scope of work template
							                                                                                         Signal Converter/Amplifier SC200
CONVERTERS
 QC SERIES


                                                                           Function: The SC200 is a general purpose non-isolating signal converter,
                                                                           conditioner, transmitter, amplifier which will give a transmission level voltage
                                                                           or current output from a single low or medium level process signal input. The
                                                                           SC200 can also accept Frequency inputs from a variety of transducer types
                                                                           and perform Frequency to Current/Voltage conversion. For very low
                                                                           frequencies (less than 10Hz) see data sheet on the SI300/20.
                                                                           Options on the SC200 include: a signal inverter; a signal limiter; an integrator;
                                                                           and a differentiator.


             SPECIFICATIONS
             Please note that the following are          Resistance (2 wire)                           OUTPUTS:                                     GENERAL:
             typical standard ranges. We will            Between 0 and 10K ohms                        DC Current
             manufacture instruments to cater            Minimum span 10 ohms                                                                       Linearity Error
                                                                                                       0 to 1mA into 10 to 20K ohms                 Proportional to input ±0.1% of
             for other ranges too, within certain        Maximum span 10K ohms                         1 to 5mA into 10 to 4K ohms
             limitations. Please contact our                                                                                                        span
                                                         Potentiometers (3 wire)                       0 to 10mA into 10 to 2K ohms
             internal sales department for further                                                     4 to 20mA into 10 to 1K ohms                 Temperature Coefficient
                                                         Between 0 and 20K ohms
             clarification.                                                                            Minimum span 1mA                             ±0.1% of span/ 10ºC
                                                         Minimum span 10 ohms
                                                         Maximum span 20K ohms                         Maximum span 20mA                            (for inputs > 100mV)
             INPUTS:                                                                                                                                + Cold junction error, for
             DC Current                                  Resistance Thermometers                       DC Voltage                                   thermocouple inputs
             0 to 1mA into 1K ohms                       (RTDs, PT100s)                                0 to 1 Volt into 100 ohms min
                                                         2 or 3 wire, 100 ohms at 0ºC or               1 to 5 Volts into 500 ohms min               Ripple Rejection
             0 to 10mA into 100 ohms                                                                                                                Greater than 60dB at 50 Hz
             4 to 20mA into 62.5 ohms                    130 ohms at 0ºC                               0 to 10 Volts into 1K ohms min
             10 to 50mA into 25 ohms                     Minimum temperature span 10ºC                 Minimum span 100mVolt                        Operating Temperature Range
             Other current inputs as required            Maximum temperature span 600ºC                Maximum span 10 Volts                        0 to +50ºC
             Minimum current 10µA                                                                      Load Stability
                                                         Thermocouples                                 Less than 0.02% over the load                Storage Temperature Range
             Maximum current 100mA                       Type B, E, J, K, N, R, S & T                                                               –20 to +85ºC
                                                                                                       range specified
             DC Voltage                                  Temperatures covered:
                                                         Type Range        Min Temp Change                                                          Operating Humidity Range
             Between 0 and 250 Volts DC                                                                                                             0 to 95% RH non-condensing
             Minimum voltage span 5mV                    B 600 to 1800ºC           400ºC               SUPPLY:
             Maximum voltage span 250V                   E –260 to 1000ºC           65ºC               Power Supplies                               Storage Humidity Range
                                                         J –200 to 1200ºC           80ºC               100 to 120 Volt 50/60 Hz                     0 to 95% RH non-condensing
             Input Impedance                             K –260 to 1600ºC          100ºC
             1M ohms or greater                                                                        200 to 240 Volt 50/60 Hz                     Weight
                                                         N       0 to 1300ºC       150ºC               or 24 Volt DC with inverter to
                                                         R       0 to 2000ºC       400ºC                                                            SC200 290 gms
             AC Frequency or Pulse                                                                     maintain signal to power supply
             Between 10 and 10K Hz                       S       0 to 1800ºC       400ºC               isolation
             Minimum span 10 Hz                          T –260 to 800ºC           100ºC
             Maximum span 10K Hz                         Automatic cold junction                       Power Required
             Minimum amplitude 50mV RMS                  compensation                                  3 Watts Maximum
             Maximum amplitude 100 Volts                 Open circuit thermocouple                     Pilot Light
             Peak to Peak                                monitoring upscale or downscale               Green LED shows Power ON
                                                         drive


             MECHANICAL DETAILS                                                               TERMINATION DETAILS
                                                                                              Termination details are dependent upon input type and upon type of housing chosen
                                                                                              (19” rack or DIN rail mounting enclosure) and, if 19” rack, screw terminals or solder
                                                                                              terminals. Further details upon request from our internal sales department.
                               129




                                                164
                        35.5

                                                190

                      (Dimensions in mm)




             ORDERING DETAILS

             (a) Give identification code, i.e. SC200
             (b) Give power supply voltage, i.e. 240 Volt 60 Hz
             (c) Give details of input signal i.e. Chromel/Alumel thermocouple, span 0 to 250ºC. (If thermocouple input please specify upscale or downscale burnout drive)
             (d) Give details of output required, i.e. 4 to 20mA


                                                                         LEE -DICKENS LTD
                                                                         Desborough, Kettering, Northants NN14 2QW U.K.
             6.5                                                         Te l : ( 0 1 5 3 6 ) 7 6 0 1 5 6 F a x ( 0 1 5 3 6 ) 7 6 2 5 5 2

						