					                                         SATS FLAiR Series
              1.5 - 5 Ton "FCS" Floor Mounted Precision Control Air Conditioners

                                      Product Guide Specification

***************************************************************************************************************
This section must be carefully reviewed and edited by the Engineer to meet the requirements of
the specific project. Coordinate with other specification sections and the drawings as necessary.
***************************************************************************************************************

1.1 Summary

This specification describes requirements for a precision environmental control system. The
FLAiR “FCS” floor-mounted air conditioning system shall provide precision temperature and/or
humidity control for computer rooms or rooms containing telecommunications or other highly-
sensitive heat load equipment where continuous 24 hour a day, 365 days a year air conditioning
is required. The units are designed with a wide range of options to handle both precision and
comfort cooling applications.

The supplied system shall be labeled in accordance to UL 1995 Standard, and MEA NYC
approved (MEA-163-88-E) (CSA if applicable) listings.

The system model number shall be ________________________.

1.2 DESIGN REQUIREMENTS

The environmental control system shall be an SATS FLAiR factory-assembled unit. The unit shall
be designed for corner installation, requiring front only access through a hinged and removable
front access panel. The electric box shall hinge outward allowing for front only access to all
components. No allowance for side service access shall be required, however removable side
access panels shall be provided for additional access. On direct expansion models, the
refrigeration system shall be split with a matching outdoor air-cooled condenser, or with the
compressor located in a remote or close-coupled condensing unit.

The evaporator section shall be specifically designed for high sensible heat ratio. The heat
exchanger shall be propeller fan (for outdoor installation) or centrifugal fan (for indoor installation).

Each system shall be capable of handling _______CFM (CMH) at ________inches (mm) of water
external static pressure with (up discharge front return air flow, down discharge top return air flow,
up discharge rear return air flow pattern. The unit shall have the cooling capacity of ________
Btu/hr (kW) and the sensible cooling capacity of ________Btu/hr (kW), based on entering air
condition of ___________°F (°C) dry bulb and _______°F (°C) wet bulb. The humidifier shall
have the capacity of __________lb/hr (kg/hr.). Reheat shall have a capacity of ________ Btu/hr
(kW). The main fan motor(s) shall be ______HP (kW).

The unit shall have a power supply of ________ volts, ________ phase, ______Hz.

2.0 PRODUCT

2.1 Cabinet and Frame Construction



                           1572 Tilco Drive  Frederick, Maryland 21704 USA
                     Phone: 301-620-2033  Fax: 301-662-5487  www.stulz-ats.com

                                                                                               QG-FQS0045
                                                                                                     Rev -
                                                Page 1 of 10
The cabinet and access panels shall be fabricated from 16 gauge galvanized steel and painted
with a 2-ply epoxy finish to match and provide corrosion protection. The panels shall be lined
with 1/2" (13 mm), 2 lb (.90 kg), high-density sound and thermal insulation and sealed with self-
extinguishing gasketing conforming to NFPA 90A and 90B. The main unit color shall be
____________________.
2.2     Electric System

2.2.1   Modular Motor Controllers

The systems shall incorporate modular motor controllers utilizing motor start protectors and circuit
breakers to eliminate the need for fuses. All wiring shall be in accordance with the National
Electric Code (NEC) and shall include:

* Motor branch circuit short circuit protection;
* Motor load switching controllers (contactors) and
* Motor overload protection.

The control circuit shall be a 24 VAC Class II low voltage circuit, including primary and secondary
circuit protection. Low voltage, high voltage, and common wires shall be color-coded and shall
be individually numbered at each end for ease of service tracing. All wiring shall be in
accordance with the National Electric Code (NEC).

2.2.2   Remote Stop / Start Contacts

Included in the system’s electrical control circuit shall be a 2 –pin terminal connection for remote
stop/start of the FLAiR air conditioner by remote source.

2.2.3   Main Power-Electric Non-Fused Disconnect Switch

The unit mounted main power disconnect switch factory provided, is as standard. The disconnect
switch shall be dust-proof, non-fused type with a lockable handle.

2.3 Direct Expansion System

2.3.1 Coils

The system shall be configured for a draw-thru air pattern to provide uniform air distribution over
the coil face. The coils shall be designed to provide maximum coil surface area and minimum
depth to provide a high sensible cooling capacity. The coils shall be seamless drawn copper
tubes, mechanically bonded to tempered aluminum fins with a raised lanced fin design for
maximum heat transfer. Coil end plates shall be hot dipped galvanized steel. The evaporator coil
shall be mounted in an insulated UL-94-V-O polymeric or stainless steel condensate drain,
depending upon FCS model size

The evaporator coil shall have a _______ft² (m²) face area and be _______rows deep. It shall be
constructed of copper tubes and aluminum fins and have a maximum face velocity of
______ft/min (m/s) at _______CFM (CMH). Refrigerant flow shall be controlled by an externally
equalized thermostatic expansion valve.




                         1572 Tilco Drive  Frederick, Maryland 21704 USA
                   Phone: 301-620-2033  Fax: 301-662-5487  www.stulz-ats.com

                                                                                       QG-FQS0045
                                                                                             Rev -
                                            Page 2 of 10
2.3.2 Refrigeration System

All refrigerant piping shall be refrigerant grade tubing. Each refrigeration circuit shall include, as a
minimum a refrigerant drier/strainer sight glass with moisture detector, a thermal expansion valve
with rapid bleed port feature and external equalizer, an evaporator coil, a compressor, a high
pressure switch with manual reset, and a low pressure switch with automatic reset.

Split/Remote systems shall have a liquid line solenoid for refrigerant isolation to prevent liquid
slugging. All high-pressure joints shall be brazed, and the entire system shall be pressure tested
at the factory with dry nitrogen, evacuated to at least 50 microns and fully charged with
refrigerant.

2.3.3 Scroll Compressor

The compressor shall be high efficiency, high reliability and low noise scroll compressor(s). The
compressor shall be complete with charging and service shraeder ports, internal vibration
isolation, internal thermal overloads, an internal pressure relief valve, an internal discharge gas
vibration eliminator, and external vibration mounting isolation.

2.4     Fan Section

2.4.1   Direct-Driven Systems (Models FCS-018/060)

The blower(s) shall be direct-driven with double-width, double-inlet housing and forward-curved
blades. The blower(s) shall be dynamically and statically balanced to minimize vibration and
operate in the Class 1 range. The blower(s) shall be corrosion protected with a painted housing
and impeller wheel. The three-speed (208V) evaporator motor shall be factory wired for the
correct speed to produce the specified air quantity. The blower motor shall have internal overload
protection. (277 and 460V direct-drive motors shall be two-speed.)

The fan motor shall be ___________hp (kW) at 1075 rpm.

2.5     Temperature and Humidity Control

The standard FLAiR “FCS” floor A/C includes the A-TECH-20 Microprocessor Controller, and
Dehumidification Mode with Electric Reheat/ Heat providing precision temperature and humidity
control.

2.5.1   A-Tech-20 Microprocessor Temperature & Humidity Controller with Alarms

This controller shall incorporate a “user-friendly” operating environmental to allow easy system
setup and operation. The control system shall monitor unit operation and activate audible and
visual alarms in the event of the following factory preset alarm conditions:

*   High temperature
*   Low temperature
*   High humidity
*   Low humidity
*   High head pressure
*   Loss of air flow



                         1572 Tilco Drive  Frederick, Maryland 21704 USA
                   Phone: 301-620-2033  Fax: 301-662-5487  www.stulz-ats.com

                                                                                         QG-FQS0045
                                                                                               Rev -
                                             Page 3 of 10
* Leak Detection; and
* Dirty filter.

Unit Status Display shall be available for:

      Current Dry Bulb Temperature Set Point
      Current Relative Humidity Set Point
      Current Unit Status:
       Unit ON/OFF, Power ON, Cooling, Humidifying, Dehumidifying, Reheating and/or
       Heating…etc.
      Actual Room DB Temperature
      Actual Room Relative Humidity

More Standard A-TECH-20 Features:


      Selectable Automatic or Manual Restart with non-volatile memory for "last" stored setting
       recall
      Keypad lock-out feature to prevent unauthorized tampering
      Common alarm dry-contact connection for remote BMS communication
      Time Clock for Night Set-Back
      Built-in short cycle protection

2.6.       Humidity Control

2.6.1 Canister Steam Humidification

The humidifier shall be an electrode steam canister type and shall have an adjustable humidity
output setting from 25 to 100% of the full rated humidifier capacity. The humidifier shall have an
automatic flush cycle that senses the current consumption of the humidifier and controls mineral
concentration of the water. A “Change Cylinder” light shall notify service personnel when the
humidification output is below rated requirements and when maintenance is due.

2.7 Dehumidification Cycle

The floor A/C shall provide refrigeration-based dehumidification mode. Moisture is condensed on
the cooling coil and discharged through the condensate drain. Reheat (electric, hot gas, steam,
or hot water) shall be provided to offset sensible cooling during the dehumidification cycle.

2.7.1 Electric Reheat

A factory mounted and wired low-watt density, nichrome-wire electric resistance heater shall be
included to provide automatic sensible re-heating as required during the dehumidification cycle
and automatic heating mode. Electric heaters shall be provided with miniature thermal/magnetic
circuit breakers, which shall protect each ungrounded conductor. Also included will be one
automatic reset and one manual reset over-temperature safety device (pilot duty).

2.8        Air Pattern




                           1572 Tilco Drive  Frederick, Maryland 21704 USA
                     Phone: 301-620-2033  Fax: 301-662-5487  www.stulz-ats.com

                                                                                      QG-FQS0045
                                                                                            Rev -
                                              Page 4 of 10
2.8.1   Top Discharge Grille with:

        * Front “Free” Return;

2.9     Filter Chamber

The filter chamber shall be an integral part of the unit, located within the cabinet and serviceable
from the front of the unit.

The A/C shall have a slide out, 1" deep, class 2 (per U.L. Standard 900) filter. The filter shall be
easily accessed through the front, hinged access door.

2.10    Standard Features / Individual Systems

2.10.1 Air Cooled

The air-cooled system shall consist of the following:
1. Split air cooled with remote outdoor condenser;
2. Split air cooled with remote indoor centrifugal-type condenser;
3. Split air handling unit with remote outdoor propeller-type condensing unit; or
4. Split air-handling unit with remote indoor centrifugal-type condensing unit.

2.10.1.1 Remote Outdoor Propeller Condenser

The system shall be a remote outdoor air cooled condenser with direct-driven propeller fan(s).
The condenser cabinet shall be of aluminum construction and contain copper tubes and
aluminum fins. The condenser cabinet shall house the condenser coil, direct-drive propeller
fan(s) and TEFC fan motor(s), and NEMA 3R condenser motor control/enabling box. The
compressor(s) shall be located with the FCS-( )-AR evaporator section. The condenser shall be
sized to provide the total heat rejection of the system at 95°F ambient temperature for the
corresponding model FCS-( )-AR FLAiR evaporator unit. The following head pressure control
features are offered:

* HES-( )-LAA (012 to 060): Low Ambient Head Pressure Control down to a minimum
   ambient temperature of 0°F via fan cycling head pressure control.

* HES-( )-LSA (042 to 060): Low ambient head pressure control down to a minimum ambient
  temperature of -20°F via variable fan speed head pressure control.

* HES-( )-LFA (012 to 060): Low ambient head pressure control down to a minimum ambient
   temperature of -30°F via flooded head pressure control.

2.10.1.2 Remote Indoor Centrifugal Condenser

The system shall be a remote indoor, ceiling mounted, air cooled condenser with centrifugal
blower. The condenser cabinet shall be of aluminum construction and contain copper tubes and
aluminum fins. The condenser cabinet shall house the condenser coil, blower and blower motor,
receivers (if applicable), and condenser motor control/enabling box. The compressor(s) shall be
located with the FCS-( )-AR evaporator section. The condenser shall be sized to provide the total




                          1572 Tilco Drive  Frederick, Maryland 21704 USA
                    Phone: 301-620-2033  Fax: 301-662-5487  www.stulz-ats.com

                                                                                        QG-FQS0045
                                                                                              Rev -
                                            Page 5 of 10
heat rejection of the system at 95°F ambient temperature for the corresponding model FCS-( )-
AR evaporator unit. The following head pressure control features are offered.

* HES-( )-CAA (012 to 036): Low ambient head pressure control down to a minimum ambient
  temperature of 0°F via fan cycling/speed head pressure control.

* HES-( )-CAA (012 to 060): Low ambient head pressure control down to a minimum ambient
   temperature of -30°F via flooded head pressure control.


2.10.1.3 Split air handling unit with remote outdoor propeller type condensing unit

The system shall be an outdoor, remote air cooled condensing unit with direct-driven, propeller
fan(s). The system’s compressor shall be located with the remote condensing unit section. The
condensing unit cabinet shall be of aluminum construction and contain copper tubes and
aluminum fins. The condensing unit cabinet shall house the condenser coil, compressor(s),
direct-drive propeller fan(s) and TEFC fan motor(s), and a NEMA 3R condenser motor
control/enabling box. The condensing unit shall be sized to provide the total heat rejection of the
system at 95°F ambient temperatures for the corresponding model FCS-( )-AHU FLAiR air
handling unit. The following head pressure control features are offered.

* SCO-( )-H22 (012 to 060): Low ambient head pressure control down to a minimum ambient
temperature of 0°F via fan cycling head pressure control.

* SLO-( )-H22 (012 to 060): Low ambient head pressure control down to a minimum ambient
temperature of -30°F via flooded head pressure control.


2.10.1.4 Split air handling unit with remote indoor centrifugal type condensing unit

The system shall be indoor, ceiling mounted, remote air cooled condensing unit with centrifugal
blower. The condensing unit cabinet shall be of aluminum construction with copper tubes and
aluminum fins condenser coil. The condensing unit cabinet shall house the condenser coil,
compressor(s), blower and blower motor, receivers (if applicable), and condenser motor
control/enabling box. The condenser shall be sized to provide the total heat rejection of the
system at 95°F ambient temperature for the corresponding model FCS-( )-AHU FLAiRair handling
unit. The following head pressure control features are offered:

* OHS-( )-RCU-I (012 to 060): Low ambient head pressure control down to a minimum ambient
temperature of 0°F via fan cycling head pressure control.

* OHS-( )-RCU-I (012 to 060): Low ambient head pressure control down to a minimum ambient
temperature of -30°F via flooded head pressure control.

2.11 Water Cooled Systems

2.11.1   Integral Coaxial Water Condensers

The water-cooled condenser shall be an integral coaxial type with a factory installed head
pressure water-regulating valve. The unit shall have a total heat of rejection of _________Btu/hr



                         1572 Tilco Drive  Frederick, Maryland 21704 USA
                   Phone: 301-620-2033  Fax: 301-662-5487  www.stulz-ats.com

                                                                                     QG-FQS0045
                                                                                           Rev -
                                           Page 6 of 10
(kW), require _______gpm (l/s) of ____________°F (°C) water, and have a maximum pressure
drop of _________ft. (kpa.)

2.11.2 Head Pressure Control

Each refrigerant circuit’s head pressure shall be controlled by a factory-installed two-way water
regulating valve rated for 150 psig. w.w.p.

2.12    Glycol-Cooled Systems

2.12.1 Integral Coaxial Glycol Condensers

The glycol cooled condenser shall be an integral coaxial type with a factory-installed head
pressure glycol regulating valve. The unit shall have total heat of rejection _________Btu/hr
(kW), require _______gpm (l/s) of _________°F (°C) water, and have a maximum pressure drop
of __________ft. (kpa.)

2.12.2 Head Pressure Control

Each refrigerant circuit’s head pressure shall be controlled by a factory installed two-way glycol
regulating valve rated for 150 psig. w.w.p.

2.13    Drycooler

Drycooler casings shall be fabricated from heavy aluminum for corrosion protection and
appearance. The aluminum also reduces the weight of the drycooler to reduce roof loading and
shipping costs. Structure components shall be fabricated from galvanized steel for support.
Motors shall be permanently lubricated ball bearings and be internally protected. The fan blades
shall be made from aluminum and have zinc plated hubs for strength and corrosion protection.
Multiple drycoolers shall have internal air baffles to prevent air bypass from one fan section to
another and to maximize air through each coil section. The drycooler shall be designed for
________°F (°C) ambient.

2.14    Glycol Pump Package

The pump packages are available as single pump or dual automatically redundant pump
packages. The system shall be mounted on an aluminum angle chassis and be protected by a
removable aluminum cover. The controls shall be mounted in a NEMA-4 enclosure at the end of
the pump package.. The pump packages shall include, but not be limited to:

* Pump starter(s)/contactor(s) with fusing per NEC;
* Aquastat(s) to sense the coolant temperature and controls to cycle the drycooler fan(s) to
   maintain the coolant temperature;
* A 15 gallon expansion tank;
* An airtrol fitting (automatic air bleed valve);
* A single point main power connection for pump and drycooler.

The pump shall be sized to provide _____ gpm _____ l/s (total system flow rate) at
______ft._______(kpa) of head. The glycol shall be _____% Ethylene / Propylene glycol
solution.



                         1572 Tilco Drive  Frederick, Maryland 21704 USA
                   Phone: 301-620-2033  Fax: 301-662-5487  www.stulz-ats.com

                                                                                      QG-FQS0045
                                                                                            Rev -
                                           Page 7 of 10
2.15   Chilled Water System Components

2.15.1 Chilled Water Cooling Coil
                                             2   2
The cooling coil shall have a ____________ft (m ) face area and be 4 rows deep. The coil shall
be constructed of seamless drawn copper tubes, mechanically bonded to tempered aluminum
fins with a raised lance fin design for maximum heat transfer, and mounted in a stainless steel
condensate drain pan. The coil shall be designed for under 500 ft/min face velocity. The water
circuit shall be designed to distribute water into the entire coil face area. The coil shall be
supplied with _____°F (°C) entering water temperature with a __________°F (°C) rise. The coil
shall be supplied with _________gpm (l/s) of chilled water and pressure drop shall not exceed
______psi (kpa).

2.15.2 Chilled Water Control

The water circuit shall include a two-way slow close motorized valve. Design pressure shall be
150 psig (1035 kpa) two-way or three-way 250 psig (1724 kpa) shall be provided as an option.

2.16    Optional Equipment / All Systems

2.16.1 Remote Mounted A-Tech-20 Controller Display

Remote mounting of the A-Tech-20 key pad display is optional. A 30 ft. interconnecting
communications cable with easy plug-in end connectors shall be factory provided standard with
remote A-Tech-20 display option.

2.16.2 A-Tech-1.1

The A-Tech-1.1 is available as a cost savings alternative to the A-Tech-20 for those non critical
applications requiring temperature (cooling/heating) only control and no humidity control. The
FLAiR Series floor mounted A/C shall be provided with SATS “slimline”, ultra-thin profile, 1-stage
cool/1-stage heat, unit or remote wall-mounted programmable digital microprocessor based
controller.

2.16.6 Head Pressure Control ( Low Ambient Control)

AIR COOLED – Low Ambient

0°F, Fan Cycling / Fan Speed

The air cooled system shall incorporate a low ambient fan cycling/fan speed head pressure
control for year-round A/C system operation down to 0°F DB minimum ambient air temperature.

-20°F, Variable Speed Control (Model HES-()-LSA Condenser)

The air cooled system shall incorporate a low ambient variable speed fan head pressure control
for year-round A/C system operation down to -20°F DB minimum ambient air temperature.




                        1572 Tilco Drive  Frederick, Maryland 21704 USA
                  Phone: 301-620-2033  Fax: 301-662-5487  www.stulz-ats.com

                                                                                    QG-FQS0045
                                                                                          Rev -
                                          Page 8 of 10
-30°F, Flooded Control

The air cooled system shall incorporate a low ambient flooded head pressure control for year-
round A/C system operation down to -30°F DB minimum ambient air temperature. This option
shall include a factory installed crankcase heater, cold-start relay, liquid refrigerant receiver with
receiver liquid level sight glass and head pressure regulating valve for flooded condenser option.

2.16.7 Water / Glycol Systems

Two-Way, 350 psig Regulating Valve

Each refrigerant circuit’s head pressure shall be controlled by a factory installed, High Pressure
two-way water /glycol regulating valve rated for 350 psig. w.w.p.


Three-Way, Head Pressure Regulating Valve

Each refrigerant circuit’s head pressure shall be controlled by a factory supplied and field
installed:
         * 3-Way, 150 psig w.w.p. head pressure valve: or
         * 3-Way, 350 psig w.w.p. head pressure valve.


2.17    DX - Capacity Modulation/Freeze -Protection

2.17.1 Snap-Acting, Hot Gas Bypass (Models Available FCS-( )-AR, W & G)

The FLAiR floor A/C units shall incorporate a hot gas bypass system to provide modulation of the
unit’s cooling capacity. This options shall also provide evaporator coil freeze protection under
low load conditions. The Snap-Acting system is only available on those systems where the
compressor is located in the evaporator section.
2.17.2 Modulating Chilled Water Control Valves

   2-Way, 250 psig w.w.p. chilled water modulating valve shall be factory piped and
    wired. The valve shall automatically meter the flow of chilled water to the
    cooling coil in response to a proportional signal (typically 0-10 VDC) provided
    to the valve by the A-Tech-20 proportional controller.

   3-Way, 250 psig w.w.p. chilled water modulating valve shall be factory piped and
    wired. The valve shall automatically meter the flow of chilled water to the
    cooling coil in response to a proportional signal (typically 0-10 VDC) provided
    to the valve by the A-Tech-20 proportional controller. If the cooling demand]
    falls below the system’s maximum cooling capacity, the superfluous coolant
    shall be diverted back to the chilled water source.

   3-Way, 150 psig w.w.p. chilled water slow-close motorized valve shall be factory
    piped and wired.

2.18    Accessories




                         1572 Tilco Drive  Frederick, Maryland 21704 USA
                   Phone: 301-620-2033  Fax: 301-662-5487  www.stulz-ats.com

                                                                                        QG-FQS0045
                                                                                              Rev -
                                            Page 9 of 10
2.18.1 Condensate Pump

The condensate pump shall have the capacity of ______gpm (l/s) at _______ft (kpa) of head.
The condensate pump shall be specifically designed to operate with the higher condensate
temperatures caused by the flush and drain cycle of the electrode canister humdifiers.

2.18.2 Smoke Detection

An ionized smoke detector shall be factory installed and wired in the evaporator section of the
suction side of the evaporator blower. The air conditioner will shut down upon sensing smoke in
the return air stream.

2.18.3 Firestat

The air conditioner shall be provided with a factory wired and mounted firestat. The firestat will
shut down the air conditioner upon sensing a high return air temperature.

2.18.4 Remote Water Detector

A remote single point water/leak detector shall be included to provide additional safety to the
standard condensate pan safety floats. Upon sensing a water leak, the normally closed water
detector control circuit opens, which will cause the air conditioner to shut down.




                         1572 Tilco Drive  Frederick, Maryland 21704 USA
                   Phone: 301-620-2033  Fax: 301-662-5487  www.stulz-ats.com