INSTALLATION INSTRUCTIONS MULTI-CABLE GLAND by pok77069

VIEWS: 17 PAGES: 1

									                                                     INSTALLATION INSTRUCTIONS
                                                       MULTI-CABLE GLAND
         The Gleason Multi-Cable Gland is designed to form a weather-tight seal at cable entrances to                HEX HD. BOLTS and LOCKWASHERS
         junction boxes and may be used for either round or flat cables. It may be used with multiple cables
                                                                                                                                        TOP CLAMP PLATE
         stacked or side-by-side providing entire package is no larger than 1.5" x 5.125". NOTE: Gland is
         NOT a strain relief.
                                                   INSTRUCTIONS
         1. Disassemble gland (Fig. 1).                                                                                                    TOP MICARTA
         2. Using template below, cut opening and drill holes in junction box. Mount body casting with                                       BOARD
            rubber gasket between casting and junction box wall using bolts provided.                                                      RUBBER SEAL
                                                                      3. Using end or short section of                                      BOTTOM
                                                                                                                                            MICARTA
                                     CUT-OUT IN MICARTA BOARDS–          cable(s) as template, trace outline                                 BOARD
                                        1/8"(.125) LARGER THAN           of cable(s) in center of both Micarta
         MICARTA BOARDS and
                                           CABLES, ALL SIDES                                                                                  BODY
            RUBBER SEAL                                                  boards and rubber seal. (Fig. 2)
                                                                                                                                             CASTING
                                                                                   CAUTION:
                                                                             Locate cables carefully.            BOLTS FOR
                                                                         Cut-outs in Micarta boards and          SECURING
                                                                                                                 GLAND TO
                                                                         rubber seal must line up exactly.       JUNCTION              GASKET
                                                                                                                    BOX
                                                                      4. Scribe line 1/8" (0.125") OUTSIDE
                                                                         of cable outline (Fig. 2) on Micarta                  Figure 1
                                                                         boards. Cut out cable openings with jigsaw or similar tool.
                                                                      5. Scribe line 1/16"(0.062) INSIDE of cable outline (Fig 2) on seal. Cut out
              CUT-OUT IN SEAL–            CABLES
          1/16"(.062) SMALLER THAN
                                                                         cable opening using hot knife or similar tool. Sides of cut-out must be as
              CABLES, ALL SIDES          MAXIMUM CABLE PACKAGE           smooth as possible to prevent leakage.
                                        CROSS SECTION–1.5" x 5.125"
                                                                      6. Thread cable through top clamp, Micarta boards and rubber seal and
                                                                         reassemble as shown in Figure 1. Seat top clamp plate on top Micarta
                                Figure 2
                                                                         board and secure with four cap screws.
         7. Position cable as required and thoroughly tighten cap screws.
         8. Apply silicone sealant all around where body casting meets junction box, in crack between top Micarta board and cable(s) and
            where top Micarta board meets top clamp plate. Allow sealant to cure per manufacturer’s instructions.



                                              ®
                                                                               Gleason Reel Corp.
                                                                               P.O. Box 26 • 600 S. Clark St.
                                          ®
                                                                               Mayville, Wisconsin 53050-0026
                              HUBBELL     A Hubbell Company                    Phone 920-387-4120 • FAX 920-387-4189

✁
                                                                            7.125"



                                        FOUR HOLES–0.25" dia.




                                                                        5.5"
2.875"




                                                      1.75"                              CUT-OUT
                                                                                          AREA




                                                       BODY CASTING
                                                                                                   FULL SIZE TEMPLATE

                                                                                                                                       Bulletin No. 044976.a

								
To top