08745 Electrical Locking Systems by xqv17864

VIEWS: 55 PAGES: 33

									                                               SECTION 08745
                                        ELECTRICAL LOCKING SYSTEMS

                           (When editing, display hidden text notes to specifier.)
** NOTE TO SPECIFIER ** Security Door Controls; electromagnetic locks, delayed egress locking
systems, electrified mortise and cylindrical locks, electric bolt locks, electric strikes, power supplies,
access controls, request-to-exit push bars, electrical locking system accessories.

This section is based on the products of Security Door Controls., located at:
 3580 Willow Lane.
 Westlake Village, CA 91361
 Tel: 805-494-0622
 Tel: 800-413-8783 (toll free)
 Fax: 805-494-8861

  www.sdcsecurity.com


PART 1 - GENERAL

1.01   SECTION INCLUDES
** NOTE TO SPECIFIER ** Delete items below not required for project.

        A.       Electromagnetic locks.

        B.       Delayed egress locking systems.

        C.       Electrified mortise and cylindrical locks.

        D.       Electric bolt locks.

        E.       Electric strikes.

        F.       Power supplies.

        G.       Access controls.

        H.       Request-to-exit push bars.

        I.       Electrical locking system accessories.

1.02    REFERENCES

        A.       Builders Hardware Manufacturers Association (BHMA):
                 1.      BHMA A156 Standards for Door Hardware.

        B.       National Fire Protection Association (NFPA):
                 1.      NFPA 101 Life Safety Code.

        C.       Underwriters Laboratories Inc. (UL):
                 1.     UL Standards for Electrified Locking Equipment and Power Supplies.

1.03    SUBMITTALS

        A.       Submit under provisions of Section 01300.

        B.       Shop Drawings: Door Schedule showing each item of hardware to be installed on each
                 door.


                                        ELECTRICAL LOCKING SYSTEMS                                     08745 - 1
                1.      Use Architect's door numbers on schedule.
                2.      Schedule may be combined with submittals required in other door hardware
                        sections.
                3.      Description and Sequence of Operation of each electrified door hardware
                        function, including location, and interface with fire alarm, access control, and
                        security systems as applicable. Include description of component functions that
                        occur when authorized person wants to enter; authorized person wants to exit;
                        unauthorized person wants to enter; and unauthorized person wants to exit.

        C.      Product Data: Manufacturer's data sheets on each product to be used, including
                installation instructions.

        D.      Operating and Maintenance Data: Include operating, troubleshooting, maintenance, and
                repair instructions for each item, with lists of spare parts, if any, and name, address, and
                phone number of local stocking distributors.

1.04    QUALITY ASSURANCE

        A.      Manufacturer: ISO 9001 certified.

        B.      Installer Qualifications: Experienced door hardware installer.

1.05    DELIVERY, STORAGE, AND HANDLING

        A.      Store products in manufacturer's unopened packaging until ready for installation.

PART 2 - PRODUCTS

2.01    MANUFACTURERS

        A.       Acceptable Manufacturer: Security Door Controls (SDC), 3580 Willow Lane, Westlake
                 Village, CA 91361. Phone 800-413-8783; Fax 805-494-8861; www.sdcsecurity.com.
** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of
Division 1 section on product options and substitutions.

        B.      Substitutions: Not permitted.

        C.      Requests for substitutions will be considered in accordance with provisions of Section
                01600.

2.02    MATERIALS

        A.      General Requirements: Provide devices suitable for door type, lock type, frame type,
                dimensions and overall operation.
                1.     Coordinate with doors, frames, and hardware specified in other sections.
                2.     Provide all brackets, spacers, shims, lip extensions, strike boxes, and other
                       accessory parts necessary to complete the installation.
                3.     Provide all necessary components to supply power to devices from building
                       power distribution system.

2.03    ELECTROMAGNETIC LOCKS
** NOTE TO SPECIFIER ** The following are direct-pull type electromagnetic locks with holding force of
1650, 1200, and 650 pounds. Delete all that are not required. If more than one type of lock is required,
give each a type designation and indicate type on Door Schedule.

        A.      Electromagnetic Locks, 1650 lb Holding Force: SDC 1511-1542 Series locks shall be
                surface mounted and include all necessary mounting hardware. Core shall not contain
                any epoxy-resin, and consist of steel laminations welded in a steel U-Channel. The


                                   ELECTRICAL LOCKING SYSTEMS                                       08745 - 2
             winding and electronics to be contained within the aluminum housing and be replaceable
             without removing the lock from the doorframe.
             1.       Holding force shall be 1650 lbs.
             2.       Locks operate with 12 or 24VDC power input without field selection. Current
                      required shall not exceed 670 mA @ 12VDC or 350 mA @ 24VDC for single lock
                      and 1.34 Amp @ 12VDC or 700 mA @ 24VDC for double lock.
             3.       All field wiring connections shall be via on-board screw terminal connections.
                      Magnetic lock shall contain printed-circuit board providing circuit and surge
                      protection.
             4.       Locks shall be BHMA Certified Grade 1 ranking.
             5.       Locks shall be listed by Underwriters Laboratories as Auxiliary Locks (GWXT)
                      and as Burglary resistant electrically operated door locking mechanism (CVXJ).
             6.       Locks shall comply with UL10C standards for positive pressure fire rated doors.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             7.       Locks shall have a door position switch (DPS) to allow monitoring of the
                      open/closed status of the door.
             8.       Locks shall have a magnetic bond-sensor (BA) circuit to allow monitoring of the
                      strength of the magnetic field between lock and armature.
             9.       Locks shall have an anti-tamper switch (ATS) to indicate an attempt to remove
                      cover.
             10.      Locks shall have tri-color LED Status Indicator (L3): Green, Red, Yellow.
             11.      Locks shall be enclosed in full opening width housing.
             12.      Pairs of Doors Without Mullion: Provide both locks in a single housing.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             13.      Case Finish: 628 Satin Aluminum, Clear Anodized
             14.      Case Finish: 313 Dark Bronze Anodized
             15.      Case Finish: 335 Black Duronodic
             16.      Case Finish: 605E Bright Brass Anodized
             17.      Case Finish: 606E Satin Brass Plated
             18.      Case Finish: 611E Bright Bronze Plated
             19.      Case Finish: 625E Bright Chromium Plated
             20.      Case Finish: 626E Satin Chromium Plated

        B.   Electromagnetic Locks, 1200 lb Holding Force: SDC 1571-1572 Series locks shall be
             surface mounted and include all necessary mounting hardware. Core shall not contain
             any epoxy-resin, and consist of steel laminations welded in a steel U-Channel. The
             winding and electronics to be contained within the aluminum housing and be replaceable
             without removing the lock from the doorframe.
             1.       Holding force shall be 1200 lbs.
             2.       Locks shall operate with 12 or 24VDC power input without field selection.. Current
                      required shall not exceed 250 mA @ 12VDC or 125 mA @ 24VDC.
             3.       All field wiring connections shall be via on-board screw terminal connections.
                      Magnetic lock shall contain printed-circuit board providing circuit and surge
                      protection.
             4.       Locks shall be BHMA Certified Grade 2 ranking.
             5.       Locks shall be listed by Underwriters Laboratories as Auxiliary Locks (GWXT)
                      and as Burglary resistant electrically operated door locking mechanism (CVXJ).
             6.       Locks shall comply with UL10C standards for positive pressure fire rated doors.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             7.       Locks shall have a door position switch (DPS) to allow monitoring of the
                      open/closed status of the door.
             8.       Locks shall have a magnetic bond-sensor (BA) circuit to allow monitoring of the
                      strength of the magnetic field between lock and armature.
             9.       Locks shall have an anti-tamper switch (ATS) to indicate an attempt to remove
                      cover.
             10.      Locks shall have tri-color LED Status Indicator (L3): Green, Red, Yellow.


                                  ELECTRICAL LOCKING SYSTEMS                                  08745 - 3
             11.    Locks shall be enclosed in full opening width housing.
             12.    Pairs of Doors Without Mullion: Provide both locks in a single housing.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             13.    Case Finish: 628 Satin Aluminum, Clear Anodized
             14.    Case Finish: 313 Dark Bronze Anodized
             15.    Case Finish: 335 Black Duronodic
             16.    Case Finish: 605E Bright Brass Anodized
             17.    Case Finish: 606E Satin Brass Plated
             18.    Case Finish: 611E Bright Bronze Plated
             19.    Case Finish: 625E Bright Chromium Plated
             20.    Case Finish: 626E Satin Chromium Plated

        C.      Electromagnetic Locks, 650 lb Holding Force: SDC 1580 Series locks shall be surface
                mounted and include all necessary mounting hardware. Core shall not contain any epoxy-
                resin, and consist of steel laminations welded in a steel U-Channel. The winding and
                electronics to be contained within the aluminum housing and be replaceable without
                removing the lock from the doorframe.
                1.       Holding force shall be 650 lbs.
                2.       Locks shall operate with 12 or 24VDC power input with out field selection..
                         Current required shall not exceed 440 mA @ 12VDC or 220 mA @ 24VDC for
                         single lock and 880 mA @ 12VDC or 440 mA @ 24VDC for double lock.
                3.       All field wiring connections shall be via on-board screw terminal connections.
                         Magnetic lock shall contain printed-circuit board providing circuit and surge
                         protection.
                4.       Locks shall be BHMA Certified Grade 3 ranking.
                5.       Locks shall be listed by Underwriters Laboratories as Auxiliary Locks (GWXT)
                         and as Burglary resistant electrically operated door locking mechanism (CVXJ).
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
                6.       Locks shall have a door position switch (DPS) to allow monitoring of the
                         open/closed status of the door.
                7.       Locks shall have a magnetic bond-sensor (BA) circuit to allow monitoring of the
                         strength of the magnetic field between lock and armature.
                8.       Locks shall have tri-color LED Status Indicator (L3): Green, Red, Yellow.
                9.       Pairs of Doors Without Mullion: Provide both locks in a single housing.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
                10.      Case Finish: 628 Satin Aluminum, Clear Anodized
                11.      Case Finish: 313 Dark Bronze Anodized
                12.      Case Finish: 335 Black Duronodic
                13.      Case Finish: 605E Bright Brass Anodized
                14.      Case Finish: 606E Satin Brass Plated
                15.      Case Finish: 611E Bright Bronze Plated
                16.      Case Finish: 625E Bright Chromium Plated
                17.      Case Finish: 626E Satin Chromium Plated
** NOTE TO SPECIFIER ** The following are shear type electromagnetic locks with holding force of 2700
and 2000 pounds. Delete all that are not required. If more than one type of lock is required, give each a
type designation and indicate type on Door Schedule.

        D.      Electromagnetic Shear Locks, 2700 lb Holding Force: SDC 1565-1566 Series locks shall
                be mortise mounted and shall be provided with all required mounting hardware. Shear
                Lock design shall incorporate shear stops to prohibit horizontal shear motion. Units shall
                provide for both lateral and vertical field adjustment. Model 1566 shall be capable of being
                fit into 1-1/4 inch face frame.
                1.        Holding force shall be 2700 lbs.
                2.        Locks shall operate with 12 or 24VDC power input without field selection. Current
                          required shall not exceed 800 mA @ 12VDC or 400 mA @ 24VDC.



                                   ELECTRICAL LOCKING SYSTEMS                                     08745 - 4
                3.  Locks shall incorporate automatic relock with 1 to 5 second delay relock timer,
                    and shall include circuitry for voltage kickback suppression.
             4.     Locks shall be listed by Underwriters Laboratories as Auxiliary Locks (GWXT).
             5.     Finish: Satin Nickel Plated.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             6.     Locks shall have a door position switch (DPS) to allow monitoring of the
                    open/closed status of the door.
             7.     Locks shall have tri-color LED Status Indicator (L3): Green, Red, Yellow.

        E.   Electromagnetic Shear Locks, 2000 lb Holding Force: SDC 1561-1562 Series locks shall
             be mortise mounted and shall be provided with all required mounting hardware. Shear
             Lock design shall incorporate shear stops to prohibit horizontal shear motion. Units shall
             provide for both lateral and vertical field adjustment. Model 1562 shall be capable of being
             fit into 1-1/4 inch face frame.
             1.        Holding force shall be 2000 lbs.
             2.        Locks shall operate with 12 or 24VDC power input without field selection. Current
                       required shall not exceed 650 mA @ 12VDC or 350 mA @ 24VDC..
             3.        Locks shall incorporate automatic relock with 1 to 5 second delay relock timer,
                       and shall include circuitry for voltage kickback suppression.
             4.        Locks shall be listed by Underwriters Laboratories as Auxiliary Locks (GWXT).
             5.        Finish: Satin Nickel Plated.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             6.        Locks shall have a door position switch (DPS) to allow monitoring of the
                       open/closed status of the door.
             7.        Locks shall have tri-color LED Status Indicator (L3): Green, Red, Yellow.

2.04    DELAYED EGRESS LOCKING SYSTEMS
** NOTE TO SPECIFIER ** The following describes various models of delayed egress locking systems.
Delete all that are not required. If more than one type of system is required, give each a type designation
and indicate type on Door Schedule.

        A.      Self-Contained Electromagnetic Delayed Egress Locking System, Visual/ Verbal
                Annunciation: SDC 101S, 101D, 101T Series locks shall be surface-mounted and include
                all necessary mounting hardware. Lock core shall not contain any epoxy-resin, and shall
                consist of steel laminations welded in a steel U-channel; all electronics enclosed within
                the housing; all exposed surfaces plated or anodized. Locks utilized on doors with
                mechanical latching hardware shall be activated by slight movement of the door and shall
                not require a switch input from the mechanical hardware for activation. Signage required
                for use of delayed egress shall be provided.
                1.      Holding force shall be 1650 lbs.
                2.      Locks shall have a digital display that visually indicates status and provides a
                        countdown of seconds remaining until door release. Locks shall have an audio
                        speaker; 85db minimum output; and shall generate verbal status and countdown
                        messages. Speaker shall be an integral part of the delayed egress unit and shall
                        not be accessible when the door is closed.
                3.      System shall have input for automatic release upon activation of the Fire Life
                        Safety System; Request-to-Exit input; outputs for egress alarm and locked/
                        unlocked status; key switch for reset, momentary authorized egress and on-off.
                4.      Locks shall operate with 12 or 24VDC power input without field selection. Current
                        required shall not exceed 820 mA @ 12VDC or 500 mA @ 24VDC for single lock
                        and 1.5 Amp @ 12VDC or 850 mA @ 24VDC for double lock and tandem.
                5.      All field wiring connections shall be via on-board screw terminal connections.
                        Magnetic lock shall contain printed-circuit board providing circuit and surge
                        protection.
                6.      Locks shall be BHMA Certified Grade 1.




                                   ELECTRICAL LOCKING SYSTEMS                                     08745 - 5
                7.       System shall be listed by Underwriters Laboratories (FWAX Special Locking
                         Arrangements), and shall also be compliant with NFPA 101 Special Locking
                         Arrangements, and UBC Special Egress Control Devices.
                 8.      Double without Mullion.
                 9.      Tandem for surface vertical rod or Mullion.
** NOTE TO SPECIFIER ** The following paragraphs apply to different jurisdictional requirements.
Retain or delete as applicable.
                 10.     NA       NFPA, UFC, SBC, IBC, IFC Compliant
                                  Adj. 15 or 30 Second Exit Delay
                                  Adj. 0, 1, 2, 3 sec. nuisance delay
                                  Manual reset, built-in or remote
                 11.     ND       UBC, California Building Code
                                  NFPA, UFC, SBC, IBC, IFC Compliant
                                  15 Second Exit Delay (Fixed)
                                  Adj. 0, 1, 2, sec. nuisance delay
                                  Manual reset, built-in or remote
                 12.     NH       NFPA, UFC, SBC, IBC, IFC Compliant
                                  30 Second Exit Delay (Fixed)
                                  Adj. 0, 1, 2 sec. nuisance delay
                                  Manual reset, built-in or remote
                 13.     BD       BOCA Compliant
                                  15 Second Exit Delay (Fixed)
                                  *Auto reset 30 seconds after door closure
                                  *45 sec. when AHJ approved
                 14.     CD       Chicago Building Code Compliant (Contains no moving parts)
                                  15 Second Exit Delay (Fixed)
                                  1-second nuisance delay
                                  Auto reset 30 seconds after door closure
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
                 15.     Locks shall have a door position switch (DPS) to allow monitoring of the
                         open/closed status of the door.
                 16.     Locks shall have a magnetic bond-sensor (BA) circuit to allow monitoring of the
                         strength of the magnetic field between lock and armature.
                 17.     Locks shall have an anti-tamper switch (ATS) to indicate an attempt to remove
                         cover.
                 18.     For doors without mechanical latching hardware, provide for each door a power
                         transfer device (PT-2 armored loop or PTH-4 power transfer hinge) and Request-
                         to-Exit Push Bar (PSB 560 Series Sure Exit).
                 19.     Provide remote wall mount Reset Key Switch Assembly (702R-6) including key
                         cylinder in accordance with requirements of Section 08710.
                 20.     Provide remote wall mount Key Switch Assembly with dual function for Reset and
                         Authorized Egress Bypass (707R-6) including key cylinder in accordance with
                         requirements of Section 08710.
                 21.     Provide remote wall mount Key Switch Assembly with dual function for Reset and
                         System On/Off (708R-6) including key cylinder in accordance with requirements
                         of Section 08710.
                 22.     Provide remote wall mount Single Door Annunciator with audible alarm and tri-
                         color LED (101-1A).
                 23.     Provide remote wall mount Four Door Annunciator with audible alarm, mute
                         button, and 4 tri-color LEDs (101-4AM).
                 24.     Provide remote wall mount Single Door Annunciator/ Key Switch Assembly with
                         dual function for Reset and System On/Off; audible alarm and tri-color LED (101-
                         1AK) including key cylinder in accordance with requirements of Section 08710
                 25.     Provide remote wall mount Single Door Annunciator with tri-color LED and 3 push
                         button switches for Momentary Access, System On/Off, and Alarm Mute (101-
                         PAM).


                                  ELECTRICAL LOCKING SYSTEMS                                   08745 - 6
** NOTE TO SPECIFIER ** Delete one or all of the following paragraphs as required.
             26.    Provide verbal annunciation in Spanish language.
             27.    Provide verbal annunciation in French language.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             28.    Case Finish: 628 Satin Aluminum, Clear Anodized
             29.    Case Finish: 313 Dark Bronze Anodized
             30.    Case Finish: 335 Black Duronodic
             31.    Case Finish: 605E Bright Brass Anodized
             32.    Case Finish: 606E Satin Brass Plated
             33.    Case Finish: 611E Bright Bronze Plated
             34.    Case Finish: 625E Bright Chromium Plated
             35.    Case Finish: 626E Satin Chromium Plated

       B.      Self-Contained Electromagnetic Delayed Egress Locking System, Visual/ Audio
               Annunciation: SDC 1511S, 1512D, 1511T Series locks shall be surface-mounted and
               include all necessary mounting hardware. Lock core shall not contain any epoxy-resin,
               and shall consist of steel laminations welded in a steel U-channel; all electronics enclosed
               within the housing; all exposed surfaces plated or anodized. Locks utilized on doors with
               mechanical latching hardware shall be activated by slight movement of the door and shall
               not require a switch input from the mechanical hardware for activation. Signage required
               for use of delayed egress shall be provided.
               1.       Holding force shall be 1650 lbs.
               2.       Locks shall have tri-color LED indicator to provide visual status of the system:
                        Green indicates door secure, amber indicates release time-out operational and
                        red indicates door unlocked.
               3.       System shall have an 85db audio tone output. Distinct tones shall provide pre-
                        activation warning, unit activated alert and door unlocked condition.
               4.       System shall have input for automatic release upon activation of the Fire Life
                        Safety System; Request-to-Exit input; outputs for egress alarm and locked/
                        unlocked status; key switch for reset, momentary authorized egress and on-off.
               5.       Locks shall operate with 12 or 24VDC power input without field selection. Current
                        required shall not exceed 820 mA @ 12VDC or 500 mA @ 24VDC for single lock
                        and 1.5 Amp @ 12VDC or 850 mA @ 24VDC for double lock and tandem.
               6.       All field wiring connections shall be via on-board screw terminal connections.
                        Magnetic lock shall contain printed-circuit board providing circuit and surge
                        protection.
               7.       Locks shall be BHMA Certified Grade 1.
               8.       System shall be listed by Underwriters Laboratories (FWAX Special Locking
                        Arrangements), and shall also be compliant with NFPA 101 Special Locking
                        Arrangements, and UBC Special Egress Control Devices.
               9.       Provide remote wall mount Reset Key Switch Assembly (702R-6) including key
                        cylinder in accordance with requirements of Section 08710.
               10.      Provide remote wall mount Key Switch Assembly with dual function for Reset and
                        Authorized Egress Bypass (707R-6) including key cylinder in accordance with
                        requirements of Section 08710.
               11.      Provide remote wall mount Key Switch Assembly with dual function for Reset and
                        System On/Off (708R-6) including key cylinder in accordance with requirements
                        of Section 08710.
               12.      Provide remote wall mount Single Door Annunciator with audible alarm and tri-
                        color LED (101-1A).
               13.      Provide remote wall mount Four Door Annunciator with audible alarm, mute
                        button, and 4 tri-color LEDs (101-4AM).
               14.      Provide remote wall mount Single Door Annunciator/ Key Switch Assembly with
                        dual function for Reset and System On/Off; audible alarm and tri-color LED (101-
                        1AK) including key cylinder in accordance with requirements of Section 08710



                                  ELECTRICAL LOCKING SYSTEMS                                     08745 - 7
                15.      Provide remote wall mount Single Door Annunciator with tri-color LED and 3 push
                         button switches for Momentary Access, System On/Off, and Alarm Mute (101-
                         PAM).
** NOTE TO SPECIFIER ** The following paragraphs apply to different jurisdictional requirements.
Retain or delete as applicable.
                 16.     NA       NFPA, UFC, SBC, IBC, IFC Compliant
                                  Adj. 15 or 30 Second Exit Delay
                                  Adj. 0, 1, 2, 3 sec. nuisance delay
                                  Manual reset, built-in or remote
                 17.     ND       UBC, California Building Code
                                  NFPA, UFC, SBC, IBC, IFC Compliant
                                  15 Second Exit Delay (Fixed)
                                  Adj. 0, 1, 2, sec. nuisance delay
                                  Manual reset, built-in or remote
                 18.     NH       NFPA, UFC, SBC, IBC, IFC Compliant
                                  30 Second Exit Delay (Fixed)
                                  Adj. 0, 1, 2 sec. nuisance delay
                                  Manual reset, built-in or remote
                 19.     BD       BOCA Compliant
                                  15 Second Exit Delay (Fixed)
                                  *Auto reset 30 seconds after door closure
                                  *45 sec. when AHJ approved
                 20.     CD       Chicago Building Code Compliant (Contains no moving parts)
                                  15 Second Exit Delay (Fixed)
                                  1-second nuisance delay
                                  Auto reset 30 seconds after door closure
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
                 21.     Locks shall have a door position switch (DPS) to allow monitoring of the
                         open/closed status of the door.
                 22.     Locks shall have a magnetic bond-sensor (BA) circuit to allow monitoring of the
                         strength of the magnetic field between lock and armature.
                 23.     Locks shall have an anti-tamper switch (ATS) to indicate an attempt to remove
                         cover.
                 24.     For doors without mechanical latching hardware, provide for each door a power
                         transfer device (PT-2 armored loop or PTH-4 power transfer hinge) and Request-
                         to-Exit Push Bar (PSB 560 Series Sure Exit).
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
                 25.     Case Finish: 628 Satin Aluminum, Clear Anodized
                 26.     Case Finish: 313 Dark Bronze Anodized
                 27.     Case Finish: 335 Black Duronodic
                 28.     Case Finish: 605E Bright Brass Anodized
                 29.     Case Finish: 606E Satin Brass Plated
                 30.     Case Finish: 611E Bright Bronze Plated
                 31.     Case Finish: 625E Bright Chromium Plated
                 32.     Case Finish: 626E Satin Chromium Plated

        C.      Self-contained Electromagnetic Delayed Egress Locking System, Visual/Audio
                Annunciation : SDC 1581SND – 1581SBD Series locks shall be surface mounted and
                include all necessary mounting hardware. Core shall not contain any epoxy-resin, and
                consist of steel laminations welded in a steel U-channel. The winding and electronics to
                be contained within the aluminum housing and be replaceable without removing the lock
                from the door frame. Size 10”L x 2” H x 2-3/8” D
                1.      Holding force shall be 650 lbs.
                2.      Locks shall have tri-color LED indicator to provide visual status of the system.
                        Green indicates door secure, amber indicates release time- out operationall and
                        Red indicates door unlocked.


                                  ELECTRICAL LOCKING SYSTEMS                                    08745 - 8
               3.   System shall have an 85db audio tone output. Distinct tones shall provide pre-
                    activation warning, until activated alert and door unlocked condition.
             4.     All field wiring connections shall be via on-board screw terminal connections.
                    Magnetic lock shall contain printed-circuit board providing circuit and surge
                    protection.
             5.     Locks shall operate with 12 or 24VDC power input with out field selection.
             6.     Locks shall be BHMA Certified Grade 1 ranking. Provide 2 locks for pairs of
                    doors.
             7.     Locks shall be listed by Underwriters Laboratories as Auxiliary Locks (FWAX
             8.     Special Locking Arrangements, and shall also be compliant with NFPA 101
                    Special Locking Arrangements, and UBC Special Egress Control Devices.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             9.     Locks shall have a door position switch (D) to allow monitoring of the open/closed
                    status of the door.
             10.    Locks shall have a magnetic bond-sensor (B) circuit to allow monitoring of the
                    strength of the magnetic field between lock and armature.
             11.    Locks shall have tri-color LED Status Indicator (L3): Green, Red, Yellow.
             12.    Pairs of Doors Without Mullion: provide 2 locks
             13.    Provide SND option.
                    UBC, NFPA 101 , NFPA 1, UFC, IBC, IFC, and California Building Ccde
                    Compliant.
                    15 sec. exit dela,1 sec. nuisance delay
                    Station control required for lock reset following unauthorized egress.
                    Field selectable automatic or manual power-up after power outage and fire
                    emergency release. Manual power-up is a UBC and California State requirement.
             14     Provide SBD option.
                    BOCA and Chicago Building Code Compliant
                    15 sec. delay, 1 sec. nuisance delay
                    Automatically resets and locks 30 seconds after door closure
                    Reset station control not required
             15     Provide 928 EntryCheck Digital Keypad Reset/Manual Power Up, Momentary or
                    Sustained Bypass.
             16     Provide 728 Key switch, 2 Keys. Reset / Manual Power Up/ Sustained Bypass
             17     Provide 728L Key Switch, 2 Keys. LED Reset / Manual Power Up / Sustained
                    Bypass.
             18.    Provide 702R-6 Key switch assembly, less cylinder. Reset / Manual Power Up.
             19.    Provide 101-1AKKey Switch assembly, 2 gang, LED, audible alarm, less cylinder
             20.    Reset / Manual Power Up/ Sustained Bypass.
             21.    Provide 101-1A Single station annunciator is equipped with a tri-color LED and
                    audible alarm.
             22.    Provide 101-PAM Visual and audible annunciation, momentary & sustained
                    bypass, and audible mute.
             23.    Provide 101-4AM Visual and audible annunciation with audible mute for up to
                    four openings.
             24.    Provide CC-3 Cable kit for connecting two locks through the header.
             25.    Provide CC-10 Cable kit for connecting wiring for two locks in a junction box.
             26.    Provide PSB560V Sure Exit Push Bar Aluminum Anodized
             27.    Provide PSB560X Sure Exit Push Bar Dark Bronze Anodized
             28.    Provide PSB560Y Sure Exit Push Bar Black Anodized
             29.    Provide PT-2U Stainless Surface Mount Power Transfer Loops
             30.    Provide PT-2B Black Surface Mount Power Transfer loops
             31.    Provide PT-3V Aluminum Termination Box
             32.    Provide PTH-4Q Four Wire Electric Power Transfer Hinge 4.5 x 4.5 Dull Chrome
             33.    Case Finish: 628 Satin Aluminum, Clear Anodized
             34.    Case Finish: 313 Dark Bronze Anodized
             35.    Case Finish: 335 Black Duronodic


                                 ELECTRICAL LOCKING SYSTEMS                                  08745 - 9
                36.     Case Finish:   605E Bright Brass Anodized
                37.     Case Finish:   606E Satin Brass Plated
                38.     Case Finish:   611E Bright Bronze Plated
                39.     Case Finish:   625E Bright Chromium Plated
                40.     Case Finish:   626E Satin Chromium Plated

        D.       Modular Electromagnetic Delayed Egress Locking System, Visual/ Verbal Annunciation:
                 SDC 101V71S-101V85T Series shall consist of a delayed egress control module and an
                 electromagnetic lock. The control module shall be packaged on a two gang wall plate
                 suitable for recessed or surface mounting and be equipped with anti-tamper switch.
                 Electromagnetic lock shall be surface-mounted and include all necessary mounting
                 hardware. Lock core shall not contain any epoxy-resin, and consist of steel laminations
                 welded in a steel U-Channel. The winding and electronics to be contained within the
                 aluminum housing and be replaceable without removing the lock from the doorframe.
                 Locks utilized on doors with mechanical latching hardware shall be activated by slight
                 movement of the door and shall not require a switch input from the mechanical hardware
                 for activation. Signage required for use of delayed egress shall be provided.
                 1.       Lock holding force shall be 1200 lbs.; BHMA Certified Grade 2 ranking.
                 2.       Locks shall operate on 12 or 24VDC without field selection.. Current required
                          shall not exceed 470 mA @ 12VDC or 350 mA @ 24VDC for single lock and 720
                          mA @ 12VDC or 470 mA @ 24VDC for double lock.
                 3.       All field wiring connections shall be via on-board screw terminal connections.
                          Magnetic lock shall contain printed-circuit board providing circuit and surge
                          protection.
                 4.       Control Module shall have a digital display that visually indicates status and
                          provides a countdown of seconds remaining until door release. Control Module
                          shall have an audio speaker; 85db minimum output; and shall generate verbal
                          status and countdown messages.
                 5.       System shall have input for automatic release upon activation of the Fire Life
                          Safety System; Request-to-Exit input; outputs for egress alarm and locked/
                          unlocked status; key switch for reset, momentary authorized egress and on-off.
                 6.       System shall be listed by Underwriters Laboratories (FWAX Special Locking
                          Arrangements), and shall also be compliant with NFPA 101 Special Locking
                          Arrangements, and UBC Special Egress Control Devices.
** NOTE TO SPECIFIER ** The following paragraphs apply to different jurisdictional requirements.
Retain or delete as applicable.
                 7.       NA        NFPA, UFC, SBC, IBC, IFC Compliant
                                    Adj. 15 or 30 Second Exit Delay
                                    Adj. 0, 1, 2, 3 sec. nuisance delay
                                    Manual reset, built-in or remote
                 8.       ND        UBC, California Building Code
                                    NFPA, UFC, SBC, IBC, IFC Compliant
                                    15 Second Exit Delay (Fixed)
                                    Adj. 0, 1, 2, sec. nuisance delay
                                    Manual reset, built-in or remote
                 9.       NH        NFPA, UFC, SBC, IBC, IFC Compliant
                                    30 Second Exit Delay (Fixed)
                                    Adj. 0, 1, 2 sec. nuisance delay
                                    Manual reset, built-in or remote
                 10.      BD        BOCA Compliant
                                    15 Second Exit Delay (Fixed)
                                    *Auto reset 30 seconds after door closure
                                    *45 sec. when AHJ approved
                 11.      CD        Chicago Building Code Compliant (Contains no moving parts)
                                    15 Second Exit Delay (Fixed)
                                    1-second nuisance delay


                                  ELECTRICAL LOCKING SYSTEMS                                  08745 - 10
                             Auto reset 30 seconds after door closure
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             12.    Locks shall have a door position switch (DPS) to allow monitoring of the
                    open/closed status of the door.
             13.    Locks shall have a magnetic bond-sensor (BA) circuit to allow monitoring of the
                    strength of the magnetic field between lock and armature.
             14.    Locks shall have an anti-tamper switch (ATS) to indicate an attempt to remove
                    cover.
             15.    For doors without mechanical latching hardware, provide for each door a power
                    transfer device (PT-2 armored loop or PTH-4 power transfer hinge) and Request-
                    to-Exit Push Bar (PSB 560 Series Sure Exit).
             16.    Provide plastic box (SB2) for surface mounting of Control Module.
             17.    Provide remote wall mount Reset Key Switch Assembly (702R-6) including key
                    cylinder in accordance with requirements of Section 08710.
             18.    Provide remote wall mount Key Switch Assembly with dual function for Reset and
                    Authorized Egress Bypass (707R-6) including key cylinder in accordance with
                    requirements of Section 08710.
             19.    Provide remote wall mount Key Switch Assembly with dual function for Reset and
                    System On/Off (708R-6) including key cylinder in accordance with requirements
                    of Section 08710.
             20.    Provide remote wall mount Single Door Annunciator with audible alarm and tri-
                    color LED (101-1A).
             21.    Provide remote wall mount Four Door Annunciator with audible alarm, mute
                    button, and 4 tri-color LEDs (101-4AM).
             22.    Provide remote wall mount Single Door Annunciator/ Key Switch Assembly with
                    dual function for Reset and System On/Off; audible alarm and tri-color LED (101-
                    1AK) including key cylinder in accordance with requirements of Section 08710
             23.    Provide remote wall mount Single Door Annunciator with tri-color LED and 3 push
                    button switches for Momentary Access, System On/Off, and Alarm Mute (101-
                    PAM).
** NOTE TO SPECIFIER ** Delete one or all of the following paragraphs as required.
             24.    Provide verbal annunciation in Spanish language.
             25.    Provide verbal annunciation in French language.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             26.    Case Finish: 628 Satin Aluminum, Clear Anodized
             27.    Case Finish: 313 Dark Bronze Anodized
             28.    Case Finish: 335 Black Duronodic
             29.    Case Finish: 605E Bright Brass Anodized
             30.    Case Finish: 606E Satin Brass Plated
             31.    Case Finish: 611E Bright Bronze Plated
             32.    Case Finish: 625E Bright Chromium Plated
             33.    Case Finish: 626E Satin Chromium Plated

       E.      Modular Electromagnetic Delayed Egress Locking System, Visual/ Verbal Annunciation:
               SDC 101V85S- 101V85T Series shall consist of a delayed egress control module and an
               electromagnetic lock. The control module shall be packaged on a two gang wall plate
               suitable for recessed or surface mounting and be equipped with anti-tamper switch.
               Electromagnetic lock shall be surface-mounted and include all necessary mounting
               hardware. Lock core shall not contain any epoxy-resin, and consist of steel laminations
               welded in a steel U-Channel. The winding and electronics to be contained within the
               aluminum housing and be replaceable without removing the lock from the door frame.
               Locks utilized on doors with mechanical latching hardware shall be activated by slight
               movement of the door and shall not require a switch input from the mechanical hardware
               for activation. Signage required for use of delayed egress shall be provided.
               1.       Lock holding force shall be 650 lbs.; BHMA Certified Grade 3 ranking.



                                 ELECTRICAL LOCKING SYSTEMS                                 08745 - 11
                2.       Locks shall operate on 12 or 24VDC without field selection.. Current required
                         shall not exceed 660 mA @ 12VDC or 440 mA @ 24VDC for single lock and
                         1100 mA @ 12VDC or 660 mA @ 24VDC for double lock.
                 3.      All field wiring connections shall be via on-board screw terminal connections.
                         Magnetic lock shall contain printed-circuit board providing circuit and surge
                         protection.
                 4.      Control Module shall have a digital display that visually indicates status and
                         provides a countdown of seconds remaining until door release. Control Module
                         shall have an audio speaker; 85db minimum output; and shall generate verbal
                         status and countdown messages.
                 5.      System shall have input for automatic release upon activation of the Fire Life
                         Safety System; Request-to-Exit input; outputs for egress alarm and locked/
                         unlocked status; key switch for reset, momentary authorized egress and on-off.
                 6.      System shall be listed by Underwriters Laboratories (FWAX Special Locking
                         Arrangements), and shall also be compliant with NFPA 101 Special Locking
                         Arrangements, and UBC Special Egress Control Devices.
** NOTE TO SPECIFIER ** The following paragraphs apply to different jurisdictional requirements.
Retain or delete as applicable.
                 7.      NA        NFPA, UFC, SBC, IBC, IFC Compliant
                                   Adj. 15 or 30 Second Exit Delay
                                   Adj. 0, 1, 2, 3 sec. nuisance delay
                                   Manual reset, built-in or remote
                 8.      ND        UBC, California Building Code
                                   NFPA, UFC, SBC, IBC, IFC Compliant
                                   15 Second Exit Delay (Fixed)
                                   Adj. 0, 1, 2, sec. nuisance delay
                                   Manual reset, built-in or remote
                 9.      NH        NFPA, UFC, SBC, IBC, IFC Compliant
                                   30 Second Exit Delay (Fixed)
                                   Adj. 0, 1, 2 sec. nuisance delay
                                   Manual reset, built-in or remote
                 10.     BD        BOCA Compliant
                                   15 Second Exit Delay (Fixed)
                                   *Auto reset 30 seconds after door closure
                                   *45 sec. when AHJ approved
                 11.     CD        Chicago Building Code Compliant (Contains no moving parts)
                                   15 Second Exit Delay (Fixed)
                                   1-second nuisance delay
                                   Auto reset 30 seconds after door closure
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
                 12.     Locks shall have a door position switch (DPS) to allow monitoring of the
                         open/closed status of the door.
                 13.     Locks shall have a magnetic bond-sensor (BA) circuit to allow monitoring of the
                         strength of the magnetic field between lock and armature.
                 14.     Locks shall have an anti-tamper switch (ATS) to indicate an attempt to remove
                         cover.
                 15.     For doors without mechanical latching hardware, provide for each door a power
                         transfer device (PT-2 armored loop or PTH-4 power transfer hinge) and Request-
                         to-Exit Push Bar (PSB 560 Series Sure Exit).
                 16.     Provide plastic box (SB2) for surface mounting of Control Module.
                 17.     Provide remote wall mount Reset Key Switch Assembly (702R-6) including key
                         cylinder in accordance with requirements of Section 08710.
                 18.     Provide remote wall mount Key Switch Assembly with dual function for Reset and
                         Authorized Egress Bypass (707R-6) including key cylinder in accordance with
                         requirements of Section 08710.



                                  ELECTRICAL LOCKING SYSTEMS                                 08745 - 12
               19.  Provide remote wall mount Key Switch Assembly with dual function for Reset and
                    System On/Off (708R-6) including key cylinder in accordance with requirements
                    of Section 08710.
             20.    Provide remote wall mount Single Door Annunciator with audible alarm and tri-
                    color LED (101-1A).
             21.    Provide remote wall mount Four Door Annunciator with audible alarm, mute
                    button, and 4 tri-color LEDs (101-4AM).
             22.    Provide remote wall mount Single Door Annunciator/ Key Switch Assembly with
                    dual function for Reset and System On/Off; audible alarm and tri-color LED (101-
                    1AK) including key cylinder in accordance with requirements of Section 08710
             23.    Provide remote wall mount Single Door Annunciator with tri-color LED and 3 push
                    button switches for Momentary Access, System On/Off, and Alarm Mute (101-
                    PAM).
** NOTE TO SPECIFIER ** Delete one or all of the following paragraphs as required.
             24.    Provide verbal annunciation in Spanish language.
             25.    Provide verbal annunciation in French language.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             26.    Case Finish: 628 Satin Aluminum, Clear Anodized
             27.    Case Finish: 313 Dark Bronze Anodized
             28.    Case Finish: 335 Black Duronodic
             29.    Case Finish: 605E Bright Brass Anodized
             30.    Case Finish: 606E Satin Brass Plated
             31.    Case Finish: 611E Bright Bronze Plated
             32.    Case Finish: 625E Bright Chromium Plated
             33.    Case Finish: 626E Satin Chromium Plated

       F.      Modular Electromagnetic Delayed Egress Locking System, Visual/ Audio Annunciation:
               SDC 101A71S- 101A71T Series shall consist of a delayed egress control module and an
               electromagnetic lock. The control module shall be packaged on a two gang wall plate
               suitable for recessed or surface mounting and be equipped with anti-tamper switch.
               Electromagnetic lock shall be surface-mounted and include all necessary mounting
               hardware. Lock core shall not contain any epoxy-resin, and consist of steel laminations
               welded in a steel U-Channel. The winding and electronics to be contained within the
               aluminum housing and be replaceable without removing the lock from the door frame.
               Locks utilized on doors with mechanical latching hardware shall be activated by slight
               movement of the door and shall not require a switch input from the mechanical hardware
               for activation. Signage required for use of delayed egress shall be provided.
               1.       Lock holding force shall be 1200 lbs.; BHMA Certified Grade 2 ranking.
               2.       Lock shall operate on 12 or 24VDC without field selection. Current required shall
                        not exceed 400 mA @ 12VDC or 275 mA @ 24VDC for single lock and 650 mA
                        @ 12VDC or 400 mA @ 24VDC for double lock.
               3.       All field wiring connections shall be via on-board screw terminal connections.
                        Magnetic lock shall contain printed-circuit board providing circuit and surge
                        protection.
               4.       Control Module shall have tri-color LED indicator to provide visual status of the
                        system: Green indicates door secure, amber indicates release time-out
                        operational and red indicates door unlocked. Control Module shall have an audio
                        speaker; 85db minimum output; and shall generate distinct tones indicating pre-
                        activation warning, unit activated alert and door unlocked condition
               5.       System shall have input for automatic release upon activation of the Fire Life
                        Safety System; Request-to-Exit input; outputs for egress alarm and locked/
                        unlocked status; key switch for reset, momentary authorized egress and on-off.
               6.       System shall be listed by Underwriters Laboratories (FWAX Special Locking
                        Arrangements), and shall also be compliant with NFPA 101 Special Locking
                        Arrangements, and UBC Special Egress Control Devices.



                                  ELECTRICAL LOCKING SYSTEMS                                   08745 - 13
** NOTE TO SPECIFIER ** The following paragraphs apply to different jurisdictional requirements.
Retain or delete as applicable.
                 7.      NA       NFPA, UFC, SBC, IBC, IFC Compliant
                                  Adj. 15 or 30 Second Exit Delay
                                  Adj. 0, 1, 2, 3 sec. nuisance delay
                                  Manual reset, built-in or remote
                 8.      ND       UBC, California Building Code
                                  NFPA, UFC, SBC, IBC, IFC Compliant
                                  15 Second Exit Delay (Fixed)
                                  Adj. 0, 1, 2, sec. nuisance delay
                                  Manual reset, built-in or remote
                 9.      NH       NFPA, UFC, SBC, IBC, IFC Compliant
                                  30 Second Exit Delay (Fixed)
                                  Adj. 0, 1, 2 sec. nuisance delay
                                  Manual reset, built-in or remote
                 10.     BD       BOCA Compliant
                                  15 Second Exit Delay (Fixed)
                                  *Auto reset 30 seconds after door closure
                                  *45 sec. when AHJ approved
                 11.     CD       Chicago Building Code Compliant (Contains no moving parts)
                                  15 Second Exit Delay (Fixed)
                                  1-second nuisance delay
                                  Auto reset 30 seconds after door closure
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
                 12.     Locks shall have a door position switch (DPS) to allow monitoring of the
                         open/closed status of the door.
                 13.     Locks shall have a magnetic bond-sensor (BA) circuit to allow monitoring of the
                         strength of the magnetic field between lock and armature.
                 14.     Locks shall have an anti-tamper switch (ATS) to indicate an attempt to remove
                         cover.
                 15.     For doors without mechanical latching hardware, provide for each door a power
                         transfer device (PT-2 armored loop or PTH-4 power transfer hinge) and Request-
                         to-Exit Push Bar (PSB 560 Series Sure Exit).
                 16.     Provide plastic box (SB2) for surface mounting of Control Module.
                 17.     Provide remote wall mount Reset Key Switch Assembly (702R-6) including key
                         cylinder in accordance with requirements of Section 08710.
                 18.     Provide remote wall mount Key Switch Assembly with dual function for Reset and
                         Authorized Egress Bypass (707R-6) including key cylinder in accordance with
                         requirements of Section 08710.
                 19.     Provide remote wall mount Key Switch Assembly with dual function for Reset and
                         System On/Off (708R-6) including key cylinder in accordance with requirements
                         of Section 08710.
                 20.     Provide remote wall mount Single Door Annunciator with audible alarm and tri-
                         color LED (101-1A).
                 21.     Provide remote wall mount Four Door Annunciator with audible alarm, mute
                         button, and 4 tri-color LEDs (101-4AM).
                 22.     Provide remote wall mount Single Door Annunciator/ Key Switch Assembly with
                         dual function for Reset and System On/Off; audible alarm and tri-color LED (101-
                         1AK) including key cylinder in accordance with requirements of Section 08710
                 23.     Provide remote wall mount Single Door Annunciator with tri-color LED and 3 push
                         button switches for Momentary Access, System On/Off, and Alarm Mute (101-
                         PAM).
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
                 24.     Case Finish: 628 Satin Aluminum, Clear Anodized
                 25.     Case Finish: 313 Dark Bronze Anodized
                 26.     Case Finish: 335 Black Duronodic


                                  ELECTRICAL LOCKING SYSTEMS                                  08745 - 14
                27.     Case Finish:   605E Bright Brass Anodized
                28.     Case Finish:   606E Satin Brass Plated
                29.     Case Finish:   611E Bright Bronze Plated
                30.     Case Finish:   625E Bright Chromium Plated
                31.     Case Finish:   626E Satin Chromium Plated

        G.       Modular Electromagnetic Delayed Egress Locking System, Visual/ Audio Annunciation:
                 SDC 101A85S – 101A85T Series shall consist of a delayed egress control module and an
                 electromagnetic lock. The control module shall be packaged on a two gang wall plate
                 suitable for recessed or surface mounting and be equipped with anti-tamper switch.
                 Electromagnetic lock shall be surface-mounted and include all necessary mounting
                 hardware. Lock core shall not contain any epoxy-resin, and consist of steel laminations
                 welded in a steel U-Channel. The winding and electronics to be contained within the
                 aluminum housing and be replaceable without removing the lock from the door frame.
                 Locks utilized on doors with mechanical latching hardware shall be activated by slight
                 movement of the door and shall not require a switch input from the mechanical hardware
                 for activation. Signage required for use of delayed egress shall be provided.
                 1.       Lock holding force shall be 650 lbs.; BHMA Certified Grade 3 ranking.
                 2.       Locks to operate on 12 or 24VDC without field selection.. Current required shall
                          not exceed 590 mA @ 12VDC or 370 mA @ 24VDC for single lock and 1030 mA
                          @ 12VDC or 590 mA @ 24VDC for double lock.
                 3.       All field wiring connections shall be via on-board screw terminal connections.
                          Magnetic lock shall contain printed-circuit board providing circuit and surge
                          protection.
                 4.       Control Module shall have tri-color LED indicator to provide visual status of the
                          system: Green indicates door secure, amber indicates release time-out
                          operational and red indicates door unlocked. Control Module shall have an audio
                          speaker; 85db minimum output; and shall generate distinct tones indicating pre-
                          activation warning, unit activated alert and door unlocked condition
                 5.       System shall have input for automatic release upon activation of the Fire Life
                          Safety System; Request-to-Exit input; outputs for egress alarm and locked/
                          unlocked status; key switch for reset, momentary authorized egress and on-off.
                 6.       System shall be listed by Underwriters Laboratories (FWAX Special Locking
                          Arrangements), and shall also be compliant with NFPA 101 Special Locking
                          Arrangements, and UBC Special Egress Control Devices.
** NOTE TO SPECIFIER ** The following paragraphs apply to different jurisdictional requirements.
Retain or delete as applicable.
                 7.       NA        NFPA, UFC, SBC, IBC, IFC Compliant
                                    Adj. 15 or 30 Second Exit Delay
                                    Adj. 0, 1, 2, 3 sec. nuisance delay
                                    Manual reset, built-in or remote
                 8.       ND        UBC, California Building Code
                                    NFPA, UFC, SBC, IBC, IFC Compliant
                                    15 Second Exit Delay (Fixed)
                                    Adj. 0, 1, 2, sec. nuisance delay
                                    Manual reset, built-in or remote
                 9.       NH        NFPA, UFC, SBC, IBC, IFC Compliant
                                    30 Second Exit Delay (Fixed)
                                    Adj. 0, 1, 2 sec. nuisance delay
                                    Manual reset, built-in or remote
                 10.      BD        BOCA Compliant
                                    15 Second Exit Delay (Fixed)
                                    *Auto reset 30 seconds after door closure
                                    *45 sec. when AHJ approved
                 11.      CD        Chicago Building Code Compliant (Contains no moving parts)
                                    15 Second Exit Delay (Fixed)


                                   ELECTRICAL LOCKING SYSTEMS                                   08745 - 15
                             1-second nuisance delay
                             Auto reset 30 seconds after door closure
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             12.    Locks shall have a door position switch (DPS) to allow monitoring of the
                    open/closed status of the door.
             13.    Locks shall have a magnetic bond-sensor (BA) circuit to allow monitoring of the
                    strength of the magnetic field between lock and armature.
             14.    For doors without mechanical latching hardware, provide for each door a power
                    transfer device (PT-2 armored loop or PTH-4 power transfer hinge) and Request-
                    to-Exit Push Bar (PSB 560 Series Sure Exit).
             15.    Provide plastic box (SB2) for surface mounting of Control Module.
             16.    Provide remote wall mount Reset Key Switch Assembly (702R-6) including key
                    cylinder in accordance with requirements of Section 08710.
             17.    Provide remote wall mount Key Switch Assembly with dual function for Reset and
                    Authorized Egress Bypass (707R-6) including key cylinder in accordance with
                    requirements of Section 08710.
             18.    Provide remote wall mount Key Switch Assembly with dual function for Reset and
                    System On/Off (708R-6) including key cylinder in accordance with requirements
                    of Section 08710.
             19.    Provide remote wall mount Single Door Annunciator with audible alarm and tri-
                    color LED (101-1A).
             20.    Provide remote wall mount Four Door Annunciator with audible alarm, mute
                    button, and 4 tri-color LEDs (101-4AM).
             21.    Provide remote wall mount Single Door Annunciator/ Key Switch Assembly with
                    dual function for Reset and System On/Off; audible alarm and tri-color LED (101-
                    1AK) including key cylinder in accordance with requirements of Section 08710
             22.    Provide remote wall mount Single Door Annunciator with tri-color LED and 3 push
                    button switches for Momentary Access, System On/Off, and Alarm Mute (101-
                    PAM).
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             23.    Case Finish: 628 Satin Aluminum, Clear Anodized
             24.    Case Finish: 313 Dark Bronze Anodized
             25.    Case Finish: 335 Black Duronodic
             26.    Case Finish: 605E Bright Brass Anodized
             27.    Case Finish: 606E Satin Brass Plated
             28.    Case Finish: 611E Bright Bronze Plated
             29.    Case Finish: 625E Bright Chromium Plated
             30.    Case Finish: 626E Satin Chromium Plated
             31.    ** NOTE TO SPECIFIER ** The following describes various models of delayed
                    egress exit devices. Delete all that are not required. If more than one type is
                    required, give each a type designation and indicate type on Door Schedule.

2.05    ELECTRIFIED MORTISE AND CYLINDRICAL LOCKS
** NOTE TO SPECIFIER ** The following describes various models of electrified locks. Delete all types
not required. If more than one type is required, give each a type designation and indicate type on Door
Schedule.

        A.      Mortise Locks with Electric Frame-Mounted Actuators: SDC HiTower® 7500 Series shall
                consist of a heavy-duty mortise lock, with vandal resistant clutch trim, and electric frame
                mounted actuator providing locking/ unlocking functions without unlatching the door.
                Actuator mounts in hollow metal frame; no wiring through the door; all wiring in the door
                frame. BHMA Grade 1. UL listed 3 hour “A” label. Latch bolt throw:3/4 inch. Supplied less
                cylinder
                1.       Fail-safe actuators available for 1-1/4 to 2 inch face frame.
                2.       Fail-secure actuators available for 2 inch face frame.



                                   ELECTRICAL LOCKING SYSTEMS                                    08745 - 16
** NOTE TO SPECIFIER ** The following paragraphs apply to different lock functions. Retain or delete
as applicable.
               3.   Model Z7530: Fail-Safe, Inside and Outside Locked; Unlocked by access control,
                    remote control, and key from either side.
               4.   Model Z7540: Fail-Safe, Outside Locked Only; Unlocked by access control,
                    remote control, and inside lever.
               5.   Model Z7550: Fail-Safe, Outside Locked Only; Unlocked by access control,
                    remote control, outside key, and inside lever.
               6.   Model Z7560: Fail-Secure, Inside and Outside Locked; Unlocked by access
                    control, remote control, and key from either side.
               7.   Model Z7570: Fail- Secure, Outside Locked Only; Unlocked by access control,
                    remote control, outside key, and inside lever.
** NOTE TO SPECIFIER ** Delete voltage not required.
               8.   Voltage: 115VAC 0.2 Amp.
               9.   Voltage: 24VAC 0.5 Amp.
               10.  Voltage: 24VDC 0.5 Amp.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
               11.  Provide latch status switch (9A) to indicate door is latched.
               12.  Provide latch and deadlock status switch (69A) to indicate door is latched and
                    locked.
               13.  Provide socket connector (SC-10) with 10 foot cable.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
               14.  Finish: BHMA 605: Bright brass, clear coated.
               15.  Finish: BHMA 606: Satin brass, clear coated.
               16.  Finish: BHMA 611: Bright bronze, clear coated.
               17.  Finish: BHMA 612: Satin bronze, clear coated.
               18.  Finish: BHMA 613: Dark-oxidized satin bronze, oil rubbed.
               19.  Finish: BHMA 625: Bright chromium plated.
               20.  Finish: BHMA 626: Satin chromium plated.
               21.  Finish: BHMA 627: Satin aluminum, clear coated.
               22.  Finish: BHMA 629: Bright stainless steel.
               23.  Finish: BHMA 630: Satin stainless steel.

        B.     Electrified Mortise Locks: SDC SELECTRIC PRO 7800 Series shall consist of a heavy-
               duty electrified mortise lock providing locking/ unlocking functions without unlatching the
               door. Vandal resistant clutch lever permits outside lever to operate without retracting the
               latch when locked. Field selectable, mode, function, voltage, and hand. BHMA Grade 1.
               UL listed 3 hour “A” label; 3/4 inch latch bolt throw; supplied less Cylinder.
** NOTE TO SPECIFIER ** The following paragraphs apply to different lock functions. Retain or delete
as applicable.
               1.        Model Z7830: Fail-Safe, Inside and Outside Locked; Unlocked by access control,
                         remote control, and key from either side.
               2.        Model Z7850: Fail-Safe, Outside Locked Only; Unlocked by access control,
                         remote control, outside key, and inside lever.
               3.        Model Z7832: Fail-Secure, Inside and Outside Locked; Unlocked by access
                         control, remote control, and key from either side.
               4.        Model Z7852: Fail- Secure, Outside Locked Only; Unlocked by access control,
                         remote control, outside key, and inside lever.
** NOTE TO SPECIFIER ** Delete voltage not required.
               5.        Voltage: 12VDC @ 0.9 Amp.
               6.        Voltage: 24VDC @ 0.5 Amp.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
               7.        Provide internal request-to-exit (R) SPDT Switch
               8.        Provide latch and deadlock status switch (L) to indicate door is latched and
                         locked.
               9.        Provide SPDT door position switch to indicate door open or closed.


                                   ELECTRICAL LOCKING SYSTEMS                                  08745 - 17
                10. Provide cable and connector:
                    a.      CC105 5’ Cable for locks without optimal outputs
                    b.      CC105 5’ Cable for locks with optimal outputs
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             11.    Finish: BHMA 605: Bright brass, clear coated.
             12.    Finish: BHMA 606: Satin brass, clear coated.
             13.    Finish: BHMA 611: Bright bronze, clear coated.
             14.    Finish: BHMA 612: Satin bronze, clear coated.
             15.    Finish: BHMA 613: Dark-oxidized satin bronze, oil rubbed.
             16.    Finish: BHMA 625: Bright chromium plated.
             17.    Finish: BHMA 626: Satin chromium plated.
             18.    Finish: BHMA 629: Bright stainless steel.
             19.    Finish: BHMA 630: Satin stainless steel.

        C.     Electrified Cylindrical Locks: SDC HiTower® 7200/7300 Series shall consist of a heavy-
               duty electrified lock providing locking/ unlocking functions without unlatching the door.
               Vandal resistant clutch lever release with power return spring mechanism. BHMA Grade
               1. UL listed 3 hour “A” label.
               1.        Latch bolt throw: 9/16 inch. Provide 3/4 inch bolt at pairs of rated doors.
               2.        Voltage: 24VDC @ 200 mA.
** NOTE TO SPECIFIER ** The following paragraphs apply to different lock functions. Retain or delete
as applicable.
               3.        Model ZA7250: Cylindrical Lock, Fail-Safe, Outside Locked Only; Unlocked by
                         access control, remote control, outside key, and inside lever.
               4.        Model ZA7260: Cylindrical Lock, Fail- Secure, Outside Locked Only; Unlocked by
                         access control, remote control, outside key, and inside lever.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
               5.        Provide internal request-to-exit (REX) switch.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
               6.        Finish: BHMA 605: Bright brass, clear coated.
               7.        Finish: BHMA 606: Satin brass, clear coated.
               8.        Finish: BHMA 612: Satin bronze, clear coated.
               9.        Finish: BHMA 613: Dark-oxidized satin bronze, oil rubbed.
               10.       Finish: BHMA 625: Bright chromium plated.
               11.       Finish: BHMA 626: Satin chromium plated.

2.06    ELECTRIC BOLT LOCKS
** NOTE TO SPECIFIER ** The following describes various models of electric bolt locks. Delete all types
not required. If more than one type is required, give each a type designation and indicate type on Door
Schedule.

        A.   Mortise Direct Throw Type: SDC 100/ 200 Series electric bolt lock. Continuous duty
             solenoid; Requires 5 inch depth; Non-handed; Mortise strike.
** NOTE TO SPECIFIER ** Delete models not required.
             1.      Model 110: Fail-safe; 2-3/4 x 1-1/4 inch faceplate.
             2.      Model 160A: Fail-safe; Auto Relock Switch; 4-7/8 x 1-1/4 inch faceplate.
             3.      Model 210: Fail- secure; 2-3/4 x 1-1/4 inch faceplate.
             4.      Model 260:A Fail- secure; Auto Relock Switch; 4-7/8 x 1-1/4 inch faceplate.
** NOTE TO SPECIFIER ** Delete voltage not required.
             5.      Voltage: 12VDC @ 0.9 Amp. Failsafe. 12VDC @ 1Amp Failsecure.
             6.      Voltage: 24VDC @ 0.5 Amp. Failsafe. 24VDC @ 0.5 Amp Failsecure.
             7.      Voltage: 24VAC @ 0.5 Amp.                 24VAC @ 0.5 Amp Failsecure.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             8.      Provide wood frame back box (100EB) for 160/ 260 Series.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             9.      Finish: BHMA 605: Bright brass, clear coated.


                                  ELECTRICAL LOCKING SYSTEMS                                 08745 - 18
                10.     Finish:   BHMA 606: Satin brass, clear coated.
                11.     Finish:   BHMA 611: Bright bronze, clear coated.
                12.     Finish:   BHMA 612: Satin bronze, clear coated.
                13.     Finish:   BHMA 613: Dark-oxidized satin bronze, oil rubbed.
                14.     Finish:   BHMA 625: Bright chromium plated.
                15.     Finish:   BHMA 626: Satin chromium plated.
                16.     Finish:   BHMA 628: Satin aluminum, clear anodized.
                17.     Finish:   BHMA 630: Satin stainless steel.
                18.     Finish:   BHMA 313: Dark-oxidized satin bronze anodized.
                19.     Finish:   BHMA 335: Flat black anodized.

        B.   Narrow Mortise Type: SDC 1091/ 1291/ 1490/ 2490/ FS23M Spacesaver Series electric
             bolt lock. Continuous duty solenoid; Requires 1-5/8 inch depth; Non-handed; Mortise
             strike; Auto Relock Switch.
             1.       Dimensions: 8 inches (L) x 1-1/2 inches (W) x 1-5/8 inches (D).
** NOTE TO SPECIFIER ** Delete models not required.
             2.       Model 1091: Fail-safe; Less Auto Relock Switch.
             3.       Model 1091A: Fail-safe.
             4.       Model 1091ADL: Fail-safe; Deadlocking.
             5.       Model 1291A: Fail-secure.
             6.       Model 1490A: Fail-safe; fits 1-1/2 inch frame.
             7.       Model 2490A: Fail-secure; fits 1-1/2 inch frame.
             8.       Model FS23M: Dual Fail-safe.
** NOTE TO SPECIFIER ** Delete voltage not required.
             9.       Voltage: 12VDC @ 0.9 Amp. Failsafe. 12VDC @ 1Amp Failsecure.
             10.      Voltage: 24VDC @ 0.5 Amp. Failsafe. 24VDC @ 0.5 Amp Failsecure.
             11.      Voltage: 24VAC @ 0.5 Amp.                  24VAC @ 0.5 Amp Failsecure.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             12.      Provide wood frame back box (1000EB) for 1091A/ FS23M Series.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             13.      Finish: BHMA 605: Bright brass, clear coated.
             14.      Finish: BHMA 606: Satin brass, clear coated.
             15.      Finish: BHMA 611: Bright bronze, clear coated.
             16.      Finish: BHMA 612: Satin bronze, clear coated.
             17.      Finish: BHMA 613: Dark-oxidized satin bronze, oil rubbed.
             18.      Finish: BHMA 625: Bright chromium plated.
             19.      Finish: BHMA 626: Satin chromium plated.
             20.      Finish: BHMA 628: Satin aluminum, clear anodized.
             21.      Finish: BHMA 630: Satin stainless steel.
             22.      Finish: BHMA 313: Dark-oxidized satin bronze anodized.
             23.      Finish: BHMA 335: Flat black anodized.

        C.   Heavy Duty Narrow Mortise Type: SDC 1190/ 2090 Spacesaver Series electric bolt
             lock. Continuous duty solenoid; 3/4 inch diameter bolt; 3/4 inch throw; Requires 1-5/8 inch
             depth; Mortise strike; Auto Relock Switch.
             1.      Dimensions: 8 inches (L) x 1-1/2 inches (W) x 1-5/8 inches (D).
** NOTE TO SPECIFIER ** Delete models not required.
             2.      Model 1190A: Fail-safe.
             3.      Model 2090A: Fail-secure.
** NOTE TO SPECIFIER ** Delete voltage not required.
             4.      1190A 0.5 Amp @ 24VDC
             5.      Voltage: 24VDC. 2090A 3.0 Amp Inrush @ 24VDC 0.5 A Seated
             6.      Voltage: 24VAC.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             7.      Finish: BHMA 605: Bright brass, clear coated.
             8.      Finish: BHMA 606: Satin brass, clear coated.


                                    ELECTRICAL LOCKING SYSTEMS                               08745 - 19
                9.      Finish:   BHMA 611: Bright bronze, clear coated.
                10.     Finish:   BHMA 612: Satin bronze, clear coated.
                11.     Finish:   BHMA 613: Dark-oxidized satin bronze, oil rubbed.
                12.     Finish:   BHMA 625: Bright chromium plated.
                13.     Finish:   BHMA 626: Satin chromium plated.
                14.     Finish:   BHMA 628: Satin aluminum, clear anodized.
                15.     Finish:   BHMA 630: Satin stainless steel.
                16.     Finish:   BHMA 335: Dark-oxidized satin bronze anodized.
                17.     Finish:   BHMA 335: Black Duronodic

        D.   Universal Surface Mounted Type: SDC 180/ 280 Series electric bolt lock. Continuous duty
             solenoid; Fully enclosed electronics.
** NOTE TO SPECIFIER ** Delete models not required.
             1.      Model 180: Fail-safe.
             2.      Model 180A: Fail-safe; Auto Relock Switch.
             3.      Model 280: Fail-secure.
** NOTE TO SPECIFIER ** Delete voltage not required.
             4.      Voltage: 12VDC.
             5.      Voltage: 24VDC.
             6.      Voltage: 24VAC.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             7.      Finish: BHMA 628: Satin aluminum, clear anodized.
             8.      Finish: BHMA 710: Dark-oxidized satin bronze anodized.
             9.      Finish: BHMA 711: Flat black anodized.

        E.   Gate Mounted Type: SDC 160/ 260 Series electric bolt gate lock. Continuous duty
             solenoid; Fully enclosed electronics. Designed for outdoor mounting; swinging or sliding
             gates. Housing and tongue cadmium plated.
** NOTE TO SPECIFIER ** Delete models not required.
             1.      Model 160A: Fail-safe; Remote Operation.
             2.      Model 163A: Fail-safe; Remote and Electrical Key Cylinder Operation.
             3.      Model 260A: Fail- secure; Remote Operation.
             4.      Model 263A: Fail- secure; Remote and Mechanical Key Cylinder Operation.
** NOTE TO SPECIFIER ** Delete voltage not required.
             5.      Dual Voltage: 12VDC. Failsafe. 12VDC. Failsecure.
             6.      Dual Voltage: 24VDC. Failsafe. 24VDC. Failsecure.
                                                      24VAC. Failsecure.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             7.      Provide Gate Position (DPS-GL) monitor.

2.07    ELECTRIC STRIKES
** NOTE TO SPECIFIER ** The following describes various models of electric strikes. Delete all types
not required. If more than one type is required, give each a type designation and indicate type on Door
Schedule.

        A.   SDC 20 Series electric strikes for use with cylindrical locks, or mortise locks without dead
             bolts, having 1/2 inch bolt throw. Internally mounted solenoid for use with 12 or 24VDC,
             built for long life. Durable die cast body for long life and corrosion resistance; non-handed,
             reversible; plug-in connector included. Fail secure is standard; field reversible to fail safe.
             1.        ANSI/BHMA A156.5 Grade 1 and UL 1034 burglary resistant.
             2.        Voltage: 12VDC @ 0.33 Amp, 24VDC @ 0.16 Amp.
** NOTE TO SPECIFIER ** Delete models not required.
             3.        Model 20-4S: 4-7/8 inch faceplate; square corners; for wood or hollow metal
                       frames.
             4.        Model 20-6S: 6-7/8 inch faceplate; square corners; for wood or hollow metal
                       frames.



                                    ELECTRICAL LOCKING SYSTEMS                                   08745 - 20
             5.     Model 20-4R: 4-7/8 inch faceplate; radius corners; for aluminum frames.
             6.     Model 20-6R: 6-7/8 inch faceplate; radius corners; for aluminum frames.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             7.     Provide rectifier (BR64XL) for AC operation.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             8.     Finish: BHMA 605: Bright brass, clear coated.
             9.     Finish: BHMA 606: Satin brass, clear coated.
             10.    Finish: BHMA 611: Bright bronze, clear coated.
             11.    Finish: BHMA 612: Satin bronze, clear coated.
             12.    Finish: BHMA 613: Dark-oxidized satin bronze, oil rubbed.
             13.    Finish: BHMA 625: Bright chromium plated.
             14.    Finish: BHMA 626: Satin chromium plated.
             15.    Finish: BHMA 628: Satin aluminum, clear anodized.
             16.    Finish: BHMA 629: Bright stainless steel.
             17.    Finish: BHMA 630: Satin stainless steel.
             18.    Finish: BHMA 710: Dark-oxidized satin bronze anodized.
             19.    Finish: BHMA 711: Flat black anodized.

        B.   SDC 30 Series electric strikes for use with cylindrical locks, mortise locks without dead
             bolts, or mortise exit devices, having 1/2 inch or 5/8 inch bolt throw, and rim-type exit
             devices having 3/4 inch pullman type latchbolt, or the top pullman latch of a surface
             vertical-rod device. All stainless steel, tamper resistant, heavy-duty construction.
             Available for use with 12 or 24VDC; fail-secure standard, fail-safe optional. Horizontal
             keeper adjustment for door alignment. Non-handed, reversible.
             1.       ANSI/BHMA A156.5 Grade 1 and UL 1034 burglary resistant.
             2.       UL listed for use on fire doors up to 3 hours (fail-secure only).
** NOTE TO SPECIFIER ** Delete voltage not required.
             3.       Voltage: 12VDC @ 0.29 Amp.
             4.       Voltage: 24VDC @ 0.15 Amp.
** NOTE TO SPECIFIER ** Delete models not required.
             5.       Model 30-2: 9 inch faceplate; square corners; for use with cylindrical locks,
                      mortise locks without dead bolts, or mortise exit devices, having 1/2 inch or 5/8
                      inch bolt throw; for wood or hollow metal frames.
             6.       Model 30-4: 9 inch faceplate; square corners; for use with rim-type exit devices
                      having 3/4 inch pullman type latchbolt, or the top pullman latch of a surface
                      vertical-rod device; for wood or hollow metal frames.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             7.       Provide fail-safe (FS) operation (Not UL Listed).
             8.       Provide plug connector (PC).
             9.       Provide internal switch (LBM) to monitor position of lock latchbolt.
             10.      Provide internal switch (LCM) to monitor locked/ unlocked status of strike locking
                      cam.
             11.      Provide rectifier (BR64XL) for AC operation.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             12.      Finish: BHMA 606: Satin brass, clear coated.
             13.      Finish: BHMA 612: Satin bronze, clear coated.
             14.      Finish: BHMA 613: Dark-oxidized satin bronze, oil rubbed.
             15.      Finish: BHMA 625: Bright chromium plated.
             16.      Finish: BHMA 626: Satin chromium plated.
             17.      Finish: BHMA 630: Satin stainless steel.

        C.      SDC 40 Series electric strikes for use with cylindrical locks, mortise locks without dead
                bolts, or mortise exit devices, having 3/4 inch bolt throw. Stainless steel internal parts,
                tamper resistant, heavy-duty construction. Available for use with 12 or 24VDC; fail-secure
                standard, fail-safe optional. Horizontal keeper adjustment for door alignment. Non-
                handed, reversible; plug-in connector included.


                                   ELECTRICAL LOCKING SYSTEMS                                   08745 - 21
             1.     ANSI/BHMA A156.5 Grade 1 and UL 1034 burglary resistant.
** NOTE TO SPECIFIER ** Delete voltage not required.
             2.     Voltage: 12VDC @ 0.29 Amp.
             3.     Voltage: 24VDC @ 0.15 Amp.
** NOTE TO SPECIFIER ** Delete models not required.
             4.     Model 40-4S: 4-7/8 inch faceplate; square corners; for hollow metal frames.
             5.     Model 40-6S: 6-7/8 inch faceplate; square corners; for hollow metal frames.
             6.     Model 40-4R: 4-7/8 inch faceplate; radius corners; for aluminum frames.
             7.     Model 40-6R: 6-7/8 inch faceplate; radius corners; for aluminum frames.
             8.     Model 40-W4S: 4-7/8 inch faceplate; square corners and offset solenoid; for
                    wood frames.
             9.     Model 40-W6S: 6-7/8 inch faceplate; square corners and offset solenoid; for
                    wood frames.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             10.    Provide fail-safe (FS) operation (Not UL Listed).
             11.    Provide internal switch (LCM) to monitor locked/ unlocked status of strike locking
                    cam.
             12.    Provide rectifier (BR64XL) for AC operation.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             13.    Finish: BHMA 628: Satin aluminum, clear anodized.
             14.    Finish: BHMA 630: Satin stainless steel.
             15.    Finish: BHMA 710: Dark-oxidized satin bronze anodized.
             16.    Finish: BHMA 711: Flat black anodized.

        D.   SDC 50 Series electric strikes for use with cylindrical locks or mortise locks. Stainless
             steel construction, tamper resistant, inboard solenoid, heavy-duty construction. Release
             with 20 lb side load; available for use with 12 or 24VDC; fail-secure standard, fail-safe
             optional. Horizontal keeper adjustment for door alignment. Non-handed, reversible; plug-
             in connector included.
             1.       ANSI/BHMA A156.5 Grade 1 and UL 1034 burglary resistant.
             2.       UL listed for use on fire doors up to 3 hours (fail-secure only).
             3.       Fits ANSI 115.1 frame prep with face modification; for use with hollow metal or
                      aluminum frames.
** NOTE TO SPECIFIER ** Delete voltage not required.
             4.       Voltage: 12VDC @ 0.29 Amp.
             5.       Voltage: 24VDC @ 0.15 Amp.
** NOTE TO SPECIFIER ** Delete models not required.
             6.       Model 51-A Cylindrical locks, narrow stile locks with deadlatch.
             7.       Model 52-B Mortise locks and mortise panic with or without deadlatch.
             8.       Model 52-C Mortise locks and mortise panic with or without deadlatch (Schlage,
                      Sargent, Yale).
             9.       Model 53-D Mortise locks with deadlatch and latchbolt. When the deadbolt is
                      projected, the strike will not release. Keeper releases latchbolt when deadbolt is
                      retracted.
             10.      Model 53-E Mortise locks with deadlatch and latchbolt. When the deadbolt is
                      projected, the strike will not release. Keeper releases latchbolt when deadbolt is
                      retracted (Schlage, Sargent, Yale).
             11.      Model 53-F Mortise locks with deadbolt, deadlatch and latchbolt. When the
                      deadbolt is projected, the strike will not release. Keeper releases latchbolt when
                      deadbolt is retracted (Schlage, Sargent, Yale).
             12.      Model 54-D Mortise locks with latchbolt and extended deadbolt. Deadbolt and
                      latchbolt are released.
             13.      Model 54-E Mortise locks with latchbolt and extended deadbolt. Deadbolt and
                      latchbolt are released (Schlage, Sargent, Yale).
             14.      Model 54-E Cylindrical Corbin/Russwin security bolt lever locksets.



                                  ELECTRICAL LOCKING SYSTEMS                                  08745 - 22
                15. Model 54-F Mortise locks with deadlatch, latchbolt and extended deadbolt.
                    Deadbolt and latchbolt are released (Schlage, Sargent, Yale).
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             16.    Provide fail-safe (FS) operation (Not UL Listed).
             17.    Provide internal switch (LBM) to monitor position of lock latchbolt.
             18.    Provide internal switch (LCM) to monitor locked/ unlocked status of strike locking
                    cam.
             19.    Provide internal switches (LCMLBM) to monitor locked/ unlocked status of strike
                    locking cam and to monitor position of lock latchbolt.
             20.    Provide internal switches (LCMDBM) to monitor locked/ unlocked status of strike
                    locking cam and to monitor position of lock deadbolt.
             21.    Provide rectifier (BR64XL) for AC operation.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             22.    Finish: BHMA 606: Satin brass, clear coated.
             23.    Finish: BHMA 612: Satin bronze, clear coated.
             24.    Finish: BHMA 613: Dark-oxidized satin bronze, oil rubbed.
             25.    Finish: BHMA 625: Bright chromium plated.
             26.    Finish: BHMA 626: Satin chromium plated.
             27.    Finish: BHMA 630: Satin stainless steel.

        E.   SDC 70 Series electric strikes for use with cylindrical locks, mortise locks without dead
             bolts, or mortise exit devices, having 3/4 inch bolt throw. All stainless steel construction,
             tamper resistant, heavy-duty construction. Available for use with 12 or 24VDC; fail-secure
             standard, fail-safe optional. Horizontal keeper adjustment for door alignment. Non-
             handed, reversible.
             1.       ANSI/BHMA A156.5 Grade 1 and UL 1034 burglary resistant.
             2.       UL listed for use on fire doors up to 3 hours (fail-secure only).
             3.       Fits ANSI 115.1 frame prep with face modification; for use with hollow metal or
                      wood frames.
** NOTE TO SPECIFIER ** Delete voltage not required.
             4.       Voltage: 12VDC @ 0.29 Amp.
             5.       Voltage: 24VDC @ 0.15 Amp.
** NOTE TO SPECIFIER ** Delete models not required.
             6.       Model 70-12: 4-7/8 inch faceplate; square corners; for hollow metal frames.
             7.       Model 70-32: 4-7/8 inch faceplate; square corners and offset solenoid; for wood
                      frames or pair of doors.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             8.       Provide fail-safe (FS) operation (Not UL Listed).
             9.       Provide plug connector (PC).
             10.      Provide internal switch (LBM) to monitor position of lock latchbolt.
             11.      Provide internal switch (LCM) to monitor locked/ unlocked status of strike locking
                      cam.
             12.      Provide rectifier (BR64XL) for AC operation.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             13.      Finish: BHMA 606: Satin brass, clear coated.
             14.      Finish: BHMA 612: Satin bronze, clear coated.
             15.      Finish: BHMA 613: Dark-oxidized satin bronze, oil rubbed.
             16.      Finish: BHMA 625: Bright chromium plated.
             17.      Finish: BHMA 626: Satin chromium plated.
             18.      Finish: BHMA 629: Bright stainless steel.
             19.      Finish: BHMA 630: Satin stainless steel.

2.08    POWER SUPPLIES, CONTROLLERS AND BATTERY STANDBY
** NOTE TO SPECIFIER ** The following describes various models of power supplies. Delete all types
not required. If more than one type is required, give each a type designation and indicate type on Door
Schedule.


                                   ELECTRICAL LOCKING SYSTEMS                                  08745 - 23
       A.    Modular Design Power Supplies: SDC 600 Series; filtered and regulated output; field
             selectable 12/24VDC; Fire Panel release input; LED indicators for input, output, and
             battery status; thermal and short circuit protection with auto reset; battery charging
             circuitry built-in; low battery disconnect.
** NOTE TO SPECIFIER ** Delete models not required.
             1.        Model 602RF: 1 Amp Class 2 Output, 11-1/4 inch (H) x 11-1/4 inch (W) x 3-1/2
                       inch (D) 18 gauge enclosure.
             2.        Model 602RFCUL: 1 Amp Class 2 Output, 11-1/4 inch (H) x 11-1/4 inch (W) x 3-
                       1/2 inch (D) 18 gauge enclosure, cUL listed for Canada.
             3.        Model 631RF: 1.5 Amp Class 2 Output, 11-1/4 inch (H) x 11-1/4 inch (W) x 3-1/2
                       inch (D) 18 gauge enclosure.
             4.        Model 631RFA: 1.5 Amp Class 2 Output, 16 inch (H) x 14 inch (W) x 6-1/2 inch
                       (D) 16 gauge enclosure.
             5.        Model 631RFCUL: 1.5 Amp Class 2 Output, 11-1/4 inch (H) x 11-1/4 inch (W) x
                       3-1/2 inch (D) 18 gauge enclosure, cUL listed for Canada.
             6.        Model 632RF: 2 Amp Class 2 Output, 11-1/4 inch (H) x 11-1/4 inch (W) x 3-1/2
                       inch (D) 18 gauge enclosure.
             7.        Model 632RFA: 2 Amp Class 2 Output, 16 inch (H) x 14 inch (W) x 6-1/2 inch (D)
                       16 gauge enclosure.
             8.        Model 632RFCUL: 2 Amp Class 2 Output, 11-1/4 inch (H) x 11-1/4 inch (W) x 3-
                       1/2 inch (D) 18 gauge enclosure, cUL listed for Canada.
             9.        Model 634RF: Field Selectable one 4 Amp or two 2 Amp Class 2 Outputs, 16 inch
                       (H) x 14 inch (W) x 6-1/2 inch (D) 16 gauge enclosure.
             10.       Model 636RF: Field Selectable one 6 Amp or three 2 Amp Class 2 Outputs, 16
                       inch (H) x 14 inch (W) x 6-1/2 inch (D) 16 gauge enclosure.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             11.       Provide 6 foot power cord (PC) at 1-1.5 Amp power supplies:
             12.       Provide key lock (KL) cover.
             13.       Provide cover-mounted manual reset switch (MR) for fire alarm release reset.
             14.       Provide system on/off push switch (PS-1) mounted inside power supply.
             15.       Provide system on/off push switch (PS-1A) mounted on cover.
** NOTE TO SPECIFIER ** Delete modules not required.
             16.       Provide Model 12VR Module: With power supply output set at 24VDC, adds
                       separate, regulated filtered output of 12VDC @ 0.50 Amp for access control or
                       other device.
             17.       Provide Model ACM-1 Module: Access Control Board. SPDT voltage output.
                       SPDT status output, 8 trigger inputs (4 NO, 4 NC), LED status indicator.
             18.       Provide Model CR Module: Control Relay Board. Fused SPDT voltage output,
                       SPDT trigger input.
             19.       Provide Model CR4 Module: Control Relay Board. 4 Fused SPDT voltage outputs,
                       4 SPDT trigger inputs.
             20.       Provide Model FB-4 Module: Fused Terminal Board. 4 individually fused outputs.
             21.       Provide Model LR Module: Latching Relay, SPDT fused output.
             22.       Provide Model TD Module: 1-120 second adjustable time delay, SPDT fused
                       output, SPDT trigger input.
             23.       Provide Model UR-2A Module: Universal Controller for 2 doors. Field select TD,
                       LR, TD/LR, Mantrap and Communicating Bathroom Interlock. (2) Fused SPDT
                       dry outputs, 5 Amp @ 30VDC. (2) SPDT dry outputs, 1 Amp @ 30VDC. (2) Inputs
                       per station, (4) Auxiliary inputs.
             24.       Provide Model UR-4A Module: Universal Controller for 4 doors. Field select TD,
                       LR, CR, TD/LR, Mantrap and Communicating Bathroom Interlock. (4) Fused
                       SPDT dry outputs, 5 Amp @ 30VDC. (4) SPDT dry output, 1 Amp @ 30VDC. (2)
                       Inputs per stations, (4) Auxiliary inputs.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required.
             25.       Provide Model RB12V4 backup battery (1 each for 12VDC output; 2 each at
                       24VDC output) rated for 4 Amp Hour backup power.


                                 ELECTRICAL LOCKING SYSTEMS                               08745 - 24
                26.     Provide Model RB12V7 backup battery (1 each for 12VDC output; 2 each at
                        24VDC output) rated for 7 Amp Hour backup power.

2.09    ACCESS CONTROLS
** NOTE TO SPECIFIER ** The following describes various models of access controls. Delete all types
not required. If more than one type is required, give each a type designation and indicate type on Door
Schedule.

        A.   Integrated Stand Alone Keypad for Interior Use: SDC 917 EntryCheck Series. Self-
             contained electronics; Non-volatile EEPROM Memory; 120 PIN Codes, 1 to 6 digits in
             length, programmable for individual or simultaneous control of 1 relay output and 4
             voltage outputs - momentary, timed or latching. Automatic time-out, REX input, duress
             alarm, forced entry alarm, 3 LEDs. .Single-gang, flush-mount.
             1.       Relay output: Form C SPDT, 6 Amps @ 30VDC
             2.       Outputs 1,2,3,4: Switch to common, 500mA @ 24VDC.
             3.       Voltage: 12/24V AC/DC @ 0.02 Amp typical, 0.12 Amp maximum.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             4.       Finish: BHMA 605: Bright brass, clear coated.
             5.       Finish: BHMA 606: Satin brass, clear coated.
             6.       Finish: BHMA 613: Dark-oxidized satin bronze, oil rubbed.
             7.       Finish: BHMA 625: Bright chromium plated.
             8.       Finish: BHMA 630: Satin stainless steel.

        B.      Integrated Stand Alone Keypad for Exterior or Interior Use: SDC 925 EntryCheck
                Series. Self-contained electronics; Non-volatile EEPROM Memory; 480 PIN Codes, 1-6
                digits in length, programmable for individual or simultaneous control of 2 relay outputs and
                2 voltage outputs - momentary, timed or latching. Automatic time-out, REX input, duress
                alarm, forced entry alarm, door ajar, keypad lockout, alarm shunt, 2 LEDs. Weather-
                resistant, surface mount.
                1.        Dimensions: 5-1/2 inches (H) x 4 inches (W) x 3 inches (D).
                2.        Relay 1: Form “C”, 5 Amps @ 24VDC.
                3.        Relay 2: Form “C”, 1 Amp @ 24VDC.
                4.        Outputs 3 and 4: Switch to common, 100mA @ 30VDC.
                5.        Voltage: 12/24V AC/DC @ 0.01 Amp typical, 0.15 Amp maximum.
                6.        Operating Temperature: -20 degrees to +130 degrees F.
                7.        Operating Humidity: 5% to 95% non-condensing.

        C.   Integrated Stand Alone Proximity Card Reader/ Keypad for Exterior or Interior Use: SDC
             950 EntryCheck Series. Self-contained electronics; Non-volatile EEPROM Memory; 400
             Cards and/ or PIN Codes, 1-6 digits in length to control 2 relay outputs. Door open
             programmable for 1 to 99 seconds. Selectable for proximity reader only; proximity reader
             or PIN; proximity reader and PIN operation. Automatic time-out, REX input, tamper
             alarm, reader/ keypad lockout, dual color LED and audible tone. Weather-resistant,
             surface mount.
             1.      Dimensions: 5-3/4 inches (H) x 3-1/4 inches (W) x 1 inch (D).
             2.      Relay 1: Form “C”, 2 Amps @ 30VDC.
             3.      Relay 2: Form “C”, 2 Amps @ 30VDC.
             4.      Voltage: 12VDC @ 0.02 Amp typical, 0.04 Amp maximum.
             5.      Operating Temperature: 32 degrees to 122 degrees F.
             6.      Operating Humidity: 20% to 95% non-condensing.
** NOTE TO SPECIFIER ** The following paragraph is optional. Delete if not required.
             7.      Provide glass-mount kit for through-glass operation of proximity reader.

        D.      Stand Alone Keypad with Remote Controller for Exterior or Interior Use: SDC 931
                EntryCheck Series. Remote mount controller for increased security. Non-volatile
                EEPROM Memory; 6 PIN Codes, 3-8 digits in length to control 2 relay outputs. Door open


                                   ELECTRICAL LOCKING SYSTEMS                                    08745 - 25
                 programmable for 1 to 120 seconds, REX input, tamper alarm, 2 user groups, anti-
                 tailgate, keypad lockout. Relays selectable 1 door plus alarm, CCTV, or doorbell
                 activation using 1 or 2 keypads.
                 1.       Controller Dimensions: 7-1/2 inches (H) x 5-1/2 inches (W) x 2-1/2 inches (D).
                 2.       Relay 1: SPDT dry contacts.
                 3.       Relay 2: SPDT dry contacts.
                 4.       Voltage: 12/24V AC/DC @ 0.02 Amp typical, 0.25 Amp maximum.
                 5.       Controller Operating Temperature: -40 degrees to 120 degrees F.
                 6.       Controller Operating Humidity: Maximum 98% non-condensing.
                 7.       Keypad Operating Temperature: -40 degrees to 160 degrees F.
** NOTE TO SPECIFIER ** Delete all but one of the following options.
                 8.       Keypad Style KP-2U: Economy 5 button, stainless steel, 6-5/8 inches (H) x 2-1/4
                          inches (W) x 1/2 inch (D), 15 foot cable.
                 9.       Keypad Style KP-3U: 12 button, narrow frame mount, black with stainless steel
                          overlay, red and green LEDs, 7-1/8 inches (H) x 1-3/4 inches (W) x 5/8 inch (D),
                          15 foot cable.
                 10.      Keypad Style KP-3Y: 12 button, narrow frame mount, black, illuminated, red and
                          green LEDs, 7-1/8 inches (H) x 1-3/4 inches (W) x 5/8 inch (D), 15 foot cable.
                 11.      Keypad Style KP-4U: 12 button, single gang mount, stainless steel, red and green
                          LEDs, 5-1/8 inches (H) x 3-3/8 inches (W) x 7/16 inch (D), 15 foot cable.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required. If required,
delete all but one option.
                 12.      Provide additional KP-2U keypad with 15 foot cable.
                 13.      Provide additional KP-3U keypad with 15 foot cable.
                 14.      Provide additional KP-3Y keypad with 15 foot cable.
                 15.      Provide additional KP-4U keypad with 15 foot cable.

        E.       Stand Alone Keypad with Remote Controller for Exterior or Interior Use: SDC 935
                 EntryCheck Series. Remote mount controller for increased security. Non-volatile
                 EEPROM Memory; 500 PIN Codes, 3-8 digits in length; 24 hour clock, 16 user groups, 16
                 time zones, holiday schedule. Controls 1 main relay output and 2 programmable auxiliary
                 relay outputs. Door open programmable for 1 to 99 seconds. REX input, tamper alarm,
                 anti-tailgate, keypad lockout, duress codes, door ajar/ forced door alarm. 750 event audit
                 trail, parallel printer port for audit printing.
                 1.        Controller Dimensions: 7-3/4 inches (H) x 7-1/8 inches (W) x 1-1/8 inches (D).
                 2.        Main Relay: Form “C”, 6 Amps @ 30VDC.
                 3.        Relays 2 and 3: Form “C”, 6 Amps @ 30VDC.
                 4.        Voltage: 12/24V AC/DC @ 0.15 Amp.
                 5.        Controller Operating Temperature: -40 degrees to 120 degrees F.
                 6.        Controller Operating Humidity: Maximum 98% non-condensing.
                 7.        Keypad Operating Temperature: -40 degrees to 160 degrees F.
** NOTE TO SPECIFIER ** Delete all but one of the following options.
                 8.        Keypad Style KP-30U: 12 button, narrow frame mount, black with stainless steel
                           overlay, red and green LEDs, 7-1/8 inches (H) x 1-3/4 inches (W) x 5/8 inch (D),
                           15 foot cable.
                 9.        Keypad Style KP-30Y: 12 button, narrow frame mount, black, illuminated, red and
                           green LEDs, 7-1/8 inches (H) x 1-3/4 inches (W) x 5/8 inch (D), 15 foot cable.
                 10.       Keypad Style KP-40U: 12 button, single gang mount, stainless steel, red and
                           green LEDs, 5-1/8 inches (H) x 3-3/8 inches (W) x 7/16 inch (D), 15 foot cable.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required. If required,
delete all but one option.
                 11.       Provide additional KP-30U keypad with 15 foot cable for controlled egress.
                 12.       Provide additional KP-30Y keypad with 15 foot cable for controlled egress.
                 13.       Provide additional KP-40U keypad with 15 foot cable for controlled egress.




                                   ELECTRICAL LOCKING SYSTEMS                                   08745 - 26
2.10     REQUEST-TO-EXIT PUSH BARS
** NOTE TO SPECIFIER ** The following describes various models of request-to-exit push bars. Delete
all types not required. If more than one type is required, give each a type designation and indicate type on
Door Schedule.

        A.   Pressure Sensitive Non-Latching Push Bar: SDC Sure Exit PSB560 Series. Activation
             with non-perceptible movement, field adjustable sensor circuits, armored power transfer
             loop and 10 foot jacketed cable. Triple fail safe. Operable at 12 or 24 Volt DC without field
             adjustment. UL Listed under categories (ALVY) Access Control System Unit, (CVXJ)
             Burglary Resistant Electric Locking.
             1.      Lock Switch: SPDT, 3 Amp @ 30VDC.
             2.      Alarm Shunt/ Status Switch: SPDT, 3 Amp @ 30VDC.
             3.      Voltage: 12/24V AC/DC @ 0.02 Amp typical, 0.12 Amp maximum.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required..
             4.      Provide Model 500GL-KIT glass door mounting kit.
             5.      Provide Model 500-SK Shim Kit to raise bar 1/4 inch from face of door.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             6.      Finish: BHMA 605: Bright brass, clear coated.
             7.      Finish: BHMA 628: Satin aluminum, clear anodized.
             8.      Finish: BHMA 629: Bright stainless steel.
             9.      Finish: BHMA 630: Satin stainless steel.
             10.     Finish: BHMA 710: Dark-oxidized satin bronze anodized.
             11.     Finish: BHMA 711: Flat black anodized.

        B.   Mechanical Switch Non-Latching Push Bar: SDC Sure Exit MSB550 Series. Activation
             with 1/8 inch movement of bar. UL Listed under categories (ALVY) Access Control
             System Unit, (CVXJ) Burglary Resistant Electric Locking.
             1.       Lock Switch: SPDT, 5 Amp @ 30VDC.
** NOTE TO SPECIFIER ** Retain at least one of the following options. Delete types/ finishes not
required.
             2.       Provide Model PT-2B black/ brown armored loop.
             3.       Provide Model PT-2U stainless steel armored loop.
             4.       Provide Model PT-3V stainless steel armored loop with aluminum surface wire
                      junction.
** NOTE TO SPECIFIER ** The following paragraphs are optional. Delete if not required..
             5.       Provide second switch for dual-failsafe redundancy, alarm shunt, or monitor
                      output.
             6.       Provide Model 500GL-KIT glass door mounting kit.
             7.       Provide Model 500-SK Shim Kit to raise bar 1/4 inch from face of door.
** NOTE TO SPECIFIER ** Delete the following paragraphs for finishes not required.
             8.       Finish: BHMA 605: Bright brass, clear coated.
             9.       Finish: BHMA 628: Satin aluminum, clear anodized.
             10.      Finish: BHMA 629: Bright stainless steel.
             11.      Finish: BHMA 630: Satin stainless steel.
             12.      Finish: BHMA 710: Dark-oxidized satin bronze anodized.
             13.      Finish: BHMA 711: Flat black anodized.

2.11    ELECTRICAL LOCKING SYSTEM ACCESSORIES
** NOTE TO SPECIFIER ** The following describes various models of electrical locking system
accessories. Delete all types not required. If more than one type is required, give each a type designation
and indicate type on Door Schedule.

        A.      Break Glass Emergency Door Release: SDC 491 for immediate unlocking of all doors
                equipped with failsafe electric locks on the same circuit. SDC491 Emergency Door
                Release includes a 12/24 volt siren (Blue). 491BB Surface Mount Back Box available.



                                    ELECTRICAL LOCKING SYSTEMS                                    08745 - 27
B.     1. Provide SDC 491 Emergency Door Release



C.     Key Operated Key Switches: SDC 700 series rated 6 Amp @ 30VDC on single gang
       stainless steel 20 Ga. wall plate. 800 series on ¼” thick aluminum or stainless. Accepts
       standard US type mortise cylinder,(not included).

        Provide
     701U         AA SPDT key switch              808ALNV         1 MO SPDT & 1 AA SPDT
     701NU        AA SPDT key switch              808U            1 MO SPDT & 1 AA SPDT
     701TU        AA SPDT key switch              808NU           1 MO SPDT & 1 AA SPDT
     801ALV       AA SPDT key switch              808TU           1 MO SPDT & 1 AA SPDT
     801ALNV      AA SPDT key switch              709U            2 AA SPDT key switch
     801U         AA SPDT key switch              709NU           2 AA SPDT key switch
     801UN        AA SPDT key switch              709TU           2 AA SPDT key switch
     801TU        AA SPDT key switch              809ALV          2 AA SPDT key switch
     702U         MO SPDT key switch              809ALNV         2 AA SPDT key switch
     702NU        MO SPDT key switch              809U            2 AA SPDT key switch
     702TU        MO SPDT key switch              809NU           2 AA SPDT key switch
     8021ALV      MO SPDT key switch              809TU           2 AA SPDT key switch
     802ALNV      MO SPDT key switch              710U            1-60 Timer & 1 AA SPDT MO
     802U         MO SPDT key switch              710NU           1-60 Timer & 1 AA SPDT MO
     802UN        MO SPDT key switch              710TU           1-60 Timer & 1 AA SPDT MO
     802TU        MO SPDT key switch              810ALV          1-60 Timer & 1 AA SPDT MO
     704U         1-60 TIMER SPDT X MO            810ALNV         1-60 Timer & 1 AA SPDT MO
     704NU        1-60 TIMER SPDT X MO            810U            1-60 Timer & 1 AA SPDT MO
     704TU        1-60 TIMER SPDT X MO            810NU           1-60 Timer & 1 AA SPDT MO
     804ALV       1-60 TIMER SPDT X MO            810TU           1-60 Timer & 1 AA SPDT MO
     804ALNV      1-60 TIMER SPDT X MO            711U            2 MO DPDT key switch
     804U         1-60 TIMER SPDT                 711NU           2 MO DPDT key switch
     804NU        1-60 TIMER SPDT                 711TU           2 MO DPDT key switch
     804TU        1-60 TIMER SPDT                 811ALV          2 MO DPDT key switch
     705U         AA DPDT key switch              811ALNV         2 MO DPDT key switch
     705NU        AA DPDT key switch              811U            2 MO DPDT key switch
     705TU        AA DPDT key switch              811NU           2 MO DPDT key switch
     805ALV       AA DPDT key switch              811TU           2 MO DPDT key switch
     805ALNV      AA DPDT key switch              712U            1 MO DPDT & 1 AA DPDT
     805U         AA DPDT key switch              712NU           1 MO DPDT & 1 AA DPDT
     805NU        AA DPDT key switch              712TU           1 MO DPDT & 1 AA DPDT
     805TU        AA DPDT key switch              812 ALV         1 MO DPDT & 1 AA DPDT
     706U         MO DPDT key switch              812ALNV         1 MO DPDT & 1 AA DPDT
     706NU        MO DPDT key switch              812U            1 MO DPDT & 1 AA DPDT
     706TU        MO DPDT key switch              812NU           1 MO DPDT & 1 AA DPDT
     806ALV       MO DPDT key switch              812TU           1 MO DPDT & 1 AA DPDT
     806ALNV      MO DPDT key switch              713U            2 AA DPDT key switch
     806U         MO DPDT key switch              713NU           2 AA DPDT key switch
     806NU        MO DPDT key switch              713TU           2 AA DPDT key switch
     806TU        MO DPDT key switch              813ALV          2 AA DPDT key switch
     707U         2 MO DPDT key switch            813ALNV         2 AA DPDT key switch
     707NU        2 MO DPDT key switch            813U            2 AA DPDT key switch
     707TU        2 MO DPDT key switch            813NU           2 AA DPDT key switch
     807ALV       2 MO DPDT key switch            813TU           2 AA DPDT key switch
     808ALNV      1 MO SPDT & 1 AA SPDT           802ALNV         MO SPDT key switch 10Amp



                         ELECTRICAL LOCKING SYSTEMS                                    08745 - 28
808U          1 MO SPDT & 1 AA SPDT         802U           MO SPDT key switch 10Amp
808NU         1 MO SPDT & 1 AA SPDT         802UN          MO SPDT key switch 10Amp
808TU         1 MO SPDT & 1 AA SPDT         802TU          MO SPDT key switch 10Amp
709U          2 AA SPDT key switch          801U           AA SPDT key switch 10Amp
709NU         2 AA SPDT key switch          801UN          AA SPDT key switch 10Amp
701U          AA SPDT key switch 10Amp      801TU          AA SPDT key switch 10Amp
701U          AA SPDT key switch 10Amp      702U           MO SPDT key switch 10Amp
701NU         AA SPDT key switch 10Amp      702NU          MO SPDT key switch 10Amp
701TU         AA SPDT key switch 10Amp      702TU          MO SPDT key switch 10Amp
801ALV        AA SPDT key switch 10Amp      8021ALV        MO SPDT key switch10Amp
801ALNV       AA SPDT key switch 10Amp

  Finishes:

  U 630 Satin stainless steel standard for all 700 and 800 series key switches except
  800Al.l.
  V 628 Anodized Aluminum Standard finish for 800AL only.

  Special finishes
  C 605 Bright Brass          D 605 Satin Brass
  F 611 Bright Bronze         P 625 Bright Chrome
  G 612 Satin Bronze          X 313 Dark Bronze Anodized
  H 613 Oil Rubbed Bronze     (313 For 800AL only)
                              335 Black Duronodic

  OPTIONS
  10TD   Mini Timer adj. 1-60 /sec. 12/24VDC. SPDT
  CYL-KD 1 ¼” Key Cylinder with 2 keys (keyed different)
  L1     One LED. Specify RED or Green
  L2     Two LED’s Red and Green
  LT      One tricolor LED. Red, Green, Amber
  ATS    Anti-tamper sensor SPDT
  RMB    Buzzer (12v-24VDC, 20mA
  SN     85db siren ( 4v-28VDC, 18 mA




                     ELECTRICAL LOCKING SYSTEMS                                 08745 - 29
D.   Push Button Switches: 400 Series 3/4'’ Square Button 5 Amp @ 30 VAC/DC
     401U AA SPDT Push Switch
     402U MO SPDT Push Switch
     403U 1-60 Sec. Elec. Adj. Time Delay X MO
     404U MO DPDT Push Switch
     405U AA DPDT Push Switch
     406U 2-MO SPDT Push Switch

     2” Square Push Switches Illuminated 10 Amp @ 30 VAC/DC

     422GEU Green Lens ,engraved “EXIT”, MO, SPDT push switch
     422REU Red Lens, engraved “EXIT”, MO, SPDT push switch
     422GPEU Green Lens engraved “PUSH TO EXIT”, NFPA,BOCA compliant push switch
     422RPEU Red Lens, engraved “ PUSH TO EXIT”, NFPA,BOCA compliant push switch
     422BAU Blue Lens, Handicap Access Symbol, Mo, SPDT push switch

     Mushroom Push Switches 6 Amp @ 30 AC/DC x Single Gang Plate
           For Narrow Plate insert N after the part number
     431RU I-1/2” Dia. Red AA Specify NO or NC push button
     431GU 1-1/2” Dia. Green AA Specify NO or NC push button
     431BU 1-1/2 “Dia. Black AA Specify NO or NC push button
     432RU 1-1/2” Dia. Red MO Specify NO or NC push button
     432GU 1-1/2” Dia. Green MO Specify NO or NC push button
     432BU 1-1/2” Dia. Black MO Specify NO or NC push button
     432RKRU 1-1/2” Dia. Red Latching w/Key Reset push button
     433RU 1-1/2 Dia Red 1-60 Sec. Adj. Timer push button x Dbl gang plate
     433GU 1-1/2” Dia Green 1-60 Sec. Adj. Timer push button x Dbl gang plate
     433BU 1-1/2” Dia. Black 1-60 Sec Adj. Timer push button x Dbl gang plate      434RU
     1-1/2” Dia.Red MO, NO x NC push button
     434GU 1-1/2” Dia. Green MO, NO x NC push button
     434BU 1-1/2” Dia. Black MO, NO x NC push button
     435RU 1-1/2” Dia. Red AA NO x NC push button
     435GU 1-1/2” Dia. Green AA NO x NC push switch
     435BU 1-1/2” Dia. Black AA NO x NC push switch
     441RU 2-5/8” Dia. Red AA, NO & NC push switch X Dbl gang plate
     441GU 2-5/8” Dia. Green AA, NO & NC push switch x Dbl gang plate
     441BU 2-5/8” Dia. Black AA, NO & NC push switch x Dbl gang plate
     442RU 2-5/8” Dia. Red MO, NO & NC push switch x Dbl gang plate
     442GU 2-5/8” DIA Green MO, NO & NC push switch x Dbl gang plate
     442BU 2-5/8” Dia. Black MO, NO & NC push switch x Dbl gang plate
     443RU 2-5/8” Dia. Red, 1-60 sec Adj. Timer x Dbl gang plate
     443GU 2-5/8” Dia Green, 1-60 Sec. Adj, Timer x Dbl gang plate
     443BU 2-58” Dia. Black , 1-60 Sec. Adj. Timer x Dbl. Gang plate
     444RU 2-5/8” Dia. Red, MO, 2NO, 2NC x Dbl. Gang plate (3” depth)
     444GU 2-5/8” Dia. Green , MO, 2NO, 2NC x Dbl. Gang plate (3” depth)
     444BU 2-5/8” Dia. Black, MO, 2NO, 2NC x Dbl gang plate (3” depth)
     446GEU 2-5/8” Dia. MO DPDT “EXIT” push button


     VANDAL RESISTANT STEEL PUSH SWITCH WITH ¼” THICK ALUMINUM PLATE


                      ELECTRICAL LOCKING SYSTEMS                                08745 - 30
     451V AA,SPDT single gang push switch
     451NV AA, SPDT Narrow push switch
     452V MO, SPDT push switch
     452VPTD 2-60 Sec. Adj. Pneumatic SPDT Time Delay 10 Amp Res.
     452NV MO , SPDT Narrow push switch
     452NVPTD 2-60 Second Adj. Pneumatic SPDT Time Delay 10 Amp Resistive

     Finishes:

     U 630 Satin stainless steel standard for all 700 and 800 series key switches except
     800AL.
     V 628 Anodized Aluminum Standard finish for 800AL only.

     Special Finishes:
     C 605 Bright Brass              D 605 Satin Brass
     F 611 Bright Bronze             P 625 Bright Chrome
     G 612 Satin Bronze              X 313 Dark Bronze Anodized
     H 613 Oil Rubbed Bronze         (313 For 800AL only)
                                     Y 335 Black Duronodic

     Options



E.   Mini Consoles for one or two doors
     DTMO-1      (1) Momentary switch and (1) LED
     DTMO-2      (2)Momentary switches and (2) LED
     DTMOMA-2 (1) Momentary, (1) Maintained and (2) LEDs
     DTMA-2      (2) Maintained switches and (2) LEDs

F.   Modular Control Consoles
     TCC Slope Front Desk Top Design
           (12) Stations maximum when using (2) control panels
            Base unit is: Less Panels
            Color: Black side and beige top (10-1/4”W x 4-3/4”H x 9-%/8”D)
     RCC Rack Mount Console
           (24) Stations maximum when using (3) control panels
           Maximum is 20 stations with” E” panel
           Base unit is less panels.
           Color: Beige (19”W x 5-1/4” H x 6” D)

G.   Switch and Indicator Panels    Select panels to be installed in TCC or RCC chassis

     Rocker Switch Rating: 3 Amp @ 30VDC
     Power required per LED:.02 Amp @ 24VDC
     AL4 (4) Momentary switches with LEDs
     BL4 (4) Maintained switches with LED s
     CL4 (4) Momentary/Off/Maintained switches with LEDs
     DL4 (4) Momentary/Off/Momentary switches with LEDs

     AL8   (8) Momentary switches with LEDs
     BL8   (8) Maintained switches with LEDs
     CL8   (8) Momentary/Off/Maintained switches with LEDs
     DL8   (8) Momentary/Off/Momentary switches with LEDs




                       ELECTRICAL LOCKING SYSTEMS                                   08745 - 31
            AL4E     (4) Momentary switches with LEDs, Alarm, Reset Push Buttons and Key Lock
            BL4E     (4) Maintained switches with LEDs, Alarm, Reset Push Buttons and Key Lock
            CL4E     (4) Momentary/Off/ maintained switches with LEDs, Alarm, Reset Push Buttons
                        and Key Lock
            DL4E     (4) Momentary/Off/Momentary switches with LEDs Alarm, Reset Push Button
                         and Key Lock
            EA        Panel with Alarm, Reset Push Button and Key Lock
            F         Blank Panel

       H.   Cabinets
            CAB7 Black cabinet for 1 RCC (7” H x 20-1/2” W x 14-1/2” D)
            CAB12 Black cabinet for (2) RCC (12-1/2 H x 20-1/2” W x 14-1/2 D)

       I.   Latch and Deadbolt Monitor Strikes SPDT Rated 5 Amp.@ 30VAC/DC
            Strike furnished by others Non Handed
            MS-12 For cylindrical latch or deadbolt Monitor SPDT 2-3/4” strike
            MS-12D For cylindrical latch or deadbolt Monitor DPDT 2-3/4” strike
            MS-14 For cylindrical latch or deadbolt Monitor SPDT 4-7/8” strike
            MS-14D For cylindrical latch or deadbolt Monitor DPDT 4-7/8” strike
            MS-16 For mortise latchbolt Monitor SPDT 4-7/8” field reversible
            MS-16D For mortise latchbolt Monitor DPDT 4-7/8” field reversible
            MS-18 For mortise lock deadbolt Monitor SPDT 4-7/8”,field reversible
            MS-18D For mortise lock deadbolt Monitor DPDT 4-7/8” field reversible
            MS-20 For dual mortise latch and deadbolt Monitor SPDT 4-7/8”, non handed
            MS-20D For dual mortise latch and deadbolt Monitor DPDT 4-7/8” non handed

       J.   Passive Infrared Egress Control
            MD-31D-OW Motion Detector with Time Delay – Off white
            MD-31D-B       Mootion Detector with Time Delay – Black

       K.   Timer, Time Delay Relay
            10TD Time Delay Relay Module with adjustable 1-60 second relock delay
            Input: 12/24V AC/DC. Output SPDT dry contact
            2 Amps @ 30VDC (resistive) Size , 2-1/4” x 1-1/2” x3/4”.

            14-2 & day Programmable Timer with Memory Battery back-up capability
            1 SPDT Dry contact !6 Amp. @ 30VAC/DC Specify 12V or @4V AC/DC

       L.   Sirens And Buzzers: 630 Stainless Steel Standard
            400-RMB Buzzer on Sgle gang plate . (specify 12VDC or 24VDC, 20mA max.)
            400N-RMB Buzzer on narrow plate (specify 12VDC or 24VDC, 20mA max.)
            400-SN     Siren on Sgl. Gang plate (3-28VDC, 18mA max.
            400N-SN Siren on narrow plate (3-28VDC,18mA max.

       M.   Power Transfer Devices
            PT-2   Armored Flex Conduit (less wires 18” long
            PT-3   Armored Flex Conduit (less wires) with wire junction box
            PT-5   Concealed Power Transfer
            PTH-2 Power Transfer Hinge (2 wires) 20 AWG 5 Amp @ 24V AC/DC
            PTH-4 Power Transfer Hinge (4 wires) 28 AWG 5 Amp @ 24V AC/DC
            PTH-10 Power Transfer Hinge (10 wires) 30 AWG 5 Amp @ 24V AC/DC

       PART 3-EXECUTION

2.12   EXAMINATION

       A.   Do not begin installation until substrates have been properly prepared.


                               ELECTRICAL LOCKING SYSTEMS                               08745 - 32
       B.    Proceed with installation only after unsatisfactory conditions have been corrected.

2.13   INSTALLATION

       A.    Install each item according to manufacturer's written instructions, utilizing proper
             fasteners provided by manufacturer.

       B.    Items for fire doors shall be installed conforming with NFPA 80, and all other applicable
             building codes and regulations.

       C.    Set units level, plumb, and true to line and location. Adjust and reinforce attachment
             substrates as necessary for proper installation and operation.

2.14   ADJUSTING

       A.    Adjust and check each operating item of door hardware and each door to ensure proper
             operation or function of every unit. Replace units that cannot be adjusted to operate as
             intended.

       B.    Test for proper operation with building power energized; coordinate with startup
             procedures of other installers.


                                         END OF SECTION




                                ELECTRICAL LOCKING SYSTEMS                                      08745 - 33

								