Cooling Rittal liquid cooling package

Document Sample
Cooling Rittal liquid cooling package Powered By Docstoc
					           Cooling
           Rittal liquid cooling package

                                                                                                                                      B1
                                                                                                                          T1




                                                                                                                                       H1
                                                                                                               B2
                                                                                                      T2




                                                                                                 H2
                                                                                                                        B = Width
                                                                                                                        T = Depth




           Modular, upgradable and                     ● Optionally 1 or 2 server racks         Technical specifications:                       ● Control via a separate mod-
           temperature-neutral cooling                   may be cooled – stand-alone            ● Mounted as a cooling rack on                    ule which may be connected
           concept.                                      and bayed siting possible.               a server rack based on TS 8,                    to the CMC-TC for incorpora-
           ● Max. 12 kW cooling output,                ● Bayable to TS and PS server              with H = 2000 mm,                               tion into the network (monitor-
             with three cooling modules                  racks, even retrospectively.             D = 1000 mm.                                    ing).
             possible per cooling rack.                ● Active condensate handling.            ● Each cooling rack can                         ● Condensation management:
           ● Approx. 4 kW cooling output               ● Optional control and                     accommodate a maximum of                        The pump in the condensate
             per cooling module at                       monitoring1) of the cooling              three air/water heat                            tray pumps any condensation
             800 m3/h air throughput.                    rack via Rittal CMC-TC.                  exchanger cooling modules.                      into the return section of the
           ● Optimised air routing:                    ● Two-piece modules; for easy            ● Standard supply: Cooling rack                   cooling circuit.
             Cold air is blown in at the                 installation in narrow passage-          equipped with one cooling
             sides, so that the cold air is              ways.                                    module.
             evenly distributed in front of                                                     ● Individual modules upgrad-
             the 482.6 mm (19″) level.                                                            able to full installation via
                                                                                                  quick-release couplings.

                                                                                                Enclosure + 3 modules                                Individual module for 230 V/115 V
 B         Model No. SK                                                   3301.230                            3301.210                               3301.250

4.8        Rated operating voltage V, Hz
                                                                    W 300
                                                                          230, 50/60                          115, 50/60                             230, 50/60
                                                                                                                                                     250
           Dimensions in mm                                         H 2000                                                                           550
 Cooling




                                                                    D 1000                                                                           950
           Useful cooling output
                                                                          4000 W/3500 W                       4000 W/3500 W                          4000 W/3500 W
           at 15°C water inlet, 15 l/min, 20°C cold air


           Rated current max.                                             1.8 A
           Pre-fuse T                                                     5.0 A
           Cooling medium                                                 Water (specifications may be found on the Internet)
           Water inlet temperature                                        +5°C to +30°C
           Permissible operating pressure p. max.                         2 to 8 bar
           Temperature range                                              +5°C to +40°C
           Protection category to EN 60 529/10.91                         IP 30                                                                      –
           Duty cycle                                                     100 %
           Type of connection                                             Current: Connection cable with earthing-pin plug: Water: 3/4″ quick-release fastener
           Weight                                                         max. 160 kg                                                                approx. 25 kg
           Colour                                                         RAL 7035
           Air throughput of fans                                         max. 2400/2100 m3/h                                                        800/700 m3/h
           Temperature control                                            Electronically controlled magnetic valve and 4-way fan control
           1) Flow, leakage, inlet/return, intake/exhaust temperature.
           The general remarks on air/water heat exchangers (available on the Internet) apply.


           For professional installation of the heat exchanger, where possible, the enclosures being cooled should be sealed against the ingress of ambient air:
                                                                           Packs                                                                                      Packs
           Description                                Dimensions in mm           Model No.      Description                                    Dimensions in mm             Model No.
                                                                             of                                                                                         of
           Side panel, screw-fastened                 H x D 2000 x 1000      2     8100.235     Divided partitioning plate for retro-                    600 x 1000     1     7825.300
                                                                                                                                              WxD
                                                            600 x 2000       1    8610.6002)    spective sealing in the base area                        800 x 1000     1     7825.302
           Glazed door                                WxH
                                                            800 x 2000       1    8610.8002)    Divided roof plate                                       600 x 1000     1     7826.6053)
                                                                                                                                              WxD
                                                            600 x 2000       1    7824.2052)    for cable entry                                          800 x 1000     1     7826.8053)
           Sheet steel door, solid                    WxH                                       Sealing kit for two-sided
                                                            800 x 2000       1    7824.2072)                                                                          1 set   7825.305
                                                                                                cooling when bayed
           2) Alternatively: Sealing kit for vented   WxH   600 x 2000       1     7824.185
           sheet steel doors, size                    WxH   800 x 2000       1     7824.187     3) Retrospective    installation is not possible.

           Accessories Page 657 Recooling systems From page 606 Server enclosures From page 734 Configuration software Page 1063

           672                                                                                                                              Rittal Catalogue 31/System climate control