SJ and SA Steam Boiler Series

Document Sample
SJ and SA Steam Boiler Series Powered By Docstoc
					                                                     P.O. Box 37                           Phone: 540-662-3811
                                                     4407 Martinsburg Pike                 Fax: 540-665-8101
                                                     Clear Brook, VA 22624                 email: Sales@reimersinc.com
                                                     USA                                   web: www.reimersinc.com
    Electra Steam, Inc.


SJ and SA Steam Boiler Series                                                                                            ASME
                                                                                                                         CSD-1
                                                                                                                         CRN
                                                Features
                                                •    Miniature boiler designed and constructed to Section I, Parts PMB & PEB of
                                                     the A.S.M.E. Boiler Code, inspected and registered with National Board
                                                                               3
                                                     Max. vessel volume 0.35ft
                                                     Max. safety valve setting 100psi
                                                •    Dry saturated steam
                                                •    Operating pressure range 0 – 85psig
                                                •    Heavy duty 304 or 316 stainless steel pressure vessel. Boiler enclosure 304
                                                     stainless
                                                •    Pacified pressure vessel and heating elements


                                                Applications
                                                •    Ultra Pure Steam for Medical Research, Pharmaceutical and Cosmetics
                                                •    Pure Steam Humidifier
                                                •    Food Service
                                                •    Laboratories

                                                Standard equipment of each boiler includes: Low water cutoff control
                                                with manual reset, high pressure cutoff control with manual reset, one
                                                (1) operating pressure control, gauge glass set, pressure gauge and
                                                safety valve.




                       SJ and SA SERIES LOW & HIGH PRESSURE STEAM BOILERS
  MODEL        KW     LB/HR       BHP         VOLTAGE*         PHASE     SHIP WT.    OP. PRESS.      MBTU/HR     Steam Outlet (NPT)
                                                                            LB        RANGE
                                                                                                                   LP         HP
    SJ         1.5      5.2       0.15          120/240           1          75       0-85 PSIG         5          1/4        1/4
    SA          4       13        0.4           240/480           1/3        85       0-85 PSIG        13.4        1/4        1/4
    SA          8       27        0.8           240/480           1/3        85       0-85 PSIG        26.8        1/4        1/4

* Some boiler models requires two (2) power supplies: Primary heating power and secondary control voltage. Nominal
control voltage for cULus models is 120V, 60Hz, for non-cULus models nominal control voltage is 220-240V, 50Hz.


                                              Model Number Key




     Example: SAAH8E1F = SA-Series boiler with solenoid and feed pump, 8kW heating
     power, power supply 240V, 1ph, safety valve set to 100psi.
                                 Construction


Electrical Enclosure        Shell Thermal Insulation:    High Pressure Feed Water Pump:
and Shell Wrapper:          Mineral Wool:                Wetted parts:
304 Stainless Steel         2” min. thick                Choose ABS, BUNA-N, 304/316 SS
                                                         Or
                                                         All 316 SS




        Heating Elements:        Shell:                 Boiler External Piping:
        Rods and Flanges         Choose 304L SS         Choose 304L SS
        316 SS standard          or 316L SS             or 316L SS
Overall Dimensions
 SJ and SA – Models