Photoelectric Smoke Alarm For 120 VAC and 220 VAC - PDF
Document Sample


7000/7003
Photoelectric Smoke Alarm SERIES
For 120 VAC and 220 VAC Single
Station Tandem and Specialty
Applications
Applications
The 7000/7003 Series of photoelectric smoke alarms
is designed for residential and other occupancies
defined by NFPA 101, including homes, apartments,
hospitals and hotels, in compliance with UL 217 and
NFPA 72. Available in many different models, the
7000/7003 Series is engineered to virtually eliminate
nuisance alarms and deliver outstanding performance
wherever reliable fire protection is required.
The Gentex 7000/7003 Series provides an exclusive
patented three position test feature that simulates a
0.85% and 3.5% actual smoke condition in full compli-
ance with NFPA 72 and UL 217 standards.
It also provides a maintenance indicator and makes the
100% testing requirement easy.
Options include self-restoring 135°F fixed tempera-
ture integral or isolated thermals, and Form A/Form C
dry contacts for remote annunciation. Tandem inter-
connection of up to 12 units is available on several
models; tandem interconnection of up to 6 units is
available on “F” models, which activate the dry contacts
from a remote alarm through the tandem wire or a local
alarm. Approvals
The 7003 Series provides the temporal 3 evacua-
tion tone as a standard feature. When testing the
7003 Series it may take up to 16 seconds longer to
go in or out of alarm.
Standard Features
• 90dBA Solid-State Non-Latching Piezo Horn • BFP (City of Chicago) • NFPA 72
• 1 Year Warranty From Date of Purchase • MSFM Listing #1929 • UL 217
• Nominal 2.5% Sensitivity • BS+A/MEA #927-84-SA • UL 1730
• 5-to-1 Signal-to-Noise Ratio • CSFM #7257-569:104
• Pulsing LED Sensing Chamber
Also UL 1730 listed for Commercial Residential
• Fully Insect Screened and Commercial Residential Multiple-station
• Functional Test Switch — Patented Three Position Test Smoke Alarms.
• Horn Frequency 3100Hz (Nominal)
• Solid-State LED Condition Indicator
• Quick-Disconnect Wiring Harness
• Mounting Hardware Adapts to Standard Junction Boxes
• Dust Cover to Prevent Contamination During Installation
• On-Site Maintenance Washing Program
• Temporal 3 Evacuation Sounding Device (7003 Series)
• Complies With UBC/UFC (7003 Series)
7000/7200 Series
Model Number Part Number Voltage OPTIONS
Local Integral Isolated Tandem Tandem Form A/C
90 dBA 135°F 135°F Up To Up To Contacts
Piezo Thermal Thermal 12 Units 6 Units
7100 907-1109-2 120 VAC l l
7100T 907-1110-2 120 VAC l l l
7100H 907-1111-2 120 VAC l l l
7100F 9071113-2 120 VAC l l l
7100TF 907-1114-2 120 VAC l l l l
7100HF 907-1115-2 120 VAC l l l l
7200 907-1204-2 220 VAC l l
7200F 907-1207-2 220 VAC l l l
7200T 907-1205-2 220 VAC l l l
7200H 907-1206-2 220 VAC l l l
7003/7203 Series (Temporal 3 Sounder)
Model Number Part Number Voltage Local Integral Isolated Tandem Tandem Form A/C
90 dBA 135°F 135° Up To Up To Contacts
Piezo Thermal Thermal 12 Units 6 Units
7103 907-1116-2 120 VAC l l
7103T 907-1117-2 120 VAC l l l
7103H 907-1118-2 120 VAC l l l
7103F 907-1120-2 120 VAC l l l
7103TF 907-1121-2 120 VAC l l l l
7103HF 907-1122-2 120 VAC l l l l
7203 907-1208-2 220 VAC l l
7203F 907-1211-2 220 VAC l l l
7203T 907-1209-2 220 VAC l l l
7203H 907-1210-2 220 VAC l l l
Notes:
The 7100/7103 Series are round units. Square units as 710/713 also available.
Wiring Diagrams
7000/7003 SERIES
Tandem Wiring Diagram Electrical Specifications
QUICK
Operating Voltage (7100/7103) . . . . . . . . . . . . . .120 VAC, 60Hz
DISCONNECT
TYPE PLUG LIMITATIONS: (7200/7203) . . . . . . . . . . . . . .220 VAC, 50Hz
ELECTRICAL
220 VOLTS
120 VOLTS
BOX
SMOKE
Operating Current (All Voltages) . . . . . . . . . . . . . . . . . . . .45 mA
60 HZ 1 A Maximum of 12 alarms
ALARM
(7100/7103, 7100/7103T,
Operating Current (Relay Options) . . . . . . . . . . . . . . . . . .70 mA
2
3 7100/7103H, 7200/7203, Operating Ambient Temp Range . . . . . . . . . . . . . .40°F to 100°F
7200/7203T, 7200/7203H) Alarm Horn Rating . . . . . . . . . . . . . . . . . . . . . . . . .90dB at 10 ft.
may be connected together.
Do not exceed 125 feet
Nominal Sensitivity . . . . . . . . . . . . . . . . . . . . .2.5% Obscuration
ELECTRICAL
BOX
between each detector. Do not “F” Auxiliary Relay . . . . . . . . . . .1 Form A & 1 Form C (0.6 amp)
SMOKE exceed 1125 feet between the “T” Integral Thermal (Self-Restoring) . . . . . . . . . . .135°F at 50 ft.
1 ALARM
first and last detector. NOTE:
2
Gentex smoke alarms can not “H” Isolated Thermal Form A (Self-Restoring) . . . .135°F at 50 ft.
3 Size . . . . . . . . . . . . . . .Diameter: 6.5 in. OA (5.75 in. at Ceiling)
be interconnected to detectors
from other manufacturers. Depth: 2.625 in.
ELECTRICAL A MAXIMUM OF SIX (6)
BOX
SMOKE ALARMS WITH A RELAY Architect & Engineering Specifications
1 ALARM MAY BE TANDEM INTER- The Photoelectric Smoke Alarm shall be a Gentex Model
2 CONNECTED. (7100/7103F,
3
______________ or approved equal which shall provide at least
7100/7103TF, 7100/7103HF,
7200/7203F, 7200/7203TF, the following features and functions.
7200/7203HF) 1. Nominal sensitivity shall be 2.5%.
RED / YEL
2. The alarm shall utilize an infrared LED sensing circuit which
WHT TO ADDITIONAL
SMOKE DETECTORS
pulses in 4 to 5 second intervals; when subjected
BLK (MAX 12 ALARMS
PER SYSTEM)
to smoke the pulse rate shall increase 8 times. After 2 con-
secutive pulses in smoke, the detector will alarm.
3. The alarm shall provide minimum 5-to-1 signal-to-noise ratio
in the optics frame to assure stability of operation in envi-
Relay Models Isolated thermal with optional ronments of high RF and transient conditions.
Models accessory contacts. 4. The sensing chamber shall be fully protected to prevent
7100/7103F Models
7100/7103H entrance of small insects, thus reducing the probability of
7100/7103TF
7203/7203F 7100/7103HF false alarms.
7200/7203TF 7203/7203H 5. A solid state piezo alarm rated at 90dBA at 10ft.
7200/7203HF
SMOKE
6. A visual LED monitor (condition indicator) will pulse in
SMOKE DETECTOR
BRN
normal operation and will remain solid in alarm.
DETECTOR YEL
HEAT BRN 7. An easily accessible test knob shall be provided. The test
SENSOR GREY
ACCESS
CONTACTS
ORN GREY knob in the TEST position will simulate an actual smoke
BLU condition of approximately 3.4% causing the detector to
ALARM VIO
YEL
alarm within 20-36 seconds. It will also have the capability of
CONTACTS ACCESS
CONTACTS
ORN testing to 0.85% as a required minimum. A magnetic switch
VIO/BLK
BLU closure or other switch closure, or smoke generating
TANDEM
RED/YEL
ALARM VIO equipment which does not scatter the light beam or test sen-
BLK
CONTACTS
VIO/BLK
sitivity is not sufficient.
WHT 8. The alarm shall have a tandem interconnect capability of up
POWER RED/YEL
TANDEM to 12 units or 6 units with relay.
BLK
9. The manufacturer shall provide other compatible alarm mod-
POWER
WHT els with the following optional features: a) 135°F fixed tem-
CAUTION: perature isolated thermal with normally opened contact for
RED/YELLOW wire to be capped remote connection to local alarm or annunciator; b) 135°F
RELAY CONTACTS
when not in use. This wire is for
tandem connection only. Do not
RATED LOADS RESISTIVE fixed temperature integral thermal; c) auxiliary Form A/Form
0.6 AMP @ 125 VAC MAX C relay contacts for initiating remote functions and annunci-
connect to any other circuit.
1 AMP @ 24 VDC MAX
0.3 AMP @ 220 VAC MAX
ation; d) relay option that is capable of activation by tandem
interconnect wire. Thermal sensor shall be self-restoring.
10. Unit must be UL 217 listed for both wall and ceiling mount.
24 units per carton 11. Unit shall also meet all requirements of the State of
32 pounds per carton California Fire Marshal.
All equipment shall be completely factory assembled, wired and
tested, and the contractor shall be prepared to submit a certified
letter testifying to this condition.
Alarms which do not meet all of the requirements of this
specification will not be considered.
Fire Protection Products: www.gentex.com
10985 Chicago Dr., Box 310, Zeeland, MI 49464
616/392-7195 1-800/436-8391 FAX: 616/392-4219 Printed on Recycled Paper
Gentex corporation reserves the right to make changes to the product data sheets at their discretion. GX0601-2