Standard
Office Design Criteria
1. Design Philosophy
1) Intent of this document: to be used as a pre-programming template for General Purpose office Buildings (GPB), R&D office buildings, project buildings, multitenant buildings (MTB) and manufacturing support office buildings (MSB). 2) Benchmarking/Quality- Company A will evaluate the project based on local basebuild benchmark values and value for money compared to other multinational facilities in the local market. 3) Life Cycle Costing & Material Selection: a. Redundancy and reliability of equipment i. 99.2% uptime for general office building systems based on 24x5 operations. ii. 99.8% uptime for offices supporting manufacturing operations based on 24x7 operations. 4) Commodity localization- equipment and materials shall be evaluated based on total cost of ownership per above reliability criteria and also per the Company A GPB Specification Guidelines. 5) Design for Life Safety, including Fire Alarm and Fire Fighting systems, shall meet the more stringent design standards of the local jurisdiction or the National Fire Protection Association (NFPA), International Building Code (IBC), and International Fire Code (IFC). 6) Seismic-design shall meet the more stringent design standards of the local jurisdiction or Seismic Design Standards for Buildings, IMDS 2140 and Seismic Design Standards for Non-Structural Components, IMDS 2141 7) Fire & wind rated assemblies must be equivalent to Factory Mutual Standards. 8) Security requirements shall conform to the established Company A Master Design Standards. 9) Environmentally compliant systems and components should be considered in the building design.
2. References
1) Company A archives specific design standards by commodity and system and are available upon request if the designer needs additional technical information. Otherwise, the designer is expected to use their own standards and guidelines that conform to this standard.
3. Risk Management Requirements A. General
1) General Purpose Buildings shall be of noncombustible construction. 2) Structural fire ratings are to meet International Building Code or local equivalent requirements, whichever is more stringent. 3) The roof assembly should be listed in the Factory Mutual Approval Guide as “FM Approved” assembly. 4) Choose the location of outside air intakes to minimize drawing in hazardous chemicals or products of combustion coming either from the building itself or from other structures or devices (i.e., transformers, exhaust systems, etc.).
Page 1 of 24 Office Design Criteria
5) Supply air ducts, if internally insulated, shall have a flame spread index of not more than 25 and a smoke developed rating of not more than 50 when tested in accordance with NFPA 255. 6) Provide wet pipe fire sprinkler systems throughout the facility.
B. Design Standards Compliance & Applicability
1) The design of Company A facilities shall be consistent with U.S. Federal environmental, health and safety regulations, nationally recognized building, fire and equipment safety standards, Company A best known methods, and Company A Corporate Environmental, Health, and Safety (EHS) guidelines. In addition, designs shall comply with all environmental permits, utility agreements and local/state ordinances that apply to a specific project. 2) Company’s Loss Prevention Insurer, FM Global, should review all design development starting from Programming, in order to avoid potential change orders at IFC.
C. Means of Egress
1) Every building or usable portion thereof shall have at least one exit, not less than two exits in manufacturing and office areas where the number of occupants is at least 30. The maximum number of exits required for any story of a building shall be determined using the occupant load of that story according to the International Building Code. In addition: a. Every story or portion thereof having an occupant load of 501 to 1,000 shall not have less than three exits. b. Every story or portion thereof having an occupant load of 1,001 or more shall not have less than four exits. c. The width of exits in inches (mm) for any component in the means of egress system shall not be less than the total occupant load served by an exit multiplied by 0.3 (7.62) for stairways and 0.2 (5.08) for other exits nor less than specified elsewhere in IBC. Such widths of exits shall be divided approximately equally among the separate exits. d. The maximum travel distance shall not exceed 200 feet (60,960 mm). The maximum travel distance may be increased accordingly: e. In a building with an automatic sprinkler system throughout, the maximum travel distance may be 250feet (76,200 mm). f. The maximum travel distance of 200 feet (60,960 mm) and the maximum travel distance of 250feet (76,200 mm) allowed by item 1 may be increased up to an additional 100 feet (30,480 mm) when this increase in travel distance occurs in the last portion of the travel distance and is entirely within a one-hour fireresistive corridor. 2) When corridors are necessary to meet the exit travel distance, they shall be designed to the requirements listed below: a. Walls of corridors shall be of not less than one-hour fire-resistive construction and the ceilings shall not be less than that required for a one-hour fire-resistive floor or roof system. b. The minimum corridor width shall not be less than 44 inches (1118 mm). c. Where two or more exit-access doorways are required from any level or portion of a building, at least two of the exits or exit access doorways shall be placed a distance apart equal to not less than one half of the length of the maximum overall diagonal dimension of the area served measured in a straight-line between the center of such exits or exit-access doorways. Additional exits shall be
Page 2 of 24 Office Design Criteria
d.
e. f.
g. h.
arranged a reasonable distance apart so that if one becomes blocked, the others shall be available. Where more than one exit or exit-access doorway is required, the exit access shall be arranged such that there are no dead ends in hallways and corridors more than 20 feet (6096 mm) in length. Exit signs shall be readily visible from any direction of approach. No point shall be more than 100 feet (30,480 mm) from the nearest visible sign. Signs shall be illuminated at all times. In case of primary power failure, the exit signs shall be connected to an emergency electrical system to continue illumination for a duration of not less than 11/2 hours. Approved self-luminous signs meet this requirement if approved by the authority having jurisdiction. Exit doors shall swing in the direction of travel where the area served has an occupant load of 50 or more. Exit doors shall open from the inside without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, bolted, barred, latched or otherwise rendered unusable
D. Glazing
1) Safety glazing shall be used in subject to human impact. These include: 2) Glazing in ingress and egress doors. 3) Glazing in fixed and sliding panels of sliding door assemblies and panels in swinging doors. 4) Glazing in fixed or operable panels adjacent to a door where the nearest exposed edge for the glazing is within a 24-inch (610 mm) arc of either vertical edge of the door in a closed position and where the bottom exposed edge of the glazing is less than 60 inches (1525 mm) above the walking surface. 5) Glazing in an individual fixed or operable panel, other than described in Paragraph 3) above, that meets all of the following conditions: 6) Exposed area of an individual pane greater than 9 square feet m2). 7) Exposed bottom edge less than 18 inches (457 mm) above the floor. 8) Exposed top edge greater than 36 inches (914 mm) above the floor. 9) One or more walking surfaces within 36 inches (914 mm) horizontally of the plane of the glazing.
E. Fire Suppression Systems
1) An isolation valve for the Fire Sprinkler System, protecting the Computer/Data Processing/Server Rooms, shall be provided. The valve shall be supervised and connected to the Life Safety and/or the fire alarm system, depending on the system installed at the site. 2) A separate Isolation valve location for Water Flow sensors shall be connected to the Computer/Data Processing/Server/Telecom Rooms. 3) All fire sprinkler heads located within any Computer/Data Processing/ Server/Telecom Rooms and FMS shall be either recessed or guarded type. 4) If a raised floor is installed in any Computer/Data/Processing/Server Rooms and the finish floor height exceeds 6” inches, an automatic fire suppression system may be required to be installed under the raised floor in accordance with NFPA 13 and/or your local jurisdiction requirements.(depending on combustible material beneath RAF) 5) Automated Information Storage Systems (AISS) shall be protected with an automatic fire suppression system located inside the AISS unit. All AISS shall also be provided with the required early warning smoke detection system. 6) Gaseous Suppression Systems
Page 3 of 24 Office Design Criteria
a. Halon 1301 (TOTAL FLOODING SYSTEMS) shall no longer be used throughout Company A Corporation. b. FM200 is the preferred agent for sub-floor protection in Computer/Data Processing Rooms, Server Rooms, Fms And Telephone Communication Rooms, with a raised floor greater than 6 inches with combustible loading, or, as directed by the AHJ. 7) Detection Systems a. Detection Systems shall be installed to provide early warning of smoke/fire. The equipment used shall be a listed OASSDS smoke-detection type system and shall be installed and maintained in accordance with NFPA 72 and NFPA 75 Standards. b. Ionization/Photoelectric smoke detectors shall be installed in accordance with NFPA Standards and/or with the approval of the local authority having jurisdiction. 8) An Emergency Machine Off (EMO) Button shall be located at all exit locations, leading outside the immediate area of the Computer/Data Processing/Server Rooms. These EMOs shall isolate electrical power to all electronic systems in the room. 9) Portable Fire Extinguishers ******************************************************************* Editor: Some jurisdictions require fire hoses on reels in service areas in lieu of fire extinguishers. You need to use only one of these two options below. ******************************************************************** a. Fire hoses on reels. b. Fire extinguishers. !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!! c. Halon 1211 portable fire extinguishers shall no longer be purchased throughout Company A. d. Listed FE-36 portable fire extinguishers shall be provided inside the Computer/Data Processing/Server Rooms. Additional FE-36 extinguishers shall be placed outside the emergency exit doors leading out of these types of rooms. e. Fire extinguishers used to meet general building requirements within ordinary hazard occupancies where potential corrosion and/or contamination by the extinguishing agent is not a factor shall be the dry chemical multipurpose type. The agent shall be a monoammonium phosphate based agent and the extinguisher shall have a minimum rating of 4-A:20-B:C, minimum 10 lbs (4.54 kg). Travel distance for fire extinguishers shall not exceed 75 ft (22.88 m). f. FE-36 Fire extinguishers used to meet general building requirements with ordinary hazard occupancies where there is a corrosion and/or contamination potential from the extinguishing agent residue shall be FE-36 (a hydrofluorocarbon, 1,1,1,3,3,3 Hexafluoropropane). FE-36 fire extinguishers shall have a minimum fire rating of 2-A:10-B:C, and should be a minimum of 14 lbs (6.37 kg). Travel distance shall not exceed 50 ft (15.25 M). g. For some sites outside of the United States, FE-36 may not be available. The recommended agent in lieu of FE-36 is CO2 or carbon dioxide for ordinary hazard occupancies where there is a corrosion and/or contamination potential from the extinguishing agent residue. The CO2 fire extinguishers shall have a minimum rating of 10:B:C, and should be a minimum of 10 lbs (4.55 kg). Travel distance for fire extinguishers shall not exceed 30 ft. h. Note: CO2 extinguishing agent does not carry an A rating and is not acceptable for fires involving ordinary combustible materials. In areas or occupancies listed above where a safety hazard exposure from using a pressurized water fire
Page 4 of 24 Office Design Criteria
i.
j.
extinguisher on an electrical fire exists, the local AHJ or Authority Having Jurisdiction should be contacted to investigate a waiver for providing an A rating, based on the safety hazard exposure. If an A rating is required, pressurized water extinguishers should be used and should have a minimum 4:A rating and be a minimum of 10 lbs (4.55 kg). Travel distances shall not exceed 50 ft. (12.25 M). Extinguishers provided for the protection of cooking grease fires shall be only of the sodium bicarbonate or potassium bicarbonate dry chemical type. Extinguishers shall be rated for 40-B with a maximum travel distance of 30 ft (9.15 m). At a minimum, Computer/Data Processing/Tape Storage Rooms shall be encased in a 1 hour Fire Wall. In addition, all required fire assemblies doors/dampers shall be properly rated requirements to preserve the integrity of the rated fire division at all times.
F. Outside Transformers
1) Buildings or equipment exposed by liquid-filled (mineral oil and/or less flammable type oil) transformers shall be protected by separation or a fire barrier. 2) A containment system shall be provided for liquid filled (mineral oil and/or less flammable type oil) transformers of 500 gallons (1.9 cu m) or less where release of liquid would expose buildings or equipment. 3) A containment system shall be provided or all liquid filled (mineral oil and/or less flammable type oil) transformers containing more than 500 gallons (1.9 cu m) of liquid. 4) Transformer Rooms a. In rooms containing mineral oil insulated transformers the room shall have a fire resistance rating of 1 hour and automatic sprinkler protection shall be provided. Smoke detection shall be provided, arranged to alarm at a constantly attended location.
4. Baseline Office Building
1) The following is an example of a baseline office building for reference. Building size is project specific. 2) Baseline building area will include ground floor plus three upper floors for a nominal gross area of 10,000sq m (100,000sf). 3) Campus personnel traffic shall not be interspersed with vehicular traffic flow and freight traffic. 4) Gross Construction Area: The total Gross Construction Area of the building is assumed to be 10,000 sq.m., including any basement floor and technical premises, if applicable. During calculation of the gross construction area the measurements are taken from the external side of the exterior wall to the exterior side of the opposite external wall. 5) The number of floors and areas of floors will depend on local planning needs and site terrain. 6) Typical area use is defined as follows: a. Center core housing elevator shafts, conference rooms, service shafts, vending, electrical and IT rooms. b. Stairwells should be spaced per exiting distance and may not all be located in the building core area. c. Office: open area utilizing movable partition office kits. No enclosed offices are allowed. d. Special use rooms: cafeteria, fitness, training, multipurpose, large meeting rooms, copy centers, etc., specified by the project team.
Page 5 of 24 Office Design Criteria
e. Labs and data centers: secured spaces, typically hard walled, may have raised access floor; based on customer requirements. 7) Example of floor scheme and areas are approximated as follows: a. b. c. d. e. f. g. Technical basement floor: 600 sqm 1st floor (2 wings): 2,250 sqm 2nd floor (2 wings): 2,250 sqm 3rd floor (2 wings): 2,250 sqm 4th floor (2 wings): 2,250 sqm Technical floor (to be located by designer): 400 sqm Total Gross Construction Area: 10,000 sqm
5. Structural & Architectural
1) Structure may use cast in place concrete, pre-cast concrete, and or steel elements in the design. Slab surface to slab surface height will be the most efficient clearance necessary to provide clear room height of a minimum typical 2.70 meters in the office areas. Designer shall provide adequate utility plenum above finished ceiling to support conversion of office areas to dry labs. 2) Requirement for structural slabs (Uniformly distributed load, including partitions, Equipment, furniture and live loads) will be 400 kg/m2 (82lbs/sf) for Office Areas. (Computer areas, libraries (book loads), some Labs are designed at a higher design loads. Computer room live load to be 730kg/m2 (150lbs/sf)) 3) External walls shall meet local design requirements based on material availability. The building design will be in accordance with the stricter of the local regulations/codes and National Fire Protection Association (NFPA), International Building Code (IBC), and International Fire Code (IFC). Fire rated assemblies must meet or be equivalent to Factory Mutual Standards. 4) External walls shall meet local design requirements based on material availability. 5) Interior wall surfaces of the building shall be painted. Rock-wool shall be used for heat insulation. Reinforced glass cladding may be used in interior surfaces. Exterior walls with vapor barriers may be required in high humidity geographies. 6) External windows and doors shall be aluminum with sufficient insulated glass as per heat and sound conductivity calculations. Glass shall be reflective, tempered, tinted and low-E rating. External doors shall be aluminum and/or steel and insulated at non critical exterior doors. 7) Office floors shall be covered with fire retarding, rubber backed carpet tiles. Carpet tiles shall be 500 x 500 mm nominal size, minimum 950gms/m2 and treated with an anti-static application. Carpet tiles have a higher wear life, ease of maintenance/replacement, and better walking feel than basic broadloom carpeting. 8) Walls shall be painted with off-white emulsion paint. 9) The office areas are to be open space type. However in accordance with the Customer’s partitioning layouts, gypsum board partitions (12,5mm + 75mm + 12,5mm) may be used which must comply with relevant sound and fire resistance rating requirements. 10) Office areas shall use non-combustible acoustical flush ceiling tiles mounted in a modular grid system. Ceiling heights in typical open office areas are 2.70m. 11) Laminated or tempered safety glass to be used in areas where there is a potential for personnel to accidentally impact the surface. 12) Service areas, such as toilets, kitchen and kitchenettes shall have water resistant floor and walls with a rubber base, or equivalent that are easily cleanable.
Page 6 of 24 Office Design Criteria
13) Food preparation area ceilings will be metal suspended with drop in ceiling panels. High moisture areas must have a water resistant finish, or some other non-absorbent finish on the face of the tile. 14) Flat roofs shall be insulated and leak-proof and will be furnished with a 20 year warranty. Roof installation systems must meet FM approval or equivalent. Factory painted galvanized steel sheets will be used on inclined roofs. 15) Technical support areas shall have a multi-layer epoxy painted floor. Walls and ceilings will be acrylic painted. Concrete sealer may be used in areas that do not need a finish, like loading docks. 16) Fire escape stairs and landings shall have a hard high wear non-skid surface. Fire escapes shall be fire rated to a minimum of 2 hours. Walls and ceilings shall be water emulsion painted. 17) Main office doors shall be wood veneered or tempered glass doors. Other fire rated doors shall be steel. 18) Conference Room types and configurations: a. Type A: Size 3.7mx3.7m, 6-8 people b. Type B: Size 3.7mx7.3m, 14 people c. Type C: Size 7.3mx7.3m, 18-24 people 19) Conference Room quantities to be established with a total capacity of seating corresponding to approximately 6% of the total floor area. Conference rooms to be distributed in types A, B & C in accordance with the following general requirements: a. Type A- 1.1% of floor area/13.7m2 per room b. Type B- 3.45% of floor area/27m2 per room c. Type C- 1.45% of floor area/53.3m2 per room d. Large Meeting Rooms: per customer requirements 50-400 people 20) Conference Room construction: a. Typical wall construction extends to the deck and is sound insulated. b. Floors, walls and ceilings to be prepared for IT equipment as specified in this document. (see IT section) c. Acoustical criteria: i. STC: 50 ii. NC: see Mechanical section 5A (14) NC Table d. Acoustical wall treatment: for voice quality during conferencing i. Auditorium and large meeting rooms, place on 3 walls ii. Conference rooms, place on 2 adjacent walls. iii. Material performance: The acoustical material substrate should have an absorption coefficient of .8 at the 2 kHz octave band. (Typical materials meeting this specification are 1” thick fiberglass batts of insulation, or 1” thick foam sheets.) The cloth covering the wall treatment material should be acoustically transparent, or as close to as reasonably possible. 21) External grounds shall be landscaped to suit local environment. 22) Berms may be required to secure the perimeter of the site. Corporate Security representative will perform a site evaluation. 23) Traffic lanes should be separated for vehicles, bicyclists and pedestrians and be unidirectional and with clear markings. Areas should be asphalt pavement or concrete. 24) Clear directional signage as well as Company A signs to be provided.
Page 7 of 24 Office Design Criteria
6. Mechanical A. HVAC (Heating, Ventilation, and Air Conditioning) General Requirements
1) The Contractor shall carry out a design study, which shall assess the proposed system designs in compliance with and the below requirements for each area. These studies shall be submitted to Company A for review/approval. 2) The design parameters listed in this section are based on the net office area which is equal to 90% of the usable building area. 3) Heating or cooling, when required for the local conditions, shall be thermostatically controlled with zoned systems. a. Enclosed rooms such as conference rooms shall be zoned separately from adjacent open office areas. b. Use variable air volume (VAV) systems for all offices, conference rooms, labs and cafeterias. Use constant air volume (CAV) systems in all areas where constant air flow and exhaust are required. c. IT (computer/data center/server) rooms and (BCR/SCR rooms) cooling shall utilize a dedicated zone air conditioning system with appropriate backup systems. 4) Design per latest ASHRAE Handbook of Fundamentals. 5) Consider all job site related conditions such as elevation relative to sea level, freezing conditions, seismic zones, wind loading, and local utilities. 6) Design per outdoor summer and winter design conditions conforming to the 0.4%/99.6% ASHRAE values. (VE possibility: analyze cost associated with using less conservative parameters, i.e., 98%-2%) 7) Fresh air and outside ventilation to be furnished per ASHRAE Standard 62 and as follows: a. Fresh air for offices : 34 m3/person/hour b. Fresh air for meeting rooms: 34 m3/person/hour c. Regardless of the above, a minimum addition of outdoor air of 10 l/s(21 cfm) per person will be delivered, except outdoor air for cafeteria and auditorium is 3.5l/s(7.6cfm) per person and 2.55l/s(5.4cfm) per person, respectively. 8) Specific exhaust fans shall be installed to exhaust air from the offices, designated smoking areas, toilets, kitchenettes and other premises wherever required. Separate exhaust fans shall service the toilets and kitchenettes. 9) If required, Scrubbed Exhaust system will be installed to remove process corrosives from the air stream prior to being discharged to the environment. 10) Exhaust stacks will be located to avoid entrainment of exhaust fumes into make-up air or outside air intakes. 11) General Temperature Standard: a. Offices: 73 deg+/-5 deg. F ;( different temp for summer and winter can be considered for energy saving) b. Labs: Per Tool requirements or Environmental Matrices developed during building programming 12) Relative humidity: 50% +/- 20%. a. De-humidifiers: considered non-standard and must be identified as scope over base, when required. b. Humidification: considered non-standard and must be identified as scope over base, when required. 13) Satellite communication rooms (SCR) shall be equipped with a building ventilation system that will provide a positive pressure for the room as well as the heating and cooling required.
Page 8 of 24 Office Design Criteria
Additional cooling from ACU’s in some SCR’s maybe required to keep the room within the required temperature specifications. 14) Typical Noise level: Room Function Recommended NC Range Cleanrooms 55-60 Computer Rooms 45-55 Light maintenance shops 45-55 Shop Classrooms 40-50 Corridors and public circulation areas 40-50 Laboratories with fume hoods 40-50 Large offices 35-45 Open-plan offices 35-40 Lab support spaces 30-40 Private offices 30-40 General classrooms 30-40 Libraries 30-40 Executive offices 25-35 Large lecture rooms 25-30 Conference rooms 25-30 Auditoria 25-30 (a) External Noise levels should be per the specific site requirements. (b) Noise level in offices 45 dB (A) 15) Basis for Internal heat gains: i. Lighting: 19 W/m2 ii. Equipment: 19 W/m2 iii. People: 15-18 W/m2 a) Office Density: i) America & EMEAR: one person per 10 m2 of net office area ii) Asia: one person per 5.6m2 of net office area b) Conference Room Density: One person per 3 m2 Meeting and lecture rooms must be dimensioned with a person load of 1.5 m2/person c) Building is occupied 24 hours per day - 7 days per week. The following data shall be used as a supplement to the Room Data Matrix. i) Persons: 100 W/person ii) Computers: 1.2 computers are expected per person (one computer corresponding to 200 W) 240 W/person 16) Internal Heat Gain Table: Building Space Designation Typical Heat Load (need Comments to verify during design)
General Offices Labs (Light) Labs (Heavy) Computer Rooms BCR/SCR Rooms 38 Watts/m2 86 to 161 Watts/m2 161 to 430 Watts/ m2 430 to 1076 Watts/m2 377 Watts/m2
Page 9 of 24 Office Design Criteria
i.
Coordinate With Lab Owners Coordinate With Lab Owners Coordinate With System Owner
Building Space Designation
Corridors, Walkways, Lobbies, Etc. Mechanical/Electrical Rooms Copy Rooms
Typical Heat Load (need to verify during design)
None Per Equipment Mfg. Specifications 43 Watts/m2
Comments
Check Equipment Submittals
B. Chilled Water System
1) Chilled water may be provided for all cooling loads in Makeup Air Handlers, General Purpose Air Handlers, and Computer Room Air Handlers. a. Provide closed loop process cooling water (PCW) for dedicated computer room equipment or special use equipment whose cooling system could be fouled if tied into the building chilled water system. 2) Design the chiller plant with N+1 redundancy if total system design load exceeds 600 tons cooling. 3) Piping Material Schedule:
Service/ Pipe Sizes Chilled Water Supply and Return/ Greater Than or Equal To 26 Inch Diameter Chilled Water Supply and Return/ Greater Than 2 Inch, Less Than 26 Inch Diameter Chilled Water Supply and Return 2 Inch Diameter and Less Line Spec./Spec. Section ADA/40_05_16_51(15181) Material API-5L, Carbon Steel, Welded Mechanical Couplings Not Allowed A-53B, Carbon Steel, Welded Mechanical Couplings Not Allowed Type L Copper, Brazed Joints, 95-5 Antimony, or Carbon Steel If Less Expensive
ADA/40_05_16_51(15181)
ADB/40_05_16_51(15181) or 40_05_16_11(15141)
4) Pipe Sizing Criteria:
Pipe Size 20 Inches and Larger (SCHW Only) 14 Inches and Larger 3 ½ Inches - 12 Inches 1 ½ Inches - 3 Inches ½ Inch - 1 Inch Maximum Pressure Drop: 4 ft. head/ 100 ft. Maximum Allowable Velocity 10 fps 9 fps 7 fps 6 fps 5 fps Maximum Operating Pressure: 125 psig.
C. Oil Free Air System:
1) The OFA/Compressed Air System shall consist of the following components: a. Oil -free air compressor, b. Heatless or heated dryers, c. Air receiver, located between the compressor and dryer system, d. Filtered air intake,
Page 10 of 24 Office Design Criteria
e. Pressure Regulation System and Particulate filters, f. Copper or 304 SS (especially for pipe diameters larger than 4 inches) piping system to points of use. 2) The air intake filter should be sized for at least a 50% excess flow rate and should be in an easily accessible location for servicing. 3) As a minimum, equipment and piping shall be adequately seismically braced based on Seismic Design Standards for Non-Structural Components, IMDS 2141.
D. Plumbing
1) The plumbing system provides pressurized domestic hot and cold water. a. Domestic cold water: pressurized by a domestic cold-water pump. b. Domestic hot water: generated by domestic hot water pre-heating and re-heating heat exchangers utilizing high temperature hot water at 130F/70C. 2) Water Quality specification-check with world health org. 3) As a minimum, equipment and piping shall be adequately seismically braced based on Seismic Design Standards for Non-Structural Components, IMDS 2141.
E. Lifts
1) Automatic, multi-functions lifts shall be provided for multi-story buildings. 2) A minimum of two passenger lifts with separate access, each 1,250 kg shall serve the office floors. 3) Lift engine room will be located above the top floor. 4) Lifts should be traction type, and not hydraulic if possible. Hydraulic is very slow, and higher maintenance. 5) Buildings that are furnished with loading docks should evaluate installing a separate freight elevator to handle received materials. 6) Maintenance equipment access to the roof should be evaluated based on the campus. Various methods of raising equipment to the roof include: a. service crane, b. permanent skip hoist from top floor to roof, or c. freight elevator access to roof. Project/Site Services shall make this decision.
7. Electrical A. General:
1) Use this guideline in conjunction with:a. Company A’s Master Construction Specifications, Division 13 & 16 for US (NEMA) related 60 Hz projects. b. Company A’s Master Construction Specifications, Division 13 & 16 with suffix “(European)” for International (IEC) related 50Hz projects. c. Electrical Standards or equivalent:i. All applicable and current UL and NEC Standards and Codes. ii. All applicable and current IEC Standards and Codes iii. All applicable and current EC Directives iv. All applicable and current local Standards and Codes.
B. Incoming Power Supply
1) The main incoming power supply switchgear, complete with Utility tariff metering shall be either supplied by the Utility company or supplied by the Contractor.
Page 11 of 24 Office Design Criteria
2) The contractor shall design, supply and install all cables, transformers etc. necessary for the complete electrical supply to the campus. 3) Power supply shall be executed as per technical conditions of Power Authorities. 4) Operation voltage supplied from the low voltage main distribution boards shall be 380/220 volt AC, 50 Hz or as generally supplied by the local power authority. 5) Buildings that support critical functions, e.g., manufacturing and data centers will require additional features such as dual feed, redundancy, etc.
C. Medium Voltage (MV) or Low Voltage (LV) Utility Power Supply
1) The building shall be supplied from a local MV or LV power source with a dual redundant main supply. 2) Whether at MV or LV, shall be determined by the building function, the total kVA load and from discussions with the Utility supplier. 3) Transformer(s), where they are to be of a MV to LV rating, shall be as per local standards (for example 12.47kV/480V or 11kV/400V or other voltage ratings) 4) Internal power distribution will be calculated on the basis of 75 VA/m2 for useable office area with 10% spare capacity for expansion at the floor distribution panel. 5) The low voltage main switchgear shall be double-ended. 6) Low voltage main distribution boards shall be equipped with thermal and magnetic circuit breakers, voltmeters, amp meters, voltmeter selector switches, signal lamps and kW-h meter, voltage and current rate, circuit breakers status and fault signals of the main distribution board and will be monitored from the Building Management Computer, within the Facilities Maintenance Room. No control functions will be required.
D. Normal Power Distribution System
1) The Normal Power Distribution System consists of all low voltage gear including incoming supply switchgear if applicable, distribution and sub distribution switchgear, meters, UPS´s, generator set(s), motor control centers (MCC’s), distribution panels & branch circuit panel boards etc. 2) The total required power supply shall be calculated as per Table E001 below. A minimum of 25% spare capacity shall be available from the MV or LV incoming supply right down though the whole distribution chain. a. TABLE E001
Area Computer Room Command Centre Office Areas Conference, Customer, Show rooms Engineering labs Mech./Elec. support areas CCR/BCR/SCR rooms Usability lab Other (lobby, dock, restrooms, etc) Mechanical equipment Lighting (300 lux avg.) Watts / sqm. 1183 70 55 45 225 30 225 45 15 Included Above Included Above
Page 12 of 24 Office Design Criteria
Note: The figures in Table E001 above are estimates (Final details to be part of design development). 3) The switchboard shall be constructed to a minimum of IP31 (or equivalent NEMA rating), Form 3 or 4 and be of a withdrawable circuit breaker design for all incomers, bus-couplers and feeders. If the design requires a MV/LV unit substation, then the transformers shall form an integral part of the unit substation and be either singleended (for radial supply) or double-ended (for dual supply) depending on the building function. 4) The main switchboard shall be supplied with transient protection on each incomer (TVSS). 5) The incoming circuit-breaker shall be either a Four (for double-ended unit substation or switchboard) or three (for single-ended unit substation or switchboard) pole air circuit breaker (ACB). An integral current transformer driven, three phase, neutral and earth, solid state protective relay shall be provided. The ACB shall have the neutral pole and the associated electronic protection relay rated for 100% of the phase poles. 6) Provide Power Factor Correction and/or Harmonic filtering as deemed necessary to comply with local Utility requirements. 7) Feeder circuits shall be protected by MCCB’s (Molded Case Circuit Breaker) complete with short circuit and over current protection. 8) In general, unless otherwise required by local codes and regulations, the Normal Power Distribution system between Main LV Switchboard and Panel boards shall be carried out as a TN-S system. 9) No liquid-carrying pipe work shall pass through the electrical switch rooms or cupboards with the sole exception of any proposed sprinkler system. 10) Panel boards consisting of lockable fixed MCCB’s shall be located within the electrical cupboards/SCR rooms on each floor of the facility and be wired from the Main LV switchboard. Circuits to be allocated only for equipment on the same floor as the panel board. Panel boards shall comply with Form 2 and IP54 construction. 11) Branch circuit panel boards consisting of lockable miniature circuit breakers (MCB‘s) and residual current devices (RCD‘s) shall be located within the electrical cupboards on each floor of the facility. a. Separate panel boards shall be used for lighting and general service socket/receptacles. b. Dedicated panel boards shall be used for SCR’s and not shared by other services. c. Branch panel boards shall comply with Form 2, with IP54 (enclosure) and IP21 (internal components) construction. 12) Kitchen and servery areas shall be supplied from a dedicated panel board within the kitchen area c/w Emergency Stop facility and be interlocked to the kitchen fire suppression system. 13) MCC’s (Motor Control Centers) shall be complete with fixed fully fitted compartments. MCC‘s shall comply with Form 2 or 3 and IP54 construction. 14) The Contractor shall provide a containment system for all cabling. Where required, the containment system for power multicore/MC cables shall be cable basket, cable tray and/or cable ladders. All shall be sized for present needs plus 33% future growth. 15) Fire alarms, BMS (Building Management System), telecoms, security, and data shall be distributed through separate wire ways from either other and from power cables. 16) All wiring accessories such as sockets/receptacle outlets, lighting luminaries and lighting switches may be locally manufactured. 17) Socket/receptacle and data/voice cabling to workstations in open plan offices, where no raised floor is used, shall be carried out using power poles dropped from the false ceiling to the floor.
i)
Page 13 of 24 Office Design Criteria
18) Each office workstation will require four socket/receptacle outlets and five voice/data cables (see IT Section). 19) The design basis for computer circuits is three (3) general workstations per MCB with an RCD or as required by local codes. For general service socket/receptacle circuits it shall be five (5) per MCB with an RCD or as required by local codes. 20) Office furniture will come complete with four socket/receptacle outlets (local pin configuration) and four voice/data outlets (see Telecommunications Systems section) per workstation. 21) Conference rooms shall be equipped with one socket/receptacle outlet and one Voice/data outlet per three table seats, unless indicated otherwise on the room data matrix. 22) Conference room tables shall be equipped with six power/data service points, evenly spaced around the table. Each service point shall be equipped with one socket/receptacle outlet and one data outlet, unless indicated otherwise on the room data matrix. 23) Computer rooms shall be equipped for network servers, computer banks and have their own dedicated CPS (Emergency generator backed UPS) panel boards. 24) Ground (earth) fault protection shall be designed for main switchboard breakers, main feeder breakers and where required to comply with local codes, on the low voltage network. The maximum earth resistance shall be = 1 ohm. In general, breaker phase protection shall include long time and short time trip functions only. 25) Lighting system shall provide general illumination to comply with Table E002 as well as 100lux into the equipment compartments when opened. Lighting is to be provided at two separate levels for each room. One set of lights at the high open ceiling structure for general room lighting (400-500lux). Another set of task lighting located at or near the top of the equipment racks, and centered over the isles for working on equipment in the racks. (800lux) 26) Electrical equipment shall have adequate clearances for maintenance and other local electrical code requirements. 27) Provisions for future equipment shall be shown on plans and code review documents. 28) Equipment, cable trays, etc where required shall be adequately seismic braced based on the stricter of the local requirements or Seismic Design Standards for NonStructural Components, IMDS 2141.
E. Emergency Power Distribution System
1) The Contractor shall include for a diesel engine emergency generator and emergency power distribution system, to provide backup power to the IT room, HVAC, and lighting systems as well as providing backup power to the UPS (normally known as CPS). 2) The rating should be subject to final design calculations with a fuel oil capacity of 8 hours minimum running time @ 100% load. 3) The generator shall be a self-contained unit either installed indoors or in an outdoor acoustically attenuated container to meet the local noise limits. The design shall be based on automatic transfer upon failure of the utility supply. There is no requirement for co-generation/close transition between utility power and emergency power or generator redundancy. 4) The generator shall supply power to the downstream emergency power ATS (Automatic Transfer Switch) switchboard, which also has a normal power supply. After completion of a load study, including Company A defined critical loads, the Contractor shall recommend a generator kVA rating to Company A. 5) The following critical operations shall be on emergency power:
Page 14 of 24 Office Design Criteria
a. b. c. d. e. f. g.
UPS HVAC for UPS room HVAC for IT room(s) Emergency Lighting Life Safety and Security systems BMS (Building Management System) Lift/Elevator
F. Continuous Power Supply (CPS)
1) The CPS system consists of: a. A static UPS system: the UPS shall be a either an isolated or parallel redundant type with external maintenance bypass switch. The UPS shall be supplied from the upstream emergency power ATS (Automatic Transfer Switch) switchboard. Contractor to recommend a UPS KVA rating to Company A, after completion of a load study and consultation with Company A as what should be included in a critical list. b. Emergency power back up, c. Service computer socket outlets in the IT rooms only. d. A CPS distribution system: shall be of a dual supply design from the output of the UPS, installed comprising dual panel boards feeding a number of sockets and lighting fittings within the IT rooms. i. Two panel boards shall be located in each computer room to enable a dual power supply to each rack/server to be achieved. 2) The rating should be subject to final design calculations, with autonomy duration of 5 minutes minimum for 100% load, utilizing wet batteries located in a separate battery room or VRLA batteries within the UPS itself. 3) Special considerations: Earthing and 200% Neutral’s to server loads. 4) Dual power supplies shall be routed separately from each other for as far as possible so a fault in one cannot affect the other. 5) There shall be an emergency power supply equipment with automatic changeover switches in order to provide power to code required systems in addition to the below listed Category I consumers, i.e., Enterprise Data Center, IMDS 2002-403. Category I Data Center holds all Tier I applications, DMZ consolidation location. 6) In addition to the above mentioned power supply, the following most important consumers will be fed by a UPS back-up system: a. Security system including CCTV, intruder alarm and card readers, b. Fire announcement system, c. Lift dispatching system, d. Building automation computer, e. Fire alarm system, f. Critical task lighting specified for above items. 7) UPS status and alarms will be connected to the building automation system.
G. Interior and External Lighting
1) The supply and installation of the complete lighting system as follows: a. Enclosed rooms shall utilize motion detection switches to control lighting and turn off lights when rooms are unoccupied. b. The light distribution system shall be zoned in large areas and controlled manually and automatically as part of the building management system.
Page 15 of 24 Office Design Criteria
2) 3)
4) 5) 6)
c. Light fittings with high efficiency should be used, and Company A desires to have influence on the final choice of light fittings and the associated choice of light sources. d. All conference rooms shall be equipped with ultrasonic motion detectors for switching on and off general lighting when the room is occupied and unoccupied respectively. e. External lighting shall be controlled by time clocks and/or photocells, with manual over-ride facilities. f. Emergency lighting shall be as per local codes and regulations. Facade, working, evacuation and emergency lighting will be provided. Fluorescent high energy efficient lighting fixtures with suitable distribution curve will be used for offices, cultural and social premises, corridors, lobbies, and information and security areas. 5 Lux (min.) Emergency lighting shall be provided for all access/egress routes to exits. Exit signs shall either be externally or internally illuminated and placed per local code requirements. Interior and external light levels shall conform to local codes and regulations. Table E002 and Table E003 show details of suggested Company A minimum requirements respectively but are subject to clarification during design. i. TABLE E002
Room Name Laboratories Laboratories all (Env., IT, TE Test Repair, Usability, etc) Computer Rooms (Server space) Professional Services Room Office + Conference Rooms Office Areas Conference / Training Rooms Common Spaces Corridors/Aisles Food Preparation Kitchenettes Bathrooms Lobby Canteen Employee Locker Room Facility Support Spaces CCR/BCR/SCR for Offices Security Command Centre Hallway / Storage area Electrical Room Plant Room Battery UPS Room Cooling Plant roof area Lighting Levels (Lux) (or equivalent ft candles) 400-500 400-500 500 200-300 200-300 200 500 300 150 250 200 200 400-500 450-500 200 300 200 300 200
ii. TABLE E003
External areas Roof Parking lots/Car Parks Roadways Areas viewed by CCTV cameras Lighting Levels 50 Lux (entry onto roof) 20 Lux 5 Lux 20 Lux
Page 16 of 24 Office Design Criteria
H. Earthing (grounding) and Bonding system
1) All earthing shall be in accordance with the Utility supplier and local codes and regulations. 2) The following guidelines shall be followed for special area earthing: a. Raised Floor Computer Room: Provide a 50 mm2 bare copper earthing conductor in raised floor cavity of room on earthed floor, running around perimeter of room and bonded to column which is effectively bonded to underslab grid. Bond cable to raised floor pedestals at 1.8 metre intervals using suitable crossing clamps. b. Raised Floor Offices: Provide 6 mm2 conductor bonding of the raised floor system per 20 m2 raised floor. Bond cable shall be connected to the earthing busbar in the cupboard/SCR room servicing the area. Connecting of the conductor to the raised floor system shall be effectively bonded to the metal cover system. 3) The secondary side of transformers supplied and installed by the Contractor shall be bonded.
I. Lightning Protection
1) The Contractor shall provide a lightning protection system in accordance with local codes and regulations. The requirement shall be subject to a Risk Assessment study being carried out. If required the lightning system design shall be based on the Faraday Cage principle and installed by the Contractor or a licensed installer, whichever is applicable by local codes and regulations. 2) Lightning Protection shall be provided by Faraday’s cage system and shall be connected by vertical earthling bars to the earthing conductors at the lowest point of the building
J. ELF/EMI Protection
1) All Computer/Data Centre room raised floors shall be grounded (earthed) at points conforming to a grid pattern, and at intervals not exceeding 4 meters, in accordance with local codes and regulations. 2) Project to determine if building customers will utilize ELF/EMI sensitive equipment which may warrant special protection. This is a scope over base item.
K. Calculations
1) The Contractor shall supply at a minimum the following design calculations in electronic and hard copy format: a. Demand Load Study b. Voltage Drop/Load Flow Study c. Comprehensive Short Circuit Study d. Lighting Levels e. Co-ordination Study f. Recommendations shall include a table of settings and curves, which shall be computer, generated and clearly represent the system design selectivity. g. Harmonic Analysis and Power Factor Study
L. Electrical Distribution System
1) All metal trunking and cable trays and metal parts will be grounded. 2) Power distribution to the floors will be done by means of sub-panel boards (Floor panel boards) which are going to be placed at the vertical shafts and/or mechanical electrical rooms to be located at each floor.
Page 17 of 24 Office Design Criteria
3) Equipment, cable trays, etc shall be adequately seismic braced based on the stricter of the local requirements or Seismic Design Standards for Non-Structural Components, IMDS 2141. 4) Emergency and backup power systems shall be provided for critical systems.
8. Building Management System
1) The Building Management System shall monitor and/or control all technical building systems. Fire alarms, BMS (Building Management System), telecoms, security, and data shall be distributed through separate wire ways from either other and from power cables. 2) In order to control and monitor the operation of mechanical systems, such as ventilation, air conditioning, heating, etc., a direct digital control system shall be installed including computer and monitor. Automation system will consist of mainly a control equipment which is a computer and device communication protocol which controls thermo elements, pressure transducers, actuators, automatic valves etc. Wall thermostats are generally not utilized to control space temperature. 3) The Building management system will control the following according to the program prepared by mechanical system designers: a. b. c. d. Supply air temperature of the premises, Freezing control of heat coils of Air Handling Units Interlocks between supply and exhaust systems of air conditioned areas, Supply air system shall be interlocked to the fire detection system and shut down automatically on alarm. e. Buildings equipped with smoke exhaust systems shall also be interlocked to the fire alarm system and designed per the Company A Life Safety System requirements and local code. f. Pumps and Air Handling Units, g. Domestic water supply regulation and monitored. h. Domestic hot water systems regulation and monitored i. VAV boxes shall be monitored and controlled.
9. Sound System
1) One channel public address system, addressing common areas and evacuation routes and can be used for emergency announcements, otherwise serving as music system in common areas only, shall be installed. 2) Telecommunication System for global product suppliers, see Part 13 References.
10.Fire Protection A. General:
1) The building fire protection systems shall be designed in accordance with the following: a. NFPA 13, 30, and 318. b. Latest Uniform Fire Code. c. Factory Mutual (FM) Data Sheets and standards. d. Company A Risk Management Guidelines: Risk Management Design Criteria-O, IMDS 2112-O 2) All fire protection systems will be designated according to the applicable local Standards and comply with Factory Mutual standards.
Page 18 of 24 Office Design Criteria
3) Each office floor of the building will be fully equipped with individual sprinklers, fire hydrants and stand-alone fire extinguishers. Fire hoses will be connected to a fire standpipe of the internal fire fighting water supply system. 4) The Building will have a minimum of 2 separate fire zones consisting of basement technical floor and upper floors of the building. 5) Fresh air pressurization system will be designated for the elevator shafts, emergency escape staircases, elevator lobbies and wherever necessary, it means influent antismoke ventilation. (Verify with minimum requirements in FM and IBC.) 6) Fire alarm system shall communicate with the BMS and provide status and location of all Fire Notifier output signals.
B. Fire Alarm System (Analog Addressable)
1) Main control panels will be placed at the central control room. Fire alarm detectors (smoke, optical, heat raise type) local push buttons control and location monitoring modules will be provided as per design. The fire alarm system shall be adapted by the Contractor to comply with the partitioning plan of the building. 2) Equipment selection shall mesh with the following operating strategies: a. Standalone Building b. Standalone Campus Setting c. Site Campus Setting d. Leased Building e. The fire alarm system must be scalable, compatible, and integrate to other Company A buildings. Company A safety
11.IT
A. General IT Requirements 1) Design Requirements: a. IT/Telecommunications System - General (TC-Gen)-ALL BLDGS, IMDS 2001L, defines the design of the system. b. Network providing voice and data distribution within the building. c. Design must be done by a Registered Communication Distribution Designer (RCDD). The RCDD is an individual who through experience, study and effort has demonstrated the skills and professionalism in this area of specialized technology. The RCDD is certified through http://www.bicsi.com/ . The drawings must be designed and certified by the RCDD. 2) Installation Requirements a. Installation Requirements for the Company A Network, voice and data low voltage electrical system must be performed by individuals that are certified by the cable manufacturer to provide a warranted voice and data cabling system for the project. i. The Company A Approved Copper and Fiber cable manufacturers are listed in General Communications Requirements, IMCS 27_00_10_00(16701).
B. Data Center Classification Matrix
1) Data Center Classification Matrix, IMDS 2002-L, defines the type of Data Centers in the Company A Campus and Building network. Please confer with the Company A Point of Contact to clarify which type of Data Centers the project requires.
Data Center Types
Page 19 of 24 Office Design Criteria
Data Center Types High Performance Data Center, IMDS 2110404 Typical demand is >100W/sf <250gross area(Medium Density), 250W/sf gross area(High Density) Enterprise Data Center, IMDS 2110403 Holds all Tier I applications, Tier I DR. Can house general purpose applications where space available. DMZ consolidation location. Regional Data Center, IMDS 2110402 Holds general purpose applications requiring regional/global access. LHDR can be accommodated at other RDC or GPDC. General Purpose Data Center, IMDS 2110401 Holds general purpose applications requiring primarily site based access. LHDR can be accommodated at RDC or other GPDC. Small Site Data Center, IMDS 2110-401 Holds general purpose applications requiring primarily site based access. Shared DC and CCR/BCR for campus.
C.
Telecommunications Rooms
1) IT/Telecommunications Rooms, IMDS 2003-L, defines the design requirements. 2) Identify all telecommunication rooms included in project scope in the following table. 3) Please review the Area Data Sheets for specification on room adjacencies.
Communication Room Types (Master Document Reference) CCR - Campus BCR/ABCR-Building Communication Rooms. communication rooms. (2110-162) (2110-161)
SCR- Satellite Communication Room. (2110-160)
D. IT Telecommunications Cabling System
1) IT/Telecommunications Cabling System, IMDS 2010 -L, defines the design. 2) Above all, cable installation and management standards and practices must be strictly adhered to in all building environments. A conservative approach should be taken to all specifications. Refer to 2001 General IT requirements for Design and Installation requirements. 3) Environmental considerations: Special consideration must be given to communications equipment that can be either a source of or subject to the effects of Electromagnetic Interference (EMI). While UTP is a cost effective data communications medium, this cable is not immune from electromagnetic disturbances. 4) Other Company A References: a. 27_05_00_00(16126) – Common Work Results for Communications b. 27_05_28_36(16136) – Cable Trays for Communications Systems c. 27_05_43_37(16137) - Communications Handholes and Manholes d. 27_11_16_00(16138) - Communications Cabinets, Racks, Frames and Enclosures e. 27_13_02_00(16702) – Campus Distribution Subsystem f. 27_13_03_00(16703) – Vertical Distribution Subsystem g. 27_15_00_00(16704) - Communications Horizontal Cabling h. 27_16_19_00(16156) - Communications Patch Cords, Station Cords and Cross Connect Wires
Page 20 of 24 Office Design Criteria
E. IT Phone System
1) IT/Telecommunications Phone System, IMDS 2020-ABCDFOSWGWI 2) PBX Switch Processor, IMCS 27_31_13_21(16721).
F. IT Network
1) 2) 3) 4) 5) IT/Telecommunications Network System (TC-NET), IMDS 2030-ABCDFOSWGWI Local Area Network Equipment, IMCS 27_21_41_00(16741) Cable Transmission and Reception Equipment, IMCS 27_41_70_00(16770). Conference Rooms Refer to project team to identify quantity of conference rooms to design,
G. IT Audio Visual System
1) IT/Telecommunications Audio/Visual Systems (TC-AV), IMDS 2040ABCDFOSWGWI 2) Multi-Media Equipment, IMCS 27_41_80_00(16880).
H. IT Grounding
1) IT/Telecommunications Office Equipment System (TC-Off), IMDS 2060ABCDFOSWGWI. 2) Communications Grounding, IMCS 27_05_26_68(16068)
I. IT Labeling
1) Identification for Communications Systems, IMCS 27_05_53_00(16076).
12.Security A. Overview
1) This section addresses the minimum Security requirements for an Company A facility and the roles and responsibilities for the A&E, contractors and Company A personnel responsible during design and construction. Due to the nature of security at Company A and the expectations of the systems both at a site level and for enterprise wide functionality these minimum requirements must be followed. 2) All facilities shall complete a Risk and Threat Assessment by Corporate Security and the vulnerability mitigation recommendations shall be incorporated into the project scope. This should be completed during site selection. 3) The security systems and subordinate elements are to be installed in the first building on the campus. 4) Company A utilizes a globally integrated access control and CCTV system. These systems function together with enterprise databases and archive centers. See specification integration details. 5) Any entrance that allows access into the facility from public spaces shall comply with Facility Entry Control System, IMDS 1863-L. This includes: a. Un-staffed automated building entrances, b. Guard shack systems, c. Service yard entries, or d. Any other entry intended for personnel access.
Page 21 of 24 Office Design Criteria
B. Security Enterprise System includes the following systems:
1) The Enterprise System is a Company A proprietary software and database system which interfaces between other Company A databases and the local access control database. The Enterprise system is the parent database that holds and distributes worldwide badge holder records 2) The Badging Systems include workstations, badge-manufacturing equipment and video capture devices that locally capture badge holder information and stores that data in the corporate database. 3) The Employment Verification Tools includes a workstation & monitor link to the corporate database to verify badge holder identity and employee status. These devices shall be located at staffed entrances.
C. Video Systems:
1) The Digital video recording system –is a globally connected system that locally stores captured video and can archive specifically identified video segments to Company A’s Global Video Storage System. This system uses a dedicated Security LAN for interconnection and connectivity beyond the local facility. 2) The matrix switcher and analog camera elements interface with the access control system for camera positioning based on triggers generated by the access control system. Video is then stored on the digital video network.
D. Dedicated security LAN:
1) Used for isolating Security Systems from other systems. 2) Used by the Enterprise System to transport data between corporate databases and local security system servers. 3) To provide dedicated access control between general population and security personnel accessing the security network.
E. Building lock & key systems:
1) Controlled Doors & Padlock Systems 2) Furniture Control Systems-need info from Company A FOCUS group
F. Radio Systems: tbd G. Roles and Responsibilities
1) The following entities have responsibility to ensure that the Security System operates as intended: a. CCTV Integrator b. Security Integrator c. IT Integrator d. Owner furnished equipment 2) The aforementioned integrators are responsible to ensure that the CCTV, Security, and IT systems interface correctly with one another. 3) It is the responsibility of the Prime Contractor to ensure that each integrator scope of work is adequately defined and the interfaces are properly identified.
Page 22 of 24 Office Design Criteria
13.References A. Construction Specification
Section No. 27_00_10_00(16701) 27_05_00_00(16126) 27_05_26_68(16068) 27_05_53_00(16076) 27_05_28_36(16136) 27_05_43_37(16137) 27_11_16_00(16138) 27_16_19_00(16156) 27_13_02_00(16702) 27_13_03_00(16703) 27_15_00_00(16704) 27_31_13_21(16721) 27_21_41_00(16741) 27_41_70_00(16770) 27_41_80_00(16880) Section Title General Communications Requirements Common Work Results for Communications Communications Grounding Identification for Communications Systems Cable Trays for Communications Systems Communications Handholes and Manholes Communications Cabinets, Racks, Frames and Enclosures Communications Patch Cords, Station Cords and Cross Connect Wires Campus Distribution Subsystem Vertical Distribution Subsystem Communications Horizontal Cabling PBX Switch Processor Local Area Network (LAN) Systems CableTransmission And Reception Equipment Multimedia Equipment
B. Design Standards
System No.
1863-L 2001-L 2002-ABCDFSWGWI 2002-401 2002-402 2002-403 2002-404 2003-L 2010-ABCDFOSWGWI 2020-ABCDFOSWGWI 2030-ABCDFOSWGWI 2040-ABCDFOSWGWI 2060-ABCDFOSWGWI 2070-ABCDFOSWGWI 2110-110-O 2110-120-O 2110-122 2110-123-O 2110-124-O 2110-131-O 2110-132-O 2110-140-O 2110-150
System Title Facility Entry Control System IT/Telecommunications System - General (TC-Gen)-ALL BLDGS Data Center Classification Matrix General Purpose Data Center (Document to be developed) Regional Data Center (Document to be developed) Enterprise Data Center (Document to be developed) High Performance Data Center (Document to be developed) IT/Telecommunications Rooms IT/Telecommunications Cabling System IT/Telecommunications Phone System IT/Telecommunications Network System (TC-NET) IT/Telecommunications Audio/Visual Systems (TC-AV) IT/Telecommunications Office Equipment System (TC-Off) IT/Telecommunications Grounding (TGND) Design Criteria - Duct Shafts Lab, Computer Electrical Room Satellite, Electrical Rooms Main Electrical Room Main Electrical Room Elevator Equipment Rooms Equipment Penthouse Exterior Walls Facility Shop
Page 23 of 24
Office Design Criteria
System No.
2110-160-L 2110-161(suggest L) 2110-162 (suggest L) 2110-201-O 2110-220-O 2110-221-O 2110-301-O 2110-310-O 2110-340-O 2110-341-O 2110-342-O 2110-343-O 2110-344-O 2110-351-O 2110-352-O 2110-354-O 2110-362-O 2110-363-O 2110-363-O_2 2110-370-O 2110-371-O 2110-401-ABCDFOS, WG 2110-402 (suggest L) 2110-403 2110-404 2110-410-O 2110-411-O 2110-430-O 2110-432-O 2112-O 2140 2141
System Title Satellite Communication Room (SCR) BCR/ABCR – Building Communications Rooms (Document to be developed) Campus Communication Room (CCR) Elevator & Elevator Vestibule BUM-Break Room Kitchen & Servery Auditorium BUM A Conference Room B Conference Room Conference Room C C Conference Media Room (EOC) Design Criteria - NEO Training Room Design Criteria - Mail-Copy Room Design Criteria - Site Mail Center Design Criteria - Plotter Room Library Library/Learning Center Library, ELC-MSB PC Training Room EOC in Training Room General Purpose Data Center (GPDC) Regional/Manufacturing Computing Data Center (R/MC DC) Enterprise Data Center (EDC)-ABCDFOS, WG High Performance Data Center(HPDC) (Document to be developed) Dining Patio Dining Electronics Lab Chemical Labs Risk Management Design Criteria-O Seismic Design Standards for Buildings Seismic Design Standards for Non-Structural Components
End of Standard
Page 24 of 24 Office Design Criteria