Applications
   The 7000/7003 Series of photoelectric smoke alarms
is designed for residential and other occupancies
defined by NFPA 101, including homes, apartments,
hospitals and hotels, in compliance with UL 217 and
NFPA 72. Available in many different models, the
7000/7003 Series is engineered to virtually eliminate
nuisance alarms and deliver outstanding performance
wherever reliable fire protection is required.
   The Gentex 7000/7003 Series provides an exclusive
patented three position test feature that simulates a
0.85% and 3.5% actual smoke condition in full compli-
ance with NFPA 72 and UL 217 standards.
It also provides a maintenance indicator and makes the
100% testing requirement easy.
   Options include self-restoring 135°F fixed tempera-
ture integral or isolated thermals, and Form A/Form C
dry contacts for remote annunciation. Tandem inter-
connection of up to 12 units is available on several
models; tandem interconnection of up to 6 units is
available on “F” models, which activate the dry contacts
from a remote alarm through the tandem wire or a local
alarm.                                                         Approvals
   The 7003 Series provides the temporal 3 evacua-
tion tone as a standard feature. When testing the
7003 Series it may take up to 16 seconds longer to
go in or out of alarm.


 Standard Features
 •   90dBA Solid-State Non-Latching Piezo Horn                  •   BFP (City of Chicago)       • NFPA 72
 •   1 Year Warranty From Date of Purchase                      •   MSFM Listing #1929          • UL 217
 •   Nominal 2.5% Sensitivity                                   •   BS+A/MEA #927-84-SA         • UL 1730
 •   5-to-1 Signal-to-Noise Ratio                               •   CSFM #7257-569:104
 •   Pulsing LED Sensing Chamber
                                                                Also UL 1730 listed for Commercial Residential
 •   Fully Insect Screened                                      and Commercial Residential Multiple-station
 •   Functional Test Switch — Patented Three Position Test      Smoke Alarms.
 •   Horn Frequency 3100Hz (Nominal)
 •   Solid-State LED Condition Indicator
 •   Quick-Disconnect Wiring Harness
 •   Mounting Hardware Adapts to Standard Junction Boxes
 •   Dust Cover to Prevent Contamination During Installation
 •   On-Site Maintenance Washing Program
 •   Temporal 3 Evacuation Sounding Device (7003 Series)
 •   Complies With UBC/UFC (7003 Series)
7000/7200 Series
  Model Number   Part Number   Voltage                          OPTIONS
                                         Local    Integral   Isolated Tandem       Tandem    Form A/C
                                         90 dBA    135°F      135°F    Up To        Up To    Contacts
                                          Piezo   Thermal    Thermal 12 Units      6 Units
  7100            907-1109-2   120 VAC     l                               l
  7100T           907-1110-2   120 VAC     l         l                     l
  7100H           907-1111-2   120 VAC     l                    l          l
  7100F           9071113-2    120 VAC     l                                          l         l
  7100TF          907-1114-2   120 VAC     l         l                                l         l
  7100HF          907-1115-2   120 VAC     l                    l                     l         l
  7200            907-1204-2   220 VAC     l                               l
  7200F           907-1207-2   220 VAC     l                                          l         l
  7200T           907-1205-2   220 VAC     l         l                     l
  7200H           907-1206-2   220 VAC     l                    l          l




7003/7203 Series (Temporal 3 Sounder)

  Model Number   Part Number   Voltage   Local    Integral   Isolated   Tandem     Tandem    Form A/C
                                         90 dBA    135°F       135°      Up To      Up To    Contacts
                                          Piezo   Thermal    Thermal    12 Units   6 Units
 7103            907-1116-2    120 VAC     l                               l
 7103T           907-1117-2    120 VAC     l         l                     l
 7103H           907-1118-2    120 VAC     l                    l          l
 7103F           907-1120-2    120 VAC     l                                         l          l
 7103TF          907-1121-2    120 VAC     l         l                               l          l
 7103HF          907-1122-2    120 VAC     l                    l                    l          l
 7203            907-1208-2    220 VAC     l                               l
 7203F           907-1211-2    220 VAC     l                                         l          l
 7203T           907-1209-2    220 VAC     l         l                     l
 7203H           907-1210-2    220 VAC     l                    l          l




 Notes:

The 7100/7103 Series are round units. Square units as 710/713 also available.
Wiring Diagrams
                                                                                                               7000/7003                                          SERIES

Tandem Wiring Diagram                                                                                   Electrical Specifications
                                 QUICK
                                                                                                        Operating Voltage (7100/7103) . . . . . . . . . . . . . .120 VAC, 60Hz
                                 DISCONNECT
                                 TYPE PLUG                LIMITATIONS:                                                          (7200/7203) . . . . . . . . . . . . . .220 VAC, 50Hz
                   ELECTRICAL
 220 VOLTS
 120 VOLTS
                   BOX
                                       SMOKE
                                                                                                        Operating Current (All Voltages) . . . . . . . . . . . . . . . . . . . .45 mA
 60 HZ                            1                       A Maximum of 12 alarms
                                       ALARM
                                                          (7100/7103, 7100/7103T,
                                                                                                        Operating Current (Relay Options) . . . . . . . . . . . . . . . . . .70 mA
                                  2
                                  3                       7100/7103H, 7200/7203,                        Operating Ambient Temp Range . . . . . . . . . . . . . .40°F to 100°F
                                                          7200/7203T, 7200/7203H)                       Alarm Horn Rating . . . . . . . . . . . . . . . . . . . . . . . . .90dB at 10 ft.
                                                          may be connected together.
                                                          Do not exceed 125 feet
                                                                                                        Nominal Sensitivity . . . . . . . . . . . . . . . . . . . . .2.5% Obscuration
                   ELECTRICAL
                   BOX
                                                          between each detector. Do not                 “F” Auxiliary Relay . . . . . . . . . . .1 Form A & 1 Form C (0.6 amp)
                                       SMOKE              exceed 1125 feet between the                  “T” Integral Thermal (Self-Restoring) . . . . . . . . . . .135°F at 50 ft.
                                  1    ALARM
                                                          first and last detector. NOTE:
                                  2
                                                          Gentex smoke alarms can not                   “H” Isolated Thermal Form A (Self-Restoring) . . . .135°F at 50 ft.
                                  3                                                                     Size . . . . . . . . . . . . . . .Diameter: 6.5 in. OA (5.75 in. at Ceiling)
                                                          be interconnected to detectors
                                                          from other manufacturers.                                                                                    Depth: 2.625 in.
                   ELECTRICAL                             A MAXIMUM OF SIX (6)
                   BOX
                                       SMOKE              ALARMS WITH A RELAY                           Architect & Engineering Specifications
                                 1     ALARM              MAY BE TANDEM INTER-                             The Photoelectric Smoke Alarm shall be a Gentex Model
                                 2                        CONNECTED. (7100/7103F,
                                 3
                                                                                                        ______________ or approved equal which shall provide at least
                                                          7100/7103TF, 7100/7103HF,
                                                          7200/7203F, 7200/7203TF,                      the following features and functions.
                                                          7200/7203HF)                                     1. Nominal sensitivity shall be 2.5%.
                  RED / YEL
                                                                                                           2. The alarm shall utilize an infrared LED sensing circuit which
                  WHT             TO ADDITIONAL
                                  SMOKE DETECTORS
                                                                                                               pulses in 4 to 5 second intervals; when subjected
                  BLK             (MAX 12 ALARMS
                                  PER SYSTEM)
                                                                                                               to smoke the pulse rate shall increase 8 times. After 2 con-
                                                                                                               secutive pulses in smoke, the detector will alarm.
                                                                                                           3. The alarm shall provide minimum 5-to-1 signal-to-noise ratio
                                                                                                               in the optics frame to assure stability of operation in envi-
 Relay Models                              Isolated thermal with optional                                      ronments of high RF and transient conditions.
    Models                                 accessory contacts.                                             4. The sensing chamber shall be fully protected to prevent
    7100/7103F                                                              Models
                                                                            7100/7103H                         entrance of small insects, thus reducing the probability of
    7100/7103TF
    7203/7203F                                                              7100/7103HF                        false alarms.
    7200/7203TF                                                             7203/7203H                     5. A solid state piezo alarm rated at 90dBA at 10ft.
                                                                            7200/7203HF
                                                   SMOKE
                                                                                                           6. A visual LED monitor (condition indicator) will pulse in
   SMOKE                                           DETECTOR
                                                                                  BRN
                                                                                                               normal operation and will remain solid in alarm.
   DETECTOR                      YEL
                                                   HEAT                           BRN                      7. An easily accessible test knob shall be provided. The test
                                                   SENSOR                         GREY
   ACCESS
   CONTACTS
                                 ORN                                              GREY                         knob in the TEST position will simulate an actual smoke
                                 BLU                                                                           condition of approximately 3.4% causing the detector to
   ALARM                         VIO
                                                                                  YEL
                                                                                                               alarm within 20-36 seconds. It will also have the capability of
   CONTACTS                                        ACCESS
                                                   CONTACTS
                                                                                  ORN                          testing to 0.85% as a required minimum. A magnetic switch
                                 VIO/BLK
                                                                                  BLU                          closure or other switch closure, or smoke generating
   TANDEM
                                 RED/YEL
                                                   ALARM                          VIO                          equipment which does not scatter the light beam or test sen-
                                 BLK
                                                   CONTACTS
                                                                                  VIO/BLK
                                                                                                               sitivity is not sufficient.
                                 WHT                                                                       8. The alarm shall have a tandem interconnect capability of up
   POWER                                                                          RED/YEL
                                                   TANDEM                                                      to 12 units or 6 units with relay.
                                                                                  BLK
                                                                                                           9. The manufacturer shall provide other compatible alarm mod-
                                                   POWER
                                                                                  WHT                          els with the following optional features: a) 135°F fixed tem-
  CAUTION:                                                                                                     perature isolated thermal with normally opened contact for
  RED/YELLOW wire to be capped                                                                                 remote connection to local alarm or annunciator; b) 135°F
                                                   RELAY CONTACTS
  when not in use. This wire is for
  tandem connection only. Do not
                                                   RATED LOADS RESISTIVE                                       fixed temperature integral thermal; c) auxiliary Form A/Form
                                                   0.6 AMP @ 125 VAC MAX                                       C relay contacts for initiating remote functions and annunci-
  connect to any other circuit.
                                                   1 AMP @ 24 VDC MAX
                                                   0.3 AMP @ 220 VAC MAX
                                                                                                               ation; d) relay option that is capable of activation by tandem
                                                                                                               interconnect wire. Thermal sensor shall be self-restoring.
                                                                                                           10. Unit must be UL 217 listed for both wall and ceiling mount.
24 units per carton                                                                                        11. Unit shall also meet all requirements of the State of
32 pounds per carton                                                                                           California Fire Marshal.
                                                                                                           All equipment shall be completely factory assembled, wired and
                                                                                                        tested, and the contractor shall be prepared to submit a certified
                                                                                                        letter testifying to this condition.
                                                                                                           Alarms which do not meet all of the requirements of this
                                                                                                        specification will not be considered.
Fire Protection Products: www.gentex.com
10985 Chicago Dr., Box 310, Zeeland, MI 49464
616/392-7195 1-800/436-8391 FAX: 616/392-4219                                                                               Printed on Recycled Paper
Gentex corporation reserves the right to make changes to the product data sheets at their discretion.                                                                        GX0601-2