Product Line Review
1
Product Line Review
2
RS Series
UV & UV / WBIR
Alarm Relay Analog Safe Area use only Fire Sentry still sells a lot of these!
3
RS Series
UV only UV only UV/VIS/WBIR
RS-0010 RS-0010(B)
9 volt battery 12-24 VDC built-in horn non-latching relay NO or NC contacts
RS2-0010 FS2-0010(B)
RS2D-00098 FS2DCR-00098
12-24 VDC latching relay NO or NC contacts
4
12-24 VDC latching relay non-latching relay form C contacts
Model SS2
UV / WBIR / VIS Explosion Proof - Indoor & Outdoor use Internal Self-Test FirePic™ Alarm & Fault Relays FireBus™ RS485 Use Unitized or with CM1-A Controller Versions for specialty applications requiring high speed response, such as Airbag and Munitions manufacturing
5
Model SS2 (Unitized Mode)
(1) FIRE ALARM Relay – NO/NC Normally DeEnergized
(1)
24 VDC
FAULT RELAY– NO/NC Normally Energized
RS-485 FireBus™ Protocol to PC
Note: Sensitivity Setting: 60 feet Electronics Self Test Only
6
Model SS3
Safe Area use
UV & UV / WBIR / VIS
FirePic™ Alarm Relay FireBus™ RS485 Use Unitized or with CM1-A Controller
7
Model SS3
PRODUCT APPLICATIONS
Silane Gas Cabinets Clean Rooms Warehouses Computer Rooms
Note: NEMA 1 Enclosure (Use only in Non-Hazardous Areas)
8
Model SS4
UV & UV / WBIR / VIS Explosion Proof - Indoor & Outdoor use Optical and Internal Self-Test FirePic™
Alarm, Verified Fire & Fault Relays
FireBus RS485 Use Unitized or with CM1-A Controller
Optimized version for Hydrogen, Natural Gas, Methanol & Ethanol Fires
9
Model SS2 & SS4
PRODUCT APPLICATIONS
Petrochemical Plants Refineries Petroleum Product Pipelines Gas Processing Plants Offshore Drilling and Production Platforms Gas Compressor Buildings Petroleum Prod. Pumping Stations Product Storage Terminals
Crude & Product Tank Farms Gas Turbine Enclosures Gas Collection Facilities Marine Terminals Rail Loading & Unloading Terminals Gasoline Loading Terminals LNG & LPG Storage and Distribution Silane Gas Cabinets Silane Gas Storage
10
Aircraft Hangars, Commercial and Military Power Plants Paints & Solvents Storage Aerosol Filling Facilities Cogeneration Plants Warehouses Engine Test Cells Marine Engine Rooms
Model SS4 (Unitized Mode)
(1) FIRE ALARM Relay – NO/NC Normally DeEnergized FIRE VERIFY RELAY – NO/NC Normally De-Energized FAULT RELAY– NO/NC Normally Energized
(1)
(1)
24 VDC
RS-485 FireBus™ Protocol to PC
Note: Factory Sensitivity Setting: 45 feet, (selectable 60, 30 and 15 feet) Through the Lens & Electronics Self Test
11
FS2000 SYSTEM
SS2-A SS4-A
FireBus™ Protocol RS-485 4 Wire Loop
(1) MASTER ALARM RELAY - NO/NC Normally De-Energized
Up to 30 Devices in the Loop
SS3-A CM1-A Controller
(4) PROGRAMMABLE ZONE ALARM RELAYS- NO/NC Normally De-Energized (1) FAULT RELAY - NO/NC Normally Energized RS-232 PC Communication
SS2-A SS4-A
12
120 VAC
Model FS7
The World’s largest selling Fire Detector for Semiconductor Wet Benches! NIR / WBIR / VIS Two Stage Alarm
FM Approved
Leak-proof, Polypropylene Housing Unitized or Controller based versions
Six FirePics™ FireBusII™ RS485
13
Model FS7 System
PRODUCT APPLICATIONS
Clean Rooms Wet Bench Working Surfaces Clean Room Pump & Equipment Area Wet Bench Plenum Area IPA & Chemical Stations
14
Typical Location of Detectors
Head Case
Surface Area detection, including robot deck area across Process Tanks Plenum Area under Process Tanks
Robot Wafer Load and Unload Area Equipment Area behind Wet Bench
15
Model FS7 with FS7-130-SX Controller
FS7-2173 To Next Junction Box Junction Box
(4) Programmable Zone Alarms NC – Normally De-Energized Zone 1 Zone 2 Zone 3 Zone 3 ALARM ALARM ALARM ALARM or ALERT or ALERT or ALERT or ALERT
FS7-130-SX
(1)
FAULT Relay – NC Normally Energized
24 VDC
RS-232 PC Communication
1 to 12 Detectors can be connected to the controller
16
Model FS7 Detector with FSWB Controller
To Next Junction Box Manual Call Station Contact Device
(1) ALERT Relay – NO
(1) FIRE ALARM Relay – NO
FSWB-1 (1) FAULT Relay – NC (1) 24 VDC Releasing Circuit
Junction Box FS7-2173
(1) 24 VDC Annunciator (0.15A) (1) 24 VDC Output (0.1 A)
120 VAC
RS-232 PC Communication
1 to 9 Detectors can be connected to the controller
17
Model FS7-2173-2RP Unitized Fire Detector
(1) ALERT Relay – NO Normally De-Energized
(1)
FIRE ALARM Relay – NO Normally De-Energized
(1)
FAULT Relay – NC Normally Energized
RS-485 FireBus II™ Protocol to PC 24 VDC
18
Model FS10
For use with Electrostatic Liquid and Powder Paint Applications
NIR / WBIR / VIS
Complies with NFPA 33 Explosion Proof - Indoor use
Unitized, Card Controller or Wallmount Control Panel Systems FirePic™ with FireBusII RS-485
19
Model FS10
PRODUCT APPLICATIONS
Electrostatic Liquid Paint Spray Line Electrostatic Powder Coating Booths Paint Drum Storage & Paint Mix Rooms Aerosol Filling Automotive Engine Testing Infrared Curing Ovens Diesel Generators (Indoors) Gas Compressor Stations (Indoors)
20
Model FS10 Wallmount Controller
Primary Application: Paint Booths
120 VAC (1) ALERT Relay – NO/NC Normally De-Energized (0.5 sec Response) FIRE ALARM Relay – NO/NC Normally De-Energized (4 sec Response) FAULT Relay – NO/NC Normally Energized PROCESS SHUTDOWN Relays – NO/NC Normally Energized
(1)
(1) (3)
Note: Detector Sensitivity is 15 or 30 Feet
21
RS-232 PC Communication
Model FS10 Card Controller
General Finishing: Liquid & Powder Coating
120 VAC
(1)
ALERT / FEW Relay NC Normally Energized (0.5 sec Response)
FIRE ALARM Relay – NO Normally De-Energized (4 sec Response)
(1)
(1)
Model 2GF
(1)
MAJOR FAULT – NO/NC Normally Energized
MINOR FAULT – NO Normally De-Energized
Note: Detector Sensitivity: 15 or 30 Feet
22
RS-232 PC Communication
Model FS10-R Unitized Detector
(Relay Output Version)
(1) ALERT Relay – NO Normally De-Energized (0.5 sec Response)
FIRE ALARM Relay – NO Normally De-Energized (4 sec Response)
General Finishing: Liquid & Powder Coating
(1)
(1)
FAULT Relay – NC Normally Energized
24 VDC
RS-485 FireBus II™ Protocol to PC
Note: Detector Sensitivity: 15, 30, or 45 Feet, (no ALERT relay with 45 ft. sensitivity)
23
Model FS10-A Unitized Detector
(Analog Output Version)
ALERT: 12 mA (0.3 sec Response)
General Finishing: Liquid & Powder Coating
ALARM: 20 Ma (4 sec Response) NORMAL: 4 mA FAULT: 0 mA 24 VDC RS-485 FireBus II™ Protocol to PC
Note: Detector Sensitivity: 15, 30, or 45 Feet, (no ALERT relay with 45 ft. sensitivity)
24
Product Line Review
25