Full Report Home Inspection Report 20 Scotts Hill

Document Sample
Full Report Home Inspection Report 20 Scotts Hill Powered By Docstoc
					Home
Inspection
Report
20 Scotts Hill Road
Somerset, MA02

Mason and Associates Ltd
November 7th, 2009




                           Inspection report prepared by:
                             Mason and Associates Ltd
                                    November 7th 2009
                                   Subject Property




                             Front view looking north from roadside




                East                          South                            West




            Inspector Information:                    Client Information:
            Philip Mason, R.Eng.                      Mr & Mrs Homeowner
            Mason and Associates Ltd                  PO Box SD1625
            PO Box HM1477                             Any Parish, SDFX
            Hamilton, HMFX                            In Attendance: Buyer


            Cell: (441) 331-1961                      Cell: (441) 266 - 2665
            Email: pmason@mason.bm
                                                      Home: (441) 344 - 2225
            Web: www.Mason.bm
                                                      Email: homeowner@ibl.bm




IMPORTANT INFORMATION
This report is solely for the benefit of the above mentioned client. Any person or party designated by the
Client to receive information contained in this report shall be subject to the Terms and Conditions con-
tained herein. Such designation shall be provided in writing to the inspector.


                                                                               Inspection report prepared by:
                                                                                 Mason and Associates Ltd
                                                                                        November 7th 2009
General Comments:

This inspection report identifies items in need of attention, maintenance, or repair, which
is the primary function of a home inspection. Overall, it is the inspector's opinion that this
is a quality-built dwelling that is in need of only minor repair to keep it in serviceable con-
dition. Some additional maintenance items may be discovered in the course of repairs,
upgrading, or when the home is vacant. We recommend that you obtain repair estimates
from competent specialists as an aid in planning your future course of action.

The items listed in this report are marked as Satisfactory, In Need of Maintenance, Pro-
fessional Consultation, or Not Satisfactory. The inspector has identified and described
the home's major systems and components, and has listed problems found in readily ac-
cessible areas as explained in the pre-inspection agreement. You should refer to the
pages in this report for information about a specific component or system. This summary
is an overview, not an all-inclusive list of defects found in the dwelling. It is the client's re-




                  Summary of Items in need of Immediate Attention

  •   GFCI’s noticeably absent from garage, laundry area, kitchen, pool pump house, ex-
      terior pump space. Recommend a licensed professional install GFCI’s within 6ft of a
      water source ie. sink, tub, pump or exterior location.

  •   Loose and disconnected grounding wire to main pump in pool pump house. Cor-
      roded electrical connections and missing cover plates. Recommend a licensed pro-
      fessional repair and replace with new.

  •   Severely corroded galvanised hot and cold pipes to washer at sink in garage. Rec-
      ommend replacing with new piping and replace washer hoses with steel braided
      supply lines.

  •   Handyman wiring splice to water heater, no GFCI outlet and missing cover plate.
      Recommend a licensed professional repair and replace with new.

  •   Resin aggregate surface treatment on front steps, side and rear patios shows sig-
      nificant weathering and degradation. Recommend consulting a specialist to repair
      or replace with new.




                                                                             Inspection report prepared by:
                                                                               Mason and Associates Ltd
                                                                                      November 7th 2009
                              Site Grounds & Grading
Our inspection of the Site Grounds and Grading includes the surface drainage, grading, some
fencing, gates, sidewalks, patios, driveways and retaining walls adjacent to the structure. This
inspection is not intended to address or include any geotechnical condition or site stability in-
formation. For information concerning these conditions a structural engineer should be con-
sulted. Any reference to grade is limited to only areas around the exterior of the exposed foun-
dation or exterior walls. This inspection is visual in nature and does not attempt to determine
drainage performance of the site or the condition of any underground piping, including public
water supply or sewer service piping or septic systems. When decks and porches are built
close to the ground where no viewing or access is possible, we cannot make accurate opin-
ions. These areas as well as others that are too low to enter or in some other manner are inac-
cessible, are excluded from the inspection and are not addressed in this report. We routinely
recommend that inquiry be made with the seller about knowledge of conditions.




Driveway
Type:          Asphalt
Condition:     Satisfactory, monitor

Problems
Minor reflection cracking evident in asphalt surface

Comments
There are some medium to large cracks in the asphalt that are       Minor reflection cracking in as-
consistent with the age of the property but they do not affect      phalt surfacing.
functionality of the driveway. These cracks should be sealed
and monitored.




General Grading and Drainage
Condition:     Satisfactory

Problems
No evidence of long term drainage or ponding noted.

Comments
The driveway slopes towards the garage and may present a
temporary problem with stormwater intrusion however the             Driveway slopes to garage
house is somewhat elevated on the lot with gentle to moderate
ground slopes away from the building. Mature vegetation and
no evidence of bare patches in grassed areas.




                                                                        Inspection report prepared by:
                                                                          Mason and Associates Ltd
                                                                                 November 7th 2009
Steps and Landings
Type:         Concrete with resin aggregate
Condition:    Not Satisfactory

Problems
Cracking and degradation of resin bonded aggregate surface

Comments
                                                                Resin bonded aggregate stairs and
Several areas of significant detachment of the aggregate sur-   patios. Signs of delamination
face noted. Loose aggregate indicative of weathering and deg-   cracks and weathering.
radation of resin bonding. Repair or replace surfacing.
Discoloration indicates mold and mildew impregnation.

                                    Cracks in front steps




                             Weathering and general
                             degradation of resin bonding
                             causing erosion of surfacing,
                             generally noted on the west-
                             tern landing and rear patio/
                             stairs.




Fences
Type:         Chain link with mature vegetation
Condition:    Satisfactory

Problems
No problems noted

Comments
Western and northern boundary fencing has mature cherry tree    Mature hedges on western and
which are mature and well maintained. Provides privacy and      northern boundaries
wind breaks.




                                                                   Inspection report prepared by:
                                                                     Mason and Associates Ltd
                                                                            November 7th 2009
Trees and Shrubs
Condition:     Satisfactory and well maintained

Problems
No appears to be no significant risk of tall trees in proximity to
the building or root damage to foundations and walls.

Comments
Keep tree branches and shrubbery well trimmed and away
from the building walls reduces insect infestation.




Retaining Walls
Type:          Bermuda Stone - southern boundary
               Concrete masonry - pool area

Condition:     Satisfactory and well maintained

Problems
No signs of movement or cracking noted.
                                                                     Block wall around pool
Comments
Dry stone wall at the front (southern boundary) appears satis-
factory. Monitor of movement and dislocation of stone over
time. CMU wall around pool area is well maintained and shows
no signs of cracking or movement.




                                                                       Inspection report prepared by:
                                                                         Mason and Associates Ltd
                                                                                November 7th 2009
                              Exterior and Structure
The inspection of the exterior of the building includes the cladding/walls, trim, eaves, soffits,
fascias, decks, porches, downspouts, railings, doors, windows and shutters.. Areas hidden
from view by finished walls or stored items cannot be judged and are not a part of this inspec-
tion . Minor cracks are typical in many foundations and most do not represent a structural prob-
lem. If major cracks are present and indicate significant movement we routinely recommend
further evaluation be made by a registered structural engineer. All concrete slabs experience
some degree of cracking due to shrinkage in the drying and curing process or minor settle-
ment. All items listed are inspected for their proper function, poor installation, excessive wear
and general state of repair. Where deck carpeting, stacked firewood, excessive vegetation, soil
and other coverings are installed over decking and patio surfaces, the materials or their nature
of construction and condition cannot be determined.




Building Information
Year Constructed:     circa 1950
Type of residence:    Single family

Exterior Wall Structure
Type:          Bermuda stone, quarried on site
Condition:     Satisfactory
Covering:      Sand : Cement plaster typical of local construction
Comments:      This component appears to be functioning adequately




Exterior Switches and Receptacles
Type:          Exterior covered switch.
Condition:     Need of maintenance.

Type:          Pump outlet
Condition      Not Satisfactory. Replace with GFCI

Problems
Pool light switch shows signs of aging, corrosion is staining ex-
terior paint finish.

Comments                                                                    Pool light switch
Replace water pump outlet with a covered GFCI outlet, cor-
rectly grounded. Pool light switch shows aging and wesr.
should be replaced.




                                                                       Inspection report prepared by:
                                                                         Mason and Associates Ltd
                                                                                November 7th 2009
Exterior Windows and Shutters
Type:          Double pane, aluminium/vinyl clad
Condition:     Satisfactory
Shutters:      Aluminium

Problems
Windows and shutters appear fairly new. No problems noted
                                                                   Typical window and shutter.
Comments
A representative sampling of windows and shutters were in-
spected and all functioned as intended. Smooth opening and
closing, no cracks or broken seals noted and all had function-
ing locks. All screens on the representative sampling were in-
tact and functioning.



Exterior Doors
Type:          Solid wood
Condition:     Satisfactory

Problems
No problems noted

Comments
All three exterior doors appear to be newly installed. All hard-
ware and locks functioned adequately and doors were installed
with wide view peep holes for added security.
                                                                        Rear exterior door




Eaves, Soffits, Fascia and Trim
Type:          Wood, typical of Bermuda construction
Condition:     Need of maintenance

Problems
Light mildew on exposed eaves.

Comments
The building has exposed and painted eaves as is typical of
Bermuda construction. Eaves show minor discoloration from
mildew. Recommend a mild bleach solution wash.
There were no other wood soffits, fascia and trim noted.


                                                                      Inspection report prepared by:
                                                                        Mason and Associates Ltd
                                                                               November 7th 2009
Miscellaneous
Front porch column posts
Type:         Metal pipe

Condition:    Need of maintenance

Problems
Corrosion noted at the base of column posts

These hollow structural sections support the upper veranda.
Corrosion was evident at the base junction of pipe and bearing
masonry. Clean and expose metal, prime and paint. If signifi-
cant corrosion we recommend consulting registered engineer.




                    Small section of step lead-
                    ing to upper veranda shows
                    minor dry rot. Needs repair
                    and monitoring.




                     Area of veranda has hard calcite
                     scaling probably from rainwater
                     drainage over years. Consult spe-
                     cialist for removal.




                      Horizontal crack in roof slab at
                      pool pump room. Monitor.




                                                                 Inspection report prepared by:
                                                                   Mason and Associates Ltd
                                                                          November 7th 2009
                                  Roofing Components
The inspection of the roofing system includes a visual examination of the surface materials,
connections, penetrations and roof collection systems. We examine the roofing surface for
damage, deterioration and possible leaks. We may offer opinions concerning repair and or re-
placement if warranted. Opinions stated herein concerning are based on the general condition
of the roof as evidenced by our visual inspection. These do not constitute a warranty that the
roof is or will remain free of leaks. All roofing systems require regular and routine maintenance
and failure to perform routine maintenance or visual inspections after high winds may result in
leaks and accelerated deterioration of the roof and its components. The only way to determine
whether a roof is absolutely watertight is too observe it’s performance during heavy and pro-
longed rainfall. Many times this situation is not present during our inspection. We recommend a
visual inspection in the roof crawl space during heavy and prolonged rain to identify potential
leaks and water staining.




Roof Style
Bermuda hipped typical 7:12 pitch

Materials
Bermuda slate covering
2x8 rafters on 16” cts
2x4 collar ties at 2/3 height

Gutters and Downspouts                                              Discoloration on flat veranda roof
Gutter guides - slate
Downspouts - exterior cast iron

Problems
Minor hairline cracking in roof slate at two locations previously
repaired. Minor discoloration to flat portions of roof.

Comments
Previous repairs need attention in two to three locations. Re-
coat and monitor. Roof shows only minor discoloration in select     Discoloration on flat veranda roof
areas. Recoating recommended within 12-18 months. There
were no other external roof attachments such as antennae,
chimneys etc.




                    Hairline cracking at site of previous re-
                    pair. Recoat and monitor.




                                                                        Inspection report prepared by:
                                                                          Mason and Associates Ltd
                                                                                 November 7th 2009
Framing
Type:         2x8 rafters, 2x4 collar ties on 16” cts
Condition:    Satisfactory


Problems
No problems noted.
                                                                   Solid, dry roofing members. No
Comments                                                           signs of wood boring insect infes-
Access to the roof crawl space was through a scuttle hatch lo-     tation
cated in the front bedroom closet ceiling.

Timber appeared solid, dry and free of insect infestation. Some
collar ties were nailed to rafters in lieu of recommended car-
riage bolts but overall construction and workmanship looked
sound.




                                                                  Bolted collar tie to rafter connec-
                                                                  tion.




                                                                      Inspection report prepared by:
                                                                        Mason and Associates Ltd
                                                                               November 7th 2009
                     Electrical Systems & Components
Our examination of the electrical system includes a visual examination of the exposed and ac-
cessible branch circuits, wiring, service panel, over current protection devices, lighting fixtures,
switches and receptacles. Service equipment, proper grounding, wiring methods and bonding
are focal points. We inspect for adverse conditions such as lack of grounding and bonding,
over-fusing, exposed wiring, open-air wire splices, reverse polarity and defective GFCI’s. The
hidden nature of the electrical wiring prevents inspection of every length of wire or their con-
nections. Telephone, video, cable, audio, security systems and other low voltage systems were
not included in this inspection. We recommend you have the seller or a specialist demonstrate
the serviceability or locations of these systems to you if necessary. Any electrical repairs at-
tempted by anyone other than a licensed electrician should be approached with caution. Op-
eration of time clock motors is not verified. Inoperative light fixtures often lack bulbs or have
dead bulbs installed. Light bulbs are not changed during the inspection. Smoke alarms should
be installed within 15 feet of all bedroom doors and in bedrooms and should be hard wired to-
gether in series of have 10 year lithium batteries.




Service Entrance Cable
Capacity:      200 amps
Location:      Underground supply, rear garage wall,
Material:      Copper
Volts:         120/240
Condition:     Satisfactory

Problems
No problems noted.

Comments
The main breaker and panel are located at the rear of the ga-
rage. Access to the panel must be kept clear of obstructions at
all times.

                                                                      200 amp supply, main breaker
                                                                      and Belco meter in garage.




                                                                         Inspection report prepared by:
                                                                           Mason and Associates Ltd
                                                                                  November 7th 2009
Main Panel
Condition:             Satisfactory
Volts:                 120/240
Capacity:              200 amps
Overload Protection:   Circuit breakers
Grounding:             Copper rod
Location:              Garage

Problems
No problems noted.

Comments
Wiring and layout does not suggest homeowner/handyman in-
stallation. No evidence of scorching, fusing or melted insula-
tion. Wire sizing appears adequate for circuit loads.            200 amp panel




Pool House
Type of wiring:        Romex
Condition:             Not Satisfactory

Problems
Corrosion, loose grounding, no cover plates, exposed wiring
connections.

Comments                                                         Pool house pump plug. No cover,
Replace corroded connections with new and reseal/relocate all    needs a GFCI. Plug is corroded
                                                                 and should be replaced.
pool chemicals. Install GFCI’s and cover plates.




                                          Severe corrosion

                                                                 Pool pump house.

                        Exposed wire connections




                                                                     Inspection report prepared by:
                                                                       Mason and Associates Ltd
                                                                              November 7th 2009
Pool House (cont)
Condition:            Not Satisfactory

Problems
Grounding wire loose and disconnected

Comments
Consult an electrician to ensure electrical equipment is cor-
                                                                 Pool house pump



                                 Loose grounding wire




Outlets & Switches
Condition:            Not Satisfactory



Problems
No GFCI’s, open junction boxes

Comments
                                                                Outlet too close to washer drain.
GFCI’s should be installed within 6ft of a water source ie,     Reposition and replace with
                                                                GFCI.


                           Relocate washer
                           drain away from out-
                           let. Install GFCI out-
                           let within 6ft of sinks




                          Open junction box in
                          garage




                            Open junction box in
                            roof space above ceil-
                            ing.




                                                                    Inspection report prepared by:
                                                                      Mason and Associates Ltd
                                                                             November 7th 2009
Smoke Detectors
Condition:    Need of maintenance/upgrade
Type:         Battery operated
Not tested

Problems
Upgrade smoke detectors

Comments
Modern codes call for smoke detectors to be hard wired in se-
ries with battery backup or 10 year lithium battery type.




                                                                Inspection report prepared by:
                                                                  Mason and Associates Ltd
                                                                         November 7th 2009
                         Plumbing Systems & Components
Our inspection of the plumbing system includes a visual examination of the exposed portions
of the domestic water supply, drain waste, vent, gas lines, faucets, fixtures, drains, traps, ex-
posed pipes and fittings. These items are examined for proper function, excessive or unusual
wear, leakage and general state of repair. The hidden nature of piping prevents inspection of
every pipe and joint connection, especially in walls, floors and ceiling voids. This inspection
does not include irrigation systems, water wells, septic disposal systems (cesspits) unless spe-
cifically noted. Our inspection of the water heater includes a visual examination of the accessi-
ble portions of the tank, gas, electrical and /or water connections, venting and safety valves.
These items are examined for proper function, excessive or unusual wear, leakage and gen-
eral state of repair.




Water Supply
Tank:             Above ground, front veranda
Capacity:         10,000 Imp gal
Condition:        Clean with only minor sediment
Piping:           Galvanised and PVC mix
Access:           18x24 galv cover at front veranda

Problems
No problems noted.                                                             Tank access located under front
                                                                               veranda steps. Tank is shape of
                                    Tank access
                                                                               veranda and approx . 9 ft deep.



Pump:                      GE 1/2 HP
Age:                       10 yrs approx
Condition:                 Satisfactory

Pressure Tank::            20 gal, pre-pressurized
Age:                       Unknown
Condition:                 Satisfactory

Piping:                    PVC and galv. Mix
Condition:                 Marginal


Comments:
This inspection did not include operation of valves (not tested). Pump func-
tioned normally between high and low pressure controls. Pump power
switch on adjacent wall.




                                                                                   Inspection report prepared by:
                                                                                     Mason and Associates Ltd
                                                                                            November 7th 2009
Well Water System
Condition:             Unknown

Problems
Pressure gauge seal is broken. Replace

Comments
The well water system is not included in this inspection


                                                                           Well water supply equip-
                                                                           ment located in garage.
                                                                           Submersible pump lo-
                                                                           cated under access in
                                                                           driveway. Not tested or
                                                                           inspected.




Septic System
Type:          Cesspit
Condition:     Unknown

Comments
The septic system is not included in this inspection but the lo-
cation of the cesspit was noted to be in the back approx 20ft

                                                                   Cesspit surrounded by shrubs.




                                  Cesspit vent




                                            Grease trap


                                                                   Grease trap appears to be func-
                                                                   tioning adequately.




                                                                       Inspection report prepared by:
                                                                         Mason and Associates Ltd
                                                                                November 7th 2009
Water Heater
Make:         Unknown, Electric
Capacity:     30 gal
Age:          2002
Condition:    Not Satisfactory

Problems
Handyman splice needs correction. Extend safety relief valve .




                Wiring to water heater need attention. Con-
                sult a licensed electrician.




                Relief valve needs to have extension to
                within 6” of ground and facing away from
                observer.




                                                                 Inspection report prepared by:
                                                                   Mason and Associates Ltd
                                                                          November 7th 2009
 Piping
 Type:          Galvanised
 Condition:     Not satisfactory


 Problems
 Severe corrosion

 Comments
 Galvanised piping on hot and cold supply lines to washer in ga-
 rage need replacing.                                                 Severe corrosion in supply
                                                                      lines.




Soil Line Piping
Type:          Cast Iron
Condition:     Need of Maintenance


Problems
Corrosion noted. Inadequate supports

Comments
Monitor for leakage especially at joint connections. Add addi-     Strap support to cast iron pipe
tion strap supports at 36” spacing.                                corroded. Replace with new
                                                                   and space max. 36” for ade-
                                                                   quate support.




                                                                           Inspection report prepared by:
                                                                             Mason and Associates Ltd
                                                                                    November 7th 2009
                        Heating and Cooling Systems

Typically Bermuda homes do not have central heating and cooling. Split unit systems with heat
pumps are common. Our inspection of the mechanical heating and cooling is visual and lim-
ited in scope to the following conditions: Window and/or wall mounted air conditioning units are
not inspected. The cooling supply adequacy or distribution balance are not inspected. Pressure
tests on coolant systems are not within the scope of this inspection and no representation is
made regarding coolant charge or line integrity. Judgment of system efficiency or capacity fall
outside the scope of this inspection. Cooling systems are not dismantled in any way and ac-
cess covers are not removed.. The interior components of evaporators, condensers and heat
pumps are not viewed. The presence of leaking refrigerant lines, heat pump oil is outside the
scope but we will note any obvious signs of malfunction.




Air Conditioning
Type:         Split unit systems, heat pumps
Qty:          Four
Location:     East side of building
Interior:     Kitchen, living room, bedrooms


Unit #1
Make:         Sanyo
Model:        CH0951
Breaker:      15 amp
Age:          2000
Condition:    Satisfactory


Unit #2
Make:         Sanyo
Model:        CH1222
Breaker:      20 amp
Age:          1994
Condition:    Satisfactory but reaching end of useful life, cor-
rosion

Unit #3
Make:         Sanyo
Model:        CMH1822
Breaker:      30 amp
Age:          1994
Condition:    Satisfactory but reaching end of useful life, cor-
rosion

                                                                      Inspection report prepared by:
                                                                        Mason and Associates Ltd
                                                                               November 7th 2009
Unit #4
Make:        Sanyo
Model:       C0951
Breaker:     15 amp
Age:         Unknown
Condition:   Satisfactory

Comments: (General)
Insulation showing signs of age and weathering. Recommend
re-insulate exterior exposure and have systems checked for
leaks.




                                                             Inspection report prepared by:
                                                               Mason and Associates Ltd
                                                                      November 7th 2009
                                 Interior Components
Our inspection of the interior includes a visual inspection of the readily accessible portions of
the walls, ceilings, floors, doors, cabinetry, countertops, steps, stairways, balconies and rail-
ings. A representative sample of the accessible windows and electrical receptacles are in-
spected. Plumbing faucets, fixtures, drains, and traps in the kitchen and bathrooms/laundry
room are visually inspected. These features are examined for proper function, excessive wear
and general state of repair. Please note the inspector is not required to operate shut off valves.
In some cases all or portions of these components may not be visible because of furnishings
and personal items. In these cases some of the items may not be inspected. The condition of
walls behind wall coverings, paneling and furnishings cannot be judged. Only the general con-
dition of visible portions of floors is included in this inspection. As a general rule, cosmetic defi-
ciencies are considered normal wear and tear and are not reported. Determining the source of
odors is not part of the inspection. Floor covering damage or stains may be hidden by furniture.
The condition of underlying floor covering s is not inspected. Determining the condition of insu-
lated glass windows is not always possible due to temperature, weather and lighting condi-
tions. Fireplaces should be cleaned and inspected on a regular basis by a qualified profes-
sional.


General Information
Bedrooms:              Two, third converted to home/office
Bathrooms:             Two
Kitchen:
Living Room:
Hallway:

Floors:
Condition:             Satisfactory
Type of flooring:      Carpet over wood, generally

Walls:
Condition:             Satisfactory, no visible cracks of efflorescence.
Type:                  Masonry, plaster, paint

Ceilings:
Condition:             Satisfactory
Type:                  Tray, plaster on rock lath

Interior Doors:
Condition:             Generally satisfactory. End bedroom door sticks top corner
Type:                  Hollow core, varnish finish

Windows:
Condition:             Satisfactory. Appear new and all functioning well with locks,
                       screens intact


                                                                           Inspection report prepared by:
                                                                             Mason and Associates Ltd
                                                                                    November 7th 2009
Moisture and Mildew
None noted.

Fireplace
No fireplace

Laundry Room
No interior laundry facilities




Kitchen
Condition:       Satisfactory
Flooring:        Satisfactory, Sheet vinyl over wood
Countertop:      Satisfactory, Formica
Cabinets:        Satisfactory, Solid wood, plywood, custom
Sink:            Satisfactory, single, aluminium
Receptacles:     Recommend upgrading to GFCI’s
Exterior Door:   Solid wood, operational
                                                             Wall Cabinets
Range/Oven: Good condition, gas, operational
Refrigerator: Satisfactory, operational
Dishwasher: Satisfactory, operational
Microwave: Satisfactory, operational
Disposal:     None
Trash compactor:     None
Ventilation:  None. Ceiling fan plus split unit AC

Problems
None noted
                                                              Split unit AC, heat pump


Living Room
Condition:       Satisfactory
Flooring:        Satisfactory, carpet over wood
Ext Door:        Solid wood, operational


Problems
None noted




                                                                  Inspection report prepared by:
                                                                    Mason and Associates Ltd
                                                                           November 7th 2009
Bedroom (front)
Condition:     Satisfactory
Flooring:      Carpet over wood
Walls:         Masonry, plaster, paint
Ceiling:       Tray
Ventilation:   Windows, ceiling fan, split unit AC heat pump

Problems
None noted
                                                               Split unit AC



Bedroom/Office
Condition:     Satisfactory
Flooring:      Carpet solid slab
Walls:         Masonry, plaster, paint
Ceiling:       Tray
Ventilation:   Windows, ceiling fan, split unit AC heat pump

Problems
None noted



Bedroom (rear)
Condition:     Need of Maintenance
Flooring:      Carpet over solid slab
Walls:         Masonry, plaster, paint
Ceiling:       Tray
Ventilation:   Windows, ceiling fan, split unit AC heat pump

Problems
Entry door sticks top corner

Comments:
Bathroom attached




                                                                  Inspection report prepared by:
                                                                    Mason and Associates Ltd
                                                                           November 7th 2009
Bathroom (front)
Condition:     Satisfactory in general
Flooring:      Tile
Walls:         Marlite over masonry
Ceiling:       Flat, plaster rock lath
Ventilation:   Window
Toilet:        Need of Maintenance
Tub/Shower:    Satisfactory
Sink:          Satisfactory
                                          Well water flushing
Problems
None noted

Comments
Shut off valve to toilet appears to be worn and dated. Recom-
mend replacing. No mold or mildew present. Water pressure
through faucets is normal and adequate. Drains appear free
flowing and normal.




Bathroom (Rear)
Condition:     Satisfactory in general
Flooring:      Tile
Walls:         Marlite over masonry
Ceiling:       Flat, plaster rock lath
Ventilation:   Window
Toilet:        Need of maintenance - shut off valve
Tub/Shower:    Need of Maintenance - pressure and flow are
               low.
Sink:          Satisfactory

Problems
Water pressure and flow from the shower are low.

Comments
Shut off valve to toilet appears to be worn and dated. Recom-
mend replacing. No mold or mildew present. Water pressure
through sink faucets is normal and adequate. Drains appear
free flowing and normal. Recommend plumber inspect and ad-
just for flow in shower.
                           Unusual arrangement for gate valve sug-
                           gests faucets may not be functioning cor-
                           rectly. Plumber to inspect




                                                                       Inspection report prepared by:
                                                                         Mason and Associates Ltd
                                                                                November 7th 2009

				