					                                                                 Solid Fuel Commercial / Industrial Boilers                                                            Table 1b
                                                            State:                Colorado


                                                                          Control
                                          Permit Thresholds                                                                      Hazardous Air
                                                                     Requirements /
                                          (i.e., tons per year                                    Control             Opacity      Pollutant
    Source Category5                                                 Emission Limits                                                                          Comments6
                                              [tpy] of what                                      Technology          Limitations    (HAP)
                                                                       (i.e., BACT,
                                         regulated pollutant)                                                                     Limitations
                                                                      lb/mmBtu/yr)

                                                                                                                                                         No specific or different
                                                                                                                                                         permit or control
    Fuels-for-Schools                                                                                                                                    technology requirements
                                                                                                                                                         exist for Fuels-for-
        Projects7                                                                                                                                        Schools Projects. Please
       (<10mmBtu                                                                                                                                         see
       Heat Input)                                                                                                                                       Commercial/Industrial
                                                                                                                                                         category below.

                                         In attainment areas,      CAQCC Reg. No. 3            Certain VOC          20%, with       N/A, unless source   At the Aquila W.N. Clark
                                         permit thresholds are 5   requires RACT for new       controls and oil     allowance for   would trigger        Station (Canon City),
       Commercial /                      tons per year (tpy) for   and modified minor          and gas industry     30% during      major source         Unit 55 (226 mmBTU/hr)
         Industrial                      VOCs, PM, PM10 and        sources in nonattainment    controls are         startup         levels.              and Unit 59 (346
                                         PM2.5; and 10 tpy for     and                         specified under                                           mmBTU/hr) are coal-
        (>10 mmBtu                       CO, NOx and SO2. In       attainment/maintenance      CAQCC Reg. No.                                            fired units permitted to
        Heat Input8)                     nonattainment areas,      areas. PSD and NANSR        7, otherwise                                              burn up to a 5% wood
                                         permit thresholds are 1   requirements apply to       control technology                                        mixture. Unit 55 up to
                                         tpy for PM10 and PM2.5;   major stationary sources.   determinations are                                        4,182 tpy of wood and
                                                                                                                                                         Same permit and control
                                                                                                                                                         technology requirements
                                                                                                                                                         that apply to the
                                                                                                                                                         Commercial/Industrial
              Other                                                                                                                                      category above. Interest
                                                                                                                                                         in smaller units (<10
                                                                                                                                                         mmBtu/hr) used for
                                                                                                                                                         space heating or in
                                                                                                                                                         support of a process

5 Includes cordwood, chip, bark, and pelletized wood fuel

6
    Limitations of fuel switching, etc
7
    Small commercial / institutional boilers. Provide project-specific details in Table 2 (Fuels-for-Schools Projects)
8
    NSPS threshold
                                                    Solid Fuel Commercial / Industrial Boilers                                      Table 1b
                                               State:                Montana


                                                               Control
                               Permit Thresholds                                                       Hazardous Air
                                                          Requirements /
                               (i.e., tons per year                           Control       Opacity      Pollutant
    Source Category5                                      Emission Limits                                                   Comments6
                                   [tpy] of what                             Technology    Limitations    (HAP)
                                                            (i.e., BACT,
                              regulated pollutant)                                                      Limitations
                                                           lb/mmBtu/yr)

                             NO                         NO                  NO            YES         NO               Montana has a statewide
                                                                                                                       rule requiring no more
    Fuels-for-Schools                                                                                                  than 20% opacity avg'd
                                                                                                                       over 6 min.
        Projects7
       (<10mmBtu
       Heat Input)


                             NO                         NO                  NO            YES         NO               See above.

      Commercial /
        Industrial
       (>10 mmBtu
       Heat Input8)


                             NA                         NA                  NA            NA          NA               NA




            Other




5
    Includes cordwood, chip, bark, and pelletized wood fuel
6
    Limitations of fuel switching, etc
7
    Small commercial / institutional boilers. Provide project-specific details in Table 2 (Fuels-for-Schools Projects)
8
    NSPS threshold
                                                    Solid Fuel Commercial / Industrial Boilers                                          Table 1b
                                               State:              New Mexico


                                                               Control
                               Permit Thresholds                                                          Hazardous Air
                                                          Requirements /
                               (i.e., tons per year                               Control      Opacity      Pollutant
    Source Category5                                      Emission Limits                                                      Comments6
                                   [tpy] of what                                 Technology   Limitations    (HAP)
                                                            (i.e., BACT,
                              regulated pollutant)                                                         Limitations
                                                           lb/mmBtu/yr)

                             >10 pph or 25 tpy of any   Must meet standards at                                            Have not permitted any
                             regulated pollutant        property boundary                                                 such systems.
    Fuels-for-Schools
        Projects7
       (<10mmBtu
       Heat Input)


                             >10 pph or 25 tpy of any   Must meet standards at                                            All would be evaluated
                             regulated pollutant        property boundary                                                 on a project specific
      Commercial /                                                                                                        basis. We have only
        Industrial                                                                                                        seen a few applications
                                                                                                                          for commercial/industrial
       (>10 mmBtu                                                                                                         power generation
       Heat Input8)                                                                                                       projects


                             >10 pph or 25 tpy of any   Must meet standards at                                            All would be evaluated
                             regulated pollutant        property boundary                                                 on a project specific
                                                                                                                          basis.

            Other




5
    Includes cordwood, chip, bark, and pelletized wood fuel
6
    Limitations of fuel switching, etc
7
    Small commercial / institutional boilers. Provide project-specific details in Table 2 (Fuels-for-Schools Projects)
8
    NSPS threshold
                                                    Solid Fuel Commercial / Industrial Boilers                                       Table 1b
                                               State:              North Dakota


                                                               Control
                               Permit Thresholds                                                             Hazardous Air
                                                          Requirements /
                               (i.e., tons per year                                 Control       Opacity      Pollutant
    Source Category5                                      Emission Limits                                                       Comments6
                                   [tpy] of what                                   Technology    Limitations    (HAP)
                                                            (i.e., BACT,
                              regulated pollutant)                                                            Limitations
                                                           lb/mmBtu/yr)

                             None                       SO2 - 3.0 lb/MMBtu        None          20%         Comply with ND
                                                         Federal & ND AAQS                                  Air Toxics Policy
    Fuels-for-Schools                                        Exempt from PM
                                                        limits
        Projects7
       (<10mmBtu
       Heat Input)


                             None                       PM emission rate =        None          20%         Comply with ND
                                                        0.6 lb/MMBtu or less                                Air Toxics Policy
      Commercial /                                      depending on rated heat
        Industrial                                      input
                                                        SO2 = 3.0 lb/MMBtu
       (>10 mmBtu                                                   Federal &
       Heat Input8)                                     ND AAQS




            Other




5
    Includes cordwood, chip, bark, and pelletized wood fuel
6
    Limitations of fuel switching, etc
7
    Small commercial / institutional boilers. Provide project-specific details in Table 2 (Fuels-for-Schools Projects)
8
    NSPS threshold
                                                    Solid Fuel Commercial / Industrial Boilers                                                    Table 1b
                                               State:              South Dakota


                                                                Control
                               Permit Thresholds                                                                 Hazardous Air
                                                           Requirements /
                               (i.e., tons per year                                   Control         Opacity      Pollutant
    Source Category5                                       Emission Limits                                                            Comments6
                                   [tpy] of what                                     Technology      Limitations    (HAP)
                                                             (i.e., BACT,
                              regulated pollutant)                                                                Limitations
                                                            lb/mmBtu/yr)

                             Minor permit if greater     Total suspended             Case-by-case   20%         Not applicable   Not applicable
                             than 25 tons per year but   particulate matter and      basis
    Fuels-for-Schools        less than 100 tons per      sulfur dioxide emission
                             year. Title V permit if     limit based on size of unit
        Projects7            100 tons per year or
       (<10mmBtu             greater
       Heat Input)


                             Minor permit if greater     Total suspended             Case-by-case   20%         Not applicable   Not applicable
                             than 25 tons per year but   particulate matter and      basis
      Commercial /           less than 100 tons per      sulfur dioxide emission
        Industrial           year. Title V permit if     limit based on size of unit
                             100 tons per year or
       (>10 mmBtu            greater
       Heat Input8)




            Other




5
    Includes cordwood, chip, bark, and pelletized wood fuel
6
    Limitations of fuel switching, etc
7
    Small commercial / institutional boilers. Provide project-specific details in Table 2 (Fuels-for-Schools Projects)
8
    NSPS threshold
                                                    Solid Fuel Commercial / Industrial Boilers                            Table 1b
                                               State:                  Utah


                                                               Control
                               Permit Thresholds                                                     Hazardous Air
                                                          Requirements /
                               (i.e., tons per year                          Control      Opacity      Pollutant
    Source Category5                                      Emission Limits                                            Comments6
                                   [tpy] of what                            Technology   Limitations    (HAP)
                                                            (i.e., BACT,
                              regulated pollutant)                                                    Limitations
                                                           lb/MMBTU/yr)



    Fuels-for-Schools
         Projects7                 No Lower Limit              BACT
       (<10MMBTU
        Heat Input)




      Commercial /
        Industrial
                                   No Lower Limit              BACT
      (>10 MMBTU
       Heat Input8)




            Other                  No Lower Limit              BACT




5
    Includes cordwood, chip, bark, and pelletized wood fuel
6
    Limitations of fuel switching, etc
7
    Small commercial / institutional boilers. Provide project-specific details in Table 2 (Fuels-for-Schools Projects)
8
    NSPS threshold
                                                     Solid Fuel Commercial / Industrial Boilers                                                              Table 1b
                                              State:                            Washington


                                                              Control
                             Permit Thresholds                                       Control                         Hazardous Air
                                                         Requirements /
                             (i.e., tons per year                                  Technology             Opacity      Pollutant
    Source Category5                                     Emission Limits                                                                           Comments6
                                 [tpy] of what                                                           Limitations    (HAP)
                            regulated pollutant)
                                                           (i.e., BACT,               In rules                        Limitations
                                                          lb/mmBtu/yr)

                            State jurisdiction,       BACT                        Wood fired units      20% not to be    BACT, separate       De minimis emission
                            threshold is 400,000 Btu                              limited to PM of      exceeded more    criteria for state   rates: Soot blowing
                            or larger for wood fired                              0.2 grain/dscf,       than 3 minutes   regulated Toxic      must be scheduled.
                            units or emissions                                    based on EPA          per hour. One    Air Pollutants.      Fuel switching can be
    Fuels-for-Schools       above de minimis                                      Method 5 testing.     15 minute                             allowed by permit, may
        Projects
                 7          emission rates (see                                    Oil, gas, coal       period every 8                        have operating hour
                            table next to comments                                fired units limited   hours may                             restrictions or different
       (<10mmBtu            column for rates).                                    to PM of 0.1          exceed 20% for                        BACT derived emission
       Heat Input)          Local authorities may                                 grain/dscf, based     soot blowing.                         limitations.
                            have different heat input                             on EPA Method 5
                            or emission rate de                                   testing. SO2
                            minimii.                                              limited to 1000
                                                                                  ppm 1 hr average.
                            Permit required            BACT                       Same as above         Same as above. Same as above          Same as above

      Commercial /
         Industrial
       (>10 mmBtu
                  8
       Heat Input )




          Other




5
  Includes cordwood, chip, bark, and pelletized wood fuel
6
  Limitations of fuel switching, etc
7
  Small commercial / institutional boilers. Provide project-specific details in Table 2 (Fuels-for-Schools Projects)
8
    NSPS threshold

				
DOCUMENT INFO
Description: New Mexico Small Business Startup document sample