					       FREQUENTLY ASKED QUESTIONS
         AND COMMON FAULT LISTS


                      Description
                          Termination
                 Operating TM99 controller
                Setting up TM99 controllers
            Operating MM500 Controller Page 2
               Setting up MM500 controllers
    Wiring controllers to Secure Solutions Matrix Page
              Connecting Protocol Converters
                  How to set quick presets
                 Controller showing Error A
                 Controller showing Error B
           Controller is showing Error 1, 2, 3, or 4
           Controller is showing Error 5 or Error 6
                Controller is showing Error 7
                 Controller showing Error 8
         Domes won't work with Foreign Controllers
                          No Comms
                     Comms are erratic.
             No Zoom or Focus but Pan/tilt ok
        How to stop monitor from switching cameras
                     How to setup patrol
          Set unit to patrol after manual telemetry
          Set unit to Park after manual Telemetry
  Functions (OSD, Colour/B+W) using Foreign Controllers
           Want to set patrol on Meridian Domes
         One camera moves while moving another
                        Setting Alarms
    Setting dome to certain preset at certain time of day
                 MM500 Controller Menu's
            Intermittent Loss of Power or Video




Doc Ref No. MME/HO/001                                      Revision 1   Issue Date: 07/07/2005
Termination

 Q:   How Should a dome be terminated ?

 A:   The RS485 line should be terminated with 120Ω at either end, therefore if the control end is terminated
      the last dome on a line should be terminated. If the control end is not terminated then two domes or two
      daisy chains can be connected to the same port and termination is put on the end of each line.

      TM99INT/1 is terminated internally with resistor R1, which is the middle resistor above the orange plug
      where the RS485 is connected.


                                                               A   B            A    B              A       B        A   B           A    B




                                                           UNTERMINATED      UNTERMINATED     UNTERMINATED        UNTERMINATED     TERMINATED



                   A    B                                                        A   B              A       B        A   B




                 TERMINATED                                                  UNTERMINATED     UNTERMINATED         TERMINATED


                                                                                 A   B              A       B        A   B




                              A   B    A   B   A   B   A   B
                                                                             UNTERMINATED     UNTERMINATED         TERMINATED
                                  RS485 DIST RIBUTION

                                                                          Correctly Terminated




                   A    B                                      A   B            A    B              A       B        A   B            A   B




                 TERMINATED                                UNTERMINATED       TERMINATED      UNTERMINATED        UNTERMINATED      TERMINATED



                    A   B                                                        A   B              A       B        A   B




                UNTERMINATED                                                 UNTERMINATED     UNTERMINATED         TERMINATED


                                                                                 A   B              A       B        A   B




                              A   B    A   B   A   B   A   B
                                                                             UNTERMINATED     UNTERMINATED         TERMINATED
                                  RS485 DIST RIBUTION

                                                                          Incorrectly Terminated




                                      Term inated Dom e                                                         Unterm inated Dom e

                TERMINATED                                                                  UNTERMINATED


                                      Term inated RS485                                                         Unterm inated RS485
                   A    B             Distribution Output                                       A       B       Distribution Output

                                                                                                                                 MMRD00291
 Q: A system has an MM500TXA controller, a protocol converter and two domes how should it / can it be
    terminated.
 A: Could be terminated in two ways, the two domes could be connected in a daisy chain with the last dome
    terminated, or the two domes could be both be connected to the output port on the protocol converter,
    both be terminated and the termination removed from the protocol converter.
 Q: A system has an MM500/TD8 with 6 domes connected to the RS485 bus individually how they should
    be terminated?
 A: All the domes on the system should be terminated, the jumpers inside should be switched to
    unterminated if two domes are connected on the same line, if only one dome is connected to a line that
    line should be terminated.

Operating TM99 controller

 Q: How do you store and recall presets using a TM99 controller.
 A: Store presets by having key switched backwards (clockwise) and enter NUMBER PRST, recall by having
    key switched forwards (anticlockwise) and enter NUMBER PRST.


Setting up TM99 controllers

 Q: How do you set up a master controller to poll 1 Alarm Interface and 2 Slaves.
 A: Switch key backwards and set AUTO 13 to 1 and AUTO 14 to 2.

 Q: How do you change which monitor the autosequence is on.
 A: Change AUTO 15 to required number.

Operating MM500 Controllers.

 Q: How do you tell a dome to patrol on path 2.
 A: Enter 2 PATRL.
 Q: How do you tell a dome to autosequence a Monitor and how can you find out which monitors are
    Autosequencing.
 A: To start autosequence Enter monitor number then SEQ, to find out which monitors are sequencing press
    and hold SEQ.

Setting up MM500 controllers

 Q: How do you get into the menu on an MM500TX controller?
 A: The default code for getting into the menu on an MM500 controller is 9999 ENTER, this can however be
    changed in the menu by the installer.
 Q: How is an MM500TX controller setup to poll slave controllers?
 A: Enter the menu, select User Setup or System Install, scroll through to No Of Slaves.

Wiring controllers to Secure Solutions Matrix

 Q: How do you connect a controller to a Secure Solutions Matrix.
 A: If you are connecting a TM99 or MM500TX controller they must be connected to the matrix via a
    TM99INT/1, which is connected to the Master Port on the Matrix.
    If an MM500TXA or MM500TXB controller is being used then they can be connected directly to the
    Master Port of the Matrix with a D-connector lead wired with pins 1&6 straight through from the Comms
    Port of the controller.

Connecting Protocol Converters
 Q    How do you connect a protocol converter into a system
 A    This depends on the configuration of the system.


      Non-Mercer Controller to Mercer Domes

                                                                          Power                        Power                                                                      Power
                                                                          Supply                       Supply                                                                     Supply




                                              Matrix
                                              Video
                                                to
                               Port 1
                                                                                                                                                                                                       Last
                                                                                                                                                                                                      Dome
                                        MM500ENC          RS485                                                                                                                                     Terminated
                                         Protocol
              RS485/RS232               Converter
              From Matrix
             Control System
                                                       Slave
                                                       Port
                                                    Terminated




                 MMRD00147




      Connect the RS232 or RS485 from the Matrix to the Port 1 of the Protocol converter and connect the
      Slave port to the Mercer Domes. Ensure that the Protocol converter Slave port is Terminated. Note - if
      Klippon connector are on the Protocol Converter, they are used instead of the Slave Port.


      Non-Mercer Domes from Mercer Keyboard
                                                                 Port 1

                                                                                                                                      Non - Mark Mercer
                                  Slave Protocol                                                                                         Electronics
                                                                          RS232: 9 Way D-Type to 9 Way D-Type
                                    Converter                             Pin 2 to Pin 3                                                 Equipment
                                                                          Pin 3 to Pin 2
                                                                          Pin 5 to Pin 5

                                                       Slave                                                                                                    Video
                                                       Port                                                                                                     Input
                                                       Terminated
                    RS485: 9 Way D-Type to
                      Screw Type Terminal
                                 Pin 1 to A
                                 Pin 6 to B
                                            RS485




                                                                                                     Video
                                        RS485             Monitor
                                        Output           Output 2


                               Switching Matrix
                                                                           RS232 Via 8 Way Burndey
                                       or
                                                                                                                                                                              A   1   2   3   HO M E U-TURN   FO CUS

                                                                                                                                      ESC   WASH   WIPE   SEQ   PRE    CAM    B   4   5   6

                                                                                                                                                                              C   7   8   9



                             Control Panel Interface
                                                                                                                                      ENT   IRIS-O IRIS-C ALRM PATRL   MO N
                                                                                                                                                                              D   _   0   +
                                                                                                                                                                                                                       M a rk M ercer
                                                                                                                Meridian                                                                                                Electronics
                                                                                                                MM500TX Controlle r                                                                                            Limite d




                                                                                                                                MM500TX Master Control Panel
                MMRD00148                                                  Local Site System


      Connect the Mercer Matrix Control system to the Slave port of the Protocol Converter and Connect
      Port 1 to the Non-Mercer Domes. Note - If RS232 connections are required from the Mercer Matrix,
      connect to the Master port instead of Slave port.




Miscellaneous

 Q    How to set quick presets using Version 14 software
 A    Quick preset mode selected through Menu 6
 Q    How to set quick presets using Version 15 software
 A    Quick preset mode selected through Menu 7
 Q    Controller is showing Error A
A   The Controller software is not compatible with the OSD software of the Matrix.
Q   Controller is showing Error B
A   This is caused through Alarm Polling. To remove Error B from the Controller, first disable the alarms on the
    controller ( 99 ALRM) then enable the alarms again ( 0 ALRM), If user is not using alarms then switch alarms off.

Q   Controller is showing Error 1, 2, 3 or 4
A   Check comms connections to Alarm Interfaces. Matrix setup to poll for Alarm interfaces.Error shows which alarm
    interface is not connected. To remove enter System Install menu ( Menu 7) and select the number of alarm
    interfaces on the system. ( 0 if none are connected.)
Q   Controller is showing Error 5 or 6
A   Check comms connections to Slaves controllers. If ok Enter System Install menu ( Menu 7) and select the number
    of slave controllers connected to the system ( 0 if none connected) If slave connected, ensure that slave No. is
    set correctly. If ok Isolate problem by substitution.
    TM99 slave controllers - suspect 485 in TM99INT/1.

Q   Controller is showing Error 7
A   The controller is a Slave and is not receiving Polling signals from the Master Controller. Check to see if the Master
    is setup to poll for slave controllers.
Q   Controller is showing Error 8
A   Matrix is not responding to controller - check comms. Power controller off and on and check it logs on.
Q   Domes won't work with Foreign Controllers
A   Are the protocol DIP switches set correctly on the address board.


       Value                  Protocol                Value                 Protocol
      000000           Mark Mercer Meridian          000100          Mark Mercer FSK OLD
      100000        Photoscan Dimension Plus         100100             Mark Mercer FSK
      010000                   Molynx                010100                  Pelco D
      110000                   Ernitec               110100                  Pelco P
      001000                   DVST                  001100                   VCL
      101000                  Conway                 101100                   Ultrak
      011000                Geutebruck               011100                   BBV
      111000                   Phillips              111100                 Not Used


Q   No Comms
A   Check orientation of 485 A and B
Q   Erratic Comms
A   Check Termination. If termination is correct, possible faulty MAX485 IC somewhere. Remove domes one by one
    until problem disappears.

Q   No Zoom or focus but Pan/Tilt are ok.
A   No camera comms. Usually a Faulty camera or slipring.
Q   How to stop monitor from switching cameras.
A   Monitor is set to autosequence. Press and hold SEQ will show which monitors are sequencing. To stop, press
    monitor number then SEQ.

Q   How to setup a patrol
A   Select Dome Setup or Dome Install Menu, select Preset Functions then Set up Patrol. Also possible to setup
    patrol using Quick Presets, but this only stores Patrol path 1 and uses default values ( Dwell -10s and Speed -3 )

Q   Set unit to patrol after manual telemetry.
A   Set unit to AutoPatrol. Select Dome Setup or Dome Install Menu, select Autopatrol and enter Time delay .
Q   Set unit to Park after manual telemetry.
A   Set unit to AutoPark.Select Dome Setup or Dome Install Menu, select AutoPark and Enter time delay.
Q   Want to use functions such as OSD, Camera Switching ( Colour/B+W) with foreign controllers
A   Possible by using DIA software and an RS232/485 Interface.
Q   Want to set patrol on a Meridian Dome
A   All 16 presets must be stored for meridian to patrol.
Q   One camera moves while controlling another.
A   Dome addresses need checking to make sure that two are not set to the same address.
Q   Setting camera to certain preset when alarm is triggered.
A   Enter Alarms setup menu ( Menu 3) Select External alarms for External Alarm interfaces, Internal Alarms for
    Matrix alarms. Internal alarms have several possible functions. 1, Standard Alarm. 2, Patrol Alarm. 3, One pass
    Patrol Alarm. 4, Multiple Camera Alarm

Q   How to set dome to go to certain preset and certain time of day.
A   Possible to set timer. Enter Timer Setup menu ( Menu 5) and select required function.
                                                                                                                                      MERIDIAN CONTROLLER MENU CHANGES




                     Version 14 specification menu                                                                Version 15 specification menu
1. Program Presets          Program Presets                                                   1>Set Time/Date    Set Time
                            Erase presets                                                                        Set Date
2. Program Dome Setup       1. Program Patrol Paths       1. Clear Path                       2>Matrix Setup     No Of Cameras
                                                          2. Setup Path                                          No Of Monitors
                            2. Digital Zoom                                                                      Spot Monitors
                            3. Auto U-turn
                            4. Auto Park Time                                                                    Autosequencing
                            5. Auto Patrol Time                                               3>Alarms Setup     Program External
                            6. On Screen Settings         1. Display Text On                                     Program Internal
                                                          2. Display Text Off                                    Veiw Alarm Log
                                                          3. Display Text Top                 4>OSD Setup        Set Mon Title
                                                          4. Display Text Bottom                                 Set Cam Title
                            7. Day / night set up         1. Auto Switch Mode.                                   Test OSD Chips
                                                          2. Black + White Mode                                  Display ON/OFF
                                                          3. Colour Mode                                         Set Format
                                                          4. Zero Lux On                      5>Timer setup      Program Timer 01   Enable Alarms
                                                          5. Zero Lux Off                                        Program Timer 02   Disable Alarms
                                                          6. Switch Level Adjust 1. Lighter                      Program Timer 03   Start Patrol
                                                                                 2. Default                      Program Timer 04   Stop Patrol
                                                                                 3. Darker                                          Start Sequence
                                                          7. Shutter Plus                                                           Stop Sequence
                                                          8. Shutter Minus                                                          Park Dome
                            8. Setup Privacy              1. Zones on                                                               Auto Park Set
                                                          2. Zones off                                                              Auto Park Off
                                                          3. Cursor on / off                                                        Auto Patrol Set
                                                          4. Set / clear screen                                                     Auto Patrol Off
3. Program Matrix Setup     1. Number Of Cameras                                              6>Dome Install     Select Camera      Preset Functions   Program Presets
                            2. Number Of Monitors                                                                                                      Erase Presets
                            3. Spot Monitors                                                                                                           Clear Patrol
                            4. Autosequencing                                                                                                          Setup Patrol
                            5. Protocol select            1. RS485                                                                  Digital Zoom       Toggle on/off
                                                          2. FSK                                                                                       Max value
4. Alarms Setup             1. Program External Alarms                                                                              Auto U-turn
                            2. Program Internal Alarms.                                                                             Auto Park Time
                            3. Veiw Alarm Log                                                                                       Auto Patrol Time
5. Screen Display Menu      1. Set Time                                                                                             OSD Settings       Cam OSD On
                            2. Set Date                                                                                                                Cam OSD Off
                            3. Set Monitor Titles                                                                                                      Cam OSD Top
                            4. Set Camera Titles                                                                                                       Cam OSD Bottom
                            5. Test OSD Chips                                                                                                          Camera Title
                            6. Time + Date Selection                                                                                                   Preset Titles
                            7. Set Display                                                                                                             Zone Titles
6. User Setup Menu          1. No. Of Alarm Interfaces                                                                                                 Zones Toggle
                            2. No. Of Slaves                                                                                                           Zones Clear
                            3. Audible Alarm                                                                                                           Zones Reset
                            4. Quick Preset                                                                                         Day/Night Setup    Auto Switch Mode
                            5. Calibrate Joystick                                                                                                      Black&White Mode
                            6. RS485 Termination                                                                                                       Colour Mode
                            7. Change Passwords                                                                                                        Zero Lux On
7. Test Dome Functions      1. Coms Test                                                                                                               Zero Lux Off
                            2. Dome Setup                                                                                                              Switch Level Adjust     Lighter
                            3. Wiring Check                                                                                                                                    Default
                            4. Speed Test                                                                                                                                      Darker
                            5. Soak Test                                                                                                               Shutter Plus
                            6. Start Patrol                                                                                                            Shutter Minus
8. Keyboard Menu            1. Program Timer 01           1. Enable Alarms                                                          Protocol select    RS485
                            2. Program Timer 02           2. Disable Alarms                                                                            FSK_OLD
                            3. Program Timer 03           3. Start Patrol                                                                              FSK
                            4. Program Timer 04           4. Stop Patrol                                                            Setup Walk Tour    Path Number
                                                          5. Start Sequence                                                         IR Light Peak      950nm
                                                          6. Stop Sequence                                                                             850nm
                                                          7. Park Dome                                                                                 Default
                                                          8. Auto Park Set                                                          Privacy Zones      Zones On
                                                          9. Auto Park Off                                                                             Zones Off
                                                          10. Auto Patrol Set                                                                          Cursor On/Off
                                                          11. Auto Patrol Off                                                                          Set/Clear Screen
                                                                                              7>System Install   No Of Alarm Ints
9. Version Details.                                                                                              No Of Slaves
10. Restore Default Setup                                                                                        Audible Alarm
                                                                                                                 Quick Preset
                                                                                                                 Calibrate Joy
                                                                                                                 RS485 Terminate
                                                                                                                 Engineer Mode
                                                                                                                 Quick Day/Night
                                                                                                                 Change Passwords
                                                                                              8>Test Functions   Select Camera      Comms Test
                                                                                                                                    Reset Dome
                                                                                                                                    Wiring Check
                                                                                                                                    Speed Test
                                                                                              9>Version Detail
                                                                                              10>Restore Setup