Cold Storage Packing Facility by btz89935

VIEWS: 0 PAGES: 16

									Cold Storage & Packing Facility
         Salinas, CA 93901


                                 15 November 2008




                         Thermal Survey
                                   by
                         Agrarius’ Thermo-Vu™
                        PO Box 2168 Monterey, CA 93942
                             www.agrariusllc.com
     Imaging Locations (SPOTS)
                                                Spot-9             Spot-8
                        Spot-11   Spot-10
              Spot-12




                                                          Spot-5


                                                         Spot-7
                                                                  Spot-4
Spot-14                                                  Spot-6




                                            Spot-3

          Spot-1
                        Spot-2                                              2
                  Notes                     North
                                                               time frame
                                                               1500-1520
                                                                                             time frame
                                                                                             1430-1445
             15 November 2008


                           Skin
                                                                  Processing
       Object                                                  Ave temp 36-38deg
                           Temp
       Blacktop              106      time frame
       Concrete              103         1545                                                     time frame
       Door 23               145                                             Shipping             1345-1415
                                                                          Ave temp 36-39deg
  Black stuff at door        180                            Raw
    Base of Bay15            80                       Ave temp 36-38deg

      Raw plastic            90
    Base of plastic          50                                   time frame
     Side in shade           84                                   1300-1330
   Wood box white            84
       Side door             92
Plastic on side shipping   77/55/40       Time      Air Temp     Sun        Wind      Sky       VSBY      WX
      Refrigerant            44                                Overhead
                                           1230        83                    N-10      0/8       10 mi    nil
                                                                Bright
Electric boxes/batteries     80
                                                               Horizon
                                           1530        87                    N-10      0/8       10 mi    nil
                                                               Bright




                                                                                                          3
                SPOT 1




          50

Thermal
 Index    100


          150


   103


                         4
                SPOT 2




          50

Thermal
 Index    100


          150




                         5
                SPOT 3




          40

Thermal
 Index    100


          150




                         Check note @ SPOT 6
                                               6
                SPOT 4




          50
Thermal
 Index    90


          130

                         7
Thermal
 Index
                          SPOT 5




                    40

          Thermal
           Index    80


                    120            8
                SPOT 6 & 7




          40

Thermal
 Index    60

          110



                             9
                SPOT 8




          40

Thermal
 Index    80


          120
                         10
                SPOT 9 roof & wall




          40

Thermal
 Index    80


          120


                                     11
                SPOT 10 & tanks




          40

Thermal
 Index    80


          120                     12
SPOT 11 & SPOT 12




               40

     Thermal
      Index    80


               120
                     13
alcove




                   40

         Thermal
          Index    70


                   100
                         14
                SPOT 14




          40

Thermal
 Index    80


          120             15
        Comment/Recommendations
Image                                                                          Priority
                                                             Estimated           based on
  on              Significant Considerations                                                               Action
                                                              Impact          potential Cost-
 Page                                                                         Time -Impact

        Refrigerant heated while delivered to locations
 4-13                                                          ~ 1-2%                           Increase Lagging on Pipes
        where it is applied.
 6&9    Uncharacteristic hot spot – building material?                                          Check location
  8     Uncharacteristic cold spots –?                                                          Check location – use caution
                                                               ~ 3-4%
        Very Cold Roof at rear of building, ΔT 40deg on
 12                                                        based on surface                     Insulate
        15Nov
                                                             area and ΔT
                                                               ~ 5-6%                           Paint white/high albedo
        Building Hump – heat exchange, from solar effect
 12                                                        based on surface                     &
        and ambient temp
                                                             area and ΔT                        Insulate
 14     Uncharacteristic warm spot –?                                                           Check location


 Notes:
        Effect of Sun in Surfaces
        Effect of Ambient Temperatures on Surface
        Wind Effect
                                                                                                                          16

								