					                                                                            June 9, 2003                                DN-6877 • A0-190


                                                                                         BACnet Gateway
                                                                                             Section: Network Systems

General
The BACnet Gateway provides an interface between
NOTIFIER’s fire panel network NOTI•FIRE•NET™ (version
4.0 and higher) and a network using the BACnet/IP communi-
cation protocol. BACnet protocol is an American National Stan-
dard (ANSI/ASHRAE 135-1995). With the Gateway interface,                                                          CS118
devices on NOTI•FIRE•NET™ fire alarm control panels are
represented as BACnet objects to the BACnet client. The user                                S635
subscribes to Event Notification objects per FACP, and the
BACnet device receives events from objects on the FACP as
a result of this subscription.
The BACnet Gateway can be connected to a stand-alone
ONYX™ panel with an available network port, or it can be con-
nect to NOTI•FIRE•NET™ via the network port on any NCM-
W/-F. Connected to NOTI•FIRE•NET™, each BACnet Gate-
way can support 15 nodes maximum or 15,000 objects. Mul-
tiple BACnet Gateways can be used to interface with larger
networks.                                                                                                        BACnet Gateway
Features                                                                                                         Board
• Compatible with ONYX™ Series panels:
  NFS-3030, NFS-640.
• Compatible with NOTI•FIRE•NET™ de-
  vices: NFS-3030, NFS-640, NCA, NCS, and
  AFP1010/AM2020.
• The BACnet Gateway can monitor up to fif-
  teen NOTI•FIRE•NET™ panels with a
  maximum combined object count of 15,000
  (object count includes all detectors, monitor modules, noti-
  fication appliance circuits, etc.).
• Multiple BACnet Gateways can be used for large (more than




                                                                                                                             g
  15 nodes) networks.




                                                                                                                            jp
                                                                                                                        v.
                                                                                                                       co
                                                                                                                   77
• PC programmable using the BACnet Gateway Serial Con-

                                                                                                                  68
  figuration Tool, an offline programming utility used to con-
  figure the BACnet Gateway. The Serial Configuration Tool
  is used on a compatible computer that is using Windows®
  2000, 98, NT version 4.0, or later OS; and has an available               Connections
  (non-dedicated) serial port for communicating with the
  BACnet Gateway.                                                           • The BACnet Gateway is connected to NOTI•FIRE•NET™
                                                                              via the network port on the NCM-W/-F to the EIA-232 serial
• The NOTIFIER BACnet Gateway can behave as a foreign                         port on the Gateway (uses the network to DB9 cable, P/N
  device when communicating with a third-party BBMD                           75582).
  (BACnet Broadcast Management Devices).
                                                                            • BACnet Gateway is connected to the BACnet front end via
Specifications                                                                a standard RJ45 Ethernet connector (CN2).
• Complies with: UL 864; and CAN/ULC-S527-M99 Standard                      • The BACnet Gateway assembly installs in one row of a
  for Control Units for Fire Alarm Systems.                                   CAB-3 or CAB-4 Series cabinet using a CHS-4 or CHS-4L
                                                                              chassis. The BACnet Gateway, power supply, and PNET-1
• Complies with NFPA 72 National Fire Alarm Code.                             surge suppressor are installed on a BACnet Gateway/Power
• Conforms to BACnet Standard Annex J for IP and Support                      Supply Mounting Plate (P/N 18541), which takes up two
  Device Objects, Binary Output Objects, Life Safety Points/                  module positions.
  Zones, and Multi-State Inputs.                                            • The PNET-1 surge suppressor is connected to the BACnet
• Power supply: 24 VDC to 5 VDC. Input voltage range is 19                    Ethernet via a RJ45 Ethernet connector.
  VDC to 29 VDC. Input current is 360 mA @ 24 VDC. Output                   See diagram of components on mounting plate on page 2.
  current is 1.2 A @ 5 VDC.
• Operating temperature: 32°F to 120°F (0°C to 49°C).                       NOTI•FIRE•NET™ and ONYX™ are trademarks of NOTIFIER.
                                                                            Microsoft® and Windows® are registered trademarks of the
                                                                            Microsoft Corporation.

 NOTIFIER® is a               company.
 This document is not intended to be used for installation purposes. We try to keep our
 product information up-to-date and accurate. We cannot cover all specific applications
 or anticipate all requirements. All specifications are subject to change without notice.
 For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
                                                                                                                                 Made in the U.S.A.
                                    12 Clintonville Road, Northford, Connecticut 06472

                                                                                                          DN-6877 • 06/09/03 — Page 1 of 2
Agency Listings and Approvals                                           NOTIFIER parts also required:
See the first page of this data sheet for listing agencies and          • Cabinet: CAB-3 Series (see data sheet DN-3549) or CAB-4
file numbers. These listings and approvals apply to the BACnet            Series (see data sheet DN-6857).
Gateway. In some cases, certain modules or applications may             • Chassis: CHS-4L.
not be listed by certain approval agencies, or listing may be in
                                                                        • For connection to NOTI•FIRE•NET™: NFS-3030 (see data
process. Consult factory for latest listing status.
                                                                          sheet DN-6880), AM2020 (DN-0713), AFP1010 (DN-3341),
                                                                          or NFS-640 (DN-6856) FACPs, or NCM-W/-F (DN-6861).
Product Line Information
                                                                        Additional required components (from other vendors):
The BACNET GATEWAY (ordered as such) includes every-
thing required to set up an interface to an existing NOTIFIER           • IBM-compatible PC with Windows® 2000, 98, or NT version
system or network with the exception of a chassis and the                 4.0 or higher, and available serial port.
Network Control Module (NCM). It includes:                              • DB-9 to DB-9 null modem cable (PC-to-Gateway program-
• PC board for the BACnet Gateway (P/N 46173).                            ming cable).
• Power supply – 24 VDC to 5 VDC (P/N 46175).                           • Standard Ethernet network cable with RJ45 connectors.
• Surge suppressor (PNET-1).                                            PIC Statement/BACnet Information
• DB9-to-network cable (P/N 75582).                                     The BACnet Gateway PIC Statement is available at www.
• 5 VDC power connector (P/N 75581).                                    notifier.com. Select products and then network systems. For
• Software on CD-ROM (Serial Configuration Tool).                       information on the BACnet protocol, see www.bacnet.org.
• BACnet Gateway/power supply mounting plate (P/N 18541).


                                                                   Power Supply                          BACnet Gateway
                                          6877chas.jpg




                                                                                                                                   6877bord.jpg
                                                         PNET-1 Surge
                                                         Suppressor

 Mounting Plate on                                                                                                Mounting
 CHS-4L Chassis                                                                                                   Plate



System
Architecture
Example
                                                                                                                    6877arch.wmf




Page 2 of 2 — DN-6877 • 06/09/03

				