MOTOR STARTING REACTORS

Document Sample
MOTOR STARTING REACTORS Powered By Docstoc
					                                                                                                              Türkçe




                                       HOME       ABOUT US       CONTACT US         CAREERS        SITE MAP

POWER RESISTORS

Neutral Grounding Resistors
Generator Neutral Grounding &
Leads Cubicles
                                                             MOTOR STARTING REACTORS
Inverter Braking Resistors
Motor Starting &
Control Resistors
Cubicle Heaters
Harmonic Filter Resistors          Motor starting reactors are used for starting
Current Limiting Resistors         large 3 phase motors while limiting inrush
RC Filters                         currents. Large motors generally use 6 times
                                   more current than their nominal current.
                                   Normally, they are started with 70 % of
REACTORS                           voltage and the rest of the voltage, that is
                                   normally about 30 %, is dropped across the
Current Limiting Reactors          motor starting reactor. After 15 - 20
Neutral Grounding Reactors         seconds, the reactor is switched off with
Shunt Reactors                     contactors in the system.
Harmonic Filtering Reactors
Motor Starting Reactors
Electric Arc Furnace Reactors
Smoothing Reactors                 ADVANTAGES
Line and Load Reactors
Test Laboratory Reactors           q   Perfect mechanical strength to withstand
                                   high short-circuit forces.
                                   q Limited temperature rise enables longer

TESTING SYSTEMS                    lifetime.
                                   q Special surface protection against UV and
Turn-key Short Circuit             pollution class IV areas.
Laboratories                       q Maintenance-free design
High Current Injection Test Sets
R - L - C Load Banks



                                   STANDARD

                                   EN 60289 or depending on customer requirements.


                                   FEATURES

                                       q   Air core and iron core
                                       q   Dry type
                                       q   Side by side, delta or vertical arrangement depending on
                                           space availability for air core reactors
                                       q   Outdoor and indoor
                                       q   Enclosures are available on demand
                                       q   Elevated support stands are available
                                       q   Aluminum or copper winding
                                       q   RAL 7032 or other colors
                                       q   - 40 ºC / + 55 ºC ambient temperature range
                                       q   F class (155 ºC) or customer specific design
                                       q   Taps are available
                                       q   Fiberglass spacers are used in order to provide ease of
                                           cooling
                                       q   AN (air-natural) cooling method




                                   INSULATION

                                   . F class (155 ºC) film insulation or epoxy resin reinforced fiberglass.
                                   . Epoxy based paint & insulating varnish.


                                   INSTALLATION

                                   The height and the diameter of the reactor can be adjusted to customer specific needs in order to
meet unusual space requirements

Complete installation guidelines are provided with the
reactors in order to meet required magnetic clearances on
close metallic structures. Each reactor is supplied with an
INSTALLATION GUIDELINES that specifies minimum
magnetic clearances for the reactor.


SUPPORT STANDS

Aluminum, hot dip galvanized steel or concrete support
stands are designed for specific applications.




TESTS

All the routine tests are performed in accordance with EN 60289 or other standards depending on
customer request. Type test reports are available on request. All the test reports are submitted to
customer.

Basic testing program includes some or all of the following tests:

• Routine Tests (Inductance, Resistance, One Minute AC Insulation Voltage Withstand Test and
Impulse Voltage Withstand Test)
• Short Circuit Withstand Test
• Temperature Rise Test
• Sound Level Test
• Seismic Test


QUALITY ASSURANCE

Hilkar maintains a complete quality assurance program including ISO 9001 and other major
industry standards in it's manufacturing plant.


TECHNICAL SUPPORT

Hilkar provides complete technical assistance to contractors and end customers for applications,
design, calculations and field installation. All Hilkar reactors are custom designed for different
applications by considering the voltage, current, inductance, size, loss characteristics that are
required to provide the most efficient design at the most economical prices.