MOTOR(HP)       OUTPUT

          Power Packs
          B120E-P                 120VAC, 60Hz              20       13           1           24VDC; 150mA***
          B277E-P                 277VAC, 60Hz              20       -            -           24VDC; 150mA***
          B230E-P                 220-240VAC, 50/60Hz       20       13           1           24VDC; 150mA***
          B347D-P                 347VAC, 60Hz              15                    -           24VDC; 150mA***
          BZ-100                  120/277VAC, 60Hz          20       20           1           24VDC; 150mA†
          LC-100                  120/277 VAC; 50/60 Hz     20       20           1           24VDC; 150mA†
          Auxiliary Packs
          S120/277/               120/277/347VAC            20/20/15 13/-/-       1/-/-       -
          347E-P
          Form C Power Packs
          A120C-P**               120VAC, 60Hz              8NO/5NC 5NO/3NC       1NO/2.5NC   24VDC; 100mA
          A277C-P**               277VAC, 60Hz              6NO/3NC 5NO/2.5NC 2NO/.5NC        24VDC; 100mA
          2 Relay Power Packs
          C120E-P                 120VAC, 60Hz              20*      13*          1*          24VDC; 150mA
          C277E-P                 277VAC, 60Hz              20*      -            -           24VDC; 150mA
          Power Supplies
          AT-120                  120VAC, 60Hz              -        -            -           24VDC; 800mA
          AT-277                  277VAC, 60Hz              -        -            -           24VDC; 800mA

          * Ratings per relay. ** Contain an isolated relay with normally open (NO) and normally closed (NC)
          contacts. ***Output is 150mA before relay is connected and 114mA after relay is connected.
          †Output is 150mA with relay connected.


23   800.879.8585 • www.wattstopper.com
            Outdoor Motion Sensors


                Optional model with lampholders                                                                 Line and low voltage models available

          Weatherproof and raintight for reliable                                                               90 degree or long-range field of view (EN)
                                   performance
                                                                                                                Security override-ON option allows lights to be
            Adjustable light level and time delay                                                               turned on for length of time delay
                                          settings
                                                                                                                Isolated relay enables interface with security
                                                                                                                systems or other loads

  EW Specifications                                                                            EN Specifications
  • Operating temperature range: -           • Zero Crossing Circuitry                         • Operating temperature range: -            • Manual override-ON allows
    40°F to +130°F                           • 1/2’ threaded nipple fits                         40°F to +130°F                              lights to be turned on for 4
  • UL 773A rated raintight; UL 1571           standard NEMA weatherproof                      • UL 773A rated raintight; UL                 hours
    rated for wet locations                    fixture fitting                                   1571 rated for wet locations              • 3/4’ threaded nipple fits
  • Adjustable time delay of 12 sec          • Lamp holders us PAR 20 or 38                    • Adjustable time delay of 12 sec             standard NEMA weatherproof
    to 16 min                                  lamps, up to 150W each lamp                                                                   fixture fitting
                                                                                                 to 16 min
  • Light level adjustment of .5 to          • EW sensor: 6.7” x 3.2” x 2.2”
                                                                                               • Light level adjustment of .4 to           • 4.3” x 3.0” x 2.3” (110mm x
    200 fc (5 - 2152 lux)                      (170mm x 80mm x 55mm)
                                                                                                 42 fc (4.3 - 452 lux)                       77mm x 58mm)
  • Isolated relay with NO/NC                • UL and CUL listed, 5 year
    outputs; rated for 1 Amp @ 30              warranty                                        • SPDT isolated relay                       • UL and CUL listed, 5 year
    VDC/VAC (EW-200)                                                                           • Zero Crossing Circuitry                     warranty

   Applications                                                                                    Applications
   • Walkways and entranceways                • Garages and yards                                  • Walkways and entranceways              • Doorways
   • Dock lighting                            • Driveways                                          • Dock lighting                          • Corridors




EW Order Information
CATALOG #      VOLTAGE               LOAD REQ/CURRENT *        COVERAGE         FEATURES
EW-200         - 120, - 277 VAC       0-1000 W ballast          270°              Isolated relay
EWF-205        - 120 VAC              0-1000 W ballast          270°              Lamp holders
EW-205-24      24 VDC                 8 mA                      270°              Controls outdoor HIDs
EW-105-24      24 VDC                 8 mA                      180°              Controls outdoor HIDs

Specify voltage by adding -120 or -277 to Cat. #. Add -W to Cat. # for
Arctic White, -G for Architectural Grey
*For 120 VAC applications, tungsten loads are also acceptable.



                                                                         EN Order Information
                                                                         CATALOG #         VOLTAGE                   LOAD REQUIREMENT*       COVERAGE             FEATURES
                                                                         EN-100           - 120, - 277 VAC           0-1000 W ballast        90°                 Isolated relay
                                                                         EN-200           - 120, - 277 VAC           0-1000 W ballast        Long range          Isolated relay

                                                                         Specify voltage by adding -120 or -277 to Cat. #. Add -W to Cat. # for Arctic White, -G for
                                                                         Architectural Grey
                                                                         *For 120 VAC applications, tungsten loads are also acceptable.




                                                                                                                                        800.879.8585 • www.wattstopper.com        24
                   IT-200 InteliTimer Logger


          Determines energy savings potential from                                                           IT-ProSoft Software provides single-step data
                            occupancy sensor use                                                             retrieval, storage, analysis, printing

        Adjustable light pipe observes lighting level                                                        Logs when a space is occupied/ vacant and
                                                                                                             when lighting is on/off
          Logs when a space is occupied/ vacant and
                             when lighting is on/off                                                         Small and lightweight for ease of use
                                                                                                             and portability


        IT-200 Specifications                                                           IT-ProSoft Software Specifications
       • PIR technology                           • Recessed reset switch               • List entries include number, date,                               • Reports show graphs of
       • Lithium battery; 10 year average         • Stores up to 4096 entries             time of entry, and                                                 occupancy/lighting, potential
         life                                     • Stores site name to identify area     lighting/occupancy status                                          dollar savings, statistical
       • Test button to activate                    being monitored                     • Users set energy cost per kWh,                                     information
         occupancy and light level LEDs           • Connects to PC for data               size of controlled load, and site                                • Operable in 6 languages
         for 90 seconds                             retrieval                             name                                                             • Windows compatible
       • Adjustable sensitivity                                                         • HVAC adder calculates savings                                    • Downloadable at
                                                                                          from reduction of cooling                                          www.wattstopper.com




        IT-200 Controls                                                                    Sample Logger Reports
                                                                                                                                      Graphs of Lighting/Occupancy for Office Suite #301

                                                                                                                                      Date of Entries       Midnight         06:00 AM           Noon        06:00 PM
                                   Occupancy                                                                                          Monday
                                   sensor lens                                                                                        January 8
                                                                                                                                                         §
                                                                                                                                                         §
          Light pipe
                                                            Light level                                                                     graph indicates Monitored Area Lit    §
                                                                                                                                                                                  § graph indicates Monitored Area Occupied
                                                            sensitivity
                                                            adjustment                     Entries: 42                                  Cost/kWhr: $0.080
                                                                                           From: Sun, Aug 14, 1995 at12:00:00 PM        HVAC Adder: 15%
                                                                                           To:      Thu, Aug 18, 1995 at 9:32:00 PM     Load Size: 180W
                                                                                                                                                                                 LIGHTING/OCCUPANCY SUMMARY
                                                                                              1    Sun, Aug 14, 1995 at12:00:00 PM Lights ON Occupied
                                                                                              2    Sun, Aug 14, 1995 at 2:25:00 PM Lights ON Vacant
                                                                                                                                                                        ON+Occupied:        59.81 hours   17.8%
         Reset button                                      Test button                        3
                                                                                              4
                                                                                                   Mon, Aug 15, 1995 at 7:50:00 AM Lights ON Occupied
                                                                                                   Mon, Aug 15, 1995 at10:15:00 AM Lights ON Vacant
                                                           (activates                         5    Mon, Aug 15, 1995 at10:50:00 AM Lights ON Occupied
                                                                                                                                                                        ON+Vacant:          80.64 hours   24.0%


                                                           LEDs)                              6    Mon, Aug 15, 1995 at12:15:00 PM Lights OFF Vacant                    OFF+Occupied:           0 hours   0.0%

                                                                                                                                                                        OFF+Vacant:        195.55 hours   58.2%



              Red LED                                    Green LED
           (occupancy)                                   (light)
                                 Data connector
                                      port




         Order Information
          CATALOG #      DESCRIPTION
          IT-200          Occupancy and light logger, PC connector cable included

          All units are white




25   800.879.8585 • www.wattstopper.com
                TS Digital Time Switches


                  Automatically turns lights off after                                                                              Terminal style wiring for simplified installation
                                         preset time
                                                                                                                                    Digital operation and simple
                Bright electroluminescent LCD shows                                                                                 pushbutton set-up
                                   timer’s countdown
                                                                                                                                    Time scroll features allows time to adjust
       Optional audible or visual alerts before
                                                                                                                                    up or down
                                 lights turn off



Specifications                                                                                                                                                                       Applications
• TS-400: 100-300 AC; 50/60 Hz                     • Optional visual warning:                                 • TS-400-24 contains SPDT                                              • Equipment rooms
• TS-400-24: 24 VAC/VDC/VAC                          flashes lights at 5 min and 1                              isolated relay rated for 1 Amp                                       • Storage areas
  half-wave rectified input                          min prior to time-out                                      @ 30 VDC                                                             • Closets
• Time out adjustments range                       • Optional audible warning:                                • 2.66” x 1.79” x 1.76” (67.5mm x
  from 5 minutes to 12 hours (5                      beeps every 5 sec at 1 min                                 45.5mm x 44.7mm)
  minute increments to 1 hour,                       prior to time-out                                        • UL and CUL listed, 5 year
  then 15 minute increments to                     • Compatible with all electronic                             warranty
  12 hours)                                          ballasts and motor loads




TS-400 Wiring Diagram                                      TS-400-24 Wiring Diagrams
                                                                        White (Neutral)
                                    Hot
                                                                           Red (Line)                                                          InteliSwitch®
                                                                                                                                                                          +24V IN (BLU)
                                                                                                                                               Digital Time Switch

                                                                                                               Lighting
                                  Neutral                                                                                                      TS-400-24        +24V IN
                                                                                                                                                                          COMM. (WHT)
                 Load                                       White
                                                                                 Power
                                                                                                                Load                                            COMM.


                                                                                                                                                                 N.C.
                                                            Neut                                                                                                 RLY
                                                                                                                                                                COMM.     PULSE OFF (BLK)
                                                                                 Pack                                                      ON
                                                                                                                                                                 N.O.

                                                            Black                                   Red                                    1
                                                                                                                                                                 PULSE
                                                                                                                                                                  ON
                                                                                                                                                                 PULSE    PULSE ON (RED)
                                                                                                                                                                  OFF

                                                             Hot                                   (Load)
                                                                                                              Local                                                                                        #20/4
    Load




                                                                                                            OFF Switch
                                                                                      Blue




                                                                                                                                                                                                          To Panel
                                                                                                                                                                                                          1000' MAX.
                                                                                 Black
                        Ground




                                                                      RLY COMM
                                                                                             Red




                                                                                                                                                                               To circuit
                                                                       COMM
           ON
                                                            ON




                                                            1
                                                                        N.O.                                                                                                                On   Off Comm        24VRect
           1




                                                                       +24V IN
                                                                                                                                                                                             Red Black   White Blue
    Line




                                                           TS-400-24 wiring with power pack                                                         TS-400-24 wiring with lighting control panel




   Order Information
    CATALOG #                    VOLTAGE                         LOAD REQ/CURRENT
   TS-400                        100/120 VAC or             0-800 Watt ballasts or
                                 220/277 VAC; 50/60 Hz      0-1200 Watt ballast
   TS-400-24                     24 VAC/VDC/VAC rect.       Current: 12mA DC/41mA AC

    Add –I to Cat. # for Ivory, -W for White, -A for Light Almond; Single-gang cover plate ASP-211
    included. Order ASP-422 for blank 2-gang cover plate, ASP-432 for 2-gang plate with switch option,
    specify color.




                                                                                                                                                                                  800.879.8585 • www.wattstopper.com       26
Product Line Summary
                WS-200               120/277 VAC; 60 Hz             Automatic wall switch       Passive infrared


                WA-200    120/277 230/277 VAC, 50/60 Hz             Automatic wall switch       Passive infrared
                WA-300    120/277 230/277 VAC, 50/60 Hz                  -with dual relays      Passive infrared


                WI-200               120/277 VAC; 60 Hz             Automatic wall switch       Passive infrared
                WI-300               120/277 VAC; 60 Hz                  -with dual relays      Passive infrared


         WN-100-120                      120 VAC, 60 Hz    Motion sensor nightlight switch      Passive infrared
         WN-100-277                      277 VAC, 60 Hz    Motion sensor nightlight switch      Passive infrared


              WD Series            120 or 277 VAC; 60 Hz            Dimmable wall switch        Passive infrared


                CN-100                   120 VAC, 60 Hz        Residential vacancy sensor       Passive infrared
                CW-100                   120 VAC, 60 Hz        Residential vacancy sensor       Passive infrared


                  WPIR                           24 VDC             Ceiling mount sensor        Passive infrared


              CX Series                          24 VDC        Ceiling/wall mount sensor        Passive infrared


        CI-200 Series                            24 VDC             Ceiling mount sensor        Passive infrared


        CI-300 Series                            24 VDC             Ceiling mount sensor        Passive infrared
        CI-355 Series     120/230/277/347 VAC; 50/60 Hz             Ceiling mount sensor        Passive infrared


               CI-12/24                       12/24 VDC             Sensor for HVAC, BAS        Passive infrared


                CB-100                           24 VDC          Low temperature sensor         Passive infrared


               W Series                         24 VDC              Ceiling mount sensor              Ultrasonic


              WT Series                          24 VDC             Ceiling mount sensor              Ultrasonic


        UT-300 Series                            24 VDC             Ceiling mount sensor              Ultrasonic
        UT-355 Series     120/230/277/347 VAC; 50/60 Hz             Ceiling mount sensor              Ultrasonic


        DT-200 Series                            24 VDC        Ceiling/wall mount sensor        Dual technology


        DT-300 Series                            24 VDC             Ceiling mount sensor        Dual technology
        DT-355 Series     120/230/277/347 VAC; 50/60 Hz             Ceiling mount sensor        Dual technology




WS-05-20050                                                               800.879.8585 • www.wattstopper.com

				