Metal Systems, Inc.
1919 Polymer Drive Chattanooga, TN 37421 423-894-9268
MSI Equipment Centers, Inc.
1318 Bammel Road Houston, TX 77073 832-295-1200
Bulletin EC-100SS Insulated EquipmentCenter (Stainless Steel)
Application:
These units are designed for protection of equipment in corrosive environments. Applications include petrochemical, pulp & paper, wastewater treatment, mines & quarries, and general industrial locations. Product features the use of Type 304 stainless steel roof and exterior walls which has demonstrated superior corrosion resistance in industrial environments. Since these units are intended for corrosive environments a hot dip galvanized based and regular stainless steel doors are also included.
Construction:
• • • • • • • Welded structural steel base frame o Hot Dip Galvanized ¼” steel floor with anti-skid coating 18GA type 304 stainless steel interlocking panel constructed wall and roof 18GA G90 galvanized interior wall liner 18GA G90 galvanized interior ceiling Removable lift lugs at the base Insulation o Walls – R11 o Ceiling – R11 o Floor – R8
Doors
• (2) 18GA Type 304 Stainless Steel 3080 door o Closer w/ Hold open device o Neoprene weather strip mechanically fastened in place o Aluminum Threshold o Stainless steel drip shield o Stainless Steel Panic Hardware
Finish
• Exterior and interior are painted with an epoxy primer and a polyurethane top coat. Standard color is white interior and ANSI-70 Gray exterior. Floor is coated with nonskid ANSI-61 Gray epoxy. Base is coated with bituminous undercoating. o Walls and roof can have an optional #3 brushed stainless steel finish
Electrical:
• Interior Lighting - Fluorescent lights 34W 2 lamp wrap around fixtures
4/7/2008 Bulletin EC-100SS Insulated Equipment Center (Type 304SS).doc Page 1 of 5
Metal Systems, Inc.
1919 Polymer Drive Chattanooga, TN 37421 423-894-9268
MSI Equipment Centers, Inc.
1318 Bammel Road Houston, TX 77073 832-295-1200
• • • •
(2) Switches with adjacent GFCI receptacles EMT conduit (Per ANSI C80.3) / THHN wiring Panel board- 208Y/120V, 125A Main, 3 phase, 4 wire, plug-in breakers (spares by others), surface mount, 10kAIC Ground pads – (2) stainless steel 2-hole NEMA type with lugs located on opposite corners of the base
Design:
• • • • • • • • • Area classification – o General Purpose / Non-Hazardous o Corrosive Floor Loading- 250psf LL+DL Roof Loading- IBC Code, 30psf Wind Velocity- International Building Code, 100 mph, Exposure C Seismic- International Building Code Anchoring- Minimum at each removable lift lug Complete set of as-built drawings in AutoCAD format or prints
Equipment Installation Services:
None
HVAC:
Wall mount air conditioner with heat o Thermostat
Accessories
• Stock units and (1) floor cutout. Consult factory for locations. Additional floor cutouts can be added to build to order units.
Fire / Safety
• • • • • • • • • • None
Notes
Optional Accessories: (Call for pricing) Additional personnel or equipment access doors Windows Special door sizes and hardware Equipment installation Floor cutouts Vinyl floors or electrical grade rubber mat Acoustical ceilings Wall or roof penetrations
4/7/2008
Bulletin EC-100SS Insulated Equipment Center (Type 304SS).doc Page 2 of 5
Metal Systems, Inc.
1919 Polymer Drive Chattanooga, TN 37421 423-894-9268
MSI Equipment Centers, Inc.
1318 Bammel Road Houston, TX 77073 832-295-1200
• • • • • • • • •
Plumbing Fire detection and suppression systems Computer floors Platforms and stairs Aluminum or stainless steel construction Custom sizes (length, width, ceiling, etc..) Multiple shipping piece design Alternate insulation levels Custom color schemes
Bulletin EC-100SS Insulated Equipment Center (Type 304SS).doc Page 3 of 5
4/7/2008
Metal Systems, Inc.
1919 Polymer Drive Chattanooga, TN 37421 423-894-9268
MSI Equipment Centers, Inc.
1318 Bammel Road Houston, TX 77073 832-295-1200
Standard Sizes
Catalog # EC10x08SS EC15x08SS EC20x08SS EC25x08SS EC30x08SS EC35x08SS EC40x08SS EC10x10SS EC15x10SS EC20x10SS EC25x10SS EC30x10SS EC35x10SS EC40x10SS EC10x12SS EC15x12SS EC20x12SS EC25x12SS EC30x12SS EC35x12SS EC40x12SS "A" Feet 10 15 20 25 30 35 40 10 15 20 25 30 35 40 10 15 20 25 30 35 40 "B" Feet 8 8 8 8 8 8 8 10 10 10 10 10 10 10 12 12 12 12 12 12 12 HVAC Tons 1 2 2.5 3 3.5 4 5 1.5 2 2.5 3 3.5 4 5 1.5 2 2.5 3 4 5 6 Lights 2 3 4 5 6 8 9 2 3 4 5 6 8 9 2 3 4 5 6 8 9 Lift Lugs 4 4 4 6 6 6 6 4 4 4 6 6 6 6 4 4 4 6 6 6 6
Bulletin EC-100SS Insulated Equipment Center (Type 304SS).doc Page 4 of 5
4/7/2008
Metal Systems, Inc.
1919 Polymer Drive Chattanooga, TN 37421 423-894-9268
MSI Equipment Centers, Inc.
1318 Bammel Road Houston, TX 77073 832-295-1200
Bulletin EC-100SS Insulated Equipment Center (Type 304SS).doc Page 5 of 5
4/7/2008