IMPROVEMENTS TO PUBLIC SCHOOL “MECANICA DE AVIACION MIGUEL SUCH

Document Sample
IMPROVEMENTS TO PUBLIC SCHOOL “MECANICA DE AVIACION MIGUEL SUCH Powered By Docstoc
					IMPROVEMENTS TO PUBLIC SCHOOL “MECANICA DE AVIACION MIGUEL SUCH”
                            (PRAMI)
School Name:   Escuela de Mecánica de Aviación Miguel Such
Location:      Roosevelt Roads Base, Ceiba, Puerto Rico

                                    LOCATION PLAN




                                             MAP




                                     Page #1 of 14
IMPROVEMENTS TO PUBLIC SCHOOL “MECANICA DE AVIACION MIGUEL SUCH”
                            (PRAMI)
School Name:              Escuela de Mecánica de Aviación Miguel Such
Location:                 Roosevelt Roads Base, Ceiba, Puerto Rico

                                                 Actual Condition Images
PHOTO NO. 1: Aerial substation that will connect to Building              PHOTO NO. 2: Corroded structural members located in Building
#376.                                                                     #376




PHOTO NO. 3: Corroded structural members located in Building              PHOTO NO. 4: Corroded structural members located in Building
#376.                                                                     #376.




Comments:
1.   Demolition and disposal of corroded material located in Building #376. See Photos #2, 3, 4 and Exhibit A-1 (Cost Breakdown), item #2..
2.   Provide potable water storage tank along with pumping system to provide potable water to Building #376. See Exhibit A-1 (Cost
     Breakdown), item #3.
3.   Refer to list of requirements prepared by the Puerto Rico Fire Department for Building #376. See Exhibit A-1 (Cost Breakdown), item #4.
4.   Provide sixteen (16) new fire extinguishers CO2 type 10 lbs.
5.   Provide six (6) new fire extinguishers ABC type 10 lbs.
6.   Provide electrical connection from the aerial substation to a switching unit next to Building #376. Contractor shall coordinate and obtain
     the approval of the Puerto Rico Ports Authority of any electrical work to be done under this contract. See photo #1 and Exhibit A-1 (Cost
     Breakdown), item #1.


                                                          Page #2 of 14
IMPROVEMENTS TO PUBLIC SCHOOL “MECANICA DE AVIACION MIGUEL SUCH”
                            (PRAMI)
School Name:              Escuela de Mecánica de Aviación Miguel Such
Location:                 Roosevelt Roads Base, Ceiba, Puerto Rico

                                                 Actual Condition Images
PHOTO NO. 5: Touch-up paint required at exterior walls of                PHOTO NO. 6: Touch-up paint required at exterior walls of
Building #376.                                                           Building #376.




PHOTO NO. 7: Sections of roof insulation located at Building             PHOTO NO. 7A: Section of detached roof insulation and loose
#2052 that are loose.                                                    mechanical ductwork in Building #2052.




Comments:
1.   Provide touch-up paint at exterior walls of Building #376. See photos #5, 6 and Exhibit A-1 (Cost Breakdown), item #5.
2.   Repair and/or replace A/C unit at Building #2052. See Exhibit A-1 (Cost Breakdown), item #6.
3.   Repair and/or replace 4259 ft2 of roof insulation located in Building #2052. See photo #7, 7A and Exhibit A-1 (Cost Breakdown), item #7.
4.   Provide potable water storage tank along with pumping system to provide potable water to Building #2052. See Exhibit A-1 (Cost
     Breakdown), item #8.
5.   Remove existing plumbing fixtures, mirror and wall partitions of restroom located in Building #2052. Provide and install one (1) new water
     closet (ADA compliant), one (1) new lavatory (ADA compliant), one (1) new mirror (ADA compliant), one (1) liquid soap dispenser, one (1)
     sanitary paper dispenser and one (1) napkin / paper towel dispenser. See Exhibit A-1 (Cost Breakdown), item #9.
6.   Replace existing entrance door of restroom of Building #2052 and replace it with a new one that complies with the width required by ADA
     requirements (32” open clearance). See Exhibit A-1 (Cost Breakdown), item #9.


                                                         Page #3 of 14
IMPROVEMENTS TO PUBLIC SCHOOL “MECANICA DE AVIACION MIGUEL SUCH”
                            (PRAMI)
School Name:              Escuela de Mecánica de Aviación Miguel Such
Location:                 Roosevelt Roads Base, Ceiba, Puerto Rico

                                                 Actual Condition Images
PHOTO NO. 8: Flexible A/C supply conduit without a diffuser at           PHOTO NO. 9: Hung ceiling without return air grill at Classroom
Classroom of Building #2052.                                             of Building #2052.




PHOTO NO. 10: Hung ceiling in Building #2052 without                     PHOTO NO. 11: Hung ceiling in Building #2052 without
acoustical ceiling panels.                                               acoustical ceiling panels.




Comments:
    1.   Provide and install a double receptacle (125 V, 20 Amps) for each one of the work tables located in Building #2052. Contractor shall
         include wiring, electrical conduits and new breakers to connect these receptacles to the existing electrical panel. See Exhibit A-1
         (Cost Breakdown), item #10.
    2.   Refer to list of requirements prepared by the Puerto Rico Fire Department for Building #2052. See Exhibit A-1 (Cost Breakdown),
         item #11.
    3.   Provide and install supply diffusers and return air grilles at hung ceiling of Building #2052. Also repair any loose mechanical
         ductwork. See photos #7A, 8, 9 and Exhibit A-1 (Cost Breakdown), item #12.
    4.   Provide and install acoustical ceiling panels at places in hung ceiling of Building #2052 currently without panels. See Photos #8, 9,
         10, 11 and Exhibit A-1 (Cost Breakdown), item #13.




                                                         Page #4 of 14
IMPROVEMENTS TO PUBLIC SCHOOL “MECANICA DE AVIACION MIGUEL SUCH”
                            (PRAMI)
School Name:               Escuela de Mecánica de Aviación Miguel Such
Location:                  Roosevelt Roads Base, Ceiba, Puerto Rico

                                                   Actual Condition Images
PHOTO NO. 12: Connections to electrical transformers without               PHOTO NO. 13: Connections to electrical transformers without
fuses.                                                                     fuses.




PHOTO NO. 14: Existing electrical cord extension to be replaced            PHOTO NO. 15: Existing electrical receptacle at the ceiling of
at the ceiling of Building #860.                                           Building #860.




Comments:
    1.   Provide and install electrical fuses for aerial substation that provides electricity to Building #860. See photos #12, 13 and Exhibit A-1
         (Cost Breakdown), item #14.
    2.   Provide and install seven (7) new electrical extension cord reels at the ceiling of each of the three bays of Building #860 for a total of
         twenty one (21) extension cord reels. See photos #14, 15 and Exhibit A-1 (Cost Breakdown), item #15.




                                                           Page #5 of 14
IMPROVEMENTS TO PUBLIC SCHOOL “MECANICA DE AVIACION MIGUEL SUCH”
                            (PRAMI)
School Name:             Escuela de Mecánica de Aviación Miguel Such
Location:                Roosevelt Roads Base, Ceiba, Puerto Rico

                                                Actual Condition Images
PHOTO NO. 16: Existing Magnaflux machine located at Building           PHOTO NO. 17: Existing electrical conduit to be used to connect
#860.                                                                  Magnaflux machine.




PHOTO NO. 18: Classroom located in the 1st bay of Building #860        PHOTO NO. 19: Classroom located in the 2nd bay of Building
without return air grill and conduit.                                  #860 without A/C.




Comments:
1.   Provide and install electrical wiring and connection from Magnaflux machine located in Building #860 to existing electric panel. See
     photos #16, 17 and Exhibit A-1 (Cost Breakdown), item #15.
2.   Provide return air grille and conduit for a classroom located at the 1st bay of Building #860. See photo #18 and Exhibit A-1 (Cost
     Breakdown), item #16.
3.   Connect A/C system to a classroom located at the 2nd bay of Building #860. See photo #19 and Exhibit A-1 (Cost Breakdown), item #16.




                                                       Page #6 of 14
IMPROVEMENTS TO PUBLIC SCHOOL “MECANICA DE AVIACION MIGUEL SUCH”
                            (PRAMI)
School Name:              Escuela de Mecánica de Aviación Miguel Such
Location:                 Roosevelt Roads Base, Ceiba, Puerto Rico

                                                  Actual Condition Images
PHOTO NO. 20: Classroom located at the 2nd bay of Building                PHOTO NO. 21: Another classroom located at the 2nd bay of
#860 without return air conduit and grille.                               Building #860 without return air conduit and grille.




PHOTO NO. 22: Open space located on the 3rd bay of Building               PHOTO NO. 23: Existing double door and frame to be installed as
#860.                                                                     part of a new classroom.




Comments:
    1.   Provide and install return air conduits and grilles for three classrooms located at the 2 nd bay of Building #860. See photos #20, 21
         and Exhibit A-1 (Cost Breakdown), item #16 and 25.
    2.   Provide and install gypsum board wall to close existing open space to make it into a classroom at the 3 rd bay of Building #860. This
         work also includes the installation of approximately 602 ft2 of acoustical ceiling tiles and ceiling suspension system, A/C system, new
         light fixtures for hung ceilings and relocation of sprinkler heads according to the elevation of the hung ceiling. Also the contractor
         shall install a double door that will be provided by the school administration. See photo #22, 23 and Exhibit A-1 (Cost Breakdown),
         item #17, 18 and 21.
    3.   Provide potable water storage tank along with pumping system to provide potable water to Building #860. See Exhibit A-1 (Cost
         Breakdown), item #19.




                                                          Page #7 of 14
IMPROVEMENTS TO PUBLIC SCHOOL “MECANICA DE AVIACION MIGUEL SUCH”
                            (PRAMI)
School Name:              Escuela de Mecánica de Aviación Miguel Such
Location:                 Roosevelt Roads Base, Ceiba, Puerto Rico

                                                 Actual Condition Images
PHOTO NO. 24: Existing floor tiles located in a hallway of               PHOTO NO. 25: Existing floor tiles located in a classroom of
Building #860.                                                           Building #860.




PHOTO NO. 26: Ladies restroom located in Building #860.                  PHOTO NO. 27: Men restroom located in Building #860.




Comments:
   1. Remove and dispose existing floor tiles (approximately 905 ft2) located in classrooms and hallways of Building #860. After removal of
         tiles, floors must be cleaned and painted. See photos #24, 25 and Exhibit A-1 (Cost Breakdown), item #20.
    2.   Refer to list of requirements prepared by the Puerto Rico Fire Department for Building #860. See Exhibit A-1 (Cost Breakdown), item
         #22.
    3.   Remove and dispose of corroded material in the premises of Building #860. See Exhibit A-1 (Cost Breakdown), item #23.
    4.   None of the existing restrooms complies with ADA requirements. Contractor shall remove and dispose of all existing bathroom
         fixtures and accessories and provide and install in each restroom: one (1) water closet (ADA compliant), one (1) lavatory (ADA
         compliant), one (1) liquid soap dispenser, one (1) napkin / paper towel dispenser, one (1) sanitary paper dispenser and one (1) mirror
         (ADA compliant). The entrances to each restroom must comply with the required clearance (32” open clearance) by ADA. See
         photos #26, 27 and Exhibit A-1 (Cost Breakdown), item #24.


                                                         Page #8 of 14
IMPROVEMENTS TO PUBLIC SCHOOL “MECANICA DE AVIACION MIGUEL SUCH”
                            (PRAMI)
School Name:              Escuela de Mecánica de Aviación Miguel Such
Location:                 Roosevelt Roads Base, Ceiba, Puerto Rico

                                                  Actual Condition Images
PHOTO NO. 28: Hallway end without a door located at Building              PHOTO NO. 29: Leakage from hallway roof located in the 2nd bay
#860.                                                                     of Building #860.




PHOTO NO. 30: Stained acoustical ceiling panels located in a              PHOTO NO. 31: Existing door at electrical room located in
classroom in Building #860.                                               Building #860.




Comments:
    1.   Provide and install one (1) semi-solid wood door at hallway’s end located at Building #860. See photo #28 and Exhibit A-1 (Cost
         Breakdown), item #21.
    2.   Provide treatment to prevent leaks from concrete roof in Building #860. Proof of leakage can be seen in the ceiling of the hallway in
         front of the classrooms in the 2nd bay of Building #860 and inside these classrooms. See photo #29 and Exhibit A-1 (Cost
         Breakdown), item #26.
    3.   Provide and install new acoustical ceiling panels in Building #860 in places where panels are missing and in cases when existing
         panels have been stained because of roof leakage. See photos #29, 30 and Exhibit A-1 (Cost Breakdown), item #27.
    4.   Replace existing full louver door at an electrical room located in Building #860 with one (1) new full louver metal door. See photo #31
         and Exhibit A-1 (Cost Breakdown), item #28.




                                                          Page #9 of 14
IMPROVEMENTS TO PUBLIC SCHOOL “MECANICA DE AVIACION MIGUEL SUCH”
                            (PRAMI)
School Name:              Escuela de Mecánica de Aviación Miguel Such
Location:                 Roosevelt Roads Base, Ceiba, Puerto Rico

                                                  Actual Condition Images
PHOTO NO. 32: Hole for mechanical exhaust fan at roof of                  PHOTO NO. 33: Location in Building #1980 proposed by the
electrical room located in Building #860.                                 PRAMI administration for a new restroom.




PHOTO NO.:                                                                PHOTO NO.:




Comments:
1.   Repair electrical connection and ventilation system (it may be corroded) located in an electrical room in Building #860. The electrical
     room is the same where the full louver door is to be replaced. See photo #32.
2.   Provide electrical connection to Building #1980. Contractor will provide a new underground trench connection approximately 300’ long
     following the current PREPA standards. See Exhibit A-1 (Cost Breakdown), item #28.
3.   Build a new restroom in Building #1980, following ADA regulations, in the location determined by the PRAMI administration. Restroom
     shall include one (1) water closet, one (1) lavatory, one (1) mirror, one (1) liquid soap dispenser, one (1) napkin / paper towel dispenser
     and one (1) sanitary paper dispenser. See photo #33 and Exhibit A-1 (Cost Breakdown), item #29. Work also includes potable water
     and sanitary water connections.
4.   Provide potable water storage tank along with pumping system to provide potable water to Building #1980. Also Contractor shall provide
     and install a septic tank to be connected to the new restroom. See Exhibit A-1 (Cost Breakdown), item #32, 40, 41 and 42.
5.   Contractor shall build a separate floor drain sewage system for water contaminated with paint particles. This work shall include providing
     and installing a retention tank that complies with all current environmental regulations. See Exhibit A-1 (Cost Breakdown), item #32 and
     40.



                                                         Page #10 of 14
IMPROVEMENTS TO PUBLIC SCHOOL “MECANICA DE AVIACION MIGUEL SUCH”
                            (PRAMI)
School Name:              Escuela de Mecánica de Aviación Miguel Such
Location:                 Roosevelt Roads Base, Ceiba, Puerto Rico

                                                  Actual Condition Images
PHOTO NO. 34: Existing wall fans and work tables located in               PHOTO NO. 35: Existing electrical panel located in Building
Building #1980.                                                           #1980.




PHOTO NO. 36: Existing junction box that connects to the                  PHOTO NO. 37: Existing vapor proof lamps to be installed in
existing electrical panel in Building #1980                               Building #1980.




Comments:
1.   Provide and install electrical connections for two existing wall fans and two additional double receptacles for two work tables located in
     Building #1980. See photo #34 and Exhibit A-1 (Cost Breakdown), item #33.
2.   Provide a new electrical transformer and new electrical panel to energize the existing panel and equipment in Building #1980. See
     photos #35, 36 and Exhibit A-1 (Cost Breakdown), item #34.
3.   Install nine (9) existing vapor proof light fixtures hanging from the ceiling of Building #1980. Coordinate exact location with School
     administration. See photo #37 and Exhibit A-1 (Cost Breakdown), item #35. Contractor shall provide all electrical connections work and
     materials.




                                                         Page #11 of 14
IMPROVEMENTS TO PUBLIC SCHOOL “MECANICA DE AVIACION MIGUEL SUCH”
                            (PRAMI)
School Name:               Escuela de Mecánica de Aviación Miguel Such
Location:                  Roosevelt Roads Base, Ceiba, Puerto Rico

                                                   Actual Condition Images
PHOTO NO. 38: Ceiling of Building #1980.                                   PHOTO NO. 39: Floor tiles in office of Building #1980.




PHOTO NO. 40: Exhaust conduit without adequate structural
                                                                           PHOTO NO. 41: Exterior wall of Building #1980.
support located in Building #1980.




Comments:
 1. Replace existing ceiling light fixtures in Building #1980 and replace them with 24 new 2’x4’ light fixtures with plastic covers. The new light
      fixtures are to be distributed along the ceiling in coordination with the school administration. See photo #38 and Exhibit A-1 (Cost
      Breakdown), item #36.
 2.   Remove and dispose of approximately 473 ft2 of vinyl floor tiles located in a room in Building #1980. Afterwards this floor shall be
      cleaned and painted completely. See photo #39 and Exhibit A-1 (Cost Breakdown), item #37.
 3.   Provide and install new structural support for the exhaust conduit at the exterior of Building #1980. See photo #40 and Exhibit A-1 (Cost
      Breakdown), item #38.
 4.   Remove and dispose of corroded materials on and around the premises of Building #1980. Coordinate work with school administration.
      See Exhibit A-1 (Cost Breakdown), item #39.
 5.   Refer to list of requirements prepared by the Puerto Rico Fire Department for Building #1980. See Exhibit A-1 (Cost Breakdown), item
      #40.
 6.   Remove completely existing exterior paint of Building #1980 (approximately 3,500 ft2) and provide three new coats of paint. Coordinate
      with school administration for paint color. See photo #41 and Scope of Work List, item #43.

                                                          Page #12 of 14
IMPROVEMENTS TO PUBLIC SCHOOL “MECANICA DE AVIACION MIGUEL SUCH”
                            (PRAMI)
School Name:              Escuela de Mecánica de Aviación Miguel Such
Location:                 Roosevelt Roads Base, Ceiba, Puerto Rico

                                                 Actual Condition Images
PHOTO NO. 42: Interior Of Building #1980.                                PHOTO NO. 43: Interior walls of Building #1980.




PHOTO NO. 44: Exterior door in a deteriorated condition in
                                                                         PHOTO NO. 45: Water tank located in Building #376.
Building #1980.




Comments:
 1. Paint interior walls, roof structural beams and columns and doors of Building #1980. See photos 42, 43 and Exhibit A-1 (Cost
     Breakdown), item #43.
2.   Evaluate the volume of air (cfm) needed to be extracted from Building #1980 based on the amount of particulates and/or volatile
     compounds. See Exhibit A-1 (Cost Breakdown), item #44.
3.   Replace an existing exterior door in Building #1980 with a single new hollow metal door. Door shall include new hardware set and shall
     be painted with two coats of new paint. See photo #44 and Exhibit A-1 (Cost Breakdown), item #45.
4.   Supply and fill existing and new water storage tanks in all buildings. See photo #45 and Exhibit A-1 (Cost Breakdown), item #46 and 47.
5.   Clean up and remove any debris in the school grounds. See Exhibit A-1 (Cost Breakdown), item #48.




                                                        Page #13 of 14
IMPROVEMENTS TO PUBLIC SCHOOL “MECANICA DE AVIACION MIGUEL SUCH”
                            (PRAMI)
School Name:              Escuela de Mecánica de Aviación Miguel Such
Location:                 Roosevelt Roads Base, Ceiba, Puerto Rico

                                                 Actual Condition Images
PHOTO NO. 46: Work tables area located in Building #2052.                 PHOTO NO. 47: Work tables area located in Building #2052




PHOTO NO.:                                                                PHOTO NO.:




Comments:
 1. Provide and install electrical connection and wiring devices (double receptacles) to each work table in Building #2052. These receptacles
     shall be connected to an existing electrical panel in the building. Contractor shall follow NEC standards. See photos #46, 47 and Exhibit
     A-1 (Cost Breakdown), item #10.




                                                         Page #14 of 14