							         LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
       OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                            SAFETY




NFPA 72 - National Fire Alarm Code
      Chapter 4 - Notification Appliances
• 72:4-1.3 Requires these devices to be listed.
• 72:4-2.2 Appliances intended for special environments
  shall not exceed their listing (outdoors vs. indoors, high
  humidity, etc…).
• 72:4-2.3 Where subject to mechanical damage, a
  notification device shall be protected. A mechanical guard
  used to protect a notification device shall be listed for use
  with the device being used.
         LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
       OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                            SAFETY




NFPA 72 - National Fire Alarm Code
      Chapter 4 - Notification Appliances
• 72:4-3.1.2 An average sound level greater than 105 dBA
  shall require the use of a visible signal appliance.
• 72:4-3.1.2 The total sound pressure level produced by the
  ambient sound pressure and signaling appliance shall not
  exceed 120 dBA.
         LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
       OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                            SAFETY




NFPA 72 - National Fire Alarm Code
      Chapter 4 - Notification Appliances
• 72:4-3.2.1 Audible signal appliances intended for
  operation in the public mode shall have a sound level of
  not less than 75 dBA at 10 ft. or more than 120 dBA at the
  minimum hearing distance from the audible appliance.
         LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
       OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                            SAFETY




NFPA 72 - National Fire Alarm Code
      Chapter 4 - Notification Appliances
• 72:4-3.4 Sleeping Areas
   – Sleeping areas audible appliances shall have a minimum 15 dBA
     above the average ambient sound level or 5dBA above the
     maximum sound level having a duration of at least 60 seconds or a
     sound level of at least 70 dBA, whichever is greater, measured at
     the pillow level in the occupied area.
• 72:4-4.1 Visual Notification
   – UL 1638 vs. UL1971
        LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
      OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                           SAFETY




NFPA 72 - National Fire Alarm Code
     Chapter 4 - Notification Appliances

• 72:4-4.4 Wall-mounted visual appliances shall be
  mounted such that the entire lens is not less than
  80 in. (2.03 m) and not greater than 96 in. (2.43
  m) above the finished floor.
• Table 4-4.4.1.1(a) Wall-mounted appliances
• Table 4-4.4.1.1(b) Ceiling-mounted appliances
           LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
         OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                              SAFETY




 NFPA 72 - National Fire Alarm Code
        Chapter 4 - Notification Appliances
• 72:4-4.4.1. Spacing
  in a Room
• More than two visual
  devices that can be
  seen shall be
  synchronized.
       LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
     OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                          SAFETY




NFPA 72 - National Fire Alarm Code
    Chapter 4 - Notification Appliances




  Correct Spacing                 Incorrect Spacing
            LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
          OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                               SAFETY




  NFPA 72 - National Fire Alarm Code
         Chapter 4 - Notification Appliances

72:4-4.4.2. Spacing in Corridors
             LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
           OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                                SAFETY




  NFPA 72 - National Fire Alarm Code
          Chapter 4 - Notification Appliances

72:4-4.4.3 Sleeping Areas
   Visual device shall be located within 16 ft. of the pillow.

   Templates!
                LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
              OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                                   SAFETY




   NFPA 72 - National Fire Alarm Code
            Chapter 4 - Notification Appliances

Interpretive Memorandum 2000-6
Common Use Areas:
a. File Rooms
b. Copy Rooms
c. Lounges/kitchenettes/cafeteria
d. Conference Rooms
e. Exterior balconies/patios if you are required to re-enter the building to exit
               LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
             OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                                  SAFETY



  NFPA 72 - National Fire Alarm Code
     Chapter 5 - Supervising Station Fire Alarm
                     Systems
72:5-2 Central Station Service
    a) Full Service - provides all of the elements of a central station with its own
    facilities and personnel.
    b) Monitor Only - provides the signal monitoring, retransmission, and
    associated record keeping. Owner must contract out a listed “Fire alarm service
    - local company” or a “Full Service” company to provide runner and
    maintenance service.
    c) Fire alarm service - local company - provides runner and maintenance
    service. Owner must contract out a “Full Service” or a “Monitor Only” company
    to perform the monitoring.
             LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
           OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                                SAFETY



  NFPA 72 - National Fire Alarm Code
    Chapter 5 - Supervising Station Fire Alarm
                    Systems
72:5-2 Central Station Service
The fire alarm system shall be “certificated” by a third party
verification. (UL)
The monitoring station is also inspected by the third party.
Upon receipt of an alarm signal, the central station shall
   Immediately retransmit the alarm to the public fire alarm service communication
   center.
   Dispatch a runner to the protected premises to arrive within 1 hour to reset
   equipment.
   Notify subscriber.
              LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
            OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                                 SAFETY



 NFPA 72 - National Fire Alarm Code
    Chapter 5 - Supervising Station Fire Alarm
                    Systems
72:5-3 Proprietary Supervising Station Service
Monitoring facility is provided by the owner.
The protected property can be contiguous or noncontiguous.
The monitoring facility shall be located in a fire-resistive, detached building or
suitable cutoff room.
Upon receipt of an alarm signal, the proprietary supervising station shall:
    Immediately retransmit the alarm to the public fire alarm service communication
    center.
    Dispatch a runner to the protected premises to arrive within 1 hour.
             LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
           OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                                SAFETY



NFPA 72 - National Fire Alarm Code
   Chapter 5 - Supervising Station Fire Alarm
                   Systems
72:5-3 Proprietary Supervising Station Service
Upon receipt of a supervisory or trouble signal, the proprietary
supervising station shall:
   Immediately communicate with the designated person to ascertain the reason for the
   signal.
   Dispatch a runner to the protected premises to arrive within 1 hour.
   Where required, notify the fire department.
           LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
         OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                              SAFETY



NFPA 72 - National Fire Alarm Code
   Chapter 5 - Supervising Station Fire Alarm
                   Systems
72:5-4 Remote Station Service
Can be a privately owned facility.
Requires a minimum of two operators
Upon receipt of an alarm supervisory or trouble signal, the remote
station shall:
    Contact the fire service communication center.
            LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
          OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                               SAFETY



 NFPA 72 - National Fire Alarm Code
     Chapter 6 - Public Fire Alarm Reporting
                     System
72:6 Auxiliary Signaling System
Protected premises fire alarm system is tied into public fire alarm
reporting system.
Alarm signal is transmitted to the fire service communication
center.
       LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
     OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                          SAFETY



NFPA 72 - National Fire Alarm Code
    Chapter 7 - Inspection, Testing and
              Maintenance
           LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
         OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                              SAFETY



NFPA 72 - National Fire Alarm Code
    Chapter 8 - Fire Warning Equipment for
                Dwelling Units

72:8-1.1 This chapter contains minimum requirements for the
selection, installation, operation, and maintenance of fire
warning equipment for use family living units. (i.e. single
station smoke detectors placed in the sleeping rooms within the
single family living unit)
           LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
         OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                              SAFETY



      Tips for Fire Alarm Shop Drawing
               Submittal Success

1) Get all of the necessary background information on the
building (i.e. architectural review, date constructed, appeal
issues, order of correction, etc…).
2) Shop drawings should reflect the same architectural design
that was reviewed and accepted by the AHJ.
3) Shop drawings are legible, every room is identified and
drawn to a recognized scale.
4) Provide a legend that identifies every fire alarm device.
           LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
         OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                              SAFETY



      Tips for Fire Alarm Shop Drawing
               Submittal Success

5) Every visual device is identified with a candela rating.
6) Provide a reflective ceiling plan that identifies ceiling heights,
light fixtures, hvac supply diffusers with smoke detection
system layout.
7) Identify the correct fire alarm signaling system type in
accordance with NFPA 72 and provide the appropriate battery
calculations for secondary power supply. (i.e. beware of using
the term “central station”).
8) Provide a “ Sequence of Operation.”
           LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
         OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                              SAFETY



      Tips for Fire Alarm Shop Drawing
               Submittal Success


9) Provide manufacturer’s cutsheets on all devices and proof of
listing from a recognized independent testing lab.
10) Make sure that all correspondence to SFMO is from the
design professional.
11) Shop drawing review stamp.
12) If you have a code question - call us!
           LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
         OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                              SAFETY




   Fire Alarm Exemption Request Forms

Required Fire Alarm Systems
   Minor work to a system (i.e. ten or less devices)
   Allowed to replace only existing non-functioning fire alarm
   control panel, provided the signaling system is not changed.
   Submission of fire alarm panels for the installation of a
   “supervised” automatic sprinkler system or for elevator
   recall system, where the building does not have a typical fire
   alarm system for occupant notification.
          LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
        OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                             SAFETY




   Fire Alarm Exemption Request Forms

Non Required Fire Alarm Systems
Systems not mandated by the Code.
    LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
  OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                       SAFETY




http://www.dps.state.la.us/sfm
            LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
          OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                               SAFETY




Educational Occupancy Fire Alarm Exercise

Single story building.
Building is protected by a supervised automatic sprinkler system.
A fire barrier subdivides the building and with fire rated doors utilizing
hold-open devices.
             LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
           OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                                SAFETY



Educational Occupancy Fire Alarm Exercise

14.3.4 Detection, Alarm, and Communications Systems.
14.3.4.1 General.
Educational occupancies shall be provided with a fire alarm system in accordance
with Section 9.6.
Exception: This requirement shall not apply to buildings with an area not
exceeding 1000 ft2 (93 m2) that contains a single classroom and is located not
less than 50 ft (15.2 m) from another building.
14.3.4.2 Initiation.
14.3.4.2.1 Initiation of the required fire alarm system, other than as permitted by
14.3.4.2.3, shall be by manual means in accordance with 9.6.2.1(1).
14.3.4.2.2 In buildings provided with automatic sprinkler protection, the
operation of the sprinkler system shall automatically activate the fire alarm system
in addition to the initiation means required in 14.3.4.2.1.
              LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
            OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                                 SAFETY


14.3.4.3 Notification.
14.3.4.3.1 Occupant Notification.
14.3.4.3.1.1 Occupant notification shall be accomplished automatically in accordance
with 9.6.3. Positive alarm sequence shall be permitted in accordance with 9.6.3.4.
14.3.4.3.1.2 Where acceptable to the authority having jurisdiction, the fire alarm
system shall be permitted to be used for other emergency signaling or for class changes,
provided that the fire alarm is distinctive in signal and overrides all other use.
14.3.4.3.1.3 In order to prevent students from being returned to a building that is
burning, the recall signal shall be separate and distinct from any other signals. Such
signal shall be permitted to be given by use of distinctively colored flags or banners. If
the recall signal is electric, the push buttons or other controls shall be kept under lock.
The key for such lock shall be in the possession of the principal or another designated
person in order to prevent a recall at a time when there is an actual fire. Regardless of
the method of recall, the means of giving the signal shall be kept under lock.
14.3.4.3.2 Emergency Forces Notification.
Fire department notification shall be accomplished in accordance with 9.6.4.
  LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                     SAFETY
            LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
          OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                               SAFETY




Daycare Occupancy Fire Alarm Exercise

Two story building.
Building is protected by a supervised automatic sprinkler system.
          LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
        OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                             SAFETY



Daycare Occupancy Fire Alarm Exercise

16.3.4 Detection, Alarm, and Communications Systems.
16.3.4.1 General.
Day-care occupancies, other than day-care occupancies housed in one
room, shall be provided with a fire alarm system in accordance with
Section 9.6.
16.3.4.2 Initiation.
Initiation of the required fire alarm system shall be by manual means and
by operation of any required smoke detectors and required sprinkler
systems. (See 16.3.4.5.)
16.3.4.3 Occupant Notification.
16.3.4.3.1 Occupant notification shall be in accordance with 9.6.3.
16.3.4.3.2 Positive alarm sequence shall be permitted in accordance with
9.6.3.4.
           LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
         OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING
                              SAFETY




Daycare Occupancy Fire Alarm Exercise


16.3.4.4 Emergency Forces Notification.
Fire department notification shall be accomplished in accordance with
9.6.4.
16.3.4.5 Detection.
A smoke detection system in accordance with Section 9.6 shall be
installed in day-care occupancies, other than those housed in one room.
Detectors shall be installed on each story in front of the doors to the
stairways and in the corridors of all floors occupied by the day-care
occupancy. Detectors also shall be installed in lounges, recreation areas,
and sleeping rooms in the day-care occupancy.